technical specification - bidnet

23
TECHNICAL SPECIFICATION No. TS1020 Page i of 22 REV 2 DATE: 2-8-18 CATEGORY CATEGORY: CABLE SUBJECT 1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES Changes in this Revision from the last approved Revision 1 dated 7-31-17 are highlighted in gray. VERSION HISTORY Version Change By Date 0 Initial issue. Steve Breece Aug-2011 1 Correct typo’s, reword, rearrange, and expand references; increase rating to 120 kV, include references in text, replace lead (Pb) with copper laminate tape moisture barrier, use copper wires for centric neutral, add more compounds to lists, change emergency temperature to 105 C. Incorporated comments. Tom Lyons 07-31-17 2 Corrected errors, added data, added peak load value and duration, and clarified text in several sections as highlighted. Tom Lyons 02-8-18 TECHNICAL REVIEW / CONCURRENCE Name Title Initials Date Tom Lyons Principal Distribution Design Engineer Ed Stockman Principal Distribution Design Engineer Marco Villegas Principal Distribution Systems Engineer Daniel Honeyfield Manager, T&D Maintenance Planning APPROVALS Approved by Print Name Signature Date Shahbaz Khan Manager, Electric Design & Standards Maria Veloso Koenig Director, Grid Planning Mike Deis Director, Substation, Telecom, Metering

Upload: khangminh22

Post on 31-Mar-2023

1 views

Category:

Documents


0 download

TRANSCRIPT

TECHNICAL SPECIFICATION

No. TS1020 Page i of 22

REV 2 DATE: 2-8-18

CATEGORY

CATEGORY: CABLE

SUBJECT

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Changes in this Revision from the last approved Revision 1 dated 7-31-17 are highlighted in gray.

VERSION HISTORY

Version Change By Date

0 Initial issue. Steve Breece Aug-2011

1

Correct typo’s, reword, rearrange, and expand references; increase rating to 120 kV, include references in text, replace lead (Pb) with copper laminate tape moisture barrier, use copper wires for centric neutral, add more compounds to lists,

change emergency temperature to 105 C. Incorporated comments.

Tom Lyons 07-31-17

2 Corrected errors, added data, added peak load value and duration, and clarified text in several sections as highlighted.

Tom Lyons 02-8-18

TECHNICAL REVIEW / CONCURRENCE

Name Title Initials Date

Tom Lyons Principal Distribution Design Engineer

Ed Stockman Principal Distribution Design Engineer

Marco Villegas Principal Distribution Systems Engineer

Daniel Honeyfield Manager, T&D Maintenance Planning

APPROVALS

Approved by Print Name Signature Date

Shahbaz Khan Manager, Electric Design & Standards

Maria Veloso Koenig Director, Grid Planning

Mike Deis Director, Substation, Telecom, Metering

TECHNICAL SPECIFICATION

No. TS1020 Page 1 of 22

REV 2 DATE: 2-8-18

CATEGORY

CATEGORY: CABLE

SUBJECT

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Table of Contents

1 PURPOSE ................................................................................................................. 2

2 SCOPE ...................................................................................................................... 2

3 REFERENCES – LATEST EDITIONS, INTERPRETATIONS, CORRECTIONS, AND ERRATA ..................... 2

4 DEFINITIONS ............................................................................................................ 3

5 QUALIFICATION OF BIDDERS ............................................................................... 3

6 CABLE SETTING ...................................................................................................... 4

7 CABLE SPECIFICATION ......................................................................................... 6

8 CABLE ACCESSORIES (IF REQUESTED IN THE BID) ....................................... 13

9 BID SUBMITTAL REQUIREMENTS ....................................................................... 14

10 TESTING AND INSPECTION ................................................................................. 17

11 SHIPPING AND STORING ..................................................................................... 18

12 SUMMER AND WINTER TEMPERATURES IN THE SACRAMENTO AREA ........ 19

13 DRAWINGS AND MANUALS ................................................................................. 20

14 CABLE CUT-AWAY VIEW OF EXISTING SILEC CABLE ..................................... 21

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 2

of 22

1 Purpose

This Engineering Specification provides the requirements for a single conductor,

unfilled crosslinked polyethylene insulated, wet design water barrier (copper

wires with copper laminate tape), and jacketed cable for use by SMUD for its 115

kV transmission system, which is normally operated at 122 kV (1).

2 Scope

This specification covers all work and material used to design, fabricate, test, and

deliver a 120 kV cable. This specification includes the requirements for high

voltage terminations and straight, cross-bonding, and grounding joints compatible

with the specified cable (if requested on the bid request).

