    PCS100 STATCOM

    Dynamic Reactive Compensation 100kVAr to 10MVAr

    Technical Catalogue

    Copyright 2012 ABB, All rights reserved

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    2/20

    2 2UCD180000E002

    How to select your STATCOM?

    Choice1: Simply contact your local ABB sales office and let them know what you want.

    Use this catalogue as a reference for more information.

    OR

    Choice2: Build up your own ordering code by 6 steps. Each step is accompanied by a

    reference to a page that is filled with useful information.

    Type Code:

    Product Series

    STATCOM family

    Technical Specification

    Number of modules, rating

    Voltage & grounding

    Construction

    Mechanical Solution

    External CT Input rating

    Options

    Control Modes

    Redundancy

    Typical Installations

    Control Connections

    Examples

    Container Layout

    Contact and web information

    PCS100 18- 03 A- A10 A200+-1

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    3/20

    PCS100 STATCOM Technical Catalogue Rev B 3

    Product Series

    Overview

    The PCS100 STATCOM range is part of a family of low voltage power converter products

    available from ABB. Based around the PCS100 converter platform the STATCOM

    product provides wide bandwidth performance with a flexible and highly reliable modular

    power electronic configuration.

    New renewable generation such as wind and solar are becoming an increasingly

    important part of modern electricity grids, but to meet dynamic Grid Connection

    requirements STATCOM products must often be fitted. By injecting reactive current

    during a grid fault condition the STATCOM will help the generators ride through system

    fault events as required by the grid codes.

    During normal grid conditions, or at an end users site, the PCS100 STATCOM can

    provide correction for voltage flicker, poor power factor and harmonic currents. The

    PCS100 STATCOM advanced control also allows it to damp voltage disturbances in the

    electricity network. This control feature is very important to maintain power system

    stability following events such as recovering from a fault or the switching of passive

    elements. For end user industrial loads such as arc furnaces and mesh grid welders the

    PCS100 STATCOM can be applied to compensate voltage flicker and current distortion

    problems that often accompany these processes.

    User Benefits

    Improves power quality and plant reliability Increases network stability and transmission capacity

    Delivers necessary grid compliance when connecting renewable energy

    Damps disturbances and oscillations in critical system configurations

    Modular design for highest availability

    THDi < 3%, sine filter in each power module

    Based on LV converter platform especially developed for power quality applications

    Features Power factor control

    Voltage regulation

    Flicker compensation

    Harmonic current compensation Active resonance damping

    Multiple system parallel control

    High and low voltage ride through

    Appl ications PF correction, LVRT (low voltage right through), HVRT (high voltage right through),

    flicker compensation & active resonance damping for wind & solar generators

    Voltage regulation and PF correction for remote grid support

    PF correction, voltage regulation, flicker compensation,

    active resonance damping for industrial sites

    PCS100 18- 03 A- A10 A200+-1

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    4/20

    4 2UCD180000E002

    Technical Specification

    Mains connection....

    Voltage 400-480 AC/3~, 10%,

    direct connect or any LV

    or MV with a standard

    transformer

    Frequency 50 or 60 Hz

    Performance.

    Efficiency > 97% at rated power

    Overload capability for 480 V modules:

    10 min 120 %

    30 sec 150%

    2 sec 175%

    2 sec 200%

    (75 % preload for 200%)

    MTTR < 30 min by module

    exchange

    Environmental limits..

    Cabinet rating IP21 (higher IP ratings

    on request)

    Rack rating IP20

    Ambient temp. 0-50C, derating for

    temps > 40C

    Pollution degree 2

    Cooling Forced air ventilation

    Al ti tude

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    5/20

    PCS100 STATCOM Technical Catalogue Rev B 5

    Ratings, number of modules, voltage & frequency

    Number of modules

    01-12 for cabinets

    01-32 for racks

    Module type

    A 125 kVA, 480 V/3~. 50/60 Hz, 150 A, Isolation transformer coupled

    B 125 kVA, 480 V/3~. 50/60 Hz, 150 A, Direct grid connection

    All PCS100 products use the same LV power modules which employ IGBTs and integrated

    sinusoidal filters. The AC power connections of each module are protected by high speedsemiconductor fuses allowing simple paralleling of modules to achieve the required power

    rating. The DC connections of each module remain independent.

    The modules sine filter configuration differs for transformer coupled or direct grid connected

    STATCOM systems. If you are transformer coupled to e.g. a medium voltage you will choose

    module type A which incorporates an LC filter. If your STATCOM will be directly coupled to a

    low voltage installation (e.g. 380-480 Vac) you will need module type B with a LCL filter. Power

    rating for all modules is 125 kVA at nominal voltage of 480 Vac. To meet high voltage ride

    through requirements it may be necessary to reduce the AC coupling voltage at the module. In

    this case the power capacity is reduced accordingly.

