lv switchboards 8pu + busducts
DESCRIPTION
LVTRANSCRIPT
Versatile, Reliable & User Friendly
s
8PU Low Voltage Switchboards
Answers for industry.
1
2
3
4
5
6
Economical, Requirement Oriented & Type Tested:The 8PU Low Voltage Switchboard
Reference Indian and InternationalStandards
IS 8623 : Specification for Low Voltage(Part I) Switchgear & Controlgear Assemblies:
Requirement of Type Tested & PartiallyType Tested Assemblies.
IEC 439 : Low Voltage Switchgear & Controlgear(Part I) Assemblies.
IS 13947 : Specification for Low Voltage(Part I) Switchgear & Controlgear Part I:
General Rules.
IEC 60947 : Specification for Low VoltageSwitchgear & Controlgear.
IS 2147 : Degree of Protection provided byEnclosures for Low Voltage Switchgear& Controlgear.
IS 5082 : Specification for Wrought Aluminium &Aluminium Alloy Bars, Rods, Tubes &Sections for Electrical Purposes.
IS 1897 : Specification for Copper Strip forElectrical Purposes.
IS 11353 : Guide for Uniform System of Marking &Identification of Conductors &Apparatus Terminals.
IS 5578 : Guide for Marking of InsulatedConductors.
Power Control Centre
Drawout
Motor Control Centre
Non Drawout
Motor Control Centre
Non compartmentalisedDistribution Boards
Low voltage Busducts
8PU - Tested as perlatest quality norms
1
2
3
4
5
6
2
World Class Products with unmatched featurescatering to the entire low voltage spectrum
When you buy 8PU Switchboards,you buy —
• Latest technology at an affordable price
• Incredibly easy to operate & flexiblesystem under any condition
• Siemens commitment on making yoursafety our business.
In short, the best value for money
The family 8PU is a system of standard sectionsand switchgear units, suitable for all lowvoltage switchboard applications and designedfor all types of customers throughout theworld. The 8PU System is a product of manyyears of manufacturing experience withswitchgear and a thorough investigation ofcurrent market requirement and practices.
Sheet metal pre-treatment, painting, newassembly techniques and modernmanufacturing methods, including the use ofCNC machines, coupled with our own testingfacility and stringent quality control, ensure ahigh degree of reliability and safety of operatingpersonnel. The wiring systems, new generationsof Siemens switchgear and safety features likefull compartmentalisation, automatic safetyshutters and automatic draw out contactscontribute to the modern concept of low voltage
switchboard.
3
Our Product Range
8PUL4.5Power Control CentreCompact, Reliable and User-Friendly
Power Control Centre is considered to be theheart of an electrical system in any industry.Particular demands are therefore made interms of long term reliability and safety. Thisis to say, “supply”, “coupling” and “feeder”functions must be reliably available over longperiod of time. Maintenance and testing mustnot involve long down-times. Siemens 8PUmeets these requirements with 8PUL4.5Power Control Centres.
Compact and reliable
• High degree of safety by virtue of typetested assemblies.
• Test and disconnected position with doorclosed.
• For every rated current range, optimumconnection conditions for cables andbusbars.
• Separate function compartmentsconsisting of a switching device, anauxiliary equipment and a cableconnection compartment.
• High degree of safety for operatingpersonnel by virtue of cable separation onboth sides.
User friendly
Siemens drawout and non drawout circuitbreakers are used for the rated current rangefrom 630 to 6300A. This means:
• Free choice of the supply directionwithout any sacrifices in terms of technicalspecifications.
• High short-time current carrying capacityfor time-graded short-circuit protection(upto 500ms) assures reliable operation ofthe switchboard without being affected bya short-circuit.
• Indication and operation in the doorclosed condition.
4
8PUL4.5Technical Data
Rated Insulation 660V , 40-60HzVoltage
Rated operational 415V , 50HzVoltage
Rated Current 630A – 6300A
Short Circuit 50kArms, 1sec and 105kA peakWithstand (Type tested design)
Ambient Standard 40ºCTemperature Optional 45ºC, 50ºC
Degree of Standard IP 42Protection Optional IP 54 upto 1600A
Dimensions Standard W D H560/850/1000x1120x2300 mm
5
8PUL4.5Power Control CentreCompact, Reliable and User-Friendly
A unique design
Unique double panel design forthe outgoing feeders in place ofconventional double tier panel.
