ventilation & iaq fundamentals

42
ASHRAE Region VI CRC ASHRAE Region VI CRC Track III: Session 1 Track III: Session 1 Ventilation & IAQ Fundamentals Ventilation & IAQ Fundamentals Steven T. Taylor, PE Principal Taylor Engineering

Upload: hoangkhue

Post on 31-Dec-2016

236 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Ventilation & IAQ Fundamentals

ASHRAE Region VI CRCASHRAE Region VI CRCTrack III: Session 1Track III: Session 1

Ventilation & IAQ Fundamentals Ventilation & IAQ Fundamentals

Steven T. Taylor, PEPrincipal Taylor Engineering

Page 2: Ventilation & IAQ Fundamentals

As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material

or product. Questions related to specific materials, methods, and services will be addressed at the

conclusion of this presentation.

This program is registered with the AIA/CES for continuing professional education.

Page 3: Ventilation & IAQ Fundamentals

Learning ObjectivesLearning Objectives

Outline the basic aspects of indoor air quality and how ventilation promotes qualityUnderstand the ventilation fundamentals under ASHRAE 62.1-2004Identify ways to achieve LEED points through increased ventilation rates

Page 4: Ventilation & IAQ Fundamentals

AgendaAgenda

FundamentalsIndoor air quality and sick building syndromeRole of ventilation and determining ventilation rates

Ventilation requirementsASHRAE Standard 62.1 2004

LEED NC Version 2.2 Credit

Page 5: Ventilation & IAQ Fundamentals

What is Acceptable IAQ?What is Acceptable IAQ?

Standard 62: “Air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction.”

Page 6: Ventilation & IAQ Fundamentals

Sick Building SyndromeSick Building Syndrome

headachesirritation of eyes, nose, and throatdizzinessdifficulty concentrating

Definition: A cluster of non-specific, subjective health complaints and symptoms of discomfort or irritation experienced by a significant number of building occupants and that tend to go away when these individuals leave the building.

Symptoms include:

Page 7: Ventilation & IAQ Fundamentals

What are the Causes of SBS? What are the Causes of SBS? Why now?Why now?

increased sensitivities and expectations of workersnew indoor pollutants (VOCs)reduced ventilation due to energy crunchincreased complexity of HVAC systemscost cutting in design, construction, maintenance

No one really knows!!

Various theories including one or more of:

Page 8: Ventilation & IAQ Fundamentals

TotalEnvironmental

Quality

Mediating Cognitive Processes

Health & Comfort

BiologicalFactors

PsychologicalFactors

Stress

Outdoor AirQuality

Ventilation

Noise&

Vibration

IndoorAir

Quality

ThermalConditions

Lighting

ENVIRONMENT

OrganizationalFactors

Activities OfficeTechnology

Task Demands

JOB

Materials &Furnishings

OfficeLayout

Architectural Ambiance

BUILDING

PollutantSources

ControlControl

English House of Commons (1991) concludes that “SBS symptoms are not caused simply by direct exposure to indoor air contaminants... There is consistent evidence for a link between SBS symptoms [and] negative perceptions of the physical environment, individual factors [such as] sex, and occupational factors [such as] job stress [and] VDT use… It has been hypothesised that environmental, occupational, and other psychosocial factors interact to place a total stress load on a worker which is sufficient to precipitate SBS symptoms.”

Page 9: Ventilation & IAQ Fundamentals

Effect of Pollutants on PeopleEffect of Pollutants on People

Cumulative 1+2=3Independent 1+2=2Synergistic 1+2=4Antagonistic 1+2=1

Σ⇔

Page 10: Ventilation & IAQ Fundamentals

Dilution VentilationDilution Ventilation

Vs, CRA

Vs, Cs

, v, CR&N

)( sRVs CCE

NV−

=&

Source strength of pollutant in space

Supply rate of ventilation air

Concentration of pollutant in supply air

Ventilation effectiveness Concentration of pollutant in

room (at breathing level)

Page 11: Ventilation & IAQ Fundamentals

Understanding DilutionUnderstanding Dilution

Any fluid of lower concentration can be used to dilute higher

concentration

Unless the source strength is zero, the indoor concentration

will never be zero

Two important concepts:

Page 12: Ventilation & IAQ Fundamentals

The role of ventilation The role of ventilation and determining ventilation ratesand determining ventilation rates

Perception of air quality is a function of many factors, only one of which is the concentration of indoor contaminants.Dilution (ventilation) is nevertheless essential since not all pollutant sources can be eliminatedThere is still much to learn about the nature of indoor contaminants, source strengths, and maximum acceptable concentrations for non-industrial workplaces.Until more research is done, ventilation rates must be determined largely based on experience; as such, rates must be recognized as no more than rules-of-thumb.

