WORK CONDITIONS:
THIS PROJECT WILL BE CONDUCTED IN AN OPERATING CAMP FACILITY. WORKMAN WILL BE EXPECTED TO
BE RESPECTFUL OF ECHO LAKE STAFF AND RESIDENTS, WHENEVER ON-SITE. WORK AND WORKMAN WILL
BE LIMITED TO THE PROPOSED DINING HALL FACILITY, STAGING AREAS, STORAGE AREAS, AND PATHS OF
ACCESS. ALL CONSTRUCTION MATERIALS AND EQUIPMENT WILL BE TRANSPORTED TO EACH WORK AREA
BY THE CONTRACTOR. CLEANLINESS AND HOUSEKEEPING WILL BE A CONTINUOUS EXPECTATION AND
WILL BE THE RESPONSIBILITY OF EACH CONTRACTOR WORKING ON THE PROJECT AT ALL TIMES. THE
CONTRACTOR WILL BE EXPECTED TO WORK AROUND ANY EXISTING EQUIPMENT, STRUCTURES, OR
UTILITIES TO REMAIN.
GENERAL CONDITIONS:
1. ALL MATERIALS AND WORKMANSHIP SHALL BE DONE TO THE HIGHEST STANDARDS AND BEST TRADE
PRACTICES. WORK SHALL CONFORM TO THE REQUIREMENTS OF THE CBC, UPC, UMC, NEC, UFC
(LATEST ADOPTED EDITIONS) AND TO LOCAL CITY AND COUNTY ORDINANCES AS AMENDED. NOTHING
IN THE CONTRACT DOCUMENTS IS TO BE CONSTRUED AS REQUIRING OR PERMITTING WORK
CONTRARY TO THESE CODES, LAWS, AND STATUES.
2. EXAMINATION OF THE SITE AND PORTIONS THEREOF WHICH WILL AFFECT THIS WORK SHALL BE
MADE BY THE CONTRACTOR PRIOR TO SUBMITTING ANY BIDS AND AGAIN PRIOR TO BEGINNING ANY
WORK. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON SITE PRIOR TO
STARTING EACH PHASE OF WORK. ALL DISCREPANCIES AND OR OMISSIONS FROM THE DRAWINGS,
NOTES, OR SPECIFICATIONS, SHALL BE BROUGHT TO THE ATTENTION OF THE CITY OF BERKELEY
AND STRUCTURAL SYSTEM SOLUTIONS INC. IMMEDIATELY. DO NOT SCALE PLANS, DIMENSIONS
SHOWN SHALL TAKE PRECEDENCE.
3. LOCATIONS AND ALIGNMENTS OF UNDERGROUND FACILITIES SHOWN ON THE PLANS ARE
APPROXIMATE AND WERE NOT DETERMINED BY A FIELD INVESTIGATION. EXISTING UTILITIES ARE
SHOWN BASED UPON AVAILABLE RECORD DRAWINGS. NOT ALL UNDERGROUND UTILITIES MAY BE
SHOWN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE ALL EXISTING UTILITIES,
WHETHER SHOWN OR NOT, AND TO NOTIFY ALL UTILITY COMPANIES TO VERIFY IN THE FIELD THE
LOCATION OF THEIR INSTALLATION PRIOR TO BEGINNING ANY CONSTRUCTION. THE CONTRACTOR
SHALL PROTECT ALL EXISTING UTILITIES FROM DAMAGE DURING CONSTRUCTION. THE CONTRACTOR
SHALL REQUEST FIELD MARKINGS OF EXISTING UTILITIES AT LEAST 48 HOURS PRIOR TO
CONSTRUCTION. UTILITIES DISCOVERED THAT ARE NOT SHOWN ON THESE DRAWINGS WILL BE
HANDLED ON A CASE BY CASE BASIS.
4. THE CONSTRUCTION DOCUMENTS ARE PROVIDED TO ILLUSTRATE THE DESIGN AND GENERAL TYPE
OF CONSTRUCTION, MATERIALS AND WORKMANSHIP THROUGHOUT. THE DOCUMENTS DO NOT
ILLUSTRATE EVERY CONDITION.
5. THE CONTRACTOR IS REQUIRED TO OBTAIN ALL NECESSARY PERMITS FROM ALL APPLICABLE
AGENCIES AND TO PAY ALL ASSOCIATED FEES PRIOR TO CONSTRUCTION.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND TAKE ALL REASONABLE PRECAUTIONS FOR THE
SAFETY OF ALL EMPLOYEES AND OTHER PERSONS. STRUCTURAL SYSTEM SOLUTIONS INC. AND THE
CITY OF BERKELEY SHALL NOT BE HELD RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS AND
PROCEDURES USED WHICH RESULT IN AN ACCIDENT. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR THE DEVELOPMENT, COORDINATION, AND SAFE EXECUTION OF CONSTRUCTION MEANS AND
METHODS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR INITIATING, MAINTAINING, AND
SUPERVISING SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH HIS WORK.
7. UNLESS NOTED OTHERWISE ALL WORK SCOPE IS ASSUMED NEW UNLESS NOTED AS EXISTING.
8. THE WORD "PROVIDE" AS USED IN THESE DOCUMENTS IS INTENDED TO MEAN THAT SUCH SHALL BE
FURNISHED, INSTALLED AND CONNECTED, IN ACCORDANCE WITH ALL APPLICABLE CODES UNLESS
OTHERWISE NOTED.