    Module type A LC filter for t ransformer coupled systems

    Module type B LCL filter for direct grid connection

    PCS100 18- 03 A- A10 A200+-1

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    6/20

    6 2UCD180000E002

    Ratings, number of modules, voltage & frequency

    Even with power modules rated for 480V/3~ nominal voltage a STATCOM is very unlikely sized

    to operate at 480V. This is due to specifications asking for overvoltage or HVRT (high voltage

    ride through) capability. To allow for this requirement the sizing of the STATCOM range in this

    table refers to 460 V/3~ coupling voltage. For more details on the STATCOM sizing please refer

    to the chapter sizing.

    Ratings for 460 V/3~ supply. The given reactive power values can be achieved wi th 460 V

    at the inverter.

    Nominal load Overload 150% for

    30s, 100% preload

    Overload 175% for 2s,

    100 % preload

    Overload 200% for

    2s, 75% preload

    Type code

    No. of

    modulesQ

    kVAr

    I

    A

    Q

    kVAr

    I

    A

    Q

    kVAr

    I

    A

    Q

    kVAr

    I

    A120 150 180 225 210 263 240 300 PCS100 18-01A/B- 1

    240 300 360 450 420 525 480 600 PCS100 18-02A/B- 2

    360 450 540 675 630 788 720 900 PCS100 18-03A/B- 3

    480 600 720 900 840 1050 960 1200 PCS100 18-04A/B- 4

    600 750 900 1125 1050 1313 1200 1500 PCS100 18-05A/B- 5

    720 900 1080 1350 1260 1575 1440 1800 PCS100 18-06A/B- 6

    840 1050 1260 1575 1470 1838 1680 2100 PCS100 18-07A/B- 7

    960 1200 1440 1800 1680 2100 1920 2400 PCS100 18-08A/B- 8

    1080 1350 1620 2025 1890 2363 2160 2700 PCS100 18-09A/B- 9

    1200 1500 1800 2250 2100 2625 2400 3000 PCS100 18-10A/B- 10

    1320 1650 1980 2475 2310 2888 2640 3300 PCS100 18-11A/B- 11

    1440 1800 2160 2700 2520 3150 2880 3600 PCS100 18-12A/B- 12

    1560 1950 2340 2925 2730 3413 3120 3900 PCS100 18-13A/B- 13

    1680 2100 2520 3150 2940 3675 3360 4200 PCS100 18-14A/B- 14

    1800 2250 2700 3375 3150 3938 3600 4500 PCS100 18-15A/B- 15

    1920 2400 2880 3600 3360 4200 3840 4800 PCS100 18-16A/B- 16

    2040 2550 3060 3825 3570 4463 4080 5100 PCS100 18-17A/B- 17

    2160 2700 3240 4050 3780 4725 4320 5400 PCS100 18-18A/B- 18

    2280 2850 3420 4275 3990 4988 4560 5700 PCS100 18-19A/B- 19

    2400 3000 3600 4500 4200 5250 4800 6000 PCS100 18-20A/B- 20

    2520 3150 3780 4725 4410 5513 5040 6300 PCS100 18-21A/B- 21

    2640 3300 3960 4950 4620 5775 5280 6600 PCS100 18-22A/B- 22

    2760 3450 4140 5175 4830 6038 5520 6900 PCS100 18-23A/B- 23

    2880 3600 4320 5400 5040 6300 5760 7200 PCS100 18-24A/B- 24

    3000 3750 4500 5625 5250 6563 6000 7500 PCS100 18-25A/B- 25

    3120 3900 4680 5850 5460 6825 6240 7800 PCS100 18-26A/B- 26

    3240 4050 4860 6075 5670 7088 6480 8100 PCS100 18-27A/B- 27

    3360 4200 5040 6300 5880 7350 6720 8400 PCS100 18-28A/B- 28

    3480 4350 5220 6525 6090 7613 6960 8700 PCS100 18-29A/B- 29

    3600 4500 5400 6750 6300 7875 7200 9000 PCS100 18-30A/B- 30

    3720 4650 5580 6975 6510 8138 7440 9300 PCS100 18-31A/B- 31

    3840 4800 5760 7200 6720 8400 7680 9600 PCS100 18-32A/B- 32

    Depending on the chosen nominal voltage the number of modules needed to supply a certain

    power can be significantly bigger. Please use the sizing tool or contact your local ABB for

    support.

