Sprinkler Inspection Certificate For Benjamin Banneker Elementary School 27180 Point Lookout Road Loveille, Maryland 20656 Tested to NFPA 25 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Annual Inspection Inspection Date Aug 13, 2020 Building: Benjamin Banneker Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath Title: Admin Title: Inspector

Upload: khangminh22

Post on 07-May-2023

4 views

Category:

Documents


0 download

TRANSCRIPT

Sprinkler Inspection Certificate For

Benjamin Banneker Elementary School

27180 Point Lookout Road Loveille, Maryland 20656

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 13, 2020

Building: Benjamin Banneker Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Benjamin Banneker Elementary School Contact: Cathy Orolan

Address: 27180 Point Lookout Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Loveille, Maryland 20656 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 11 Fire Pump Building- 1 Fire Pump Discharge 2 Wet Pipe 12 Wet Pipe Building- 1

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 6 21.43% 6 100.00% 1 16.67% 5 83.33% Alarm 4 14.29% 4 100.00% 4 100.00% 0 0% Valve 11 39.29% 11 100.00% 9 81.82% 2 18.18% Pump 6 21.43% 6 100.00% 6 100.00% 0 0% Sprinkler 1 3.57% 1 100.00% 0 0% 1 100.00%

Totals 28 100% 28 100.00

% 20 71.43% 8 28.57%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Benjamin Banneker Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 18, 2020 6:47:07 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Fire Pump Gauge

49307051 1st mechanical room by cafe Date Expired NFPA25 13.2.7.2 49307053 1st Pump house Date Expired NFPA25 13.2.7.2 49307054 1st Pump house Date Expired NFPA25 13.2.7.2 49307055 1st Pump house Date Expired NFPA25 13.2.7.2

Fire Pump, Discharge Check Valve

47298332 1st Pump house Needs 5 Yr. Service NFPA25 13.4.2.1

Wet Pipe Check Valve

47298338 1st Floor Area Cafeteria Zone 2 Needs 5 Yr. Service NFPA25 13.4.2.1

Water Storage Tank 1 Needs 5 Yr. Service

Wet Pipe, Building- Piping

49307052 Whole building Needs 5 Yr. Service NFPA25 14.2.1.1

Code References NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Fire Pump

Gauge

49307051 1st mechanical room by cafe Replace 12DOC T/M 49307053 1st Pump house Replace 12DOC T/M 49307054 1st Pump house Replace 12DOC T/M 49307055 1st Pump house Replace 12DOC T/M

Fire Pump, Discharge

Check Valve

47298332 1st Pump house 5 Yr. Internal 08543 T/M

Wet Pipe

Check Valve

47298338 1st Floor Area Cafeteria Zone 2 5 Yr. Internal 202 T/M

Water Storage Tank

1

5 Yr. Internal 105 T/M

Wet Pipe, Building-

Piping

49307052 Whole building 5 Yr. Internal VSR T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump, Building-

Control Valve 1st Pump house Tested 9:13:19 AM 08/13/2020

Fire Pump, Discharge Fire Pump Off 1st Pump house Tested 9:12:36 AM 08/13/2020

Fire Pump Fire Pump Power 1st Floor Pump House Tested 9:12:22 AM 08/13/2020 Fire Pump Running 1st Floor Pump House Tested 9:12:38 AM 08/13/2020 Controller 1st Floor Pump House Tested 9:12:11 AM 08/13/2020 Jockey Controller 1st Pump house Tested 9:32:18 AM 08/13/2020 Jockey Pump 1st Pump house Inspected 9:32:13 AM 08/13/2020 Pump 1st Pump house Tested 9:31:44 AM 08/13/2020 Transfer Switch 1st Floor Pump House Tested 9:12:45 AM 08/13/2020

Wet Pipe Waterflow Switch 1st Floor Mechanical Room by Cafe For Zone #1 Tested 9:20:58 AM 08/13/2020 Drain 1st Floor Mechanical Room by Cafe For Zone #1 Tested 9:24:09 AM 08/13/2020 Control Valve 1st Floor outside room C112 Cafeteria Zone 2 Tested 9:23:35 AM 08/13/2020 Control Valve 1st Floor corridor Outside room C108 by stage Tested 9:23:47 AM 08/13/2020 Control Valve 1st Floor Mechanical Room by Cafe For Zone #1 Tested 9:23:57 AM 08/13/2020 Control Valve 1st Floor corridor Outside room C108 by stage Tested 9:24:06 AM 08/13/2020 Inspector's Test 1st Floor corridor Outside C108 by stage Inspected 9:32:25 AM 08/13/2020 Inspector's Test 1st Floor Area Room C108 by stage Inspected 9:32:32 AM 08/13/2020 Inspector's Test 1st Floor Cafe Entrance For Zone #1 Inspected 9:32:39 AM 08/13/2020 Inspector's Test 1st Floor Mechanical Room by Cafe Cafeteria

Zone 2 Inspected 9:32:46 AM 08/13/2020

Electrical Driver 1st Pump house Inspected 9:24:14 AM 08/13/2020

Failed/Other Fire Pump, Discharge

Check Valve 1st Pump house Inspected 9:13:36 AM 08/13/2020

Fire Pump Gauge 1st mechanical room by cafe Inspected 9:20:53 AM 08/13/2020 Gauge 1st Pump house Inspected 9:33:00 AM 08/13/2020 Gauge 1st Pump house Inspected 9:33:13 AM 08/13/2020 Gauge 1st Pump house Inspected 9:33:29 AM 08/13/2020

Wet Pipe, Building-

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Piping Whole building Inspected 9:32:06 AM 08/13/2020

Wet Pipe Water Storage Tank Annual 9:31:23 AM 08/13/2020 Check Valve 1st Floor Area Cafeteria Zone 2 Inspected 9:23:14 AM 08/13/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR 30 6” 1 47298350

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged 1st Floor Area Cafeteria Zone 2 06/20/2018 4" 47298338

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 200 1st Floor

outside room C112 Cafeteria Zone 2

4" Open Supervised 47298336

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 200 1st Floor

corridor Outside room C108 by stage

4" Open Supervised 47298349

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Nibco n/a 1st Floor

Mechanical Room by Cafe For Zone #1

6" Open Supervised 47298352

Description Isolation

Control Valve

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 200 1st Floor

corridor Outside room C108 by stage

4" Open Supervised 47298353

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID NIBCO 105 110 n/a 47298357

Location 1st Floor corridor Outside C108 by stage

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID NIBCO 105 110 n/a 47298348

Location 1st Floor Area Room C108 by stage

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain n/a n/a n/a 47298346

Location 1st Floor Cafe Entrance For Zone #1

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Nibco 100 110 n/a 47298337

Location 1st Floor Mechanical Room by Cafe Cafeteria Zone 2

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Mechanical Room by Cafe For Zone #1

1.5" 110 110 90 47298351

Previous Inspections

June 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Mechanical Room by

Cafe For Zone #1 1.5" 110 110 90 30 47298351

March 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Mechanical Room by

Cafe For Zone #1 1.5" 110 110 90 30 47298351

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Water Storage Tank

Location Capacity Internal Date Pressure psi Deg OK ScanID 75,000 07/18/2002 . na 1

Type Manufacturer Model Number In ground NIBCO 105

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Building: Benjamin Banneker Elementary School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Piping

Location Type Size Internal Date Whole building Steel 1”-5” 12/18/2003

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Tagged na 49307052

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Hubbell LX-2200 1st Floor Pump House 06/20/2018 A-211301-2-1

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 85 100 No Yes

Controller Manufacturer Model # Location Install Date Serial Number Hubbell B04 1st Pump house 06/20/2018 990104606

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 100 110 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Hubbell 12DOC 1st Pump house 06/20/2018 47298328

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 990104606 Automatic n/a n/a 5 100 110

Pump

Manufacturer Model Number Location Install Date Scan Number Patterson 12DOC 1st Pump house 06/20/2018 47298330

Serial Number Type Orientation Aligned? Water Supply Impeller Size FPVT-0034244 Pump Primary Vertical Yes Water Storage

Tank 9.313

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 97 0

75 500

62 750

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto 1st Floor Pump House n/a na 47298323

On psi Off psi AC Type Generator Batteries Run Period Timer n/a n/a Normal

Phase Yes No n/a

Alarms Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Floor Pump House 1 47298326

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Pump House n/a 1 47298327

Devices Gauge

Location Service Date 1st mechanical room by cafe 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

System Pressure Hubbell 12DOC 0 na 1/4 49307051

Gauge

Location Service Date 1st Pump house 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Hubbell 12DOC 0 na 1/4 49307055

Gauge

Location Service Date 1st Pump house 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Hubbell 12DOC 0 na 1/4 49307054

Gauge

Location Service Date 1st Pump house 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Hubbell 12DOC 0 na 1/4 49307053

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Building: Benjamin Banneker Elementary School Building-

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 202 1st Pump

house 6" Open Supervised 47298333

Description Discharge

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Building: Benjamin Banneker Elementary School Discharge

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Pump house n/a 1 47298325

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged by Grooved

1st Pump house 06/20/2018 6" 47298332

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Controller Pump 3.57% 1

Fire Pump Power Alarm 3.57% 1

Fire Pump Off Alarm 3.57% 1

Fire Pump Running Alarm 3.57% 1

Transfer Switch Pump 3.57% 1

Control Valve Valve 17.86% 5

Check Valve Valve 7.14% 2

Gauge Device 14.29% 4

Waterflow Switch Alarm 3.57% 1

Drain Device 3.57% 1

Electrical Driver Pump 3.57% 1

Water Storage Tank Device 3.57% 1

Pump Pump 3.57% 1

Piping Sprinkler 3.57% 1

Jockey Pump Pump 3.57% 1

Jockey Controller Pump 3.57% 1

Inspector's Test Valve 14.29% 4

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Electrical Driver 1 08543

06/20/2018

Fire Pump

Controller 1 LX-2200

Automatic 06/20/2018

Jockey Controller 1 B04

06/20/2018

Jockey Pump 1 12DOC Automatic

06/20/2018

Transfer Switch 1 LX450A33E6 Auto

06/20/2018

Fire Pump Power 1 n/a

Supervisory 06/20/2018

Fire Pump Running 1 n/a

Supervisory 06/20/2018

Pump 1 12DOC Pump Primary

06/20/2018

Fire Pump, Building-

Control Valve 1 202 Butterfly Discharge 06/20/2018

Fire Pump, Discharge

Check Valve 1 08543 Flanged by Grooved

06/20/2018

Fire Pump Off 1 08543

Supervisory 06/20/2018

Wet Pipe

Check Valve 1 202 Flanged

06/20/2018

Control Valve 3 200 Butterfly Isolation 06/20/2018

Control Valve 1 n/a OS&Y Isolation 06/20/2018

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Drain 1 n/a Main

06/20/2018

Inspector's Test 1 100

06/20/2018

Inspector's Test 2 105

06/20/2018

Waterflow Switch 1 VSR Vane Alarm 06/20/2018

Inspector's Test 1 n/a

06/20/2018

Wet Pipe, Building-

Piping 1 VSR Steel

06/20/2018

In Service - 15 Years to 25 Years

Wet Pipe

Water Storage Tank 1 105 In ground

06/20/2005

Fire Pump

Gauge 4 12DOC System Pressure

06/20/1998

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Benjamin Banneker Elementary School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Fire Pump 1 Gauge 1st mechanical room by cafe Date Expired 49307051

No isolation valve

Sprinkler Inspection Certificate For

Captain Walter Francis Duke Elementary School

23595 Hayden Farm Lane Leonardtown, Maryland 20650

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 12, 2020

Building: Captain Walter Francis Duke Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Captain Walter Francis Duke Elementary School

Contact: Cathy Orolan

Address: 23595 Hayden Farm Lane Phone: 301-475-4256

Address: Fax:

City/State/Zip: Leonardtown, Maryland 20650 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 26 Wet Pipe 11

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 5 8.20% 5 100.00% 4 80.00% 1 20.00% Alarm 18 29.51% 18 100.00% 18 100.00% 0 0% Valve 26 42.62% 26 100.00% 19 73.08% 7 26.92% Hose 1 1.64% 1 100.00% 0 0% 1 100.00% Pump 7 11.48% 7 100.00% 7 100.00% 0 0% Sprinkler 4 6.56% 4 100.00% 4 100.00% 0 0%

Totals 61 100% 61 100.00

% 52 85.25% 9 14.75%

Certification Company: Fire & Life Safety America, Inc. - Baltimore

Building: Captain Walter Francis Duke Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:58:56 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Captain Walter Francis Duke Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Alarm Valve 47298313 1st B20 Needs 5 Yr. Service NFPA25 13.4.1.2 47298314 1st B20 Needs 5 Yr. Service NFPA25 13.4.1.2 47298315 1st B20 Needs 5 Yr. Service NFPA25 13.4.1.2 47298318 1st A35 Cafeteria storage Needs 5 Yr. Service NFPA25 13.4.1.2

Fire Pump Check Valve

47298276 1st Floor Sprinkler Room Fire Pump Bypass Needs 5 Yr. Service NFPA25 13.4.2.1 47298287 1st Floor Sprinkler Room Fire Pump Discharge Needs 5 Yr. Service NFPA25 13.4.2.1

Gauge 47298262 1st Floor Sprinkler Room Jockey Pump Sensing

Line Date Expired NFPA25 13.2.7.2

Wet Pipe Check Valve

47298264 1st Floor Sprinkler Room FDC Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 47298263 1st Floor Back of Building Outside Sprinkler

Room Needs Hydro Test NFPA25 4.1.5.1

Code References NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Captain Walter Francis Duke Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Alarm Valve

47298313 1st B20 5 Yr. Internal cvb T/M 47298314 1st B20 5 Yr. Internal cvb T/M 47298315 1st B20 5 Yr. Internal cv-b T/M 47298318 1st A35 Cafeteria storage 5 Yr. Internal cvb T/M

Fire Pump

Check Valve

47298276 1st Floor Sprinkler Room Fire Pump Bypass 5 Yr. Internal U060717PE0 T/M 47298287 1st Floor Sprinkler Room Fire Pump

Discharge

5 Yr. Internal U060717PE0 T/M

Gauge

47298262 1st Floor Sprinkler Room Jockey Pump Sensing Line

Replace n/a T/M

Wet Pipe

Check Valve

47298264 1st Floor Sprinkler Room FDC 5 Yr. Internal U060717PE0 T/M

Fire Dep't Connection

47298263 1st Floor Back of Building Outside Sprinkler Room

Hydro Test Not Listed T/M

PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Captain Walter Francis Duke Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump

Fire Pump Off 1st Floor Sprinkler Room Tested 8:45:10 AM 08/12/2020 Fire Pump Power 1st Floor Sprinkler Room Tested 8:45:30 AM 08/12/2020 Fire Pump Running 1st Floor Sprinkler Room Tested 8:45:38 AM 08/12/2020 Tamper Switch 1st Floor Sprinkler Room Fire Pump Suction Tested 8:52:19 AM 08/12/2020 Tamper Switch 1st Floor Sprinkler Room Fire Pump Bypass #1 Tested 8:52:25 AM 08/12/2020 Tamper Switch 1st Floor Sprinkler Room Fire Pump Bypass #2 Tested 8:52:34 AM 08/12/2020 Tamper Switch 1st Floor Sprinkler Room Fire Pump Test Header Tested 8:52:41 AM 08/12/2020 Tamper Switch 1st Floor Sprinkler Room Fire Pump Discharge Tested 8:52:49 AM 08/12/2020 Controller 1st Floor Sprinkler Room Tested 8:44:41 AM 08/12/2020 Electrical Driver 1st Floor Sprinkler Room Inspected 8:44:48 AM 08/12/2020 Fire Pump Gauge 1st Floor Sprinkler Room

Suction,Discharge,Sensing Line Inspected 8:33:12 AM 08/12/2020

Jockey Controller 1st Floor Sprinkler Room Tested 8:51:10 AM 08/12/2020 Jockey Pump 1st Floor Sprinkler Room Inspected 8:51:17 AM 08/12/2020 Pump 1st Floor Sprinkler Room Tested 8:30:11 AM 08/12/2020 Transfer Switch 1st Floor Sprinkler Room Tested 8:53:22 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Suction Tested 8:35:10 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Jockey Pump Suction Tested 8:35:22 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Bypass #1 Tested 8:38:13 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Bypass #2 Tested 8:38:58 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Test Header Tested 8:41:12 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Jockey Pump

Discharge Tested 8:41:42 AM 08/12/2020

Control Valve 1st Floor Sprinkler Room Fire Pump Discharge Tested 8:41:56 AM 08/12/2020 Post Indicator Valve 1st Floor Outside of Sprinkler Room Inspected 8:51:35 AM 08/12/2020

Wet Pipe Tamper Switch 1st Floor Sprinkler Room Backflow #1 Tested 8:32:12 AM 08/12/2020 Tamper Switch 1st Floor Sprinkler Room Backflow #2 Tested 8:32:39 AM 08/12/2020 Sprinkler Box 1st Floor Sprinkler Room Inspected 8:51:53 AM 08/12/2020 Sprinkler Box Spares 1st Floor Sprinkler Room Inspected 8:51:58 AM 08/12/2020 Sprinkler Box Spares 1st Floor Sprinkler Room Inspected 8:52:08 AM 08/12/2020 Sprinkler Box Spares 1st Floor Sprinkler Room Inspected 8:52:11 AM 08/12/2020 Backflow Prevention 1st Floor Sprinkler Room Inspected 8:32:33 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Backflow #1 Tested 8:32:24 AM 08/12/2020 Control Valve 1st Floor Sprinkler Room Backflow #2 Tested 8:32:50 AM 08/12/2020

Tamper Switch 1st B20 Tested 8:52:56 AM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Tamper Switch 1st B20 Tested 8:53:02 AM 08/12/2020 Tamper Switch 1st B20 Tested 8:53:09 AM 08/12/2020 Tamper Switch 1st Cafeteria storage Tested 8:53:16 AM 08/12/2020 Waterflow Switch 1st B20 Tested 8:53:32 AM 08/12/2020 Waterflow Switch 1st B20 Tested 8:53:42 AM 08/12/2020 Waterflow Switch 1st B20 Tested 8:53:51 AM 08/12/2020 Waterflow Switch 1st Cafeteria storage Tested 8:53:59 AM 08/12/2020 Drain 1st B20 Tested 8:43:52 AM 08/12/2020 Drain 1st B20 Tested 8:44:04 AM 08/12/2020 Drain 1st B20 Tested 8:44:19 AM 08/12/2020 Drain 1st Gym A61 storage Tested 8:44:35 AM 08/12/2020 Control Valve 1st B20 Tested 8:42:42 AM 08/12/2020 Control Valve 1st B20 Tested 8:42:51 AM 08/12/2020 Control Valve 1st B20 Tested 8:43:01 AM 08/12/2020 Control Valve 1st Cafeteria storage Tested 8:43:33 AM 08/12/2020 Inspector's Test 1st B20 Inspected 8:45:48 AM 08/12/2020 Inspector's Test 1st B20 Inspected 8:45:53 AM 08/12/2020 Inspector's Test 1st B20 Inspected 8:45:59 AM 08/12/2020 Inspector's Test 1st Gym A61 storage Inspected 8:51:03 AM 08/12/2020

Failed/Other Fire Pump

Gauge 1st Floor Sprinkler Room Jockey Pump Sensing Line

Inspected 8:33:07 AM 08/12/2020

Check Valve 1st Floor Sprinkler Room Fire Pump Bypass Inspected 8:37:58 AM 08/12/2020 Check Valve 1st Floor Sprinkler Room Fire Pump Discharge Inspected 8:39:24 AM 08/12/2020

Wet Pipe Fire Dep't Connection 1st Floor Back of Building Outside Sprinkler

Room Inspected 8:45:05 AM 08/12/2020

Check Valve 1st Floor Sprinkler Room FDC Inspected 8:34:32 AM 08/12/2020

Alarm Valve 1st A35 Cafeteria storage Inspected 8:37:04 AM 08/12/2020 Alarm Valve 1st B20 Inspected 8:42:15 AM 08/12/2020 Alarm Valve 1st B20 Inspected 8:42:23 AM 08/12/2020 Alarm Valve 1st B20 Inspected 8:42:31 AM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Captain Walter Francis Duke Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298268

OS&Y Supervisory Potter 1 47298243

Components Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Wilkins 350ASTDA 6" Double Check Fire Line 06/20/2018

ScanID Water Purveyor Location Meter Account # Serial Number 47298242 n/a 1st Floor Sprinkler Room n/a 1896B

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 n/a n/a

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Sprinkler Room FDC 06/20/2018 4" 47298264

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Wilkins 48 1st Floor

Sprinkler Room Backflow #1

6" Open Supervised 47298241

Description Main Control

Control Valve

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Wilkins 48 1st Floor

Sprinkler Room Backflow #2

6" Open Supervised 47298244

Description Main Control

Devices Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Floor Back of Building Outside Sprinkler Room

Wall No Yes 2.5" 47298263

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

1 Yes No 12 unit Not Listed 1st Floor Sprinkler Room

47298257

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 6 Pendant Victaulic 1st Floor Sprinkler Room 47298258

Temperature KFactor Size Finish Response Time 155 11.2 1/2” Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 5 Pendant Victaulic 1st Floor Sprinkler Room 47298259

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 1 Concealed Pendant Victaulic 1st Floor Sprinkler Room 47298260

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Brass Fast Response

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Captain Walter Francis Duke Elementary School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Joslyn Clark G9C154-53RTU 1st Floor Sprinkler Room 06/20/2018 45030926

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 95 105 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID Weg 030360P3E284JPV 1st Floor Sprinkler Room 284JP 47298274

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3540 10 230/460 76.3/69 30 3540

Fire Pump Gauge

Location Discharge psi Suction psi OK ScanID 1st Floor Sprinkler Room Suction,Discharge,Sensing Line

na . 47298261

Controller Manufacturer Model # Location Install Date Serial Number Joslyn Clark Not Listed 1st Floor Sprinkler Room 06/20/2018 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 95 115 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Bluffton 1303007150 1st Floor Sprinkler Room 06/20/2018 47298286

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 1250-05-0DP Automatic 3450 208-230/

460 1.8/.9 105 120

Pump

Manufacturer Model Number Location Install Date Scan Number Aurora 4-383-9C 1st Floor Sprinkler Room 06/20/2018 47298275

Serial Number Type Orientation Aligned? Water Supply Impeller Size 14-2421872 Pump Primary Vertical Yes Water Storage

Tank 6.868

Pump Tests

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/12/20 120 35 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/12/20 110 35 501

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/12/20 95 35 756

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 84.5 0

75 500

56 750

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto 1st Floor Sprinkler Room n/a na 47298266

On psi Off psi AC Type Generator Batteries Run Period Timer 95 110 Normal

Phase Yes No n/a

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room n/a 1 47298240

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room 1 47298267

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room N/A 1 47298294

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298272

OS&Y Supervisory Potter 1 47298278

OS&Y Supervisory Potter 1 47298280

OS&Y Supervisory Potter 1 47298282

OS&Y Supervisory Potter 1 47298284

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged 1st Floor Sprinkler Room Fire Pump

Bypass 06/20/2014 6" 47298276

Flanged by Grooved

1st Floor Sprinkler Room Fire Pump Discharge

06/20/2014 6" 47298287

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV 1st Floor

Sprinkler Room Fire Pump Suction

6" Open Supervised 47298271

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y United 225-93 1st Floor

Sprinkler 1" Open Supervised 47298273

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Room Jockey Pump Suction

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV 1st Floor

Sprinkler Room Fire Pump Bypass #1

6" Open Supervised 47298277

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV 1st Floor

Sprinkler Room Fire Pump Bypass #2

6" Open Supervised 47298279

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV 1st Floor

Sprinkler Room Fire Pump Test Header

6" Open Supervised 47298281

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y United 225-93 1st Floor

Sprinkler Room Jockey Pump Discharge

1" Open Supervised 47298283

Description Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV 1st Floor

Sprinkler Room Fire Pump Discharge

6" Open Supervised 47298285

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Description Discharge

Post Indicator Valve

Manufacturer Model Location Kennedy 2945A 1st Floor Outside of Sprinkler Room

Type Position Status Size OK ScanID Ground Open Locked 6" 47298295

Devices Gauge

Location Service Date 1st Floor Sprinkler Room Jockey Pump Sensing Line 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika n/a 95 n/a 1/4 47298262

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Captain Walter Francis Duke Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Pump Pump 1.64% 1

Tamper Switch Alarm 18.03% 11

Control Valve Valve 21.31% 13

Backflow Prevention Valve 1.64% 1

Gauge Device 1.64% 1

Fire Pump Gauge Pump 1.64% 1

Check Valve Valve 4.92% 3

Alarm Valve Valve 6.56% 4

Drain Device 6.56% 4

Controller Pump 1.64% 1

Electrical Driver Pump 1.64% 1

Fire Dep't Connection Hose 1.64% 1

Fire Pump Off Alarm 1.64% 1

Fire Pump Power Alarm 1.64% 1

Fire Pump Running Alarm 1.64% 1

Inspector's Test Valve 6.56% 4

Jockey Controller Pump 1.64% 1

Jockey Pump Pump 1.64% 1

Post Indicator Valve Valve 1.64% 1

Sprinkler Box Sprinkler 1.64% 1

Sprinkler Box Spares Sprinkler 4.92% 3

Transfer Switch Pump 1.64% 1

Waterflow Switch Alarm 6.56% 4

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Control Valve 3 586n OS&Y Isolation 06/20/2018

Control Valve 1 osysu2 OS&Y Isolation 06/20/2018

Inspector's Test 1 N/A

06/20/2018

Inspector's Test 1 vsr

06/20/2018

Tamper Switch 4 osysu2 OS&Y Supervisory 06/20/2018

Waterflow Switch 4 vsr Vane Alarm 06/20/2018

Inspector's Test 1 N/A

06/20/2018

Inspector's Test 1 vsr

06/20/2018

Alarm Valve 1 cv-b Flanged

06/20/2018

Alarm Valve 3 cvb Flanged

06/20/2018

Drain 4 300 Auxiliary

06/20/2018

Fire Pump

Pump 1 4-383-9C Pump Primary

06/20/2018

Jockey Pump 1 1303007150 Automatic

06/20/2018

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Controller 1 G9C154-53RTU

Automatic 06/20/2018

Fire Pump Running 1 n/a

Supervisory 06/20/2018

Jockey Controller 1 Not Listed

06/20/2018

Transfer Switch 1 G9C154-53RTU Auto

06/20/2018

Post Indicator Valve 1 2945A Ground

06/20/2018

Control Valve 2 RWGV OS&Y Bypass 06/20/2018

Control Valve 1 RWGV OS&Y Discharge 06/20/2018

Control Valve 1 RWGV OS&Y Isolation 06/20/2018

Control Valve 1 RWGV OS&Y Suction 06/20/2018

Fire Pump Off 1 n/a

Supervisory 06/20/2018

Fire Pump Power 1 N/A

Supervisory 06/20/2018

Tamper Switch 5 OSYSU-2 OS&Y Supervisory 06/20/2018

Control Valve 1 225-93 OS&Y Discharge 06/20/2018

Control Valve 1 225-93 OS&Y Suction 06/20/2018

Electrical Driver 1 030360P3E284JPV

06/20/2018

Fire Pump Gauge 1 n/a Discharge

06/20/2018

Gauge 1 n/a Supply Pressure

06/20/2018

Wet Pipe

Fire Dep't Connection 1 Not Listed Wall

06/20/2018

Sprinkler Box 1 Not Listed

06/20/2018

Tamper Switch 2 OSYSU-2 OS&Y Supervisory 06/20/2018

Check Valve 1 U060717PE0 Grooved

06/20/2018

Sprinkler Box Spares 1 2708 Pendant

06/20/2018

Sprinkler Box Spares 1 3412 Pendant

06/20/2018

Sprinkler Box Spares 1 3802 Concealed Pendant

06/20/2018

Backflow Prevention 1 350ASTDA Double Check

06/20/2018

Control Valve 2 48 OS&Y Main Control 06/20/2018

In Service - 5 Years to 10 Years

Fire Pump

Check Valve 1 U060717PE0 Flanged

06/20/2014

Check Valve 1 U060717PE0 Flanged by Grooved

06/20/2014

Sprinkler Inspection Certificate For

Chopticon High School 25390 Colton Point Road Morganza, Maryland 20660

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 12, 2020

Building: Chopticon High School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Chopticon High School Contact: Cathy Orolan

Address: 25390 Colton Point Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Morganza, Maryland 20660 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump Building- 14 Wet Pipe Building- 53

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 13 19.40% 13 100.00% 4 30.77% 9 69.23% Alarm 14 20.90% 14 100.00% 14 100.00% 0 0% Valve 25 37.31% 25 100.00% 24 96.00% 1 4.00% Hose 1 1.49% 1 100.00% 1 100.00% 0 0% Pump 6 8.96% 6 100.00% 5 83.33% 1 16.67% Sprinkler 8 11.94% 8 100.00% 7 87.50% 1 12.50%

Totals 67 100% 67 100.00

% 55 82.09% 12 17.91%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Chopticon High School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 18, 2020 6:48:29 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Chopticon High School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Fire Pump, Building- Check Valve

47298558 Outside Pump House Needs 5 Yr. Service NFPA25 13.4.2.1

Transfer Switch 47298534 Outside Pump House Special Note NFPA25 8.3.6.2

Wet Pipe, Building- Gauge

49307070 1st janitor closet b3 Date Expired NFPA25 13.2.7.2 49307067 1st janitor closet b3 Date Expired NFPA25 13.2.7.2 49307068 1st janitor closet b2 Date Expired NFPA25 13.2.7.2 49307069 2nd janitor closet b4 Date Expired NFPA25 13.2.7.2 49307066 2nd janitor closet b4 Needs 5 Yr. Service 49307071 pump house Date Expired NFPA25 13.2.7.2 49307072 pump house Date Expired NFPA25 13.2.7.2 49307073 pump house Date Expired NFPA25 13.2.7.2

Piping 47298557 All Building Needs 5 Yr. Service NFPA25 14.2.1.1

Water Storage Tank 1 outside by pump house Needs 5 Yr. Service

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 8.3.6.2 Automatic transfer switches shall be tested routinely and exercised in accordance with NFPA 110 NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Chopticon High School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Fire Pump, Building-

Check Valve

47298558 Outside Pump House 5 Yr. Internal n/a T/M

Transfer Switch

47298534 Outside Pump House Correct 25017FP T/M

Wet Pipe, Building-

Gauge

49307070 1st janitor closet b3 Replace N/A T/M 49307067 1st janitor closet b3

N/A T/M 49307068 1st janitor closet b2 Replace N/A T/M 49307069 2nd janitor closet b4 Replace N/A T/M 49307066 2nd janitor closet b4 5 Yr. Internal N/A T/M 49307071 pump house Replace N/A T/M 49307072 pump house Replace N/A T/M 49307073 pump house Replace N/A T/M

Piping

47298557 All Building 5 Yr. Internal N/A T/M

Water Storage Tank

1 outside by pump house 5 Yr. Internal na T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Chopticon High School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump, Building-

Fire Pump Off Outside Pump House Tested 12:17:44 PM 08/12/2020 Fire Pump Power Outside Pump House Tested 12:17:17 PM 08/12/2020 Fire Pump Running Outside Pump House Tested 12:17:41 PM 08/12/2020 Waterflow Switch Outside Pump House Pump House Wet Riser Tested 12:21:59 PM 08/12/2020 Controller Outside Pump House Tested 12:17:48 PM 08/12/2020 Electrical Driver Outside Pump House Inspected 12:18:21 PM 08/12/2020 Jockey Controller Outside Pump House Tested 12:17:53 PM 08/12/2020 Jockey Pump Outside Pump House Inspected 12:17:56 PM 08/12/2020 Pump Outside Pump House Tested 12:35:38 PM 08/12/2020 Control Valve Outside Pump House Fire Pump Discharge Tested 12:18:41 PM 08/12/2020 Control Valve Outside Pump House Pump House Wet Riser Tested 12:18:52 PM 08/12/2020 Control Valve Outside Pump House Fire Pump Test Header Tested 12:19:42 PM 08/12/2020