9. THE CONTRACTOR SHALL KEEP ON THE JOB SITE A SET OF RECORD DRAWINGS TO BE UPDATED FOR
AS-BUILT DRAWINGS, NOTING EVERY CHANGE FROM THE CONTRACT DOCUMENTS AND CLEARLY AND
ACCURATELY INDICATE ALL COVERED, CIVIL, STRUCTURAL, ELECTRICAL AND HEATING REVISIONS.
10. THE CONTRACTOR SHALL GUARANTEE ALL WORKMANSHIP AND MATERIALS FOR A PERIOD OF (1)
YEAR FROM THE DATE OF NOTICE OF COMPLETION.
11. ALL MATERIALS, COLORS AND FINISHES TO BE VERIFIED BY THE CITY OF BERKELEY PRIOR TO
ORDERING AND INSTALLATION. SUBMITTALS ARE REQUIRED FOR APPROVAL.
12. THE CONTRACTOR SHALL PROTECT AREA OF WORK AND NEW AND EXISTING MATERIALS AND
FINISHES FROM DAMAGE WHICH MAY OCCUR FROM CONSTRUCTION, DEMOLITION, DUST, WATER,
WEATHER, ETC. THE CONTRACTOR SHALL REPAIR OR REPLACE ANY DAMAGE TO NEW AND EXISTING
MATERIALS, FINISHES, STRUCTURES AND EQUIPMENT TO THE SATISFACTION OF THE OWNER AND AT
NO COST TO THE OWNER.
13. EXISTING ELEMENTS THAT ARE TO REMAIN, THAT ARE DIRECTLY IMPACTED BY NEW CONSTRUCTION,
SHALL BE RESTORED, REPAIRED AND MADE WHOLE TO THE SAME OR BETTER CONDITION THAN HAD
EXISTED.
14. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN TEMPORARY BARRICADES, ENCLOSURES, AND OR
SIGNAGE AS REQUIRED TO PROTECT ALL EMPLOYEES AND PERSONNEL DURING THE ENTIRE PERIOD
OF CONSTRUCTION.
15. UPON COMPLETION OF CONSTRUCTION, THE CONTRACTOR SHALL LEAVE THE JOB SITE AND
STAGING AREAS CLEAN AND IN AN ORDERLY MANNER READY FOR USE. THE CONTRACTOR SHALL
RESTORE ANY AND ALL AREAS USED FOR STAGING MEN, MATERIALS, AND EQUIPMENT IN THE
PERFORMANCE OF THIS WORK TO A CONDITION EQUALING ITS ORIGINAL CONDITION. AT A MINIMUM
THIS RESTORATION SHALL INCLUDE REMOVAL OF ALL CONSTRUCTION DEBRIS AND OR SOIL,
GRADING THE SITE AND DUST CONTROLS.
DESCRIPTION OF WORK:
PROJECT CONSISTS OF STRUCTURAL REMEDIATION AND RETROFITS TO THE EXISTING CITY OF
BERKELEY'S ECHO LAKE DINING HALL. THE RETROFIT CONSISTS OF REPLACING DAMAGED FRAMING
MEMBERS INCLUDING TRUSS CHORDS, TRUSS CONNECTIONS, POSTS, BEAMS AND JOISTS. REMOVAL OF
EXISTING T1-11 SIDING AND REPLACE WITH PLYWOOD SHEATHING AND BATTENS, SHEARWALL NAILING,
SEISMIC TIES, AND INTERIOR ENDWALL FRAMING.
CODE ANALYSIS - 2013 CALIFORNIA BUILDING CODE:
A. OCCUPANCY CLASSIFICATION (CBC SECTION 303): A-2
B. RISK CATEGORY: II (OCCUPENT LOAD < 250)
C. CONSTRUCTION TYPE (CBC CHAPTER 6): V (REMEDIATION AND RETROFIT REPAIRS)
D. LOCATION ON PROPERTY: NORTH WEST CORNER OF APN: 036-300-01
E. SEISMIC ZONE (ASCE 7-10, CHAPTER 11): D - SEE SHEET S0.1
F. FLOOR AREA (CBC SECTION 503): 2685 SQ FT
G. BUILDING HEIGHT AND NUMBER OF STORIES (IBC CHAPTER 5): 24'-0" TALL (SINGLE STORY)
H. APPLICABLE CODES AS ADOPTED BY LOCAL ORDINANCES:
CALIFORNIA BUILDING CODE - CBC
NATIONAL ELECTRIC CODE - NEC
CALIFORNIA ENERGY CODE - CEC
CALIFORNIA FIRE CODE - CFC
CALIFORNIA MECHANICAL CODE - CMC
I. WIND LOADS (ASCE 7-10, CHAPTER 26): 130 MPH - SEE SHEET S0.1
J. GROUND SNOW LOADS (ASCE 7-10, CHAPTER 7): 335 PSF - SEE SHEET S0.1
ABBREVIATIONS
& AND
@ AT
AB ANCHOR BOLT
ABV ABOVE
AC ASPHALT CONCRETE
ADDL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
APPD APPROVED
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BLW BELOW
BM BEAM
BN BOUNDARY NAIL
BO BOTTOM OF
BOT BOTTOM
BRG BEARING
CIP CAST-IN-PLACE
CJ CONSTRUCTION JOINT
CL CENTER LINE
CLR CLEAR
CONC CONCRETE
COND CONDITION
CONN CONNECTION
CONT CONTINUOUS
CTJ CONTROL JOINT
CTR CENTER
CTRD CENTERED