    PCS100 18- 03 A- A10 A200+-1

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    7/20

    PCS100 STATCOM Technical Catalogue Rev B 7

    Mechanical Solution

    Construction

    Ax0 standard cabinet in 1 row based on (800 x 800) mm sections

    Ax0 no. of 800 mm sections (width) for standard cabinet (max. 6 modules per 800mm)

    possible combinations are A10 & A20 (max. 12 modules)

    Bxx standard rack in 1 row, a rack can have sections of 1000 mm width

    Bxx number of 1000mm sections (max. 8 modules per 1000mm)

    possible combinations for racks: 1-8 modulesB1x, 9-16 modulesB2x, etc.

    Bxx AC-termination of rack system

    possible termination: left termination Bx5, right terminationBx6, center

    termination BxB, center terminationBxC. Examples shown below.

    Cxx customized solution, the following numbers are serial numbers for solutions

    PCS100 18-16A-B25 PCS100 18-08A-B16

    Xxx

    PCS100 18- 03 A- A10 A200+-1

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    8/20

    8 2UCD180000E002

    PCS100 18-24A-B3B PCS100 18-24A-B3C

    PCS100 18-32A-B4B

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    9/20

    PCS100 STATCOM Technical Catalogue Rev B 9

    Standard cabinets

    The standard cabinet has a foot print of approximately 800 mm x 800 mm. A maximum of 6 inverter

    modules can be installed into one cabinet. For PCS100 STATCOM systems with more than 6 inverter

    modules multiple cabinets are used. One enclosure is deemed the master and the remaining are deemed

    slaves. The master cabinet houses the master auxiliary module which contains a power supply and the

    system control electronics. The slave inverter enclosure houses a slave auxiliary module which containsa power supply. The Graphical Display Module (GDM) is always mounted in the door of the master Inverter

    enclosure.

    Dimensions, weight, losses and air flow for standard cabinets

    Dimensions Weight Heat dissipation Air flow

    Type code

    No. of

    modulesHeight

    in mm

    Width

    in mm

    Depth

    in mm

    kg kW BTU/h m/h ft/min

    2154 809 804 361 2.9 9.8 600 353.2 PCS100 18-01A/B-A10 1

    2154 809 804 441 5.8 19.6 1200 706.5 PCS100 18-02A/B-A10 2

    2154 809 804 521 8.6 29.4 1800 1059.7 PCS100 18-03A/B-A10 32154 809 804 601 11.5 39.2 2400 1412.9 PCS100 18-04A/B-A10 42154 809 804 681 14.4 49.0 3000 1766.2 PCS100 18-05A/B-A10 52154 809 804 761 17.3 58.9 3600 2119.4 PCS100 18-06A/B-A10 62154 1609 804 1166 20.1 68.7 4200 2472.6 PCS100 18-07A/B-A20 72154 1609 804 1246 23.0 78.5 4800 2825.9 PCS100 18-08A/B-A20 82154 1609 804 1326 25.9 88.3 5400 3179.1 PCS100 18-09A/B-A20 92154 1609 804 1406 28.8 98.1 6000 3532.3 PCS100 18-10A/B-A20 102154 1609 804 1486 31.6 107.9 6600 3885.6 PCS100 18-11A/B-A20 112154 1609 804 1566 34.5 117.7 7200 4238.8 PCS100 18-12A/B-A20 12

    Auxiliary supply & master module

    with CAN I/O board mounted

    CAN I/O Boardterminals

    Auxiliary module

    terminals

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    10/20

    10 2UCD180000E002

    Standard racks

    Racks are used for easy containerization or

    integration into switchboards.

    The racks have two different footprints of

    1000mm x 800mm per section for 1-8 modules

    and 2000mm x 800mm for 9-16 modules. Empty

    slots will be covered by a blanking plate

    The modules are installed in 2 levels with ac

    busbars running between the 2 levels. Busbars

    can be terminated to either end of the rack.

    Usually a termination cabinet containing an AC

    breaker is installed next to the rack by the system

    integrator.

    The master controllerand the auxiliary supply

    for each system are built as a module for

    integration into a separate control cabinet.

    The GDM (Graphic Display Module) is normally

    installed in the control cabinet as well.

