STATCOM
Wednesday, September 21,
2016Comsys ADF Power Tuning 1
Partner company name
Powerisn’t perfect
Wednesday, September 21,
2016Comsys ADF Power Tuning 2
• STATCOM
• Introduction to STATCOM
• Hybrid STATCOM concept
• How-to-guide
• Selected References
STATCOM, System IntegrationAgenda
Wednesday, September 21,
2016Comsys ADF Power Tuning 3
Partner company name
STATCOM Introduction
Wednesday, September 21,
2016Comsys ADF Power Tuning 4
• Static synchronous compensator
• VSC based (Voltage Source Converter)
• Traditionally, reactive power only (all quadrants)
• If connected to energy supply, can generate active power
• Faster, more complex than SVC(Static VAR Compensator)
Partner company name
STATCOM Applications
Wednesday, September 21,
2016Comsys ADF Power Tuning 5
• Dynamic Reactive power usable for:
• Compensating cable capacitance
• Stabilize voltage
• DVR applications
• Flicker reduction
• Other grid applications
Partner company name
STATCOM: VSC
Wednesday, September 21,
2016Comsys ADF Power Tuning 6
• Converter part (green)
• Identical to what is being used in 2-level active filters and drive inverters (if using IGBT)
• Maximum IGBT blocking voltage typically 6500V
• IGCT is also an option
• Blocking voltage presents majorchallenge!
• Line filter (red)
• Image shows L-filter; in ADF always LC or LCL
• Scales perfectly with current and voltage
Partner company name
STATCOM: VSC:: High voltage
Wednesday, September 21,
2016Comsys ADF Power Tuning 7
• Voltage limits of converter
• With 2-level, maximum native line voltage <3kV
• Multi-level converter increases this to approx. 6.6 kV
• How to increase voltage tolerance?
1. Series connection(shown)
2. Transformer
Partner company name
STATCOM: VSC:: High voltage
Wednesday, September 21,
2016Comsys ADF Power Tuning 8
1. Series connection
• Series connection requires exact
concurrent ignition of IGBT
(depending on equivalent
inductance in connecting cable)
or single IGBT will take all the
voltage IGBT failure!
2. Transformer
• This is a “simple” solution but
may degrade efficiency; adding
transformer losses to converter
losses. Or?
Partner company name
STATCOM: VSC:: High voltage
Wednesday, September 21,
2016Comsys ADF Power Tuning 9
1. Series connection
• Series connection requires exact
concurrent ignition of IGBT
(depending on equivalent
inductance in connecting cable)
or single IGBT will take all the
voltage IGBT failure!
• Medium voltage series
connected IGBT: prohibitive
complexity!
Image courtesy of ABB. Used without permission
Partner company name
STATCOM: VSC:: High voltage
Wednesday, September 21,
2016Comsys ADF Power Tuning 10
2. Transformer
• Transformer is in itself an inductive component
• By custom-making the transformer, the secondary inductance can be utilized as part of line filter!
• ADF units are then equipped with custom LC line filter
• This is what we did on the first ADF P700
TRAFO1
PPC1-1MCC1 PPC1-2 PPC1-3 PPC1-4
YNyn 0
22.5kV/690V
2000kVA
8%
Dry
Y Y
PPC2-4 MCC2PPC2-3 PPC2-2 PPC2-1WCSC
YNyn 0
22.5kV/690V
2000kVA
8%
Dry
Y Y
Partner company name
STATCOM: LV STATCOM concept
Wednesday, September 21,
2016Comsys ADF Power Tuning 11
• Modular, 2x2 MVA solution
• 690V low voltage switchgear internally – easier to service
• 22 kV main connection
MCC1 PCC1-1 PCC1-2 PCC1-3 PCC1-4 WCSC PCC2-4 PCC2-3 PCC2-2 PCC2-1 MCC2
PP1
PP2
PP3
PP4
PP5
PP1
PP2
PP3
PP4
PP5
PP1
PP2
PP3
PP4
PP5
PP1
PP2
PP3
PP4
PP5
3 2
PP1
PP2
PP3
PP4
PP5
PP1
PP2
PP3
PP4
PP5
PP1
PP2
PP3
PP4
PP5
PP1
PP2
PP3
PP4
PP5
2 3
5 5
See
PP-M3
See MCC-
M2, M3, M4
5 5 5 5 5 5 5 5 5 5 5 5 5 5
See WCSC-
M4, M5
See MCC-M6
See MCC-M1
See MCC-M1
T
A
See
TA-M4
T
A
T
A
T
A
T
A
T
A
T
A
T
A
X10 X10 X10 X10 X10 X10 X10 X10 X10 X20 X10X10 X20
X30X30
See
PP-M1,M2
See
MCC-M1
See
WCSC-M1
X20
M4 M5
Partner company name
STATCOM: LV STATCOM concept (2)
Wednesday, September 21,
2016Comsys ADF Power Tuning 12
• We have supplied LV/HV hybrid
STATCOM up to 130 kV so far
• Scales well to at least 10 MVAr
(depending on voltage/project)
• For very high ratings, LV/HV
hybrid solution becomes
impractical
Partner company name
STATCOM: How-to-guide
Wednesday, September 21,
2016Comsys ADF Power Tuning 13
• Basic idea: stack enough P300 units and connect to large enough transformer!