3 References – Latest Editions, Interpretations, Corrections, and Errata

The manufacturer shall fabricate and test the cable and accessories in

accordance with the following standards as applicable. When there is a conflict

between the listed standards and this specification, the requirements of this

specification shall govern.

3.1 AEIC CS9: Specification for Extruded Insulation Power Cables and their

Accessories Rated Above 46 kV Through 345 kV.

3.2 ASTM B8: Standard Specification for Concentric Lay Stranded Copper

Conductors: Hard, Medium-Hard, or Soft.

3.3 ASTM B496: Standard Specification for Compact Round Concentric-Lay-

Stranded Copper Conductors.

3.4 ICEA P-32-382: Short Circuit Characteristics of Insulated Cables.

3.5 ICEA P-45-482: Short Circuit Performance of Metallic Shields and

Sheaths on Insulated Cable.

3.6 ICEA S-108-720: Extruded Insulation Power Cables Rated Above 46

Through 345 kV.

3.7 ICEA T-31-610: Test Method for Conducting Longitudinal Water

Penetration Resistance Tests on Blocked Conductors.

3.8 ICEA T-32-645: Test Method for Establishing Volume Resistivity

Compatibility of Water Blocking Components with Extruded

Semiconducting Shield Materials.

3.9 ICEA T-34-664: Test Method for Conducting Longitudinal Water

Penetration Resistance Tests on Longitudinal Water Blocked Cables.

3.10 IEC 60840: Power cables with extruded insulation and their accessories

for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) –

Test methods and requirements

(1)

ICEA S-108-720, Appendix F, Note 2: The actual operating voltage shall not exceed the rated circuit voltage by

more than (a) 5 percent during continuous operations or (b) 10 percent during emergencies lasting not more

than 15 minutes.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 3

of 22

3.11 IEEE 48: Test Procedures and Requirements for Alternating Current

Cable Terminations Used on Shielded Cables Having Laminated

Insulation Rated 2.5 kV through 765 kV or Extruded Insulation Rated 2.5

kV through 500 kV.

3.12 IEEE 404: Extruded and Laminated Dielectric Shielded Cable Joints

Rated 2.5 kV to 500 kV.

3.13 IEEE 532: Guide for Selecting and Testing Jackets for Power,

Instrumentation, and Control Cables.

3.14 IEEE 1142: Guide for the Selection, Testing, Application, and Installation

of Cables having Radial-Moisture Barriers and/or Longitudinal Water

Blocking.

3.15 NEMA WC-26: Binational Wire and Cable Packaging Standard.

3.16 SMUD TD6406: Underground Transmission Conductor Ampacity.

4 Definitions

For definitions not listed, refer to IEEE 100 CD Standards Dictionary: Glossary of Terms and Definitions.

5 Qualification of Bidders

Bids will only be accepted from manufacturers who have:

5.1 A minimum of ten years of continuous experience manufacturing

crosslinked polyethylene cable of 115 kV, or greater, voltages.

5.2 A manufacturing process which uses a triple extrusion process where the

conductor shield, insulation, and insulation shield are extruded through a

single extrusion device.

5.3 The capability to manufacture or to supply cable terminations and cross-

bonding joints for the cable specified by this specification.

5.4 Manufacturing facility must use a vertical tower extrusion process to build

this cable.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 4

of 22

6 Cable Setting

The supplier shall provide a cable compatible with SMUD’s system and

installation described below.

6.1 System Characteristics

6.1.1 Normal Operating Current and Temperature = 766 Amps, 90° C (2),

6.1.2 Emergency Operating Current and Temperature = 920 Amps, 105° C

for 2,880 cumulative hours (3)

6.1.3 Emergency overload duration and magnitude: Hours 0 – 6 = 50% of

peak magnitude, Hours 7 – 11 = 80% of peak magnitude, Hours 12 –

18 = 100% of peak, and Hours 19 – 23 = 60% of peak, repeated for

three consecutive days (72-hours total),

6.1.4 Frequency = 60 Hz,

6.1.5 Nominal phase-to phase operating voltage = 122.2 kV,

6.1.6 Maximum phase-to-phase operating voltage = 128.3 kV,

6.1.7 Nominal phase-to-ground operating voltage = 70.6 kV,

6.1.8 Maximum phase-to-ground operating voltage = 74.1 kV,

6.1.9 BIL = 550 kV,

6.1.10 Symmetrical Fault Current = 30 kA for 30 cycles three-phase to

ground and phase-to-ground(4),

6.1.11 Asymmetrical Fault Current = 48 kA for 9 cycles three-phase to

ground and phase-to-ground (4),

6.1.12 Fault Limitation Temperature = 250° C,

6.1.13 Maximum Laminate Temperature = 150 C, and

6.1.14 Normal Operating Daily Load Factor = 80%.

6.2 Existing Cable Installation

6.2.1 Connection = three phase, single point ground. Sheaths are either

bonded directly to ground, cross-bonded at splices and connected to

ground through surge arrestors, cross bonded with no ground

connections, or spliced straight through (#4/0 bare copper ground at

bottom center of entire duct bank). Refer to Figure 2 on page 22.