DBA DEFORMED BAR ANCHOR
DBL DOUBLE
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DN DOWN
DWG DRAWING
DWL DOWEL
(E) EXISTING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
ELEV ELEVATION
EN EDGE NAIL
EPS EXPANDED POLYSTYRENE
EQ EQUAL
ES EACH SIDE
EW EACH WAY
EXA EXPANSION ANCHOR
EXT EXTERIOR
FDN FOUNDATION
FG FINISHED GRADE
FIN FINISH
FLR FLOOR
FN FIELD NAIL
FOC FACE OF CONCRETE
FOW FACE OF WALL
FS FAR SIDE
FTG FOOTING
GALV GALVANIZED
GB GRADE BEAM
GR GRADE
HORIZ HORIZONTAL
GR GRADE
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSB HIGH STRENGTH BOLT
HSS HOLLOW STRUCTURAL SHAPE
IF INSIDE FACE
IN INCH
INT INTERIOR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LW LIGHTWEIGHT
MANUF MANUFACTURED
MAX MAXIMUM
MB MACHINE BOLT
MIN MINIMUM
MTL METAL
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OF OUTSIDE FACE
OH OPPOSITE HAND
OPG OPENING
PDF POWER DRIVEN FASTENER
PL PLATE
R RADIUS
RE REFER TO
REINF REINFORCEMENT
REQ REQUIRED
RS ROUGH SAWN
SCHD SCHEDULE
SECT SECTION
SHTG SHEATHING
SIM SIMILAR
SPECS SPECIFICATIONS
SQ SQUARE
STGRD STAGGERED
STD STANDARD
STIFF STIFFENER
STL STEEL
SYMM SYMMETRICAL
T&B TOP AND BOTTOM
TFF TOP OF FINISHED FLOOR
THRD THREADED
TOC TOP OF CONCRETE
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VIF VERIFY IN FIELD
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WS WATERSTOP
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
SHEET INDEX:
G1.0 GENERAL NOTES, SITE & AREA PLANS, SHEET INDEX
G1.1 EROSION CONTROL
S0.1 STRUCTURAL NOTES, STANDARD DETAILS
S1.0 FLOOR/FOUNDATION PLAN FRAMING PLAN
S1.1 ENDWALL FRAMING
S1.2 FOUNDATION DETAILS
S2.0 ROOF FRAMING PLAN, TRUSS CHORD BRACING, ROOF DIAPHRAGM NAILING
S2.1 ROOF FRAMING DETAILS
S3.0 BUILDING SECTION, DETAILS
S4.0 WINTER SUPPORT PLAN
S4.1 WINTER SUPPORT SECTION, DETAILS
S5.0 BUILDING ELEVATIONS
CITY OF BERKELEY
ECHO LAKE CAMP - DINING HALL
STRUCTURAL REMEDIATION
BID SET - NOT FOR CONSTRUCTION
EROSION CONTROL NOTES:
1. THE CONTRACTOR SHALL IMPLEMENT EROSION AND SEDIMENT CONTROL MEASURES FOR ALL SITE
DEVELOPMENT.
2. EROSION CONTROL SHALL BE IMPLEMENTED TO PRESERVE EXISTING VEGETATION AND TO
RE-VEGETATE DISTURBED AREAS AFTER GRADING AND CONSTRUCTION.
3. SEDIMENT CONTROL FACILITIES SHALL BE IMPLEMENTED TO PREVENT THE TRANSPORTATION OR
DISCHARGE OF ERODED EARTHEN MATERIALS FROM THE SITE FOR THE DURATION OF
CONSTRUCTION AND MAINTAINED REGULARLY.
4. EACH WEEK THE CONTRACTOR AND OR THEIR AUTHORIZED AGENTS SHALL REMOVE ALL SEDIMENT,
MUD, CONSTRUCTION DEBRIS, OR OTHER POTENTIAL POLLUTANTS THAT HAVE BEEN DISCHARGED
AS A RESULT OF CONSTRUCTION ACTIVITIES ASSOCIATED WITH THIS PROJECT. SUCH MATERIALS
SHALL BE PREVENTED FROM ENTERING THE STORM DRAIN SYSTEM.
5. ACCUMULATED SEDIMENT IN BMPS SHALL BE REMOVED PRIOR ANY ANTICIPATED STORM EVENT.
SEDIMENT MUST BE REMOVED WHEN THE BMP DESIGN CAPACITY IS REDUCED BY MORE THAN 50%.
6. THE CONTRACTOR SHALL INSPECT ALL DISTURBED AREAS, AREAS USED FOR STORAGE, VEHICLE
PATH, AND BMPS WEEKLY, PRIOR TO A FORECASTED RAIN EVENT AND WITHIN 24 HOURS OF AN
ACTUAL RAIN EVENT. THE CONTRACTOR SHALL UPDATE OR MODIFY THE STORMWATER POLLUTION
PREVENTION PLAN AS NECESSARY.
7. CONSTRUCTION MATERIALS SHALL BE PROPERLY STORED AND COVERED WHEN NOT IN USE.
8. CONTRACTOR SHALL CONSTRUCT AND OR INSTALL TEMPORARY SEDIMENT AND EROSION CONTROL
DEVICES PRIOR TO ANY GRADING OR SITE DEVELOPMENT ACTIVITY.