Independent auxiliary compartment givesoptimum space for mounting auxiliary deviceseven for extensive control and interlockingschemes.
Fewer joints between busbars and air circuitbreakers makes the panel cooler.
Independent accessto power terminalsensures high degreeof safety duringoperation as wellas reduces downtime duringmaintenance.
Also more cabling space ensures easy cabletermination for both the feeders.
6
Easy to operate and maintain
Telescopic rail facilitates access formaintenance with ACB in the Panel.
All control accessories accessible fromthe front, hence testing is possiblewith the CB door closed.
Provides safety
We provide automatic safetyshutter on breaker chassis.
All indicators like ACB positionindicator, mechanical counter &“ready to close” condition arevisible with the door closed.
The main busbars& neutral busbarsare enclosed inseparate busbarchambers thuseliminating phaseto neutral faults.
7
8PUS1.5Drawout Motor Control CentreErgonomic, Reliable and Versatile
Whether in power plants, industrial installationsor office complexes, an adequate amount ofenergy must be available at the necessarylocation and at all times. However, requirementsfrequently change. For example, motor powerratings change or new loads have to beconnected.
Siemens’ 8PU drawout design offers theunmatched degree of power supply flexibility.What’s more, it was conceived on the basis ofergonomic criteria. Easy handling and shortconversion times assure high availability of thesystem.
8PUS1.5 drawout design offersversatility and reliability withadaptation to changing requirements• Drawout modules of the same sizes are
interchangeable, irrespective of equipmentmounted.
• Neither any shutdown nor any cutting ordrilling required for changing or addingfeeders disposition at site.
• Direct alignment with Power control Centre(8PUL4.5) to form PMCC’s.
8PUS1.5 – a safe and user friendlydesign• High degree of safety by virtue of type tested
assemblies.• Standard operating method for all sizes of
drawout units.• All parts are inside the contours of the
drawout units and are therefore protectedagainst damage.
• Hinged instrument plate for easy access toequipment.
• High packing density (upto 11 feeders of160mm height per cubicle)
• Positive earthing of each of the drawoutmodule as well as panel doors.
• Power terminals location at rear give largespace for cable run & also ensures safeworking in cable alley.
• Feeder compartment door and cable alleydoor opens in opposite direction for ampleworking space.
• All equipment are accessible from front.• All feeders are fully compartmentalised.
8
8PUS1.5Technical Data
Rated Insulation 660V, 40-60HzVoltage
Rated operational 415V, 50HzVoltage
Rated Current Main Horizontal Busbars : 630A – 3200AVertical Busbars : 630A
Short Circuit 50kArms, 1sec and 105kA peakWithstand (Type tested design)
Ambient Standard 40ºCTemperature Optional 45ºC, 50ºC
Degree of Standard IP 52Protection Optional IP 54
Dimensions Standard W D HSingle front 850 x 560 x 2300mmwith Top/bottomcable entryDouble front 850 x 800 x 2300mmwith top/bottomcable entry
9
8PUS1.5Drawout Motor Control CentreErgonomic, Reliable and Versatile
Cable alley of internal width of 270mm facilitatesease in cable termination & maintenance.
Trolley width of more than 500 mm ensures betterequipment dispersion as well as safe & easyequipment replacement and maintenance.
Self aligning and self-disconnecting main &auxiliary contacts.
Vertical busbars with a multi layer plating onAluminium called ‘Alstan’ which ensures reliableelectrical contact, resistance to abrasion andbetter electrical properties.
Unique swivel lever arrangement which ensuresfaster positive movement and engagement ofmodule inside the compartment.
Main busbars and control busbars totallysegregated from each other. Upto 11 numbercontrol bus per panel can be offered whichensure that solid links are used instead ofwires thus leading to reduction in inter-panelcabling.
Easy to operate and maintainOnly 8PUS1.5 has..
10
Totally enclosed main & vertical busbarcompartment.
Power terminals for lower rating being at therear, makes them unapproachable withouttaking out the trolley as well as ensuresmaximum area for cable routing in cable alley.
Gravity operated shutters ensures positiveisolation of module compartment withvertical busbars after the trolley is drawn out.
Finger touch proof controlgear& auxiliary contacts.