6.2.2 Worst Case Duct bank Condition (see Figure 1 next page):

6.2.2.1 Three (3) horizontal 6-inch (6") PVC conduits, (1) – 120 kV

cable per duct (no spare conduits for 120 kV cable),

6.2.2.2 (1) – 2" conduit for communication cable,

(2)

As per SMUD TP6401 Transmission Facilities Ratings Methodologies, Rev 3, 11/2014 (3)

From ICEA S-108-720, Appendix B: “Operation up to the stated maximum overload temperature should be for

no more than 72 hours duration on average per year during the design life of the cable system, without

exceeding 216 hours in any 12-month period. Assuming a 40-year design life (for planning purposes not a

guarantee), this implies that the cable system should be able to withstand cumulative operation at overload

temperature for a total of 72 x 40 = 2880 hours.” (4)

As per email from SMUD’s System Protection And Control group 12-11-17.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 5

of 22

6.2.2.3 6-inch (6") concrete encasement at top and bottom of ducts,

6.2.2.4 4-1/2-inch (4.5") concrete encasement at sides of ducts,

6.2.2.5 A 100-foot section of the duct bank is buried with the top of the

bank 14' below the surface. (The remainder of the duct bank

has an average depth to the top of the bank of only 5' below

the surface),

6.2.2.6 Duct bank under pavement/asphalt for the entire run,

6.2.2.7 Concrete thermal resistivity (rho) = 90° C·cm/W or less,

6.2.2.8 Ambient earth thermal resistivity (ρ) = 120º C·cm/W (2),

6.2.2.9 Ambient Air Temperature = 46° C (115° F) (2),

6.2.2.10 Ambient Ground Temperature at all burial depths = 25° C (77° F),

6.2.2.11 Minimum Temperature at which cable will be installed: -5° C

(23° F), and

6.2.2.12 Location = wet.

Figure 1 – Worst case scenario for duct bank installation: top of bank is 14’ below grade.

(All dimensions are in inches.)

4.53.0

6.0

6.0

2.0

2.0Ø2.0

Ø6.625

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 6

of 22

7 Cable Specification

7.1 General

7.1.1 Minimum length on at least one reel = 1,900 feet.

7.1.2 The manufacturer shall design, fabricate, and test the cable in

accordance with ICEA S-108-720, as applicable except as otherwise

defined in this specification.

7.1.3 The manufacturer shall use triple head extrusion of conductor shield,

insulation, and insulation shield.

7.1.4 The manufacturer shall use a dry-cure process.

7.1.5 The manufacturer shall have a materials handling process that does

not introduce contamination into the insulation system during

manufacturing.

7.1.6 The cable manufacturer shall utilize material from a single supplier

for the conductor shield, the insulation, and the insulation shield. All

materials shall meet the testing requirements in Section 10 of this

specification.

7.1.7 The manufacturer shall test all materials used to manufacture the

cable and they shall have successfully passed the qualification tests

per ICEA S-108-720. The manufacturer will also provide a cable

system qualification test report in accordance with AEIC CS9.

7.1.8 The cable design shall allow for the thermal expansion of the

components without degradation of the cable.

7.1.9 Cable shall be manufactured with concentric copper wires and a

copper laminate foil shield:

7.1.9.1 Compact Copper Conductor: Strand-Filled – the strand fill will

be compatible with the conductor shield and will not leach into

the conductor shield over time. The conductor may also

contain water blocking yarn or tapes,

7.1.9.2 Optional Semi-Conductive tape,

7.1.9.3 Extruded Non-metallic Semi-conductive Conductor Shield,

7.1.9.4 Extruded unfilled XLPE Insulation,

7.1.9.5 Extruded Non-metallic Semi-conductive Insulation shield,

7.1.9.6 Cushioning Water-Swellable Semi-Conductive Tape,

7.1.9.7 Copper Concentric Wires,

7.1.9.8 Cushioning Water-Swellable Semi-Conductive Tape,

7.1.9.9 Copper Laminate Foil Tape Shield,

7.1.9.10 High Density Polyethylene Jacket, and

7.1.9.11 Semi-Conductive Jacket Layer.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 7

of 22

7.2 Conductor

7.2.1 General

The conductor shall meet the requirements of ICEA S-108-720 and

AEIC CS-9.

