doc techn hta janvier 2006 - girpi · the readings for the breaking pressures for hta® and hta®-f...

71
EDITION SEPTEMBER 2008 TECHNICAL DOCUMENTATION safety for your pipeworks SYSTEM’O ® HTA ® & HTA ® -F PIPES, FITTINGS and VALVES

Upload: others

Post on 22-Jun-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

EDITIONSEPTEMBER 2008

TECHNICAL DOCUMENTATION

safety for your pipeworks

SYSTEM’O®

HTA® & HTA®-FPIPES, FITTINGS and VALVES

Page 2: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

Main certifications

ATEC

Véritas Marine

Great Britain

France

France

Germany

France

Spain

UBAtcBelgium

SYSTEM’O® is over 98% recyclable.

* For more information, visit: www.vinyl2010.org

*

Page 3: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

TECHNICAL DOCUMENTATIONCONTENTS

Technical Sheet

0.0n° Technical Sheet

How to select the system best adapted to your needs ? 1.1

General characteristics SYSTEM’O®

• Applications 2.1 • Benefits 2.2 • Characteristics 2.3 & 2.4 • Operating conditions 2.5 & 2.6

Range 3.1 & 3.2

Works on pipes and fittings • Tools 4.1• Welding procedure 4.2 & 4.3• Recommendations 4.4• Commissioning inspection tests and putting into service 4.5

Expansion - contraction • Phenomenon - Calculations 5.1 & 5.2• Consequences - Remedies 5.3 & 5.4• Loop arm calculation 5.5• Use of expansion joints 5.6 & 5.7• Linear expansion compensators 5.8

Pipework environment • Monoklip® brackets 6.1 to 6.3• Basket trays for insulated pipes 6.4 • Insulation 6.5 & 6.6• Special cases 6.7

Pressures losses • Calculation rules 7.1• Diagram 7.2 to 7.6

Technical sheet • Pipes 8.1• Fittings 8.2 to 8.12• Monoklip® brackets 8.13 & 8.14• Wedges 8.15 • Gaskets 8.16 • Valves 16 to 63 9.1 & 9.2• Valves 75 to 110 9.3 • Non-return valves 10.1 & 10.2

Chemical resistance • Chemical resistance tables 11.1 to 11.7• Pipework treatments 12.1• Additives 13.1

Air conditionning networks 14.1 Specification

IMPORTANT DETAIL: the date on each page of this documentation is not a printing date but an updating date.

2008

Page 4: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O® KRYOCLIM® QUICKAIR®/ GIRAIR® PVC-U K62system system pressure fittings

PN: Working Pressure PN 10 (ø20 to 160)PN 25 (ø12 to 20)

(at 20°C)PN 16 (ø25 to 225)PN 10 (ø250 to 315)

Fire classification Bs1d0 M1 M2

Welding polymer RERFIX HPFIX RERFIX

Main French certifications* CSTB technical advice CSTB technical advice Approval NFPLNE fire certificate LNE fire certificate

not notACS applicable applicable ACS

Non permeable to oxygen

yes yes yes yes

Working temperatures (°C) [- 30° ; + 40°] [ 0° ; + 40°] +20°

HOW TO SELECT THE SYSTEMBEST ADAPTED TO YOUR NEEDS?

Technical Sheet

2008

1.1GIRPI, specialist of pipeworks made from synthetic materials, has developped complete systems to meet today’s require-ments in the building industry.

In addition to SYSTEM’O®, described in this documentation, GIRPI offers systems adapted to each application.

How to select the system best adapted to your needs?APPLICATIONS GIRPI SYSTEMS

Domestic hot SYSTEM’O®and cold water services

Low temperature heating HTA®

(see technical sheet 14.1)

Drainage up to 100°C HTA®-ECold water, swimming pool, irrigation, PVC-U K62water treatment

Comfort cooling/air conditioning KRYOCLIM®

Industrial cooling KRYOCLIM®

Air conditioning in the food industry KRYOCLIM®

Compressed air distribution QUICKAIR®/GIRAIR®

PN 25 (ø16 to 63) PN 16 (ø16 to 160)

PN 16 (ø32 to 160)

HTA® HTA®-FPN 12,5

(ø20 to 63)

NPD

PN 12,5

(ø16 to 110)

Bs1d0

GAFIX

LNEFire certificate

[+5° ; +90°] +20°100° without pressure up to 70°

HTA® HTA®-F

Drinking watercertified*

It is important to verify the chemical compatibility before using specific additives or specific fluids such as anti-freeze, etc...(see our technical documentation or ask GIRPI for tests)* Please consult us for certifications outside France.

Page 5: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL CHARACTERISTICSAPPLICATIONS

Technical Sheet

2008

2.1Preserving and maintaining water quality in distribution and supply pipeworks has become an absolute priority. Thatrequirement naturally applies to healthcare buildings, but also to public buildings and dwellings.

The safety of pipeworks depends upon a good design and a wise selection of materials in order to prevent efficientlybacteria proliferation risks, right from the start.

Experts recommend 3 fundamental actions to effectively restrict bacteria development in water pipeworks:- avoid stagnation and ensure effective water circulation,- fight against scaling and corrosion with network design and maintenance appropriate for water quality requirements andadapted to the installation’s specific characteristics,- keep the water within the pipeworks at a high temperature, or be able to elevate the temperature when required.

Domestic water networks can be treated in addition to the above: chlorine shock*, continuous chlorination*, temporarytemperature elevation (70°C for 1/2 hour).(*Treatments recommended by the French Ministry of Health’s D.G.S., please consult T.S.12.1).

Therefore, the pipeworks must be corrosion proof, prevent scale, prevent biofilm development, be compatiblewith chemical and thermal treatments, including cold water pipevorks.

GIRPI offers the solution to meet all of the above requirements: SYSTEM’O®, a complete system for domestic hot and cold water services.

SYSTEM’O® consists of:- HTA® pipe (brown): the solution for hot water services. - HTA®-F pipe (caramel/orange): the solution for cold water services.- One single range of fittings.- The Monoklip® range of pipe brackets.- One single welding polymer.

IMPORTANT SYSTEM’O® is a complete system, especially developped to bring global reliability. Therefore, all of the system’s elements mustimperatively be used. The use of components of external origin will make GIRPI’s guarantee null and void.

Page 6: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GéNéRAL CHARACTERISTICSBENEFITS

Fiche Technique

2.2

2008

STRONG ASSETS SYSTEM’O® :

- A complete system for domestic hot and cold water services.

- A cost effective solution.

- No risk of confusion: 2 different pipes, 1 single range of fittings, 1 single welding polymer.

- Fire classification: the SYSTEM’O® is Bs1d0 rated (Euroclasses). This is the best rating which synthetic materials canachieve.

- No corrosion: SYSTEM’O® is not susceptible to corrosion thus guaranteeing that your systems are sustainable andwaterproof.

- Limits scaling: one of the aggravating factors in bacteria formation.

- Makes the fight against bacteria easier.

- Suitable for chemical and heat treatment for both hot and cold water.

- Optimal water low: the smooth internal surface of SYSTEM’O® reduces frictional losses, prevents furring and scaling.

- Installation time under control: a professional solution facilitating installation, even on occupied sites. Lightweightpipes, simple tools, no fire permit required for installation.

- Safe joints: easy visual seal quality check, specific application tools, high performance joints.

- Dedicated bracketing: a wide range of Monoklip® pipe brackets Ø 16 to 160, fully appropriate for supporting SYSTEM’O®.

- Low noise SYSTEM’O® pipes.

- Recycling friendly: SYSTEM’O® is over 98% recyclable. * For more information, visit: www.vinyl2010.org

- Durability / Watertightness: designed for .

The elements which constitute HTA® & HTA®-F are ATEC certified under n°14/03-831 (C-PVC pipework system made ofpipes and fittings).Pipes series 4 for diameters 16 to 63 mm.Pipes series 6.3 for diametre 32 to 160 mm.

The ATEC certificate also covers the use of HTA® & HTA®-F fittings, and of the RERFIX welding polymer (no abrading,no scouring).

*

Page 7: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL CHARACTERISTICSTechnical Sheet

2008

2.3

1 MPa = 10 bar

1. PHYSICAL CHARACTERISTICS

2. MECHANICAL CHARACTERISTICS

Characteristics Standards Units ValuesPhysical aspect NF EN 15 877 — CompliesFire classification EN 13501-1 - EN 15015 — Bs1d0Density (volumic mass) NF EN ISO 1183-1 g/cm3 1,45 to 1,65Linear expansion coefficient ASTM D 696-70 mm/m.°C 0,065Thermal conductivity λ ASTM C 177-76 W/m.°K 0,16Shrinkage at 150°C (pipes) NF EN 743 % ≤ 5%Shrinkage at 150°C (fittings) NF EN 580 — Complies

Characteristics Standards Units ValuesBending under load temperature (pipe) NF EN ISO 75-1 °C ≥ 97

(fittings) ≥ 90VICAT softening temperature (pipe) °C ≥ 110(5 daN load) NF EN 727

(fittings) °C ≥103Tensile elasticity modulus (pipe) NF EN ISO 6259-1 MPa 3400Tensile strength atyield limit (pipe) NF EN ISO 6259-1 MPa ≥ 60Breaking tensile strength (pipe) NF EN ISO 6259-2 MPa ≥ 50Breaking elongation NF EN ISO 6259-2 % ≥ 40

Hardness: Shore D NF EN ISO 868 85

Resistance to static pressure• Pipe at 20°C time ≥1 h MPa σ = 46• Pipe at 80°C time ≥170 h ATEC 14/03-831 MPa σ = 13• Pipe at 80°C time ≥1000 h NF EN 921 MPa σ = 10• Fittings at 20°C time ≥1 h NF EN ISO 15 877• Fittings at 80°C time ≥3000 h ATEC Resistance to alternating pressure(On fittings and glued jointings) NF T 54 094Pressure NF T 54 034 20/60 barDiameters 16 to 90 = Frequency 1 Hz ATEC 14/03-831 Cycles ≥ 5000Diameters 110 and 160 = Frequency 0,42 Hz Cycles ≥ 2500

Page 8: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL CHARACTERISTICSTechnical Sheet

2.4

2008

� CHEMICAL RESISTANCEAny fluid or water containing chemical agent (in suspension or in solution) other (or in different quantities) than thosepermitted by the standards and regulations concerning drinking water are considered as chemical products.Therefore, their compatibility with HTA® and HTA®-F must be verified.

Refer to our table indicating the performance of C-PVC with respect to chemical agents, technical sheets 11.1 to11.7.

If in doubt, please contact both the product supplier and GIRPI technical services.

� PRODUCT QUALITYTo provide a constant quality level for its products and to guarantee its users that the stated performances are respected,GIRPI has implemented the control regulations imposed by the different French and international standards.The controls concern the physical and mechanical characteristics of the pipes and fittings.However, in addition to the above verifications and to guarantee the maximum reliability level in actual operating condi-tions, GIRPI has developped and carries out additional tests, as per NF T 54-094 standard.Thus, an alternate pressure test (on complete joint sections) is regularly carried out. This test simulates pressure shocksto which our products are submitted in live pipeworks (such as pressure hammers, flow speed variations). The couplingsare subjected to water hammer pressure cycles (20/60 bar) at 3600 cycles/hour for diameters 12 to 90 and 1500cycles/hour for diameters 110 to 160.

Furthermore, operational tests are constantly carried out on our laboratory’s testing rigs. This enables us to betterguarantee the adaptation of each component in the pipework to its own function.

The ISO 9001 V2000 certified procedures applied at all stages globally guarantee the technical performances of GIRPI’sproducts (industrial processes, logistics) and GIRPI’s Service quality (deliveries, technical assistance).

� ELECTRICAL CHARACTERISTICSCharacteristics Standards Units Values

Transversal resistivity (under1000 V) ASTM/D 257/76 Ohm.cm 1015

Dielectric constant (103 Hz) ASTM/D 150/74 3Angle of loss tangent (103 Hz) ASTM/D 150/74 10-2

Dielectric strength ASTM/ 149/75 KV/mm 25

Page 9: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL CHARACTERISTICSTechnical Sheet

2008

2.5� WORKING LIFETIMEThe working pressures and temperatures indicated in the following tables are determined for a working life of 50 yearswithout interruption.

Working pressures according to working temperatures are figured out by using regression curves as per standardNF EN ISO 9080.

� TESTING PRESSURE

A pressure pipework can be classified as PN 16 or PN 25 (with a safety factor of 2.5 after 50 years) if it can tolerate,during one hour, a pressure equal to 4.2 times this PN.

The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve,represented by a straight line with logarithmic scale.

This straight line is drawn on the basis of 1hour, 100 h, 1000 h and 10,000 h tests, at 20°C, 60°C, 70°C and 95°C, accordingto ISO 9080 standard.

PN Testing pressure1 hour

HTA®-F 16 approx. 67.2 bar HTA®

HTA® 25 approx. 105 bar

2,5 PN

4,2 PN

1 hour 100 h 1000 h 10 000 h 50 years

Page 10: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

OPERATING CONDITIONSTechnical Sheet

2.6

2008

� WORKING PRESSURES

The above table shows maximum working pressures for installations working continuously at the above temperatures fora duration of 50 years. The pressures indicated were figured out by using the corresponding regression curves with asafety coefficient superior to 2.

� APPLICATION CLASSESCovered by CSTB’s ATEC certificate, in PN25 and PN16.• European and international standards have modernised the application classes by incorporating operating periods atstabilised working conditions, but also overheating / malfunction periods for the heating appliances. For instance, class 2(HCWS) incorporates: a stabilised working period of 49 years at 70°C, a total of 1 year at 80°C for overheating periods,and a total of 100 hours at 95°C for malfunction situations.

� CERTIFIED FIELDS OF APPLICATION• Application classes 2 and 4 are in compliance with ISO 10508. According to that standard, it is reminded that, whateverthe application class used, the system must also allow for the transportation of cold water at 20°C for a duration of50 years, at a working pressure of 10 bar.• Class 2: domestic hot and cold water services (70°C).• Class 4: low temperature heating.• Cold water distribution: domestic cold water distribution network, to be capable of withstanding 70°C peaks for disinfec-tion purposes, under conditions such as described in the “technical maintenance guide for networks conveying water forhuman consumption inside buildings” about hot water distribution networks.• Centralised kitchens: drainage installations for laundries and industrial kitchens, or for heating plant condensates, witheffluent temperatures not exceeding 100°C, ending when entering grease interception units or cooling tanks. In the fra-mework of the above applications, the effluents are always and exclusively conveyed by gravity.

� GUARANTEES• For all applications specified in the technical documentation, regardless of pipe diameter, GIRPI has an insurance toguarantee installations which are carried out in accordance with its own general recommendations, and which respect thetemperature and pressure conditions and the nature of fluid specified above.

HTA®

Ø 16 to Ø 63PN 25 Series 4

HTA®

Ø 32 to Ø 160PN 16 Series 6.3

HTA®-F Ø 16 to Ø 160

PN 16 Working pressure

bar Working pressure

barWorking pressure

barTemperature

°C5 25 16 16

20 25 16 1640 20 1260 13 880 6 490 4 2

70°C peak 6for 30 minutes

International Servuce Maximal Malfunction Typical corresponding Previous designationsClasses Conditions Conditions Conditions application under old French

application class system

Class 2 70°C 80°C 95°C Domestic Hot and ECFS (HCWS) classfor 49 years for 1 year for 100 h Cold Water Services20°C for 25 years 70°C 100°C Low Temperature Heating

Class 4 & 40°C for 20 years for 2,5 years for 100 h (radiators or floor) Class 2& 60°C for 25 years

Page 11: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

SYSTEM’O® RANGE Technical Sheet

2008

3.1

1/2” 3/4”1/2” 3/4” 1”

Description TechnicalSheetRef.