9. CONTRACTOR SHALL STABILIZE EQUIPMENT PARKING ARES WITH GRAVEL.
10. ALL LOOSE PILES OF SOIL, SILT, CLAY, SAND, DEBRIS, OR EARTHEN MATERIALS SHALL BE
PROTECTED IN A REASONABLE WAY TO PREVENT DISCHARGE.
11. AFTER COMPLETION OF EACH PHASE, ALL SURPLUS OR WASTE MATERIAL SHALL BE REMOVED FROM
THE SITE AND DEPOSITED AT A LEGAL POINT OF DISPOSAL.
12. THE CONTRACTOR SHALL DEVELOP, PROPOSE AND IMPLEMENT AN APPROPRIATE DUST CONTROL
PROGRAM TO BE USED THROUGHOUT CONSTRUCTION. THE DUST CONTROL PLAN SHALL BE
SUBMITTED TO THE EL DORADO COUNTY BUILDING DEPARTMENT AND SHALL SATISFY ALL
APPLICABLE STATE AND FEDERAL REQUIREMENTS. CONTRACTOR SHALL BE REQUIRED TO PAY ANY
ASSOCIATED FEES TO SATISFY DUST CONTROL REQUIREMENTS. CONTRACTOR SHALL TAKE ALL
NECESSARY STEPS TO CONTROL DUST IN CONSTRUCTION AND STAGING AREAS. SUFFICIENT WATER
TRUCKS SHALL BE MADE AVAILABLE FOR DUST CONTROL PURPOSES. THE CONTRACTOR IS
REQUIRED TO SUPRESS DUST AT ALL TIMES, 24 HOURS A DAY, 7 DAYS A WEEK.
ENVIRONMENTAL MANAGEMENT SYSTEM:
1. THE CONTRACTOR SHALL IMPLEMENT AND BE RESPONSIBLE FOR AN ENVIRONMENTAL MANAGEMENT
PLAN.
2. THE CONTRACTOR SHALL IDENTIFY AND CONTROL THE ENVIRONMENTAL IMPACT OF ALL
CONSTRUCTION ACTIVITIES, PRODUCTS, AND SERVICES.
3. THE CONTRACTOR SHALL MAINTAIN SUFFICIENT MEASURES OF CONTROL FOR ENVIRONMENTAL
RISKS ASSOCIATED WITH SPILLS, WATER MANAGEMENT, WASTE MANAGEMENT, RECLAMATION,
EMISSIONS, AND ENERGY USE.
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
BID SET - NOT FOR CONSTRUCTION
1. GENERAL
1.1 THE FOLLOWING STRUCTURAL NOTES SHALL APPLY TO ALL STRUCTURAL DRAWINGS UNLESS
SPECIFICALLY SHOWN OR NOTED OTHERWISE.
1.2 ALL WORK SHALL CONFORM TO THESE NOTES, DRAWINGS, AND SPECIFICATIONS IN ALL
RESPECTS.
1.3 PROMPTLY REPORT ANY DISCREPANCY FOUND AMONG THESE NOTES, DRAWINGS,
SPECIFICATIONS, AND EXISTING CONDITIONS TO BOTH THE CITY OF BERKELEY AND
STRUCTURAL SYSTEM SOLUTIONS, INC. ALL DISCREPANCIES WILL BE CORRECTED IN
WRITING. ANY WORK DONE BY THE CONTRACTOR AFTER THE DISCOVERY OF SUCH
DISCREPANCY PRIOR TO RECIEVING WRITTEN DIRECTION FROM THE CITY OF BERKELEY AND
STRUCTURAL SYSTEM SOLUTIONS, INC. IS AT THE CONTRACTORS OWN RISK. VERIFY AND
COORDINATE THE DIMENSIONS AMONG ALL DRAWINGS PRIOR TO PROCEEDING WITH ANY
WORK OR FABRICATION.
1.4 DO NOT SCALE WORKING DIMENSIONS FROM THESE PLANS, SECTIONS, OR DETAILS.
1.5 DETAILS OF THE CONSTRUCTION NOT FULLY SHOWN OR NOTED ON THE DRAWINGS OR
CALLED FOR IN THE SPECIFICATIONS SHALL BE OF THE SAME SIZE AND CHARACTER AS FOR
SIMILAR CONDITIONS WHICH ARE SHOWN AND NOTED.
1.6 THE WORD "TYPICAL" SHALL MEAN THAT INFORMATION SHOWN SHALL BE APPLIED TO ALL
SIMILAR CONDITIONS WHETHER OR NOT THE INFORMATION IS SPECIFICALLY REFERENCED,
UNLESS OTHERWISE NOTED ON THE DRAWINGS.
1.7 MODIFICATIONS OR SUBSTITUTIONS TO THE DESIGN, MATERIALS, OR PRODUCTS SPECIFIED ON
THE PLANS ARE PROHIBITED WITH OUT PRIOR WRITTEN APPROVAL BY THE CITY OF BERKELEY
AND STRUCTURAL SYSTEM SOLUTIONS, INC..
1.8 THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR PROVIDING AND MAINTAINING A SAFE
WORK ENVIRONMENT IN ACCORDANCE WITH ALL LOCAL, STATE, FEDERAL SAFETY AND HEALTH
STANDARDS LAWS AND REGULATIONS. THE CONTRACTOR SHALL EXECUTE WORK TO ENSURE
SAFETY OF PERSONS AND PROPERTY AGAINST DAMAGE AND SHALL PROVIDE ADEQUATE
SHORING AND BRACING AS REQUIRED FOR STABILITY DURING ALL PHASES OF CONSTRUCTION.