7.2.2 Conductor Size

The manufacturer shall provide 1250 kcmil copper conductor,

compact strand.

7.2.3 Conductor Material

Copper phase conductors shall be soft drawn copper Class B

furnished in accordance with ASTM B8.

7.2.4 Conductor Stranding

Copper Conductor stranding shall be in compact stranded per

ASTM B496.

7.2.5 Conductor Sealant

7.2.5.1 In order to prevent water propagation through the conductor

strands and to prevent water treeing of the insulation, the

cable manufacturer shall apply a strand blocking to the inner

layers of all stranded conductors in accordance with ICEA S-

108-720, Section 2.2.

7.2.5.2 The manufacturer shall use a material compatible with the

conductor, conductor shield materials, and the insulation in

accordance with ICEA T-32-645.

7.2.5.3 The conductor water blocking shall withstand a water

penetration test pressure of 5.0 psig (AEIC CS9, 2.1.2) for

qualification and production testing in accordance with ICEA

T-31-610.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 8

of 22

7.3 Non-metallic Semi-conductive Conductor Shield

7.3.1 The manufacturer may apply an optional semi-conductive tape over

the bare conductor, based upon the manufacturer’s normal cable

design methodology.

7.3.2 The manufacturer shall apply a conductor shield in accordance with

ICEA S-108-720. The manufacturer shall cover the conductor with

an extruded layer of super smooth semi-conducting crosslinked

polyethylene thermo-setting material. The manufacturer shall use

any of the Dow compounds listed below. Borealis compounds can

only be used with the written permission from SMUD Standards

group.

Dow Borealis

HFDA-0801 BK EHV (Preferred) LE 0500

HFDA-0801 BK LE 0592 S

HFDB-0801 BK EC

HFDC-0586 BK S

The compounds chosen for the conductor fill, conductor shield,

insulation, and insulation shield shall be compatible with each other.

7.3.3 Thickness: The conductor shield shall have a minimum thickness of

24 mils (ICEA S-108-720, Table 3-1). This is a MINIMUM thickness.

7.3.4 Protrusions and Irregularities: The interface between the extruded

conductor shield and the insulation shall be cylindrical and shall be

free of protrusions and irregularities that extend more than three (3)

mils into the insulation and three (3) mils into the extruded conductor

shield (ICEA S-108-720, section 3.3).

7.3.5 Voids: The interface between the extruded conductor shield and the

insulation shall be free of any voids larger than two (2) mils in its

greatest dimension (ICEA S-108-720, section 3.4).

7.3.6 The conductor shield material shall have characteristics compatible

with those of the cable insulation, cable conductor, and the strand

blocking material.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 9

of 22

7.4 Insulation

7.4.1 The cable manufacturer shall use insulation that meets all

appropriate requirements of ICEA S-108-720.

7.4.2 The manufacturer shall use unfilled crosslinked polyethylene (XLPE)

with no mineral fillers. The manufacturer shall use any of the Dow

compounds listed below. Borealis compounds can only be used with

the written permission from SMUD Standards group.

Dow Borealis

HFDK-4201 EHV (Preferred) LE 4201 EHV

HFDK-9253 S LS 4201 EHV

LE 4201 S

LS 4201 S

7.4.3 The insulation shall have a minimum average thickness of 800 mils (5)

(ICEA S-108-720, Appendix F, Table F-1) with a maximum insulation

eccentricity of 8% (exceeds ICEA S-108-720, Table 4.2).

7.4.4 The insulation shall:

7.4.4.1 Voids: Be free of voids larger than two (2) mils in its greatest

dimension, and the number of voids larger than one (1) mil

shall not exceed 30 per cubic inch (ICEA S-108-720, section

4.3.3.1),

7.4.4.2 Contaminants: Be free of contaminants larger than five (5)

mils at its greatest dimension and the number of contaminants

between two (2) and five (5) mils in size shall not exceed 10

per cubic inch (ICEA S-108-720, section 4.3.3.1), and

7.4.4.3 Amber: Be free of any amber (localized area of insulation

which is dissimilar in color from surrounding insulation) larger

than 10 mils in its greatest dimension (ICEA S-108-720,

section 4.3.3.1).