Page 13: Ventilation & IAQ Fundamentals

How Much Ventilation is How Much Ventilation is Enough?Enough?

Depends on goalVentilation for minimum health?

Harmful contaminants from indoor sourcesDisease transmission

Ventilation for x% occupant satisfaction?Ventilation for x% visitor first impression?Ventilation for maximum productivity?Ventilation for maximum life cycle cost?

What’s appropriate for a Code??

Page 14: Ventilation & IAQ Fundamentals

How Much Ventilation How Much Ventilation is Enough for any of these goals?is Enough for any of these goals?

We really don’t know…Limited data from:

Chamber studiesMostly limited to body odor

Epidemiological studiesMostly observational rather than experimentalMany potential confounding factorsRates not always accurately measured

Anecdotal and Empirical “Evidence”

Page 15: Ventilation & IAQ Fundamentals

Historical PerspectiveHistorical PerspectiveVentilation Rates in OfficesVentilation Rates in Offices

Vent

ilatio

n R

ate

(cfm

/per

son)

1920 1940 1960 1980 2000 2010

ASHRAE 62-89

ASHRAE 62-81

ASHRAE 62-73

30

25

20

15

10

5

0

Yaglou1936

Flugge1905

Recommended Smoking

Standard 62.1-2004

Page 16: Ventilation & IAQ Fundamentals

Rationale for 62.1Rationale for 62.1--2004 Rates2004 Rates

Explicitly recognizes building as a source of indoor air pollutants

Followed lead of European standardsExplicitly accounts for ventilation efficiencyMany more studies to guide rate selection

Almost exclusively officesStill consider historical rates as a guideRates still largely based on judgment of the 62 Project Committee, not explicit science

Page 17: Ventilation & IAQ Fundamentals

50%

55%

60%

65%

70%

75%

80%

85%

90%

95%

100%

0 10 20 30 40 50

CFM/person

% S

atis

fied

Cain & Leaderer

Fanger

Iwashita

Chamber Body Odor StudiesChamber Body Odor StudiesImpact of ventilation rate on Impact of ventilation rate on ““visitorsvisitors””

15

Page 18: Ventilation & IAQ Fundamentals

Body Odor Studies (Cain & Leaderer)

50%

60%

70%

80%

90%

100%

110%

5 10 15 20

Cfm/person

% S

atisf

ied

Visitors (unadapted)

Occupants (adapted)

Page 19: Ventilation & IAQ Fundamentals

Standard 62.1Standard 62.1--20042004Ventilation Rate ProcedureVentilation Rate Procedure

People Component Building ComponentBreathing Zone Outdoor Air Ventilation Rate, CFM

Minimum CFM/Person

Number of People

Minimum CFM/sqft

Floor Area

zazpbz ARPRV +=

Page 20: Ventilation & IAQ Fundamentals

Ventilation System EfficiencyVentilation System Efficiency

Vbz = Design outdoor air rate to breathing zone

Vz = Design outdoor air rate to space

Ez = Zone air distribution (air change) effectiveness

Vot = Total outdoor air at ventilation system intake

EV = System ventilation efficiency (ventilation system effects)

V

z

ot E

VV

∑= spaces all

z

bzz E

VV =

Page 21: Ventilation & IAQ Fundamentals
Page 22: Ventilation & IAQ Fundamentals

Office Building StudiesOffice Building Studies

0 10 20 30 l/s/person

Mean Outdoor Air Ventilation Rate

Jaakkola ’91Jaakkola ’91Wyon ’92Menzies ’93Wyon ’92Jaakkola ’91Jaakkola ’91Nagda ’91Sundell ’92Jaakkola ’90Nagda ’91Jaakkola ’91Jaakkola ’91

Mendell, 1993

Associated withSBS Symptoms

0 20 40 60 cfm/person

Page 23: Ventilation & IAQ Fundamentals

How to Determine the People and How to Determine the People and Building Component Rates?Building Component Rates?