1.9 THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE AND
DO NOT INDICATE MEANS AND METHODS OF CONSTRUCTION.
2. DESIGN CRITERIA
2.1 DESIGN, MATERIALS, AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE 2013
CALIFORNIA BUILDING CODE AS AMENDED AND ADOPTED BY EL DORADO COUNTY,
CALIFORNIA.
2.2 ALL OTHER CODES AND STANDARDS SHALL BE THE MOST CURRENT ADOPTED EDITION AS OF
THE DATE OF THESE DRAWINGS.
2.3 SNOW LOADS:
GROUND SNOW LOAD, Pg: 335 PSF ELEVATION: 7538'
SNOW EXPOSURE FACTOR, Ce: 1.0
SNOW LOAD IMPORTANCE FACTOR, Is: 1.0
THERMAL FACTOR, Ct: 1.2
FLAT ROOF SNOW LOAD, Pf: 281 PSF
2.4 WIND DESIGN:
ULTIMATE DESIGN WIND SPEED: 130 MPH (Vult)
100 MPH (Vasd)
RISK CATEGORY: II
WIND EXPOSURE: C
INTERNAL PRESSURE COEFFICIENT, GCpi: ±0.18
2.5 SEISMIC DESIGN:
RISK CATEGORY: II
SEISMIC IMPORTANCE FACTOR, Is: 1.0
MAPPED SPECTRAL ACCELERATION, SS: 1.11 g
S1: 0.40 g
SITE CLASS: D
SPECTRAL RESPONSE COEFFICIENT, SDS: 0.78 g
SD1: 0.43 g
SEISMIC DESIGN CATEGORY: D
SEISMIC FORCE-RESISTING SYSTEM: BEARING WALLS (LIGHT-FRAME (WOOD)
WALLS SHEATHED WITH WOOD
STRUCTURAL PANELS
DESIGN BASE SHEAR: 5.0 KIP
SEISMIC RESPONSE COEFFICIENT, Cs: 0.12
RESPONSE MODIFICATION COEFFICIENT, R: 6.5
ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE
3. FOUNDATIONS
3.1 ALLOWABLE LOAD-BEARING VALUES OF SOILS:
ALLOWABLE FOUNDATION PRESSURE: 1500 PSF
LATERAL BEARING: 150 PSF
LATERAL SLIDING: 0.25
SUBGRADE MODULUS: 350 PSI/IN
MIN DEPTH OF FOOTINGS: 24" MIN
3.2 BEFORE COMMENCING EARTHWORK, VERIFY LOCATION OF ALL UTILITIES AND
STRUCTURES. NOTIFY BOTH THE CITY OF BERKELEY AND STRUCTURAL SYSTEM SOLUTIONS,
INC. WHERE CONFLICTS EXIST. RELOCATE OR AVOID AS NECESSARY AS TO NOT DAMAGE OR
INTERFERE WITH EXISTING TO REMAIN.
3.3 PLACE ALL FOOTINGS ON APPROVED SOIL (UNDISTURBED NATURAL SOILS OR COMPACTED
ENGINEERED FILL). FILL HOLES DUE TO REMOVAL OF LARGE ROCKS OR OVER-EXCAVATION
WITH CONCRETE.
3.4 PLACE ALL LOOSE SOIL AND FILL, INCLUDING BACKFILL BEHIND WALLS IN 6" LIFTS AND
UNIFORMLY COMPACT TO AT LEAST 90% MAXIMUM DENSITY PER ASTM D1557.
3.5 FOUNDATIONS AT THE BUILDING PERIMETER SHALL BE PROTECTED AGAINST WATER
INFILTRATION, SEEPAGE, AND SURFACE AND SUBSURFACE FLOW.
4. CAST-IN-PLACE CONCRETE
4.1 CONCRETE MATERIALS AND CONSTRUCTION SHALL COMPLY WITH CBC CHAPTER 19, ACI 318,
AND ACI 301.
4.2 CONCRETE PROPERTIES AND COMPOSITION:
PROPERTY CLASS A
28-DAY f'c (1) (4000) PSI
W/C 0.45
UNIT WT (2) 145 PCF
AIR (+/-) (3) 6%
SLUMP (MAX) (4) 3"
SHRINKAGE (5) NR
CEMENT (6) TYPE II
MIN CEMENT 520
NOTES:
(1) FOUNDATION DESIGN FOR CONCRETE ENCLOSED IN () IS DESIGNED FOR 2500 PSI AND
DOES NOT REQUIRE SPECIAL INSPECTION.
(2) AGGREGATE PER ACI 318, SECTION 3.3
(3) 6% MAXIMUM AIR FOR 3/4" MAX AGGREGATE AND 7% FOR 1/2" MAX AGGREGATE
(4) SLUMPS ARE FOR UNPLASTICIZED CONCRETE. LARGER SLUMPS MAY BE ATTAINED
THROUGH THE USE OF SUPERPLASTICIZER. WATER REDUCING ADMIXTURES FOR PIERS
SHALL CONFORM TO ASTM C 494, TYPE D, TO MEET SLUMP REQUIREMENTS.