16 20 25 32 40 50 63 75 90 110 125 160Diameters in mm

16 16 16 20 20 20 20 32 4020 20 25 25 25 25 40 50

25 32 32 32 32 50 6340 40 40 63 75

50 50 75 9063

16 16 20 20 20 25 50 90 7516 20 20 25 25 25 32 63 90

25 32 32 32 40 75 11040 40 50

50 63

C-PVC PIPES TUHTAF 8.1C-PVC PIPES THT 8.1

TUBHT 8.1

ELBOWS 90° H4M 8.2

ELBOWS 45° H8M 8.2

COUPLINGS HMA 8.2

CAPS HBO 8.3

BENDS 90° H4C 8.3

EQUAL TEES 90° HTE 8.3

TEES REDUCED 90° HTR 8.4

REDUCING BUSHES HRD 8.5LONG PATTERN

REDUCING BUSHES HRS 8.6LONG PATTERN

REDUCING BUSHES HRDC 63 8.6SHORT PATTERN 75ADAPTOR NIPPLES HEAL 8.6WITH BRASS THREAD HEBL 8.6ADAPTOR NIPPLES HEAS 8.7WITH STAINLESS STEEL THREADADAPTOR NIPPLES HEA 1/2” 3/4” 1” 1”1/4 1”1/2 2” 8.7

HEB 1/2” 1” 1”1/4 1”1/2 2” 8.7 HMIL 8.7

1/2” ou 3/4”

HALF SHELL ANCHORS HPTF 8.7

3 PIECE UNIONS C-PVC H3G/L 3/8” 1/2” 3/4” 1” 1”1/4 1”1/2 2” 8.8 & BRASS

3 PIECE UNIONS C-PVC H3F/L 3/8” 1/2” 3/4” 1” 1”1/4 1”1/2 2” 8.8 & BRASS

3 PIECE UNIONS C-PVC H3P 8.8

3 PIECE UNIONS C-PVC H3F/P 8.9 H3F/PB 8.9

HOSE TAILS HDC 8.9

THREADED INSERTS HFT 1/2” 3/4” 8.9

ADAPTORS FOR MEASURINGACCESSORIES WITH 1/2” THREAD

Page 12: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

SYSTEM’O® RANGETechnical Sheet

3.2

2008

Description Technical SheetRef.

SERRATED STUB HCS 8.10 FLANGESTHREADED ADAPTORS HMML 3/8” 1/2” 3/4” 1” 1”1/4 1”1/2 2” 2”1/2 3” 8.10 WITH BRASS INSERTTHREADED ADAPTORS HMMS 1/2” 3/4” 1” 8.10WITH STAINLESS STEEL INSERT

THREADED ADAPTORS HMM 1/2” 3/4” 1” 1”1/4 1”1/2 2” 8.10

PLAIN NIPPLES HMC 8.11TUBHT

TAP CONNECTORS HDR 1/2” 3/4” 1” 1”1/4 1”1/2 2” 8.11WITH BRASS NUTS

THREADED 90° TEES HTG 1/2” 1/2” 3/4” 8.11

THREADED 90° TEES HTGR 3/4” 3/4” 3/4” 8.11REDUCEDTHREADED ELBOWS 90° H4GL 1/2” 1/2” 3/4” 8.12WITH BRASS INSERTTHREADED ELBOWS 90° H4GP 1/2” 1/2” 3/4” 8.12WITH BACK PLATE BRASS INSERTEXPANSION JOINTS HCD/G 1/2” 1/2” 3/4” 1” 1”1/4 1”1/2 8.12

MONOKLIP BRACKETS HCKP 8.13

MONOKLIP BRACKETS HCK 8.13

MONOKLIP BRACKETS HCKC 8.14

WEDGES FOR MONOKLIP CALE1225 8.15BRACKETSWEDGES FOR MONOKLIP CALE3263 8.15BRACKETSWEDGES FOR MONOKLIP CALE3263/4 8.15BRACKETSWEDGES FOR MONOKLIP CALE75110 8.15BRACKETSFLAT GASKETS FOR JPVCS (FPM) 8.16FLANGE ADAPTORS JPNCS(EPDM) 8.16FLANGES BVR 15 20 25 32 40 50 60 80 100 125 150

8.1640 50 60 65 110

FLANGES BPA 40 50 60 8.1680 85 80 100 125

UNION BALL VALVES VHCEP 9.1

FLANGED BALL VALVES VHFEP 9.3 LINEAR EXPANSION COMP 5.4COMPENSATORNON RETURN VALVES HCB3P 10.1WITH DISCSNON RETURN VALVES HCBS 10.2WAFER TYPEWELDING POLYMER RERFIX 4.3

16 20 25 32 40 50 63 75 90 110 125 160Diameters in mm

65 80

Page 13: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

WORKS ON PIPES AND FITTINGSTOOLS

Technical Sheet

2008

4.1� CUTTING• The roller plastic pipe-cutterAllows for neat, clean cuts to be carried out.

• The chamfering pipe-cutterThis type of tool cuts and chamfers pipes in one single operation. According to the modeland size used, it can cut and chamfer pipes from Ø 32 to 160 mm, with the help ofreducing half-shells.

• The use of disk saws to cut pipes is strictly prohibited.

� TRIMMING - CHAMFERINGAfter cutting, the pipe must be trimmed inside and a chamfer must be made on the outside.These operations can be performed by means of the following tools:

• Trimming and chamfering coneThis tool can be used to trim the inside of the pipe, and on the other side, it chamfers the outside. Ref. GIRPI CONE50U for pipes Ø 16 to 50 mm

• Chamfering tool This tool chamfers the pipe outside from Ø 32 to Ø 160.Ref. GIRPI CHANF160

• Chamfering pipe-cutter (see “cutting” section).

• TrimmerThis reams the inside of pipes of all diameters. Ref. GIRPI EBAV1 Ø 20 to 160 mm• The use of tools including cutting or abrading disks to chamfer pipes isstrictly prohibited.

• Chain vice Polyurethane pipe-rests hold the pipe without any scratching.

• Strap wrench Maximum gripping power, with no risk of deforming the pipes or fittings (braidednylon strap).

• Bench vice When using such traditional vices, it is mandatory to clamp the pipes by meansof wooden notched pipe-rests.

� HOLDING TOOLS

IMPORTANT

pipe-rest

Page 14: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

WORKS ON PIPES AND FITTINGSWELDING PROCEDURE

Technical Sheet

4.2

2008

� CHECKS PRIOR TO WELDINGThe priming operation can be replaced by the cleaning of pipes and fittings with a clean cloth if the pipes and fittings areclean and dry, and the working zone is wholesome. Otherwise, the priming will be made with D171P cleaner to eliminateall traces of fat (finger marks, greasy dirt,...).Before welding it is important to make certain checks:a) on the pipes and fittings: see that they contain no sign of impact, deep scratches, etc...b) on the welding polymer: it must be fluid, homogeneous, check use-by date.

IMPORTANT- Water impairs the welding polymer and subsequently the welding quality. No cold welding will therefore be made if the

parts to be assembled are damp (prior drying required).- RERFIX can be applied when the temperature is over + 5° C and under + 35° C. Welding can take place at 0° C ambient

temperature with a welding polymer kept at 20° C.- The atmospheric conditions (temperature, humidity) considerably affect the curing time (drying, evaporation of

solvents) of the welding polymer.- At low temperature, the parts when assembled should be held together for 20 to 30 seconds.- In hot weather, the adhesive should be applied rapidly and the parts immediatly jointed.- So as to avoid evaporation of the welding polymer, the pot must be closed after each welding operation, and it must be

used as quickly as possible once opened, especially under warm climatic conditions.

� MARKING OF THE SOCKET LENGTH- Using a thick pencil or felt maker, draw a mark on the pipe at a distance equal to the corresponding socket depth.

This mark enables the application of the welding polymer over the necessary length, and helps the installer to checkwhether the penetration length of the male end in the socket is correct. The use of GIRPI’s socket gauge is recommended(ref. JAUGE)

E E

CUTTING CHAMFERING CHECKS WELDING POLYMERAPPLICATION

PUSH JOINTINGSTRAIGHT

Mark

Page 15: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL RULES OF INSTALLATIONWELDING PROCEDURE

Technical Sheet

2008

4.3� WELDING POLYMER APPLICATION

- Once the checks and marking have been done, apply RERFIX welding polymer, available in250 ml or 1 liter pots.

- To apply the welding polymer, use the brush provided with the pot. - Brushes provided with 250 ml pots are fit for use with sizes 16 to 40mm.- Brushes provided with 1 liter pots are fit for use with sizes 20 to 160mm.

For sizes smaller than 16mm or larger than 160mm, it is advised to use a suitable brush.

The use of any other means or method is prohibited, namely: fingers, wood sticks, or any other usten-sil. Dropping the pipes or fittings directly into the welding polymer pots is prohibited as well (suchpractices lead to the creation of thick welding polymer deposits, which can cause obstruction of smallbore pipeworks).

- Apply the cement moderately (in a thin coat) over the whole (the female) interlock length and overthe whole length of the male end (marked on pipe). The cement should be applied so as to obtain auniform, homogeneous coat, well spread over the whole interlock surface.

Owing to the standardized tolerance ranges of the male ends (pipe / spigots) and the sockets, some gap may appear. Inthis case, double welding must be carried out. This consists in coating the male end once, then the socket once, and final-ly the male end a second time, then joint them.CAUTION: diluting the welding polymer (e.g. by use of thinner) or modifying it by any method is prohibited.

� JOINTING- Immediately after applying the welding polymer, joint the two elements right home (as far as the marks previously traced) by pushing longitudinally and without twisting.- Keep held together for 5 seconds.

NB1: In certain cases it is necessary to mark the position of one element in relation to the other (see sketch above). NB2: On large sizes, 2 fitters must operate simultaneously, i.e one fitter will coat the male end, while the other fitter willbe coating the female end with welding polymer. This method enables a quick jointing, needed for a strong weld.

� DRYING TIMES- For drinking water applications:

� New installation: 24 hours.� Maintenance works: see table below.

6 bar • C-PVC = 60°Cø 16 - 63 ø 75 - 110 ø 125 - 160

Ambienttemperature

5 - 10°C11 - 35°C

2 h1 h

4 h2 h

24 h24 h

DRYING TIMES BEFORE PRESSURE TESTS:

Page 16: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL RULES OF INSTALLATIONRECOMMENDATIONS

Technical Sheet

4.4

2008

� NETWORK FLUSHING PROCEDURE. Drinking water pipeworksWhen dealing with drinking water networks, before first use, applicable rules must be followed, i.e. fill the pipeworks withwater, flush them and purge them.In France, for domestic hot and cold water services, the guidelines of CSHPF (French Hospitals’ health and safety com-mitee) dated 8th July 2003 apply:- For new networks, before first use, carry out 3 complete flushing cycles, each of them including a 24h water stagnationperiod followed by a complete purging operation.- For renovation works, before reinstatement of the installation, carry out a flushing operation in which the volume of waterdrained from the valve downstream of the point of repair (point B) and the point of repair itself (point A) approximatelyrepresents 10 times the volume of water contained by the pipework section comprised between those two points.

. Air conditioning pipeworksFan coil units, cooling beams, heat pumps, may contain traces of synthetic oils incompatible with HTA® pipework.Therefore, they must be flushed perfectly clean before installation. Please refer to T.S.14.1 for more detailed guidance.

� HANDLING AND STORAGEThe pipes and fittings will be stored separately on an even area, away from dust and sun. In all cases, take special careto avoid rough handling, impacts and especially with indenting, cutting or heavy objects, particularly in cold weather.

� THERMOFORMINGThermoforming of pipes from the SYSTEM’O® range (HTA® and HTA-F®) is strictly prohibited on the work site andinvolves cancellation of the GIRPI guarantee. For all direction changes, make use of standard HTA® fittings only. ContactGIRPI’S Technical Assistance when faced with particular problems.

� CONNECTIONS BETWEEN SYSTEM’O® AND THREADED METAL COMPONENTSFittings that are equipped with threaded metal components: HMML, HEAL, HEBL, H4GL, H4GP, can be used when hightorque is required for connections to metal threaded components. They allow for the use of traditional sealants, exceptanaerobic resins.

Excluding connection to wall plates (namely our reference GAAP), obtained by means of tap connectors (HDR reference),connections between HTA® and metal pipes, fittings and equipment featuring male or female threads (conical/taper orcylindrical/parallel) must be made by means of the CPVC/metal couplings provided for this purpose.

In no case should GIRPI’s SYSTEM’O® pipes and fittings be machine threaded inside or outside.For all other “all-HTA®” threaded fittings (HEA, HEB, HMM) with metal reinforcing rings, connections with cylindrical/parallelthreaded metal components is possible. In such a case, they will be connected by hand. If needed, the last ¼ turn shallbe done with a tool, preferrably a strap wrench, but the use of tow, hemp or anaerobic resins is prohibited, knowingthat excessive tightening can cause the fittings to break up.

The following sealants will be preferred:- PTFE (e.g. “Teflon”) tape, preferrably high density.- Soft silicon paste. Drying time: 24h, which can be reduced to 3h minimum for sizes ½” and ¾”.

Please contact the silicone paste manufacturers to get their confirmation as to the compatibility resistance andsealing capacity under pressure of their products.

Page 17: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

GENERAL RULES OF INSTALLATIONCOMMISSIONING, TESTS AND

PUTTING INTO SERVICE

Technical Sheet

2008

4.5� GENERALSYSTEM’O® pipes and fittings are inspected throughout their manufacture and are guaranteed for a use complying withtheir design, within the limits indicated.During the installation and before putting the SYSTEM’O® network into service, it is advisable to make a certain numberof checks, as with all other materials.In France, refer to guidelines DTU 60-31 (NF P41-211) and DTU 60-1 (NF P40-201).

� INSPECTIONa) Visual inspectionDuring and after installation, the pipes and fittings should be inspected so as to eliminate doubtful elements containing abnor-malities such as impacts and deep scores caused by unsuitable handling. Before the tests, the whole network will be visuallyinspected to eliminate any pipework section containing deep cuts or notches, large deformations due to sudden impacts, tracesof blow torch burns, etc... Any damaged part should be replaced before putting into service. The aim of the visual inspection is also to ensure that the ins-tallation complies with the drawings and hence the correct installation of all the components (connection, supports, monitoringand safety mechanisms, etc...).b) Leak testsAfter installation of the network, a leak test will be carried out (all parts of the network should be visible and accessible duringthat test). c) Pressure testThe network shall be filled with water (purge the air from all high points) and kept under pressure long enough to enable visualcontrol of all joints, and no less than 30 minutes (for large installations, test by sections). In France, consult DTU 60-1 (NF P40-201).The testing pressure will amount to 1.5 times the maximum working pressure, with a minimum of:- 6 bar for heating and cooling networks.- 10 bar for domestic hot and cold water services.. If a leak is detected on a welded joint, replace the leaking section and test again.. If a leak is detected on a mechanical joint, tighten the connection or replace gasket.d) Temperature testWhen raising the pipework’s temperature for the first time, the absence of leaks must be checked for all valves and joints.

� TEST BEFORE PUTTING INTO SERVICEOnce the leak tests have been made, it is advisable, in order to remove all foreign matter, to clean the inside of the network. All appli-cable tests and controls before putting into service must be carried out, according to all relevant regulations, rules and codes ofpractice.