(5)

SMUD’s existing 1200 kcmil, 115 kV XLPE lead (Pb) sheath cable has an insulation thickness of 800 mils. It

was decided to specify 800-mil thickness insulation in the spare cable to minimize difficulty in splicing the two

cables together.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 10

of 22

7.5 Non-Metallic Insulation Shield and Tape

7.5.1 Extruded Layer

The manufacturer shall apply a continuously bonded extruded layer

of semi-conducting crosslinked polyethylene insulation shield, with a

minimum and maximum thickness based upon Table 5-1 in

ICEA S-108-720. The manufacturer shall use any of the Dow

compounds listed below. Borealis compounds can only be used with

the written permission from SMUD Standards group.

Dow Borealis

HFDA-0801 BK EHV (Preferred) LE 0500

HFDA-0801 BK LE 0592 S

HFDB-0801 BK EC

HFDC-0586 BK S

The manufacturer shall apply this layer in accordance with ICEA S-

108-720.

7.5.2 Protrusions and Irregularities: The interface between the extruded

insulation shield and the insulation shall be cylindrical and shall be

free of protrusions and irregularities that extend more than five (5)

mils into the insulation and five (5) mils into the extruded insulation

shield (ICEA S-108-720, section 5.3).

7.5.3 Voids: The interface between the extruded insulation shield and the

insulation shall be free of any voids larger than two (2) mils in its

greatest dimension (ICEA S-108-720, section 5.4).

7.5.4 Volume Resistivity: The volume resistivity of the extruded insulation

shield shall not exceed 500 ohm-meter at 90 C (ICEA S-108-720,

5.6.1).

7.5.5 Tape Layer

The manufacturer shall apply a semi-conducting, water swellable

cushioning tape over the extruded insulation shield in accordance

with ICEA S-108-720 with a minimum thickness of 20 mils. This is a

MINIMUM thickness.

7.5.6 Concentric copper wires will be installed over the tape layer

mentioned in section 7.5.5, this specification, with a minimum wire

size of # 14 AWG.

7.5.6.1 Length of Lay

The concentric wires shall have a minimum length of lay of six

(6) to ten (10) times the diameter of the cable as measured

over the concentric neutral wires. Either a left or right-hand

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 11

of 22

lay will be determined by the manufacturer and stated in the

bid response.

7.5.6.2 Wire Spacing

The wires shall be spaced around the circumference of the

cable such that the distance between conductors is

approximately equal, but spacing between conductors shall

not exceed 0.5 inch (ICEA S-108-720, 6.2.3).

7.5.6.3 Wire Layer Requirements

All other requirements of the ICEA S-108-720 shall apply to

the concentric wires.

7.5.7 The concentric copper wires will have the capacity to carry a

symmetrical fault current of 30,000 Amps for 30 cycles.

7.5.8 The manufacturer shall apply a semi-conducting, water swellable

cushioning tape over the concentric copper wires in accordance with

ICEA S-108-720 with a minimum thickness of 20 mils.

7.5.9 A copper laminate foil tape shield will be applied over the semi-

conducting, water swellable cushioning tape mentioned above and

must confirm to AEIC-CG-13. A CG13 qualification report is

required.

A 6 mils thick copper sheet with a 2 mils non-conductive copolymer

coating on one side shall be longitudinally applied over the cable

core with a one half-inch (0.5”) minimum overlap. The non-

conductive coated side shall be bonded to the polyethylene jacket.

The heat of extrusion during application of the polyethylene jacket

shall bond the outer coating of the copper laminate sheath to the

cable jacket to form the bonded laminate sheath. The overlap is

sealed by inserting hot melt adhesive into the overlap to complete the

moisture barrier. The copper laminate sheath must allow for thermal

expansion and contraction of the insulation for conductor

temperatures between

21° C and 90° C, and be free of any wrinkles at the overlap. The

copper laminate sheath shall be Wuxi/Kemaite, ET20-S, Exabon,

system. Hot melt adhesive shall be Henkel Adhesive System Hot

Melt Macromelt TPX 20-230 or Q8740, or SMUD approved equal (it

will be the responsibility of the manufacturer to provide test reports

supporting the “or equal” status).

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 12

of 22

7.6 Jacket

7.6.1 The manufacturer shall apply an inner insulating jacket of black linear

high-density polyethylene, in accordance with ICEA S-108-720. An

outer jacket coating of semiconducting material shall also be applied,

as per ICEA S-108-720, section 7. The manufacturer shall use the

Dow compounds listed below. Borealis compounds can only be used

with the written permission from SMUD Standards group.

Dow Borealis

DGDL-3479 BK HE-6067

DHDA-7708 BK (for outer

semicon jacket) LE0563

7.6.2 The minimum and maximum thickness of the jacket shall be as

specified in Tables 7-3 and 7-4 of ICEA S-108-720.