(5) SHRINKAGE AT 28 DAYS (IN/IN) PER ASTM C157
(6) CEMENT PER ASTM C150, C595, C1157 AS APPROPRIATE
CLASS A: FOUNDATIONS, UNO
4.3 ADMIXTURES SHALL COMPLY WITH ACI 318, SECTION 3.6
4.4 CONCRETE THAT IS TO BE PLACED DURING FREEZING OR NEAR-FREEZING WEATHER SHALL
COMPLY WITH THE REQUIREMENTS OF ACI 318, SECTION 5.12. EQUIPMENT SHALL BE PROVIDED
FOR HEATING CONCRETE MATERIALS AND PROTECTING CONCRETE. CONCRETE MATERIALS
AND REINFORCEMENT, FORMS, FILLERS, AND GROUND WITH WHICH CONCRETE WILL COME IN
CONTACT SHALL BE FREE OF FROST. FROZEN MATERIALS OR MATERIALS CONTAINING ICE
SHALL NOT BE USED.
4.5 APPROVAL MUST BE OBTAINED PRIOR TO PLACING CONCRETE FOR ANY OPENINGS, SLEEVES,
OR OTHER ATTACHMENTS NOT SHOWN ON DRAWINGS.
4.6 PROVIDE 3/4" CHAMFER ON ALL EXPOSED CORNERS OF CONCRETE UNLESS DETAILED
OTHERWISE.
4.7 ROUGHEN THE EXISTING CONCRETE SURFACE AT THE INTERFACE OF CONSTRUCTION JOINTS
TO AN AMPLITUDE OF (+/-) 1/4" PRIOR TO PLACING NEW CONCRETE. THOROUGHLY WET THE
INTERFACE SURFACE AND REMOVE ANY STANDING WATER.
INTERFACE SURFACE AND REMOVE ANY STANDING WATER.
5. CONCRETE REINFORCEMENT
5.1 REINFORCEMENT SHALL CONFORM TO ACI 318, SECTION 3.5 AND ASTM A615, GRADE 60, UNO.
5.2 CONCRETE REINFORCEMENT DETAILS INCLUDING BAR SUPPORTS AND PLACING SHALL
CONFORM TO ACI 315 AND THE CONCRETE REINFORCING STEEL INSTITUTE "MANUAL OF
STANDARD PRACTICE." HOOKS SHALL BE PER ACI 318, SECTION 7.1 UNLESS DETAILED
OTHERWISE.
5.3 PROVIDE THE FOLLOWING COVER ON REINFORCEMENT UNLESS NOTED OTHERWISE IN
DRAWINGS. COVER SHALL BE TO FACE OF BAR, MECHANICAL COUPLER, OR WELDED HEADED
BAR.
CAST-IN-PLACE CONCRETE MINIUM CONCRET COVER
CAST AGAINST AND EXPOSED TO EARTH 3"
EXPOSED TO EARTH OR WEATHER
#5 AND SMALLER 1 1/2"
5.4 PROVIDE LAP SPLICES, AND DEVELOPMENT OF STANDARD HOOKS AS SPECIFIED IN ACI 318,
CHAPTER 12. MAKE LAP SPLICES ONLY AT LOCATIONS SHOWN ON DRAWINGS, AS INDICATED IN
THESE NOTES, OR AS APPROVED BY THE ENGINEER.
5.5 SECURELY TIE ALL REINFORCEMENT PRIOR TO PLACING CONCRETE INCLUDING LAP SPLICES.
5.6 SUBMIT SHOP DRAWINGS OF REINFORCEMENT LAYOUTS AND DETAILS FOR REVIEW PRIOR TO
FABRICATION. SHOW ALL PROPOSED SPLICE LOCATIONS, FABRICATE FROM APPROVED
DRAWINGS ONLY.
5.7 BEND REINFORCING STEEL IN ACCORDANCE WITH ACI 301, SECTION 3.3.2.8. #3, #4, & #5 BARS
MAY BE BENT COLD THE FIRST TIME PROVIDED TEMPERATURE OF BAR IS ABOVE 32F. FOR
OTHER BAR SIZES PREHEAT REINFORCING BARS PRIOR TO BENDING.
5.8 PROMPTLY NOTIFY BOTH THE CITY OF BERKELEY AND STRUCTURAL SYSTEM SOLUTIONS, INC.
IF CONDITIONS ARISE WHERE THERE IS INSUFFICIENT CLEAR DISTANCE BETWEEN BARS OR
WHERE CONGESTION OCCURS.
6. ANCHORS TO CONCRETE
6.1 ANCHOR BOLTS AND OTHER BOLTS EMBEDDED IN CONCRETE SHALL BE ASTM A307, UNLESS
OTHERWISE DETAILED. THREADED ROD SHALL BE ASTM A36, UNLESS OTHERWISE DETAILED.
6.2 EXPANSION ANCHORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS
WRITTEN INSTRUCTIONS.
6.3 MINIMUM EXPANSION ANCHOR EMBEDMENT SHALL BE AS INDICATED ON THE PLANS BUT IN NO
CASE LESS THEN SPECIFIED BY THE MANUFACTURER.
6.4 EPOXY ANCHORS SHALL BE INSTALLED USING SIMPSON SET-XP (ESR-2508) PER THE
MANUFACTURERS WRITTEN INSTRUCTION. USE ASTM A307 (F1554, GR 36) THREADED ROD
UNLESS NOTED OTHERWISE.
