KNOXVILLE UTILITIES BOARD Addendum No. 1 Project: AL Line 69KV Transmission Line Upgrade & OPGW
Installation Control No: 294 Issued: To all listed Plan holders Date: September 30, 2015 This addendum forms a part of the Contract described above. The original Contract Documents and any prior addenda remain in full force and effect except as modified by the following which shall take precedence over any contrary provisions in prior documents. See attached sheet for specifics of this addendum. Each Bidder shall acknowledge receipt of this addendum by affixing his signature below, by noting this addendum on his Bid Form, and by attaching this addendum to his Bid. Failure to acknowledge this addendum could be cause for bid rejection.
ACKNOWLEDGMENT The undersigned acknowledges receipt of this addendum and the Bid submitted is in accordance with information, instructions and stipulations set forth here in.
BIDDER ____________________________________
AUTHORIZED SIGNATURE__________________________
DATE _____________________________________
PAGE 2
ADDENDUM 1 – AL Line 69KV Transmission Line Upgrade & OPGW Installation Control No: 294 Clarifications to Questions Question 1: Clearing times for the 69kv line Answer 1: The crews will not have to put the 69kv line back into service every night. KUB only requires that in case of storm or some other event the line is able to put back into service within 12 hours Question 2: Length of OPGW on reels Answer 2: The OPGW comes in 5,000' reels Question 3: How to attach fiber to poles to get to splice box storage assemblies Answer 3: Please see attached PDF for description of fiber assemblies in particular DWG-16904-OPGW5. The crews will use downlead clamps attached to the bolt step clips on the pole. Also refer to the 3rd to last page with a more detailed description of the downlead cushion for OPGW or ADSS. Question 4: Fiber entrance to Murray Rd substation Answer 4: We originally discussed using the 2nd 2" conduit on the existing wood pole at this location. It has been discovered this conduit has been cut and cannot be used. KUB will disconnect the supervisory cable inside Murray Rd substation and the contract crews will pull the supervisory cable out of the station. Then the contract crews will pull BOTH the supervisory cable and the ADSS fiber in the SAME 2" conduit going into the station. The 2" conduit is big enough for both cables but they have to be pulled in at the same time. Question 5: Typically if there are any major road crossing on a project, all permits and Traffic Control Plans are provided by the Owner (KUB). Just to clarify, on the AL Line, whose responsibility is it to provide the crossing permit and Traffic Control Plan for the Clinton Highway area? Answer 5: KUB will provide the crossing permit and Traffic Control Plan Clarifications to Specifications 1. The following line items have been added to Section 00330sup Unit Price Schedule. Use the attached Section 00330sup Unit Price Schedule when submitting the bid.
www.AFLglobal.com or 800-235-3423
Fiber Optic Cable Hardware
5
© 2008-2012, AFL, all rights reserved. Revision 3, 7.23.12Specifications are subject to change without notice.
AlumaCore ODEC
Slotted Core ODEC
CentraCore ODEC
OPGW Dead End Range code in Decimal Inches (See Table 1)
"G" for Cable Guide,"N" for No Cable
Guide
Number of Keepers (See Table 1, Keeper
Designation)
ODE C YYY/YYY X ##
Used for Alumacore, Centracore, and Slotted
Core
NOTES: 1. For installation instructions, see pg 128. 2. This deadend is approved only for AFL cables. 3. Cables above 30,000 lbs RBS have to be tested.