Wet Pipe, Building- Waterflow Switch 1st Mechanical Mechanical Riser 1 Tested 12:44:43 PM 08/12/2020 Waterflow Switch 1st Mechanical Mechanical Riser 3 Tested 12:48:40 PM 08/12/2020 Waterflow Switch 1st Mechanical Mechanical Riser 2 Tested 12:48:56 PM 08/12/2020 Waterflow Switch 1st Mechanical Mechanical Riser 1 main flow Tested 12:50:25 PM 08/12/2020 Waterflow Switch 1st Closet Closet B1 Tested 12:55:09 PM 08/12/2020 Waterflow Switch 1st Closet Closet B1 Tested 12:56:41 PM 08/12/2020 Waterflow Switch 1st Closet Closet B2 Tested 1:00:58 PM 08/12/2020 Waterflow Switch 1st Closet Closet B2 Tested 1:05:00 PM 08/12/2020 Waterflow Switch 2nd Closet Closet B4 Tested 1:06:23 PM 08/12/2020 Waterflow Switch 2nd Closet Closet B4 Tested 1:07:10 PM 08/12/2020 Drain 1st Mechanical Mechanical Riser 2 Tested 12:49:47 PM 08/12/2020 Drain 1st Mechanical Mechanical Riser 2 Tested 12:49:58 PM 08/12/2020 Drain 1st Mechanical Mechanical Riser 2 Tested 12:50:06 PM 08/12/2020 Drain Outside Pump House Pump House Wet Riser Tested 12:19:22 PM 08/12/2020 Fire Dep't Connection Outside Main Entrance Inspected 12:16:44 PM 08/12/2020 Sprinkler Box Outside Pump House Inspected 12:16:21 PM 08/12/2020 Sprinkler Box Outside Pump House Inspected 12:16:36 PM 08/12/2020 Sprinkler Box Outside Pump House Inspected 12:16:48 PM 08/12/2020 Sprinkler Box Spares Outside Pump House Inspected 12:16:24 PM 08/12/2020 Sprinkler Box Spares Outside Pump House Inspected 12:16:27 PM 08/12/2020 Sprinkler Box Spares Outside Pump House Inspected 12:16:31 PM 08/12/2020 Sprinkler Box Spares Outside Pump House Inspected 12:16:41 PM 08/12/2020 Control Valve 1st Mechanical Mechanical Riser 1 Tested 12:43:59 PM 08/12/2020 Control Valve 1st Mechanical Mechanical Riser 2 Tested 12:44:07 PM 08/12/2020 Control Valve 1st Mechanical Mechanical Riser 3 Tested 12:44:19 PM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Control Valve 1st Mechanical Mechanical Riser 4 Tested 12:44:31 PM 08/12/2020 Control Valve 1st Mechanical Mechanical Riser 1 Tested 12:49:20 PM 08/12/2020 Control Valve 1st Mechanical Mechanical Riser 1 Tested 12:51:11 PM 08/12/2020 Control Valve 1st Closet Closet B1 Tested 12:55:23 PM 08/12/2020 Control Valve 1st Closet Closet B1 Tested 12:55:37 PM 08/12/2020 Control Valve 1st Closet Closet B2 Tested 1:01:17 PM 08/12/2020 Control Valve 1st janitor closet b2 Closet B2 Tested 1:04:25 PM 08/12/2020 Control Valve 1st janitor closet b2 Closet Closet B2 Tested 1:04:52 PM 08/12/2020 Control Valve 2nd Closet Closet B4 Tested 1:06:01 PM 08/12/2020 Control Valve 2nd janitor closet b4 Closet B4 Tested 1:06:12 PM 08/12/2020 Control Valve 2nd Closet EMR elevator Tested 1:07:18 PM 08/12/2020 Inspector's Test 1st Closet Closet B1 Inspected 12:56:13 PM 08/12/2020 Inspector's Test 1st Closet Closet B1 Inspected 12:57:20 PM 08/12/2020 Inspector's Test 1st Closet Closet B2 Inspected 1:01:36 PM 08/12/2020 Inspector's Test 1st janitorial closet b2 Closet B2 Inspected 1:04:17 PM 08/12/2020 Inspector's Test 2nd janitor closet b4 Closet B4 Inspected 1:05:41 PM 08/12/2020 Inspector's Test 2nd Closet Closet B4 Inspected 1:07:01 PM 08/12/2020 Inspector's Test Outside Pump House Pump House Wet Riser Inspected 12:18:59 PM 08/12/2020

Failed/Other Fire Pump, Building-

Transfer Switch Outside Pump House Tested 12:21:24 PM 08/12/2020 Check Valve Outside Pump House Inspected 12:19:54 PM 08/12/2020

Wet Pipe, Building- Gauge 1st janitor closet b3 Inspected 12:19:19 PM 08/12/2020 Gauge 1st janitor closet b3 Inspected 1:01:59 PM 08/12/2020 Gauge 1st janitor closet b2 Inspected 1:05:09 PM 08/12/2020 Gauge 2nd janitor closet b4 Inspected 1:05:20 PM 08/12/2020 Gauge 2nd janitor closet b4 Inspected 1:05:34 PM 08/12/2020 Gauge pump house Inspected 12:20:11 PM 08/12/2020 Gauge pump house Inspected 12:20:23 PM 08/12/2020 Gauge pump house Inspected 12:20:45 PM 08/12/2020 Water Storage Tank outside by pump house Inspected 12:21:47 PM 08/12/2020 Piping All Building Inspected 12:17:14 PM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Chopticon High School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD25 30 4 1 47298564

Vane System Sensor WFD25 30 4 1 47298566

Vane System Sensor WFD25 30 4 1 47298565

Vane System Sensor WFD60 30 6 1 47298567

Vane System Sensor WFD40 30 4 1 47298587

Vane System Senor WFD40 30 4 1 47298638

Vane System Sensor WFD40 30 4 1 47298584

Vane System Sensor WFD40 30 4 1 47298592

Vane System Senor WFD40 39 4 1 47298580

Vane System Senor WFD40 39 4 1 47298581

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD47 1st

Mechanical Mechanical Riser 1

4" Open Supervised 47298568

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD47 1st

Mechanical Mechanical Riser 2

4" Open Supervised 47298569

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD47 1st

Mechanical Mechanical

4" Open Supervised 47298570

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Riser 3

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD47 1st

Mechanical Mechanical Riser 4

4" Open Supervised 47298571

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD47 1st

Mechanical Mechanical Riser 1

4" Open Supervised 47298575

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD47 1st

Mechanical Mechanical Riser 1

4" Open Supervised 47298563

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO AGD4765 1st Closet

Closet B1 4" Open Supervised 47298588

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AV20 1st Closet

Closet B1 4" Open Supervised 47298605

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly System Sensor VFR22 1st Closet

Closet B2 4" Open Supervised 47298585

Description Isolation

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic F4R112 1st janitor

closet b2 Closet B2

4" Open Supervised 47298590

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO F4R112 1st janitor

closet b2 Closet Closet B2

1" Open Supervised 47298591

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD470 2nd Closet

Closet B4 1" Open Supervised 47298578

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD470 2nd janitor

closet b4 Closet B4

1" Open Supervised 47298579

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO GD470 2nd Closet

EMR elevator 1" Open Supervised 47298583

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Giacomini 141 100 12 47298606

Location 1st Closet Closet B1

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Giacomini 141 110 12 30 47298639

Location 1st Closet Closet B1

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 102 95 12 47298586

Location 1st Closet Closet B2

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 102 110 15 47298589

Location 1st janitorial closet b2 Closet B2

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 141 110 15 47298577

Location 2nd janitor closet b4 Closet B4

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 141 110 15 47298640

Location 2nd Closet Closet B4

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain N/A 75 15 47298544

Location Outside Pump House Pump House Wet Riser

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Mechanical Mechanical Riser 2

2" 110 95 90 30 47298574

Previous Inspections

June 8, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Mechanical Mechanical

Riser 2 2" 110 95 90 47298574

March 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Mechanical Mechanical

Riser 2 2" 110 95 90 30 47298574

Current Inspection

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Mechanical Mechanical Riser 2

2" 110 90 90 30 47298573

Previous Inspections

June 8, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Mechanical Mechanical

Riser 2 2" 110 90 90 47298573

March 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Mechanical Mechanical

Riser 2 2" 110 90 90 30 47298573

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Mechanical Mechanical Riser 2

2" 110 100 90 47298572

Previous Inspections

June 8, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Mechanical Mechanical

Riser 2 2" 110 100 90 30 47298572

March 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Mechanical Mechanical

Riser 2 2" 110 100 90 30 47298572

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main Outside Pump House Pump House Wet Riser

2” 105 95 80 30 47298545

Previous Inspections

June 8, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside Pump House Pump

House Wet Riser 2” 105 95 80 47298545

March 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside Pump House Pump

House Wet Riser 2” 105 95 80 30 47298545

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID Outside Main Entrance Wall Yes Yes 2.5" 47298553

Gauge

Location Service Date 1st janitor closet b3 07/16/2018

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307070

Gauge

Location Service Date 1st janitor closet b3 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307067

Gauge

Location Service Date 1st janitor closet b2 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307068

Gauge

Location Service Date 2nd janitor closet b4 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307069

Gauge

Location Service Date 2nd janitor closet b4 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307066

Gauge

Location Service Date pump house 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307071

Gauge

Location Service Date pump house 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 100 none 1/4

” 49307072

Gauge

Location Service Date pump house 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

System Pressure Wika N/A 100 none 1/4”

49307073

Piping

Location Type Size Internal Date All Building Steel 1/2”-6” 07/16/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47298557

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

12 Yes No 12 unit N/A Outside Pump House 47298541

12 Yes No 12 unit N/A Outside Pump House 47298540

12 Yes No 12 unit N/A Outside Pump House 47298539

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Horizontal Sidewall Tyco Outside Pump House 47298555

Temperature KFactor Size Finish Response Time 155 5.6 1/2 Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 6 Pendant Tyco Outside Pump House 47298552

Temperature KFactor Size Finish Response Time 155 5.6 1/2 Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 4 Pendant Tyco Outside Pump House 47298551

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Brass Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 8 Pendant Rasco Outside Pump House 47298554

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Chrome Fast Response

Water Storage Tank

Location Capacity Internal Date Pressure psi Deg OK ScanID outside by pump house 75,000 12/18/2019 . na 1

Type Manufacturer Model Number In ground na na

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Chopticon High School Building-

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Hubbell LX2200 Outside Pump House 07/16/2018 A823097-1-1

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 75 100 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID US Electrical Motors

324TP Outside Pump House S307A-B05-5813M

47298536

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 1775 10 minutes 230/460 103/51.5 40 1775

Controller Manufacturer Model # Location Install Date Serial Number Hubbell N/A Outside Pump House 07/16/2018 not listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 85 100 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Grundfos not legible Outside Pump House 07/16/2018 49302553

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi not legible Automatic not legible not

legible not legible

85 100

Pump

Manufacturer Model Number Location Install Date Scan Number Patterson PVT Outside Pump House 07/16/2018 47298535

Serial Number Type Orientation Aligned? Water Supply Impeller Size 4TSC-C012376-01

Pump Primary Vertical Yes Water Storage Tank

12 DMC

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/12/20 115 0 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/12/20 90 0 501

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/12/20 75 0 756

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 105 0

90 500

73 750

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto Outside Pump House N/A . 47298534

On psi Off psi AC Type Generator Batteries Run Period Timer

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

75 100 Normal Phase

Yes No 10

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory Outside Pump House N/A 1 47298531

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory N/A Outside Pump House 1 47298533

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory Outside Pump House N/A 1 47298532

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD25 30 2” 1 47298542

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged Outside Pump House 07/16/1997 6" 47298558

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Nibco SWP Outside Pump

House Fire Pump Discharge

6" Open Locked 47298559

Description Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy n/a Outside Pump

House Pump House Wet Riser

2" Open Supervised 47298543

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Nibco 40227 Outside Pump

House Fire Pump Test Header

6" Closed Locked 47298546

Description Test Header

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Chopticon High School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Sprinkler Box Sprinkler 4.48% 3

Sprinkler Box Spares Sprinkler 5.97% 4

Fire Dep't Connection Hose 1.49% 1

Piping Sprinkler 1.49% 1

Fire Pump Power Alarm 1.49% 1

Fire Pump Running Alarm 1.49% 1

Fire Pump Off Alarm 1.49% 1

Controller Pump 1.49% 1

Jockey Controller Pump 1.49% 1

Jockey Pump Pump 1.49% 1

Electrical Driver Pump 1.49% 1

Control Valve Valve 25.37% 17

Inspector's Test Valve 10.45% 7

Gauge Device 11.94% 8

Drain Device 5.97% 4

Check Valve Valve 1.49% 1

Transfer Switch Pump 1.49% 1

Water Storage Tank Device 1.49% 1

Waterflow Switch Alarm 16.42% 11

Pump Pump 1.49% 1

Device Type

Qty Model # Type Description Install Date

In Service - 90 Days - 1 Year

Wet Pipe, Building-

Water Storage Tank 1 na In ground

12/18/2019

In Service - 2 Years to 3 Years

Fire Pump, Building-

Jockey Pump 1 not legible Automatic

07/16/2018

Controller 1 LX2200

Automatic 07/16/2018

Fire Pump Off 1 LX2200

Supervisory 07/16/2018

Fire Pump Power 1 LX2200

Supervisory N/A 07/16/2018

Fire Pump Running 1 LX2200

Supervisory 07/16/2018

Jockey Controller 1 N/A

07/16/2018

Transfer Switch 1 25017FP Auto

07/16/2018

Control Valve 1 n/a Butterfly Isolation 07/16/2018

Control Valve 1 40227 OS&Y Test Header 07/16/2018

Control Valve 1 SWP OS&Y Discharge 07/16/2018

Pump 1 PVT Pump Primary

07/16/2018

Waterflow Switch 1 WFD25 Vane Alarm 07/16/2018

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Electrical Driver 1 324TP

07/16/2018

Wet Pipe, Building-

Control Valve 1 AV20 Butterfly Isolation 07/16/2018

Inspector's Test 2 141

07/16/2018

Piping 1 N/A Steel

07/16/2018

Sprinkler Box 3 N/A

07/16/2018

Control Valve 1 AGD4765 Butterfly Isolation 07/16/2018

Control Valve 1 F4R112 Butterfly Isolation 07/16/2018

Control Valve 4 GD47 Butterfly Isolation 07/16/2018

Control Valve 2 GD47 Butterfly Main Control 07/16/2018

Control Valve 3 GD470 Butterfly Isolation 07/16/2018

Drain 3 2 Main

07/16/2018

Fire Dep't Connection 1 N/A Wall

07/16/2018

Sprinkler Box Spares 1 F1 Pendant

07/16/2018

Waterflow Switch 3 WFD40 Vane Alarm 07/16/2018

Control Valve 1 VFR22 Butterfly Isolation 07/16/2018

Drain 1 WFD25 Main

07/16/2018

Waterflow Switch 3 WFD25 Vane Alarm 07/16/2018

Waterflow Switch 3 WFD40 Vane Alarm 07/16/2018

Waterflow Switch 1 WFD60 Vane Alarm 07/16/2018

Inspector's Test 2 102

07/16/2018

Inspector's Test 2 141

07/16/2018

Inspector's Test 1 N/A

07/16/2018

Sprinkler Box Spares 1 TY3131 Pendant

07/16/2018

Sprinkler Box Spares 1 TY3251 Pendant

07/16/2018

Sprinkler Box Spares 1 TY4332 Horizontal Sidewall

07/16/2018

Control Valve 1 F4R112 Butterfly Isolation 07/16/2018

In Service - 15 Years to 25 Years

Wet Pipe, Building-

Gauge 7 N/A System Pressure

07/16/2004

Gauge 1 N/A System Pressure

01/01/1999

Fire Pump, Building-

Check Valve 1 n/a Flanged

07/16/1997

Fire & Life Safety America, Inc. - Baltimore 19 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Chopticon High School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Fire Pump, Building- 1 Transfer Switch Outside Pump House Special Note 47298534

Transfer switch did not operate during annual pump test. Further investigation required.

Wet Pipe, Building- 2 Gauge 1st janitor closet b3 Date Expired 49307070

No isolation valve

Sprinkler Inspection Certificate For

Leonardtown Technology Center 24005 Point Lookout Road Leonardtown, Maryland 20650

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 11, 2020

Building: Leonardtown Technology Center Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Leonardtown Technology Center Contact: Cathy Orolan

Address: 24005 Point Lookout Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Leonardtown, Maryland 20650 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Dry Pipe Building- 7 Wet Pipe Building- 17

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 5 20.83% 5 100.00% 3 60.00% 2 40.00% Alarm 4 16.67% 4 100.00% 4 100.00% 0 0% Valve 8 33.33% 8 100.00% 4 50.00% 4 50.00% Pump 1 4.17% 1 100.00% 1 100.00% 0 0% Sprinkler 6 25.00% 6 100.00% 4 66.67% 2 33.33%

Totals 24 100% 24 100.00

% 16 66.67% 8 33.33%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Leonardtown Technology Center

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:56:36 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Leonardtown Technology Center The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Dry Pipe, Building- Dry Pipe Valve

47298453 1st Electrical Classroom Feeding Outside Canopy Special Note NFPA25 4.1.5.1

Gauge 47298443 1st Electrical Classroom Feeding Outside Canopy

(1) Water (1) Air Date Expired NFPA25 13.2.7.2

Piping 47298444 1st Electrical Classroom Feeding Outside Canopy Special Note NFPA25 4.1.5.1

Wet Pipe, Building- Check Valve

47298461 Outside Sprinkler Room Wet Riser #2 Needs 5 Yr. Service NFPA25 13.4.2.1 47298462 Outside Sprinkler Room Wet Riser #1 Needs 5 Yr. Service NFPA25 13.4.2.1 47298471 Outside Sprinkler Room Needs 5 Yr. Service NFPA25 13.4.2.1

Gauge 47298496 Outside Sprinkler Room (2) Water Date Expired NFPA25 13.2.7.2

Piping 47298495 Outside Sprinkler Room All Building Needs 5 Yr. Service NFPA25 14.2.1.1

Code References NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Leonardtown Technology Center

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Dry Pipe, Building-

Dry Pipe Valve

47298453 1st Electrical Classroom Feeding Outside Canopy

Correct F3061 T/M

Gauge

47298443 1st Electrical Classroom Feeding Outside Canopy (1) Water (1) Air

Replace topi-pg T/M

Piping

47298444 1st Electrical Classroom Feeding Outside Canopy

Correct n/a T/M

Wet Pipe, Building-

Check Valve

47298461 Outside Sprinkler Room Wet Riser #2 5 Yr. Internal 7800FP T/M 47298462 Outside Sprinkler Room Wet Riser #1 5 Yr. Internal 7800FP T/M 47298471 Outside Sprinkler Room 5 Yr. Internal 7800FP T/M

Gauge

47298496 Outside Sprinkler Room (2) Water Replace n/a T/M

Piping

47298495 Outside Sprinkler Room All Building 5 Yr. Internal n/a T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Leonardtown Technology Center The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Dry Pipe, Building-

Waterflow Switch 1st Electrical Classroom Feeding Outside Canopy

Tested 12:51:15 PM 08/11/2020

Drain 1st Electrical Classroom Feeding Outside Canopy

Tested 12:50:40 PM 08/11/2020

Air Compressor 1st Electrical Classroom Feeding Outside Canopy

Inspected 12:29:41 PM 08/11/2020

Control Valve 1st Electrical Classroom Feeding Outside Canopy

Tested 12:48:03 PM 08/11/2020

Wet Pipe, Building- Tamper Switch Outside Sprinkler Room Main System Control

Valve Tested 12:44:28 PM 08/11/2020

Waterflow Switch Outside Sprinkler Room Wet Riser #2 Tested 12:43:41 PM 08/11/2020 Waterflow Switch Outside Sprinkler Room Wet Riser #1 Tested 12:43:49 PM 08/11/2020 Drain Outside Sprinkler Room Wet Riser #2 Tested 12:43:34 PM 08/11/2020 Drain Outside Sprinkler Room Wet Riser #1 Tested 12:50:56 PM 08/11/2020 Sprinkler Box Outside Sprinkler Room Inspected 12:43:17 PM 08/11/2020 Sprinkler Box Spares Outside Sprinkler Room Inspected 12:43:19 PM 08/11/2020 Sprinkler Box Spares Outside Sprinkler Room Inspected 12:43:27 PM 08/11/2020 Wrenches Outside Sprinkler Room Inspected 12:43:15 PM 08/11/2020 Control Valve Outside Sprinkler Room Wet Riser #2 Tested 12:48:31 PM 08/11/2020 Control Valve Outside Sprinkler Room Wet Riser #1 Tested 12:48:40 PM 08/11/2020 Control Valve Outside Sprinkler Room Main System Control

Valve Tested 12:49:38 PM 08/11/2020

Failed/Other Dry Pipe, Building-

Gauge 1st Electrical Classroom Feeding Outside Canopy (1) Water (1) Air

Inspected 12:30:03 PM 08/11/2020

Piping 1st Electrical Classroom Feeding Outside Canopy

Inspected 12:30:37 PM 08/11/2020

Dry Pipe Valve 1st Electrical Classroom Feeding Outside Canopy

Tested 12:51:08 PM 08/11/2020

Wet Pipe, Building- Gauge Outside Sprinkler Room (2) Water Inspected 12:43:09 PM 08/11/2020 Piping Outside Sprinkler Room All Building Inspected 12:43:05 PM 08/11/2020 Check Valve Outside Sprinkler Room Wet Riser #2 Inspected 12:29:13 PM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Check Valve Outside Sprinkler Room Wet Riser #1 Inspected 12:29:23 PM 08/11/2020 Check Valve Outside Sprinkler Room Inspected 12:29:30 PM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Leonardtown Technology Center Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298458

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD40 30 4” 1 47298463

Vane System Sensor WFD40 30 4” 1 47298464

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved Outside Sprinkler Room Wet Riser #2 07/16/2018 4" 47298461

Grooved Outside Sprinkler Room Wet Riser #1 07/16/2018 4" 47298462

Grooved Outside Sprinkler Room 07/16/2018 6" 47298471

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Gruvlock AE7722-3A Outside

Sprinkler Room Wet Riser #2

4" Open Supervised 47298459

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Gruvlock AE7722-3A Outside

Sprinkler Room Wet Riser #1

4" Open Supervised 47298460

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Clow AwwA Outside

Sprinkler 6" Open Supervised 47298470

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Room Main System Control Valve

Description Main Control

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main Outside Sprinkler Room Wet Riser #2

2" 115 115 75 39 47298465

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside Sprinkler Room Wet

Riser #2 2" 115 115 75 30 47298465

March 12, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside Sprinkler Room Wet

Riser #2 2" 115 115 75 30 47298465

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main Outside Sprinkler Room Wet Riser #1

2" 120 115 78 30 47298466

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside Sprinkler Room Wet

Riser #1 2" 120 115 78 30 47298466

March 12, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside Sprinkler Room Wet

Riser #1 2" 120 115 78 30 47298466

Gauge

Location Service Date Outside Sprinkler Room (2) Water 07/16/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Argco n/a 110 none 1/4 47298496

Piping

Location Type Size Internal Date Outside Sprinkler Room All Building

Steel 1/2”-6” 07/16/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47298495

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

12 Yes No 12 unit steel Outside Sprinkler Room

47298442

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Upright Tyco Outside Sprinkler Room 47298497

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Brass Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Pendant Tyco Outside Sprinkler Room 47298467

Temperature KFactor Size Finish Response Time 155 5.6 1/2” White Fast Response

Wrenches

Qty Type Manufacturer Location OK ScanID 1 Sprinkler Rasco Outside Sprinkler Room 47298468

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Leonardtown Technology Center Building-

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Air Compressor

Location Mfr. Model # Phase On psi Off psi Serial No. 1st Electrical Classroom Feeding Outside Canopy

General OL33550AC

1 35 45 OL335-05420291

Type Description Rated Speed Horsepower Volts Amps OK ScanID Automatic Tankless 1725 .5 115 9.8 47298454

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Pressure Switch System Sensor EPS10-2 1/2” 1 47298456

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Gem 7700FP 1st Electrical

Classroom Feeding Outside Canopy

3" Open Supervised 47298455

Description Isolation

Dry Pipe Valve

Manufacturer Model # Location Internal Date OK ScanID Gem F3061 1st Electrical Classroom Feeding

Outside Canopy 12/20/2018 47298453

Type Status Position Size Serial # Flanged by Grooved 3" 663A

Water psi Air Pressure Trip Air Trip Time Total Timing (sec)

Partial Trip Date Full Trip Date

12/20/2018 12/20/2018

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Electrical Classroom 1.25" 110 105 90 30 47298457

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Feeding Outside Canopy

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Electrical Classroom

Feeding Outside Canopy 1.25" 110 105 90 30 47298457

March 12, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Electrical Classroom

Feeding Outside Canopy 1.25" 110 105 90 30 47298457

Gauge

Location Service Date 1st Electrical Classroom Feeding Outside Canopy (1) Water (1) Air

03/16/1998

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika topi-pg 110 n/a 1/4 47298443

Piping

Location Type Size Internal Date 1st Electrical Classroom Feeding Outside Canopy

Steel 1/2”-3” 07/16/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked n/a 47298444

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Leonardtown Technology Center

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Check Valve Valve 12.50% 3

Air Compressor Pump 4.17% 1

Gauge Device 8.33% 2

Piping Sprinkler 8.33% 2

Wrenches Sprinkler 4.17% 1

Sprinkler Box Sprinkler 4.17% 1

Sprinkler Box Spares Sprinkler 8.33% 2

Drain Device 12.50% 3

Waterflow Switch Alarm 12.50% 3

Tamper Switch Alarm 4.17% 1

Control Valve Valve 16.67% 4

Dry Pipe Valve Valve 4.17% 1

Device Type

Qty Model # Type Description Install Date

In Service - 15 Years to 25 Years

Dry Pipe, Building-

Control Valve 1 7700FP Butterfly Isolation 03/16/1998

Dry Pipe Valve 1 F3061 Flanged by Grooved

03/16/1998

Air Compressor 1 OL33550AC Automatic Tankless 03/16/1998

Piping 1 n/a Steel

03/16/1998

Drain 1 EPS10-2 Main

03/16/1998

Waterflow Switch 1 EPS10-2 Pressure Switch Alarm 03/16/1998

Gauge 1 topi-pg Supply Pressure

03/16/1998

Wet Pipe, Building-

Gauge 1 n/a System Pressure

03/16/1998

Control Valve 1 AwwA OS&Y Main Control 03/16/1998

Check Valve 3 7800FP Grooved

03/16/1998

Control Valve 2 AE7722-3A Butterfly Isolation 03/16/1998

Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/16/1998

Wrenches 1 n/a Sprinkler

03/16/1998

Piping 1 n/a Steel

03/16/1998

Sprinkler Box 1 n/a

03/16/1998

Waterflow Switch 2 WFD40 Vane Alarm 03/16/1998

Drain 2 n/a Main

03/16/1998

Sprinkler Box Spares 1 Ty3131 Upright

03/16/1998

Sprinkler Box Spares 1 TY5231 Pendant

03/16/1998

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Leonardtown Technology Center

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Dry Pipe, Building- 1 Dry Pipe Valve 1st Electrical Classroom Feeding Outside

Canopy Special Note 47298453

Needs five-year internal inspection also needs three year air test. 2 Gauge 1st Electrical Classroom Feeding Outside

Canopy (1) Water (1) Air

Date Expired 47298443

A total of two. Only one needs replaced. 3 Piping 1st Electrical Classroom Feeding Outside

Canopy Special Note 47298444

Air compressor runs daily recommend to perform a 3 year air test on the system to check for leaks. Due for 5 year internal.

Sprinkler Inspection Certificate For

Esperanza Middle School 22790 Maple Road Lexington Park, Maryland 20653

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 11, 2020

Building: Esperanza Middle School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Esperanza Middle School Contact: Cathy Orolan

Address: 22790 Maple Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Lexington Park, Maryland 20653 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Dry Pipe 6 Dry Pipe Building- 4 Fire Pump 18 Wet Pipe 14 Wet Pipe Building- 2 Wet Pipe Building- 18 Wet Pipe Building- Building- 3

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 11 13.92% 11 100.00% 3 27.27% 8 72.73% Alarm 17 21.52% 17 100.00% 17 100.00% 0 0% Valve 37 46.84% 37 100.00% 23 62.16% 14 37.84% Hose 1 1.27% 1 100.00% 0 0% 1 100.00% Pump 7 8.86% 7 100.00% 5 71.43% 2 28.57% Sprinkler 6 7.59% 6 100.00% 4 66.67% 2 33.33%

Totals 79 100% 79 100.00

% 52 65.82% 27 34.18%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Esperanza Middle School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 11, 2020 9:03:08 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Esperanza Middle School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Dry Pipe Dry Pipe Valve

47298214 1st Floor At Loading Dock Sprinkler Room Needs 3 Yr. Service NFPA25 13.4.5.2.2.2; 13.4.5.2.9

Fire Pump Check Valve

47298211 1st Floor At Loading Dock Sprinkler Room Discharge

Needs 5 Yr. Service NFPA25 13.4.2.1

47298008 1st Floor At Loading Dock Sprinkler Room Bypass

Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 47298224 1st Floor At Loading Dock Sprinkler Room Fire

Pump Bypass #1 Special Note NFPA25 4.1.5.1

Pump 47298204 1st Floor At Loading Dock Sprinkler Room Special Note NFPA25 8.2.1

Wet Pipe Alarm Valve

47298215 1st Floor At Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 47298216 1st Floor At Loading Dock Sprinkler Room Zone

5,6,7 Needs 5 Yr. Service NFPA25 13.4.2.1

Building- Dry Pipe Gauge

45585476 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2 45585477 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2 45585478 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2

Piping 45585479 Ground Sprinkler Loading dock sprinkler room Special Note NFPA25 4.1.5.1

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

ScanID Location Problem Reference

Building- Wet Pipe Check Valve

47298230 1st Stair 1 Needs 5 Yr. Service NFPA25 13.4.2.1 47298235 1st Stair 4 Needs 5 Yr. Service NFPA25 13.4.2.1 47298251 1st Stair 3 Needs 5 Yr. Service NFPA25 13.4.2.1 47298256 2nd Stair 1 Needs 5 Yr. Service NFPA25 13.4.2.1 47298247 2nd Stair 3 Needs 5 Yr. Service NFPA25 13.4.2.1 47298232 2nd Stair 4 Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 47298225 1st Stair 3 Special Note NFPA25 4.1.5.1

Gauge 45585470 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2 45585471 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2 45585472 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2 45585474 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2 45585475 Ground Sprinkler Loading dock sprinkler room Date Expired NFPA25 13.2.7.2

Piping 47298180 Ground Sprinkler Loading dock sprinkler room Needs 5 Yr. Service NFPA25 14.2.1.1

Building- Wet Pipe, Building- Check Valve

47298177 1st Front Desk Front office storage Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 47298178 1st Front Desk Front office drop off Needs Hydro Test NFPA25 4.1.5.1

Fire Pump Gauge 47298179 Ground Sprinkler total of 2 Loading dock

sprinkler room Date Expired NFPA25 4.1.5.1

Code References NFPA25 13.4.5.2.2.2; 13.4.5.2.9

Every 3 years and whenever the system is altered, the dry pipe valve shall be trip tested with the control valve fully open and the quick-opening device, if provided, in service. Dry pipe systems shall be tested once every 3 years for gas leakage.

NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition.

NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 8.2.1 The purpose of inspection shall be to verify that the pump assembly appears to be in operating

condition and is free from physical damage NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Esperanza Middle School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Dry Pipe

Dry Pipe Valve

47298214 1st Floor At Loading Dock Sprinkler Room 3 yr air test S/756 T/M

Fire Pump

Check Valve

47298211 1st Floor At Loading Dock Sprinkler Room Discharge

5 Yr. Internal 6-175 T/M

47298008 1st Floor At Loading Dock Sprinkler Room Bypass

5 Yr. Internal 7800FP T/M

Control Valve

47298224 1st Floor At Loading Dock Sprinkler Room Fire Pump Bypass #1

Correct 693P T/M

Pump

47298204 1st Floor At Loading Dock Sprinkler Room Correct 5x3 MAC T/M

Wet Pipe

Alarm Valve

47298215 1st Floor At Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

5 Yr. Internal F517 T/M

Check Valve

47298216 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

5 Yr. Internal S380 T/M

Building- Dry Pipe

Gauge

45585476 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

45585477 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

45585478 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

Piping

45585479 Ground Sprinkler Loading dock sprinkler room

Correct N/A T/M

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

ScanID Location Solution Model # Cost Fix

Building- Wet Pipe

Check Valve

47298230 1st Stair 1 5 Yr. Internal 202 T/M 47298235 1st Stair 4 5 Yr. Internal k212 T/M 47298251 1st Stair 3 5 Yr. Internal 202 T/M 47298256 2nd Stair 1 5 Yr. Internal 202 T/M 47298247 2nd Stair 3 5 Yr. Internal D1 T/M 47298232 2nd Stair 4 5 Yr. Internal D1 T/M

Control Valve

47298225 1st Stair 3 Correct 212 T/M

Gauge

45585470 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

45585471 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

45585472 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

45585474 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

45585475 Ground Sprinkler Loading dock sprinkler room

Replace N/A T/M

Piping

47298180 Ground Sprinkler Loading dock sprinkler room

5 Yr. Internal N/A T/M

Building- Wet Pipe, Building-

Check Valve

47298177 1st Front Desk Front office storage 5 Yr. Internal 202 T/M

Fire Dep't Connection

47298178 1st Front Desk Front office drop off Hydro Test 200 T/M

Fire Pump Gauge

47298179 Ground Sprinkler total of 2 Loading dock sprinkler room

Replace 110 T/M

PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Esperanza Middle School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Dry Pipe

Pressure Switch 1st Floor At Loading Dock Sprinkler Room Tested 8:34:13 AM 08/11/2020 Waterflow Switch 1st Floor At Loading Dock Sprinkler Room Tested 8:34:20 AM 08/11/2020 Waterflow Switch 1st Floor Mechanical Room E108 Tested 8:52:53 AM 08/11/2020 Drain 1st Floor At Loading Dock Sprinkler Room Tested 8:33:45 AM 08/11/2020 Air Compressor 1st Floor At Loading Dock Sprinkler Room Inspected 8:45:34 AM 08/11/2020

Fire Pump Fire Pump Off 1st Floor At Loading Dock Sprinkler Room Tested 8:43:07 AM 08/11/2020 Fire Pump Power 1st Floor At Loading Dock Sprinkler Room Tested 8:43:00 AM 08/11/2020 Fire Pump Running 1st Floor At Loading Dock Sprinkler Room Tested 8:57:41 AM 08/11/2020 Tamper Switch 1st Floor At Loading Dock Sprinkler Room Fire

Pump Suction Tested 8:29:18 AM 08/11/2020

Controller 1st Floor At Loading Dock Sprinkler Room Tested 8:44:09 AM 08/11/2020 Electrical Driver 1st Floor At Loading Dock Sprinkler Room Inspected 8:29:49 AM 08/11/2020 Jockey Controller 1st Floor At Loading Dock Sprinkler Room Tested 8:45:15 AM 08/11/2020 Jockey Pump 1st Floor At Loading Dock Sprinkler Room Inspected 8:47:53 AM 08/11/2020 Control Valve 1st Floor At Loading Dock Sprinkler Room Fire

Pump Suction Tested 8:29:32 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Fire Pump Bypass #2

Tested 8:31:43 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Fire Pump Test Header

Tested 8:32:37 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Fire Pump Discharge

Tested 8:32:46 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Dry System

Tested 8:35:43 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Jockey Pump Suction

Tested 8:41:14 AM 08/11/2020

Building- Wet Pipe Waterflow Switch 2nd Stair 4 Tested 8:54:08 AM 08/11/2020 Control Valve 2nd Stair 3 Tested 8:47:01 AM 08/11/2020 Control Valve 2nd Stair 4 Tested 8:53:55 AM 08/11/2020 Inspector's Test 1st Stair 4 Inspected 9:02:15 AM 08/11/2020 Inspector's Test 2nd Stair 4 Inspected 8:53:40 AM 08/11/2020

Wet Pipe, Building- Waterflow Switch 1st Stair 4 Tested 9:02:58 AM 08/11/2020 Inspector's Test 1st Floor Mechanical Room E108 Inspected 8:53:06 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Device Type Location Service Time Date Wet Pipe

Tamper Switch 1st Floor At Loading Dock Sprinkler Room Backflow #1

Tested 8:25:16 AM 08/11/2020

Tamper Switch 1st Floor At Loading Dock Sprinkler Room Backflow #2

Tested 8:26:57 AM 08/11/2020

Waterflow Switch 1st Floor At Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

Tested 8:46:05 AM 08/11/2020

Waterflow Switch 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

Tested 8:47:48 AM 08/11/2020

Drain 1st Floor At Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

Tested 8:52:19 AM 08/11/2020

Drain 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

Tested 8:52:31 AM 08/11/2020

Backflow Prevention 1st Floor At Loading Dock Sprinkler Room Inspected 8:42:25 AM 08/11/2020 Control Valve 1st Floor At Loading Dock Sprinkler Room

Backflow #1 Tested 8:25:29 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Backflow #2

Tested 8:26:55 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

Tested 8:35:59 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

Tested 8:52:09 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

Tested 8:52:40 AM 08/11/2020

Waterflow Switch 1st Stair 1 Tested 8:41:52 AM 08/11/2020 Waterflow Switch 1st Stair 3 Tested 8:50:04 AM 08/11/2020 Waterflow Switch 2nd Stair 1 Tested 8:43:44 AM 08/11/2020 Waterflow Switch 2nd Stair 3 Tested 8:46:44 AM 08/11/2020 Fast Response Ground Sprinkler Loading dock sprinkler room Inspected 8:27:35 AM 08/11/2020 Fast Response Ground Sprinkler Loading dock sprinkler room Inspected 8:27:50 AM 08/11/2020 Sprinkler Box Ground Sprinkler Loading dock sprinkler room Inspected 8:27:53 AM 08/11/2020 Wrenches Ground Sprinkler Loading dock sprinkler room Inspected 8:27:31 AM 08/11/2020 Control Valve 1st Stair 1 Tested 8:41:30 AM 08/11/2020 Control Valve 1st Stair 4 Tested 9:02:50 AM 08/11/2020 Control Valve 2nd Stair 1 Tested 8:43:41 AM 08/11/2020 Inspector's Test 1st Stair 3 Inspected 8:50:11 AM 08/11/2020 Inspector's Test 2nd Stair 1 Inspected 8:43:52 AM 08/11/2020 Inspector's Test 2nd Stair 3 Inspected 8:46:50 AM 08/11/2020

Failed/Other Building- Dry Pipe

Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:35:05 AM 08/11/2020 Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:35:16 AM 08/11/2020 Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:35:32 AM 08/11/2020 Piping Ground Sprinkler Loading dock sprinkler room Inspected 8:34:51 AM 08/11/2020

Dry Pipe Dry Pipe Valve 1st Floor At Loading Dock Sprinkler Room Tested 8:33:29 AM 08/11/2020

Fire Pump

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Device Type Location Service Time Date Pump 1st Floor At Loading Dock Sprinkler Room Tested 8:26:39 AM 08/11/2020 Check Valve 1st Floor At Loading Dock Sprinkler Room

Bypass Inspected 8:32:13 AM 08/11/2020

Check Valve 1st Floor At Loading Dock Sprinkler Room Discharge

Inspected 8:32:28 AM 08/11/2020

Control Valve 1st Floor At Loading Dock Sprinkler Room Fire Pump Bypass #1

Tested 8:31:24 AM 08/11/2020

Building- Wet Pipe, Building- Fire Dep't Connection 1st Front Desk Front office drop off Inspected 8:38:48 AM 08/11/2020 Fire Pump Gauge Ground Sprinkler total of 2 Loading dock

sprinkler room Inspected 8:51:18 AM 08/11/2020

Check Valve 1st Front Desk Front office storage Inspected 8:28:59 AM 08/11/2020

Building- Wet Pipe Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:36:49 AM 08/11/2020 Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:37:37 AM 08/11/2020 Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:44:26 AM 08/11/2020 Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:44:42 AM 08/11/2020 Gauge Ground Sprinkler Loading dock sprinkler room Inspected 8:50:33 AM 08/11/2020 Piping Ground Sprinkler Loading dock sprinkler room Inspected 8:27:27 AM 08/11/2020 Check Valve 1st Stair 1 Inspected 8:41:46 AM 08/11/2020 Check Valve 1st Stair 3 Inspected 8:47:36 AM 08/11/2020 Check Valve 1st Stair 4 Inspected 9:02:11 AM 08/11/2020 Check Valve 2nd Stair 1 Inspected 8:43:32 AM 08/11/2020 Check Valve 2nd Stair 3 Inspected 8:46:42 AM 08/11/2020 Check Valve 2nd Stair 4 Inspected 8:53:44 AM 08/11/2020 Control Valve 1st Stair 3 Tested 8:49:21 AM 08/11/2020

Wet Pipe Alarm Valve 1st Floor At Loading Dock Sprinkler Room Zone

1 Classrooms/Zone 2 Gym Inspected 8:48:13 AM 08/11/2020

Check Valve 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

Inspected 8:51:49 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Esperanza Middle School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Senor 1 47298188

OS&Y Supervisory System Senor 1 47298190

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD30 30 3” 1 47298208

Vane System Sensor WFD30 30 3” 1 47298209

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Ready Riser F517 Trim Open Supervised 3" 47298215

Internal Date 06/20/2018

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Febco 870V 6" Double Check Fire Line 06/20/1999

ScanID Water Purveyor Location Meter Account # Serial Number 47298191 N/A 1st Floor At Loading Dock Sprinkler

Room N/A 99102311414

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Check Valve

Type Location Internal Date Size OK ScanID

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Grooved 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

06/20/2018 3" 47298216

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y AVK AWWAC509 1st Floor At

Loading Dock Sprinkler Room Backflow #1

6" Open Supervised 47298187

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y AVK AWWAC509 1st Floor At

Loading Dock Sprinkler Room Backflow #2

6" Open Supervised 47298189

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

3" Open Supervised 47298219

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Zone 5,6,7

3" Open Supervised 47298220

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly NIBCO As14 1st Floor At

Loading Dock Sprinkler Room Zone 5,6,7

4" Open Supervised 47298228

Description

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Isolation

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor At Loading Dock Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

1.25" 130 120 115 30 47298226

Previous Inspections

June 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor At Loading Dock

Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

1.25" 130 120 115 30 47298226

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor At Loading Dock

Sprinkler Room Zone 1 Classrooms/Zone 2 Gym

1.25" 130 120 115 30 47298226

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor At Loading Dock Sprinkler Room Zone 5,6,7

1.25" 130 120 115 30 47298227

Previous Inspections

June 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor At Loading Dock

Sprinkler Room Zone 5,6,7 1.25" 130 120 115 30 47298227

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor At Loading Dock

Sprinkler Room Zone 5,6,7 1.25" 130 120 115 30 47298227

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Building: Esperanza Middle School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor D1 30 3 1 47298249

Vane System Sensor w30 20 3 1 47298238

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged 1st Stair 1 06/20/2018 2.5" 47298230

Flanged 1st Stair 3 06/20/2018 2.5" 47298251

Flanged 1st Stair 4 06/20/2018 3" 47298235

Flanged 2nd Stair 1 06/20/2018 2.5" 47298256

Flanged 2nd Stair 3 06/20/2018 2.5" 47298247

Flanged 2nd Stair 4 06/20/2018 3" 47298232

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 202 2nd Stair 3 2.5" Open Supervised 47298246

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 202 2nd Stair 4 3" Open Supervised 47298233

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 212 1st Stair 3 2.5" Open Supervised 47298225

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID United N/A 78 N/A 47298236

Location 1st Stair 4

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

United N/A 78 N/A 47298234

Location 2nd Stair 4

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Potter VSR N/A N/A 47298809

Location 1st Floor Mechanical Room E108

Devices Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585475

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585470

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585471

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585472

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585474

Piping

Location Type Size Internal Date Ground Sprinkler Loading dock

Steel 1/2”-6” 06/20/2018

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

sprinkler room

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked N/A 47298180

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Building: Esperanza Middle School Building-, Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Fire Pump Gauge

Location Discharge psi Suction psi OK ScanID Ground Sprinkler total of 2 Loading dock sprinkler room

na na 47298179

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged 1st Front Desk Front office storage 06/20/2018 2.5" 47298177

Devices Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Front Desk Front office

drop off Wall Yes Yes 2.5" 47298178

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Esperanza Middle School

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Air Compressor

Location Mfr. Model # Phase On psi Off psi Serial No. 1st Floor At Loading Dock Sprinkler Room

General 8-140969-04

1 20 40 N/A

Type Description Rated Speed Horsepower Volts Amps OK ScanID Automatic Tankless 1725 .5 115 3.3 47298207

Alarms Pressure Switch

Type Description Manufacturer Low High Zone/Address OK ScanID Low Supervisory System Sensor 15 N/A 1 47298175

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Pressure Switch System Sensor EPS40-2 .5 1 47298174

Vane Potter VSR 4” 1 47298808

Components Dry Pipe Valve

Manufacturer Model # Location Internal Date OK ScanID Victaulic S/756 1st Floor At Loading Dock Sprinkler

Room 12/17/2018 47298214

Type Status Position Size Serial # Grooved Supervised Trim Open 2.5" N/A

Water psi Air Pressure Trip Air Trip Time Total Timing (sec)

Partial Trip Date Full Trip Date

100 35 12/17/2018 12/17/2018

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor At Loading Dock Sprinkler Room

2" 130 110 120 30 47298173

Previous Inspections

June 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Main 1st Floor At Loading Dock Sprinkler Room

2" 130 110 120 30 47298173

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor At Loading Dock

Sprinkler Room 2" 130 110 120 30 47298173

Fire & Life Safety America, Inc. - Baltimore 19 08/24/2020

Building: Esperanza Middle School Building-

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585478

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585477

Gauge

Location Service Date Ground Sprinkler Loading dock sprinkler room 06/20/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Victaulic N/A na na 1/4

” 45585476

Piping

Location Type Size Internal Date Ground Sprinkler Loading dock sprinkler room

Steel 1/2”-2 1/2” 06/20/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked N/A 45585479

Fire & Life Safety America, Inc. - Baltimore 20 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Esperanza Middle School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Firetrol FTA1350-AE30B 1st Floor At Loading Dock Sprinkler Room 06/20/1999 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 110 130 No No

Electrical Manufacturer Model # Location Serial Number ScanID US Electric Motors S750A 1st Floor At Loading Dock Sprinkler Room FF30-S1AS 47298196

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3520 10 208/230/460 83/72/36 30 3520

Controller Manufacturer Model # Location Install Date Serial Number Patterson Not Listed 1st Floor At Loading Dock Sprinkler Room 06/20/2018 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 120 130 No No

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Baldor 84.Z00009 1st Floor At Loading Dock Sprinkler

Room 06/20/1998 47298210

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 35N185-037361

Automatic 3450 208-230/460

5.9-5.6/2.8

120 130

Pump

Manufacturer Model Number Location Install Date Scan Number Patterson 5x3 MAC 1st Floor At Loading Dock Sprinkler Room 06/20/1999 47298204

Serial Number Type Orientation Aligned? Water Supply Impeller Size FP-C21705 Pump Primary Horizontal Yes Municipal 6.688

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/11/20 122 45 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature

Fire & Life Safety America, Inc. - Baltimore 21 08/24/2020

Other 08/11/20 103 33 501

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/11/20 82 25 756

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 80 0

70 500

62 750

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor At Loading Dock Sprinkler

Room N/A 1 47298193

Fire & Life Safety America, Inc. - Baltimore 22 08/24/2020

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Floor At Loading Dock Sprinkler Room 1 47298192

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor At Loading Dock Sprinkler

Room N/A 1 47297992

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298186

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor At Loading Dock Sprinkler

Room Bypass 06/20/2018 4" 47298008

Flanged 1st Floor At Loading Dock Sprinkler Room Discharge

06/20/2018 6" 47298211

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Kennedy KS2 1st Floor At

Loading Dock Sprinkler Room Fire Pump Suction

6" Open Supervised 47298185

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Fire Pump Bypass #2

4" Open Supervised 47298223

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Fire Pump Test Header

4" Closed Supervised 47298212

Description

Fire & Life Safety America, Inc. - Baltimore 23 08/24/2020

Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Fire Pump Discharge

4" Open Supervised 47298213

Description Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Dry System

4" Open Supervised 47298222

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-SCS 1st Floor At

Loading Dock Sprinkler Room Jockey Pump Suction

1" Open Supervised 47298176

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 693P 1st Floor At

Loading Dock Sprinkler Room Fire Pump Bypass #1

4" Closed Supervised 47298224

Description Isolation

Fire & Life Safety America, Inc. - Baltimore 24 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Esperanza Middle School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Tamper Switch Alarm 3.80% 3

Control Valve Valve 22.78% 18

Pump Pump 1.27% 1

Piping Sprinkler 2.53% 2

Wrenches Sprinkler 1.27% 1

Fast Response Sprinkler 2.53% 2

Sprinkler Box Sprinkler 1.27% 1

Check Valve Valve 12.66% 10

Electrical Driver Pump 1.27% 1

Dry Pipe Valve Valve 1.27% 1

Drain Device 3.80% 3

Pressure Switch Alarm 1.27% 1

Waterflow Switch Alarm 12.66% 10

Gauge Device 10.13% 8

Fire Dep't Connection Hose 1.27% 1

Backflow Prevention Valve 1.27% 1

Fire Pump Power Alarm 1.27% 1

Fire Pump Off Alarm 1.27% 1

Inspector's Test Valve 7.59% 6

Controller Pump 1.27% 1

Jockey Controller Pump 1.27% 1

Air Compressor Pump 1.27% 1

Jockey Pump Pump 1.27% 1

Alarm Valve Valve 1.27% 1

Fire Pump Gauge Pump 1.27% 1

Fire Pump Running Alarm 1.27% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Fast Response 1 2PK Pendant N/A 06/20/2018

Control Valve 2 202 Butterfly Isolation 06/20/2018

Control Valve 1 K212 Butterfly Isolation 06/20/2018

Waterflow Switch 4 w30 Vane Alarm 06/20/2018

Inspector's Test 3 N/A

06/20/2018

Sprinkler Box 1 N/A

06/20/2018

Fast Response 1 N/A Upright N/A 06/20/2018

Wrenches 1 N/A Sprinkler

06/20/2018

Fire Pump

Jockey Controller 1 Not Listed

06/20/2018

Wet Pipe, Building-

Fire & Life Safety America, Inc. - Baltimore 25 08/24/2020

Waterflow Switch 1 w30 Vane Alarm 06/20/2018

Building- Dry Pipe

Piping 1 N/A Steel

06/20/2018

Building- Wet Pipe

Check Valve 3 202 Flanged

06/20/2018

Check Valve 2 D1 Flanged

06/20/2018

Check Valve 1 k212 Flanged

06/20/2018

Control Valve 2 202 Butterfly Isolation 06/20/2018

Control Valve 1 212 Butterfly Isolation 06/20/2018

Waterflow Switch 1 D1 Vane Alarm 06/20/2018

Inspector's Test 2 N/A

06/20/2018

Piping 1 N/A Steel

06/20/2018

Building- Wet Pipe, Building-

Check Valve 1 202 Flanged

06/20/2018

Fire Dep't Connection 1 200 Wall

06/20/2018

Fire Pump Gauge 1 110 Discharge

06/20/2018

In Service - 15 Years to 25 Years

Fire Pump

Controller 1 FTA1350-AE30B

Automatic 06/20/1999

Control Valve 1 693P Butterfly Bypass 06/20/1999

Control Valve 1 693P Butterfly Discharge 06/20/1999

Control Valve 3 693P Butterfly Isolation 06/20/1999

Control Valve 1 KS2 OS&Y Suction 06/20/1999

Control Valve 1 BB-SCS Butterfly Suction 06/20/1999

Fire Pump Off 1 N/A

Supervisory 06/20/1999

Fire Pump Power 1 N/A

Supervisory 06/20/1999

Fire Pump Running 1 N/A

Supervisory 06/20/1999

Pump 1 5x3 MAC Pump Primary

06/20/1999

Tamper Switch 1 OSY2 OS&Y Supervisory 06/20/1999

Electrical Driver 1 S750A

06/20/1999

Wet Pipe

Control Valve 2 AWWAC509 OS&Y Main Control 06/20/1999

Backflow Prevention 1 870V Double Check

06/20/1999

Control Valve 2 693P Butterfly Isolation 06/20/1999

Control Valve 1 As14 Butterfly Isolation 06/20/1999

Drain 2 N/A Main

06/20/1999

Alarm Valve 1 F517 Grooved

06/20/1999

Check Valve 1 S380 Grooved

06/20/1999

Tamper Switch 2 OSY2 OS&Y Supervisory 06/20/1999

Waterflow Switch 2 WFD30 Vane Alarm 06/20/1999

Building- Dry Pipe

Gauge 3 N/A System Pressure

06/20/1999

Building- Wet Pipe

Gauge 5 N/A System Pressure

06/20/1999

Dry Pipe

Air Compressor 1 8-140969-04 Automatic Tankless 06/20/1998

Waterflow Switch 1 VSR Vane Alarm 06/20/1998

Drain 1 N/A Main

06/20/1998

Fire & Life Safety America, Inc. - Baltimore 26 08/24/2020

Pressure Switch 1 ESP40-1 Low Supervisory 06/20/1998

Waterflow Switch 1 EPS40-2 Pressure Switch Alarm 06/20/1998

Dry Pipe Valve 1 S/756 Grooved

06/20/1998

Fire Pump

Jockey Pump 1 84.Z00009 Automatic

06/20/1998

Check Valve 1 7800FP Grooved

06/20/1998

Check Valve 1 6-175 Flanged

06/20/1998

Wet Pipe, Building-

Inspector's Test 1 VSR

06/20/1998

Fire & Life Safety America, Inc. - Baltimore 27 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Esperanza Middle School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Building- Dry Pipe 1 Piping Ground Sprinkler Loading dock sprinkler room Special Note 45585479

Due for 3 year air test and 5 year internal inspection

Building- Wet Pipe 2 Control Valve 1st Stair 3 Special Note 47298225

Reports as a water flow alarm should report as a tamper supervisory.

Fire Pump 3 Control Valve 1st Floor At Loading Dock Sprinkler Room Fire

Pump Bypass #2 Passed 47298223

Both fire pump bypass control valves found in the closed position. Does not report to the control panel 4 Control Valve 1st Floor At Loading Dock Sprinkler Room Fire

Pump Bypass #1 Special Note 47298224

Both fire pump bypass control valves found in the closed position. Does not report to the control panel 5 Pump 1st Floor At Loading Dock Sprinkler Room Special Note 47298204

Needs a repacking the packing glands a shot . See attached pictures.

Sprinkler Inspection Certificate For

Evergreen Elementary School 43765 Evergreen Way California, Maryland 20619

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 11, 2020

Building: Evergreen Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Evergreen Elementary School Contact: Cathy Orolan

Address: 43765 Evergreen Way Phone: 301-475-4256

Address: Fax:

City/State/Zip: California, Maryland 20619 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 17 Fire Pump Building- Building- 3 Wet Pipe 15 Wet Pipe Building- 2

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 2 3.70% 2 100.00% 2 100.00% 0 0% Alarm 11 20.37% 11 100.00% 11 100.00% 0 0% Valve 27 50.00% 27 100.00% 19 70.37% 8 29.63% Hose 1 1.85% 1 100.00% 0 0% 1 100.00% Pump 8 14.81% 8 100.00% 8 100.00% 0 0% Sprinkler 5 9.26% 5 100.00% 4 80.00% 1 20.00%

Totals 54 100% 54 100.00

% 44 81.48% 10 18.52%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Evergreen Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 11, 2020 6:55:55 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Evergreen Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Check Valve 47298115 Room Mechanical Sprinkler Needs 5 Yr. Service NFPA25 13.4.2.1 47298131 Room B20 Custodial Needs 5 Yr. Service NFPA25 13.4.2.1 47298132 Room B20 Custodial Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 47298114 Room Mechanical Sprinkler Needs Hydro Test NFPA25 4.1.5.1

Piping 47298116 Room Mechanical Sprinkler Needs 5 Yr. Service NFPA25 14.2.1.1

Fire Pump Check Valve

47298120 1st Floor Sprinkler Room Bypass Needs 5 Yr. Service NFPA25 13.4.2.1

Wet Pipe Alarm Valve

47298092 1st Floor Sprinkler Room Alarm Valve Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 47298093 1st Floor Sprinkler Room Needs 5 Yr. Service NFPA25 13.4.2.1 47298085 1st Floor Sprinkler Room Needs 5 Yr. Service NFPA25 13.4.2.1

Building- Wet Pipe Check Valve

47298136 Room C20 Custodial Needs 5 Yr. Service NFPA25 13.4.2.1

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material. NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Evergreen Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Check Valve

47298115 Room Mechanical Sprinkler 5 Yr. Internal cvf1 T/M 47298131 Room B20 Custodial 5 Yr. Internal 08005 T/M 47298132 Room B20 Custodial 5 Yr. Internal 08005 T/M

Fire Dep't Connection

47298114 Room Mechanical Sprinkler Hydro Test N/A T/M

Piping

47298116 Room Mechanical Sprinkler 5 Yr. Internal N/A T/M

Fire Pump

Check Valve

47298120 1st Floor Sprinkler Room Bypass 5 Yr. Internal CV-1F T/M

Wet Pipe

Alarm Valve

47298092 1st Floor Sprinkler Room Alarm Valve 5 Yr. Internal AV-1 T/M

Check Valve

47298093 1st Floor Sprinkler Room 5 Yr. Internal CV-1F T/M 47298085 1st Floor Sprinkler Room 5 Yr. Internal CV-1F T/M

Building- Wet Pipe

Check Valve

47298136 Room C20 Custodial 5 Yr. Internal 08005 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Evergreen Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Building- Fire Pump, Building-

Gauge Room Mechanical Sprinkler Inspected 6:53:18 AM 08/11/2020 Fire Pump Gauge 2 total Room Mechanical Sprinkler Inspected 6:52:56 AM 08/11/2020 Fire Pump Gauge Room Mechanical Sprinkler Inspected 6:52:59 AM 08/11/2020

Fire Pump Fire Pump Off 1st Floor Sprinkler Room Tested 6:55:15 AM 08/11/2020 Fire Pump Power 1st Floor Sprinkler Room Tested 6:55:28 AM 08/11/2020 Fire Pump Running 1st Floor Sprinkler Room Tested 6:54:45 AM 08/11/2020 Tamper Switch 1st Floor Sprinkler Room Fire Pump Suction Tested 1:55:29 PM 08/10/2020 Controller 1st Floor Sprinkler Room Tested 1:57:37 PM 08/10/2020 Electrical Driver 1st Floor Sprinkler Room Inspected 1:55:40 PM 08/10/2020 Jockey Controller 1st Floor Sprinkler Room Tested 6:55:39 AM 08/11/2020 Jockey Pump 1st Floor Sprinkler Room Inspected 6:55:34 AM 08/11/2020 Pump 1st Floor Sprinkler Room Tested 1:55:36 PM 08/10/2020 Transfer Switch 1st Floor Sprinkler Room Tested 6:55:10 AM 08/11/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Suction Tested 1:55:25 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Jockey Pump Suction Tested 1:55:48 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Bypass #2 Tested 1:55:59 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Bypass #1 Tested 1:56:18 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Jockey Pump

Discharge Tested 1:56:25 PM 08/10/2020

Control Valve 1st Floor Sprinkler Room Fire Pump Test Header Tested 1:56:43 PM 08/10/2020

Building- Wet Pipe Waterflow Switch Room B20 Custodial Tested 2:00:54 PM 08/10/2020

Wet Pipe Tamper Switch 1st Floor Sprinkler Room Backflow #1 Tested 1:54:12 PM 08/10/2020 Tamper Switch 1st Floor Sprinkler Room Backflow #2 Tested 1:55:01 PM 08/10/2020 Waterflow Switch 1st Floor Sprinkler Room Alarm Valve Tested 1:57:21 PM 08/10/2020 Waterflow Switch 1st Floor Sprinkler Room Main Fire Service Tested 6:54:28 AM 08/11/2020 Drain 1st Floor Sprinkler Room Alarm Valve Tested 1:57:27 PM 08/10/2020 Backflow Prevention 1st Floor Sprinkler Room Inspected 1:54:57 PM 08/10/2020 Backflow Prevention 1st Floor Sprinkler Room Inspected 6:55:45 AM 08/11/2020 Control Valve 1st Floor Sprinkler Room Backflow #1 Tested 1:54:43 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Backflow #2 Tested 1:55:19 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Alarm Valve Tested 1:56:49 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Main Riser Tested 6:54:18 AM 08/11/2020 Inspector's Test 1st Floor Sprinkler Room Alarm Valve Inspected 6:53:36 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date

Waterflow Switch Room B20 Custodial Tested 2:00:33 PM 08/10/2020 Waterflow Switch Room C20 Custodial Tested 6:53:12 AM 08/11/2020 Fast Response Room Mechanical Sprinkler Inspected 2:11:19 PM 08/10/2020 Fast Response Room Mechanical Sprinkler Inspected 2:11:29 PM 08/10/2020 Sprinkler Box Room Mechanical Sprinkler Inspected 2:11:07 PM 08/10/2020 Wrenches Room Mechanical Sprinkler Inspected 2:11:34 PM 08/10/2020 Control Valve Room B20 Custodial Tested 1:59:11 PM 08/10/2020 Control Valve Room B20 Custodial Tested 2:01:16 PM 08/10/2020 Control Valve Room C20 Custodial Tested 2:03:36 PM 08/10/2020 Inspector's Test Room B20 Custodial Inspected 2:00:26 PM 08/10/2020 Inspector's Test Room B20 Custodial Inspected 2:02:07 PM 08/10/2020 Inspector's Test Room C20 Custodial Inspected 6:53:31 AM 08/11/2020

Failed/Other Fire Pump

Check Valve 1st Floor Sprinkler Room Bypass Inspected 1:56:10 PM 08/10/2020

Building- Wet Pipe Check Valve Room C20 Custodial Inspected 2:04:36 PM 08/10/2020

Wet Pipe Alarm Valve 1st Floor Sprinkler Room Alarm Valve Inspected 1:57:12 PM 08/10/2020 Check Valve 1st Floor Sprinkler Room Inspected 1:56:35 PM 08/10/2020 Check Valve 1st Floor Sprinkler Room Inspected 6:54:09 AM 08/11/2020

Fire Dep't Connection Room Mechanical Sprinkler Inspected 2:11:48 PM 08/10/2020 Piping Room Mechanical Sprinkler Inspected 2:17:27 PM 08/10/2020 Check Valve Room B20 Custodial Inspected 2:00:21 PM 08/10/2020 Check Valve Room B20 Custodial Inspected 2:01:39 PM 08/10/2020 Check Valve Room Mechanical Sprinkler Inspected 2:11:59 PM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Evergreen Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298105

OS&Y Supervisory System Sensor 1 47298101

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR 30 4” 1 47298083

Vane Potter VSR 30 4” 1 47298087

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Tyco AV-1 Open Supervised 4" 47298092

Internal Date 06/19/2018

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Watts 709 6” Double Check Fire Line 06/19/2008

ScanID Water Purveyor Location Meter Account # Serial Number 47298122 N/A 1st Floor Sprinkler Room N/A 142037

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Watts 007QT 0.5" Double Check Fire Line Bypass 06/19/2008

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

ScanID Water Purveyor Location Meter Account # Serial Number 47298154 N/A 1st Floor Sprinkler Room N/A 9623

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Sprinkler Room 06/19/2018 4" 47298093

Grooved 1st Floor Sprinkler Room 06/19/2018 4" 47298085

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Watts AWWA 1st Floor

Sprinkler Room Backflow #1

6" Open Supervised 47298104

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Watts AWWA 1st Floor

Sprinkler Room Backflow #2

6" Open Supervised 47298102

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7722-3A 1st Floor

Sprinkler Room Alarm Valve

4" Open Supervised 47298090

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7722-3A 1st Floor

Sprinkler 4" Open Supervised 47298086

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Room Main Riser

Description Main Control

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain AV-1 140 N/A 47298084

Location 1st Floor Sprinkler Room Alarm Valve

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Sprinkler Room Alarm Valve

2" 145 140 136 30 47298088

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room

Alarm Valve 2" 145 140 136 47298088

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room

Alarm Valve 2" 145 140 136 30 47298088

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Building: Evergreen Elementary School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD30 35 3 1 47298128

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged Room C20 Custodial 06/19/2018 2.5" 47298136

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Evergreen Elementary School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Joslyn Clark E9C154-5T 1st Floor Sprinkler Room 06/19/2008 308208

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 110 120 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID Weg 284JP 1st Floor Sprinkler Room 19JUN08 47298097

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3540 10 208-230/460 82.2-74.3/37.2 30 3540

Controller Manufacturer Model # Location Install Date Serial Number Joslyn Clark Not Listed 1st Floor Sprinkler Room 06/19/2008 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 120 135 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Bluffton 1303007150 1st Floor Sprinkler Room 06/19/2008 47298117

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 081-121063-1 Automatic 3450 208-230/

460 1.8/.9 120 135

Pump

Manufacturer Model Number Location Install Date Scan Number Aurora 4-383-9C 1st Floor Sprinkler Room 06/19/2008 47298098

Serial Number Type Orientation Aligned? Water Supply Impeller Size 08-1743607 Pump Primary Vertical Yes Municipal 6.938

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/10/20 124 37 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Other 08/10/20 105 30 501

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/10/20 84 25 756

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 88 0

75 500

60 750

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto 1st Floor Sprinkler Room N/A N/A 47298106

On psi Off psi AC Type Generator Batteries Run Period Timer N/A N/A Normal

Phase Yes No N/A

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room N/A 1 47298108

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room 1 47298109

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room N/A 1 47298103

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298100

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Sprinkler Room Bypass 06/19/2018 4" 47298120

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV 1st Floor

Sprinkler Room Fire Pump Suction

6" Open Supervised 47298099

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-SCS 1st Floor

Sprinkler Room Jockey Pump Suction

1" Open Supervised 47298121

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7722-3A 1st Floor

Sprinkler Room Bypass #2

4" Open Supervised 47298095

Description Main Control

Control Valve

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7722-3A 1st Floor

Sprinkler Room Bypass #1

4" Open Supervised 47298094

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-SCS 1st Floor

Sprinkler Room Jockey Pump Discharge

1" Open Supervised 47298089

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7722-3A 1st Floor

Sprinkler Room Fire Pump Test Header

4" Closed Supervised 47298091

Description Main Control

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Building: Evergreen Elementary School Building-, Building-

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Fire Pump Gauge

Location Discharge psi Suction psi OK ScanID 2 total Room Mechanical Sprinkler

na na 47298123

Room Mechanical Sprinkler na na 47298124

Devices Gauge

Location Service Date Room Mechanical Sprinkler 06/19/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Tyco 4 total 100 none 1/2 47298139

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Evergreen Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Tamper Switch Alarm 5.56% 3

Control Valve Valve 24.07% 13

Backflow Prevention Valve 3.70% 2

Pump Pump 1.85% 1

Electrical Driver Pump 1.85% 1

Check Valve Valve 12.96% 7

Alarm Valve Valve 1.85% 1

Waterflow Switch Alarm 9.26% 5

Drain Device 1.85% 1

Controller Pump 1.85% 1

Inspector's Test Valve 7.41% 4

Sprinkler Box Sprinkler 1.85% 1

Fast Response Sprinkler 3.70% 2

Wrenches Sprinkler 1.85% 1

Fire Dep't Connection Hose 1.85% 1

Piping Sprinkler 1.85% 1

Fire Pump Gauge Pump 3.70% 2

Gauge Device 1.85% 1

Fire Pump Running Alarm 1.85% 1

Transfer Switch Pump 1.85% 1

Fire Pump Off Alarm 1.85% 1

Fire Pump Power Alarm 1.85% 1

Jockey Pump Pump 1.85% 1

Jockey Controller Pump 1.85% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Control Valve 2 08005 Butterfly Isolation 06/19/2018

Control Valve 1 AS214 Butterfly Isolation 06/19/2018

Fire Dep't Connection 1 N/A Wall

06/19/2018

Check Valve 2 08005 Flanged

06/19/2018

Sprinkler Box 1 N/A

06/19/2018

Inspector's Test 1 N/A

06/19/2018

Inspector's Test 1 NA

06/19/2018

Waterflow Switch 2 wfd30 Vane Alarm 06/19/2018

Inspector's Test 1 N/A

06/19/2018

Check Valve 1 cvf1 Flanged

06/19/2018

Fast Response 1 3131 Pendant N/A 06/19/2018

Fast Response 1 3131 Upright N/A 06/19/2018

Wrenches 1 N/A Sprinkler

06/19/2018

Piping 1 N/A Steel

06/19/2018

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Building- Fire Pump, Building-

Fire Pump Gauge 1 N/A Suction

06/19/2018

Gauge 1 4 total System Pressure

06/19/2018

Building- Wet Pipe

Check Valve 1 08005 Flanged

06/19/2018

Waterflow Switch 1 WFD30 Vane Alarm 06/19/2018

In Service - 10 Years to 15 Years

Fire Pump

Control Valve 3 AE7722-3A Butterfly Main Control 06/19/2008

Pump 1 4-383-9C Pump Primary

06/19/2008

Jockey Pump 1 1303007150 Automatic

06/19/2008

Controller 1 E9C154-5T

Automatic 06/19/2008

Jockey Controller 1 Not Listed

06/19/2008

Transfer Switch 1 E9C154-5T Auto

06/19/2008

Control Valve 2 BB-SCS Butterfly Main Control 06/19/2008

Control Valve 1 RWGV OS&Y Main Control 06/19/2008

Fire Pump Off 1 N/A

Supervisory 06/19/2008

Fire Pump Power 1 N/A

Supervisory 06/19/2008

Fire Pump Running 1 N/A

Supervisory 06/19/2008

Tamper Switch 1 OSY2 OS&Y Supervisory 06/19/2008

Check Valve 1 CV-1F Grooved

06/19/2008

Electrical Driver 1 284JP

06/19/2008

Wet Pipe

Control Valve 1 AE7722-3A Butterfly Isolation 06/19/2008

Control Valve 1 AE7722-3A Butterfly Main Control 06/19/2008

Waterflow Switch 2 VSR Vane Alarm 06/19/2008

Drain 1 wog Main

06/19/2008

Tamper Switch 2 OSY2 OS&Y Supervisory 06/19/2008

Inspector's Test 1 AV-1

06/19/2008

Check Valve 2 CV-1F Grooved

06/19/2008

Alarm Valve 1 AV-1 Grooved

06/19/2008

Backflow Prevention 1 007QT Double Check

06/19/2008

Backflow Prevention 1 709 Double Check

06/19/2008

Control Valve 2 AWWA OS&Y Main Control 06/19/2008

In Service - 15 Years to 25 Years

Building- Fire Pump, Building-

Fire Pump Gauge 1 N/A Discharge

06/19/2005

Sprinkler Inspection Certificate For

George Washington Carver Elementary School

46155 Carver School Boulevard Great Mills, Maryland 20634

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 10, 2020

Building: George Washington Carver Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: George Washington Carver Elementary School