� OPERATING CONDITIONSWhatever the use, the safety mechanisms necessary for the traditional protection of networks (regulation, pressure reductionand limitation, temperature regulation and limitation, shut off mechanisms, etc...), should be planned, installed and kept in per-fect working order throughout operation.a) VibrationsVibrations can be a source of disorders on both pipework and supports ; it is highly advisable to install a suitable system pre-venting vibrations from spreading.b) Sources of heat and UVBeing made from thermoplastic material, SYSTEM’O® should in no case be installed close to a source of heat causing a rise intemperature greater than its limits of use, and must be protected from exposure to ultraviolet rays.c) Prevention of impactsAs with all networks conveying pressurised fluids, SYSTEM’O® pipework systems must be protected from impacts which mightoccur in passage ways used by handling machinery or suspended loads in movement (use of safety barriers, railings, etc...).d) Chemical compatibilityHTA-F® pipes have been designed for the distribution of domestic cold water. For other applications, we draw your attention topotential compatibility problems if chemicals are introduced into the pipework.e) Air conditioning networksThe introduction of monopropylene glycol (MPG) antifreeze is prohibited.f) BracketingPipe brackets available on the marketplace may contain substances likely to cause alteration to SYSTEM’O® pipes. The use ofMONOKLIP® brackets is recommended.g) Insulation materialsElectric cable insulation materials contain substances that can potentially damage SYSTEM’O® pipes. Therefore, it is advisednot to store or install SYSTEM’O® pipes near electric cables.

Page 18: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

EXPANSION - CONTRACTION PHENOMENON - CALCULATIONS

Technical Sheet

5.1

2008

� THE PHENOMENONAll materials whatsoever:

- expand when the temperature rises,- contract when the temperature drops.

� CALCULATION PARAMETERS FOR HTA®

The linear expansion coefficient of HTA®

and HTA®-F is:

The installation of the system must take the elongation or contraction of the pipe into account, which is calculated by thisformula in which:

α = expansion-contraction coefficient (linear)L = length of the piping when installed, in metersΔT = temperature deviation in degrees Celsius/Centigrade (°C)(difference between the maximum or minimum temperature in service and the installation temperature).ΔL = length variation in millimeters (mm)(difference in length between L on installation and L in operation, i.e. elongation or shrinkage length).

Ex 1 : installation temperature + 10°Cinstalled length 10 mworking temperature (fluid or room) + 60°CΔT = 60 - 10 = 50°CΔL = 0,065 x 10 x 50 = 33 mm

Ex 1 : installation temperature (fluid or room) + 15°Cinstalled length 30 mworking temperature (fluid or room) + 5°CΔT = 15 - 5 = 10°CΔL = 0,065 x 30 x 10 = 19 mm

ABACUS to work out the ΔL resulting from the above formula (see descriptive sheet 5.2)

Exemple � : Find the ΔL of a 10 m long pipe section for a ΔT = 50°CAnswer: 33 mm

Exemple � : Find the ΔL of a 30 m long pipe section for a ΔT = 10°CAnswer: 19 mm to find that result take 3,0 m on Ox and read 1,9 on Oy passing by ΔT 30°C and multiply the result by 10 = 1,9 mm x 10.

GIRPI’s installation guide and rulers will enable you to figure out expansion loop dimensions and bracket positioning inchanges of direction. You can obtain then upon simple request from [email protected]

α = 0,065 millimeter per meter per °C (mm/m.°C)

ΔL = α x L x ΔT

L at + 15°C

L at + 5°CΔL

ΔLL at + 10°C

L at + 60°C

Page 19: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

EXPANSION - CONTRACTIONPHENOMENON - CALCULATIONS

Technical Sheet

2008

5.2

33

1,9

LENGTH OF PIPE (in m)

EXPANSION (in mm)

Page 20: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

EXPANSION - CONTRACTIONCONSEQUENCES

Technical Sheet

5.3

2008

� CONSEQUENCES OF CONTRACTION-EXPANSION AND SOLUTIONSUnder certain conditions, the elongation due to the expansion causes compression of the pipe resulting in buckling.Conversely, the shortening due to the contraction of the pipe cause it to be tensioned. The sketches below illustrate a num-ber of cases of compression or tension, which cause abnormal stress on the material and may cause serious disorders.

The French DTU, ATEC, SINDOTEC handbooks, and various guides all over the world concerning the installation ofpiping, whatever their nature, generally indicate that “when installing, it is necessary, in order to avoid disorders which maybe caused by variations in length, to recognise them and address them”.

� EXPANSION (compression between fixed points).DON’Ts:

- buckling of the pipe between anchors

- thrust on the walls, obstacles, jointings or on the materials forming an anchor

� CONTRACTION (tension between fixed points)- tensioning of pipes, mechanical couplings, jointings between anchors

- tensioning between walls, obstacles, jointings or material forming an anchor

Risk of deformation or separation

Risk of deformation or separation

(F.P.) (F.P.)(L.G.) (L.G.) (L.G.)

(F.P.) (L.G.) (L.G.)

(F.P.) (L.G.)

(F.P.)

(L.G.)

(F.P.) (F.P.)(L.G.) (L.G.) (L.G.)

(F.P.) (L.G.) (L.G.)

(F.P.) (L.G.)

(F.P.)

(L.G.)

Anchor (F.P.) (1)Guide (L.G.) (2)Action due to pipe movementFree Support

(1) PF: ANCHOR: This is a support blocking the pipework system at one point, in order to “orientate” the movements cau-sed by expansion and contraction.(2) LG: GUIDE: They support the pipes while allowing them to expand and contract freely.

••

Page 21: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

EXPANSION - CONTRACTIONREMEDIES

Technical Sheet

2008

5.4� THE REMEDIESIn order to avoid the disorders subsequent to the movements of the pipes, it is necessary to let them expand andcontract freely.

It is therefore necessary to:- Use pipe brackets allowing the longitudinal movements of the pipe to be guided (GUIDES).- See to it that there never is a straight length of pipe between 2 anchors, either by using a change in direction, or bymaking a loop (see illustration below).

1° Change in direction, which is generally efficient in most cases

2° Loop made with SYSTEM’O® pipes and fittings

3° Expansion joints (HCD/G flexibles)

� LINEAR COMPENSATORS (COMP BELLOWS)

Bellows and flexibles are elements which need no maintenance, but they are subject to wear. Assuch, they need to be checked at regular intervals (in France, refer to corresponding DTU guide-lines and NF standards, or equivalent relevant texts outside France). It must be possible to inspectthem, dismantle them, and replace them without having to dismantle the elements next to them.

(P.F.) (P.F.)(G.L.)(G.L.)

LOOP

CHANGE IN DIRECTION BRANCH

:Length of pipe section during installation.

:Length at maximum temperature.:Length at minimum temperature.:Length difference between L1 or L2 and L.:Length of loop’s arm.B

L1L

ΔLL2

expansion expansion

expansion expansion

Page 22: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

CONTRACTION - EXPANSIONCALCULATION OF LEG B

Technical Sheet

5.5

2008

EXAMPLE � :Determine Bfor a Ø 40 mm pipe anda ΔL of 53 mmResult: B = 1,55 m.

Calculation formula of loop leg:

B = 34 √ Ø x ΔL34: constant material value

Ø: external diameter

ΔL: length variation

EXAMPLE � :Determine Bfor a Ø 110 mm pipe anda ΔL of 28 mmResult: B = 1,85 m

1

FOR DIAMETERS 20, 25, 32, 40 50, 63 IN HTA

length

varia

tion (

in mm

)

B = Length of leg (in m)

FOR DIAMETERS 75, 90, 110, 125, 160 IN HTA

length

varia

tion (

in mm

)

B = Length of leg (in m)

Page 23: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

CONTRACTION - EXPANSIONFLEXIBLE EXPANSION JOINTS

Technical Sheet

2008

5.6

Flexible expansion joints supporting1) The first guide will be at distance � ≈ 75 mm (maximum distance), the next bracket in line will be at a distance � ≈ 120 mmfrom the first.2) The surface finish of the free support supporting the expansion joint will be such that the braiding is not deteriorated by friction.

Distance on installationDirection of expansion

D

Elbow H4MThreaded adaptor: HMML

Adaptor nipple: HEAL

Expansion joint:HCD/G Max. clearance

Absorbed expansionlength (ΔL)d

E

Ø pipeHTA-HTA-F Article D d E

162025

HCD/G16HCD/G20HCD/G25

180220280

100100100

230282338

Ø pipeHTA-HTA-F Article D d E

324050

HCD/G32HCD/G40HCD/G50

350420500

100100100

407442591

Free support(flexible expansion joint installed horizontally)

Anchor bracket

Guide bracketsGuide brackets Guide brackets

� FLEXIBLE EXPANSION JOINTS SUPPORTING

� WORKING PRESSURE FOR FLEXIBLE EXPANSION JOINTS FROM 5°C TO 100°C

16

HCD/G16

18

20

HCD/G20

18

25

HCD/G25

14

32

HCD/G32

10

40

HCD/G40

10

50

HCD/G50

7

Ø pipe HTAHTA-F

Article

Workingpressure

(bar)

Page 24: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

EXPANSION - CONTRACTION FLEXIBLE EXPANSION JOINTS

Technical Sheet

5.7

2008

� IMPLEMENTATION OF FLEXIBLE EXPANSION JOINTS To guarantee correct operation, the following rules must be respected when designing the installation and installing theflexible expansion joints:

a) respect the clearances defined on sheet 5.6b) ensure that the flexible expansion joint is not subjected to twisting during installation or during operationc) provide appropriate supporting in situations where the flexible expansion joint is overhanging.

INSTALLATION EXAMPLES:

in line

direction changeon same level

direction change on twodifferent levels

branch

Anchor

Guide

Pipework movements

Page 25: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

EXPANSION - CONTRACTIONLINEAR EXPANSION COMPENSATORS

Technical Sheet

2008

5.8

Absorption of expansion/contraction

REF. Contraction Expansion Length E BACKING STUB SCREWSPACING RING FLANGE

DILAPLAST mm + mm - mm mm REF REF DIM.COMP 40 20 30 100 62 BVR32B HCS40 M 16x50COMP 50 20 30 100 62 BPA40 HCS50 M 16x50COMP 63 20 30 100 62 BPA50 HCS63 M 16x50COMP 75 20 30 100 62 BPA65 HCS75 M 16x55COMP 90 20 30 100 58 BPA80 HCS90 M 16x60COMP 110 20 30 100 58 BPA100 HCS110 M 16x60COMP 125 20 30 100 58 BPA125 HCS125 M 16x60COMP 160 20 30 100 54 BPA150 HCS160 M 20x70

VERTICAL INSTALLATION HORIZONTAL INSTALLATION

� INSTALLATIONNever work with sharp tools, which may damage the rubber bellows.The flange screws must not protrude towards the bellow. Under operating conditions, the spherical bellow rolls on thesmooth disks of the flange. All parts must be fully deburred and cleaned (otherwise, there is a risk of damaging the bel-lows).Rubber parts must not be painted (solvents and chemical products have a negative effect).We recommend that you use spacer wedges when you install the DILAPLAST compensator. This will maintain the spa-cing defined at installation temperature (E).Torque: refer to sheet 8-16 for backing flanges.For more information about Dilaplast compensators, please consult GIRPI for technical assistance.

Please refer to sheet 5.1 to reckonexpansion or contraction.

L

Fixed pointAnchor

Strongly anchored axialguiding support

«E»

spac

ing to

be

resp

ecte

d wh

en in

stallin

g

Screw

Washer

Flange thread

Non protrudingscrew

WasherHCS stub flange

BVR or BPA backing ring

Spac

er

Anchoring point on floor

Ceiling or wall

Fixed point and anchoring point forDilaplast

HCS stub flange

BVR or BPA backing ring

Screw Washer

Strongly anchoredaxial guiding support

Anchor

Spacer

Page 26: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

MONOKLIP® BRACKETSGENERAL DESCRIPTION - SUPPORTING

SPACING

Technical Sheet

6.1

2008

� GENERAL DESCRIPTIONMONOKLIP® brackets have been especially designed to support SYSTEM’O® pipeworks. The pipe is allowed to move freely insidethe bracket as it expands and contracts. Depending on their size, they are offered with M6, M8 and 7x150 female threaded brassinserts, or with a plain 5.5mm diameter drilled base.

SYSTEM’O® is a complete system, specially developped to bring global reliability. Therefore, all of the system’s elements mustimperatively be used. The use of components of external origin will make GIRPI’s guarantee null and void, especially the use ofother brackets than MONOKLIP®.

In all cases, the supports:- shall continue to support their load even under temperature variation effects,- shall allow the pipeworks to expand freely,- shall keep the pipeworks which they support at enough clearance from any wall or obstacle so as to allow for the expansionmovements and also for the assembly and disassembly of the mechanical couplings and accessories (unions, flanges, valves,pressure limiters, etc... ),- shall in no event either injure or damage the pipeworks.

� SPACING OF SUPPORTS (FOR FILLED PIPEWORKS)

NOTE:For vertical pipes, the above distances can be multiplied by 1.3 up to 60°C and 1.2 for temperatures over 60°C. When tapsor heavy accessories are installed on a pipe, these must be supported independently.

� WEDGESMONOKLIP® brackets in sizes 16 to 25 can be heightened by using 20 mm high wedges (ref CALE1225) made for that purpose.- For MONOKLIP® brackets in sizes 32 to 63 use 20 mm or 4 mm high wedges (ref CALE3263) which can be piled up.- For MONOKLIP® brackets in sizes 75 to 110 use 20 mm high wedges (ref CALE75110) which can be piled up.

DISTANCE BETWEEN SUPPORTS(HORIZONTAL PIPES)

Øpipe ≤ 20° 40° 60° 80° 90°16 0,75 0,70 0,65 0,60 0,5020 0,85 0,80 0,70 0,65 0,5525 0,90 0,85 0,75 0,70 0,6032 1,00 0,95 0,85 0,75 0,6540 1,10 1,05 0,95 0,80 0,7550 1,25 1,15 1,05 0,90 0,8063 1,40 1,30 1,20 1,10 1,0075 1,50 1,40 1,25 1,10 1,0090 1,75 1,60 1,35 1,15 1,05

110 1,85 1,75 1,60 1,35 1,10125 1,90 1,80 1,65 1,35 1,15 160 2,00 1,90 1,75 1,40 1,20

Ambient or fluid temperature (°C)

Page 27: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

MONOKLIP® BRACKETS EXAMPLES

Technical Sheet

2008

6.2� EXAMPLES OF SUPPORTS

MONOKLIP® brackets

� ANCHORSAnchors can be made with HTA® kit HPTF available for sizes 25 to 63 mm.

CWS

HWSReturn

HWS

Support at bottomof riser

anchor on a pipe anchor on a tee

Shell

Page 28: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

MONOKLIP® BRACKETS ACCESSORIES - SPECIAL POINT

Technical Sheet

6.3

2008

IMPORTANT:The sliding supports must be positioned in such a way that the couplings or accessories do not come in contact withthem when the pipes expand and contract.

Various accessories or special points require specific supporting: this supporting must be carefully designed in eachcase, to prevent the pipes from being subjected to mechanical forces.

CASE TYPES OF SUPPORT REASONS� • C-PVC male and female Free or fixed on either side To avoid tension on threads due to

threaded fittings and hose (double support) movement out of axisnozzles

� • Valves and fittings On either side and often Weight, must operate without twisting with fixed point on pipe and threads(double support)

� • Hoses/Expansion joints (See technical sheet 5.6) To allow movement without rotation, without moving out of axis and withoutchaffing

� • Riser bottom Free or fixed depending on the case To support the weight of the riser� • Direction changes Forming a right angle To allow translation of the loop arm,

to prevent sag and wear

no ��

��

��

no

support

level 6

level 5

F.P.

F.P.

P.F.

F.P.

F.P.

F.P.

F.P.

F.P. P.F.

F.P.

F.P.

F.P.

F.P.

F.P.

F.P.

L.G.

L.G.

L.G.L.G.L.G.

G.L.

L.G.

level 1

For risers, we recommend that anexpansion compensating elementis installed (expansion joint, hose)at five (floor) level intervals.

foot support

valves

weight

weight

yes yes

hose

hose

F.P.

supportvalve

valve

Elbow

Equal tee 90°

Page 29: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

SELF SUPPORTING TRAYSTechnical Sheet

2008

6.4� DETERMINATION OF THE SELF SUPPORTING TRAY’S WIDTH• The total load to be supported must be centered on the basket tray.• Allow for enough clearance (for contraction and expansion) at the changes in direction.• Make clean openings (no sharp edges) to avoid damaging the insulating material and the pipe.