TABLE 1
OPGW RBS NO. OF * KEEPERS
KEEPER DESIGNATION
DIMENSION "A"
14000 OR LESS 7 07 25.98
14001 - 17000 8 08 28.38
17001 - 21000 9 09 30.78
21000 - 26000 10 10 33.18
26001 - 30000 11 11 35.58
IF > 30001* 12 12 37.98
* SEE NOTE 3
KEEPER
LINK PLATE(ORDERED SEPARATELY)
5/8" BREAK-AWAY BOLT (M14-METRIC)
(76.2 MM)3"
Bolted Dead End for OPGW(Core Tube Type Cable)
AFL NO.CABLE DIAMETER RANGEMIN MAX
ODEC350/359GXX 0.350 0.359ODEC360/369GXX 0.360 0.369ODEC370/379GXX 0.370 0.379ODEC380/389GXX 0.380 0.389ODEC390/399GXX 0.390 0.399ODEC400/409GXX 0.400 0.409ODEC410/419GXX 0.410 0.419ODEC420/429GXX 0.420 0.429ODEC430/439GXX 0.430 0.439ODEC440/449GXX 0.440 0.449ODEC450/459GXX 0.450 0.459ODEC460/469GXX 0.460 0.469ODEC470/479GXX 0.470 0.479ODEC480/489GXX 0.480 0.489
AFL NO.CABLE DIAMETER RANGEMIN MAX
ODEC490/499GXX 0.490 0.499ODEC500/509GXX 0.500 0.509ODEC510/519GXX 0.510 0.519ODEC520/529GXX 0.520 0.529ODEC530/539GXX 0.530 0.539ODEC540/549GXX 0.540 0.549ODEC550/559GXX 0.550 0.559ODEC560/569GXX 0.560 0.569ODEC570/579GXX 0.570 0.579ODEC580/589GXX 0.580 0.589ODEC590/599GXX 0.590 0.599ODEC600/609GXX 0.600 0.609ODEC610/619GXX 0.610 0.619ODEC620/629GXX 0.620 0.629
AFL NO.CABLE DIAMETER RANGEMIN MAX
ODEC630/639GXX 0.630 0.639ODEC640/649GXX 0.640 0.649ODEC650/659GXX 0.650 0.659ODEC660/669GXX 0.660 0.669ODEC670/679GXX 0.670 0.679ODEC680/689GXX 0.680 0.689ODEC690/699GXX 0.690 0.699ODEC700/709GXX 0.700 0.709ODEC710/719GXX 0.710 0.719ODEC720/729GXX 0.720 0.729ODEC730/739GXX 0.730 0.739ODEC740/749GXX 0.740 0.749
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
( -:: PREVIOUS) ( SECTION CONTENTS) ( SEARCH ) ( NEXT::-)
~ PREFORMED LINE PRODUCTS
5-4
FIBERLIGN® Dead-end for OPGW
FIBERLIGN Dead-end for OPTICAL GROUND WIRE (OPGW) Patented
Ordering Instructions: Select the appropriate FIBERLIGN Dead-end from the catalog table in this section.Consult PLp® for designs for OPGW diameters, strengths, or lay directions not shown. Also call PLP for availability of all sizes and designs.
Accessories: Accessories may be included in the same container with the Dead-end by adding the appropriate suffix code. Ex. 2801312G, includes Dead-end with ground wire assembly, #710010016.
CAUTION: Determine the appropriate material and size wire necessary to provide adequate grounding for your system before ordering the ground wire assemblies. For proper performance and personal safety be sure to select the proper ground wire before application.
Catalog Number
710010016
710010294
710011205
Suffix Code Description
G 4' long (1.2 m) #4 (7W) copper ground wire with terminal on one end.
GA 4' (1.2 m) long 4/0 (7W) aluminum ground wire with terminal on one end.
GA2 5' (1.5 m) long 95 mm2 (19W) aluminum ground wire with terminals at both ends.
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
~
1. CURRENT TRANSFER TAB ACCEPTS 1/2" BOLT TO ATTACH GROUND
I
\
~la-2 ,
SEE NOTE 2
'-
o \
\
/ /
/
-VIEW "A"
PREFORnED LINE PRODUCTS
I
STRUCTURAL REINFORCING ROD LENGTH 120·
~ _O~TER ROD LENGTH 63"l I
l-~ SEE VIEW "A"
5~ 8
1 If
Id
Ie
Ib
la-4
la-3
la-2
la-I
la
1
tem
1 SET
1 SET
1
Re 'd
64966 CURRENT TRANSFER TAB
4320114 OUTER SUPPORT ROOS
4310112 STRUCTURAL REINFORCING ROOS
BOL T, LOCKWASHER, NUT
STRAP
INSERT
CAST HOUSING (2 HAL VES)
410012B HARDWARE COMPONENT PACKAGE
4300117 FlBERUGNfIJ SUSPENSION FOR OP
Ref. No. Deseri tion
ALUMINUM ALLOY
ALUMINUM ALLOY
ALUMINUM ALLOY
GALli. STEEL
ALUMINUM ALLOY ELASTOMER WITH ALUMINUM R£lNF()fIC£M T
ALUMINUM ALLOY
Moterial
FIBERLlGN4!I Suspension For OPGW The data and Information contained In this document are CATALOG No. 4300117
CONFIDENTIAL 1171£
proprietary to PREFORMED Line Products (PLP), Such data OPGW RANGE .633"-.666" and Information are provided soley for use with PLP's t-::==-r-;;;::-:;::::'"r-;;-:,;;:::"r'--=.::-::-..,-'-'-'-:=-:7.::=--! 660 BETA DRIVE MAYFIElD, OHIO 44143
PH: (440)-461-5200 FAX: (440)-442-6616 DWN BY.- RLE NAME
products and shall not be disclosed, duplicated. or otherwise I-"=-=-+.=::....::'"--I-.E.:==;,.--If-=""--f-----' ..... .= ..... ---I J. Jono. 4300117 http://www.proformod.com used without the express written approval of PLP. AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
NOTES: 1. CATALOG SERIES No. 2872XXX 2. SUFFIX CODE "C1 E1" INCLUDES THIMBLE CLEVIS (TC-5F)
AND EXTENSION LINK WITH EYE NUT (#71002366)
! 5/8" EYE NUT
AU-=) SELF SUPPORTING CABLE
MAXIMUM SPAN LENGTH = 600 ft. MAXIMUM INITIAL TENSION = 1,000 Ibs. MAXIMUM LOADED TENSION = 2,500 Ibs.