Start with offices for which most data is availableStudies based mostly on total outdoor air rate at intakeFew studies on building component and all EuropeanData predominantly support 62-89/01 rate of 20 cfm/person

Use “adapted” rate for people componentMet philosophy of “code minimum”Occupants are the target of standardAddressed concerns about over-ventilating dense spaces

Back-calculate building rate from total rate and occupant rate, adjusted for efficiencyUse judgment to determine rates for other occupancies based on office component rates

Page 24: Ventilation & IAQ Fundamentals

V R P D R AEot

P D B B

V

=+

Office Buildings

~20 cfm/person (Mendell)

~0.8 for heating (Fisk)

~5 cfm/person (adapted)

~5 people/1000 ft2(typical )

~0.06 cfm/ft2(EUR )

Total OA Flow rate at air

intake, cfm

Determining Ventilation RatesDetermining Ventilation Rates

Page 25: Ventilation & IAQ Fundamentals

People ComponentPeople Component

Page 26: Ventilation & IAQ Fundamentals

Building ComponentBuilding Component

Page 27: Ventilation & IAQ Fundamentals

ExampleExample

62n Ventilation Rates62n Ventilation Rates

Prescriptive Ventilation

Requirement

Guideline Occupancy

Assumptions

Ventilation Requirements at Guideline Occupancy and Typical System Efficiency

People Building Density Diversity System Outdoor Outdoor Occupancy RP RB people/ Factor Efficiency air air Category cfm/person cfm/ft2 1000 ft2 cfm/person cfm/ft2

Office space 5.0 0.06 5 1 0.8 21.3 0.11

Retail sales floor 7.5 0.12 15 1 1.0 15.5 0.23 General classrooms 10.0 0.12 35 1 0.8 16.7 0.59 Conference rooms 5.0 0.06 50 1 1.0 6.2 0.31

Page 28: Ventilation & IAQ Fundamentals

Breathing ZoneBreathing Zone

Outdoor Air Rate ComparisonOutdoor Air Rate Comparison

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

Offices

Conference

Classroom

Retail

62-200162.1-2004

0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0Breathing Zone Outdoor Air, l/s per square meter

Breathing Zone Outdoor Air, cfm per square foot

Page 29: Ventilation & IAQ Fundamentals

Accounting for Multiple Space Accounting for Multiple Space EffectsEffects

Two methods: Simple: Use default Ev from Table 6.3; orComplex: Calculate Ev from Appendix A

Recommended for Systems with multiple return air paths such as Fan-powered VAV and Dual Duct Systems

Recommended for Single Duct Systems such as VAV Reheat Systems

Page 30: Ventilation & IAQ Fundamentals

Table 6.3 Default Efficiencies Table 6.3 Default Efficiencies

Use Appendix G> 0.55

0.6≤ 0.55

0.7≤ 0.45

0.8≤ 0.35

0.9≤ 0.25

EVMax (ZP)

Zp = Voz/Vpz

Page 31: Ventilation & IAQ Fundamentals

Multiple Zone Systems with Multiple Zone Systems with Multiple Recirculation PathsMultiple Recirculation Paths

Page 32: Ventilation & IAQ Fundamentals

Appendix A Calculation Appendix A Calculation using spreadsheet using spreadsheet

Building:System Tag/Name:Operating Condition Description:Units (select from pull-down list)

Inputs for System Name Units SystemFloor area served by system As sf 15080Population of area served by system (including diversity) Ps P 73Design primary supply fan airflow rate Vpsd cfm 14000OA req'd per unit area for system (Weighted average) Ras cfm/sf 0.06OA req'd per person for system area (Weighted average) Rps cfm/p 5.0Does system have Outdoor Air Economizer Select from pull-down list No

Inputs for Potentially Critical zones

Zone NameZone title turns purple italic for critical zone(s)

North Conference

Room

Interior Conference

roomZone Tag VAV-3 VAV-20

Space type Select from pull-down listConference/

meetingConference/

meetingFloor Area of zone Az sf 267 443Design population of zone Pz P (default value listed; may be overridden) 10 10Design total supply to zone (primary plus local recirculated) Vdzd cfm 265 325Induction Terminal Unit, Dual Fan Dual Duct or Transfer Fan? Select from pull-down list or leave blank if N/A FT FTLocal recirc. air % representative of ave system return air Er 0.5 0.5

Inputs for Operating Condition AnalyzedPercent of total design airflow rate at conditioned analyzed Ds % 100% 100% 100%Zone air distribution effectiveness at conditioned analyzed Ez 1.00 1.00Primary air fraction of supply air at conditioned analyzed Ep 0.90 0.69