Contact: Cathy Orolan

Address: 46155 Carver School Boulevard Phone: 301-475-4256

Address: Fax:

City/State/Zip: Great Mills, Maryland 20634 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Wet Pipe 5 Wet Pipe Backflow #1 2 Wet Pipe Backflow #2 2 Wet Pipe FDC 1 Wet Pipe Zone #1 Riser 6 Wet Pipe Zone #2 Riser 6 Wet Pipe Zone 1&2 Risers 1

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 3 13.04% 3 100.00% 2 66.67% 1 33.33% Alarm 4 17.39% 4 100.00% 4 100.00% 0 0% Valve 10 43.48% 10 100.00% 7 70.00% 3 30.00% Hose 1 4.35% 1 100.00% 0 0% 1 100.00% Sprinkler 5 21.74% 5 100.00% 3 60.00% 2 40.00%

Totals 23 100% 23 100.00

% 16 69.57% 7 30.43%

Certification Company: Fire & Life Safety America, Inc. - Baltimore

Building: George Washington Carver Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 11, 2020 6:51:21 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: George Washington Carver Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Wet Pipe Fire Dep't Connection

47297937 1st Floor At Building Main Entrance Needs Hydro Test NFPA25 4.1.5.1

Wet Pipe, FDC Check Valve

47297943 1st Floor Classroom #1 FDC Needs 5 Yr. Service NFPA25 13.4.2.1

Wet Pipe, Zone #1 Riser Piping

47297942 1st Floor Zone #1 Riser Needs 5 Yr. Service NFPA25 14.2.1.1

Wet Pipe, Zone #2 Riser Alarm Valve

47297953 1st Floor Sprinkler Room Zone #2 Riser Needs 5 Yr. Service NFPA25 13.4.1.2

Control Valve 47297928 1st Floor Sprinkler Room Zone #2 Riser Leaking NFPA25 13.3.2.2 (5)

Piping 47297941 1st Floor Zone #2 Riser Needs 5 Yr. Service NFPA25 14.2.1.1

Wet Pipe, Zone 1&2 Risers Gauge

47297936 1st Floor Sprinkler Room (6) Water all but 2 have no isolation valves

Date Expired NFPA25 13.2.7.2

Code References NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material. NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.3.2.2 (5) The valve inspection shall verify that the valves are in the following condition: Free from external leaks

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

ScanID Location Problem Reference

NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: George Washington Carver Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Wet Pipe

Fire Dep't Connection

47297937 1st Floor At Building Main Entrance Hydro Test N/A T/M

Wet Pipe, FDC

Check Valve

47297943 1st Floor Classroom #1 FDC 5 Yr. Internal F-1 T/M

Wet Pipe, Zone #1 Riser

Piping

47297942 1st Floor Zone #1 Riser 5 Yr. Internal N/A T/M

Wet Pipe, Zone #2 Riser

Alarm Valve

47297953 1st Floor Sprinkler Room Zone #2 Riser 5 Yr. Internal F-1 T/M

Control Valve

47297928 1st Floor Sprinkler Room Zone #2 Riser Replace 0833 T/M

Piping

47297941 1st Floor Zone #2 Riser 5 Yr. Internal N/A T/M

Wet Pipe, Zone 1&2 Risers

Gauge

47297936 1st Floor Sprinkler Room (6) Water all but 2 have no isolation valves

Replace N/A T/M

PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: George Washington Carver Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Wet Pipe, Backflow #1

Tamper Switch 1st Floor Sprinkler Room Backflow #1 Tested 11:08:58 AM 08/10/2020 Control Valve 1st Floor Sprinkler Room Backflow #1 Tested 11:08:53 AM 08/10/2020

Wet Pipe, Backflow #2 Tamper Switch 1st Floor Sprinkler Room Backflow #2 Tested 11:09:18 AM 08/10/2020 Control Valve 1st Floor Sprinkler Room Backflow #2 Tested 11:09:33 AM 08/10/2020

Wet Pipe, Zone #1 Riser Waterflow Switch 1st Floor Sprinkler Room Zone #1 Riser Tested 11:10:39 AM 08/10/2020 Drain 1st Floor Sprinkler Room Zone #1 Riser Tested 11:17:55 AM 08/10/2020 Alarm Valve 1st Floor Sprinkler Room Zone #1 Riser Inspected 11:10:35 AM 08/10/2020 Control Valve 1st Floor Sprinkler Room Zone #1 Riser Tested 11:09:48 AM 08/10/2020 Inspector's Test 1st Floor Sprinkler Room Zone #1 Riser Inspected 11:16:31 AM 08/10/2020

Wet Pipe, Zone #2 Riser Waterflow Switch 1st Floor Sprinkler Room Zone #2 Riser Tested 11:10:48 AM 08/10/2020 Drain 1st Floor Sprinkler Room Zone #2 Riser Tested 11:17:40 AM 08/10/2020 Inspector's Test 1st Floor Sprinkler Room Zone #2 Riser Inspected 11:17:25 AM 08/10/2020

Wet Pipe Sprinkler Box 1st Floor Sprinkler Room Inspected 11:11:14 AM 08/10/2020 Sprinkler Box Spares 1st Floor Sprinkler Room Inspected 11:11:23 AM 08/10/2020 Sprinkler Box Spares 1st Floor Sprinkler Room Inspected 11:18:06 AM 08/10/2020 Backflow Prevention 1st Floor Sprinkler Room Inspected 11:09:08 AM 08/10/2020

Failed/Other Wet Pipe, FDC

Check Valve 1st Floor Classroom #1 FDC Inspected 11:14:59 AM 08/10/2020

Wet Pipe, Zone #1 Riser Piping 1st Floor Zone #1 Riser Inspected 11:14:16 AM 08/10/2020

Wet Pipe, Zone #2 Riser Piping 1st Floor Zone #2 Riser Inspected 11:13:55 AM 08/10/2020 Alarm Valve 1st Floor Sprinkler Room Zone #2 Riser Inspected 11:10:27 AM 08/10/2020 Control Valve 1st Floor Sprinkler Room Zone #2 Riser Tested 11:16:17 AM 08/10/2020

Wet Pipe, Zone 1&2 Risers Gauge 1st Floor Sprinkler Room (6) Water all but 2

have no isolation valves Inspected 11:18:15 AM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Device Type Location Service Time Date Wet Pipe

Fire Dep't Connection 1st Floor At Building Main Entrance Inspected 11:15:38 AM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: George Washington Carver Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Willins 350A 6" Double Check Fire Line 06/18/2005

ScanID Water Purveyor Location Meter Account # Serial Number 47297955 N/A 1st Floor Sprinkler Room N/A 03705

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Devices Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Floor At Building Main

Entrance Wall Yes Yes 2.5" 47297937

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

5 No No 6 unit N/A 1st Floor Sprinkler Room

47297933

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 4 Pendant Viking 1st Floor Sprinkler Room 47297934

Temperature KFactor Size Finish Response Time 156 5.6 1/2” Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

4 Concealed Pendant Viking 1st Floor Sprinkler Room 47297935

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Brass Fast Response

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Building: George Washington Carver Elementary School Backflow #1

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID Lever Supervisory Potter 1 47297909

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Clow 2838 1st Floor

Sprinkler Room Backflow #1

6" Open Supervised 47297908

Description Main Control

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Building: George Washington Carver Elementary School Backflow #2

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID Lever Supervisory Potter 1 47297927

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Clow 2838 1st Floor

Sprinkler Room Backflow #2

6" Open Supervised 47297900

Description Main Control

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Building: George Washington Carver Elementary School FDC

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Classroom #1 FDC 06/18/2018 4" 47297943

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Building: George Washington Carver Elementary School Zone #1 Riser

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR-F 30 4” 1 47297952

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Viking F-1 Trim Open Supervised 4" 47297954

Internal Date 06/18/2018

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 0833 1st Floor

Sprinkler Room Zone #1 Riser

4" Open Supervised 47297951

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain N/A 60 N/A 35 47297929

Location 1st Floor Sprinkler Room Zone #1 Riser

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Sprinkler Room Zone #1 Riser

2" 65 55 50 30 47297932

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room Zone

#1 Riser 2" 65 55 50 30 47297932

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Main 1st Floor Sprinkler Room Zone #1 Riser

2" 65 55 50 38 47297932

Piping

Location Type Size Internal Date 1st Floor Zone #1 Riser

Steel 1”-4” 06/18/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47297942

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Building: George Washington Carver Elementary School Zone #2 Riser

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR-F 30 4” 1 47297956

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Viking F-1 Trim Open Supervised 4" 47297953

Internal Date 06/18/2018

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 0833 1st Floor

Sprinkler Room Zone #2 Riser

4" Open Supervised 47297928

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain N/A 60 N/A 39 47297930

Location 1st Floor Sprinkler Room Zone #2 Riser

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Sprinkler Room Zone #2 Riser

2" 65 60 50 30 47297931

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room Zone

#2 Riser 2" 65 60 50 30 47297931

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Main 1st Floor Sprinkler Room Zone #2 Riser

2" 65 60 50 35 47297931

Piping

Location Type Size Internal Date 1st Floor Zone #2 Riser

Steel 1”-4” 06/18/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47297941

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Building: George Washington Carver Elementary School Zone 1&2 Risers

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Gauge

Location Service Date 1st Floor Sprinkler Room (6) Water all but 2 have no isolation valves

06/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 60 None 1/4 47297936

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: George Washington Carver Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Control Valve Valve 17.39% 4

Tamper Switch Alarm 8.70% 2

Backflow Prevention Valve 4.35% 1

Alarm Valve Valve 8.70% 2

Waterflow Switch Alarm 8.70% 2

Sprinkler Box Sprinkler 4.35% 1

Sprinkler Box Spares Sprinkler 8.70% 2

Piping Sprinkler 8.70% 2

Check Valve Valve 4.35% 1

Fire Dep't Connection Hose 4.35% 1

Inspector's Test Valve 8.70% 2

Drain Device 8.70% 2

Gauge Device 4.35% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Wet Pipe, Backflow #1

Control Valve 1 2838 Gate Main Control 06/18/2018

Tamper Switch 1 OSYSU-2 Lever Supervisory 06/18/2018

Wet Pipe, Backflow #2

Control Valve 1 2838 Gate Main Control 06/18/2018

Tamper Switch 1 OSYSU-2 Lever Supervisory 06/18/2018

In Service - 15 Years to 25 Years

Wet Pipe

Sprinkler Box 1 N/A

06/18/2005

Fire Dep't Connection 1 N/A Wall

06/18/2005

Sprinkler Box Spares 1 M06 Pendant

06/18/2005

Sprinkler Box Spares 1 V3802 Concealed Pendant

06/18/2005

Backflow Prevention 1 350A Double Check

06/18/2005

Wet Pipe, FDC

Check Valve 1 F-1 Grooved

06/18/2005

Wet Pipe, Zone #1 Riser

Control Valve 1 0833 Butterfly Isolation 06/18/2005

Piping 1 N/A Steel

06/18/2005

Waterflow Switch 1 VSR-F Vane Alarm 06/18/2005

Inspector's Test 1 N/A

06/18/2005

Drain 1 N/A Main

06/18/2005

Fire & Life Safety America, Inc. - Baltimore 19 08/24/2020

Alarm Valve 1 F-1 Grooved

06/18/2005

Wet Pipe, Zone #2 Riser

Control Valve 1 0833 Butterfly Isolation 06/18/2005

Piping 1 N/A Steel

06/18/2005

Waterflow Switch 1 VSR-F Vane Alarm 06/18/2005

Inspector's Test 1 N/A

06/18/2005

Drain 1 Randleman Main

06/18/2005

Alarm Valve 1 F-1 Grooved

06/18/2005

Wet Pipe, Zone 1&2 Risers

Gauge 1 N/A System Pressure

06/18/2005

Sprinkler Inspection Certificate For

Green Holly Elementary School 46060 Millstone Lansing Road Lexington Park, Maryland 20653

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 10, 2020

Building: Green Holly Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Green Holly Elementary School Contact: Cathy Orolan

Address: 46060 Millstone Lansing Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Lexington Park, Maryland 20653 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 18 Wet Pipe 8 Wet Pipe Building- 3

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 2 5.56% 2 100.00% 0 0% 2 100.00% Alarm 7 19.44% 7 100.00% 6 85.71% 1 14.29% Valve 15 41.67% 15 100.00% 12 80.00% 3 20.00% Hose 1 2.78% 1 100.00% 0 0% 1 100.00% Pump 5 13.89% 5 100.00% 5 100.00% 0 0% Sprinkler 6 16.67% 6 100.00% 5 83.33% 1 16.67%

Totals 36 100% 36 100.00

% 28 77.78% 8 22.22%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Green Holly Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 11, 2020 6:50:56 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Green Holly Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Gauge 47298075 total of 3 Sprinkler Mechanical Pump and wet

system Date Expired NFPA25 13.2.7.2

Piping 47298096 Sprinkler Mechanical Pump and wet system Special Note NFPA25 4.1.5.1

Fire Pump Check Valve

47298076 1st Floor Sprinkler Room Bypass Needs 5 Yr. Service NFPA25 13.4.2.1

Tamper Switch 47298065 1st Floor Sprinkler Room Fire Pump Suction Special Note NFPA25 4.1.5.1

Wet Pipe Drain

47298057 1st Floor Sprinkler Room @ Fire Pump Damaged/Worn NFPA25 4.1.5.1

Wet Pipe, Building- Check Valve

47298047 Sprinkler Mechanical FDC check Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 47298046 Sprinkler Mechanical Outside door Needs 5 Yr. Service

Inspector's Test 47298080 Sprinkler Room Room 29 ceiling Leaking NFPA25 4.1.5.1

Code References NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 4.1.5.1 The property owner or occupant shall promptly correct or repair deficiencies, damaged parts, or

impairments found while performing the inspection, test, and maintenance requirements of this standard.

NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move freely, and are in good condition.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Green Holly Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Gauge

47298075 total of 3 Sprinkler Mechanical Pump and wet system

Replace 1 system gauge and

T/M

Piping

47298096 Sprinkler Mechanical Pump and wet system Correct Unknown T/M

Fire Pump

Check Valve

47298076 1st Floor Sprinkler Room Bypass 5 Yr. Internal N/A T/M

Tamper Switch

47298065 1st Floor Sprinkler Room Fire Pump Suction Correct OSYSU-2 T/M

Wet Pipe

Drain

47298057 1st Floor Sprinkler Room @ Fire Pump Replace Test and Drain T/M

Wet Pipe, Building-

Check Valve

47298047 Sprinkler Mechanical FDC check 5 Yr. Internal 909 T/M

Fire Dep't Connection

47298046 Sprinkler Mechanical Outside door Hydro Test WP175 T/M

Inspector's Test

47298080 Sprinkler Room Room 29 ceiling Investigate test and drain T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Green Holly Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump

Fire Pump Off 1st Floor Sprinkler Room Tested 1:16:38 PM 08/10/2020 Fire Pump Power 1st Floor Sprinkler Room Tested 1:16:04 PM 08/10/2020 Fire Pump Running 1st Floor Sprinkler Room Tested 1:13:00 PM 08/10/2020 Controller 1st Floor Sprinkler Room Tested 1:12:54 PM 08/10/2020 Electrical Driver 1st Floor Sprinkler Room Inspected 1:12:32 PM 08/10/2020 Jockey Controller 1st Floor Sprinkler Room Tested 1:16:11 PM 08/10/2020 Jockey Pump 1st Floor Sprinkler Room Inspected 1:16:33 PM 08/10/2020 Pump 1st Floor Sprinkler Room Tested 1:12:42 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Bypass #2 Tested 1:06:52 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Discharge Tested 1:13:05 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Test Header Tested 1:13:17 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Suction Tested 1:13:58 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Bypass #1 Tested 1:15:21 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Jockey Pump

Discharge Tested 1:16:45 PM 08/10/2020

Control Valve 1st Floor Sprinkler Room Jockey Pump Suction Tested 1:16:57 PM 08/10/2020 Pressure Regulating 1st Floor Sprinkler Room Inspected 1:17:15 PM 08/10/2020

Wet Pipe Tamper Switch 1st Floor Sprinkler Room Backflow #2 Tested 1:15:38 PM 08/10/2020 Tamper Switch 1st Floor Sprinkler Room Backflow #1 Tested 1:15:52 PM 08/10/2020 Waterflow Switch 1st Floor Sprinkler Room Main Fire Service Tested 1:13:27 PM 08/10/2020 Standard Response Sprinkler Mechanical Inspected 1:12:26 PM 08/10/2020 Backflow Prevention 1st Floor Sprinkler Room Inspected 1:15:45 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Backflow #1 Tested 1:07:04 PM 08/10/2020 Control Valve 1st Floor Sprinkler Room Backflow #2 Tested 1:13:33 PM 08/10/2020

Sprinkler Box Sprinkler Mechanical Inspected 1:10:55 PM 08/10/2020 Standard Response Mechanical Sprinkler Inspected 1:09:31 PM 08/10/2020 Standard Response Sprinkler Mechanical Inspected 1:09:47 PM 08/10/2020 Wrenches Sprinkler Mechanical Inspected 1:10:31 PM 08/10/2020 Post Indicator Valve Sprinkler Mechanical Loading dock Inspected 1:11:28 PM 08/10/2020

Failed/Other Fire Pump

Tamper Switch 1st Floor Sprinkler Room Fire Pump Suction Tested 1:15:02 PM 08/10/2020 Check Valve 1st Floor Sprinkler Room Bypass Inspected 1:16:28 PM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Wet Pipe, Building-

Fire Dep't Connection Sprinkler Mechanical Outside door Inspected 1:10:26 PM 08/10/2020 Check Valve Sprinkler Mechanical FDC check Inspected 1:10:51 PM 08/10/2020 Inspector's Test Sprinkler Room Room 29 ceiling Inspected 1:12:15 PM 08/10/2020

Wet Pipe Drain 1st Floor Sprinkler Room @ Fire Pump Tested 12:57:22 PM 08/10/2020

Gauge total of 3 Sprinkler Mechanical Pump and wet

system Inspected 1:11:18 PM 08/10/2020

Piping Sprinkler Mechanical Pump and wet system Inspected 1:02:09 PM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Green Holly Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298067

OS&Y Supervisory Potter 1 47298069

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Pottee VSR 6” 1 47298060

Components Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Not Legible Not Legible 6" Double Check Fire Line 06/19/1989

ScanID Water Purveyor Location Meter Account # Serial Number 47298068 N/A 1st Floor Sprinkler Room N/A Not Legible

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller B 1st Floor

Sprinkler Room Backflow #1

6" Open Supervised 47298062

Description Main Control

Control Valve

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller B 1st Floor

Sprinkler Room Backflow #2

6" Open Supervised 47298063

Description Main Control

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Sprinkler Room @ Fire Pump

2" 50 50 40 30 47298057

Previous Inspections

June 11, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room @

Fire Pump 2" 50 50 40 30 47298057

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room @

Fire Pump 2" 50 50 40 30 47298057

Standard Response

Qty Type Size KFactor Finish Temperature OK ScanID 2 Concealed Pendant .5 5.6 Brass 165 53738021

Location Description Application Orientation Sprinkler Mechanical N/A na na

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Building: Green Holly Elementary School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged Sprinkler Mechanical FDC check 06/19/2018 4" 47298047

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID United N/A test and

drain 150 N/A 47298080

Location Sprinkler Room Room 29 ceiling

Devices Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID Sprinkler Mechanical Outside

door Wall No Yes 2.5" 47298046

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Green Holly Elementary School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Firetrol FTA1000-AA60B 1st Floor Sprinkler Room 06/19/1989 N/A

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 90 100 Yes No

Electrical Manufacturer Model # Location Serial Number ScanID General Electric 5K326AL115D1 1st Floor Sprinkler Room 60BC03U 47298048

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3555 10 230/460 137.8/68.9 60 3555

Controller Manufacturer Model # Location Install Date Serial Number Cutler Hammer Unknown 1st Floor Sprinkler Room 06/19/2018 Unknown

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 100 110 No No

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number General Electric Not Legible 1st Floor Sprinkler Room 06/19/1989 47298077

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi Not Legible Automatic Not Legible Not

Legible Not Legible

100 110

Pump

Manufacturer Model Number Location Install Date Scan Number Peerless Pump 5AEF8G 1st Floor Sprinkler Room 06/19/1989 47298049

Serial Number Type Orientation Aligned? Water Supply Impeller Size 453795 Pump Primary Horizontal N/A N/A 6.99

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/10/20 124 42 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Other 08/10/20 102 30 1000

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/10/20 68 15 1512

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 83 0

70 1000

52.4 1500

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room N/A 1 47298078

Fire Pump Power

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Description Location Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room 1 47298070

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Sprinkler Room N/A 1 47298056

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298065

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Sprinkler Room Bypass 06/19/2018 4" 47298076

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller DI 1st Floor

Sprinkler Room Fire Pump Bypass #2

4" Open Supervised 47298061

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller DI 1st Floor

Sprinkler Room Fire Pump Discharge

6" N/A N/A 47298058

Description Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller DI 1st Floor

Sprinkler Room Fire Pump Test Header

6" N/A N/A 47298059

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller B 1st Floor

Sprinkler Room Fire

6" Open Supervised 47298064

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Pump Suction

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller DI 1st Floor

Sprinkler Room Fire Pump Bypass #1

4" N/A N/A 47298066

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Nibco 175 1st Floor

Sprinkler Room Jockey Pump Discharge

1" N/A N/A 47298081

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Nibco 175 1st Floor

Sprinkler Room Jockey Pump Suction

1" N/A N/A 47298082

Description Suction

Pressure Regulating

Type Description Status Position Inlet psi Outlet psi Size OK ScanID Reducing Field Adjustable N/A N/A N/A N/A 0.75" 47298107

Location 5-Year Service Date 1st Floor Sprinkler Room 07/18/2018

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Green Holly Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Drain Device 2.78% 1

Piping Sprinkler 2.78% 1

Control Valve Valve 25.00% 9

Standard Response Sprinkler 8.33% 3

Fire Dep't Connection Hose 2.78% 1

Wrenches Sprinkler 2.78% 1

Check Valve Valve 5.56% 2

Sprinkler Box Sprinkler 2.78% 1

Gauge Device 2.78% 1

Post Indicator Valve Valve 2.78% 1

Inspector's Test Valve 2.78% 1

Electrical Driver Pump 2.78% 1

Pump Pump 2.78% 1

Controller Pump 2.78% 1

Fire Pump Running Alarm 2.78% 1

Waterflow Switch Alarm 2.78% 1

Tamper Switch Alarm 8.33% 3

Backflow Prevention Valve 2.78% 1

Fire Pump Power Alarm 2.78% 1

Jockey Controller Pump 2.78% 1

Jockey Pump Pump 2.78% 1

Fire Pump Off Alarm 2.78% 1

Pressure Regulating Valve 2.78% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Post Indicator Valve 1 2925 Ground

06/19/2018

Gauge 1 1 system gauge and

System Pressure

06/19/2018

Sprinkler Box 1 1

06/19/2018

Standard Response 1 458L Upright N/A 06/19/2018

Standard Response 1 F98 Upright N/A 06/19/2018

Wrenches 1 N/A Sprinkler

06/19/2018

Piping 1 Unknown Steel

06/19/2018

Fire Pump

Jockey Controller 1 Unknown

06/19/2018

Wet Pipe

Standard Response 1 F976 Concealed Pendant N/A 06/19/2018

Wet Pipe, Building-

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Fire Dep't Connection 1 WP175 Wall

06/19/2018

Inspector's Test 1 test and drain

06/19/2018

Check Valve 1 909 Flanged

06/19/2018

In Service - 25 Years or Older

Fire Pump

Pressure Regulating 1 55L Reducing Field Adjustable 06/19/1989

Controller 1 FTA1000-AA60B

Automatic 06/19/1989

Electrical Driver 1 5K326AL115D1

06/19/1989

Jockey Pump 1 Not Legible Automatic

06/19/1989

Control Valve 1 B OS&Y Suction 06/19/1989

Control Valve 2 DI Butterfly Bypass 06/19/1989

Control Valve 1 DI Butterfly Discharge 06/19/1989

Control Valve 1 DI Butterfly Isolation 06/19/1989

Fire Pump Off 1 N/A

Supervisory 06/19/1989

Fire Pump Power 1 N/A

Supervisory 06/19/1989

Fire Pump Running 1 N/A

Supervisory 06/19/1989

Control Valve 2 175 Gate Suction 06/19/1989

Pump 1 5AEF8G Pump Primary

06/19/1989

Tamper Switch 1 OSYSU-2 OS&Y Supervisory 06/19/1989

Check Valve 1 N/A Grooved

06/19/1989

Wet Pipe

Control Valve 2 B OS&Y Main Control 06/19/1989

Backflow Prevention 1 Not Legible Double Check

06/19/1989

Waterflow Switch 1 VSR Vane Alarm 06/19/1989

Tamper Switch 2 OSYSU-2 OS&Y Supervisory 06/19/1989

Drain 1 Test and Drain Main

06/19/1989

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Green Holly Elementary School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Fire Pump 1 Tamper Switch 1st Floor Sprinkler Room Fire Pump Suction Special Note 47298065

Tamper switch did not report to the panel. Attempted to adjust but did not clear from panel. Recommend replacing.

Wet Pipe, Building- 2 Inspector's Test Sprinkler Room Room 29 ceiling Leaking 47298080

Inspectors test was leaking needs repairs.

Wet Pipe 3 Drain 1st Floor Sprinkler Room @ Fire Pump Damaged/Worn 47298057

Handle is broken. 4 Piping Sprinkler Mechanical Pump and wet system Special Note 47298096

1” inspectors test is leaking at threads recommend replacing

Sprinkler Inspection Certificate For

Greenview Knolls Elementary School

45711 Military Lane Great Mills, Maryland 20734

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 11, 2020

Building: Greenview Knolls Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Greenview Knolls Elementary School Contact: Cathy Orolan

Address: 45711 Military Lane Phone: 301-475-4256

Address: Fax:

City/State/Zip: Great Mills, Maryland 20734 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Wet Pipe 18

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 3 16.67% 3 100.00% 3 100.00% 0 0% Alarm 3 16.67% 3 100.00% 2 66.67% 1 33.33% Valve 6 33.33% 6 100.00% 2 33.33% 4 66.67% Hose 1 5.56% 1 100.00% 0 0% 1 100.00% Sprinkler 5 27.78% 5 100.00% 4 80.00% 1 20.00%

Totals 18 100% 18 100.00

% 11 61.11% 7 38.89%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Greenview Knolls Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:57:28 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Greenview Knolls Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Wet Pipe Alarm Valve

47298026 1st Mechanical Sprinkler Mechanical suite Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 47298034 1st Storeroom Front Desk FDC Needs 5 Yr. Service NFPA25 13.4.2.1 47298052 1st Mechanical Sprinkler Mechanical suite Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 47298053 1st Mechanical Sprinkler Mechanical suite Special Note NFPA25 4.1.5.1

Fire Dep't Connection 47298040 1st Front Desk Entrance Needs Hydro Test NFPA25 4.1.5.1

Piping 47298037 1st Mechanical Sprinkler Needs 5 Yr. Service NFPA25 14.2.1.1

Tamper Switch 47298051 1st Mechanical Sprinkler Mechanical suite Special Note NFPA25 4.1.5.1

Code References NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Greenview Knolls Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Wet Pipe

Alarm Valve

47298026 1st Mechanical Sprinkler Mechanical suite 5 Yr. Internal B T/M

Check Valve

47298034 1st Storeroom Front Desk FDC 5 Yr. Internal 1078 T/M 47298052 1st Mechanical Sprinkler Mechanical suite 5 Yr. Internal CV-B T/M

Control Valve

47298053 1st Mechanical Sprinkler Mechanical suite Correct 765 T/M

Fire Dep't Connection

47298040 1st Front Desk Entrance Hydro Test 100 T/M

Piping

47298037 1st Mechanical Sprinkler 5 Yr. Internal 3115 T/M

Tamper Switch

47298051 1st Mechanical Sprinkler Mechanical suite Correct OSYSUA2 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Greenview Knolls Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Wet Pipe

Waterflow Switch 1st Mechanical Sprinkler Mechanical suite Tested 9:19:20 AM 08/11/2020 Waterflow Switch 1st Mechanical Sprinkler Mechanical suite Tested 9:19:24 AM 08/11/2020 Drain 1st Mechanical Sprinkler Zone2 Tested 9:17:21 AM 08/11/2020 Drain 1st Mechanical Sprinkler Zone1 Tested 9:22:03 AM 08/11/2020 Gauge 1st Mechanical Sprinkler 3 Water all with

isolation valves Inspected 9:23:25 AM 08/11/2020

Fast Response 1st Mechanical Sprinkler Inspected 9:22:59 AM 08/11/2020 Sprinkler Box 1st Mechanical Sprinkler Inspected 9:19:29 AM 08/11/2020 Standard Response 1st Mechanical Sprinkler Inspected 9:19:41 AM 08/11/2020 Wrenches 1st Mechanical Sprinkler Inspected 9:19:38 AM 08/11/2020 Control Valve 1st Mechanical Sprinkler Mechanical suite Tested 9:15:54 AM 08/11/2020 Inspector's Test 1st Mechanical Sprinkler Mechanical suite Inspected 9:22:55 AM 08/11/2020

Failed/Other Wet Pipe

Tamper Switch 1st Mechanical Sprinkler Mechanical suite Tested 9:16:19 AM 08/11/2020 Fire Dep't Connection 1st Front Desk Entrance Inspected 9:23:21 AM 08/11/2020 Piping 1st Mechanical Sprinkler Inspected 9:23:09 AM 08/11/2020 Alarm Valve 1st Mechanical Sprinkler Mechanical suite Inspected 9:16:53 AM 08/11/2020 Check Valve 1st Mechanical Sprinkler Mechanical suite Inspected 9:17:39 AM 08/11/2020 Check Valve 1st Storeroom Front Desk FDC Inspected 9:20:15 AM 08/11/2020 Control Valve 1st Mechanical Sprinkler Mechanical suite Tested 9:19:07 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Greenview Knolls Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298051

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD40 30 4 1 47298027

Vane Potter VSR 39 4 1 47298031

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Flanged Grimes B Trim Open Supervised 4" 47298026

Internal Date 06/19/2018

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Mechanical Sprinkler Mechanical

suite 06/19/2018 4" 47298052

Flanged 1st Storeroom Front Desk FDC 06/19/2018 4" 47298034

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Stockham 176 1st

Mechanical Sprinkler Mechanical suite

4" Open Supervised 47298045

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 765 1st

Mechanical Sprinkler Mechanical

4" Open Supervised 47298053

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

suite

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 1324 75 12 47298030

Location 1st Mechanical Sprinkler Mechanical suite

Devices Drain

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Sectional

1st Mechanical Sprinkler Zone2

2" 75 70 60 30 47298038

Sectional

1st Mechanical Sprinkler Zone1

2" 75 75 60 30 47298029

Fast Response

Qty Type Size KFactor Finish Temperature OK ScanID 2 Pendant .5 5.6 Chrome 155 47298035

Location Description 1st Mechanical Sprinkler 01

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Front Desk Entrance Wall Yes Yes 2.5" 47298040

Gauge

Location Service Date 1st Mechanical Sprinkler 3 Water all with isolation valves 06/19/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Tyco 100 75 n/a 1/4 47298039

Piping

Location Type Size Internal Date 1st Mechanical Sprinkler

Steel 4" 06/19/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked n/a 47298037

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

1 Yes No 6 unit Randleman 1st Mechanical Sprinkler

47298032

Standard Response

Qty Type Size KFactor Finish Temperature OK ScanID

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

3 Upright .5 5.6 Brass 155 47298036

Location Description Application Orientation 1st Mechanical Sprinkler 01 na na

Wrenches

Qty Type Manufacturer Location OK ScanID 1 Sprinkler Randleman 1st Mechanical Sprinkler 47298033

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Greenview Knolls Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Control Valve Valve 11.11% 2

Tamper Switch Alarm 5.56% 1

Alarm Valve Valve 5.56% 1

Drain Device 11.11% 2

Check Valve Valve 11.11% 2

Waterflow Switch Alarm 11.11% 2

Sprinkler Box Sprinkler 5.56% 1

Wrenches Sprinkler 5.56% 1

Standard Response Sprinkler 5.56% 1

Inspector's Test Valve 5.56% 1

Fast Response Sprinkler 5.56% 1

Piping Sprinkler 5.56% 1

Fire Dep't Connection Hose 5.56% 1

Gauge Device 5.56% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Wet Pipe

Fire Dep't Connection 1 100 Wall

06/19/2018

Tamper Switch 1 OSYSUA2 OS&Y Supervisory 06/19/2018

Waterflow Switch 1 VSR Vane Alarm 06/19/2018

Sprinkler Box 1 1

06/19/2018

Wrenches 1 1 Sprinkler

06/19/2018

Control Valve 1 176 OS&Y Main Control 06/19/2018

Waterflow Switch 1 WFD40 Vane Alarm 06/19/2018

Inspector's Test 1 1324

06/19/2018

Gauge 1 100 System Pressure

06/19/2018

Standard Response 1 3115 Upright 01 06/19/2018

Drain 2 2106E Sectional

06/19/2018

Control Valve 1 765 Butterfly Isolation 06/19/2018

Fast Response 1 V27 Pendant 01 06/19/2018

In Service - 25 Years or Older

Wet Pipe

Alarm Valve 1 B Flanged

06/19/1989

Piping 1 3115 Steel

06/19/1989

Check Valve 1 CV-B Grooved

06/19/1988

Check Valve 1 1078 Flanged

01/19/1988

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Greenview Knolls Elementary School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Wet Pipe 1 Control Valve 1st Mechanical Sprinkler Mechanical suite Special Note 47298053