PREFORnED LINE PRODUCTS
660 BErA DRIVE MAYFIELD, OHIO +41 +3 PH: (4040)-461-5200 FAX: (4040)-473-9103
htt :/ /www.refonned.com
38" (O.97M)
48" (1.22M)
CATALOG NUMBER 2872010C1E1 SUFFIX "F1-(71002386) SUFFIX "'1:1-
(TC-5F)
2862070
7 SET 2882070
Item Req' Ref. No.
CONFIDENTIAL The data and information contained in this document are
proprietary to PREFORMED Line Products (PLP). Such dato
14 EXTENSION LINK - 15.000 Ibo G4LVAoIVZfl) DIJCTIL£ IRON AND W EYC-N/ff - 12.500 Ibo AND G4LVAoIVZfl) 57m.
THIlr/8/.E CLEVIS - 26,900 lb. G4LVAoIVZfl) DIJCTIL£ IRON AND G4LVAoIVZfl) 57m.
DEAD-ENO COMPONENT ELECTRO GALVANIZED STEEl.
STRUCTURAL REINFORCING RODS ELECTRO GALVANIZED STEEl.
Description Moteriol
Tm.£ FIBERLlGN® Limited Tension Dead-End for ADSS with Thimble Clevis, Extension Link, and Eye-Nut Cable Diametar Range .693"~737" (17.5mm-18.7mm)
and information are provided solely for use with PLP's !-=:""..,,,,....r-:-::::-=--r---,,,=--r-=,..,,....,.-==,,,....--! l-~o~~mo~.~~NW~mo~·t-_~~~~:_t-~~-t~m£~~~~_1 products and shall not be disclosed. duplicated. or otherwise
used without the express wn"tten approval of PLP. DAW 287201OC1E1
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
LONG COYOTE® Splice Tray Kit for LITE-GRIP Blocks/Sleeves - Single Fusion ONLY. 72 Count
6 25
~-------- 1 I. 77 --------~
I~------------ 12.69 ---------~
PREFORnED LINE PRODUCTS www.preformed.com
CO NF I DE NT I AL
Tn e do 10 an din formal io n con 10 i ne din I his doc ume n I are pr op r i e I a r y 10
PREFORMED Line Products (PLPI, Such dolo and information are
pro vi ded sol ely for use wit h PLP' s pr od u ct sand s ha II not be dis c lose d,
dupllcaled, or other wise used wllhoul the express written approval of PLP
T I HE
DWN BY
JLH
I CATALOG No. LGSTS72 I
LONG COYOTE® Splice Tray Kit for LITE-GRIP Blocks/Sleeves
Single Fusion ONLY. 72 Count FILE NAME SHEET No
LGSTS72 1 OF 1
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
G.5" X 22" COYOTE® Dome Closure for OPGW with I Splice Tray (3G count) - Flexible Buffer Tube Storage
COYOTE® DOME CLOSURE WITH BUFFER TUBE STORAGE BRACKETS
[P[Kl[g[F®[K:m1Jrn@) LINE PRODUCTS 660 BETA DRIVE MAYFIELD, OHIO 44143
PH: (440)-461-5200 R&E FAX: (440)-473-9103 www.preformed.com
CONFIDENTIAL
The data and information contained in this document are proprietary to PREFORMED Line Products (PLP), Such data
and information are provided solely for use with PLP's products and shall not be disclosed, duplicated, or otherwise
used without the express written approval of PLP.