7.7 Cable Jacket Marking

7.7.1 The manufacturer shall mark the cable as required by

ICEA S-108-720 using permanent printing in a contrasting color from

the jacket, or indented printing in the same color as the jacket,

consisting of:

7.7.1.1 The Manufacturer’s Identification or trade name,

7.7.1.2 Size of Conductor,

7.7.1.3 Conductor Material,

7.7.1.4 Type of Insulation,

7.7.1.5 Voltage Rating,

7.7.1.6 Nominal Insulation Thickness, and

7.7.1.7 Year of Manufacture.

7.7.2 The manufacturer shall mark the cable with sequential length (in feet)

not less than every two (2) feet along the length of the cable. It is

desired that the beginning of the cable installed on the reel be

labeled “zero” so that the footage displayed at the end of the cable

will also give the remaining length of cable on the reel.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 13

of 22

8 Cable Accessories (if requested in the bid)

SMUD will require the cable supplier to provide cable accessories such as cable

terminations, straight joints, cross-bonding joints, cross-bonding joints grounded

via surge arresters, and grounded joints. The cable supplier shall provide all

materials and accessories needed for terminating or splicing the cable. The

terminations and joints shall meet the requirements of the following sections.

8.1 Cable Terminations

8.1.1 Termination Ratings

The termination shall have the following ratings:

8.1.1.1 Basic Impulse Level, 550 kV, and

8.1.1.2 Insulation Class, 120 kV

8.1.2 Termination Class

The supplier shall provide terminations that meet the requirements of

a Class 1A termination as defined in IEEE Std 48.

8.1.3 Termination Markings

Cable terminations shall have the following markings:

8.1.3.1 Manufacturer’s name, type, designation number,

manufacturing date or date code,

8.1.3.2 IEEE termination class number,

8.1.3.3 Insulation class,

8.1.3.4 Maximum design voltage to ground,

8.1.3.5 Maximum and minimum cable conductor size,

8.1.3.6 Maximum and minimum cable insulation diameter, and

8.1.3.7 Basic Impulse Level (BIL).

8.1.4 Outdoor Terminations

The cable supplier shall provide terminations with non-porcelain

termination insulators that are compatible with their cable.

8.1.5 SF6 Gas Insulated Switchgear Terminations

SMUD may connect the specified cable to SF6 gas insulated

switchgear. When specified, SMUD will provide the dimension

requirements or the cable supplier shall coordinate with the GIS

provider to ensure correct dimensions as directed in the purchasing

documents.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 14

of 22

8.2 Straight joints, cross-bonding joints, cross-bonding joints grounded

via surge arresters, and grounded joints

8.2.1 Straight Splice Joint Category

The supplier shall provide extruded straight splice joints that meet the

requirements defined in IEEE Std 404.

8.2.2 Straight Splice Joint Construction

The supplier shall provide pre-molded straight splice joints that are

compatible with their cable and with the existing SILEC cable. These

joints will be capable to have the concentric shield grounded through

a surge arrester.

8.2.3 Straight Splice Joint Ratings

The supplied straight splice joint shall have the following ratings:

8.2.3.1 Maximum phase to phase voltage rating, 128.3 kV,

8.2.3.2 Maximum phase to ground voltage rating, 74.1 kV, and

8.2.3.3 Basic Impulse Level (BIL), 550 kV.

8.2.4 Straight Splice Joint Size

8.2.5 The supplier shall provide pre-molded straight splice joints that, in

addition to accommodating the cable specified in this specification,

can connect to existing installed cables:

8.2.5.1 1200 kcmil, 115 kV, 800 mils XLPE insulation, with lead (Pb)

sheath, manufactured by SILEC (refer to cut-away drawing in

Section 14, this specification), or

8.2.5.2 1250 kcmil, 115 kV, 800 mils XLPE insulation, with lead (Pb)

sheath, manufactured by ALCATEL.

9 Bid Submittal Requirements

9.1 Cable Bid Submittals

At the time of bid, the cable supplier shall provide a cross-sectional

drawing of the cable being bid, identifying the components to construct the

cable identified in Section 7 above.

Manufacturers proposing cables with different designs shall provide similar

dimensional information and layer identification of the cable.