Tamper did not report to fire control panel 2 Tamper Switch 1st Mechanical Sprinkler Mechanical suite Special Note 47298051

Tamper did not report to fire control panel

Sprinkler Inspection Certificate For

Hollywood Elementary School 44345 Joy Chapel Road Hollywood, Maryland 20636

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 13, 2020

Building: Hollywood Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Hollywood Elementary School Contact: Cathy Orolan

Address: 44345 Joy Chapel Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Hollywood, Maryland 20636 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 18 Service Main Building- Mechanical Building- 15 Wet Pipe 2

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 3 8.57% 3 100.00% 2 66.67% 1 33.33% Alarm 9 25.71% 9 100.00% 9 100.00% 0 0% Valve 11 31.43% 11 100.00% 8 72.73% 3 27.27% Hose 1 2.86% 1 100.00% 0 0% 1 100.00% Pump 6 17.14% 6 100.00% 4 66.67% 2 33.33% Sprinkler 5 14.29% 5 100.00% 4 80.00% 1 20.00%

Totals 35 100% 35 100.00

% 27 77.14% 8 22.86%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Hollywood Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 18, 2020 6:48:15 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Hollywood Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Fire Pump Alarm Valve

47298138 1st Floor boiler room Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 47298146 1st Floor In Pit Sprinkler Room Fire Pump Bypass Needs 5 Yr. Service NFPA25 13.4.2.1 47298158 1st Floor In Pit Sprinkler Room Needs 5 Yr. Service NFPA25 13.4.2.1

Building- Mechanical Service Main, Building- Fire Dep't Connection

47298203 1st Floor East Front Desk Main Building front Needs Hydro Test NFPA25 4.1.5.1

Fire Pump Gauge 47298202 1st Floor In Pit Sprinkler Room Main Building Date Expired NFPA25 4.1.5.1 47298198 1st Floor In Pit Sprinkler Room Main Building Date Expired NFPA25 4.1.5.1

Gauge 47298199 1st Floor In Pit Sprinkler Room Main Building Date Expired NFPA25 13.2.7.2

Piping 47298147 1st Floor In Pit Sprinkler Room Main Building Needs 5 Yr. Service NFPA25 14.2.1.1

Code References NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Hollywood Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Fire Pump

Alarm Valve

47298138 1st Floor boiler room 5 Yr. Internal 175 T/M

Check Valve

47298146 1st Floor In Pit Sprinkler Room Fire Pump Bypass

5 Yr. Internal CV-1-S T/M

47298158 1st Floor In Pit Sprinkler Room 5 Yr. Internal N/A T/M

Building- Mechanical Service Main, Building-

Fire Dep't Connection

47298203 1st Floor East Front Desk Main Building front Hydro Test A22 T/M

Fire Pump Gauge

47298202 1st Floor In Pit Sprinkler Room Main Building Replace 1 T/M 47298198 1st Floor In Pit Sprinkler Room Main Building Replace 1 T/M

Gauge

47298199 1st Floor In Pit Sprinkler Room Main Building Replace 1 T/M

Piping

47298147 1st Floor In Pit Sprinkler Room Main Building 5 Yr. Internal 1 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Hollywood Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump

Fire Pump Off 1st Floor In Pit Sprinkler Room Tested 8:15:42 AM 08/13/2020 Fire Pump Power 1st Floor In Pit Sprinkler Room Tested 8:15:16 AM 08/13/2020 Fire Pump Running 1st Floor In Pit Sprinkler Room Tested 8:15:08 AM 08/13/2020 Tamper Switch 1st Floor In Pit Sprinkler Room Fire Pump

Discharge Tested 8:19:57 AM 08/13/2020

Tamper Switch 1st Floor In Pit Sprinkler Room Fire Pump Suction

Tested 8:26:16 AM 08/13/2020

Waterflow Switch 1st Floor In Pit Sprinkler Room Main Building Tested 10:02:33 AM 08/12/2020 Drain 1st Floor In Pit Sprinkler Room Fire Pump

Discharge Side Tested 8:25:54 AM 08/13/2020

Controller 1st Floor In Pit Sprinkler Room Tested 8:25:43 AM 08/13/2020 Electrical Driver 1st Floor In Pit Sprinkler Room Inspected 8:26:07 AM 08/13/2020 Pump 1st Floor In Pit Sprinkler Room Tested 8:14:19 AM 08/13/2020 Transfer Switch 1st Floor In Pit Sprinkler Room Tested 8:26:29 AM 08/13/2020 Control Valve 1st Floor In Pit Sprinkler Room Fire Pump

Discharge Tested 8:14:59 AM 08/13/2020

Control Valve 1st Floor In Pit Sprinkler Room Fire Pump Bypass #1

Tested 8:16:06 AM 08/13/2020

Control Valve 1st Floor In Pit Sprinkler Room Tested 8:17:26 AM 08/13/2020 Control Valve 1st Floor In Pit Sprinkler Room Fire Pump

Bypass #2 Tested 8:24:52 AM 08/13/2020

Building- Mechanical Service Main, Building- Tamper Switch 1st Floor In Pit Sprinkler Room Main Building Tested 9:55:44 AM 08/12/2020 Waterflow Switch 1st Floor In Pit Sprinkler Room Main Building Tested 8:26:38 AM 08/13/2020 Drain 1st Floor East Front Desk Main Building front Tested 8:25:49 AM 08/13/2020 Sprinkler Box 1st Floor In Pit Sprinkler Room Main Building Inspected 10:03:45 AM 08/12/2020 Standard Response 1st Floor In Pit Sprinkler Room Main Building Inspected 10:03:22 AM 08/12/2020 Standard Response 1st Floor In Pit Sprinkler Room Main Building Inspected 10:03:32 AM 08/12/2020 Wrenches 1st Floor In Pit Sprinkler Room Main Building Inspected 10:03:41 AM 08/12/2020 Control Valve 1st Floor boiler room Main Building Tested 10:02:59 AM 08/12/2020 Control Valve 1st Floor boiler room Main Building Tested 8:21:48 AM 08/13/2020 Control Valve 1st Floor boiler room Main Building Tested 8:25:38 AM 08/13/2020

Wet Pipe Tamper Switch 1st Floor In Pit Sprinkler Room Tested 8:17:53 AM 08/13/2020 Control Valve 1st Floor In Pit Sprinkler Room Tested 8:25:02 AM 08/13/2020

Failed/Other

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Fire Pump

Alarm Valve 1st Floor boiler room Inspected 8:24:30 AM 08/13/2020 Check Valve 1st Floor In Pit Sprinkler Room Inspected 8:16:48 AM 08/13/2020 Check Valve 1st Floor In Pit Sprinkler Room Fire Pump

Bypass Inspected 8:16:57 AM 08/13/2020

Building- Mechanical Service Main, Building- Gauge 1st Floor In Pit Sprinkler Room Main Building Inspected 10:04:50 AM 08/12/2020 Fire Dep't Connection 1st Floor East Front Desk Main Building front Inspected 10:04:02 AM 08/12/2020 Fire Pump Gauge 1st Floor In Pit Sprinkler Room Main Building Inspected 10:04:20 AM 08/12/2020 Fire Pump Gauge 1st Floor In Pit Sprinkler Room Main Building Inspected 10:04:35 AM 08/12/2020 Piping 1st Floor In Pit Sprinkler Room Main Building Inspected 8:11:59 AM 08/13/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Hollywood Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298162

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Nibco N/A 1st Floor In Pit

Sprinkler Room

6" Open Supervised 47298163

Description Discharge

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Private Fire Service Mains Generated by: BuildingReports.com

Building: Hollywood Elementary School Building- Mechanical, Building-

This section lists out all the devices and components that have been associated with a Private Fire Service Main and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Fire Pump Gauge

Location Discharge psi Suction psi OK ScanID 1st Floor In Pit Sprinkler Room Main Building

na N/A 47298202

1st Floor In Pit Sprinkler Room Main Building

na na 47298198

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298153

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR-F 4 1 47298200

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Kennedy 200W 1st Floor

boiler room Main Building

4" Closed Locked 47298195

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Kennedy 200W 1st Floor

boiler room Main Building

4" Open Supervised 47298155

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 2612 1st Floor

boiler room Main Building

4" Open Supervised 47298201

Description Main Control

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor East Front Desk Main Building front

2" 70 65 55 47298156

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor East Front Desk Main

Building front 2" 70 65 55 30 47298156

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor East Front Desk Main

Building front 2" 70 65 55 47298156

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Floor East Front Desk Main

Building front Wall Yes Yes 2.5" 47298203

Gauge

Location Service Date 1st Floor In Pit Sprinkler Room Main Building 06/19/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Unknown 1 75 n/a 1/4 47298199

Piping

Location Type Size Internal Date 1st Floor In Pit Sprinkler Room Main Building

Steel 4" 06/19/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal n/a Marked n/a 47298147

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

1 Yes No 6 unit Kennedy 1st Floor In Pit Sprinkler Room Main Building

47298150

Standard Response

Qty Type Size KFactor Finish Temperature OK ScanID 5 Upright .5 5.6 Brass 200 47298148

Location Description Application Orientation 1st Floor In Pit Sprinkler Room Main Building

chrome na na

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Standard Response

Qty Type Size KFactor Finish Temperature OK ScanID 5 Pendant .5 5.6 Chrome 155 47298151

Location Description Application Orientation 1st Floor In Pit Sprinkler Room Main Building

chrome na na

Wrenches

Qty Type Manufacturer Location OK ScanID 1 Sprinkler Kennedy 1st Floor In Pit Sprinkler Room

Main Building 47298149

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Hollywood Elementary School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Metron M30A-25-460B 1st Floor In Pit Sprinkler Room 06/19/2018 EL-9311396-01

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 90 110 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID Marathon Z0256TTDR5617AN

L 1st Floor In Pit Sprinkler Room 2563-V 47298143

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3525 10 230/460 56/28 25 2900

Pump

Manufacturer Model Number Location Install Date Scan Number Patterson VIP 1st Floor In Pit Sprinkler Room 06/19/1993 47298142

Serial Number Type Orientation Aligned? Water Supply Impeller Size 93FP05255-L3 Pump Primary Vertical Yes Water Storage

Tank 71/8

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/13/20 175 75 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/13/20 150 70 308

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/13/20 125 60 445

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating Net Pressure Gallons Per Minute Rotations Per Minute Amps Volts

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

A B C A-B B-C A-C 97 0

75 300

56 450

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto 1st Floor In Pit Sprinkler Room N/A N/A 47298166

On psi Off psi AC Type Generator Batteries Run Period Timer N/A N/A Normal

Phase Yes No N/A

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor In Pit Sprinkler Room N/A 1 47298168

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Floor In Pit Sprinkler Room 1 47298169

Fire Pump Running

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor In Pit Sprinkler Room N/A 1 47298170

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298160

OS&Y Supervisory Federal 1 47298141

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR-F 4 1 47298152

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Flanged Viking 175 Trim Open Supervised 4" 47298138

Internal Date 06/19/2018

Check Valve

Type Location Internal Date Size OK ScanID Flanged 1st Floor In Pit Sprinkler Room 06/19/2018 6" 47298158

Grooved 1st Floor In Pit Sprinkler Room Fire Pump Bypass

06/19/2018 4" 47298146

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Nibco SWP 1st Floor In Pit

Sprinkler Room Fire Pump Discharge

6" Open Supervised 47298161

Description Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller 62L0 1st Floor In Pit

Sprinkler Room Fire Pump Bypass #1

4" Open Supervised 47298145

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y EVA 722U 1st Floor In Pit

Sprinkler Room

4" Open Supervised 47298140

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller 62L0 1st Floor In Pit

Sprinkler Room Fire Pump Bypass #2

4" Open Supervised 47298144

Description Bypass

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor In Pit Sprinkler Room Fire Pump Discharge Side

2" 55 55 55 47298159

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor In Pit Sprinkler Room

Fire Pump Discharge Side 2" 55 55 55 30 47298159

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor In Pit Sprinkler Room

Fire Pump Discharge Side 2" 55 55 55 30 47298159

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Hollywood Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Tamper Switch Alarm 11.43% 4

Waterflow Switch Alarm 5.71% 2

Control Valve Valve 22.86% 8

Standard Response Sprinkler 5.71% 2

Wrenches Sprinkler 2.86% 1

Sprinkler Box Sprinkler 2.86% 1

Fire Dep't Connection Hose 2.86% 1

Fire Pump Gauge Pump 5.71% 2

Gauge Device 2.86% 1

Piping Sprinkler 2.86% 1

Pump Pump 2.86% 1

Fire Pump Running Alarm 2.86% 1

Fire Pump Power Alarm 2.86% 1

Fire Pump Off Alarm 2.86% 1

Check Valve Valve 5.71% 2

Alarm Valve Valve 2.86% 1

Controller Pump 2.86% 1

Drain Device 5.71% 2

Electrical Driver Pump 2.86% 1

Transfer Switch Pump 2.86% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Fire Pump

Controller 1 M30A-25-460B

Automatic 06/19/2018

Transfer Switch 1 MTS-100A Auto

06/19/2018

Control Valve 2 62L0 Butterfly Bypass 06/19/2018

Control Valve 1 SWP OS&Y Discharge 06/19/2018

Wet Pipe

Control Valve 1 N/A OS&Y Discharge 06/19/2018

In Service - 25 Years or Older

Fire Pump

Control Valve 1 722U OS&Y Suction 06/19/1993

Tamper Switch 1 OSY2 OS&Y Supervisory 06/19/1993

Check Valve 1 CV-1-S Grooved

06/19/1993

Electrical Driver 1 Z0256TTDR5617ANL

06/19/1993

Fire Pump Off 1 N/A

Supervisory 06/19/1993

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Fire Pump Power 1 N/A

Supervisory 06/19/1993

Fire Pump Running 1 N/A

Supervisory 06/19/1993

Check Valve 1 N/A Flanged

06/19/1993

Drain 1 801 Main

06/19/1993

Pump 1 VIP Pump Primary

06/19/1993

Waterflow Switch 1 VSR-F Vane Alarm 06/19/1993

Tamper Switch 1 OSY2 OS&Y Supervisory 06/19/1993

Alarm Valve 1 175 Flanged

06/19/1993

Wet Pipe

Tamper Switch 1 OSY2 OS&Y Supervisory 06/19/1993

Building- Mechanical Service Main, Building-

Control Valve 2 200W OS&Y Main Control 06/19/1993

Control Valve 1 2612 Butterfly Main Control 06/19/1993

Sprinkler Box 1 N/A

06/19/1993

Wrenches 1 1 Sprinkler

06/19/1993

Drain 1 175W Main

06/19/1993

Waterflow Switch 1 VSR-F Vane Alarm 06/19/1993

Fire Dep't Connection 1 A22 Wall

06/19/1993

Tamper Switch 1 OSY2 OS&Y Supervisory 06/19/1993

Fire Pump Gauge 1 1 Discharge

06/19/1993

Fire Pump Gauge 1 1 Suction

06/19/1993

Gauge 1 1 Supply Pressure

06/19/1993

Piping 1 1 Steel

06/19/1993

Standard Response 1 589A Pendant chrome 06/19/1993

Standard Response 1 589A Upright chrome 06/19/1993

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Hollywood Elementary School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Building- Mechanical Service Main, Building- 1 Piping 1st Floor In Pit Sprinkler Room Main Building Needs 5 Yr.

Service 47298147

4” test header pipe is leaking at the first Vic from the control valve and near where the pipe penetrates the wall for the test header. Total of 2 leaks while testing the pump.

Fire Pump 2 Waterflow Switch 1st Floor In Pit Sprinkler Room Main Building Passed 47298152

The main riser for the building was found in the closed position upon arrival, there is no tag indicating why this valve is closed. Recommend fire watch for this building because the sprinkler system is current impaired.

Sprinkler Inspection Certificate For

Leonardtown Elementary School 22885 Duke Street Leonardtown, Maryland 20650

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 12, 2020

Building: Leonardtown Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Leonardtown Elementary School Contact: Cathy Orolan

Address: 22885 Duke Street Phone: 301-475-4256

Address: Fax:

City/State/Zip: Leonardtown, Maryland 20650 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Wet Pipe Building- 22

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 3 13.64% 3 100.00% 2 66.67% 1 33.33% Alarm 4 18.18% 4 100.00% 4 100.00% 0 0% Valve 9 40.91% 9 100.00% 6 66.67% 3 33.33% Hose 1 4.55% 1 100.00% 0 0% 1 100.00% Sprinkler 5 22.73% 5 100.00% 4 80.00% 1 20.00%

Totals 22 100% 22 100.00

% 16 72.73% 6 27.27%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Leonardtown Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:54:21 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Leonardtown Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Wet Pipe, Building- Alarm Valve

47298601 1st Floor Outside Sprinkler Room Zone #1 Needs 5 Yr. Service NFPA25 13.4.1.2 47298602 1st Floor Outside Sprinkler Room Zone #2 Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 47298608 1st Floor Outside Sprinkler Room FDC Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 47298617 1st Floor Outside Sprinkler Room Needs Hydro Test NFPA25 4.1.5.1

Gauge 47298614 1st Floor Outside Sprinkler Room (4) Water Date Expired NFPA25 13.2.7.2

Piping 47298613 1st Floor Outside Sprinkler Room Needs 5 Yr. Service NFPA25 14.2.1.1

Code References NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Leonardtown Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Wet Pipe, Building-

Alarm Valve

47298601 1st Floor Outside Sprinkler Room Zone #1 5 Yr. Internal CV-1F T/M 47298602 1st Floor Outside Sprinkler Room Zone #2 5 Yr. Internal CV-1F T/M

Check Valve

47298608 1st Floor Outside Sprinkler Room FDC 5 Yr. Internal VSR-F T/M

Fire Dep't Connection

47298617 1st Floor Outside Sprinkler Room Hydro Test n/a T/M

Gauge

47298614 1st Floor Outside Sprinkler Room (4) Water Replace 111.10SP.100.2013

T/M

Piping

47298613 1st Floor Outside Sprinkler Room 5 Yr. Internal n/a T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Leonardtown Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Wet Pipe, Building-

Tamper Switch 1st Floor Outside Sprinkler Room Backflow #1 Tested 1:49:55 PM 08/11/2020 Tamper Switch 1st Floor Outside Sprinkler Room Backflow #2 Tested 1:50:07 PM 08/11/2020 Waterflow Switch 1st Floor Outside Sprinkler Room Zone #2 Tested 1:54:13 PM 08/11/2020 Waterflow Switch 1st Floor Outside Sprinkler Room Zone #1 Tested 8:54:10 AM 08/12/2020 Drain 1st Floor Outside Sprinkler Room Zone #2 Tested 1:56:00 PM 08/11/2020 Drain 1st Floor Outside Sprinkler Room Zone #1 Tested 1:56:14 PM 08/11/2020 Sprinkler Box 1st Floor Outside Sprinkler Room Inspected 1:52:03 PM 08/11/2020 Sprinkler Box Spares 1st Floor Outside Sprinkler Room Inspected 1:52:07 PM 08/11/2020 Sprinkler Box Spares 1st Floor Outside Sprinkler Room Inspected 1:52:10 PM 08/11/2020 Sprinkler Box Spares 1st Floor Outside Sprinkler Room Inspected 1:52:22 PM 08/11/2020 Backflow Prevention 1st Floor Outside Sprinkler Room Fire Line Inspected 1:55:47 PM 08/11/2020 Control Valve 1st Floor Outside Sprinkler Room Backflow #1 Tested 1:49:52 PM 08/11/2020 Control Valve 1st Floor Outside Sprinkler Room Backflow #2 Tested 1:50:34 PM 08/11/2020 Control Valve 1st Floor Outside Sprinkler Room Zone #2 Tested 1:53:56 PM 08/11/2020 Control Valve 1st Floor Outside Sprinkler Room Zone #1 Tested 1:54:06 PM 08/11/2020 Post Indicator Valve 1st Floor Outside Sprinkler Room Inspected 1:52:49 PM 08/11/2020

Failed/Other Wet Pipe, Building-

Gauge 1st Floor Outside Sprinkler Room (4) Water Inspected 1:51:25 PM 08/11/2020 Fire Dep't Connection 1st Floor Outside Sprinkler Room Inspected 1:52:38 PM 08/11/2020 Piping 1st Floor Outside Sprinkler Room Inspected 1:51:53 PM 08/11/2020 Alarm Valve 1st Floor Outside Sprinkler Room Zone #2 Inspected 1:53:33 PM 08/11/2020 Alarm Valve 1st Floor Outside Sprinkler Room Zone #1 Inspected 1:53:49 PM 08/11/2020 Check Valve 1st Floor Outside Sprinkler Room FDC Inspected 1:50:52 PM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Leonardtown Elementary School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298596

OS&Y Supervisory Potter 1 47298607

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR-F 30 4” 1 47298599

Vane Potter VSR-F 30 4” 1 47298600

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved TFP CV-1F Trim Open Supervised 4" 47298602

Internal Date 07/17/2018

Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved TFP CV-1F Trim Open Supervised 4" 47298601

Internal Date 07/17/2018

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Wilkins 350A 6" Double Check Fire Line 07/17/2007

ScanID Water Purveyor Location Meter Account # Serial Number 47298594 n/a 1st Floor Outside Sprinkler Room

Fire Line n/a U03613

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Held At Condition of Control Valve 1 Condition of Control Valve 2 n/a n/a

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Outside Sprinkler Room

FDC 07/17/2018 4" 47298608

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Clow 2638 1st Floor

Outside Sprinkler Room Backflow #1

6" Open Supervised 47298595

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Clow 2638 1st Floor

Outside Sprinkler Room Backflow #2

6" Open Supervised 47298593

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Nibco GD-4765-8N 1st Floor

Outside Sprinkler Room Zone #2

4” Open Supervised 47298603

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Nibco GD-4765-8N 1st Floor

Outside Sprinkler Room Zone #1

4” Open Supervised 47298604

Description Isolation

Post Indicator Valve

Manufacturer Model Location

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Mueller N/A 1st Floor Outside Sprinkler Room

Type Position Status Size OK ScanID Ground Open Locked 6" 47298616

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Outside Sprinkler Room Zone #2

2" 55 50 35 30 47298597

Previous Inspections

June 8, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #2 2" 55 50 35 30 47298597

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #2 2" 55 50 35 30 47298597

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Outside Sprinkler Room Zone #1

2" 55 50 35 30 47298598

Previous Inspections

June 8, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #1 2" 55 50 35 30 47298598

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #1 2" 55 50 35 30 47298598

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Floor Outside Sprinkler

Room Wall Yes Yes 2.5" 47298617

Gauge

Location Service Date 1st Floor Outside Sprinkler Room (4) Water 07/17/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika 111.10SP.100.201

3 75 none 1/4 47298614

Piping

Location Type Size Internal Date

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

1st Floor Outside Sprinkler Room

Steel 1”-6” 07/17/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47298613

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

12 Yes No 12 unit steel 1st Floor Outside Sprinkler Room

47298609

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 4 Upright Tyco 1st Floor Outside Sprinkler

Room 47298610

Temperature KFactor Size Finish Response Time 155 11.2 1/2” Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 4 Upright Tyco 1st Floor Outside Sprinkler

Room 47298611

Temperature KFactor Size Finish Response Time 200 5.6 1/2” Brass Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 4 Pendant Tyco 1st Floor Outside Sprinkler

Room 47298612

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Chrome Fast Response

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Leonardtown Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Control Valve Valve 18.18% 4

Tamper Switch Alarm 9.09% 2

Check Valve Valve 4.55% 1

Gauge Device 4.55% 1

Piping Sprinkler 4.55% 1

Sprinkler Box Sprinkler 4.55% 1

Sprinkler Box Spares Sprinkler 13.64% 3

Fire Dep't Connection Hose 4.55% 1

Post Indicator Valve Valve 4.55% 1

Alarm Valve Valve 9.09% 2

Waterflow Switch Alarm 9.09% 2

Backflow Prevention Valve 4.55% 1

Drain Device 9.09% 2

Device Type

Qty Model # Type Description Install Date

In Service - 5 Years to 10 Years

Wet Pipe, Building-

Post Indicator Valve 1 N/A Ground

07/17/2013

Fire Dep't Connection 1 n/a Wall

07/17/2013

Gauge 1 111.10SP.100.2013

Supply Pressure

07/17/2013

In Service - 10 Years to 15 Years

Wet Pipe, Building-

Control Valve 2 2638 OS&Y Main Control 07/17/2007

Control Valve 2 GD-4765-8N Butterfly Isolation 07/17/2007

Check Valve 1 VSR-F Grooved

07/17/2007

Tamper Switch 2 OSYSU-2 OS&Y Supervisory 07/17/2007

Waterflow Switch 2 VSR-F Vane Alarm 07/17/2007

Drain 2 N/A Main

07/17/2007

Piping 1 n/a Steel

07/17/2007

Sprinkler Box 1 n/a

07/17/2007

Alarm Valve 2 CV-1F Grooved

07/17/2007

Sprinkler Box Spares 1 TY3131 Upright

07/17/2007

Sprinkler Box Spares 1 TY3231 Pendant

07/17/2007

Sprinkler Box Spares 1 TY5237 Upright

07/17/2007

Backflow Prevention 1 350A Double Check

07/17/2007

Sprinkler Inspection Certificate For

Leonardtown High School 23995 Point Lookout Road Leonardtown, Maryland 20650

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 11, 2020

Building: Leonardtown High School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Leonardtown High School Contact: Cathy Orolan

Address: 23995 Point Lookout Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Leonardtown, Maryland 20650 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Dry Pipe Building- 6 Fire Pump Building- 12 Wet Pipe Building- 60

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 22 28.21% 22 100.00% 3 13.64% 19 86.36% Alarm 16 20.51% 16 100.00% 16 100.00% 0 0% Valve 27 34.62% 27 100.00% 22 81.48% 5 18.52% Pump 7 8.97% 7 100.00% 7 100.00% 0 0% Sprinkler 6 7.69% 6 100.00% 4 66.67% 2 33.33%

Totals 78 100% 78 100.00

% 52 66.67% 26 33.33%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Leonardtown High School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:57:03 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Leonardtown High School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Dry Pipe, Building- Dry Pipe Valve

47298429 Outside at Well House Dry Valve Special Note NFPA25 4.1.5.1

Piping 47298428 1st at Mechanical room Needs 5 Yr. Service NFPA25 14.2.1.1

Fire Pump, Building- Check Valve

47298415 Outside at Well House Needs 5 Yr. Service NFPA25 13.4.2.1

Wet Pipe, Building- Alarm Valve

49304109 1st at Mechanical room Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 49304107 1st at Mechanical room Needs 5 Yr. Service NFPA25 13.4.2.1 49304108 1st at Mechanical room Needs 5 Yr. Service NFPA25 13.4.2.1

Gauge 49304113 1st at Mechanical room Date Expired NFPA25 13.2.7.2 49304115 1st at Mechanical room Date Expired NFPA25 13.2.7.2 49307057 1st at pump room Date Expired NFPA25 13.2.7.2 49307058 1st at pump room Date Expired NFPA25 13.2.7.2 49307059 1st at pump room Date Expired NFPA25 13.2.7.2 49307060 1st at pump room Date Expired NFPA25 13.2.7.2 49307088 1st A77 closet Date Expired NFPA25 13.2.7.2 49307089 1st A77 closet Date Expired NFPA25 13.2.7.2 49307090 1st A77 closet Date Expired NFPA25 13.2.7.2 49307091 1st A77 closet Date Expired NFPA25 13.2.7.2 49307092 1st A77 closet Date Expired NFPA25 13.2.7.2 49307094 1st at pump room Date Expired NFPA25 13.2.7.2 49307061 1st at pump room Date Expired NFPA25 13.2.7.2 49307062 1st at pump room Date Expired NFPA25 13.2.7.2 49307063 1st at pump room Date Expired NFPA25 13.2.7.2 49307083 2nd at Room Area 2D07 Date Expired NFPA25 13.2.7.2

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

ScanID Location Problem Reference

49307084 2nd at Room Area 2D07 Date Expired NFPA25 13.2.7.2 49307085 2nd at Room Area 2D07 Date Expired NFPA25 13.2.7.2

Piping 49304116 1st at Mechanical room Needs 5 Yr. Service NFPA25 14.2.1.1

Water Storage Tank 49307093 1st at pump room Needs 5 Yr. Service

Code References NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Leonardtown High School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Dry Pipe, Building-

Dry Pipe Valve

47298429 Outside at Well House Dry Valve Correct INAF2 T/M

Piping

47298428 1st at Mechanical room 5 Yr. Internal N/A T/M

Fire Pump, Building-

Check Valve

47298415 Outside at Well House 5 Yr. Internal G-1 T/M

Wet Pipe, Building-

Alarm Valve

49304109 1st at Mechanical room 5 Yr. Internal N/A T/M

Check Valve

49304107 1st at Mechanical room 5 Yr. Internal N/A T/M 49304108 1st at Mechanical room 5 Yr. Internal N/A T/M

Gauge

49304113 1st at Mechanical room Replace N/A T/M 49304115 1st at Mechanical room Replace N/A T/M 49307057 1st at pump room Replace N/A T/M 49307058 1st at pump room Replace N/A T/M 49307059 1st at pump room Replace N/A T/M 49307060 1st at pump room Replace N/A T/M 49307088 1st A77 closet Replace 14902 T/M 49307089 1st A77 closet Replace 14902 T/M 49307090 1st A77 closet Replace 14902 T/M 49307091 1st A77 closet Replace 14902 T/M 49307092 1st A77 closet Replace 14902 T/M 49307094 1st at pump room Replace N/A T/M 49307061 1st at pump room Replace N/A T/M 49307062 1st at pump room Replace N/A T/M 49307063 1st at pump room Replace N/A T/M 49307083 2nd at Room Area 2D07 Replace 14902 T/M 49307084 2nd at Room Area 2D07 Replace 14902 T/M 49307085 2nd at Room Area 2D07 Replace 14902 T/M

Piping

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

ScanID Location Solution Model # Cost Fix

49304116 1st at Mechanical room 5 Yr. Internal N/A T/M

Water Storage Tank

49307093 1st at pump room 5 Yr. Internal N/A T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Leonardtown High School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Dry Pipe, Building-

Pressure Switch Outside at Well House Dry Pipe Tested 11:23:17 AM 08/11/2020 Waterflow Switch Outside at Well House Dry Pipe Tested 11:09:11 AM 08/11/2020 Air Compressor Outside at Well House Dry Valve Inspected 11:09:55 AM 08/11/2020 Control Valve Outside at Well House Wet System Tested 11:24:27 AM 08/11/2020

Fire Pump, Building- Fire Pump Power Outside at Well House Tested 11:02:43 AM 08/11/2020 Fire Pump Running Outside at Well House Tested 11:02:45 AM 08/11/2020 Tamper Switch Outside at Well House Fire Pump Discharge Tested 11:10:38 AM 08/11/2020 Controller Outside at Well House Tested 11:02:28 AM 08/11/2020 Electrical Driver Outside at Well House Inspected 11:02:56 AM 08/11/2020 Jockey Controller Outside at Well House Tested 11:02:21 AM 08/11/2020 Jockey Pump Outside at Well House Inspected 11:02:17 AM 08/11/2020 Pump Outside at Well House Tested 11:04:03 AM 08/11/2020 Transfer Switch Outside at Well House Tested 11:02:49 AM 08/11/2020 Control Valve Outside at Well House Fire Pump Discharge Tested 11:10:34 AM 08/11/2020 Control Valve Outside at Well House Fire Pump Test Header Tested 11:23:04 AM 08/11/2020

Wet Pipe, Building- Waterflow Switch 1st at Room Area Room A77 corridor lobby Tested 11:37:13 AM 08/11/2020 Waterflow Switch 1st at Room Area Room A77 aux gym aerobics Tested 11:37:22 AM 08/11/2020 Waterflow Switch 1st at Room Area Room A77 gym area Tested 11:37:43 AM 08/11/2020 Waterflow Switch 1st at Room Area Room A77 area B Tested 11:39:11 AM 08/11/2020 Waterflow Switch 1st at Room Area Room A77 stage Tested 11:39:21 AM 08/11/2020 Waterflow Switch 1st Stairwell 5 lobby Tested 12:25:22 PM 08/11/2020 Waterflow Switch 1st at Mechanical room Tested 12:28:13 PM 08/11/2020 Waterflow Switch 2nd at Room Area 2D07 zone 2 Tested 11:20:24 AM 08/11/2020 Waterflow Switch 2nd at Room Area 2D07 zone 1 Tested 11:22:09 AM 08/11/2020 Waterflow Switch 2nd at Room Area 2D07 zone3 Tested 11:22:30 AM 08/11/2020 Waterflow Switch Outside at Well House Wet System Tested 11:09:01 AM 08/11/2020 Drain 1st at Mechanical room Tested 11:33:28 AM 08/11/2020 Drain Outside at Well House Dry Pipe Tested 11:12:11 AM 08/11/2020 Drain Outside at Well House Dry Valve Tested 11:23:29 AM 08/11/2020 Sprinkler Box Outside at Well House Inspected 11:10:13 AM 08/11/2020 Sprinkler Box Spares Outside at Well House Inspected 11:10:04 AM 08/11/2020 Sprinkler Box Spares Outside at Well House Inspected 11:10:07 AM 08/11/2020 Sprinkler Box Spares Outside at Well House Inspected 11:10:10 AM 08/11/2020 Control Valve 1st at Room Area Room A77 stage Tested 11:31:22 AM 08/11/2020 Control Valve 1st at Room Area Room A77 corridor lobby Tested 11:31:33 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Device Type Location Service Time Date Control Valve 1st at Room Area Room A77 aux gym aerobics Tested 11:31:41 AM 08/11/2020 Control Valve 1st at Room Area Room A77 gym area Tested 11:31:49 AM 08/11/2020 Control Valve 1st at Room Area Room A77 area b Tested 11:31:58 AM 08/11/2020 Control Valve 1st Stairwell 5 lobby Tested 11:32:15 AM 08/11/2020 Control Valve 1st at Mechanical room Tested 11:33:11 AM 08/11/2020 Control Valve 2nd at Room Area 2D07 Tested 11:19:01 AM 08/11/2020 Control Valve 2nd at Room Area 2D07 Tested 11:19:20 AM 08/11/2020 Control Valve 2nd at Room Area 2D07 Tested 11:19:51 AM 08/11/2020 Control Valve Outside at Well House Wets System Tested 11:08:56 AM 08/11/2020 Inspector's Test 1st at Room Area Room A77 lobby corridor Inspected 11:37:47 AM 08/11/2020 Inspector's Test 1st at Room Area Room A77 aux gym aerobics Inspected 11:37:51 AM 08/11/2020 Inspector's Test 1st at Room Area Room A77 gym zone Inspected 11:37:56 AM 08/11/2020 Inspector's Test 1st at Room Area Room A77 stage auditorium Inspected 11:38:00 AM 08/11/2020 Inspector's Test 1st at Room Area Room A77 area B Inspected 11:38:03 AM 08/11/2020 Inspector's Test 2nd at Room Area 2D07 Inspected 11:22:34 AM 08/11/2020 Inspector's Test 2nd at Room Area 2D07 Inspected 11:22:40 AM 08/11/2020 Inspector's Test 2nd at Room Area 2D07 Inspected 11:22:43 AM 08/11/2020