Tray wi Elastomer Splice Blocks #80805514 -1 Included
m®~ ~~~
Endplate Grommet Kits - .30'-.85" Includes 2 ea. 8003664 and # 8003701
Heat ShOnk Splice Protector Kit (60mm -12 per KI) catalog #8003509· 31nduded
6.5" X 22" COYOTE® Dome Closure for OPGW with 1 Splice Tray (36 count) - Flexible Buffer Tube Storage.
121
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
UNRS tl INCHES UNI£SS NOIED PREFORnED
LINE PRODUCTS 660 BETA IlII\'E MAYFIElD, OHIO 44143
PH: (440)-461-5200 R&E FAX: (440)-473-9103 www.preformed.com
BANDED VERSION (BANDING STRAPS NOT INCLUDED)
CONFIDENTIAL
The data and information contained in this document are proprietary to PREFORMED Un. Products (PLP), Such data
and information are provided solely for use with PLP's products and shall not be disclosed, duplicated, or otherwise
used without the express written approval of PLP.
BOLTED VERSION (LAG BOLTS INCLUDED)
COYOTE® Dome Vertical Mounting Bracket
OWN BY: RL£ NAME:
Sept. 17, 2007 BOOJ702
SH££T No.
1 OF 1 AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
NOTES: 1. Item included but not required for Double Arm Application -
Used for COYOTE® DEFENDER Applications only. 2. The Cross-Arm can be bolted (shown) or banded to the
structure. Banding or through bolts for mounting are not included with the kit.
Through Bolt - See Note 2
CATALOG NUMBER 8003569
PREFORnED LINE PRODUCTS
660 BETA DRIVE MAYFIELD, OHIO +11 +J PH: (440)-481-5200 FAX: (440)-+12-8816
htt :/ /www.reformed.com
See Note 1 7 4
6 4
5 4
4 2
:5 4
2 4
4
Item Req'
CONFIDENTIAL
The data and inrorrnation contained in this document are
proprietary to PREFORMED Line Products (PLP). Such data
HEX HEAD SELF TAP SCREW 1'."-20 ZINC COATED STEEL
HEX NUT *"-11 ZINC COA TED STEEL
LOCK WASHER *" ZINC COATED STEEL
CROSS ARM GALVANIZED STEEL
SPOOL URETHANE
ROUND WASHER *"-11 X 1-'1f." DO ZINC COA TED STEEL
HEX HEAD BOLT *"-11 X 6" LONG ZINC COATED STEEL
TITLE
Description Material
FIBERLIGN® Vertical Cable Storage System Double Arm Application
and infbrrnation are provided soley for use with PLP's !--"=,,.,...-r-==.,.-=,....--,-=--r--____ ----1 products and shall not be disclosed, duplicated, or otherwise I--"0WN=""'''''-I",APR=-",",,,-, -+---,""=TEo.' _+-"'''''''=LE''--+--<.''!!OlE'''NAME''''''-----1
used without the express written approval of' PLP. DAW 8003569
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
FIBERLIGN® DOWNLEAD CUSHION KIT
SUFFIX CODES FOR MOUNTING OPTIONS: "H 1" - LAG SCREW WITH WASHERS FOR WOOD POLE "LTC 1 - AL CLAMP WITH 6" BOLT FOR LATTICE TOWER & STANDOFF "LTC2 - AL CLAMP WITH 5" BOLT FOR LATTICE TOWER "B 1" - BANDING BRACKET WITH BOLT FOR CONCRETE OR STEEL POLES
MOUNTING HARDWARE NOT INCLUDED
CONFIDENTIAL The data and Information contained in this document are
proprietary to PREFORMED Line Products (PLP). Such data
MOUNTING HOLE WILL FIT 5/8" DIA. HARDWARE
ALUMINUM DOWNLEAD HALF
CATALOG No.: 8003269
TITLE FIBERLIGN Downlead Cushion for OPGW or ADSS, Range .610"-.656"
PREFORnED LINE PRODUCTS
660 BETA DRIVE MAYFIELD. OHIO 44143 and Information are provided soley for use with PLP's 1-::::::::-:::::-1r.-:;:::-:::::-T""""::=-'--::==--'1r---:::-:=-::=--! LD~~~B~~~NW~~B~~·+,m~~~T:~~~~~I-'-~ffl£~N~.~~-; products and shall not be disclosed. duplicated. or otherwlse.---PH: (440)-461-5200 FAX: (440)-442-8816
http://www.preformed.com used without the express written approval of PLP. J. Jones 2005 NONE 8003269 AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
B I. -11/32'
o 159164' E 3-7/64'
,.PIN
2 -11/32'
- 4'/64'
112"-13 UNe P 3 -15118'
I7ln
SECTlON A-A
la- "
-c-- D -
Ii - --f.+--~ J k;;;;~ L 'r. ~,In ~~~ -E--p-
1------------- STRUCTURAL REINFORCING RODS LENGTH = 41" (104cm)
CATALOG NUMBER 4700109
~~~~r;-e ~ -0 ot:d=1 Reverse View Shows Hex Nuts with Washers and Ground Attachment Hole.