9.2 Additional information to be supplied by the Manufacturer:

9.2.1 Nominal phase-to-phase voltage,

9.2.2 Normal conductor maximum operation temperature the cable was

designed to meet,

9.2.3 Emergency conductor maximum operation temperature the cable

was designed to meet,

9.2.4 The voltage stress at the conductor shield/insulation interface

(maximum stress) and at the insulation/insulation shield interface

(minimum stress),

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 15

of 22

9.2.5 Maximum allowable pulling tension (with basket and with eye) and

maximum sidewall bearing pressure,

9.2.6 Dielectric constant,

9.2.7 Skin, proximity, and loss factors for the conductor,

9.2.8 TanDelta and Epsilon for the insulation,

9.2.9 Minimum bending radius, and

9.2.10 Weight per unit of length.

9.3 Safety Data Sheets: The material used in the manufacturing of the cable,

including supplier’s technical data sheet and complete material description

including all Safety Data Sheets of the components to construct the cable

identified in Section 7 above.

9.4 Qualification Tests: A copy of the qualification tests in accordance with

ICEA S-108-720 and AEIC CS9 and Water Penetration Resistance Test

per ICEA T-31-610 or SMUD approved equivalent standard for the specific

combination of cable materials proposed.

9.5 Manufacturing Process: The manufacturing of the triple extrusion and

dry-curing equipment and complete description of the extrusion and curing

process. Manufacturer must use a vertical tower extrusion process.

9.6 The short circuit capability of the conductor and the shield: At 30

cycles and 9 cycles per ICEA P-32-382 and ICEA P-45-482 and

calculations of the maximum temperature of the conductors at the fault

levels prescribed in this specification Section 6.

For a single circuit installed in accordance with methods per this

specification Section 6, indicate the method of calculation and the

ampacity for a single point grounded shield and a multipoint-grounded

shield:

9.6.1.1 Normal ampacity and

9.6.1.2 Emergency ampacity.

9.7 The shipping reel information for each cable being bid including:

9.7.1 The reel flange diameter, the outside traverse flange-to–flange width,

the drum diameter, and the shaft-hole dimensions.

9.7.2 The longest expected length of each cable on the reel along with the

maximum weight of each reel with the longest length with wood

lagging or other lagging method approved by SMUD.

9.7.3 The labeling on the reel will include the weight of the cable, the tare

weight, and the total weight (all in pounds).

9.7.4 Please refer to Section 11, this specification, for dimensional limits for

reel.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 16

of 22

9.7.5 Please note – for cable designated as “spare,” the cable reel will

remain on site for the life of the cable. Please include the price of the

reel with your bid.

9.8 Termination Bid Submittals (if requested in bid)

9.8.1 At the time of bid, the cable supplier shall provide outline and cross-

section drawings identifying component parts and showing

dimensions.

9.8.2 The cable supplier shall provide the following ratings for the

terminations:

9.8.2.1 Basic Impulse Level (BIL),

9.8.2.2 Basic Switching Impulse Insulation Level,

9.8.2.3 Insulation Class Maximum,

9.8.2.4 Cable Diameter Minimum,

9.8.2.5 Cable Diameter Maximum, and

9.8.2.6 Design Voltage-to-ground.

9.8.3 At the time of bid, the cable supplier shall provide installation

instructions for the specific terminations proposed.

9.9 Cross-bonding joint Bid Submittals (if requested in bid)

9.9.1 At the time of bid, the cable supplier shall provide outline and cross-

section drawings identifying component parts and showing

dimensions.

9.9.2 The cable supplier shall provide the following ratings for the joints:

9.9.2.1 Voltage rating, phase to phase,

9.9.2.2 Voltage rating, phase to ground, and

9.9.2.3 Basic Impulse Level.

9.9.3 At the time of bid, the cable supplier shall provide installation

instructions for the specific cross-bonding joints proposed.

9.10 Cable and Accessories Storage

The cable manufacturer shall provide any requirements for long-term

storage (approximately 20+ years) of cable on reels such as indoor or

outdoor storage, reel rotation, etc. and for the long-term storage and shelf

life of any terminations or straight splice joints if specified in the bid.

Please refer to Section 12, this document, for the peak high and low

temperatures for the Sacramento area for 2010 through 2016 which would

show the temperature conditions that the spare cable would be subjected

to if stored outdoors. The manufacturer shall provide a separate price for

supplying any equipment necessary for long-term storage of cable as an

option with the bid.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 17

of 22

9.11 Cable Design Changes

Following approval by SMUD of the specific design and materials

submitted to SMUD by the supplier, the supplier shall not make changes

in such design or materials without the prior written approval of SMUD.

Any potential changes require submittal of information in accordance with

Section 9, this specification.

10 Testing and Inspection

10.1 Witnessing Production and Testing

SMUD shall have the right to witness any or all production or production

tests. The manufacturer shall notify SMUD at least two weeks prior to any

manufacturing and and/or testing of cable supplied in accordance with

these specifications.