7. LUMBER, TIMBER AND MANUFACTURED WOOD PRODUCTS
7.1 ROUGH FRAMING SHALL CONFORM TO THE REQUIREMENTS OF CBC CHAPTER 23 & NDS-2005 .
7.2 FOR SAWN LUMBER (2X & 4X) USE DOUGLAS FIR #1 AS PER WCLB. USE PRESSURE TREATED
DOUGLAS FIR #2 FOR SILL PLATES AND WOOD WITHIN 6" OF EARTH. ALL FRAMING MEMBER
SHALL HAVE A MAXIMUM MOISTURE CONTENT OF 19% UNO ON PLANS.
7.3 FOR SAWN TIMBERS (5X AND LARGER) USE DOUGLAS FIR DENSE SELECT STRUCTURAL AS PER
WCLB WITH A MAXIMUM MOISTURE CONTENT OF 19%.
FOR COMPOSITE LUMBER USE BOISE CASCADE 2.0E-2900F LVL OR APPROVED EQ.
7.4 ALL PLYWOOD SHEATHING SHALL BE CERTIFIED AND MARKED IN ACCORDANCE WITH PS 1-95,
SECTION 7. EACH PANEL SHALL BEAR MARKINGS IDENTIFYING THE QUALIFIED TESTING AND
INSPECTION AGENCY, GRADE, NOMINAL THICKNESS, SPAN RATING, EXPOSURE DURABILITY
CLASSIFICATION, AND THE STANDARD TO WHICH IT IS CERTIFIED.
7.5 INTERIOR WALL SHEATHING SHALL BE APA RATED SHEATHING, EXPOSURE I AS FOLLOWS:
MIN THICKNESS: 15/32"
MINIMUM NAILING: 10d, BN = 6", EN = 6", FN = 12"
ORIENTED STRAND BOARD (OSB) MEETING THE REQUIREMENTS FOR WOOD STRUCTURAL
PANELS AS DEFINED IN IBC 2302 MAY BE SUBSTITUTED FOR PLYWOOD SHEATHING PROVIDED
SUCH PRODUCT ALSO MEETS REQUIRED APA RATING.
PROVIDE 2X BLOCKING AT ALL PANEL EDGES NOT SUPPORTED BY STUDS.
7.6 WINTER PARTITION PANELS SHALL BE STRUCTURAL 1, APA C-D SPAN RATED APA RATED
SHEATHING, EXPOSURE I AS FOLLOWS:
MIN THICKNESS: 3/8"
MINIMUM NAILING: 10d, BN = 6", EN = 6", FN = 12"
ORIENTED STRAND BOARD (OSB) MAY NOT BE SUBSTITUTED FOR WOOD STRUCTURAL PANELS.
7.7 EXTERIOR WALL SHEATHING SHALL BE APA RATED SHEATHING, DOUGLAS-FIR ROUGH/SAWN
PREMIUM 303-6 PLAIN AS FOLLOWS:
MIN THICKNESS: 5/8"
MINIMUM NAILING: 10d, BN = 6", EN = 6", FN = 12"
ORIENTED STRAND BOARD (OSB) MAY NOT BE SUBSTITUTED FOR WOOD STRUCTURAL PANELS.
7.8 LAP PLYWOOD FOR FLOORS AND ROOFS WITH FACE GRAIN PERPENDICULAR TO JOISTS AND
WITH END JOINTS STAGGERED. WHERE PANELS ARE LESS THAN 24" WIDE BLOCK ALL EDGES.
7.9 ATTACH SILL PLATES USING 5/8" DIA TITEN HD x 6" LONG ANCHOR BOLTS AT 32" MAXIMUM. EACH
ANCHOR BOLT SHALL BE INSTALLED WITH A MINIMUM 3" X 3" X 1/4" PLATE WASHER. EACH
SEPARATE LENGTH OF SILL PLATE SHALL BE ATTACHED WITH A MINIMUM OF (2) SPECIFIED
ANCHOR BOLTS IN ADDITION TO ANY BOLTS FOR HOLDOWNS.
7.10 FOR WOOD TO WOOD NAILED CONNECTIONS, PROVIDE (11) FASTENER DIAMETERS FOR
SPACING AND (6) FASTENER DIAMETERS FOR EDGE DISTANCES.
7.11 WHERE REQUIRED TO AVOID SPLITTING, PRE-DRILL HOLES WITH A DRILL BIT DIAMETER EQUAL
TO THE NEXT SMALLEST NAIL DIAMETER.
7.12 WHERE NAILS WILL BE EXPOSED TO WEATHER, USE ZINC COATED OR STAINLESS STEEL NAILS
CONFORMING TO ASM A153.