1b
10-3
10-2
10-1
10
1
Item
1 SET
1 EA_
2
4 EA.
11 PAIR
1
Req'
4702109 STRUCTURAl REINFORCING RODS ALUMINUM ALLOY
Ji"-'3 x *" LONG BOLT & LOCK WASHER GALVANIZED STEEL
U BOLT CAPTURED WITH GROMMETS ""-VANIZED SIIEL "-BOLT ElASroOIER
FLAT WASHER, LOCK WASHER, NUT GALVANIZED STEEL
KEEPER HALF WITH CUSHION INSERTS ALUMINUM AU.OY KEEPER E1..ASTOMER INSERTS
4700109 ~ Ref. Na. n
PREFORnED CDNFIDENTIAL TITLE The daTQ and InFor",QT/on contained In 'this doCUMent are FIBERLlGN® Cushion Clamp for OPGW (LHL)
LINE PRODUCTS proprieTary 'to PR£FORH£D Line Products (PLP)~ Such daTa Cable DiameterRange.616"-.641" (15.7mm-16.3mm)
660 BETA DRIVE MAYFIELD. CHID _~~!43 and InForMQt/on are provided solely For use with PLP's BVG BY, I APR BY, I .D.41£1 I SCALE I FILE NANE
PHI (440!:~1~5200 FAXI (440)-473-9103 produ~::d and shall t:'t be dlsclosed~ dupl/cQted~ :;. c;:.~~rw/se DAW 1 JLJ 107. ?a nal NONE 1
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
5 CAPABILITIES:
- MAXIMUM LINE ANGLE = 20"
- MAXIMUM VERTICAL LOAD = 1000 lb •.
- MAXIMUM SPAN LENGTH: CABLE 00<1.00" = 600' (NESC HEAvy) CABLE 00>1.00" = 300' (NESC HEAVY)
PREFORnED LINE PRODUCTS
660 BErA DRIVE MAYFIELD. OHIO +4143 PH: (4040)-461-5200 FAX: (4040)-473-9103
htt :/ /www.reformed.com
Pole Bolt (Supplied
by others)
ADSS Cable
1----5"·---~
Banding Slot Accepts Up To 1-114" Banding (Not Included)
CATALOG NUMBER 4450104 7 2
6
5
4
J
2
Item Req .
CONFIDENTIAL The data and Information contained In this document are
proprietary to PREFORMED Line Products (PLP). Such dato
CUSHION INSEKT HALF 00070129 (2 REQtJIRED PER HOUSING) URETHANE
SUPPOFrT BASE ALUMINUM AJ.lOY
SUPPOFrT KEEPER ALUMINUM AJ.lOY
GROI./MET ElASTOI.IER
%' ROUNO FIAT WASHER GALVANIZED STff/.
%' LOCK WASHER GALVANIZED STff/.
%' HEX HEAD BOLT GALVANIZED STff/.