If the space between the pipe and the basket tray is not enough to compensate the contraction or the expansion, use one ofthe solutions presented on sheet 5.4: loop, flexible expansion joint, linear expansion compensator.

� BRANCHESWhen self-supporting trays are used, branches can be made above or below the pipes provided that a sufficiently large ope-ning is made without sharp edges, so as not to block or damage the insulating material or the pipe during expansion andcontraction movements.

Self-supporting tray width ≥ ( 2ø + E ) + 2ΔL maxi

Self-supporting tray width

Diameter after insulation

E: space between 2 pipes (flow and return), about10mm, according to fitting dimensions

LΔL : contraction/expansion

� DRAINSA sufficiently large opening must be made without sharp edges, so as not to block or damage the insulating material or the pipeduring expansion and contraction movements

Page 30: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

INSULATIONINSULATED PIPEWORKS

Technical Sheet

6.5

2008

� INSULATIONThe low thermal conductivity coefficient (λ = 0.16 W/mK) of CPVC and the high thermal resistance of SYSTEM’O® helpsreduce heat losses and delay the condensation phenomena. Like all other materials, SYSTEM’O® must be insulated tobe protected against frost, to reduce heat losses and to avoid condensation when the outside pipe temperature is belowdew point.Most insulation products can be used, except those whose installation requirements (e.g. use of certain adhesives) orchemical composition are not compatible with SYSTEM’O®.If in doubt, the user must check the insulation product’s compatibility with its manufacturer or with GIRPI.Condensation phenomena resulting from the circulation of fluids colder than ambient temperature have no physical orchemical influence on SYSTEM’O®. Therefore, insulation is not systematically required. The decision will be made according to the installation’s specific cha-racteristics, and to the consequences of potential condensation on the environment around the pipework. In comparison with traditional metal pipeworks, SYSTEM’O® delays condensation.

� SURFACE TEMPERATUREThe table hereunder, showing various surface temperatures, shows that the low thermal conductivity of SYSTEM’O® pro-vides you with a security margin in situations such as: underdimensionned insulation, incorrectly jointed insulation sec-tions, insulation’s accidental failure...

Example:

� The following table shows the heat losses (expressed in W/m) of SYSTEM’O® pipeworks (with or without insulation:

� APPLICATIONS:

* The above thicknesses are given as an indication only, and can vary according to the project’s location (i.e. dew point, ambienthumidity, ambient temperature will vary according to location) and to the network’s configuration (length, network loop design,fluid velocity). It is the user’s responsibility to have thicknesses checked by a specialised consulting engineer.

Fluid temperature = 50°C Insulation material Insulation material Insulation material Insulation material Ambient temperature = 20°C No insulation (λ=0.039W/mK) (λ=0.039W/mK) (λ=0.039W/mK) (λ=0.039W/mK)

he = 10/Wm2K Thickness = 9mm Thickness = 13mm Thickness = 19mm Thickness = 32mmø25 19,5 9,3 7,9 6,6 5,2ø50 37,3 15,9 13,1 10,6 7,9ø110 66,4 29,1 23,8 18,9 13,5

Surface temperature (non insulated)Metallic pipe HTA® pipe HTA® coupling

Fluid temperature = 7° ø25 7°C 9°C 12°CAmbient temperature = 23°C ø50 7°C 11°C 14°Che = 8 W/m2K ø110 7°C 12°C 15°CDew point = 16,1°C

Recommended thicknessApplication Temperature Recommended for internal useInsulation material (mm)*

Hot & Cold Water Services + 60°C/+ 70°C Mineral wool 25 - 30

Comfort cooling + 15°C in summer Rubber foam 0 - 9+ 35°C in winter

Heating / cooling “reversible” + 7°C for cooling Rubber foam 13 - 192-pipe air conditioning + 50°C for heating μ > 5000

μ: material permeability.

he: external surface exchange coefficient

Page 31: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

LAGGINGBASIC IMPLEMENTATION RULES

Technical Sheet

2008

6.6Contact GIRPI to obtain more detailed technical data sheets about each application and a personnalised thermal study.CAUTION:Insulation made from phenolic foam can cause brass to crack. If in doubt, please contact the insulation manufacturer for more information.

In France, the installation of the insulation must be done according to technical guidelines DTU 67.1 (thermal insulation ofrefrigerating pipeworks) and DTU 65.20.Outside France, please refer to applicable rules.SYSTEM’O® does not require need any anti-corrosion treatment before insulation.The fire rating of the insulating products must comply with the security standards against fire in public buildings.It is better not to glue directly the insulating materials on the SYSTEM’O® pipes and fittings.

� THERMAL RINGSTo prevent the insulating material from crushing at collar level, a thermal ring must be used. They allow HTA® and HTA-F®

pipes to expand and contract freely.

� IMPLEMENTATION OF RUBBER FOAMS AND EXTRUDED / CUT POLYSTYRENEPlease refer to manufacturer’s instructions and to applicable codes of practice.

Thermal ring

ReferenceF16B40F20B50F25B50F32B63F40B75F50B90F63B110F75B125F90B140F110B160

Ø pipe HTA®

(inside ring diameter)

162025324050637590110

Ø Monoklip®

(outside ringdiameter)

405050637590110125140160

Theoreticalthickness

12131316182024252525

Example for 32 mm ØThermal ring

F32B63

Monoklip®

Ø 63HCKC63

HTA® Ø 32

Page 32: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

SPECIAL CASES Technical Sheet

6.7

2008

� Passing through partitions and floors

When a SYSTEM’O® pipe goes through a wall or a floor, it must be protected by a rigid sleeve made of synthetic material, and preferrably C-PVC.The sleeve internal diameter is chosen with enough tolerance to allow the pipes to expand and contract freely.The sleeve must be long enough to protrude on both sides of the finished masonry element.

� Built-in or embedded installations

SYSTEM’O® can be built or embedded in the masonry as long as there is no disconnectable coupling in that pipeworksection. The following precautions must be respected.

• The pipe must be made integral with the masonry either by means of the couplings making up the system or usinghalf-shells onto the wall of the pipe.• Each time the pipe enters the masonry it must be protected against shearing by a sleeve which protrudes from thefinished surface of the masonry.• The chase will be filled with a homogeneous material without sharp gravel which could damage the pipe.• The commissioning tests must be carried out before filling the chase or pouring the concrete.

� BURIED INSTALLATIONSSYSTEM’O® pipeworks can be buried if the following precautions are respected:

• The bottom of the excavation must be levelled and free of large grained materials and have nosurface hard spots.• A carefully compacted bed of 10 cm minimum will be made of clean sand 0/10 containing lessthan 10 % of fines.• The backfill directly in contact with the pipe (comprised of sand containing less than 12 % offines and free of gravel with diameter greater than 30 mm) will cover the pipe to a depth of 15cm minimum and will be compacted.

• The covering backfill will be compacted in successive layers comprised of materials removed from the trench and whichcontain less than 30 % of elements greater than 20 mm.• The minimum total height of the backfill above the pipe will be:• general case: 60 cm • under road/rail traffic: 80 cm • under concrete slab: 40 cm

� LOOP SYSTEMIn larger networks, loops must be planned at early design stage. Loops allow for emergency and continuous water treat-ments especially in the event of an epidemic. Furthermore, loops help keep water at a constant temperature, and ensureconstant water flow.

� ASSEMBLY WITH FLANGES

� LOOP SYSTEMIn larger networks, loops must be planned at early design stage. Loops allow for emergency and continuous water treat-ments especially in the event of an epidemic. Furthermore, loops help keep water at a constant temperature, and ensureconstant water flow.

Mechanical coupling Socket Tee Elbow

20

70

4

14

25

80

4

14

32

90

4

14

40

100

4

18

50

100

4

18

63

100

4

18

75

110

4 or 8*

18

90

110

8

18

110

110

8

18

160

130

8

22

Ø pipeScrew

length (mm)Nb ofscrews

Screw Ø (mm)

ScrewBVR or BPA

flange

HCS serratedstub flange

HTA® pipe

* according to the type of flanges in use

Saddle piece

SleeveSleeveSleeve

Sleeve

Page 33: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

PRESSURE LOSSESCALCULATION RULES

Technical Sheet

2008

7.1� CALCULATION BASESThe quality of the internal surface condition of the SYSTEM’O® pipes and fittings guarantees a flow rate higher (for an equi-valent section) than the one provided by metal pipes.

To calculate the pressure loss in SYSTEM’O® pipes, GIRPI has had pressure loss nomograms at 7°C, 20°C, 45°C, 60°C,80°C produced by the CATED (Technical sheet 7.2 to 7.6).

These nomograms have been established using the formula:

with Colebrooks λ calculated as follows:

J = pressure losses (mCE/m)U = flow speed (m/s)D = pipe internal diameter (m)g = gravity acceleration (9,81 m/s2)λ = Colebrook factor (no measurement unit)Re = Reynold’s factor (no measurement unit) = ε = rugosity = 0,001 mmV = flow kinematic viscosity (m2/s)

When using antifreeze or additives, the viscosity of the resulting fluid must be taken into consideration to calculatepressure drops.

U2J = λ 2gD

UDV

1 ε 2,51= - 2 log ( + )√λ 3,7 D Re√λ

Page 34: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

USpeed(in m/s)

Nominal Ø (in mm)

Inside Ø (in mm)

QFlow rate

(in l/s)

JPressure loss (in mCE/m)

Designed and made by CATED (January 1997)

160

150

110

90

75

63 PN1663 PN2550 PN1650 PN2540 PN1640 PN2532 PN1632 PN25

25

20

16

SYSTEM’O®

7.2PRESSURE LOSSES ON PIPESNOMOGRAM AT 7°C

2008

Technical Sheet

125

Define expected flow rate in l/s and speed in m/s. Draw a straight line between the two to find out pipe size and pressureloss in m CE/m (i.e. in meters of water column per pipework linear meter).

Page 35: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

PRESSURE LOSSES ON PIPESNOMOGRAM AT 20°C

Technical Sheet

7.320

08

USpeed(in m/s)

Designed and made by CATED (January 1997)

JPressure loss(in mCE/m)

Nominal Ø (in mm)

Inside Ø (in mm)

QFlow rate

(in l/s)

63 PN1663 PN25

50 PN1650 PN25

40 PN1640 PN25

32 PN2532 PN16

125

Page 36: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

PRESSURE LOSSES ON PIPESNOMOGRAM AT 45°C

Technical Sheet

7.4

2008

USpeed(in m/s)

Designed and made by CATED (January 1997)

JPressure loss(in mCE/m)

Nominal Ø (in mm)

Inside Ø (in mm)

QFlow rate

(in l/s)

63 PN1663 PN25

50 PN1650 PN2540 PN1640 PN25

32 PN2532 PN16

Page 37: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

PRESSURE LOSSES ON PIPESNOMOGRAM AT 60°C

Technical Sheet

7.520

08

USpeed(in m/s)

Designed and made by CATED (January 1997)

JPressure loss(in mCE/m)

Nominal Ø (in mm)

Inside Ø(in mm)

QFlow rate

(in l/s)

63 PN1663 PN25

50 PN1650 PN2540 PN1640 PN25

32 PN2532 PN16

Page 38: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

PRESSURE LOSSES ON PIPESNOMOGRAM AT 80°C

Technical Sheet

7.6

2008

USpeed(in m/s)

Designed and made by CATED (January 1997)

JPressure loss(in mCE/m)

Nominal Ø (in mm)

Inside Ø (in mm)

QFlow rate

(in l/s)

63 PN1663 PN25

50 PN1650 PN25

40 PN1640 PN25

32 PN2532 PN16

Page 39: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.120

08

Differentiated colours of marking and cover according to the PN:- yellow marking and yellow cover for PN16,- white marking and orange cover for PN25.

CAUTION: • All the sizes indicated in the dimension sheets are in millimeters, when not specified.• All the threaded fittings are BSP :

- On HTA®, male threads are conical (taper) and female threads are cylindrical (parallel). - On brass, all threads are cylindrical (parallel).

IMPORTANT NOTE:With the constant concern to improve the range and quality of its products within the context of the standards used at pre-sent, GIRPI reserves the right to modify the dimensional characteristics of its pipes and fittings together with the scope ofits ranges, without prior notice.

Ø ≤ 50 : 3 m lengths with chamferred ends - Ø ≥ 63: 4 m lengths with chamferred endsHTA® C-PVC PIPES

HTA®-F PIPES

PN 25

Pack. mini Weight internal Cont.D Dn Reference PN thick(*) kg/ml Ø l/m32 25 THT3216 10 16 2,4 0,360 27,2 0,5840 32 THT4016 10 16 3,0 0,559 34,0 0,9150 40 THT5016 5 16 3,7 0,908 42,6 1,4263 50 TUBHT63 5 16 4,7 1,440 53,6 2,2575 65 TUBHT75 1 16 5,5 1,960 64,0 3,2190 80 TUBHT90 1 16 6,6 2,760 76,8 4,58

110 100 TUBHT110 1 16 8,1 4,310 93,8 6,91125 110 TUBHT125 1 16 9,2 5,56 106,6 8,92160 150 TUBHT160 1 16 11,8 9,200 136,4 14,6

PN 16

Pack Weight internal Cont.D Dn Reference PN mini(*) thick kg/ml Ø l/m

16 10 TUBHT163 10 25 1,8 0,140 12,4 0,1220 15 TUBHT203 10 25 2,3 0,220 15,4 0,1925 20 TUBHT253 10 25 2,8 0,330 19,4 0,2932 25 TUBHT323 10 25 3,6 0,540 24,8 0,4840 32 TUBHT403 10 25 4,5 0,840 31,0 0,7550 40 TUBHT503 5 25 5,6 1,307 38,8 1,1863 50 THT6325 5 25 7,1 1,945 48,8 1,87

(*) Number of pipes per bundle

PN 16Pack. mini Weight internal Cont.D Dn Reference PN thick(*) kg/ml Ø l/m

16 10 TUHTAF16 10 4 1,8 0,140 12,4 0,1220 15 TUHTAF20 10 4 2,3 0,220 15,4 0,1925 20 TUHTAF25 10 4 2,8 0,330 19,4 0,2932 25 TUHTAF32 10 6.3 2,4 0,360 27,2 0,5840 32 TUHTAF40 10 6.3 3,0 0,559 34,0 0,9150 40 TUHTAF50 5 6.3 3,7 0,908 42,6 1,4263 50 TUHTAF63 5 6.3 4,7 1,440 53,6 2,2575 65 TUHTAF75 1 6.3 5,5 1,960 64,0 3,2190 80 TUHTAF90 1 6.3 6,6 2,760 76,8 4,58110 100 TUHTAF110 1 6.3 8,1 4,310 93,8 6,91125 110 TUHTAF125 1 6.3 9,2 5,56 106,6 8,92160 150 TUHTAF160 1 6.3 11,8 9,200 136,4 14,6

Page 40: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.2

2008

D Dn Reference Z E A16 10 H4M16 9 15 2420 15 H4M20 11 16 3025 20 H4M25 14 19 3732 25 H4M32 17 23 4440 32 H4M40 21,5 27 5450 40 H4M50 27 32 6563 50 H4M63 31 38 8075 65 H4M75 38 44 9290 80 H4M90 46 52 112

110 100 H4M110 57 62 136125 110 H4M125 63,5 69 147 160 150 H4M160 81 86 190

ELBOWS 90°SOC.

D Dn Reference Z E A16 10 H8M16 4,5 14,5 2420 15 H8M20 5 17 3025 20 H8M25 6 19 3732 25 H8M32 7,5 24 4540 32 H8M40 9,5 28 5450 40 H8M50 11 32 6563 50 H8M63 12,5 39 8075 65 H8M75 18 44 9290 80 H8M90 19,5 52 115

110 100 H8M110 23,5 61,5 135125 110 H8M125 28 69 152160 150 H8M160 34,5 86,5 190

ELBOWS 45°SOC.