Door interlocks & padlockingfacility
The Switch fuse unit upto 125Acomes with built in lyra contactswith solid connections betweenthe switch, lyra contact andvertical busbars.
Provides safety
11
8PUF4.5Non Drawout Motor Control CentreEconomical, Reliable and Flexible
In certain applications, either there is no need toreplace components under operating conditionsor short idle times are acceptable. In such cases,Siemens 8PUF4.5 non drawout design offersexcellent economy, reliability and variability.
8PUF4.5 non drawout design offerseconomical yet reliable system
• High degree of safety by virtue of type-testedassemblies.
• Any combination of modular function units.
• Easy replacement of functional units afterde-energising the switchboard.
• Direct alignment with 8PUL4.5 or 8PUS1.5.
8PUF4.5 : more than a non drawoutpanel
• The modular functional units enable efficientinstallation and maintenance.
• Main busbars, vertical busbars as well ascable chambers are accessible even in doublefront panels.
• Internal separation between each functionalunits.
• Fully shrouded power cable terminationsensures shock hazard protection.
• All terminals are visible and can be testedfrom front.
12
8PUF4.5Technical Data
Rated Insulation 660V, 40-60HzVoltage
Rated operational 415V, 50HzVoltage
Rated Current Main Horizontal Busbars : 630A – 3200AVertical Busbars : upto 1400A
Short Circuit 50kArms,1sec and 105kA peakWithstand (Type tested design)
Ambient Standard 40ºCTemperature Optional 45ºC, 50ºC
Degree of Standard IP 52Protection Optional IP 54
Dimensions Standard W D H1-panel 980 x 560 x 2300mmSingle/doublefront unit withtop/bottomcable entry2-panel 1760 x 560 x 2300mmSingle/doublefront unit withtop/bottomcable entry
13
8PUF4.5Non Drawout Motor Control CentreEconomical, Reliable and Flexible
Vertical busbars are placed one behind the otherwith the access to the last vertical busbaravailable from front in case of single front panels& from both sides in case of double front panels.
Module width of 500 mm ensures betterequipment dispersion as well as safe & easyequipment replacement.
Wider Cable alley makes cable termination easy.
Door interlocks & padlocking facility.
Totally shrouded Power terminals.
Main busbars and control busbars aretotally segregated from each other. Upto11 number control bus per panel can beoffered which ensure that solid links areused instead of wires thus leading toreduction in inter-panel cabling.
Easy to operate and maintain Provides safety
14
Non CompartmentalisedDistribution BoardsCompact, Economical & Safe
Non compartmentalised distribution boards are newentrants in the Siemens Low Voltage Switchboards productrange. They are designed for the various industrialapplications as well as for the high rise buildings. Thesedistribution boards can be used for distribution of electricalpower for lighting and other resistive loads.
Compact, Flexible yet safe
• The incoming switching device (MCCB/SFU) is providedin a separate compartment.
• State of the art Siemens Switchgear (SFU / MCCB / MCBs)are used.
• All the outgoing MCBs are DIN rail mounted withadequate spacing between them.
• Metering devices can also be provided on the panel door.
• The height ranges from 500mm to 2000mm.
• Double door design are provided for extra safety.
• Wall mounted design upto 1500mm height and floormounted design for 1550mm and 2000mm heightdistribution boards are available.
• There is a flexibility for Top as well as Bottom Cableentry.
Floor mounting Distributionboard for the industrialapplications.
Wall mountingDistribution board for thehigh rise buildings.
Technical Data
Rated Insulation Voltage 660V, 50Hz
Rated Operational Voltage 415V, 50Hz
Rated Current IncomingSwitch/MCCB- 250A-400AOutgoing MCBs : upto 63A
Short circuit Strength 10kA
Degree of Protection IP 52
Dimensions W D H500 x 300 x 500mm – Wall Mounting
500 x 300 x 1000mm – Wall Mounting
500 x 300 x 1500mm – Wall Mounting
500 x 300 x 1550mm – Floor Mounting
600 x 500 x 2000mm – Floor Mounting
15
Low Voltage BusductCompact, Economical, and Safe
In any electrical system of an industry thebusduct is an important link to feed theincoming supply from transformer to the mainPower Control Centre. Siemens Low VoltageBusduct is type tested, light weight and verycompact. The bolted design ensures highdegree reliability and flexibility duringinstallation and maintenance.