10.2 Cable Tests

10.2.1 Cable Qualification Tests

The manufacturer of the cable shall have successfully passed all

applicable Qualification Tests in accordance with ICEA S-108-720

and AEIC CS9 for the design of cables similar to that proposed for

delivery to SMUD.

10.2.2 Water Penetration Test

Longitudinal Water Penetration Resistance Tests shall be

successfully performed per ICEA T-31-610 or SMUD approved

equivalent standard.

10.2.3 Production Tests

The manufacturer shall perform all factory Production Tests in

accordance with ICEA S-108-720 Part 9. Report data shall be

recorded and kept on file at the manufacturing facility for a minimum

of three years. All test data shall be made available to SMUD upon

request. One copy of completed Production Test Reports performed

in accordance with ICEA S-108-720, and certified by the

manufacturer’s Quality Assurance organization shall be submitted

before or at the time of shipment of the cable. The tests report shall

be sent to SMUD’s specifying engineer listed on purchase

documents.

10.2.4 Cable Acceptance

Cable acceptance and payment for the cable may be affected by

delays in receipt of the production test data.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 18

of 22

10.3 Termination Tests (if requested in bid)

The supplied terminations shall meet the applicable testing requirement of

Section 7 of IEEE Std 48.

10.4 Joint Tests (if requested in bid)

The supplied joints shall meet the applicable testing requirement of

Section 7 of IEEE Standard 404.

11 Shipping and Storing

11.1 The manufacturer shall furnish the “spare” cable on non-returnable steel

fluted reels, similar to Class II heavy duty, in accordance with NEMA

Standard No. WC-26. The cable reel dimensions shall not exceed 120

inches on the flange and 82 inches on the reel width unless explicitly

approved otherwise. The reel shall easily accommodate a 5-inch diameter

shaft.

11.2 The “spare” reel barrel dimension shall be adequate for long-term storage

(20+ years) of the cable on the reel without damage. The manufacturer

shall protect the cable by utilizing Class 4 wood lagging in accordance

with NEMA Standard No. WC-26, Section 4, or other SMUD approved

lagging. If the 120-inch diameter by 82-inch wide reels will not

accommodate the specified cable lengths with the wood lagging, the

supplier may request in writing to waive the wood lagging requirement or

recommend use of another reel.

11.3 The manufacturer shall suggest any other method(s) that can be applied

to the cable and reel to prevent deterioration due to moisture, UV light, or

other factors that could degrade the cable over time.

11.4 SMUD will list reel shipping lengths in the purchasing documents. The

tolerance on all defined lengths shall be -0% and +5%. SMUD will not

accept lengths shorter than the values defined.

11.5 The manufacturer shall install a pulling eye on outer end of the cable on

each reel. The manufacturer shall seal the inner cable ends and the

pulling eyes against moisture and water intrusion.

11.6 The manufacturer will provide instructions as to how to re-seal the cable

ends after a section has been removed.

11.7 Cable reel stand. Owing to the anticipated weight of the reel, the

manufacturer shall include in their bid a cable stand capable of

supporting the “spare” reel for long-term (20+ years) storage.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 19

of 22

12 Summer and Winter Temperatures in the Sacramento Area Below is a chart of the average high and peak high temperatures (in degrees F) for July and August in the Sacramento Area from 2010 through 2016.

Below is a chart of the average low and peak low temperatures (in degrees F) for January and February in the Sacramento Area from 2010 through 2016.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 20

of 22

13 Drawings and Manuals

An electronic version of the final documents submitted and or agreed upon

shall be provided in Acrobat® (*.pdf), Microsoft Word® (*.docx), Microsoft

Excel® (*.xlsx), and/or AutoCAD® (*.dwg) format and shall be submitted to

SMUD’s specifying engineer listed on purchase documents.

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 21

of 22

14 Cable Cut-Away View of Existing SILEC cable

TECH. SPEC. TS1020

REV 2

1250 kcmil, 120 kV CROSSLINKED POLYETHYLENE INSULATED CABLE AND ACCESSORIES

Page 22

of 22

Non

-lin

ear

resi

stor

per

phas

e

bet

wee

n g

as i

nsu

late

d c

ell

and

ter

min

atio

n.

Sp

lice

wit

hou

t gro

und

ing

Sp

lice

wit

h d

irec

t gro

un

din

g.

Non

-lin

ear

resi

stor

per

phas

e

bet

wee

n s

hie

ld a

nd g

rou

nd

.

Sp

lice

wit

h g

rou

nd

ing

th

rou

gh

non

-lin

ear

resi

stor.

Figure 2 - Grounding Scheme Between Station A and Station D