D Dn Reference Z E L A16 10 HMA16 3,5 15 33,5 2220 15 HMA20 3,5 17 37,5 2725 20 HMA25 3,5 19,5 42 3332 25 HMA32 3,5 23 49,5 4240 32 HMA40 3 27 57 5350 40 HMA50 3,5 31 65,5 6563 50 HMA63 3 38 79 7875 65 HMA75 4,5 45 94,5 9090 80 HMA90 5 51,5 108 106

110 100 HMA110 4 61,5 127 132125 110 HMA125 6 69 144 147160 150 HMA160 10 86 182 185

COUPLINGSSOC.

Page 41: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.320

08

BENDS 90° SOC.

D Dn Reference Z E A R20 15 H4C20 40 16 28 4025 20 H4C25 50 19 32,5 5032 25 H4C32 64 22 40 6440 32 H4C40 80 26 52 8050 40 H4C50 100 31 64,5 10063 50 H4C63 126 37,5 79,5 126

D Dn Reference Z E L A K16 10 HTE16 9 14 46 24 2320 15 HTE20 11 16 54 30 2725 20 HTE25 13,5 18 64 37 3232 25 HTE32 17 22 78 45 3940 32 HTE40 21 26 96 54 4850 40 HTE50 26 31 116 65 5863 50 HTE63 33 38 143 86 7175 65 HTE75 39 44 167 92 8390 80 HTE90 46 52 196 112 98

110 100 HTE110 56 62 235 133 118125 110 HTE125 84 69 306 150 153 160 150 HTE160 84 86 340 191 170

EQUAL TEES 90° SOC.

D Dn Reference E L A16 10 HBO16 16 21 2420 15 HBO20 16 23 3025 20 HBO25 20 28 3732 25 HBO32 24 33 4540 32 HBO40 28 38 5450 40 HBO50 33 44 6563 50 HBO63 39 54 8075 65 HBO75 44,5 60 9090 80 HBO90 54 72 111

110 100 HBO110 62 88,5 140125 125 HBO125 70 102 160160 150 HBO160 87 144,5 187

CAPS SOC.

Page 42: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.4

2008

D-d Dn Reference Z Z1 E E1 L A a20-16 15-10 HTR20/16 10 11 17 14 54 30 2425-16 20-10 HTR25/16 14 14 18,5 14 65 36,5 2425-20 20-15 HTR25/20 12,5 13,5 18,5 16,5 62 36,5 3032-16 25-10 HTR32/16 17 18 23 14 80 44,5 2432-20 25-15 HTR32/20 17 18 23 16 80 44,5 3032-25 25-20 HTR32/25 17 19 23 18,5 80 44,5 3740-20 32-15 HTR40/20 22 23 26,5 16 97 54 3040-25 32-20 HTR40/25 22 23 26,5 19 97 54 3740-32 32-25 HTR40/32 22 21 26,5 23 97 53,5 4550-20 40-15 HTR50/20 27 29 32 17 118 61,5 3350-25 40-20 HTR50/25 26 26 31,5 19 115 65 3750-32 40-25 HTR50/32 26 26 31,5 22,5 115 65 4550-40 40-32 HTR50/40 26 26 31,5 26,5 115 65 53,563-20 50-15 HTR63/20 32 31,5 37,5 17,5 139 80 30,563-25 50-20 HTR63/25 32 31,5 37,5 20 139 80 3763-32 50-25 HTR63/32 32 32 37,5 23 139 80 45,563-40 50-25 HTR63/40 32 32 37,5 26 139 80 5463-50 50-40 HTR63/50 32 32 37,5 31 139 80 6575-20 65-15 HTR75/20 38,5 38 44,5 16 166 80 3575-25 65-20 HTR75/25 38,5 38 44,5 19 166 92,5 3575-32 65-25 HTR75/32 38,5 38 44,5 22,5 166 92,5 4575-40 65-32 HTR75/40 38,5 38 44,5 26,8 166 92,5 5475-50 65-40 HTR75/50 38,5 38,5 44,5 32 166 93 6575-63 65-50 HTR75/63 38,5 38,5 44,5 38 166 93 8090-32 80-25 HTR90/32 46 46 52 23,4 196 114 4590-40 80-32 HTR90/40 46 46 52 26 196 114 5490-50 80-40 HTR90/50 46 46 52 32,5 196 114 6590-63 80-50 HTR90/63 46 46,5 52 38 196 114 8090-75 80-63 HTR90/75 46 46 52 44 196 114 93110-40 100-32 HTR11/40 56 56 62 26 236 135 54110-50 100-40 HTR11/50 56 56 62 31 236 135 65110-63 100-50 HTR11/63 55,5 56,5 62 38 235 135,5 80110-75 100-63 HTR11/75 56 56 62 45,5 235 135 93110-90 100-80 HTR11/90 56 56 62 51 235 135 108

REDUCING TEES 90° SOC.

Page 43: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.520

08

REDUCING BUSHES LONG PATTERNØ Spig - (øR) Soc.

D-d Dn Reference Z E e L25-16 20-10 HRD25/16 25,5 19 14,5 44,532-16 25-10 HRD32/16 30,5 23 15 53,532-20 25-15 HRD32/20 31 22,5 16,5 53,540-16 32-10 HRD40/16 36 27 14 6340-20 32-15 HRD40/20 36 27 16 6340-25 32-20 HRD40/25 36 27 19 6350-20 40-15 HRD50/20 44 32 17 7650-25 40-20 HRD50/25 44 32 19,5 7650-32 40-25 HRD50/32 44 32 23 7663-20 50-15 HRD63/20 55 39 17 9463-25 50-20 HRD63/25 55 39 19 9463-32 50-25 HRD63/32 55 39 23 9463-40 50-32 HRD63/40 55 39 27 9475-20 65-15 HRD75/20 63 45,5 17 108,575-25 65-20 HRD75/25 63 45,5 18,5 108,575-32 65-25 HRD75/32 63 45,5 23 108,575-40 65-32 HRD75/40 63 45,5 26,5 108,575-50 65-40 HRD75/50 61 45 32 10690-25 80-20 HRD90/25 75 52,5 19,5 127,590-32 80-25 HRD90/32 75 52,5 23 127,590-40 80-32 HRD90/40 75 52,5 26,5 127,590-50 80-40 HRD90/50 75 52,5 32 127,590-63 80-50 HRD90/63 74 52 39 126110-50 100-40 HRD11/50 91,5 61,5 31 153110-63 100-50 HRD11/63 90 62 38 152110-75 100-65 HRD11/75 90,5 61,5 44,5 152125-90 110-80 HRD12/90 99,5 68,5 52 168160-110 150-100 HRD16/11 128 86,5 62 214,5160-125 110-150-110 HRD16/12 120 86 68,5 206160-90 150-80 HRD16/90 126 87 51 213

Page 44: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.6

2008

D-d Dn Reference Z E L20-16 15-10 HRS20 2,5 15 17,525-20 20-15 HRS25 3 17 2032-25 25-20 HRS32 4,5 19 23,540-32 32-25 HRS40 5,5 23 28,550-40 40-32 HRS50 6,5 26 32,563-50 50-40 HRS63 8 31 3975-63 65-50 HRS75 7 37,5 44,590-75 80-65 HRS90 7,5 44 51,5110-90 100-80 HRS110 10 52 62125-110 110 HRS125 8 63 71

REDUCING BUSHES SHORT PATTERNØ Spig - (øR) Soc.

D-F Reference D1 Z E E1 A L L1 Nb pans16-3/8” HEAL16 20 32,5 17 15 32 49,5 11 820-1/2” HEAL20 25 41 19 17 36 60 15 825-3/4” HEAL25 32 43 22,5 19,5 41 65,5 16 832-1” HEAL32 40 49 27 23 49,5 76 19,5 840-1”1/4 HEAL40 50 55 31 26 60 86 22 850-1”1/2 HEAL50 63 55 37,5 31 66 92,5 22 863-2” HEAL63 75 63 43,5 37,5 82 106,5 26 875-2”1/2 HEAL75 90 71 51 43,5 100 122 30,5 890-3” HEAL90 110 83 61 51 117 144 35,5 8

F A

L1

D1 D

ZL

E

E1

ADAPTOR NIPPLES A SPIG./SOC. x male brass thread

ADAPTOR NIPPLES B SPIG./SOC. x male brass thread

For high torque

D-F Reference D1 Z E E1 A L L1 Nb pans16-1/2” HEBL16 20 36,5 16,5 14,5 32 53 13,5 820-3/4” HEBL20 25 43 19,5 17 41 62,5 16 825-1” HEBL25 32 45,5 23 19 49,5 68,5 19,5 8

D-d Dn Reference E L125-63 110-50 HRDC1263 38,5 69,5125-75 110-65 HRDC1275 44,5 69,5

REDUCING BUSHES SHORT PATTERNØ Spig - (øR) Soc.

Page 45: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.720

08

D-F Dn Reference D1 Z E A L20-1/2” 15 HEA20 27,5 28 16 30 4525-3/4” 20 HEA25 32 34 19,5 36 5332-1” 25 HEA32 40 42 22,5 47 6540-1”1/4 32 HEA40 50 44 26,5 55,5 7150-1”1/2 40 HEA50 63 45,5 31,5 68 7763-2” 50 HEA63 75 49,5 38,5 78,5 87,5

ADAPTOR NIPPLES A with stainless steel reinforcing insert for C-PVC male thread SOC. x male thread

Assembling: see Technical Sheet 4.4 D-F Dn Reference D1 Z E A L

16-1/2” 10 HEB16 23 27,5 15 24 4325-1” 20 HEB25 32 35,5 17 36,5 55,532-1”1/4 25 HEB32 40 40 21 47 6340-1”1/2 32 HEB40 50 43,5 23 54,5 69,550-2” 40 HEB50 63 49,5 27 68 82

ADAPTORS FOR MEASURING ACCESSORIES with brass threadSOC. x female thread branch

HALF SHELL ANCHORS

D-G Reference A1 Z E L A H Nb pans110 HMIL110/12 36 20 61 163 132 100 8 110 HMIL110/34 41 20 61 163 132 101 8

D Reference L D1 h25 HPTF25 19 33 2032 HPTF32 22 42 2740 HPTF40 26 53 3150 HPTF50 30 65 3863 HPTF63 37 78 48

LD

D1

h

D-F Reference D1 Z E E1 A L L1 Nbr sides20-1/2” HEAS20 25 41 19 17 36 60 15 8 25-3/4” HEAS25 32 43 22,5 19,5 41 65,5 16 8 32-1” HEAS32 40 49 27 23 49,5 76 19,5 8

ADAPTOR NIPPLES with 316 L grade stainless steel threaded insert SOC./SPIG. x male stainless steel thread

A D

E L

H

A1G

Z

Page 46: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.8

2008

D-G Dn Reference Z E E1 G1 A1 A2 L16-3/8” 10 H3G/L16 10 15 11,5 3/4” 29 27 36,520-1/2” 15 H3G/L20 8 18 14 1” 36 27 4025-3/4” 20 H3G/L25 9 19 15 1“1/4 45 32 4332-1” 25 H3G/L32 11 23,5 16 1”1/2 52 38 50,540-1”1/4 32 H3G/L40 12 27 20 2” 66 47 5950-1”1/2 40 H3G/L50 13 32 18 2”1/4 72 53 6363-2” 50 H3G/L63 12 38 22 2”1/2 89 65 72

D-G Dn Reference Z E L G1 A1 A216-3/8” 10 H3F/L16 34 15 49 3/4” 29 1820-1/2” 15 H3F/L20 33 18 51 1” 36 2125-3/4” 20 H3F/L25 51 19 70 1”1/4 45 2832-1” 25 H3F/L32 56 23 79 1”1/2 52 3340-1”1/4 32 H3F/L40 58 27 85 2” 66 4250-1”1/2 40 H3F/L50 63 32 95 2”1/4 72 4863-2” 50 H3F/L63 70 38 108 2”3/4 89 60

3 PIECE UNION C-PVC & BRASS with EPDM gasketC-PVC SOC. x BRASS Female thread

3 PIECE UNION C-PVC & BRASS with EPDM gasketC-PVC SOC. x BRASS Male thread

Assembling: see Technical Sheet 4.4

Assembling: see Technical Sheet 4.4

D Dn Reference Z E A K L16 10 H3P16 14 15 22 34,5 4420 15 H3P20 14 16,5 27,5 42,5 4725 20 H3P25 13,5 19 36 54,5 51,532 25 H3P32 14,5 22,5 41,5 62,5 6040 32 H3P40 15 27 53 75,5 6950 40 H3P50 19 31,5 59 83 8263 50 H3P63 22 38,5 74 100,5 99

3 PIECE UNION C-PVC with EPDM gasketSOC. x SOC

Page 47: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.920

08

D F Reference Z Z1 F1 L A A1 K E16 1/2” H3F/PB16 19 15 15 58,5 36 3/4” 13 15,520 1/2” H3F/P20 22 13 15 60,5 44 1” 43 17,520 3/4” H3F/PB20 22 17 16,5 66,5 44 1” 49 17,525 3/4” H3F/P25 25 18,5 16,5 71,5 56 1”1/4 52 19,525 1” H3F/PB25 25 20 19 75,5 56 1”1/4 56 19,5

3 PIECE UNIONS C-PVC with EPDM gasketSoc. x Male thread

- H3F/P or H3F/PB 3-piece unions have a C-PVC socket and a male C-PVC thread.- They can be connected with C-PVC and metal fittings (brass, maleable iron, stainless steel, carbon steel).- Only use TEFLON (PTFE) tape as a sealant (no tow).Alternatively, sealing pastes may be used if compatible with C-PVC.- The male thread is conical (taper).

D Dn Reference D1 E E1 L A16 10 HDC16 16,3 16 27 48 2420 15 HDC20 21 18 35 59 3025 20 HDC25 27,5 20 35 62 36,532 25 HDC32 33 23 36 67,5 4540 32 HDC40 42 26 45 80,5 53,550 40 HDC50 53 31 50 91,5 64,5

HOSE TAILS SOC. x SPIG. tail

HFT bushes transform a welded jointing into a threaded jointing in order to fasten accesso-ries (such as thermometers, pressure gauges, etc...) excluding any operating mechanism(taps, valves, etc...) or any moving part (hoses, for example).

THREADED BUSHES SPIG. x Female thread

Assembling: see Technical Sheet 4.4

D-G Dn Code E25-1/2” 20 HFT25 1932-3/4” 25 HFT32 23

Page 48: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.10

2008

D Dn Reference Z E D2 M A25 20 HCS25 3 20 41 7 3332 25 HCS32 3 23 50 7 4140 32 HCS40 3 27 61 8 5050 40 HCS50 3 32 73 8 6163 50 HCS63 3 39 90 9 7675 65 HCS75 3 44 106 10 9090 80 HCS90 5 51,5 125 11 108

110 100 HCS110 5 62 150 12 131125 125 HCS125 5,5 67,5 170 13 147160 150 HCS160 6 86 212 16 187

SERRATED STUB FLANGES to be used with flat gasket, delivered without gasketSOC.