Description Material TTTI.£
FIBERLlGN® Aluminum Support for ADSS Cable ~iameter Range .676"-.750" (17.2mm-19.1mm)
and Information are provided solely for use with PLP's ""'===""T"-:==-="....,r-""",,=-""T"-:'=:-T'"-:=="""'--! I-~OHW~~8r.~.-II-~NW~~8r.~.-II-~~~m~·_-II-~~~t-~m£~~~~~--I products and shall not be disclosed. duplicated. or otherwise
used without the express written approval of PLP. DAW 4450104
AL Line 69KV Transmission Line Upgrade & OPGW Installation - Addendum 1
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-1
I1.1 A-8SH 1 EA $ $ I1.2 A-10DH 32 EA $ $ I1.3 A-8" expanding anchors 1 EA $ $ I1.4 DG-7/16 54 EA $ $ I1.5 HG-7/16 5 EA $ $ I1.6 H2-B795 3 EA $ $ I1.7 P1-BP-B795 22 EA $ $ I1.8 P2-BP-B795 1 EA $ $ I1.9 H5-B795 1 EA $ $
I1.10 S5-B795 2 EA $ $ I1.11 3CO-65A 1 EA $ $ I1.12 T2-795 2 EA $ $ I1.13 T1-795 2 EA $ $ I1.14 T1DE-795 1 EA $ $ I1.15 S-2CU 5 EA $ $ I1.16 T1DDE-1/0 2 EA $ $ I1.17 S-4ar 1 EA $ $ I1.18 SL-1/0 1 EA $ $ I1.19 DE-1/0 2 EA $ $
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
INSTALLATION UNITS
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-2
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
I1.20 T2DDE-795 2 EA $ $ I1.21 1TR-50K 1 EA $ $ I1.22 1TR-15K 2 EA $ $ I1.23 EXPANSION ANCHORS 5 EA $ $ I1.24 3/8 OVERHEAD GUY WIRE 1000 LF $ $ I1.25 TANDGENT ADSS ASSLY 1 EA $ $ I1.26 DDE ADSS ASSLY (ADSS5) 2 EA $ $ I1.27 DE ADSS ASSLY (ADSS6) 4 EA $ $ I1.28 ADSS FIBER 1100 LF $ $ I1.29 OPGW FIBER 14000 LF $ $ I1.30 FIBER SPLICE BOX AND STORAGE ASSLY 3 EA $ $ I1.31 TANGENT OPGW ASSLY (OPGW1) 5 EA $ $ I1.32 LONG SPAN TANGENT OPGW ASSLY (OPGW2) 26 EA $ $ I1.33 DDE OPGW ASSLY (OPGW5) 1 EA $ $ I1.34 DE OPGW ASSLY (OPGW6) 7 EA $ $ I1.35 69KV SWITCH WITH GROUNDING PLATE (SW/69KV) 1 EA $ $ I1.36 UNDERSLUNG 13KV SWITCHES (SW/DISC) 1 EA $ $ I1.37 TXDE 3 EA $ $ I1.38 1S-4 6 EA $ $ I1.39 LT-100HP 1 EA $ $
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-3
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
I1.40 LT-250HP 6 EA $ $ I1.41 GROUND RODS 27 EA $ $ I1.42 55 CLASS 1 STEEL POLE 2 EA $ $ I1.43 35' DUCTILE IRON CLASS 2 1 EA $ $ I1.44 85' H4 STEEL POLE 2 EA $ $ I1.45 85' H5 STEEL POLE 1 EA $ $ I1.46 90' H2 STEEL POLE 1 EA $ $ I1.47 90' H3 STEEL POLE 2 EA $ $ I1.48 90' H4 STEEL POLE 2 EA $ $ I1.49 90' H5 STEEL POLE 1 EA $ $ I1.50 90'H H6 STEEL POLE 1 EA $ $ I1.51 95' H2 STEEL POLE 2 EA $ $ I1.52 95' H3 STEEL POLE 1 EA $ $ I1.53 95' H4 STEEL POLE 2 EA $ $ I1.54 95' H5 STEEL POLE 1 EA $ $ I1.55 100' H6 STEEL POLE 1 EA $ $ I1.56 115' H6 STEEL POLE 1 EA $ $ I1.57 100' H3 STEEL POLE 1 EA $ $ I1.58 45' WOOD POLE CLASS 4 3 EA $ $ I1.59 30' WOOD POLE CLASS 5 1 EA $ $
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-4
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