• Size according to needed MVAr
• For flicker projects, rule-of-thumb is to size so that ADF reactive power exceeds load
• In most cases, custom Transformer/LC-filters are not needed
• Might be considered in some cases
• Special care must be taken with transformer, cooling and CT
Partner company name
STATCOM: How-to-guide: components
Wednesday, September 21,
2016Comsys ADF Power Tuning 14
• Building blocks:
• Regular ADF P300 units, or
• System integration components (PPM300, SCC2, etc; more on this later)
• Up to 6 modules per computer
• Up to 0.167 MVAr per module (690V Liquid cooled)
• In multi-master, max 15 units;
• 15 computer x 6 modules = 15 MVAr!
• Multi-master not necessary in all cases
• Only difference between separate components and complete products is packaging.
Partner company name
STATCOM: How-to-guide: transformer
Wednesday, September 21,
2016Comsys ADF Power Tuning 15
• Typically, Yyn or similar “straight” transformer must be used
• Cannot be used with non-symmetrical loads
• Unbalanced loads will overload such transformer
• For DPF and flicker projects, impedance is selected to give a reasonable short-circuit power
• For Harmonics projects, transformer must be custom-ordered – spectrum to be supplied to transformer mfgr
Partner company name
STATCOM: How-to-guide: switchgear
Wednesday, September 21,
2016Comsys ADF Power Tuning 16
• If using P300 units, dedicated switchgear may not be necessary
• If using gG (or similar fuses), ADF fuses protect connecting cable as well
• Again, short-circuit current must be taken into account
• For example, 4MVA @ uk=6% may give up to 100 kA
• In this case it may be better to divide into two separate transformers
• Take care to follow local regulation!
Partner company name
STATCOM: How-to-guide: CT
Wednesday, September 21,
2016Comsys ADF Power Tuning 17
• Normally use Open Loop configuration
• STATCOM projects typically pin-point load and/or facility
• All of Comsys STATCOMs have open-loop configuration!
• CTs might need to be custom ordered
• CTs placed on medium voltage do not always have 5A secondary
• In some cases, LEM current transducers must be used to maintain measurement precision
Partner company name
STATCOM: How-to-guide: cooling
Wednesday, September 21,
2016Comsys ADF Power Tuning 18
• Majority of Comsys STATCOM installations are liquid cooled
• For liquid cooling, system integration concept is presently only option
• P300W will re-appear
• Main difference is power density and overload-ability in flicker applications
Partner company name
STATCOM: (selected) Reference list
Wednesday, September 21,
2016Comsys ADF Power Tuning 19
Site Year Application Size Voltage
Höganäs 2007 EAF/Flicker 2x2 MVAr +
42 MVAr (THY)
22 kV
Dantysk 2015 Offshore wind farm (DPF) 4x1.5 MVAr 33 kV
Kville 2012 Wind farm/STATCOM (DPF) 2.5 MVAR 130 kV
Lingbo 2012 Wind farm/STATCOM (Flicker) 1 MVAr 33 kV
WDI 2012 Welding/Flicker 2.5 MVAr 20 kV
Sandvik 2010 EAF/Flicker 4 MVAr 10 kV
Global
Casting
2015 Casting/STATCOM (DPF) 4 MVAr 10 kV
Partner company name
Wednesday, September 21,
2016Comsys ADF Power Tuning 20
ADF – the shapeof power to come
Thank you for your time!
Partner company name
Wednesday, September 21,
2016Comsys ADF Power Tuning 21
Questions?
Partner company name
Comsys in brief
Wednesday, September 21,
2016Comsys ADF Power Tuning 22
Power
Quality
expert
Global
partner
Research
driven
Dedicated
to key
segments