D-G Dn Reference D1 Z E L A Nbr sides16-3/8” 10 HMML16 20 9 17 38,5 32 820-1/2” 15 HMML20 25 9 16,5 44 36 825-3/4” 20 HMML25 32 9,5 19,5 49 41,5 832-1” 25 HMML32 40 9,5 23 56,5 49,5 840-1”1/4 32 HMML40 50 7 31 64 60 850-1”1/2 40 HMML50 63 7 37,5 69,5 66 863-2” 50 HMML63 75 8 43,5 80,5 82 875-2”1/2 65 HMML75 90 13,5 51 91,5 100 890-3” 80 HMML90 110 18,5 61 108,5 117 8

THREADED ADAPTORS for high torqueSOC./SPIG x Female brass thread

D-G Dn Reference D1 Z E L A Nbr sides20-1/2” 15 HMMS20 25 9 16,5 44 36 825-3/4” 20 HMMS25 32 9,5 19,5 49 41,5 8 32-1” 25 HMMS32 40 9,5 23 56,5 49,5 8

THREADED ADAPTORS 316L for high torqueSOC./SPIG x female thread stainless steel

D-G Dn Reference Z E L D1 A Nbr sides20-1/2” 15 HMM20 5,5 16 38,5 25 34 625-3/4” 20 HMM25 5,5 19 42,5 32 40 632-1” 25 HMM32 5 22 48 40 50 640-1”1/4 32 HMM40 6,5 27,5 58,5 50 55 650-1”1/2 40 HMM50 8,5 31,5 63,5 63 66,5 663-2” 50 HMM63 9 41,5 78,5 75 76,5 6

THREADED ADAPTORS with metal reinforcing ring outsideSOC./SPIG x Female thread

Assembling: see Technical Sheet 4.4

Especially adapted for connection with metal threaded fittings and high torque

Page 49: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.1120

08

D Dn Reference L d16 10 HMC16 33 12,520 15 HMC20 37 15,525 20 HMC25 42 19,532 25 HMC32 49 2540 32 HMC40 57 3150 40 HMC50 67 3963 50 HMC63 80 4975 65 HMC75 92 64

PLAIN NIPPLES SPIG. x SPIG.

D-G Dn Reference Z E A116-1/2” 10 HDR16 20 15 2420-3/4” 15 HDR20 22 17 29,525-1” 20 HDR25 23 20 3632-1”1/4 25 HDR32 26 23 4540-1”1/2 32 HDR40 29 27 5250-2” 40 HDR50 31 32 65,5

TAP CONNECTORS delivered with flat gasket, anti-friction ring and brass loose nutSPIG. x Female brass thread

Assembling: see Technical Sheet 4.4NB: The gasket must be in contact with a flat surface

D-G Dn Reference Z E L A Z1 A1 L116-1/2” 10 HTG16 9 15 48 30 13 24 2920-1/2” 15 HTG20 13,5 17 61 30 12 30 3025-3/4” 20 HTG25 13,5 19,5 66 40 18 36 35

THREADED 90° TEES with metal reinforcing ring outsideSOC. x Female thread branch

Assembling: see Technical Sheet 4.4

THREADED 90° TEES REDUCEDSOC. x Female thread branch

with metal reinforcing ring outside

Assembling: see Technical Sheet 4.4

D G Reference Dn Z E A A1 L Z1 L140 3/4” HTGR4034 32 21,5 26,5 54 40 96,5 24 42,550 3/4” HTGR5034 40 26 33 65 40 118,5 28,5 4763 3/4” HTGR6334 50 33,0 38,5 79,5 40 142,5 35 53,5

Page 50: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.12

2008

THREADED ELBOWS 90° for high torqueSOC. x Female brass thread

Especially adapted for connection with metal threaded fittings and high torqueAssembling: see Technical Sheet 4.4

D-G Dn Reference Z E A A1 L16-1/2” 10 H4GL16 12 15 24 36 3220-1/2” 15 H4GL20 16 16,5 29 36 3225-3/4” 20 H4GL25 17 19,5 35 41 37,5

THREADED ELBOWS 90° with back plateSOC. x Female brass thread

Assembling: see Technical Sheet 4.4

D-G Dn Reference Z E A A1 L B16-1/2” 10 H4GP16 12 15 24 36 32 1720-1/2” 15 H4GP20 16 16,5 29 36 32 2125-3/4” 20 H4GP25 17 19,5 35 41 37,5 20,5

Distance between plate holes:50 mm

Plate hole size:8 mm

D-G Dn Reference LF LU DE DI16-1/2” 10 HCD/G16 330 380 18 1020-1/2” 15 HCD/G20 410 457 22 1325-3/4” 20 HCD/G25 520 592 28 1732-1” 25 HCD/G32 640 720 35 2240-1”1/4 32 HCD/G40 760 825 42 2850-1”1/2 40 HCD/G50 980 1067 50 34

EXPANSION JOINTSFlexible, with one male threaded brass end and oneloose female threaded nut

DE

DI: Internal diameterof the expansion joint

Page 51: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.1320

08

Diameter 16 to 25

MONOKLIP® BRACKETS Specially designed to support pipes. They are highly resistant, corrosion-proof, fitted instantly and allow the pipe to expandfreely.Max spacing between supports: see technical sheet no 6.1Monoklip® brackets with drilled bases can be used with countersunk-head screws Ø 4 and 5 mm.

MONOKLIP® BRACKETS in black polypropylene metal threaded insert M6, M8 or 7x150

MONOKLIP® BRACKETS in black polypropylene with drilled base Ø 5,5

L

L

D Dn Reference H A B C L E16 10 HCKP16/5 18 12 27 20 16 120 15 HCKP20/5 22 14 32 22 16 125 20 HCKP25/5 22 16 39 25 16 1

D Dn Reference H A B C L Ewith THREADED INSERT M6

16 10 HCK16/6 18 12 27 20 16 120 15 HCK20/6 22 14 32 22 16 125 20 HCK25/6 22 16 39 25 16 1

with THREADED INSERT M816 10 HCK16/8 18 12 27 20 16 120 15 HCK20/8 22 14 32 22 16 125 20 HCK25/8 22 16 39 25 16 1

with THREADED INSERT 7 x 15016 10 HCK16/7 18 12 27 20 16 120 15 HCK20/7 22 14 32 22 16 125 20 HCK25/7 22 16 39 25 16 1

NB: compatible with wedgesref. CALE1225, 20 mm high

NB: compatible with wedgesref. CALE1225, 20 mm high

Ø 16 to 25Polypropylene

black

Page 52: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.14

2008

D Dn Reference H A B C L

32 25 HCKC32/6 28 20 44 24,5 3440 32 HCKC40/6 32 24 55 24,5 3450 40 HCKC50/6 35 30 65,6 24,5 5263 50 HCKC63/6 35 41 79,5 24,5 52

32 25 HCKC32/8 28 20 44 24,5 3440 32 HCKC40/8 32 24 55 24,5 3450 40 HCKC50/8 35 30 65,6 24,5 5263 50 HCKC63/8 35 41 79,5 24,5 52

32 25 HCKC32/7 28 20 44 24,5 3440 32 HCKC40/7 32 24 55 24,5 3450 40 HCKC50/7 35 30 65,6 24,5 5263 50 HCKC63/7 35 41 79,5 24,5 52

with THREADED INSERT M6

with THREADED INSERT M8

with THREADED INSERT 7 x 150

Ø 32 to 63Polyamide

black

Diameter 32 to 63

NB: Compatible with wedges Ref. CALE3263, 20 mm high orRef. CALE3263/4, 4 mm high,which can be piled upon eachother.

NB: Compatible with wedge Ref. CALE75110, 20 mm high.

D-dn Reference d1 H A B C L d E J

75-65 HCKC75/8 M8 80 42 96 30 80 9 40 790-80 HCKC90/8 M8 80 49 113 30 80 9 40 7

110-100 HCKC110/8 M8 80 60 130 30 80 9 40 7125-125 HCKC125/8 M8 120 70 159 30 190 9 170 7160-150 HCKC160/8 M8 120 85 194 30 230 9 210 7

with THREADED INSERT M8Ø 75 to 160Polyamide

black

Page 53: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.1520

08

D Reference H d1 H12 to 25 CALE1225 26 16 20

WEDGES FOR MONOKLIP® BRACKETSØ 16 to 25 - 20 mm high - only compatible with Monoklip® brackets HCKC 16 to 25

D Reference H I L32 to 63 CALE3263 20 25 52

WEDGES FOR MONOKLIP® BRACKETS Ø 32 to 63 - 20 mm high - only compatible with Monoklip® brackets HCKC 32 to 63

D Reference H I L75 to110 CALE75110 20 30 80

WEDGES FOR MONOKLIP® BRACKETS Ø 75 to 110 - 20 mm high - only compatible with Monoklip® brackets HCKC 75 to 110

D Reference H I L32 to 63 CALE3263/4 4 30 80

WEDGES FOR MONOKLIP® BRACKETS Ø 32 to 63 - 4 mm high - only compatible with Monoklip® brackets HCKC 32 to 63

Page 54: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DIMENSION SHEETTechnical Sheet

8.16

2008

Reference Dn D I EJPVCS20 15 32 20 2JPVCS25 20 39 25 2JPVCS32 25 48 32 2JPVCS40 32 59 40 3JPVCS50 40 71 50 3JPVCS63 50 88 63 3JPVCS75 65 104 75 3JPVCS90 80 123 90 3JPVCS110 100 148 110 4JPVCS125 125 168 125 4 JPVCS140 125 186 140 4 JPVCS160 150 211 160 4JPVCS200 200 272 200 4

FLAT GASKETS FOR FLANGE ADAPTORS - VITONReference Dn D I EJPNCS20 15 32 20 2JPNCS25 20 39 25 2JPNCS32 25 48 32 2JPNCS40 32 59 40 3JPNCS50 40 71 50 3JPNCS63 50 88 63 3JPNCS75 65 104 75 3JPNCS90 80 123 90 3JPNCS110 100 148 110 4JPNCS125 125 168 125 4 JPNCS140 125 186 140 4 JPNCS160 150 211 160 5JPNCS200 200 272 200 4

FLAT GASKETS FOR FLANGEADAPTORS - EPDM

FLANGES PN16 according to DIN 16-966 (glass fibre reinforced polyester) - color: white

Pipe Flange Nbr TorqueReference A B C D E RØ Dn of holes20 15 BVR15 28 14 65 95 14 1,5 4 0,5 to 1 mkg25 20 BVR20 34 14 75 105 18 1,5 4 0,5 to 1 mkg32 25 BVR25 42 14 85 115 20 1,5 4 0,5 to 1 mkg40 32 BVR32B 52 18 100 140 20 2 4 2 to 4 mkg40 40 BVR40A 54 18 110 150 20 2 4 2 to 4 mkg50 40 BVR40B 63 18 110 150 20 2 4 2 to 4 mkg50 50 BVR50A 65 18 125 165 22 2,5 4 2 to 4 mkg63 50 BVR50B 78 18 125 165 22 2,5 4 2 to 4 mkg63 60 BVR60A 78 18 135 175 22 2,5 4 2 to 4 mkg63 65 BVR65A 81 18 145 185 22 2,5 4 2 to 4 mkg75 80 BVR80A 94 18 160 200 24 3 8 2 to 4 mkg90 80 BVR80B 110 18 160 200 24 3 8 3 to 4 mkg

110 100 BVR100 133 18 180 220 26 3 8 3 to 4 mkg110 110 BVR110A 133 18 190 230 24 3 8 3 to 4 mkg125 125 BVR125A 150 18 210 250 28 4 8 3 to 4 mkg160 150 BVR150 190 22 240 285 30 4 8 3 to 4 mkg

Drilled GN 10/16

FLANGES PN16 according to DIN 16-966 (glass fibre reinforced polyamide) - color: black

Pipe Flange Nbr TorqueReference A B C D E RØ Dn of holes50 40 BPA40 62,5 18 110 150 18 2,5 4 3 mkg63 50 BPA50 78,5 18 125 165 19 2,5 4 3 mkg63 60 BPA60 78,5 18 135 175 19 2,5 4 3 mkg75 65/60 BPA65 92 18 145 185 22 2,5 4 4 mkg90 80 BPA80 110 18 160 200 22 2,5 8 4 mkg

110 100 BPA100 133 18 180 218 24 3 8 5 mkg125 125 BPA125 150 18 210 250 26 3 8 5 mkg140 125 BPA140 167 18 210 250 28 4 8 5 mkg

Page 55: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DOUBLE UNION C-PVC BALL VALVESCEMENTED SOCKET ENDS

Technical Sheet

9.120

08

d Reference DN L Z C E H B g X Ø Fig.16 VHCEP16 10 14 69 97 47 45 66 160 31 5,5 A20 VHCEP20 15 16 70 102 47 45 66 160 31 5,5 A25 VHCEP25 20 19 82 120 57 55 78 260 31 5,5 A32 VHCEP32 25 22 87 131 68 67 86 380 40 6,5 A40 VHCEP40 32 26 98 150 86 83 100 655 45 8 B50 VHCEP50 40 31 101 163 98 91 110 925 50 8 B63 VHCEP63 50 38 121 197 122 11 130 1695 50 8 B

Ballvalve

Ø

16 202532405063

Screw Øfor

brassinsert(mm)5,55,55,56,5888

ANCHORING SYSTEM

These ball valves have a built-in anchoring system.There are two holes underneath fitted with threaded brassinserts (use screw in accordance with data below).These valves are solvent cemented to pipes, and can bedismantled thanks to their double union concept.

ø 16 to 63Nut

Welded/threaded socket end union

BodyBall

Ball seat supportHandleSpindle

Socket o’ringSeat gasket

Ball seatSpindle o’ring

Ball seat support o’ringSpindle o’ring

�������

1

1

5

9

9

13

2

2

6

1010

3

711

111213

48

8

12

Page 56: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

DOUBLE UNION C-PVC BALL VALVESCEMENTED SOCKET ENDS

Technical Sheet

9.2

2008

� FIELD OF APPLICATION• the same as that of CPVC HTA fittings (drinking water,food liquids, various fluids).• max. temperature of use: 80 °C • The nominal pressure (PN) in normal use, i.e. for waterat maximum 20°C is: 16 bar for Ø 16 to 63 mm.

DN 10 to 50

WORKING PRESSURE

Wor

king

pres

sure

(bar

)

Working temperature(°C)

OPERATION TORQUE(PRESSURE 16 BAR)

Pres

sure

loss

(kg/

cm2 )

Flow rate (l/mn)

d-G 16-3/8” 20-1/2” 25-3/4” 32-1” 40-1”1/4 50-1”1/2 63-2”Dn-G 10-3/8” 15-1/2” 20-3/4” 25-1” 32-1”1/4 40-1”1/2 50-2”KV 70 190 350 700 1000 1650 3100

FLOW COEFFICIENT AT FULL OPENING

Ø 16 20 25 32 40 50 63

Torque 2.0 3.0 3.0 5.0 6.0 9.0 9.0Nm

PRESSURE LOSSES ACCORDING TO FLOW RATES

ø 16 to 63

Page 57: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

FLANGED C-PVC BALL VALVESCEMENTED SOCKET ENDS

Technical Sheet

9.320

08

� FIELD OF APPLICATION • the same as that of CPVC HTA® fittings (drinking water, food liquids, various fluids).• max. working temperature: 80°C• the nominal pressure (PN) in normal use, i.e. for water at maximum 20°C is: 16 bar for Ø 75 to 110 mm.

Weight d Ref. EPDM l z h e b c a i (kg)75 VHFEP75 43 148 234 211 177 210 25 105 790 VHFEP90 52 148 252 211 177 210 25 105 7110 VHFEP110 63 174 300 252 220 255 30 121 11

The weight of the ball valve and its correct use require its anchoring on a convenient support.There are two holes underneath the valve body which allow to hang it with bolts on the correct support.The table above gives the width of the holes and their spacing.. Valves in Ø 75 to 110 are carefully assembled in our workshops. It is strongly recommended NOT to dismantle the bac-king plates which ensure good valve operation. The socket flanges may be dismantled.

A

11 1111

Ball valve Ø

7590110

X (mm)

110110135

ANCHORING SYSTEM

ø 75 to 110

HandleBodyBall

SpindleBall seat support

Cemented socket endNuts

Ball seatO-rings

Counterplate

�������

LEGEND�

b

c

a

e d

i

ll zh

Page 58: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

NON-RETURN VALVES CEMENTED SOCKET ENDS - UNION TYPE

Technical Sheet

10.1

2008

� GENERAL CHARACTERISTICS

Materials:• The different components of the GIRPI non return valves (disc type) are made of brown foodstuff quality injected C-PVC.• Disc � is made of black PPG.• Gaskets � and are made of EPDM.• Disc locking screws are made of stainless steel 18-6.Dimensions:• See table below.Assembly:• By bonding: female socket Ø 20 to 40 mm, meeting NF T 54-048, DIN 8063 and ISO 727 standards.Operating field:• The operating field of these non return valves is identical to that of our SYSTEM’O® system in C-PVC(drinking water, foodstuff liquids, industrial fluids, water treatment, swimming pools).Operating limits:• Maximum service temperature: 80°C.• PN16 at 20°C.Installation:• GIRPI non return valves can be installed horizontally or vertically.• Watertight with 1 bar minimum counterpressure.