7.13 USE COMMON NAILS ONLY. BOX NAILS AND SINKERS ARE NOT PERMITTED.
7.14 USE THE FOLLOWING MINIMUM NAILING SCHEDULE:
JOIST TO SILL OR GIRDER, TOENAIL (3) 10d
BRIDGING TO JOIST, TOENAIL EACH END (2) 10d
SOLE PLATE TO JOIST OR BLOCKING, FACE NAIL 16d @ 12"
TOP PLATE TO STUD, END NAIL (2) 16d
STUD TO SOLE PLATE, TOENAIL (4) 8d
STUD TO SOLE PLATE, END NAIL (2) 16d
DOUBLE STUDS, FACE NAIL 16d @ 16"
DOUBLED TOP PLATE, FACE NAIL 16d @ 12"
CONTINUOUS HEADER, TWO PIECES, ALONG EDGE 16d @ 12"
CEILING JOIST TO PLATE, TOENAIL (3) 8d
JOISTS, LAPS OVER PARTITIONS , FACE NAIL (3) 16d
CEILING JOISTS TO PARALLEL RAFTERS , FACE NAILS (3) 16d
RAFTERS, JOISTS TO PLATE, TOENAIL (3) 10d
BLOCKING BETWEEN JOISTS OR RAFTERS TO PLATE (3) 16d @ EACH BLOCK
RIM JOIST TO TOP PLATE OR SILL PLATE, TOENAIL 10d @ 6"
BUILT UP CORNER STUDS 16d @ 16"
7.15 USE FRAMING HARDWARE AS MANUFACTURED BY SIMPSON STRONG TIE OF THE TYPE AND
SIZE INDICATED ON THE PLANS.
7.16 USE ASTM A307 MACHINE BOLTS AND WASHERS. DRILL HOLES MAXIMUM 1/16" LARGER THAN
BOLT DIAMETER. INSTALL PER ANSI/ASME STANDARD B18.2.1. PROVIDE STANDARD CUT
WASHERS BETWEEN WOOD AND BOLT HEAD AND NUT.
8. STEEL CONSTRUCTION
8.1 STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO CBC
CHAPTER 22 AND AISC 360, AISC 341, AND AISC 303.
8.2 PROVIDE SHOP DRAWINGS INCLUDING DETAILS FOR CUTS, HOLES AND WELDS FOR ALL
FABRICATED PARTS FOR REVIEW AND APPROVAL PRIOR TO FABRICATION.
8.2 PLATES SHALL BE ASTM A36, UNO.
8.3 THREADED ROD SHALL BE ASTM F1554, GR 55 - S1 (WELDABLE) WITH ASTM A563A HEAVY HEX
NUTS AND ASTM F436 WASHERS.
WELDING SHALL CONFORM TO AWS D1.1. CERTIFIED WELDERS SHALL PERFORM ALL WELDING.
NUTS AND ASTM F436 WASHERS.
8.4 WELDING SHALL CONFORM TO AWS D1.1. CERTIFIED WELDERS SHALL PERFORM ALL WELDING.
USE E7018 ELECTRODES WITH A MINIMUM CHARPY V-NOTCH TOUGHNESS OF 20 FT-LB AT O°F.
8.5 GRIND SMOOTH AND DEBUR ALL EXPOSED WELDS AND CUT EDGES.
8.6 ALL EXPOSED STEEL SHALL BE CLEANED, SHOP PRIMED AND PAINTED BLACK (SINGLE COAT OF
NOT LESS THAN 1.5 MILS.)
9. SPECIAL INSPECTIONS AND TESTING
9.1 PROVIDE SPECIAL INSPECTIONS IN COMPLIANCE WITH IBC 1704 BY AN APPROVED ICC
INSPECTOR.
9.2 STEEL CONSTRUCTION, IBC 1705.2: PERIODIC SPECIAL INSPECTION REQUIRED FOR GROOVE
WELDS PERFORMED IN AN APPROVED FABRICATORS SHOP.
9.3 REINFORCED CONCRETE, IBC 1705.3: SPECIAL INSPECTION NOT REQUIRED FOR CONCRETE
CONSTRUCTION. DESIGN BASED ON 2500 PSI.
9.4 POST-INSTALLED CONCRETE ANCHORS, IBC 1705.3: PERIODIC SPECIAL INSPECTION REQUIRED.
10. STRUCTURAL OBSERVATIONS
9.1 STRUCTURAL OBSERVATION SHALL BE PROVIDED BY A REGISTERED DESIGN PROFESSIONAL
FOR GENERAL CONFORMANCE OF CONSTRUCTION TO THE APPROVED CONSTRUCTION
DOCUMENTS AT SIGNIFICANT CONSTRUCTION STAGES AND AT COMPLETION OF THE
STRUCTURAL SYSTEM.
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
STRU
CTU
RAL N
OTES, STAN
DARD
D
ETAILS
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
FO
UN
DATIO
N FRAM
IN
G PLAN
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
EN
DW
ALL FRAM
IN
G
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
FO
UN
DATIO
N D
ETAILS
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
RO
OF FRAM
IN
G PLAN
, TRU
SS CH
ORD
BRACIN
G
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
BU
ILD
IN
G SECTIO
N, D
ETAILS
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
WIN
TER SU
PPO
RT PLAN
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
WIN
TER SU
PPO
RT SECTIO
N, D
ETAILS
BID SET - NOT FOR CONSTRUCTION
STRUCTURAL
SYSTEM
SOLUTIONS INC.
227 VINE ST
RENO, NV 89503
775-232-4664
www.sss464.com
RE
VD
AT
ED
ES
CR
IP
TIO
NA
PP
VD
DRAWN:
CHECKED:
DATE:
SCALE:
PROJECT NO:
SHEET NO:
CIT
Y O
F B
ER
KE
LE
Y
EL D
OR
AD
O C
OU
NT
YC
ALIF
OR
NIA
EC
HO
L
AK
E C
AM
P - D
IN
IN
G H
AL
L
STRU
CTU
RAL REM
ED
IATIO
N
BU
ILD
IN
G ELEVATIO
NS
BID SET - NOT FOR CONSTRUCTION