Failed/Other Dry Pipe, Building-

Piping 1st at Mechanical room Inspected 11:08:47 AM 08/11/2020 Dry Pipe Valve Outside at Well House Dry Valve Tested 11:33:25 AM 08/11/2020

Fire Pump, Building- Check Valve Outside at Well House Inspected 11:04:17 AM 08/11/2020

Wet Pipe, Building- Gauge 1st at pump room Inspected 11:04:31 AM 08/11/2020 Gauge 1st at pump room Inspected 11:09:35 AM 08/11/2020 Gauge 1st at pump room Inspected 11:09:49 AM 08/11/2020 Gauge 1st at Mechanical room Inspected 11:33:59 AM 08/11/2020 Gauge 1st A77 closet Inspected 11:34:45 AM 08/11/2020 Gauge 1st A77 closet Inspected 11:35:03 AM 08/11/2020 Gauge 1st A77 closet Inspected 11:35:20 AM 08/11/2020 Gauge 1st A77 closet Inspected 11:35:33 AM 08/11/2020 Gauge 1st A77 closet Inspected 11:35:49 AM 08/11/2020 Gauge 1st at pump room Inspected 11:38:15 AM 08/11/2020 Gauge 1st at pump room Inspected 11:38:32 AM 08/11/2020 Gauge 1st at pump room Inspected 11:38:42 AM 08/11/2020 Gauge 1st at pump room Inspected 11:38:51 AM 08/11/2020 Gauge 1st at pump room Inspected 11:39:00 AM 08/11/2020 Gauge 1st at Mechanical room Inspected 12:25:04 PM 08/11/2020 Gauge 2nd at Room Area 2D07 Inspected 11:21:06 AM 08/11/2020 Gauge 2nd at Room Area 2D07 Inspected 11:21:35 AM 08/11/2020 Gauge 2nd at Room Area 2D07 Inspected 11:22:53 AM 08/11/2020 Water Storage Tank 1st at pump room Inspected 11:36:38 AM 08/11/2020 Piping 1st at Mechanical room Inspected 11:37:00 AM 08/11/2020 Alarm Valve 1st at Mechanical room Inspected 11:32:30 AM 08/11/2020 Check Valve 1st at Mechanical room Inspected 11:32:51 AM 08/11/2020 Check Valve 1st at Mechanical room Inspected 11:33:02 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Leonardtown High School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSRF 30 2.5 1 47298395

Vane Potter Electric VSRF 30 2.5 1 47298397

Vane Potter Electric VSRF 30 2.5 1 47298407

Vane Potter Electric VSRF 30 2.5 1 47298412

Vane Potter Electric VSRF 39 2.5 1 47298409

Vane Potter Electric VSR-F 30 4 1 47298446

Pressure Switch N/A N/A 30 N/A 1 49304117

Vane Potter Electric 14902 30 4 1 47298450

Vane Potter Electric 14902 39 4 1 47298451

Vane Potter Electric 14902 39 4 1 47298452

Vane System Sensor WFD20 30 2” 1 47298430

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Flanged N/A N/A Trim Open Supervised N/A 49304109

Internal Date 07/18/2018

Check Valve

Type Location Internal Date Size OK ScanID Threaded 1st at Mechanical room 07/18/2018 N/A 49304107

Flanged 1st at Mechanical room 07/18/2018 N/A 49304108

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 1st at Room

Area Room A77 stage

2.5" Open Supervised 47298392

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Butterfly Kennedy 14902 1st at Room Area Room A77 corridor lobby

2.5" Open Supervised 47298393

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 1st at Room

Area Room A77 aux gym aerobics

2.5" Open Supervised 47298405

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 1st at Room

Area Room A77 gym area

2.5" Open Supervised 47298406

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 1st at Room

Area Room A77 area b

2.5" Open Supervised 47298413

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 1st Stairwell 5

lobby 4" Open Supervised 47298447

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y N/A N/A 1st at

Mechanical room

N/A Open Supervised 49304112

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 2nd at Room

Area 2D07 4" Open Supervised 47298445

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 2nd at Room

Area 2D07 4" Open Supervised 47298448

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 2nd at Room

Area 2D07 4" Open Supervised 47298449

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-SCS Outside at

Well House Wets System

2" Open Supervised 47298431

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 12 47298394

Location 1st at Room Area Room A77 lobby corridor

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 12 47298396

Location 1st at Room Area Room A77 aux gym aerobics

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 12 47298404

Location 1st at Room Area Room A77 gym zone

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 12 47298408

Location 1st at Room Area Room A77 stage auditorium

Inspector's Test

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 12 47298411

Location 1st at Room Area Room A77 area B

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 15 47298805

Location 2nd at Room Area 2D07

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 15 47298806

Location 2nd at Room Area 2D07

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain 146 110 12 47298807

Location 2nd at Room Area 2D07

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st at Mechanical room 3" 120 N/A 100 49304114

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st at Mechanical room 3" 120 N/A 100 30 49304114

March 12, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st at Mechanical room 3" 120 N/A 100 . 49304114

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main Outside at Well House Dry Pipe 1" 105 95 100 47298421

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside at Well House Dry Pipe 1" 105 95 100 30 47298421

March 12, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Main Outside at Well House Dry Pipe 1" 105 95 100 .N/A

47298421

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main Outside at Well House Dry Valve

1.25" 105 100 95 30 47298426

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside at Well House Dry

Valve 1.25" 105 100 95 30 47298426

March 12, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Outside at Well House Dry

Valve 1.25" 105 100 95 .N/

A 47298426

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307060

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307057

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307094

Gauge

Location Service Date 1st at Mechanical room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID N/A N/A N/A 110 None N/A 49304113

Gauge

Location Service Date 1st A77 closet 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307088

Gauge

Location Service Date

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

1st A77 closet 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 0 na 1/4 49307089

Gauge

Location Service Date 1st A77 closet 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307090

Gauge

Location Service Date 1st A77 closet 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307091

Gauge

Location Service Date 1st A77 closet 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307092

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307063

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307058

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307059

Gauge

Location Service Date 1st at pump room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307061

Gauge

Location Service Date 1st at pump room 07/18/2018

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49307062

Gauge

Location Service Date 1st at Mechanical room 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure N/A N/A 120 None N/A 49304115

Gauge

Location Service Date 2nd at Room Area 2D07 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307083

Gauge

Location Service Date 2nd at Room Area 2D07 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307085

Gauge

Location Service Date 2nd at Room Area 2D07 12/31/1969

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Kennedy 14902 . na 1/4 49307084

Piping

Location Type Size Internal Date 1st at Mechanical room

Steel N/A 08/26/2019

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal N/A N/A N/A 49304116

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

6 Yes No 6 unit N/A Outside at Well House 47298420

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Pendant Central Outside at Well House 47298417

Temperature KFactor Size Finish Response Time 165 5.6 1/2” Chrome Standard Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Upright Rasco Outside at Well House 47298418

Temperature KFactor Size Finish Response Time

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

155 5.6 1/2” Brass Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Pendant Tyco Outside at Well House 47298419

Temperature KFactor Size Finish Response Time 165 5.6 1/2” Chrome Standard Response

Water Storage Tank

Location Capacity Internal Date Pressure psi Deg OK ScanID 1st at pump room 75,000 07/18/2018 .N/A na 49307093

Type Manufacturer Model Number In ground N/A N/A

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Leonardtown High School Building-

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Air Compressor

Location Mfr. Model # Phase On psi Off psi Serial No. Outside at Well House Dry Valve

General OL11016AC

1 30 40 OL110-JL70684

Type Description Rated Speed Horsepower Volts Amps OK ScanID Automatic Tankless 1725 1 115 3.7 47298414

Alarms Pressure Switch

Type Description Manufacturer Low High Zone/Address OK ScanID Low Supervisory System Sensor N/A N/A 1 47298425

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Pressure Switch System Sensor ESP10-2 30 1/2” 1 47298432

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-SCS Outside at

Well House Wet System

2" Open Supervised 47298427

Description Isolation

Dry Pipe Valve

Manufacturer Model # Location Internal Date OK ScanID Central INAF2 Outside at Well House Dry Valve 12/20/2018 47298429

Type Status Position Size Serial # Flanged 2" not listed

Water psi Air Pressure Trip Air Trip Time Total Timing (sec)

Partial Trip Date Full Trip Date

12/20/2018 12/20/2018

Devices Piping

Location Type Size Internal Date 1st at Mechanical room

Steel N/A 08/26/2019

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal N/A N/A N/A 47298428

Fire & Life Safety America, Inc. - Baltimore 19 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Leonardtown High School Building-

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Hubbell LX2200 Outside at Well House 07/16/2001 A022078-3-1

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 85 105 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID US Electric Motors 324TP Outside at Well House C01R748A R-A3 47298435

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 1775 10 460 51.5 40 1775

Controller Manufacturer Model # Location Install Date Serial Number Hubbell LX2200 Outside at Well House 07/16/2001 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 90 105 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Grundfos MS402 Outside at Well House 07/16/2001 47298801

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 79362005 Automatic 3450 120 not

legible 90 105

Pump

Manufacturer Model Number Location Install Date Scan Number Patterson Not Listed Outside at Well House 07/16/2001 47298433

Serial Number Type Orientation Aligned? Water Supply Impeller Size FPVT-00225111 Pump Primary Vertical Yes Water Storage

Tank 12 DMC

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/11/20 110 0 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature

Fire & Life Safety America, Inc. - Baltimore 20 08/24/2020

Other 08/11/20 90 0 501

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/11/20 72 0 756

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 106 0 1770

90 500 1770

71 750 1770

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto Outside at Well House N/A .N/A 47298438

On psi Off psi AC Type Generator Batteries Run Period Timer N/A N/A Normal

Phase Yes No N/A

Fire & Life Safety America, Inc. - Baltimore 21 08/24/2020

Alarms Fire Pump Power

Description Location Zone/Address OK ScanID N/A Outside at Well House 1 47298439

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory Outside at Well House N/A 1 47298440

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298423

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged by Grooved

Outside at Well House 07/16/2018 6" 47298415

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy Arw Outside at

Well House Fire Pump Discharge

6" Open Supervised 47298422

Description Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 14902 Outside at

Well House Fire Pump Test Header

6" Closed Supervised 47298424

Description Isolation

Fire & Life Safety America, Inc. - Baltimore 22 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Leonardtown High School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Jockey Pump Pump 1.28% 1

Jockey Controller Pump 1.28% 1

Controller Pump 1.28% 1

Fire Pump Power Alarm 1.28% 1

Fire Pump Running Alarm 1.28% 1

Transfer Switch Pump 1.28% 1

Electrical Driver Pump 1.28% 1

Pump Pump 1.28% 1

Check Valve Valve 3.85% 3

Gauge Device 23.08% 18

Piping Sprinkler 2.56% 2

Control Valve Valve 17.95% 14

Waterflow Switch Alarm 15.38% 12

Air Compressor Pump 1.28% 1

Sprinkler Box Spares Sprinkler 3.85% 3

Sprinkler Box Sprinkler 1.28% 1

Tamper Switch Alarm 1.28% 1

Drain Device 3.85% 3

Inspector's Test Valve 10.26% 8

Pressure Switch Alarm 1.28% 1

Alarm Valve Valve 1.28% 1

Dry Pipe Valve Valve 1.28% 1

Water Storage Tank Device 1.28% 1

Device Type

Qty Model # Type Description Install Date

In Service - 15 Years to 25 Years

Dry Pipe, Building-

Dry Pipe Valve 1 INAF2 Flanged

07/16/2001

Air Compressor 1 OL11016AC Automatic Tankless 07/16/2001

Control Valve 1 BB-SCS Butterfly Isolation 07/16/2001

Piping 1 N/A Steel

07/16/2001

Pressure Switch 1 ESP10-2 Low Supervisory 07/16/2001

Waterflow Switch 1 ESP10-2 Pressure Switch Alarm 07/16/2001

Fire Pump, Building-

Jockey Pump 1 MS402 Automatic

07/16/2001

Controller 1 LX2200

Automatic 07/16/2001

Fire Pump Power 1 LX2200

N/A 07/16/2001

Fire Pump Running 1 LX2200

Supervisory 07/16/2001

Jockey Controller 1 LX2200

07/16/2001

Transfer Switch 1 350E33E6 Auto

07/16/2001

Fire & Life Safety America, Inc. - Baltimore 23 08/24/2020

Control Valve 1 14902 Butterfly Isolation 07/16/2001

Control Valve 1 Arw Butterfly Discharge 07/16/2001

Pump 1 Not Listed Pump Primary

07/16/2001

Tamper Switch 1 OSYSU-2 OS&Y Supervisory 07/16/2001

Electrical Driver 1 324TP

07/16/2001

Check Valve 1 G-1 Flanged by Grooved

07/16/2001

Wet Pipe, Building-

Drain 1 N/A Main

07/16/2001

Drain 1 N/A Main

07/16/2001

Sprinkler Box Spares 1 F950 Pendant

07/16/2001

Control Valve 9 14902 Butterfly Isolation 07/16/2001

Gauge 8 14902 System Pressure

07/16/2001

Control Valve 1 BB-SCS Butterfly Isolation 07/16/2001

Alarm Valve 1 N/A Flanged

07/16/2001

Check Valve 1 N/A Flanged

07/16/2001

Check Valve 1 N/A Threaded

07/16/2001

Control Valve 1 N/A OS&Y Main Control 07/16/2001

Drain 1 N/A Main

07/16/2001

Gauge 1 N/A N/A

07/16/2001

Gauge 9 N/A Supply Pressure

07/16/2001

Piping 1 N/A Steel

07/16/2001

Sprinkler Box 1 N/A

07/16/2001

Water Storage Tank 1 N/A In ground

07/16/2001

Waterflow Switch 1 N/A Pressure Switch N/A 07/16/2001

Waterflow Switch 3 14902 Vane Alarm 07/16/2001

Waterflow Switch 1 VSR-F Vane Alarm 07/16/2001

Waterflow Switch 5 VSRF Vane Alarm 07/16/2001

Sprinkler Box Spares 1 F-1 Upright

07/16/2001

Waterflow Switch 1 WFD20 Vane Alarm 07/16/2001

Inspector's Test 8 146

07/16/2001

Sprinkler Box Spares 1 TY4211 Pendant

07/16/2001

Fire & Life Safety America, Inc. - Baltimore 24 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Leonardtown High School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Dry Pipe, Building- 1 Piping 1st at Mechanical room Needs 5 Yr.

Service 47298428

Need 5 year internal inspection and also 3 year air test 2 Dry Pipe Valve Outside at Well House Dry Valve Special Note 47298429

Dry pipe valve is due for a five-year internal inspection and a three year air test. Also recommend replacing rubber gasket.

Wet Pipe, Building- 3 Gauge 1st A77 closet Date Expired 49307088

No isolation valve 4 Gauge 1st A77 closet Date Expired 49307089

No isolation valve 5 Gauge 1st A77 closet Date Expired 49307092

No isolation valve. 6 Gauge 1st at pump room Date Expired 49307094

No isolation valve 7 Gauge 2nd at Room Area 2D07 Date Expired 49307083

No three way valve. 8 Gauge 2nd at Room Area 2D07 Date Expired 49307084

No three way valve. 9 Gauge 2nd at Room Area 2D07 Date Expired 49307085

No three way valve.

Sprinkler Inspection Certificate For

Leonardtown Middle School 24015 Point Lookout Road Leonardtown, Maryland 20650

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 12, 2020

Building: Leonardtown Middle School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Leonardtown Middle School Contact: Cathy Orolan

Address: 24015 Point Lookout Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Leonardtown, Maryland 20650 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump Building- 13 Wet Pipe Building- 37

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 5 10.00% 5 100.00% 3 60.00% 2 40.00% Alarm 12 24.00% 12 100.00% 12 100.00% 0 0% Valve 22 44.00% 22 100.00% 18 81.82% 4 18.18% Hose 1 2.00% 1 100.00% 0 0% 1 100.00% Pump 6 12.00% 6 100.00% 6 100.00% 0 0% Sprinkler 4 8.00% 4 100.00% 3 75.00% 1 25.00%

Totals 50 100% 50 100.00

% 42 84.00% 8 16.00%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Leonardtown Middle School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:56:13 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Leonardtown Middle School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Fire Pump, Building- Check Valve

47298503 1st Fire Pump Discharge Needs 5 Yr. Service NFPA25 13.4.2.1

Wet Pipe, Building- Alarm Valve

47298481 1st Fire Pump Room Zone 3 Needs 5 Yr. Service NFPA25 13.4.1.2 47298487 1st Fire Pump Room Zone 2 Needs 5 Yr. Service NFPA25 13.4.1.2 47298489 1st Fire Pump Room Zone 1 Needs 5 Yr. Service NFPA25 13.4.1.2

Fire Dep't Connection 47298529 1st Front of Building Needs 5 Yr. Service

Gauge 47298516 1st Fire Pump Room (10) Water Date Expired NFPA25 13.2.7.2

Piping 47298517 All Building Needs 5 Yr. Service NFPA25 14.2.1.1

Water Storage Tank 49307065 1st outside fire Pump room Needs 5 Yr. Service

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Leonardtown Middle School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Fire Pump, Building-

Check Valve

47298503 1st Fire Pump Discharge 5 Yr. Internal 78FP T/M

Wet Pipe, Building-

Alarm Valve

47298481 1st Fire Pump Room Zone 3 5 Yr. Internal VDS T/M 47298487 1st Fire Pump Room Zone 2 5 Yr. Internal VDS T/M 47298489 1st Fire Pump Room Zone 1 5 Yr. Internal VDS T/M

Fire Dep't Connection

47298529 1st Front of Building 5 Yr. Internal N/A T/M

Gauge

47298516 1st Fire Pump Room (10) Water Replace N/A T/M

Piping

47298517 All Building 5 Yr. Internal N/A T/M

Water Storage Tank

49307065 1st outside fire Pump room 5 Yr. Internal 2360 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Leonardtown Middle School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump, Building-

Fire Pump Off 1st Fire Pump Room Tested 1:49:23 PM 08/11/2020 Fire Pump Power 1st Fire Pump Room Tested 8:54:38 AM 08/12/2020 Fire Pump Running 1st Fire Pump Room Tested 8:54:45 AM 08/12/2020 Controller 1st Fire Pump Room Zone 1 Tested 1:28:42 PM 08/11/2020 Electrical Driver 1st Fire Pump Room Inspected 1:46:37 PM 08/11/2020 Jockey Controller 1st Fire Pump Room Tested 1:25:59 PM 08/11/2020 Pump 1st Fire Pump Room Tested 1:17:25 PM 08/11/2020 Transfer Switch 1st Fire Pump Room Tested 8:55:49 AM 08/12/2020 Control Valve 1st Fire Pump Room Fire Pump Bypass 2 Tested 1:23:05 PM 08/11/2020 Control Valve 1st Fire Pump Room Fire Pump Discharge Tested 1:37:40 PM 08/11/2020 Control Valve 1st Fire Pump Room Fire Pump Test Header Tested 1:37:49 PM 08/11/2020 Control Valve 1st Fire Pump Room Fire Pump Bypass 1 Tested 1:43:34 PM 08/11/2020

Wet Pipe, Building- Tamper Switch 1st mechanical room Tested 8:55:07 AM 08/12/2020 Tamper Switch 1st mechanical room Tested 8:55:16 AM 08/12/2020 Tamper Switch 1st Fire Pump Room Fire Pump Suction Tested 8:55:23 AM 08/12/2020 Tamper Switch 1st Fire Pump Room Jockey Pump Suction Tested 8:55:30 AM 08/12/2020 Tamper Switch Outside In Pit Tested 8:55:37 AM 08/12/2020 Tamper Switch Outside In Pit Tested 8:55:43 AM 08/12/2020 Waterflow Switch 1st Fire Pump Room Zone 1 Tested 1:19:43 PM 08/11/2020 Waterflow Switch 1st Fire Pump Room Zone 2 Tested 1:20:08 PM 08/11/2020 Waterflow Switch 1st Fire Pump Room Zone 3 Tested 1:20:50 PM 08/11/2020 Drain 1st Fire Pump Room Zone 1 Tested 1:21:21 PM 08/11/2020 Drain 1st Fire Pump Room Zone 2 Tested 1:21:29 PM 08/11/2020 Drain 1st Fire Pump Room Zone 3 Tested 1:46:19 PM 08/11/2020 Jockey Pump 1st Fire Pump Room Inspected 8:55:01 AM 08/12/2020 Sprinkler Box 1st Fire Pump Room Inspected 1:25:55 PM 08/11/2020 Sprinkler Box Spares 1st Fire Pump Room Inspected 1:25:48 PM 08/11/2020 Sprinkler Box Spares 1st Fire Pump Room Inspected 1:25:52 PM 08/11/2020 Backflow Prevention 1st Mechanical Room Inspected 1:24:25 PM 08/11/2020 Control Valve 1st Fire Pump Room Zone 3 Tested 1:17:43 PM 08/11/2020 Control Valve 1st Fire Pump Room Zone 2 Tested 1:17:50 PM 08/11/2020 Control Valve 1st Fire Pump Room Zone 1 Tested 1:17:58 PM 08/11/2020 Control Valve 1st Fire Pump Room Jockey Pump Discharge Tested 1:28:00 PM 08/11/2020 Control Valve 1st Fire Pump Room Jockey Pump Suction Tested 1:28:19 PM 08/11/2020 Control Valve 1st Mechanical Room Tested 1:36:25 PM 08/11/2020 Control Valve 1st Mechanical Room Tested 1:37:30 PM 08/11/2020 Control Valve 1st Fire Pump Room Fire Pump Suction Tested 1:45:48 PM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Control Valve Outside In Pit Tested 1:46:03 PM 08/11/2020 Control Valve Outside In Pit Tested 1:46:11 PM 08/11/2020 Inspector's Test 1st Fire Pump Room Zone 2 Inspected 8:54:50 AM 08/12/2020 Inspector's Test 1st Fire Pump Room Zone 1 Inspected 8:54:53 AM 08/12/2020 Inspector's Test 1st Fire Pump Room Zone 3 Inspected 8:54:57 AM 08/12/2020

Failed/Other Fire Pump, Building-

Check Valve 1st Fire Pump Discharge Inspected 1:29:26 PM 08/11/2020

Wet Pipe, Building- Gauge 1st Fire Pump Room (10) Water Inspected 1:25:44 PM 08/11/2020 Water Storage Tank 1st outside fire Pump room Inspected 8:56:01 AM 08/12/2020 Fire Dep't Connection 1st Front of Building Inspected 1:24:42 PM 08/11/2020 Piping All Building Inspected 1:25:13 PM 08/11/2020 Alarm Valve 1st Fire Pump Room Zone 3 Inspected 1:18:37 PM 08/11/2020 Alarm Valve 1st Fire Pump Room Zone 2 Inspected 1:19:05 PM 08/11/2020 Alarm Valve 1st Fire Pump Room Zone 1 Inspected 1:19:37 PM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Leonardtown Middle School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Burke’s 2241S 1st Fire Pump Room 07/16/2018 47298523

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 01448939 Automatic 3450 110 Not Listed 110 125

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298475

OS&Y Supervisory System Sensor 1 47298476

OS&Y Supervisory System Sensor 1 47298509

Lever Supervisory System Sensor 1 47298510

OS&Y Supervisory System Sensor 1 48541191

OS&Y Supervisory System Sensor 1 48541193

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD40 30 4” 1 47298492

Vane System Sensor WFD40 30 4” 1 47298488

Vane System Sensor WFD40 30 4” 1 47298480

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Rasco VDS Trim Open Supervised 4" 47298481

Internal Date 07/16/2018

Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Rasco VDS Trim Open Supervised 4" 47298487

Internal Date 07/16/2018

Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Grooved Rasco VDS Trim Open Supervised 4" 47298489

Internal Date 07/16/2010

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Wilkins 350A 4" Double Check Fire Line 07/16/1998

ScanID Water Purveyor Location Meter Account # Serial Number 47298494 N/A 1st Mechanical Room N/A J34434

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Zone 3 4" Open Supervised 47298482

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Zone 2 4" Open Supervised 47298485

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Zone 1 4" Open Supervised 47298491

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Nibco KT505 1st Fire Pump

Room Jockey Pump Discharge

1" Open Supervised 47298500

Description

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Landsdale 175 1st Fire Pump

Room Jockey Pump Suction

1" Open Supervised 47298511

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Wilkins 350A 1st

Mechanical Room

4" Open Supervised 47298478

Description Backflow

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Wilkins 350A 1st

Mechanical Room

4" Open Supervised 47298479

Description Backflow

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Mueller 2360 1st Fire Pump

Room Fire Pump Suction

4" Open Supervised 47298508

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller AE7728 Outside In Pit 3" Open Supervised 48541192

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Murller AE7728 Outside In Pit 8" Open Supervised 48541194

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Giacomini A61 120 N/A 47298486

Location

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

1st Fire Pump Room Zone 2

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Giacomini A61 120 N/A 47298490

Location 1st Fire Pump Room Zone 1

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Giacomini A61 120 N/A 47298499

Location 1st Fire Pump Room Zone 3

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Fire Pump Room Zone 1 1" 130 120 115 30 47298484

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Fire Pump Room Zone 1 1" 130 120 115 30 47298484

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Fire Pump Room Zone 1 1" 130 120 115 30 47298484

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Fire Pump Room Zone 2 1" 130 120 110 30 47298483

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Fire Pump Room Zone 2 1" 130 120 110 30 47298483

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Fire Pump Room Zone 2 1" 130 120 110 30 47298483

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Fire Pump Room Zone 3 1" 130 120 110 30 47298469

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Fire Pump Room Zone 3 1" 130 120 110 30 47298469

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Fire Pump Room Zone 3 1" 130 120 110 30 47298469

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Front of Building Wall Yes Yes 2.5" 47298529

Gauge

Location Service Date 1st Fire Pump Room (10) Water 07/16/2008

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Reliable N/A 120 None 1/4 47298516

Piping

Location Type Size Internal Date All Building Steel 1/2”-4” 07/16/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47298517

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

12 Yes No 12 unit N/A 1st Fire Pump Room 47298513

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 6 Concealed Pendant Viking 1st Fire Pump Room 47298515

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Brass Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 6 Concealed Pendant Viking 1st Fire Pump Room 47298514

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Brass Fast Response

Water Storage Tank

Location Capacity Internal Date Pressure psi Deg OK ScanID 1st outside fire Pump room 75,000 12/31/1969 . na 49307065

Type Manufacturer Model Number Above ground Mueller 2360

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Leonardtown Middle School Building-

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Master MCRTZ40-25-46-H

X 1st Fire Pump Room Zone 1 07/16/2018 11193

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 100 125 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID Emmerson AD21 1st Fire Pump Room 620727JC3 47298504

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3525 10 230/460 61.0/30 25 3525

Controller Manufacturer Model # Location Install Date Serial Number STH Not Listed 1st Fire Pump Room 07/16/2018 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 110 125 No Yes

Pump

Manufacturer Model Number Location Install Date Scan Number Peerless 3PVF11 1st Fire Pump Room 07/16/2018 47298505

Serial Number Type Orientation Aligned? Water Supply Impeller Size 39270224010 Pump Primary Vertical Yes Water Storage

Tank 7.99

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/11/20 130 15 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/11/20 102 12 308

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Hose Monster II 1 3/4"

08/11/20 88 10 445

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 102 0

90 300

66 450

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto 1st Fire Pump Room N/A na 47298519

On psi Off psi AC Type Generator Batteries Run Period Timer N/A N/A Normal

Phase Yes No N/A

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Supervisory 1st Fire Pump Room N/A 1 47298522

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Fire Pump Room 1 47298520

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Fire Pump Room N/A 1 47298521

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged by Grooved

1st Fire Pump Discharge 12/20/2009 4" 47298503

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Fire Pump Bypass 2

4" Open Supervised 47298506

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Fire Pump Discharge

4" Open Supervised 47298501

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Fire Pump Test Header

4" Open Supervised 47298502

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly AnvilStar AE7728-3A 1st Fire Pump

Room Fire Pump Bypass 1

4" Open Supervised 47298507

Description Isolation

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Leonardtown Middle School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Pump Pump 2.00% 1

Control Valve Valve 28.00% 14

Alarm Valve Valve 6.00% 3

Waterflow Switch Alarm 6.00% 3

Drain Device 6.00% 3

Backflow Prevention Valve 2.00% 1

Fire Dep't Connection Hose 2.00% 1

Piping Sprinkler 2.00% 1

Gauge Device 2.00% 1

Sprinkler Box Spares Sprinkler 4.00% 2

Sprinkler Box Sprinkler 2.00% 1

Jockey Controller Pump 2.00% 1

Controller Pump 2.00% 1

Check Valve Valve 2.00% 1

Electrical Driver Pump 2.00% 1

Fire Pump Off Alarm 2.00% 1

Fire Pump Power Alarm 2.00% 1

Fire Pump Running Alarm 2.00% 1

Inspector's Test Valve 6.00% 3

Jockey Pump Pump 2.00% 1

Tamper Switch Alarm 12.00% 6

Transfer Switch Pump 2.00% 1

Water Storage Tank Device 2.00% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Fire Pump, Building-

Control Valve 4 AE7728-3A Butterfly Isolation 07/16/2018

Electrical Driver 1 AD21

07/16/2018

Controller 1 MCRTZ40-25-46-HX

Automatic 07/16/2018

Fire Pump Off 1 MCRTZ40-25-46-HX

Supervisory 07/16/2018

Fire Pump Power 1 MCRTZ40-25-46-HX

Supervisory 07/16/2018

Fire Pump Running 1 MCRTZ40-25-46-HX

Supervisory 07/16/2018

Transfer Switch 1 MCRTZ40-25-46-HX

Auto

07/16/2018

Pump 1 3PVF11 Pump Primary

07/16/2018

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Jockey Controller 1 Not Listed

07/16/2018

Wet Pipe, Building-

Control Valve 3 AE7728-3A Butterfly Isolation 07/16/2018

Jockey Pump 1 2241S Automatic

07/16/2018

Drain 3 A61 Main

07/16/2018

Inspector's Test 3 A61

07/16/2018

Control Valve 1 175 Gate Suction 07/16/2018

Control Valve 1 2360 Butterfly Suction 07/16/2018

Control Valve 1 AE7728 OS&Y Isolation 07/16/2018

Water Storage Tank 1 2360 Above ground

07/16/2018

Control Valve 1 AE7728 OS&Y Isolation 07/16/2018

Sprinkler Box 1 N/A

07/16/2018

Control Valve 1 KT505 Butterfly Discharge 07/16/2018

Fire Dep't Connection 1 N/A Wall

07/16/2018

Alarm Valve 2 VDS Grooved

07/16/2018

Tamper Switch 1 OSY2 Lever Supervisory 07/16/2018

Tamper Switch 1 OSY2 OS&Y Supervisory 07/16/2018

Tamper Switch 4 OSYSU2 OS&Y Supervisory 07/16/2018

Waterflow Switch 3 WFD40 Vane Alarm 07/16/2018

Sprinkler Box Spares 1 11 Concealed Pendant

07/16/2018

Sprinkler Box Spares 1 V13 Concealed Pendant

07/16/2018

In Service - 10 Years to 15 Years

Wet Pipe, Building-

Alarm Valve 1 VDS Grooved

07/16/2010

Fire Pump, Building-

Check Valve 1 78FP Flanged by Grooved

12/20/2009

In Service - 15 Years to 25 Years

Wet Pipe, Building-

Gauge 1 N/A System Pressure

07/16/2005

Piping 1 N/A Steel

07/16/1998

Backflow Prevention 1 350A Double Check

07/16/1998

Control Valve 2 350A OS&Y Backflow 07/16/1998

Sprinkler Inspection Certificate For

Margaret Brent Middle School 29675 Point Lookout w Helen, Maryland 20659

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 12, 2020

Building: Margaret Brent Middle School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Margaret Brent Middle School Contact: Cathy Orolan

Address: 29675 Point Lookout w Phone: 301-475-4256

Address: Fax:

City/State/Zip: Helen, Maryland 20659 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 28 Fire Pump Building- 1 Wet Pipe 1 Wet Pipe Building- 13

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 12 25.00% 12 100.00% 3 25.00% 9 75.00% Alarm 8 16.67% 8 100.00% 8 100.00% 0 0% Valve 15 31.25% 15 100.00% 11 73.33% 4 26.67% Hose 1 2.08% 1 100.00% 0 0% 1 100.00% Pump 8 16.67% 8 100.00% 6 75.00% 2 25.00% Sprinkler 4 8.33% 4 100.00% 3 75.00% 1 25.00%

Totals 48 100% 48 100.00

% 31 64.58% 17 35.42%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Margaret Brent Middle School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 18, 2020 6:47:56 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Margaret Brent Middle School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Water Storage Tank 1 1st pump room Needs 5 Yr. Service