D Reference L B A Z E20 HCB3P20 123,5 17 76,5 89,5 16 25 HCB3P25 129 17 76,5 90 1932 HCB3P32 155 21 84 109 2240 HCB3P40 189 32 102 135 26

Z

A

L

E

� Reducer to fit pipe’s OD� Disc O-ring� Disc� Disc locking screw� Rotating loose part Flat gasket Nut� Male threaded body

Page 59: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

NON-RETURN VALVESFLANGED WAFER TYPE

Technical Sheet

10.220

08

D Reference A B C E F50 HCBS50 73 21 18 15 8163 HCBS63 90 32 18 15 81� Disc O-ring

� Disc locking screw� Hanger� Valve body� Disc Flat gasket (thick. 3 mm)

� GENERAL CHARACTERISTICSMaterials:• Body � of the GIRPI non-return valve (wafer type) is made of brown foodstuff quality injected CPVC.• Disc � is made of black PPG.• Gaskets � and are made of EPDM.• Disc locking screws are made of stainless steel 18-6.• Hanger � is made of galvanised steel.

Dimensions:• See above table.

Assembly:• By flange: - the two flat gaskets are supplied with the check valve.

- Use GIRPI stub flanges (ref. HCS), glass fibre reinforced polyester flanges (ref. BVR)and glass fibre reinforced polyamid flanges (ref. BPA).

Operating field:• The operating field of these check valves is identical to that of our SYSTEM’O® system in CPVC(drinking water, foodstuff liquids, industrial fluids, water treatment, swimming pools).

Operating limits:• Maximum service temperature: 80 °C.• PN16 at 20 °C.

Installation:• GIRPI check valves can be installed horizontally or vertically.• Watertight with 1 bar minimum counterpressure.

Page 60: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

11.1

2008

The indications given in the tables below are extracts from French or foreign documents or the result of our own experi-ments. They cannot be considered to be absolute or guaranteed, as they are not valid in all specific operating conditions.It must also be noted that the nature of chemical agents and their mixtures, the presence of impurities, and the degree ofvulcanisation of elastomers, can lead to large variations in these indications; only practical tests in these cases can pro-vide valid results. We cannot be held liable for the indications given.The chemical agents are classified in alphabetical order.Meaning of symbols:2: Good resistance, 0: Not resistant (use not recommended), - : Not testedSPECIAL NOTE FOR BRASS:Some of the articles offered in SYSTEM’O® include brass components (a copper-zinc based alloy). These articleswere specially designed for potable water pipeworks. However, some particularly aggressive potable watersmight not be compatible with brass and cause brass components to deteriorate. Consequently, the people incharge of a project (contractors, consulting engineers, investors, etc.) need to check the potable water’s qualitywith the water supplying company, and get assurances from them and from the manufacturer that the water isindeed compatible with brass. Also, the compatibility of additives introduced into double purpose air conditio-ning networks (comfort cooling + heating in one single flow and return pipework) with brass must be checkedbefore use. You are requested to consult the manufacturer for applications other than domestic water servicesand double purpose air conditioning.

Acetaldehyde 0 0 0 - - - -Acetic acid (vapour) 2 0 0 2 - - 0Acetic acid 0-20% 2 2 2 2 - 2 -Acetic acid 20-30% 2 - 0 - - 2 -Acetic acid 30-60% 2 - 0 - - - -Acetic acid 80-100% 2 - 0 - - 0 0Acetic anhydride 0 0 0 - - - -Acetone 0 0 0 - - - -Acetylene 2 2 - 2 - 2 -Acid raw oil 2 2 2 - - - -Acid water for washing minerals 2 2 2 - - 2 -Adipic acid 2 2 2 2 2 2 2Allyl alcohol 96% 2 - - - - - 0Allyl chloride 0 0 0 - - - -Alum 2 2 2 2 2 2 2Aluminium chloride 2 2 2 2 2 2 2Aluminium fluoride 2 2 2 2 - 2 -Aluminium hydroxide 2 2 2 - - - -Aluminium nitrate 2 2 2 - - 2 2Aluminium oxychloride 2 2 2 - - - -Ammonia (dry gas) 2 2 2 2 1 0 -Ammonia (liquid) - 0 0 2 - 0 -Ammonium bifluoride 2 2 2 - - 2 0Ammonium carbonate 2 2 2 2 2 2 2Ammonium chloride 2 2 2 2 2 2 2Ammonium fluoride 2 - - 2 2 2 -Ammonium hydroxide 28% 0 0 0 - - - -Ammonium nitrate 2 2 2 2 2 2 2Ammonium persulphate 2 2 2 - - 2 2Ammonium phosphate 2 2 2 2 2 2 2(ammoniacal and neutral)Ammonium sulphate 2 2 2 2 2 2 2Ammonium sulphite 2 2 2 - - 2 2

C-PVC EPDM “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIVE

Page 61: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

C-PVC EPDM “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIVE

Ammonium thiocyanate 2 2 2 - - - -Amyl acetate 0 0 0 - - - -Amyl acid 2 2 2 2 2 1 1Amyl chloride 0 0 0 - - 2 -Anhydrous nitric acid 0 0 0 - - - -Aniline 0 0 0 - - - -Aniline chlorate 2 0 0 - - - -Aniline hydrochloride 0 0 0 - - - 0Aniline hydrochloride 0 0 0 - - 1 0Anthraquinone 2 - - - - 2 2Antimony trichloride 2 2 2 2 2 2 2Aqua regia (nitrohydrochloric acid) 2 2 2 0 - - -Arsenic acid 80% 2 2 2 2 2 2 2Asphalt 2 2 2 0 - - -Barium carbonate 2 2 2 - - 2 2Barium chloride 2 2 2 2 2 2 2Barium hydroxide 2 2 2 2 2 - -Barium sulphate 2 2 2 2 2 2 2Barium sulphite 2 2 2 - - 2 2Beer 2 2 2 2 - 2 2Beetroot (sweet liqueur) 2 2 2 - - 2 2Benzaldehyde 0 0 0 - - - -Benzine 0 0 0 - - - -Benzoic acid 2 0 0 2 2 2 2Benzol 0 0 0 - - - -Borax 2 2 2 2 2 2 2Boric acid 2 2 2 2 2 2 2Boric trifluoride 2 2 2 - - - -Brine 2 2 2 2 2 2 2Bromic water 2 2 2 - - - -Bromoethyl 0 0 0 - - - -Butadiene 2 2 2 0 0 2 2Butyl acetate 0 0 0 - - - -Butyl alcohol 2 - - 2 2 2 2Butylene 2 - - 2 - - -Butylnediol (erythritol) 2 0 0 2 - 2 -Butylphenol 100% 2 0 0 - 0 - -Butyric acid 2 0 0 1 - 2 1Calcium carbonate 2 2 2 - - 2 2Calcium chlorate 2 2 2 - - 2 -Calcium hydroxide 2 2 2 - - - -Calcium nitrate 2 2 2 2 2 2 2Calcium sulphate 2 2 2 2 2 2 2Cane sugar melasses 2 2 2 - - - -Carbon dioxide in aqueous solution 2 2 2 2 - 2 -Carbon monoxide - - - 2 2 - -Carbon sulphide 1 0 0 0 - - 2Carbon tetrachloride 1 0 0 0 0 2 2Carbonic acid 2 2 2 2 2 2 2Castor oil 2 2 2 - - 2 2Caustic potash 2 2 2 2 2 - 0Caustic soda 2 2 2 2 2 1 0Cellosolve 2 - - - - 0 0Chloral hydrate 2 2 2 - - 0 -

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

2008

11.2

Page 62: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

C-PVC EPDM “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIVE

Chloric gas (dry) - - - 0 0 - -Chloric gas (wet) - - - 2 - - -Chlorinated lime 2 2 2 2 2 2 2Chlorine water 2 2 2 2 - - -Chloroacetic acid 2 - - - - - 0Chlorobenzine 0 0 0 - - - -Chloroform 0 0 0 - - - -Chlorosulphonic acid 100% 2 - - - - 0 0Chromic acid 10% 2 2 2 - - 2 2Chromic acid 30% 2 - - - - 2 2Chromic acid 40% 2 - - - - 2 2Chromic acid 50% 2 - - - - 2 2Chromic alum 2 2 2 2 2 2 2Citric acid 20% 2 2 0 2 2 2 2Coke oven gas - - - 1 - - -Copper chloride 2 2 2 2 2 2 2Copper fluoride 2 2 2 2 - 2 -Copper nitrate 2 2 2 2 2 2 2Copper sulphate 2 2 2 2 2 2 2Core oil 2 2 2 - - - -Cottonseed oil 2 2 2 - - 2 -Cresol 90% 2 0 0 - - 2 -Cyclohexanol 0 0 0 - - - -Cyclohexanon 0 0 0 - - - -Demineralised water 2 2 2 2 2 2 2Dextrin 18% 2 2 2 2 2 2 2Dextrose 2 2 2 - - 2 2Diazotization salts 2 2 2 - - - -Diglycolic acid 30% 2 2 2 2 - 2 2Dimethylamine 0 0 0 - - - -Dioctyl phthalate 0 0 0 - - - -Disodic phosphate 2 2 2 - - 2 2Distilled water 2 2 2 2 2 2 2Dry sulphurous gas - - - 2 - - -Ether 0 0 0 - - - -Ethyl acetate 0 0 0 - - - -Ethyl acrylate 0 0 0 - - - -Ethyl alcohol 2 2 2 2 2 2 0Ethyl chloride 0 0 0 - - - -Ethyl chlorohydrine 0 0 0 - - - -Ethyl ether 0 0 0 - - - -Ethylenoxide 0 0 0 - - - -Fatty acid 2 2 2 - - 2 2Ferric chloride 2 2 2 2 2 2 2Ferric nitrate 2 2 2 2 2 2 2Ferrous chloride 2 2 2 2 2 2 2Fluoboric acid 2 2 2 - - - -Fluosilicic acid 2 2 2 - - - 0Formaldehyde 0 0 0 2 2 - -Formic acid 2 0 0 2 2 2 0Freon 12 2 - - 1 - 1 1Fresh water 2 2 2 2 2 2 2Fructose 2 2 2 - - 2 2Fruit juice and pulp 2 2 2 - - 2 2Fuel (containing SO4 H2) 2 2 2 0 0 2 -

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

11.3

2008

Page 63: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

C-PVC Joint EPDM Joint “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIF

Furfural 0 0 0 - - - -Gallic acid 2 2 2 - - 2 2Gelatine 2 2 2 2 - 2 2Glacial acetic acid 2 0 0 1 1 0 0Glucose 2 2 2 2 2 2 2Glycerine 2 2 2 2 2 2 2Glycol 2 2 2 2 2 2 2Glycol ether 2 2 2 2 2 2 2Glycolic acid 2 2 2 2 - 2 2Heptane - - - 1 - - -Hexane 2 - - - - 2 2Hydrobromic acid 10% 2 2 2 2 2 2 2Hydrochloric acid 0-25% 2 2 2 2 2 2 2Hydrochloric acid 20% 2 2 2 2 2 2 2Hydrochloric acid 25-40% 2 2 2 - - 2 -Hydrocyanic acid 2 2 2 - - 2 2Hydrofluoric acid 40% 2 2 2 - 0 2 2Hydrofluoric acid 60% 2 0 0 - 0 2 -Hydrofluosilicic acid 2 2 - - - 2 0Hydrogen - - - 2 2 - -Hydrogen peroxide 50% 2 2 2 - - 2 -Hydrogen peroxide 90% 2 2 2 - - -Hydrogen phosphorus 2 2 2 - - - -Hydroquinone 2 2 2 - - 2 -Hydroxylamine sulphate 12% 2 2 2 2 2 2 -Hypochlorous acid 2 2 2 - - 2 2Iodine - - - 1 1 - -Iron sulphate (copperas) 2 2 2 2 2 2 2Iron sulphate 2 2 2 2 2 2 2Kerosene 2 2 2 - 0 2 2Lactic acid 28% 2 2 - - - 2 2Lard 2 2 2 - - - -Lauric acid 2 2 2 - - - -Lauryl chloride 2 2 2 - - - -Lauryl sulphate 2 2 2 - - - -Lead acetate 2 2 2 2 2 1 1Lime sulphide 2 2 2 2 - - -Linoleic acid 2 2 2 - - 2 2Linseed oil 0 0 0 - - 2 2Liqueurs (beverages) - - - 2 - - -Liquid bromine 0 0 0 - - - -Lubricating oil 2 2 2 - - 2 -Magnesium carbonate 2 2 2 - - 2 2Magnesium chloride 2 2 2 2 2 2 2Magnesium hydroxide 2 2 2 - - - -Magnesium nitrate 2 2 2 2 2 - -Magnesium sulphate 2 2 2 2 2 2 2Maleic acid 35% 2 2 2 2 2 2 2Malic acid 2 2 2 2 - 2 2Melasses 2 2 2 2 2 2 2Mercuric chloride 2 2 2 2 2 2 2Mercuric cyanide 2 2 2 2 - 2 2Mercury 2 2 2 2 2 2 2Mercury nitrate 2 2 2 2 2 - -Methyl alcohol 10% 2 2 2 2 2 2 0

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

11.420

08

Page 64: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

C-PVC EPDM “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIVE

Methyl chloride 0 0 0 - - - -Methyl sulphate 2 2 2 - - - -Methylene chloride 0 0 0 - - - -Methylethylcetone 0 0 0 - - - -Monoethyleneglycol (MEG) 2 2 2 - - - -Milk 2 2 2 2 - 2 2Mineral oil 2 2 2 - - 2 2Naphtha 2 2 2 - - 2 2Naphthalene 0 0 0 - - - -Natural gas (dry) - - - 1 - - -Natural gas (wet) - - - 1 - - -Nickel chloride 2 2 2 2 2 2 2Nickel nitrate 2 2 2 2 2 2 2Nickel sulphate 2 2 2 2 2 2 2Nicotine 2 2 2 2 - 2 2Nicotinic acid 2 2 2 - - - -Nitric acid 30-50% 2 - - - - 2 -Nitric acid 50-60% 2 0 0 0 0 - 0Nitric acid 60% 2 0 0 0 0 0 0Nitric acid 68% 2 0 0 0 0 0 0Ocenol (non-saturated alcohol) 2 2 2 - - - -Oils and fats 2 2 2 - - 2 2Oleic acid 2 2 2 - 0 2 2Oleum 0 0 0 - - - -Oxalic acid 2 2 - 2 2 2 2Oxygen - - - 2 2 - -Ozone 2 2 2 2 2 1 1Palmitic acid 100% 2 2 2 - - 2 2Peracetic acid 40% 2 0 0 - - - -Perchloric acid 10% 2 - - 2 2 2 2Perchloric acid 70% 2 0 0 2 2 2 2Phenol 2 - - 0 0 - -Phenylhydrazine 0 0 0 - - - -Phenylhydrazine hydrochloride 2 0 0 2 - - -Phosgene (gas) 100% 2 - - 2 2 - -Phosgene (liquid) 0 0 0 - - - -Phosphoric acid 0-25% 2 2 2 2 2 2 2Phosphoric acid 25-50% 2 2 2 2 2 2 2Phosphoric acid 50-85% 2 2 2 2 - 2 2Phosphorus - - - - - - -Phosphorus pentoxide 2 - - 2 2 2 2Phosphorus trichloride 0 0 0 - - - -Photographic baths 2 2 2 2 2 2 2Picric acid 1% 0 0 0 2 - 2 2Potassium bicarbonate 2 2 2 2 2 2 2Potassium bichromate 2 2 2 2 - 2 -Potassium borate 2 2 2 2 2 2 2Potassium bromate 2 2 2 2 2 2 2Potassium bromide 2 2 2 2 2 2 2Potassium carbonate 2 2 2 2 - 2 2Potassium chlorate 2 2 2 2 2 2 2Potassium chloride 2 2 2 2 2 2 2Potassium chromate 2 2 2 2 - 2 -Potassium cyanide 2 2 2 2 - 2 2Potassium dichromate 2 2 2 - - 2 -