Compact, Flexible yet safe
• High degree of safety by virtue of typetested assembly.
• Designed to match the connections of anymake Low Voltage transformers and anymake PCC panels.
• Compact size and light inweight ensures easyhandling duringinstallation.
• Bolted design makes thebusduct flexible and easyfor maintenance.
• Suitable for both indoorand outdoor applications.
• Positive earthing ofbusduct by earth busbarsrunning throughout thelength. Technical Data
Rated Insulation Voltage 660V, 40-60Hz
Rated Operational Voltage 415V, 50Hz
Rated Current upto 4000A
Short Circuit strength 50kA 1 sec.
Degree of Protection IP 54
16
8PU - Tested as per latestquality norms
Siemens 8PU is a type tested switchboardwhose physical characteristics weredesigned in the test laboratory both fornormal operating conditions as well as forfault situations. These type tests,conducted in an independent testlaboratory/Inhouse, assures maximumreliability and safety. A few of the majortype tests carried out are:
• Verification of temperature rise limits.
• Verification of impulse voltage.
• Verification of the short circuitwithstand.
• Verification of degree of protection.
Every Siemens 8PU switchboard assemblyundergoes routine testing before deliverywhich are :
• Inspection of the assembly includinginspection of wiring and electricaloperation test.
• Dielectric Test.
• Checking of protective measures andof the electrical continuity of theprotective circuits.
• Verification of mechanical operation.
Siemens 8PU adheres to the moststringent quality norms with a strictemphasis on the quality of materials andequipments that comprise the endproduct. Some of the salient features are:
• Conformances of our qualitymanagement system to ISO 9001.
• Conformances of our manufacturingfacility to ISO 14001.
• Computer assisted project planning atall stages of product manufacturing.
• Use of exclusive, high grade insulatingmaterial and reliable “Siemens” makeSwitchgear/Controlgear.
17
Product upgradation is a continuous process. Hence, data in this catalog is subject to change
without prior notice. For the latest information, please get in touch with our Sales Offices.
Siemens Ltd.
Industry SectorSwitchboards and BuswaysThane Belapur Road
Thane - 400 601Fax: +91 22 27623725
Siemens Ltd.
A&D-03-151-013
This replaces A&D-03-151-001
Your partners
SOUTH
Offices:
•Bangalore - 560001
1st Floor, Jyothimahal
#49, St. Marks Road
� : +91 80 22042000
Fax: +91 80 22224131
•Chennai - 600034
4, Mahatma Gandhi Road
� : +91 44 28334000
Fax: +91 44 28334088
•Coimbatore - 641018
7th Floor, East Wing, Global Towers
1057, Avinashi Road
� : +91 422 4336300
Fax: +91 422 4336310
•Hyderabad - 500004
5-9-19, Lakshmi Narsinh Estate
4th Floor, Secretariat Road
Opp. Secretariat, Saifabad
� : +91 40 23482500
Fax: +91 40 23243145
WEST
Offices:
•Ahmedabad - 380009
3rd Floor, Prerna Arbour
Girish Cold Drinks Cross Roads
Off. C. G. Road
� : +91 79 40207600
Fax: +91 79 40207699
•Mumbai - 400018
130, Pandurang Budhkar Marg, Worli
� : +91 22 24987000-02
Fax: +91 22 24987312
•Nagpur - 440010
5th Floor, Landmark Building
Ramdas Peth
� : +91 712 6633000
Fax: +91 712 6633111
•Pune - 411016
Tower B / 701 - 705, ICC Trade Tower
403A, Senapati Bapat Road
� : +91 20 2570 6000
Fax: +91 20 2570 6060
NORTH
Offices:
•Chandigarh - 160017
SCO 189 - 191, 3rd Floor
Sector 17C
� : +91 172 4690300
Fax: +91 172 4690399
•Lucknow - 226001
28/45, Ashok Marg
Opposite Indira Bhawan
� : +91 522 4031022, 4031000
Fax : +91 522 4031019
•New Delhi - 110002
4A, Ring Road, I.P. Estate
� : +91 11 42995000-09
Fax: +91 11 42995030
EAST
Offices:
•Kolkata - 700042
43 Shanti Palli, R B Connector
Eastern Metropolitan Bypass
� : +91 33 24449000, 24428641-47
Fax: +91 33 24449010 / 13
www.siemens.com/industry