Fire Pump Check Valve

47298373 1st Floor Room 600 Sprinkler Room Boiler Needs 5 Yr. Service NFPA25 13.4.2.1 47298380 1st Floor Room 600 Sprinkler Room Fire Pump

Discharge Needs 5 Yr. Service NFPA25 13.4.2.1

47298391 1st Floor Room 600 Sprinkler Room Water Tank Discharge to Pump

Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 47298402 1st Floor Room 600 Sprinkler Room Flow Meter

Discharge Special Note NFPA25 4.1.5.1

Fire Dep't Connection 47298372 1st Floor Room 600 Sprinkler Room Boiler Needs Hydro Test NFPA25 4.1.5.1

Fire Pump Gauge 47298370 1st Floor Room 600 Sprinkler Room Boiler Date Expired NFPA25 4.1.5.1 47298371 1st Floor Room 600 Sprinkler Room Boiler Date Expired NFPA25 4.1.5.1

Piping 47298369 1st Floor Room 600 Sprinkler Room Boiler Needs 5 Yr. Service NFPA25 14.2.1.1

Wet Pipe, Building- Gauge

49307109 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307110 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307111 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307112 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307113 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307114 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307115 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2 49307116 1st Floor Room 600 Sprinkler Room Date Expired NFPA25 13.2.7.2

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

ScanID Location Problem Reference

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Margaret Brent Middle School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Water Storage Tank

1 1st pump room 5 Yr. Internal na T/M

Fire Pump

Check Valve

47298373 1st Floor Room 600 Sprinkler Room Boiler 5 Yr. Internal 202 T/M 47298380 1st Floor Room 600 Sprinkler Room Fire

Pump Discharge

5 Yr. Internal N/A T/M

47298391 1st Floor Room 600 Sprinkler Room Water Tank Discharge to Pump

5 Yr. Internal 758 T/M

Control Valve

47298402 1st Floor Room 600 Sprinkler Room Flow Meter Discharge

Correct 707 T/M

Fire Dep't Connection

47298372 1st Floor Room 600 Sprinkler Room Boiler Hydro Test 1001 T/M

Fire Pump Gauge

47298370 1st Floor Room 600 Sprinkler Room Boiler Replace 1001 T/M 47298371 1st Floor Room 600 Sprinkler Room Boiler Replace 1001 T/M

Piping

47298369 1st Floor Room 600 Sprinkler Room Boiler 5 Yr. Internal F13 T/M

Wet Pipe, Building-

Gauge

49307109 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307110 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307111 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307112 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307113 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307114 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307115 1st Floor Room 600 Sprinkler Room Replace 758 T/M 49307116 1st Floor Room 600 Sprinkler Room Replace 758 T/M

PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Margaret Brent Middle School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump, Building-

Control Valve 1st Boiler Sprinkler/boiler room Tested 11:18:36 AM 08/12/2020

Fire Pump Fire Pump Off 1st Floor Room 600 Sprinkler Room Tested 11:05:32 AM 08/12/2020 Fire Pump Power 1st Floor Room 600 Sprinkler Room Tested 11:05:10 AM 08/12/2020 Fire Pump Running 1st Floor Room 600 Sprinkler Room Tested 11:05:29 AM 08/12/2020 Tamper Switch 1st Floor Room 600 Sprinkler Room Water Tank

Discharge to Pump Tested 11:06:17 AM 08/12/2020

Tamper Switch 1st Floor Room 600 Sprinkler Room Fire Pump Suction

Tested 11:07:13 AM 08/12/2020

Drain 1st Floor Room 600 Sprinkler Room Boiler Old school

Tested 11:16:59 AM 08/12/2020

Drain 1st Floor Room 600 Sprinkler Room Boiler Cafeteria

Tested 11:17:05 AM 08/12/2020

Drain 1st Floor Room 600 Sprinkler Room Boiler Gym Tested 11:17:08 AM 08/12/2020 Controller 1st Floor Room 600 Sprinkler Room Tested 11:05:36 AM 08/12/2020 Electrical Driver 1st Floor Room 600 Sprinkler Room Inspected 11:16:49 AM 08/12/2020 Jockey Controller 1st Floor Room 600 Sprinkler Room Tested 11:19:52 AM 08/12/2020 Jockey Pump 1st Floor Room 600 Sprinkler Room Flow Meter Tested 11:17:46 AM 08/12/2020 Pump 1st Floor Room 600 Sprinkler Room Tested 11:03:28 AM 08/12/2020 Transfer Switch 1st Floor Room 600 Sprinkler Room Tested 11:17:55 AM 08/12/2020 Fast Response 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:03:45 AM 08/12/2020 Fast Response 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:03:49 AM 08/12/2020 Sprinkler Box 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:03:42 AM 08/12/2020 Control Valve 1st Floor Room 600 Sprinkler Room Water Tank

Discharge to Pump Tested 11:06:09 AM 08/12/2020

Control Valve 1st Floor Room 600 Sprinkler Room Fire Pump Suction

Tested 11:07:24 AM 08/12/2020

Control Valve 1st Floor Room 600 Sprinkler Room Flow Meter Tested 11:11:36 AM 08/12/2020

Wet Pipe, Building- Control Valve 1st Boiler Sprinkler/boiler room Tested 11:14:30 AM 08/12/2020 Control Valve 1st Boiler Sprinkler/boiler room Tested 11:18:02 AM 08/12/2020 Control Valve 1st Boiler Sprinkler/boiler room Tested 11:18:31 AM 08/12/2020 Inspector's Test 1st Boiler Sprinkler/boiler room Inspected 11:17:24 AM 08/12/2020 Inspector's Test 1st Boiler Sprinkler/boiler room Inspected 11:17:29 AM 08/12/2020

Wet Pipe Control Valve 1st Floor Room 600 Sprinkler Room Jockey

Pump Suction Tested 11:06:59 AM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Device Type Location Service Time Date

Waterflow Switch 1st Boiler Sprinkler/boiler room Tested 11:20:25 AM 08/12/2020 Waterflow Switch 1st Boiler Sprinkler/boiler room Tested 11:20:30 AM 08/12/2020 Waterflow Switch 1st Boiler Sprinkler/boiler room Tested 11:20:36 AM 08/12/2020 Inspector's Test 1st Boiler Sprinkler/boiler room Inspected 11:17:18 AM 08/12/2020

Failed/Other Fire Pump

Fire Dep't Connection 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:04:45 AM 08/12/2020 Fire Pump Gauge 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:04:15 AM 08/12/2020 Fire Pump Gauge 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:04:30 AM 08/12/2020 Piping 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:04:01 AM 08/12/2020 Check Valve 1st Floor Room 600 Sprinkler Room Boiler Inspected 11:04:56 AM 08/12/2020 Check Valve 1st Floor Room 600 Sprinkler Room Water Tank

Discharge to Pump Inspected 11:07:10 AM 08/12/2020

Check Valve 1st Floor Room 600 Sprinkler Room Fire Pump Discharge

Inspected 11:14:16 AM 08/12/2020

Control Valve 1st Floor Room 600 Sprinkler Room Flow Meter Discharge

Tested 11:19:34 AM 08/12/2020

Wet Pipe, Building- Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:06:48 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:07:36 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:07:56 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:15:17 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:15:32 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:15:53 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:16:16 AM 08/12/2020 Gauge 1st Floor Room 600 Sprinkler Room Inspected 11:16:32 AM 08/12/2020

Water Storage Tank 1st pump room Annual 11:20:08 AM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Margaret Brent Middle School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-ScS 1st Floor

Room 600 Sprinkler Room Jockey Pump Suction

0.75" Open Supervised 47298388

Description Suction

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Building: Margaret Brent Middle School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 683p 1st Boiler

Sprinkler/boiler room

4" Open Supervised 47298381

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 683p 1st Boiler

Sprinkler/boiler room

4" Open Supervised 47298382

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy 683p 1st Boiler

Sprinkler/boiler room

4" Open Supervised 47298383

Description Isolation

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain VSRF 135 12 47298360

Location 1st Boiler Sprinkler/boiler room

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Test and Drain VSRF 135 12 47298376

Location 1st Boiler Sprinkler/boiler room

Devices Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307116

Gauge

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307115

Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307114

Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307109

Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307110

Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307111

Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307112

Gauge

Location Service Date 1st Floor Room 600 Sprinkler Room 08/15/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Mueller 758 . na 1/4 49307113

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Margaret Brent Middle School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Hubbell LXI2900 1st Floor Room 600 Sprinkler Room 06/20/2004 A-412097-1-1

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 130 140 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID Weg 286JP 1st Floor Room 600 Sprinkler Room 03JUNO4BN1545

9 47298355

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3540 10 208-230/460 94.9/47.5 40 3540

Fire Pump Gauge

Location Discharge psi Suction psi OK ScanID 1st Floor Room 600 Sprinkler Room Boiler

na na 47298370

1st Floor Room 600 Sprinkler Room Boiler

na na 47298371

Controller Manufacturer Model # Location Install Date Serial Number Hubbell Not Listed 1st Floor Room 600 Sprinkler Room 06/20/2004 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase n/a 140 150 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number FireTrol H1002A41 1st Floor Room 600 Sprinkler Room

Flow Meter 06/20/2004 47298399

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 1768AF1126 Automatic 3460 208 2.6 135 145

Pump

Manufacturer Model Number Location Install Date Scan Number Patterson 4x3 VIP 1st Floor Room 600 Sprinkler Room 06/20/2004 47298356

Serial Number Type Orientation Aligned? Water Supply Impeller Size FP-C044408 Pump Primary Vertical n/a Yes Water Storage

Tank 8.500

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/12/20 140 4 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Flowmeter 08/12/20 135 0 300

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Flowmeter 08/12/20 125 0 450

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 135 0

125 300

122 450

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto 1st Floor Room 600 Sprinkler Room n/a na 47298172

On psi Off psi AC Type Generator Batteries Run Period Timer 140 150 Normal

Phase Yes No n/a

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Room 600 Sprinkler Room n/a 1 47298365

Fire Pump Power

Description Location Zone/Address OK ScanID Supervisory 1st Floor Room 600 Sprinkler Room 1 47298366

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory 1st Floor Room 600 Sprinkler Room n/a 1 47298367

Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47298390

OS&Y Supervisory System Sensor 1 47298386

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged 1st Floor Room 600 Sprinkler Room

Boiler 06/20/2018 4" 47298373

Flanged 1st Floor Room 600 Sprinkler Room Water Tank Discharge to Pump

08/15/2018 4" 47298391

Flanged by Grooved

1st Floor Room 600 Sprinkler Room Fire Pump Discharge

08/15/2018 4" 47298380

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Kennedy KS-FW 1st Floor

Room 600 Sprinkler Room Water Tank Discharge to Pump

4" Open Supervised 47298389

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Nibco AWWA 1st Floor 4" Open Supervised 47298387

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Room 600 Sprinkler Room Fire Pump Suction

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy n/a 1st Floor

Room 600 Sprinkler Room Flow Meter

4" Trim Open Supervised 47298385

Description Flow meter

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 707 1st Floor

Room 600 Sprinkler Room Flow Meter Discharge

4" N/A N/A 47298402

Description Discharge

Devices Drain

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Combination

1st Floor Room 600 Sprinkler Room Boiler Old school

1.5" 150 150 125 47298400

Combination

1st Floor Room 600 Sprinkler Room Boiler Cafeteria

1.5" 150 150 125 47298401

Combination

1st Floor Room 600 Sprinkler Room Boiler Gym

1.5" 150 150 125 47298403

Fast Response

Qty Type Size KFactor Finish Temperature OK ScanID 3 Pendant .25 5.6 Chrome 155 47298410

Location Description 1st Floor Room 600 Sprinkler Room Boiler 01

Qty Type Size KFactor Finish Temperature OK ScanID 3 Pendant .25 8 Brass 15 47298368

Location Description 1st Floor Room 600 Sprinkler Room Boiler brass

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

1st Floor Room 600 Sprinkler Room Boiler

Wall Yes Yes 2.5" 47298372

Piping

Location Type Size Internal Date 1st Floor Room 600 Sprinkler Room Boiler

Steel 4" 06/20/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked n/a 47298369

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

1 No No 6 unit Victaulic 1st Floor Room 600 Sprinkler Room Boiler

47298375

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Building: Margaret Brent Middle School Building-

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee 404 1st Boiler

Sprinkler/boiler room

1.25" Open Supervised 47298384

Description Bypass

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Margaret Brent Middle School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Pump Pump 2.08% 1

Sprinkler Box Sprinkler 2.08% 1

Fast Response Sprinkler 4.17% 2

Piping Sprinkler 2.08% 1

Fire Pump Gauge Pump 4.17% 2

Fire Dep't Connection Hose 2.08% 1

Check Valve Valve 6.25% 3

Fire Pump Power Alarm 2.08% 1

Fire Pump Running Alarm 2.08% 1

Fire Pump Off Alarm 2.08% 1

Controller Pump 2.08% 1

Control Valve Valve 18.75% 9

Tamper Switch Alarm 4.17% 2

Gauge Device 16.67% 8

Electrical Driver Pump 2.08% 1

Drain Device 6.25% 3

Inspector's Test Valve 6.25% 3

Jockey Pump Pump 2.08% 1

Transfer Switch Pump 2.08% 1

Jockey Controller Pump 2.08% 1

Water Storage Tank Device 2.08% 1

Waterflow Switch Alarm 6.25% 3

Device Type

Qty Model # Type Description Install Date

In Service - 90 Days - 1 Year

Water Storage Tank 1 na Above ground

12/19/2019

In Service - 2 Years to 3 Years

Waterflow Switch 3 VSRF Vane Alarm 06/20/2018

Inspector's Test 1 VSRF

06/20/2018

Fire Pump, Building-

Control Valve 1 404 Butterfly Bypass 06/20/2018

Wet Pipe, Building-

Control Valve 3 683p Butterfly Isolation 06/20/2018

Inspector's Test 2 VSRF

06/20/2018

In Service - 15 Years to 25 Years

Fire Pump

Jockey Pump 1 H1002A41 Automatic

06/20/2004

Controller 1 LXI2900

Automatic 06/20/2004

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Fire Pump Off 1 WYE

Supervisory 06/20/2004

Jockey Controller 1 Not Listed

06/20/2004

Transfer Switch 1 LX450A33E6 Auto

06/20/2004

Check Valve 1 202 Flanged

06/20/2004

Control Valve 1 KS-FW OS&Y Suction 06/20/2004

Control Valve 1 n/a Butterfly Flow meter 06/20/2004

Check Valve 1 758 Flanged

06/20/2004

Fire Pump Power 1 N/A

Supervisory 06/20/2004

Fire Pump Running 1 n/a

Supervisory 06/20/2004

Control Valve 1 AWWA OS&Y Suction 06/20/2004

Pump 1 4x3 VIP Pump Primary

06/20/2004

Check Valve 1 N/A Flanged by Grooved

06/20/2004

Fire Dep't Connection 1 1001 Wall

06/20/2004

Tamper Switch 2 OSY2 OS&Y Supervisory 06/20/2004

Drain 3 1000 Combination

06/20/2004

Control Valve 1 707 Butterfly Discharge 06/20/2004

Fast Response 1 F13 Pendant 01 06/20/2004

Fast Response 1 F13 Pendant brass 06/20/2004

Fire Pump Gauge 1 1001 Discharge

06/20/2004

Fire Pump Gauge 1 1001 Suction

06/20/2004

Piping 1 F13 Steel

06/20/2004

Sprinkler Box 1 n/a

06/20/2004

Electrical Driver 1 286JP

06/20/2004

Wet Pipe

Control Valve 1 BB-ScS Butterfly Suction 06/20/2004

Wet Pipe, Building-

Gauge 8 758 System Pressure

06/20/2004

Fire & Life Safety America, Inc. - Baltimore 19 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Margaret Brent Middle School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Fire Pump 1 Control Valve 1st Floor Room 600 Sprinkler Room Flow Meter

Discharge Special Note 47298402

Control valve must be chain and locked or electronically supervised. 2 Piping 1st Floor Room 600 Sprinkler Room Boiler Needs 5 Yr.

Service 47298369

Recommend to add a test header to the system to do a proper flow test on the fire pump. *required every 3 years (flow test)

Wet Pipe, Building- 3 Gauge 1st Floor Room 600 Sprinkler Room Date Expired 49307109

No isolation valve 4 Gauge 1st Floor Room 600 Sprinkler Room Date Expired 49307110

No isolation valve 5 Gauge 1st Floor Room 600 Sprinkler Room Date Expired 49307111

No isolation valve

Sprinkler Inspection Certificate For

Park Hall Elementary School 20343 Hermanville Road Park Hall, Maryland 20667

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 10, 2020

Building: Park Hall Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Park Hall Elementary School Contact: Cathy Orolan

Address: 20343 Hermanville Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Park Hall, Maryland 20667 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Wet Pipe 13

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 2 15.38% 2 100.00% 1 50.00% 1 50.00% Alarm 2 15.38% 2 100.00% 2 100.00% 0 0% Valve 2 15.38% 2 100.00% 1 50.00% 1 50.00% Hose 1 7.69% 1 100.00% 0 0% 1 100.00% Sprinkler 6 46.15% 6 100.00% 5 83.33% 1 16.67%

Totals 13 100% 13 100.00

% 9 69.23% 4 30.77%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Park Hall Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 11, 2020 6:50:24 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Park Hall Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Wet Pipe Alarm Valve

47297894 Sprinkler/Mechanical Room Needs 5 Yr. Service NFPA25 13.4.1.2

Fire Dep't Connection 47297898 Side of Building Near Sprinkler/Mechanical Room Needs Hydro Test NFPA25 4.1.5.1

Gauge 47297893 2 total Sprinkler/Mechanical Room Alarm Valve

(2) Water w/isolation valve Date Expired NFPA25 13.2.7.2

Piping 47297903 Sprinkler/Mechanical Room Alarm Valve Needs 5 Yr. Service NFPA25 14.2.1.1

Code References NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Park Hall Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Wet Pipe

Alarm Valve

47297894 Sprinkler/Mechanical Room 5 Yr. Internal G T/M

Fire Dep't Connection

47297898 Side of Building Near Sprinkler/Mechanical Room

Hydro Test N/A T/M

Gauge

47297893 2 total Sprinkler/Mechanical Room Alarm Valve (2) Water w/isolation valve

Replace N/A T/M

Piping

47297903 Sprinkler/Mechanical Room Alarm Valve 5 Yr. Internal WFD40 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Park Hall Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Wet Pipe

Tamper Switch Side of Building Near Sprinkler/Mechanical Room PIV

'Tested', 9:10:27 AM 08/10/2020

Waterflow Switch Sprinkler/Mechanical Room Alarm Valve Tested 9:06:57 AM 08/10/2020 Drain Sprinkler/Mechanical Room Alarm Valve Tested 9:07:26 AM 08/10/2020 Sprinkler Box Sprinkler/Mechanical Room Inspected 9:06:13 AM 08/10/2020 Sprinkler Box Spares Sprinkler/Mechanical Room Inspected 9:05:49 AM 08/10/2020 Sprinkler Box Spares Sprinkler/Mechanical Room Inspected 9:05:52 AM 08/10/2020 Sprinkler Box Spares Sprinkler/Mechanical Room Inspected 9:06:00 AM 08/10/2020 Wrenches Sprinkler/Mechanical Room Inspected 9:05:56 AM 08/10/2020 Post Indicator Valve Side of Building Near Sprinkler/Mechanical

Room Inspected 9:12:03 AM 08/10/2020

Failed/Other Wet Pipe

Gauge 2 total Sprinkler/Mechanical Room Alarm Valve (2) Water w/isolation valve

Inspected 9:09:59 AM 08/10/2020

Fire Dep't Connection Side of Building Near Sprinkler/Mechanical Room

Inspected 9:05:44 AM 08/10/2020

Piping Sprinkler/Mechanical Room Alarm Valve Inspected 9:05:21 AM 08/10/2020 Alarm Valve Sprinkler/Mechanical Room Inspected 9:06:41 AM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Park Hall Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID Lever Supervisory System Sensor 1 47297901

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor WFD40 30 4” 1 47297891

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Flanged by Grooved

Central G Trim Open Supervised 4" 47297894

Internal Date 06/18/2018

Post Indicator Valve

Manufacturer Model Location Powhatan N/A Side of Building Near Sprinkler/Mechanical Room

Type Position Status Size OK ScanID Wall Open Supervised 4" 47297902

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main Sprinkler/Mechanical Room Alarm Valve

2" 150 140 130 30 47297892

Previous Inspections

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Sprinkler/Mechanical Room

Alarm Valve 2" 150 140 130 35 47297892

December 16, 2019

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Sprinkler/Mechanical Room 2" 150 140 130 30 47297892

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Alarm Valve

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID Side of Building Near

Sprinkler/Mechanical Room Wall Yes Yes 2.5" 47297898

Gauge

Location Service Date 2 total Sprinkler/Mechanical Room Alarm Valve (2) Water w/isolation valve

06/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika N/A 140 none 1/4 47297893

Piping

Location Type Size Internal Date Sprinkler/Mechanical Room Alarm Valve

Steel 4" 06/18/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked N/A 47297903

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

6 Yes No 6 unit N/A Sprinkler/Mechanical Room

47297889

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Pendant Tyco Sprinkler/Mechanical Room 47297899

Temperature KFactor Size Finish Response Time 155 5.6 1/2” Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Pendant Tyco Sprinkler/Mechanical Room 47297897

Temperature KFactor Size Finish Response Time 155 5.6 1/2 Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 2 Pendant Tyco Sprinkler/Mechanical Room 47297895

Temperature KFactor Size Finish Response Time 165 5.6 1/2” Chrome Standard Response

Wrenches

Qty Type Manufacturer Location OK ScanID 1 Sprinkler Tyco Sprinkler/Mechanical Room 47297896

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Park Hall Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Piping Sprinkler 7.69% 1

Fire Dep't Connection Hose 7.69% 1

Sprinkler Box Spares Sprinkler 23.08% 3

Wrenches Sprinkler 7.69% 1

Sprinkler Box Sprinkler 7.69% 1

Alarm Valve Valve 7.69% 1

Waterflow Switch Alarm 7.69% 1

Drain Device 7.69% 1

Gauge Device 7.69% 1

Tamper Switch Alarm 7.69% 1

Post Indicator Valve Valve 7.69% 1

Device Type

Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years

Wet Pipe

Piping 1 WFD40 Steel

06/18/2018

Waterflow Switch 1 WFD40 Vane Alarm 06/18/2018

Drain 1 Randleman Main

06/18/2018

In Service - 5 Years to 10 Years

Wet Pipe

Sprinkler Box 1 N/A

06/18/2013

Fire Dep't Connection 1 N/A Wall

06/18/2013

Post Indicator Valve 1 N/A Wall

06/18/2013

Tamper Switch 1 OSYSU-2 Lever Supervisory 06/18/2013

Sprinkler Box Spares 1 TY3211 Pendant

06/18/2013

Sprinkler Box Spares 1 TY3231 Pendant

06/18/2013

Sprinkler Box Spares 1 TY4232 Pendant

06/18/2013

Wrenches 1 N/A Sprinkler

06/18/2013

Gauge 1 N/A System Pressure

06/18/2013

In Service - 25 Years or Older

Wet Pipe

Alarm Valve 1 G Flanged by Grooved

01/01/1993

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Park Hall Elementary School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Wet Pipe 1 Post Indicator Valve Side of Building Near Sprinkler/Mechanical

Room Passed 47297902

Very difficult to operate could not shut recommend replacement

Sprinkler Inspection Certificate For

Piney Point Elementary School 44550 Tall Timbers Road Tall Timbers, Maryland 20690

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 11, 2020

Building: Piney Point Elementary School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Piney Point Elementary School Contact: Cathy Orolan

Address: 44550 Tall Timbers Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Tall Timbers, Maryland 20690 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Fire Pump 13 Wet Pipe 18 Wet Pipe Building- 1 Wet Pipe FDC 6

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 5 13.16% 5 100.00% 2 40.00% 3 60.00% Alarm 8 21.05% 8 100.00% 8 100.00% 0 0% Valve 13 34.21% 13 100.00% 11 84.62% 2 15.38% Hose 1 2.63% 1 100.00% 0 0% 1 100.00% Pump 5 13.16% 5 100.00% 5 100.00% 0 0% Sprinkler 6 15.79% 6 100.00% 3 50.00% 3 50.00%

Totals 38 100% 38 100.00

% 29 76.32% 9 23.68%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Piney Point Elementary School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:57:15 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Piney Point Elementary School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Fire Pump Gauge

47297979 Outside Sprinkler Room 4 total In Pit Pump Gauges Suction/Discharge Jockey and Fire Pu

Date Expired NFPA25 13.2.7.2

Wet Pipe Piping

47298017 1st Floor Sprinkler Room Riser Zone #1 Needs 5 Yr. Service NFPA25 14.2.1.1 47298018 1st Floor Sprinkler Room Riser Zone #2 Needs 5 Yr. Service NFPA25 14.2.1.1

Wet Pipe, Building- Check Valve

1 outside fire pump pit Needs 5 Yr. Service NFPA25 13.4.2.1

Wet Pipe, FDC Check Valve

47298050 1st Floor Sprinkler Room FDC Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 3 1st Floor outside Sprinkler Room Needs Hydro Test NFPA25 4.1.5.1

Gauge 47298044 1st Floor Sprinkler Room Needs 5 Yr. Service

Piping 47298020 1st Floor Sprinkler Room FDC Needs 5 Yr. Service NFPA25 14.2.1.1

Water Storage Tank 2 1st Floor Sprinkler Room Needs 5 Yr. Service

Code References NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Piney Point Elementary School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Fire Pump

Gauge

47297979 Outside Sprinkler Room 4 total In Pit Pump Gauges Suction/Discharge Jockey and Fire Pu

Replace N/A T/M

Wet Pipe

Piping

47298017 1st Floor Sprinkler Room Riser Zone #1 5 Yr. Internal n/a T/M 47298018 1st Floor Sprinkler Room Riser Zone #2 5 Yr. Internal n/a T/M

Wet Pipe, Building-

Check Valve

1 outside fire pump pit 5 Yr. Internal N/A T/M

Wet Pipe, FDC

Check Valve

47298050 1st Floor Sprinkler Room FDC 5 Yr. Internal N/A T/M

Fire Dep't Connection

3 1st Floor outside Sprinkler Room Hydro Test 1 T/M

Gauge

47298044 1st Floor Sprinkler Room 5 Yr. Internal 1 T/M

Piping

47298020 1st Floor Sprinkler Room FDC 5 Yr. Internal 1 T/M

Water Storage Tank

2 1st Floor Sprinkler Room 5 Yr. Internal 1 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Piney Point Elementary School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Fire Pump

Fire Pump Off Outside Sprinkler Room In Pit Tested 10:03:48 AM 08/11/2020 Fire Pump Power Outside Sprinkler Room In Pit Tested 10:03:24 AM 08/11/2020 Fire Pump Running Outside Sprinkler Room In Pit Tested 10:03:20 AM 08/11/2020 Controller Outside Sprinkler Room In Pit Tested 10:03:10 AM 08/11/2020 Electrical Driver Outside Sprinkler Room In Pit Inspected 10:04:05 AM 08/11/2020 Jockey Controller Outside Sprinkler Room In Pit Tested 10:05:01 AM 08/11/2020 Jockey Pump Outside Sprinkler Room In Pit Inspected 10:04:14 AM 08/11/2020 Pump Outside Sprinkler Room In Pit Tested 10:11:01 AM 08/11/2020 Control Valve 1st Floor Sprinkler Room Fire Pump Test Header Tested 10:21:12 AM 08/11/2020 Control Valve Outside Sprinkler Room In Pit Fire Pump Bypass Tested 10:00:16 AM 08/11/2020 Control Valve Outside Sprinkler Room In Pit Jockey Pump

Suction Tested 10:11:17 AM 08/11/2020

Control Valve Outside Sprinkler Room In Pit Jockey Pump Discharge

Tested 10:21:31 AM 08/11/2020

Wet Pipe, FDC Backflow Prevention 1st Floor Sprinkler Sprinkler Inspected 10:05:59 AM 08/11/2020

Wet Pipe Tamper Switch 1st Floor Sprinkler Room Riser Zone #1 Tested 10:19:50 AM 08/11/2020 Tamper Switch 1st Floor Sprinkler Room Riser Zone #2 Tested 10:20:26 AM 08/11/2020 Tamper Switch Outside Sprinkler Room In Pit Fire Pump Suction Tested 10:05:15 AM 08/11/2020 Waterflow Switch 1st Floor Sprinkler Room Riser Zone #1 Tested 10:18:55 AM 08/11/2020 Waterflow Switch 1st Floor Sprinkler Room Riser Zone #2 Tested 10:19:03 AM 08/11/2020 Drain 1st Floor Sprinkler Room Riser Zone #1 Tested 10:19:13 AM 08/11/2020 Drain 1st Floor Sprinkler Room Riser Zone #2 Tested 10:19:34 AM 08/11/2020 Sprinkler Box 1st Floor Sprinkler Room FDC Inspected 10:17:53 AM 08/11/2020 Standard Response 1st Floor Sprinkler Room FDC Inspected 10:17:13 AM 08/11/2020 Standard Response 1st Floor Sprinkler Room FDC Inspected 10:17:20 AM 08/11/2020 Control Valve 1st Floor Sprinkler Room Riser Zone #1 Tested 10:19:47 AM 08/11/2020 Control Valve 1st Floor Sprinkler Room Riser Zone #2 Tested 10:20:19 AM 08/11/2020 Control Valve Outside Sprinkler Room In Pit Fire Pump

Discharge Tested 10:00:03 AM 08/11/2020

Control Valve Outside Sprinkler Room In Pit Fire Pump Suction Tested 10:05:11 AM 08/11/2020 Inspector's Test 1st Floor Boiler Inspected 10:18:42 AM 08/11/2020 Inspector's Test 1st Floor Classroom 316 Inspected 10:18:46 AM 08/11/2020

Failed/Other Fire Pump

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Gauge Outside Sprinkler Room 4 total In Pit Pump

Gauges Suction/Discharge Jockey and Fire Pu Inspected 10:03:04 AM 08/11/2020

Wet Pipe, Building- Check Valve outside fire pump pit Inspected 10:06:16 AM 08/11/2020

Wet Pipe, FDC Gauge 1st Floor Sprinkler Room Inspected 10:16:58 AM 08/11/2020 Water Storage Tank 1st Floor Sprinkler Room Inspected 10:05:42 AM 08/11/2020 Fire Dep't Connection 1st Floor outside Sprinkler Room Inspected 10:05:54 AM 08/11/2020 Piping 1st Floor Sprinkler Room FDC Inspected 10:17:49 AM 08/11/2020 Check Valve 1st Floor Sprinkler Room FDC Inspected 10:21:26 AM 08/11/2020

Wet Pipe Piping 1st Floor Sprinkler Room Riser Zone #1 Inspected 10:20:47 AM 08/11/2020 Piping 1st Floor Sprinkler Room Riser Zone #2 Inspected 10:20:57 AM 08/11/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Piney Point Elementary School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 47298015

OS&Y Supervisory Potter 1 47298012

Lever Supervisory Potter 1 47298003

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR-F 30 4” 1 47298013

Vane Potter VSR-F 30 4” 1 47298009

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Kennedy 38898 1st Floor

Sprinkler Room Riser Zone #1

4" Open Supervised 47298016

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Kennedy 38898 1st Floor

Sprinkler Room Riser Zone #2

4" Open Supervised 47298014

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Nibco WD-310 Outside

Sprinkler Room In Pit Fire Pump Discharge

6" Open Supervised 47298001

Description

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Discharge

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Mueller 2360 Outside

Sprinkler Room In Pit Fire Pump Suction

6" Open Supervised 47298004

Description Suction

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Grinnell 1 70 12 47298025

Location 1st Floor Boiler

Inspector's Test

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Grinnell 1 80 12 47298023

Location 1st Floor Classroom 316

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Sprinkler Room Riser Zone #1

2" 94 80 50 30 47298010

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room Riser

Zone #1 2" 94 80 50 30 47298010

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room Riser

Zone #1 2" 94 80 50 30 47298010

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Sprinkler Room Riser Zone #2

2" 100 80 55 47298011

Previous Inspections

June 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room Riser 2" 100 80 55 30 47298011

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Zone #2

March 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Sprinkler Room Riser

Zone #2 2" 100 80 55 30 47298011

Piping

Location Type Size Internal Date 1st Floor Sprinkler Room Riser Zone #1

Steel 2”-4” 06/19/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Missing Cast Iron Marked n/a 47298017

Piping

Location Type Size Internal Date 1st Floor Sprinkler Room Riser Zone #2

Steel 2”-4” 06/19/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Missing Cast Iron Marked n/a 47298018

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

1 Yes No 12 unit Victaulic 1st Floor Sprinkler Room FDC

47298019

Standard Response

Qty Type Size KFactor Finish Temperature OK ScanID 2 Upright .5 5.6 Brass 155 47298022

Location Description Application Orientation 1st Floor Sprinkler Room FDC brass N/A N/A

Standard Response

Qty Type Size KFactor Finish Temperature OK ScanID 2 Pendant .5 5.6 Chrome 155 47298021

Location Description Application Orientation 1st Floor Sprinkler Room FDC N/A N/A N/A

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Building: Piney Point Elementary School Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Components Check Valve

Type Location Internal Date Size OK ScanID Flanged outside fire pump pit 06/19/1996 6" 1

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Building: Piney Point Elementary School FDC

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Watts 007m1qt 2" Double Check Fire Pump Tank 09/06/1994

ScanID Water Purveyor Location Meter Account # Serial Number 47297993 N/A 1st Floor Sprinkler Sprinkler N/A 47259

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Condition of Control Valve 1 Condition of Control Valve 2 N/A N/A

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Sprinkler Room FDC 06/19/1996 4" 47298050

Devices Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Floor outside Sprinkler

Room Siamese Yes Yes 2.5" 3

Gauge

Location Service Date 1st Floor Sprinkler Room 06/19/1996

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Grinnell 1 70 n/a 1/2 47298044

Piping

Location Type Size Internal Date 1st Floor Sprinkler Room FDC

Steel 4" 06/19/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal n/a n/a n/a 47298020

Water Storage Tank

Location Capacity Internal Date Pressure psi Deg OK ScanID 1st Floor Sprinkler Room 75,000 06/19/1996 0 45 2