Potentially Critical Zones

Typical Office BuildingAHU-1Design coolingIP

ResultsVentilation System Efficiency Ev 0.80Outdoor air intake required for system Vot cfm 1596Outdoor air per unit floor area Vot/As cfm/sf 0.11Outdoor air per person served by system (including diversity) Vot/Ps cfm/p 21.9Outdoor air as a % of design primary supply air Ypd cfm 11%

Page 33: Ventilation & IAQ Fundamentals

EErr Research (RP 1276)Research (RP 1276)

Er

3- 1- 5

3- 1- 6

3- 1- 7

3- 1- 2

3- 1- 3

0 5 10

0 5 10 20

Fee t

M e te rs

30

TestZone

1.15

0.19

0.43

0.91

0.67

Page 34: Ventilation & IAQ Fundamentals

Appendix A MethodAppendix A Method

Allows credit for systems with multiple recirculation paths

Fan-powered VAVDual fan dual ductTransfer or exhaust fans

Can justify low or even zero primary airflow minimum volume setpoints on these systemsCan be used to backwards calculate zone Vpz for systems where Vot is fixed

Tenant improvements and remodelsConsiderable judgment required to estimate variables

Do we trust designers to do “the right thing?”At least Ev cannot be larger than 1.0!

Page 35: Ventilation & IAQ Fundamentals

USGBC LEED Rating System & Going Beyond Code Minimum

Page 36: Ventilation & IAQ Fundamentals

LEED NC IEQ Credit 2LEED NC IEQ Credit 2

LEED NC 2.1 CreditAir change effectiveness >0.9Problem:

Achieved inherently in all cooling systemsAdjustment in rates required by Standard 62 so no IAQ impactCurrent LEED documentation is onerous (ADPI and ACE calculation required for each space type)

Page 37: Ventilation & IAQ Fundamentals

LEED NC 2.2 IEQ Credit 2LEED NC 2.2 IEQ Credit 2

Revised LEED 2.2 CreditOutdoor air rate > 30% above Standard 62.1-2004

Rationale62.1-2004 rates are lower for most occupancies than 62-2001 due to code-minimum perspectiveRecent research suggests higher rates offer reduced SBS symptoms and absenteeism, increased productivityLEED should encourage beyond-code minimum designs

Page 38: Ventilation & IAQ Fundamentals

Research shows higher rates may be Research shows higher rates may be cost effective in officescost effective in offices

Source: Seppanen et al

1999

CFM/person0 20 40 60 80 100 120

62.1

Page 39: Ventilation & IAQ Fundamentals

Other RecommendationsOther Recommendations

EUROVEN, 2002: Outdoor air rates below 25 l/s (50 cfm) per person in offices increase the risk of SBS symptoms, increase short-term sick leave, and decrease productivity.Seppanen, 1999: Increases in ventilation rates above 10 L/s (20 cfm) per person up to approximately 20 L/s (40 cfm) per person, are associated with a statistically significant decrease in the prevalence of SBS symptoms.Wargocki, 2000: Over an outdoor airflow of 3, 10, and 30 L/s (6, 20, and 60 cfm) per person, for each twofold increase in ventilation rate, performance improved on average by 1.7%.

Page 40: Ventilation & IAQ Fundamentals

Effects of Outdoor Air Ventilation Effects of Outdoor Air Ventilation Rate on ProductivityRate on Productivity

Study Team Finding Lawrence Berkeley Lab & Univ. of California, Berkeley in U.S.

2% faster work with very high ventilation rate, but result may be coincidental

Technical University of Denmark

6% faster work with 50 cfm/p. vs. 5 -10 cfm/p. when new air filter was in place, opposite finding with old filter

Heschong-Mahone Group in U.S.

1% increase in work speed per 10 cfm/p. increase in ventilation rate

Singapore National University Study

9% increase in work speed with increase from 20 to 46 cfm/p, but only with higher indoor temp. (76 oF)

0

50

100

150

200

250

Salary Energy

$/ft2

/yea

r

Page 41: Ventilation & IAQ Fundamentals

SummarySummary

VentilationFundamentalsStandard 62.1 Outdoor Air Requirements

LEED NC 2.2 Credit 2Requires 30% more outdoor air than 62.1

Page 42: Ventilation & IAQ Fundamentals

Questions?Questions?

Steven TaylorTaylor Engineering