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

11.5

2008

Page 65: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

C-PVC Joint EPDM Joint “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIF

Potassium ferrocyanide 2 2 2 2 2 2 2Potassium ferrocyanide 2 2 2 2 2 2 2Potassium fluoride 2 2 2 2 - 2 -Potassium hydroxide 2 2 2 - - - -Potassium nitrate 2 2 2 2 2 2 2Potassium perborate 2 2 2 - - - -Potassium permanganate 10% 2 2 2 2 2 2 2Potassium persulphate 2 2 2 2 2 2 2Potassium sulphate 2 2 2 2 2 2 2Primary butanol 2 - - 2 2 2 2Propane - - - 1 1 - -Propargyl alcohol 2 2 2 2 2 - -Propyl alcohol 2 2 2 2 2 2 2Propylene dichloride 0 0 0 - - - -Raw ethyl acetate 0 0 0 1 1 0 -Raw petrol 2 2 2 0 - 2 2Rayon coagulating bath 2 2 2 - - - -Refined petrol 2 - - 0 - 2 2Saline 2 2 2 2 2 2 2Secondary butanol 2 0 0 2 2 2 2Selenic acid 2 - - - - - -Silicic acid 2 2 - 2 2 2 2Silver cyanide 2 2 2 2 - 2 2Silver nitrate 2 2 2 2 2 2 2Silvering solutions 2 2 2 - - - -Soaps 2 2 2 2 2 - -Sodium acetate 2 2 2 - - - -Sodium acid phosphate 2 2 2 2 2 2 2Sodium Arsenite 2 2 2 - - 2 2Sodium benzoate 2 2 2 2 2 2 2Sodium bicarbonate 36% 2 2 2 2 2 2 2Sodium bisulphate 2 2 2 - - - -Sodium bisulphite 2 2 2 2 2 2 2Sodium bromide 2 2 2 - - 2 2Sodium carbonate (soda ashes) 2 2 2 2 2 2 2Sodium chlorate 2 2 2 2 2 2 2Sodium chloride 2 2 2 2 2 2 2Sodium chlorite 2 2 2 2 - 2 2Sodium cyanide 2 2 2 2 - 2 2Sodium dichromate 2 2 2 - - 2 -Sodium ferrocyanide 2 2 2 2 2 2 2Sodium ferrocyanide 2 2 2 2 2 2 2Sodium fluoride 2 2 2 2 - 2 -Sodium hydroxide 2 2 2 2 2 - 0Sodium nitrate 2 2 2 2 2 2 2Sodium nitrite 2 2 2 2 2 2 -Sodium silicate 2 2 2 2 2 2 2Sodium sulphate 2 2 2 2 2 2 2Sodium sulphide 2 2 2 2 2 0 0Sodium sulphite 2 2 2 - - 2 2Sodium thisulphate (or hypo-) 2 2 2 2 2 2 2Soft raw oil 2 2 2 - - - -Stannic chloride 2 2 2 2 2 2 2

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

11.620

08

Page 66: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

CHEMICAL RESISTANCE TABLES Technical Sheet

11.7

2008

C-PVC EPDM “Viton”FPM

20°C 60°C 80°C 20°C 60°C 20°C 60°CREACTIVE

Stannous chloride 2 2 2 2 2 2 2Stearic acid 2 2 2 2 2 2 2Stoddard solvent 2 2 2 - - - -Sulphur 2 2 2 2 2 2 2Sulphuretted hydrogen (dry) - - - 2 2 - -Sulphuretted hydrogenin aqueous solution 2 2 2 2 2 1 0Sulphuric acid 0-40% 2 2 2 2 2 2 2Sulphuric acid 40-80% 2 2 0 2 - 2 2Sulphuric acid 80-90% 2 0 0 0 0 2 2Sulphuric acid 95% 2 0 0 0 0 - 0Sulphuric anhydride 2 0 0 - - 0 -Sulphurous acid 2 0 0 - - 2 2Tannic acid 2 2 2 - - 2 2Tartaric acid 2 2 2 2 - 2 2Tertiary hexanol 2 2 2 2 - - -Tetraethyl lead 2 2 2 - - - -Tetrahydrofurane 0 0 0 - - - -Thionyl chloride 0 0 0 - - - -Titanium tetrachloride 2 0 0 0 0 - -Toluol or toluene 0 0 0 - - - -Town gas - - - 1 - - -Tributyl phosphate 0 0 0 - - - -Trichlorethylene 0 0 0 - - 2 -Tricresylphosphate 0 0 0 - - - 0Triethanolamine 0 0 0 - - - -Triethylamine 2 2 - - - 2 2Trimethylolpropane 10% 2 2 2 2 2 2 2Trisodic phosphate 2 2 2 - - 2 2Turpentine essence 2 2 2 1 - - -Urea 30% 2 2 0 2 2 2 2Urine 2 2 2 2 2 2 2Vinegar 2 2 2 2 2 - -Vinyl acetate 0 0 0 - - - -Wet carbon dioxide - - - 2 2 - -Wet sulphurous gas - - - 2 - - -Whisky 2 2 2 2 - 2 2Wines 2 2 2 2 - 2 2Xylene or Xylol 0 0 0 - - - -Zinc chloride 2 2 2 2 2 2 2Zinc chromate 2 2 2 2 - 2 -Zinc cyanideinc 2 2 2 2 - 2 2Zinc nitrate 2 2 2 2 2 2 2Zinc sulphate 2 2 2 2 2 2 2

Page 67: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

SYSTEM’O®

TREATMENT OF PIPEWORKSTechnical Sheet

2008

12.1

� CURATIVE SPOT TREATMENT

� CONTINUOUS TREATMENT

Bacteria which are potentially harmful to human beings and which contaminate pipeworks for hot and cold water servicesmust be eradicated using two treatment procedures: temperature elevation and chemical attack. The recommendationshereunder originate from the French Ministry of Health (DGS).

USED FOR CONTINUOUS TREATMENTS(Decontamination agent concentrations must remain compatible with potable water / feeding applications).

Chlorinated agents generating hypochlorites: Free Chlorine concentration equal or superior Sodium hypochlorite NaOCl, to 0.3mg/l according to the pipework, and to Molecular, Chlorine Cl2, the water’s quality and pH (concentrationCalcium hypochlorite, Ca(ClO)2 must not remain below 1mg/l at all times).This table was made according to the recommendations of the French High Council for Public Hygiene, taking into account thespecific requirements of health establishments.

USED FOR CURATIVE SPOT TREATMENTS IN DISRUPTED PIPEWORKS(Concentration levels of decontamination agents are given as an indication.

It must be ensured before use that the pipework materials are compatible with the recommended decontamination agents,at the concentration levels indicated).

Chlorinated agents generating hypochlorites: - 100mg/l free chlorine for 1hSodium hypochlorite NaOCl, - Or 50mg/l free chlorine for 12hMolecular, Chlorine Cl2, - Or 15mg/l free chlorine for 24hCalcium hypochlorite, Ca(ClO)2)This table was made according to the recommendations of the French High Council for Public Hygiene, taking into account the speci-fic requirements of health establishments. The decontamination processes recommended for spot treatments are not approved forlarge pipeworks. Therefore, those spot treatments are not quoted in the guide.It must be checked that the silver based stabilisers used are authorised by the Ministry of Health.

Page 68: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

HTA®

REFRIGERATION FLUIDS AND OTHERTechnical Sheet

13.1

2008

In general, heating / cooling (8°C / 50°C) so-called “reversible” 2-pipe air conditioning networks do not require the additionof any antifreeze fluid, since the use of such fluids would dictate the increase of some network components’ sizes. Should the network require the use of an antifreeze, an anticorrosion or a bactericide fluid, the compatibility of such fluidswith HTA® must be checked with their manufacturers or with GIRPI’s Technical Assistance.

Monopropyleneglycol (MPG) is not compatible with CPVC material.

• Air cooling terminal units (e.g. fan coil units, cooling panels, cooling beams…) may contain residual quantities of metalmachining lubricating oils (generally located in the coils). Such oils are not compatible with CPVC and can cause the pipe-work to suffer from major disorders. It is your responsibility to get your supplier to guarantee the coils’ cleanliness before installation

• Products containing: esthers, ethoxyles, amines are not compatible with CPVC.

• Silica and Phosphate based anticorrosion fluids are known to corrode the EPDM components of the flexible expansionjoints. Their use is prohibited. More generally, the compatibility of such anticorrosion fluids with flexible expansion jointsmust be checked with their manufacturers.

It is reminded that for all comfort cooling or chilled water applications, GIRPI’s KRYOCLIM® pipework systemis perfectly adapted.

Page 69: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

HTA®

AIR CONDITIONING NETWORKS ADVICE AND PRECAUTIONS CONCERNING

AIR CONTITIONING NETWORKS FEATURING HEAT PUMPS

Technical Sheet

2008

14.1� GENERAL PRECAUTIONS VALID FOR ALL INSTALLATIONSIn every case, particular attention should be paid to the cleanliness and absence of any oil trace on the teminal units (fancoil units, cooling beams, etc.). It is the installer’s responsibility to make contact with his supplier or to clean the terminalunits. In order to avoid the accidental introduction of synthetic oil or traces of synthetic oil into the HTA® pipework, the HTA® net-work must be separated from the heat pump by means of a “heat exchanger” installed between a primary CHW networkmade from another material than HTA® (e.g. metal) and a secondary CHW network made from HTA®, following the diagrambelow:

� MAINTENANCE OF THE PIPEWORKIn order to prevent sludge from building up inside and around the pipes, their corrosion due to various deposits must beavoided by:- Periodical visual checks of the pipework’s state of cleanliness.- As soon as a leak seems to appear, check for the absence of corrosion or cracks by using endoscopy, ultrasounds ormagnetic / electric fields (“courants de Foucault”).

� MAINTENANCE OF THE CHILLER UNITDuring the unit’s working life, service controls and tests must be carried out in accordance with applicable regulations.Any leak, however small, is unacceptable. Every measure should be taken to avoid leak risks, and immediate actionshould be taken to eliminate each and every detected leak.Every sampling process and emptying of the refrigeration fluid in the primary circuit must be carried out by a qualifiedtechnician and with adapted material.Yearly leak control operations must be recorded in the maintenance book.For big sized machines, a vibratory signature (“signature vibratoire”) must be carried out when first started, and periodi-cally during the installation’s working life.

� MAINTENANCE OF THE PRIMARY CIRCUIT (CONTAINING REFRIGERATION FLUID)The pipework must be flushed perfectly clean before use, as well as the chiller unit’s heat exchangers, and the exchan-gers of the terminal units (fan coil units, cooling beams, etc.).The installer must make sure that the units installed have been properly cleaned before delivery, and that the antifreezerefrigeration liquids are compatible with the materials installed (gaskets – pipeworks).Take every precaution to avoid installation disorders such as the generation of sludge.The system must always be kept in perfect working orderPeople in charge of the air conditionning installation’s maintenance and cleaning need to protect themselves from at leastthree problems:

1) Internal corrosion of the pipes which may lead to the formation of holes or leaking cracks.2) Vibrations transmitted at exchanger level, which may cause the pipework to break.3) Refrigeration liquids freezing solid.

Heatpump

Heat exchanger

Page 70: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

DESCRIPTION FOR SPECIFICATION

Pipework system made from synthetic material (CPVC) for the transportation of hot andcold pressurized fluids.

FIELDS OF APPLICATION:Hot Water Services and Cold Water Services (HWS & CWS).

IDENTIFICATION:The pipes shall be coloured all through their mass, and their colour will allow for differenciation between CWS(orange) and HWS (brown).Only one type of fittings, coloured all through their mass, shall be used (brown).Only one welding polymer (orange), allowing for the commissioning of welds, shall be used. The range of pipes for HWS shall be:

- PN25 from diameter 16 to 63 - series 4.- PN16 from diameter 32 to 160 - series 6.3

The range of pipes for CWS shall be:- PN16 from diameter 16 to 160.

All pipes and fittings shall be qualified for transporting water at 70°C.All components of the system (including fittings and welded joints) shall be tested at alternate pressures of20/60 bar, at a rate of: - 5000 cycles per hour for diameters 16 to 90, - 2500 cycles per hour for diameters 110 to 160, according to NF T 54-094 standard.The system shall come from an ISO 9001 and ISO 14001 certified company:The system shall be ATEC certified (ATEC = NF certificate in the absence of an appropriate standard) for diame-ters 16 to 160, and for the following fields of application: distribution of domestic hot and cold water, class 2 (for-merly HCWS class).Both pipes and fittings for the distribution of domestic hot and cold water shall be ACS certified (ACS = SanitaryCompliance Certificate, issued by the French Ministry of Health).The system shall be certified by CSTBat (CSTBat = Scientifical Center for Building Techniques).The system’s fire rating shall be Bs1d0 certified according to EUROCLASSES.

WELDING POLYMER:The joints between the system’s various elements (pipes and fittings) shall be performed by cold chemical welding,by using the orange coloured welding polymer, allowing for the commissioning of welds.Curing times, before the reinstatement of a 6 bar pressure shall be guaranteed by the manufacturer and shall varybetween 1 and 2 hours, according to the ambient temperature and the joint’s diameter.

TREATMENTS FOR THE PREVENTION OF BACTERIA AND DECONTAMINATION OF SAME:In consideration of the existing development of certain bacteria in HCWS pipeworks, the system shall be able towithstand all treatments known todate, such as thermal shock treatments, or chlorine shock treatment withoutlimitation of the treatment product’s concentration rate.

GUARANTEES:The manufacturer must be able to provide professional training courses for the implementation of his system.The manufacturer’s Technical Assistance Department shall be able to validate solutions brought to address expansionand contraction phenomena encountered on the pipeworks, or to draw an execution drawing made from the generaldrawings supplied by the contracting company in charge of a project.

ENVIRONMENT:The system shall be recyclable through an existing recovery network. The system shall comply with H.E.Q. (HighEnvironmental Quality) requirements. The manufacturer shall be able to supply reliable environmental data.

Page 71: doc techn HTA janvier 2006 - girpi · The readings for the breaking pressures for HTA® and HTA®-F are evaluated, as shown in the above regression curve, represented by a straight

Stockist

More services from GIRPI...Training centre, analysis of your needs, specification work, adaptation and development of specific fabricated

products are daily services offered to facilitate sales and installation of our products

Réf.

SYDT

ECA

- RC

S Le

Hav

re B

719

803

249

09

/08 4

000

exe

mplai

res

NETWORK DESIGNOur technical assistance and design service can help optimize network drawings- Drawings featuring all GIRPI articles.- Complete bill of materials.- Calculations of bracketing,...

TRAINING CENTREOur training centre (officially recognized for vocational training) gives installersand decision-makers modular training courses about technical installation.

CUSTOM-MADE ITEMSOur fabrication workshop can manufacture your special items as per yourrequirements and can also prefabricate pipework sections.Please consult us for prices and deliveries.

Head Office: GIRPIB.P. 36 - Rue Robert Ancel - 76700 Harfleur - FranceTel: 33 (0)2 32 79 66 03 - Fax: 33 (0)2 32 79 60 28 - www.girpi.comNetwork Design GIRPI: [email protected]

safety for your pipeworks