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Type Manufacturer Model Number In ground Grinnell 1

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Fire Pump Testing Generated by: BuildingReports.com

Building: Piney Point Elementary School

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number Firetrol FTA1350-AM30H Outside Sprinkler Room In Pit 06/19/1996 479525-01RE

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Phase Reversal N/A 70 105 No No

Electrical Manufacturer Model # Location Serial Number ScanID Baldor 40HO68W303 Outside Sprinkler Room In Pit 97040 47298000

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3500 10 208 88 30 3500

Controller Manufacturer Model # Location Install Date Serial Number Firetrol Not Listed Outside Sprinkler Room In Pit 06/19/1996 Not Listed

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 85 105 No No

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Bluffton 1303007156 Outside Sprinkler Room In Pit 06/19/1996 47297994

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 1707270512 Automatic 3450 208-230/

460 2.6/1.3 85 105

Pump

Manufacturer Model Number Location Install Date Scan Number Peerless 5PVF7 Outside Sprinkler Room In Pit 06/19/1996 47297983

Serial Number Type Orientation Aligned? Water Supply Impeller Size 170638A Pump Primary Vertical Yes Water Storage

Tank 6.02

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/11/20 70 3 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Other 08/11/20 58 1 501

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/11/20 45 0 690

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 65.3 0

54 500

42.8 750

Alarms Fire Pump Off

Description Location Time Delay Zone/Address OK ScanID Supervisory Outside Sprinkler Room In Pit N/A 1 47297991

Fire Pump Power

Fire & Life Safety America, Inc. - Baltimore 15 08/24/2020

Description Location Zone/Address OK ScanID Supervisory Outside Sprinkler Room In Pit 1 47298005

Fire Pump Running

Description Location Time Delay Zone/Address OK ScanID Supervisory Outside Sprinkler Room In Pit N/A 1 47297980

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Nibco GD-4765-BN 1st Floor

Sprinkler Room Fire Pump Test Header

6" Closed Supervised 47298024

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Nibco LD 3510-8 Outside

Sprinkler Room In Pit Fire Pump Bypass

6" Open Supervised 47298002

Description Bypass

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Ball Watts N/A Outside

Sprinkler Room In Pit Jockey Pump Suction

1" Open Supervised 47298006

Description Suction

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate United 137 Outside

Sprinkler Room In Pit Jockey Pump Discharge

1" Open Supervised 47298007

Description Discharge

Devices Gauge

Fire & Life Safety America, Inc. - Baltimore 16 08/24/2020

Location Service Date Outside Sprinkler Room 4 total In Pit Pump Gauges Suction/Discharge Jockey and Fire Pu

06/19/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika N/A 100 None 1/4 47297979

Fire & Life Safety America, Inc. - Baltimore 17 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Piney Point Elementary School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Control Valve Valve 21.05% 8

Gauge Device 5.26% 2

Controller Pump 2.63% 1

Fire Pump Running Alarm 2.63% 1

Fire Pump Power Alarm 2.63% 1

Fire Pump Off Alarm 2.63% 1

Electrical Driver Pump 2.63% 1

Jockey Pump Pump 2.63% 1

Jockey Controller Pump 2.63% 1

Tamper Switch Alarm 7.89% 3

Water Storage Tank Device 2.63% 1

Fire Dep't Connection Hose 2.63% 1

Backflow Prevention Valve 2.63% 1

Check Valve Valve 5.26% 2

Pump Pump 2.63% 1

Standard Response Sprinkler 5.26% 2

Piping Sprinkler 7.89% 3

Sprinkler Box Sprinkler 2.63% 1

Inspector's Test Valve 5.26% 2

Waterflow Switch Alarm 5.26% 2

Drain Device 5.26% 2

Device Type

Qty Model # Type Description Install Date

In Service - 15 Years to 25 Years

Fire Pump

Electrical Driver 1 40HO68W303

06/19/1996

Jockey Pump 1 1303007156 Automatic

06/19/1996

Controller 1 FTA1350-AM30H

Automatic 06/19/1996

Jockey Controller 1 Not Listed

06/19/1996

Fire Pump Off 1 N/A

Supervisory 06/19/1996

Fire Pump Power 1 N/A

Supervisory 06/19/1996

Fire Pump Running 1 N/A

Supervisory 06/19/1996

Control Valve 1 GD-4765-BN Butterfly Isolation 06/19/1996

Control Valve 1 LD 3510-8 Butterfly Bypass 06/19/1996

Pump 1 5PVF7 Pump Primary

06/19/1996

Control Valve 1 137 Gate Discharge 06/19/1996

Control Valve 1 N/A Ball Suction 06/19/1996

Gauge 1 N/A Supply Pressure

06/19/1996

Wet Pipe

Standard Response 1 1 Upright brass 06/19/1996

Fire & Life Safety America, Inc. - Baltimore 18 08/24/2020

Control Valve 2 38898 OS&Y Isolation 06/19/1996

Control Valve 1 2360 Gate Suction 06/19/1996

Control Valve 1 WD-310 Butterfly Discharge 06/19/1996

Tamper Switch 1 OSYSU-1 Lever Supervisory 06/19/1996

Tamper Switch 2 OSYSU-2 OS&Y Supervisory 06/19/1996

Waterflow Switch 2 VSR-F Vane Alarm 06/19/1996

Standard Response 1 722A Pendant N/A 06/19/1996

Piping 2 n/a Steel

06/19/1996

Drain 2 N/A Main

06/19/1996

Sprinkler Box 1 1

06/19/1996

Wet Pipe, Building-

Check Valve 1 N/A Flanged

06/19/1996

Wet Pipe, FDC

Check Valve 1 N/A Grooved

06/19/1996

Piping 1 1 Steel

06/19/1996

In Service - 25 Years or Older

Wet Pipe

Inspector's Test 2 1

09/06/1994

Wet Pipe, FDC

Fire Dep't Connection 1 1 Siamese

09/06/1994

Gauge 1 1 Supply Pressure

09/06/1994

Water Storage Tank 1 1 In ground

09/06/1994

Backflow Prevention 1 007m1qt Double Check

09/06/1994

Sprinkler Inspection Certificate For

Spring Ridge Middle School 19856 Three Notch Road Lexington Park, Maryland 20653

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 10, 2020

Building: Spring Ridge Middle School Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: Spring Ridge Middle School Contact: Cathy Orolan

Address: 19856 Three Notch Road Phone: 301-475-4256

Address: Fax:

City/State/Zip: Lexington Park, Maryland 20653 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Wet Pipe 29

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 3 7.50% 3 100.00% 0 0% 3 100.00% Alarm 6 15.00% 6 100.00% 5 83.33% 1 16.67% Valve 21 52.50% 21 100.00% 17 80.95% 4 19.05% Hose 1 2.50% 1 100.00% 0 0% 1 100.00% Pump 6 15.00% 6 100.00% 6 100.00% 0 0% Sprinkler 3 7.50% 3 100.00% 2 66.67% 1 33.33%

Totals 40 100% 40 100.00

% 30 75.00% 10 25.00%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: Spring Ridge Middle School

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 11, 2020 6:50:11 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: Spring Ridge Middle School The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Check Valve 47297882 Mechanical Phase 4 Needs 5 Yr. Service NFPA25 13.4.2.1

Water Storage Tank 1 outside sprinkler room Needs 5 Yr. Service

Wet Pipe Check Valve

47297865 Fire Pump Room Needs 5 Yr. Service NFPA25 13.4.2.1

Control Valve 47297853 Fire Pump Room Flow Meter Bypass Special Note NFPA25 4.1.5.1 47297854 Fire Pump Room Flow Meter Bypass Special Note NFPA25 4.1.5.1

Fire Dep't Connection 47297861 Side of Building Near FACP Room Needs Hydro Test NFPA25 4.1.5.1

Gauge 2 Fire Pump Room 4 total Date Expired NFPA25 13.2.7.2 4 mechanical room 6 total Date Expired NFPA25 13.2.7.2

Piping 47297866 All Building Needs 5 Yr. Service NFPA25 14.2.1.1

Tamper Switch 47297851 Fire Pump Room Fire Pump Suction Special Note NFPA25 4.1.5.1

Code References NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: Spring Ridge Middle School

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Check Valve

47297882 Mechanical Phase 4 5 Yr. Internal 114 T/M

Water Storage Tank

1 outside sprinkler room 5 Yr. Internal na T/M

Wet Pipe

Check Valve

47297865 Fire Pump Room 5 Yr. Internal 717 T/M

Control Valve

47297853 Fire Pump Room Flow Meter Bypass Correct 705 T/M 47297854 Fire Pump Room Flow Meter Bypass Correct 705 T/M

Fire Dep't Connection

47297861 Side of Building Near FACP Room Hydro Test N/A T/M

Gauge

2 Fire Pump Room 4 total Replace 3PVF11 T/M 4 mechanical room 6 total Replace 3PVF11 T/M

Piping

47297866 All Building 5 Yr. Internal N/A T/M

Tamper Switch

47297851 Fire Pump Room Fire Pump Suction Correct OSY2 T/M PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: Spring Ridge Middle School The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Wet Pipe

Tamper Switch Fire Pump Room Tank Fill Tested 8:39:38 AM 08/10/2020 Waterflow Switch Fire Pump Room Fire Pump Room Wet System Tested 8:35:53 AM 08/10/2020 Waterflow Switch Mechanical Tested 8:47:46 AM 08/10/2020 Waterflow Switch Mechanical Tested 8:47:53 AM 08/10/2020 Waterflow Switch Mechanical Tested 8:47:58 AM 08/10/2020 Controller Fire Pump Room Tested 8:39:58 AM 08/10/2020 Electrical Driver Fire Pump Room Inspected 8:49:09 AM 08/10/2020 Jockey Controller Fire Pump Room Tested 8:40:06 AM 08/10/2020 Jockey Pump Fire Pump Room Inspected 8:42:19 AM 08/10/2020 Pump Fire Pump Room Tested 8:42:00 AM 08/10/2020 Transfer Switch Fire Pump Room Tested 8:40:02 AM 08/10/2020 Sprinkler Box Fire Pump Room Inspected 8:34:43 AM 08/10/2020 Sprinkler Box Spares Fire Pump Room Inspected 8:34:49 AM 08/10/2020 Control Valve Fire Pump Room Fire Pump Room Wet System Tested 8:35:45 AM 08/10/2020 Control Valve Fire Pump Room Jockey Pump Discharge Tested 8:36:18 AM 08/10/2020 Control Valve Fire Pump Room Jockey Pump Suction Tested 8:37:02 AM 08/10/2020 Control Valve Fire Pump Room Fire Pump Test Header Tested 8:38:36 AM 08/10/2020 Control Valve Fire Pump Room Tank Drain Tested 8:38:57 AM 08/10/2020 Control Valve Fire Pump Room Fire Pump Suction Tested 8:39:05 AM 08/10/2020 Control Valve Fire Pump Room Tank Fill Tested 8:39:53 AM 08/10/2020 Control Valve Fire Pump Room Fire Pump Discharge Tested 8:49:03 AM 08/10/2020

Alarm Valve Mechanical Feeds Kitchen Inspected 8:45:11 AM 08/10/2020 Alarm Valve Mechanical Phase 1-2 Inspected 8:46:57 AM 08/10/2020 Alarm Valve Mechanical Supply Inspected 8:47:14 AM 08/10/2020 Control Valve Mechanical Phase 1-2 Tested 8:44:33 AM 08/10/2020 Control Valve Mechanical Phase 4 Tested 8:44:41 AM 08/10/2020 Control Valve Mechanical Kitchen Tested 8:44:46 AM 08/10/2020 Inspector's Test Mechanical Phase 1-2 Inspected 8:47:18 AM 08/10/2020 Inspector's Test Mechanical Phase 4 Inspected 8:47:35 AM 08/10/2020 Inspector's Test Mechanical Kitchen Inspected 8:47:39 AM 08/10/2020

Failed/Other Wet Pipe

Tamper Switch Fire Pump Room Fire Pump Suction Tested 8:39:32 AM 08/10/2020 Gauge Fire Pump Room 4 total Inspected 8:48:19 AM 08/10/2020 Gauge mechanical room 6 total Inspected 8:49:28 AM 08/10/2020 Fire Dep't Connection Side of Building Near FACP Room Inspected 8:35:10 AM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Device Type Location Service Time Date Piping All Building Inspected 8:35:35 AM 08/10/2020 Check Valve Fire Pump Room Inspected 8:36:38 AM 08/10/2020 Control Valve Fire Pump Room Flow Meter Bypass Tested 8:37:52 AM 08/10/2020 Control Valve Fire Pump Room Flow Meter Bypass Tested 8:38:28 AM 08/10/2020

Water Storage Tank outside sprinkler room Inspected 8:42:16 AM 08/10/2020 Check Valve Mechanical Phase 4 Inspected 8:46:46 AM 08/10/2020

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Spring Ridge Middle School

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Controller Manufacturer Model # Location Install Date Serial Number TornaTech GPR-460/25/3/60 Fire Pump Room 06/18/2013 Z 134392

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 85 100 No Yes

Electrical Manufacturer Model # Location Serial Number ScanID Weg CC029A Fire Pump Room 12685428 47297856

Timing Min/Sec

Full Run Volts Amps Horsepower Rated Speed 3530 10 208-230/460 64.10-58/29.00 25 3530

Controller Manufacturer Model # Location Install Date Serial Number TornaTech JP3-460/0.75/3/60 Fire Pump Room 06/18/2013 Z131523

AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase N/A 100 110 No Yes

Jockey Pump

Manufacturer Model Number Location Install Date Scan Number Bluffton MOD130324210

3 Fire Pump Room 06/18/2013 47297867

Serial Number Type Horse Pwr Rated Spd Volts Amps On psi Off psi 1408210080 Automatic 3450 208-230/

460 3.0/1.5 100 110

Pump

Manufacturer Model Number Location Install Date Scan Number Peerless Pump 3PVF11 Fire Pump Room 06/18/2013 47297868

Serial Number Type Orientation Aligned? Water Supply Impeller Size 9927088637-10-A

Pump Primary Vertical Yes Water Storage Tank

8

Pump Tests Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/10/20 112 3 0

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Other 08/10/20 95 1 307

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Discharge Device Date Disch. PSI Suct. PSI GPM RPM Oil Pressure Water Temperature Hose Monster II 1 3/4"

08/10/20 68 0 454

Amps A Amps B Amps C Volts A-B Volts B-C Volts A-C

Pump Rating

Net Pressure Gallons Per Minute Rotations Per Minute

Amps Volts

A B C A-B B-C A-C 104 0

90 300

65.9 450

Transfer Switch

Type Location Time Meter (hrs) Time Delay OK ScanID Auto Fire Pump Room N/A N/A 47297862

On psi Off psi AC Type Generator Batteries Run Period Timer

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

N/A N/A Normal Phase

Yes No 10

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory System Sensor 1 47297849

OS&Y Supervisory System Sensor 1 47297851

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane System Sensor

N/A WFD 39 1

1/4” 1 47297846

Vane System Sensor wfd40 30 4 1 47297871

Vane System Sensor wfd40 30 4 1 47297872

Vane System Sensor wfd40 30 4 1 47297870

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved Fire Pump Room 06/18/2018 6" 47297865

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Milwaukee BB-SCS Fire Pump

Room Fire Pump Room Wet System

1.25" Open Supervised 47297847

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Ball FPPI WOG Fire Pump

Room Jockey Pump Discharge

1" Open Supervised 47297858

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Ball FPPI WOG Fire Pump

Room Jockey Pump Suction

1" Open Supervised 47297857

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Butterfly Victaulic 705 Fire Pump Room Fire Pump Test Header

3" Open Supervised 47297890

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Fire Pump

Room Tank Drain

2.5" Closed Supervised 47297850

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Gate Mueller R1365 Fire Pump

Room Fire Pump Suction

6" Open Supervised 47297852

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Mueller RWGV Fire Pump

Room Tank Fill

4" Closed Supervised 47297848

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Fire Pump

Room Fire Pump Discharge

6" Open Supervised 47297855

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Fire Pump

Room Flow Meter Bypass

4" Closed Supervised 47297853

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Fire Pump 4" Open Supervised 47297854

Fire & Life Safety America, Inc. - Baltimore 11 08/24/2020

Room Flow Meter Bypass

Description Isolation

Devices Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID Side of Building Near FACP

Room Wall Yes Yes 2.5" 47297861

Gauge

Location Service Date Fire Pump Room 4 total 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Peerless Pump 3PVF11 na na 1/4 2

Gauge

Location Service Date mechanical room 6 total 07/18/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Peerless Pump 3PVF11 na na 1/4 4

Piping

Location Type Size Internal Date All Building Steel 1/2”-6” 06/18/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Cast Iron Marked N/A 47297866

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

3 No No 6 unit N/A Fire Pump Room 47297859

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 3 Concealed Pendant Victaulic Fire Pump Room 47297860

Temperature KFactor Size Finish Response Time 155 5.6 N/A Brass Fast Response

Fire & Life Safety America, Inc. - Baltimore 12 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: Spring Ridge Middle School

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Sprinkler Box Sprinkler 2.50% 1

Sprinkler Box Spares Sprinkler 2.50% 1

Fire Dep't Connection Hose 2.50% 1

Piping Sprinkler 2.50% 1

Control Valve Valve 32.50% 13

Waterflow Switch Alarm 10.00% 4

Check Valve Valve 5.00% 2

Tamper Switch Alarm 5.00% 2

Controller Pump 2.50% 1

Transfer Switch Pump 2.50% 1

Jockey Controller Pump 2.50% 1

Pump Pump 2.50% 1

Water Storage Tank Device 2.50% 1

Jockey Pump Pump 2.50% 1

Alarm Valve Valve 7.50% 3

Inspector's Test Valve 7.50% 3

Gauge Device 5.00% 2

Electrical Driver Pump 2.50% 1

Device Type

Qty Model # Type Description Install Date

In Service - 90 Days - 1 Year

Water Storage Tank 1 na Above ground

12/16/2019

In Service - 2 Years to 3 Years

Alarm Valve 3 114 Grooved

06/18/2018

Control Valve 3 709 Butterfly Isolation 06/18/2018

Inspector's Test 3 709

06/18/2018

In Service - 5 Years to 10 Years

Check Valve 1 114 Grooved

06/18/2014

Wet Pipe

Jockey Pump 1 MOD1303242103 Automatic

06/18/2013

Control Valve 2 WOG Ball Main Control 06/18/2013

Control Valve 1 BB-SCS Butterfly Isolation 06/18/2013

Control Valve 1 R1365 Gate Main Control 06/18/2013

Control Valve 1 RWGV OS&Y Main Control 06/18/2013

Fire Dep't Connection 1 N/A Wall

06/18/2013

Piping 1 N/A Steel

06/18/2013

Sprinkler Box 1 N/A

06/18/2013

Gauge 2 3PVF11 System Pressure

06/18/2013

Pump 1 3PVF11 Pump Primary

06/18/2013

Fire & Life Safety America, Inc. - Baltimore 13 08/24/2020

Tamper Switch 2 OSY2 OS&Y Supervisory 06/18/2013

Waterflow Switch 3 wfd40 Vane Alarm 06/18/2013

Waterflow Switch 1 WFD Vane Alarm 06/18/2013

Controller 1 GPR-460/25/3/60

Automatic 06/18/2013

Jockey Controller 1 JP3-460/0.75/3/60

06/18/2013

Transfer Switch 1 GPU-460/25/3/60 Auto

06/18/2013

Check Valve 1 717 Grooved

06/18/2013

Control Valve 5 705 Butterfly Isolation 06/18/2013

Sprinkler Box Spares 1 3802 Concealed Pendant

06/18/2013

Electrical Driver 1 CC029A

06/18/2013

Fire & Life Safety America, Inc. - Baltimore 14 08/24/2020

Notes & Recommendations Generated by: BuildingReports.com

Building: Spring Ridge Middle School

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.

Note Device Type Location Comment ScanID

Wet Pipe 1 Control Valve Fire Pump Room Flow Meter Bypass Special Note 47297853

Tamper did not annunciate to FACP 2 Control Valve Fire Pump Room Flow Meter Bypass Special Note 47297854

Tamper did not annunciate to FACP 3 Gauge Fire Pump Room 4 total Date Expired 2

4 total 4 Tamper Switch Fire Pump Room Fire Pump Suction Special Note 47297851

Would not report supervisory to the panel, adjusted switch and could not get signal

Sprinkler Inspection Certificate For

St. Mary’s Central Administration Building

23160 Moakley Street Leonardtown, Maryland 20650

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Annual Inspection Inspection Date Aug 12, 2020

Building: St. Mary’s Central Administration Building Company: Fire & Life Safety America, Inc. - Baltimore Contact: Cathy Orolan Contact: Calio Vannarath

Title: Admin Title: Inspector

Fire & Life Safety America, Inc. - Baltimore 1 08/24/2020

Executive Summary Generated by: BuildingReports.com

Building Information Building: St. Mary’s Central Administration Building Contact: Cathy Orolan

Address: 23160 Moakley Street Phone: ?(240) 561-0780?

Address: Fax:

City/State/Zip: Leonardtown, Maryland 20650 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Fire & Life Safety America, Inc. - Baltimore Inspector: Calio Vannarath

Address: 1340 Charwood Road Suite P Phone: 410-371-9440

Address: Fax:

City/State/Zip: Hanover, Maryland 21076 Mobile:

Country: United States of America Email: [email protected]

System Control Unit System Type System Location Protected Area Devices Wet Pipe Building- 20 Wet Pipe Building- 4

Fire & Life Safety America, Inc. - Baltimore 2 08/24/2020

Inspection Summary Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Device 6 25.00% 6 100.00% 2 33.33% 4 66.67% Alarm 4 16.67% 4 100.00% 4 100.00% 0 0% Valve 8 33.33% 8 100.00% 5 62.50% 3 37.50% Hose 1 4.17% 1 100.00% 0 0% 1 100.00% Sprinkler 5 20.83% 5 100.00% 3 60.00% 2 40.00%

Totals 24 100% 24 100.00

% 14 58.33% 10 41.67%

Certification Company: Fire & Life Safety America, Inc. - Baltimore Building: St. Mary’s Central Administration Building

Inspector: Calio Vannarath Contact: Cathy Orolan

Signed: Aug 12, 2020 8:59:09 AM Signed:

Fire & Life Safety America, Inc. - Baltimore 3 08/24/2020

Discrepancy Report Generated by: BuildingReports.com

Building: St. Mary’s Central Administration Building The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Reference

Wet Pipe, Building- Alarm Valve

55938212 1st Floor Outside Sprinkler Room Zone #1 Needs 5 Yr. Service NFPA25 13.4.1.2 55938213 1st Floor Outside Sprinkler Room Zone #1 Needs 5 Yr. Service NFPA25 13.4.1.2

Check Valve 49302567 1st Floor Outside Sprinkler Room FDC Needs 5 Yr. Service NFPA25 13.4.2.1

Fire Dep't Connection 49302568 1st Floor Outside Sprinkler Room FDC Needs Hydro Test NFPA25 4.1.5.1

Piping 49302556 1st Floor Outside Sprinkler Room Zone #2 Needs 5 Yr. Service NFPA25 14.2.1.1 49302558 1st Floor Outside Sprinkler Room Zone #1 Needs 5 Yr. Service NFPA25 14.2.1.1

Building- Wet Pipe Gauge

55938253 sprinkler room Needs 5 Yr. Service 55938254 sprinkler room Date Expired NFPA25 13.2.7.2 55938255 sprinkler room Date Expired NFPA25 13.2.7.2 55938256 sprinkler room Date Expired NFPA25 13.2.7.2

Code References NFPA25 13.4.1.2 Alarm valves and their associated strainers, filters, and restriction orifices shall be inspected internally

every 5 years unless tests indicate a greater frequency is necessary. NFPA25 13.4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate correctly, move

freely, and are in good condition. NFPA25 4.1.5.1 The property owner or designated representative shall correct or repair deficiencies or impairments. NFPA25 14.2.1.1 An assessment of the internal condition of piping shall be conducted at a minimum of every 5 years for

the purpose of inspecting for the presence of foreign organic and inorganic material. NFPA25 13.2.7.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge.

Fire & Life Safety America, Inc. - Baltimore 4 08/24/2020

Proposed Solutions Report

Generated by: BuildingReports.com

Building: St. Mary’s Central Administration Building

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Wet Pipe, Building-

Alarm Valve

55938212 1st Floor Outside Sprinkler Room Zone #1 5 Yr. Internal VSR T/M 55938213 1st Floor Outside Sprinkler Room Zone #1 5 Yr. Internal VSR T/M

Check Valve

49302567 1st Floor Outside Sprinkler Room FDC 5 Yr. Internal 717 T/M

Fire Dep't Connection

49302568 1st Floor Outside Sprinkler Room FDC Hydro Test 717 T/M

Piping

49302556 1st Floor Outside Sprinkler Room Zone #2 5 Yr. Internal n/a T/M 49302558 1st Floor Outside Sprinkler Room Zone #1 5 Yr. Internal n/a T/M

Building- Wet Pipe

Gauge

55938253 sprinkler room 5 Yr. Internal N/A T/M 55938254 sprinkler room Replace N/A T/M 55938255 sprinkler room Replace N/A T/M 55938256 sprinkler room Replace N/A T/M

PO #: (none) T/M

Fire & Life Safety America, Inc. - Baltimore 5 08/24/2020

Inspection & Testing Generated by: BuildingReports.com

Building: St. Mary’s Central Administration Building The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Wet Pipe, Building-

Tamper Switch 1st Floor Outside Sprinkler Room Backflow #1 Tested 7:33:51 AM 08/12/2020 Tamper Switch 1st Floor Outside Sprinkler Room Backflow #2 Tested 7:34:35 AM 08/12/2020 Waterflow Switch 1st Floor Outside Sprinkler Room Zone #2 Tested 7:39:36 AM 08/12/2020 Waterflow Switch 1st Floor Outside Sprinkler Room Zone #1 Tested 7:39:58 AM 08/12/2020 Drain 1st Floor Outside Sprinkler Room Zone #2 Tested 7:39:43 AM 08/12/2020 Drain 1st Floor Outside Sprinkler Room Zone #1 Tested 7:40:02 AM 08/12/2020 Sprinkler Box 1st Floor Outside Sprinkler Room Inspected 7:33:27 AM 08/12/2020 Sprinkler Box Spares 1st Floor Outside Sprinkler Room Inspected 7:33:18 AM 08/12/2020 Sprinkler Box Spares 1st Floor Outside Sprinkler Room Inspected 7:33:23 AM 08/12/2020 Backflow Prevention 1st Floor Outside Sprinkler Room Inspected 7:34:27 AM 08/12/2020 Control Valve 1st Floor Outside Sprinkler Room Backflow #1 Tested 7:33:45 AM 08/12/2020 Control Valve 1st Floor Outside Sprinkler Room Backflow #2 Tested 7:34:32 AM 08/12/2020 Control Valve 1st Floor Outside Sprinkler Room Zone #1 Tested 7:35:34 AM 08/12/2020 Control Valve 1st Floor Outside Sprinkler Room Zone #2 Tested 7:44:25 AM 08/12/2020

Failed/Other Building- Wet Pipe

Gauge sprinkler room Inspected 7:43:40 AM 08/12/2020 Gauge sprinkler room Inspected 7:43:50 AM 08/12/2020 Gauge sprinkler room Inspected 7:44:00 AM 08/12/2020 Gauge sprinkler room Inspected 7:44:11 AM 08/12/2020

Wet Pipe, Building- Fire Dep't Connection 1st Floor Outside Sprinkler Room FDC Inspected 7:33:12 AM 08/12/2020 Piping 1st Floor Outside Sprinkler Room Zone #1 Inspected 7:35:11 AM 08/12/2020 Piping 1st Floor Outside Sprinkler Room Zone #2 Inspected 7:44:37 AM 08/12/2020 Alarm Valve 1st Floor Outside Sprinkler Room Zone #1 Inspected 7:36:00 AM 08/12/2020 Alarm Valve 1st Floor Outside Sprinkler Room Zone #1 Inspected 7:39:24 AM 08/12/2020 Check Valve 1st Floor Outside Sprinkler Room FDC Inspected 7:32:45 AM 08/12/2020

Fire & Life Safety America, Inc. - Baltimore 6 08/24/2020

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: St. Mary’s Central Administration Building Building-

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Manufacturer Zone/Address OK ScanID OS&Y Supervisory Potter 1 49302564

OS&Y Supervisory Potter 1 49302566

Waterflow Switch

Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter VSR 30 4” 1 49302555

Vane N/A Potter N/A VSR 30 4” 1 49302554

Components Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Potter N/A VSR Trim Open Supervised 4" 55938213

Internal Date 12/31/1969

Alarm Valve

Type Manufacturer Model # Position Status Size OK ScanID Grooved Potter N/A VSR Trim Open Supervised 4" 55938212

Internal Date 12/31/1969

Backflow Prevention

Manufacturer Model # Size Type Service Type Install Date Wilkins 350 6" Double Check Fire Line 08/14/2002

ScanID Water Purveyor Location Meter Account # Serial Number 49302557 N/A 1st Floor Outside Sprinkler Room N/A J07741

Initial Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Held At Repairs or Notes

Final Test

Check Valve 1 Check Valve 2 Relief Valve Pressure Vacuum Breaker

Fire & Life Safety America, Inc. - Baltimore 7 08/24/2020

Held At Condition of Control Valve 1 Condition of Control Valve 2 n/a n/a

Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st Floor Outside Sprinkler Room

FDC 08/14/2018 4" 49302567

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Clow AWW 1st Floor

Outside Sprinkler Room Backflow #1

6" Open Supervised 49302563

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Clow AWW 1st Floor

Outside Sprinkler Room Backflow #2

6" Open Supervised 49302565

Description Main Control

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy n/a 1st Floor

Outside Sprinkler Room Zone #1

4" Open Supervised 49302561

Description Isolation

Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Kennedy n/a 1st Floor

Outside Sprinkler Room Zone #2

4" Open Supervised 49302562

Description Isolation

Devices Drain

Fire & Life Safety America, Inc. - Baltimore 8 08/24/2020

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Outside Sprinkler Room Zone #2

2" 70 65 50 30 49302560

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #2 2" 70 65 50 30 49302560

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #2 2" 70 65 50 30 49302560

Current Inspection

Type Location Size Supply psi Restored psi Residual psi Sec OK ScanID

Main 1st Floor Outside Sprinkler Room Zone #1

2" 70 65 50 49302559

Previous Inspections

June 9, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #1 2" 70 65 50 30 49302559

March 10, 2020

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main 1st Floor Outside Sprinkler

Room Zone #1 2" 70 65 50 30 49302559

Fire Dep't Connection

Location Type BallDrip Rotating Swivels Size OK ScanID 1st Floor Outside Sprinkler

Room FDC Siamese Yes Yes 2.5" 49302568

Gauge

Location Service Date sprinkler room 10/01/2019

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure N/A N/A N/A N/A 1/4 55938253

Gauge

Location Service Date sprinkler room 10/01/2019

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure N/A N/A N/A N/A 1/4 55938254

Gauge

Location Service Date sprinkler room 10/01/2019

Fire & Life Safety America, Inc. - Baltimore 9 08/24/2020

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure N/A N/A N/A N/A 1/4 55938255

Gauge

Location Service Date sprinkler room 10/01/2019

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure N/A N/A N/A N/A 1/4 55938256

Piping

Location Type Size Internal Date 1st Floor Outside Sprinkler Room Zone #1

Steel 1/2” - 4” 08/14/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked N/a 49302558

Piping

Location Type Size Internal Date 1st Floor Outside Sprinkler Room Zone #2

Steel 1/2” - 4” 08/14/2018

Hangers Braces Fittings Identified Antifreeze ScanID Normal Normal Malleable Iron Marked N/a 49302556

Sprinkler Box

Qty Tool Available? SIN List? Size Manufacturer Location OK ScanID

12 Yes No 12 unit steel 1st Floor Outside Sprinkler Room

49302549

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 3 Pendant Viking 1st Floor Outside Sprinkler

Room 49302551

Temperature KFactor Size Finish Response Time 155 4.2 1/2” Chrome Fast Response

Sprinkler Box Spares

Qty Type Manufacturer Location OK ScanID 9 Pendant Tyco 1st Floor Outside Sprinkler

Room 49302550

Temperature KFactor Size Finish Response Time 155 4.2 1/2” Chrome Fast Response

Fire & Life Safety America, Inc. - Baltimore 10 08/24/2020

Inventory & Warranty Report

Generated by: BuildingReports.com

Building: St. Mary’s Central Administration Building

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Check Valve Valve 4.17% 1

Fire Dep't Connection Hose 4.17% 1

Sprinkler Box Spares Sprinkler 8.33% 2

Sprinkler Box Sprinkler 4.17% 1

Control Valve Valve 16.67% 4

Tamper Switch Alarm 8.33% 2

Backflow Prevention Valve 4.17% 1

Piping Sprinkler 8.33% 2

Alarm Valve Valve 8.33% 2

Waterflow Switch Alarm 8.33% 2

Drain Device 8.33% 2

Gauge Device 16.67% 4

Device Type

Qty Model # Type Description Install Date

In Service - 15 Years to 25 Years

Building- Wet Pipe

Gauge 4 N/A System Pressure

10/01/2002

Wet Pipe, Building-

Control Valve 2 AWW OS&Y Main Control 08/14/2002

Control Valve 2 n/a Butterfly Isolation 08/14/2002

Tamper Switch 2 OSYSU-2 OS&Y Supervisory 08/14/2002

Waterflow Switch 1 VSR Vane Alarm 08/14/2002

Alarm Valve 2 VSR Grooved

08/14/2002

Waterflow Switch 1 VSR Vane N/A Alarm 08/14/2002

Fire Dep't Connection 1 717 Siamese

08/14/2002

Piping 2 n/a Steel

08/14/2002

Sprinkler Box 1 n/a

08/14/2002

Drain 2 N/A Main

08/14/2002

Sprinkler Box Spares 1 4232 Pendant

08/14/2002

Check Valve 1 717 Grooved

08/14/2002

Sprinkler Box Spares 1 M02 Pendant

08/14/2002

Backflow Prevention 1 350 Double Check

08/14/2002