I1.60 60' H5 STEEL POLE 1 EA $ $ I1.61 70' CLASS 1 STEEL POLE 2 EA $ $ I1.62 70' H2 STEEL POLE 2 EA $ $ I1.63 80' H1 STEEL POLE 2 EA $ $ I1.64 85' H2 STEEL POLE 1 EA $ $ I1.65 85' H3 STEEL POLE 4 EA $ $ I1.66 2" SCH 80 PVC CONDUIT 20 EA $ $ I1.67 40' WOOD POLE CLASS 4 1 EA $ $ I1.68 T1-795 1 EA $ $ I1.69 T2-795 1 EA $ $ I1.70 50' WOOD POLE CLASS 3 1 EA $ $ I1.71 T1-1/0 1 EA $ $ I1.72 T2-1/0 1 EA $ $ I1.73 TOP POLE 12 EA $ $ I1.74 MASTER GROUND 5 EA $ $ I1.75 161 KV DE POLYMER 20 EA $ $ I1.76 ROCK ANCHORS 5 EA $ $
SUBTOTAL OF INSTALLATION UNITS $
REMOVAL UNITS
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-5
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
R1.1 45' WOOD POLE CLASS 3 3 EA $ $ R1.2 80' WOOD POLES CLASS 1 11 EA $ $ R1.3 30' WOOD POLES CLASS 5 3 EA $ $ R1.4 75' WOOD POLES CLASS 2 13 EA $ $ R1.5 35' WOOD POLES CLASS 5 3 EA $ $ R1.6 60' WOOD POLES CLASS 3 3 EA $ $ R1.7 70' WOOD POLES CLASS 2 2 EA $ $ R1.8 55' WOOD POLES CLASS 3 2 EA $ $ R1.9 80' CONC POLES CLASS H 2 EA $ $
R1.10 65' WOOD POLES CLASS 3 1 EA $ $ R1.11 85' WOOD POLES CLASS 1 1 EA $ $ R1.12 85' CONC POLES CLASS H 1 EA $ $ R1.13 90' WOOD POLES CLASS 1 1 EA $ $ R1.14 40' WOOD POLES CLASS 4 2 EA $ $ R1.15 8" SH ANCH (A-8SH) 4 EA $ $ R1.16 10'' DG ANCHORS (A-10DH) 19 EA $ $ R1.17 8" EXPANSION ANCHORS 1 EA $ $ R1.18 DG-7/16 34 EA $ $ R1.19 DG-3/8 5 EA $ $ R1.20 HG-7/16 1 EA $ $
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-6
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
R1.21 HG-3/8 3 EA $ $ R1.22 H2-B795 12 EA $ $ R1.23 P1-B795 2 EA $ $ R1.24 H4-B795 1 EA $ $ R1.25 S5-B795 2 EA $ $ R1.26 S2-B795 5 EA $ $ R1.27 S1-B795 1 EA $ $ R1.28 T2DE-1/0 1 EA $ $ R1.29 T1-795 5 EA $ $ R1.30 T2DDE-795 1 EA $ $ R1.31 C1-795 1 EA $ $ R1.32 C1-1/0 1 EA $ $ R1.33 S-2CU 5 EA $ $ R1.34 T1DDE-1/0 2 EA $ $ R1.35 S-4AR 1 EA $ $ R1.36 WOOD CROSS ARM 8' 4 EA $ $ R1.37 WOOD CROSS ARM 10' 1 EA $ $ R1.38 DE-1/0 1 EA $ $ R1.39 S-1/0 1 EA $ $ R1.40 T2-795 1 EA $ $
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-7
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
R1.41 3CO-65A 1 EA $ $ R1.42 1TR-25K 1 EA $ $ R1.43 1TR-15K 2 EA $ $ R1.44 SW/DISC-900A 1 EA $ $ R1.45 SW/INLN 1 EA $ $ R1.46 W-3/8HS 9100 LF $ $ R1.47 1S-4CU 4 EA $ $ R1.48 SL-1/0 1 EA $ $
SUBTOTAL OF REMOVAL UNITS $
T1.1 SV-1 12 EA $ $ T1.2 SV-5 1 EA $ $ T1.3 SV-3 2 EA $ $ T1.4 TXDE-1/0 6 EA $ $ T1.5 LT-100HP 1 EA $ $ T1.6 LT-250HP 6 EA $ $ T1.7 TANGENT 3/8 OVERHEAD GUY WIRE ASSLY 5 EA $ $ T1.8 DE 3/8 OVERHEAD GUY WIRE ASSLY 5 EA $ $
SUBTOTAL OF TRANSFER UNITS $
TRANSFER UNITS
AL Line 69KV Transmission Line Upgrade and OPGW Installation
Control Number: 294
Revised 06/10/14 Unit Price Schedule Supplement - Addendum 1 00330Sup-8
UNIT PRICE BID
Item No. Description Est.
Quan. Unit Bid Unit Price
Extended Bid Unit Price
$
(Total, numbers)
Dollars Total, words (transfer to bid form, page 3)
END OF SECTION