    Dimensions, weights, losses and air flow for standard racks

    Dimensions Weight Heat dissipation Air flow

    Type code

    No. of

    modulesHeight

    in mm

    Width in

    mm

    Depth

    in mm

    kg kW BTU/h m/h ft/min

    2200 1041 703 344 2.9 9.8 600 353.2 PCS100 18-01A/B-B10 1

    2200 1041 703 420 5.8 19.6 1200 706.5 PCS100 18-02A/B-B10 22200 1041 703 496 8.6 29.4 1800 1059.7 PCS100 18-03A/B-B10 32200 1041 703 557 11.5 39.2 2400 1412.9 PCS100 18-04A/B-B10 42200 1041 703 628 14.4 49.0 3000 1766.2 PCS100 18-05A/B-B10 52200 1041 703 700 17.3 58.9 3600 2119.4 PCS100 18-06A/B-B10 6

    2200 1041 703 771 20.1 68.7 4200 2472.6 PCS100 18-07A/B-B10 72200 1041 703 842 23.0 78.5 4800 2825.9 PCS100 18-08A/B-B10 82200 2041 703 1015 25.9 88.3 5400 3179.1 PCS100 18-09A/B-B20 92200 2041 703 1081 28.8 98.1 6000 3532.3 PCS100 18-10A/B-B20 102200 2041 703 1152 31.6 107.9 6600 3885.6 PCS100 18-11A/B-B20 112200 2041 703 1224 34.5 117.7 7200 4238.8 PCS100 18-12A/B-B20 122200 2041 703 1295 37.4 127.5 7800 4592.0 PCS100 18-13A/B-B20 132200 2041 703 1366 40.3 137.3 8400 4945.2 PCS100 18-14A/B-B20 142200 2041 703 1437 43.1 147.1 9000 5298.5 PCS100 18-15A/B-B20 152200 2041 703 1508 46.0 157.0 9600 5651.7 PCS100 18-16A/B-B20 16

    From 16-32 modules additional racks are used. Please add the values for the appropriate no. of

    modules.

    For B modules please add 10 kg weight per module.

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    11/20

    PCS100 STATCOM Technical Catalogue Rev B 11

    Options

    The options for all PCS100 are defined by additional codes. Each option has an own code and

    will be added to the type code by a plus. The options are categorized.

    Available options

    A standard PCS100 STATCOM contains a GDM (graphic display module) and one CAN-I/O-

    board (CIOB). The GDM has a USB port to interface to a PC (ABB Service) and an Ethernet

    port to allow Modbus TCP/IP or remote web server functionality. The CAN-I/O-board (CIOB)

    also contains a serial RS485 Modbus connection.

    +A200 External aux. power supply for cabinets (instead of powering from main

    terminals), 230 and 110 V/1~ 2 kVA for up to 6 modules.

    +CT1 or +CT5 Optional external CT input for cabinets. 1A or 5A.

    +VT110 or VT480 Optional external VT input for cabinets. 110V L-L or 480V L-L.

    +OCB Output circuit breaker(s) in extra 400mm cabinet.

    +IP23 or IP42 Increased IP rating for cabinet systems. Upon request.

    Redundancy

    The PCS100 Advanced Redundancy feature represents a further milestone of power electronics

    reliability and availability improvements.

    It allows uninterrupted operation in case of a module failure with N-1 reduced capability. The

    faulty module will be taken out of operation while the rest of the system continues.

    Value:

    Reduces power output in a failure only by a small fraction of the total system power.

    Enables built in n+1 configurations by adding a spare module to achieve breakthrough levels in

    power availability.

    Allows careful and flexible planning of converter repair/faulty module replacement.

    PCS100 18- 03 A- A10 A200+-1

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    12/20

    12 2UCD180000E002

    Control Modes

    A PCS100 STATCOM can be controlled in different modes depending on the application.

    Voltage Control mode:

    The PCS100 STATCOM receives a voltage reference. The internal controller compares

    measured voltage (MV or LV level) and reference. Is the voltage below the reference, capacitive

    reactive power is injected. If the voltage is too high inductive Q will be delivered. Voltage

    feedback is needed.

    Power Factor mode:

    The PCS100 STATCOM receives a PF reference. The internal controller compares measured

    PF and reference and controls the power factor on the connection point to meet the reference. It

    delivers capacitive or inductive VArs depending on the existing PF. Voltage and current

    feedback is needed. There are 2 variants of the PF mode. Fixed PF defines the signed PF and

    PF range allows a PF in a +/- range. E.g PF range 0.98 means the PF should stay between

    -0.981+0.98. Only if the PF gets out of this range the STATCOM is active. Voltage andcurrent feedback is needed.

    Reactive Current mode:

    The PCS100 STATCOM receives a reference proportional to the amount of reactive current

    needed. The signed reference defines inductive or capacitive reactive current.

    Flicker mitigation:

    Flicker mitigation is a feature that can be used with the voltage control mode. Depending on the

    application we need to specify the position of the current feedback. Current and voltage

    feedback is needed.

    Harmonic fil tering:

    The PCS100 STATCOM has the capability to suppress low frequency harmonics, especially 5th

    and 7th. The PCS100 is capable of correcting two integer or non-integer harmonics, up to the

    7th. This feature is available in every control mode and requires current and voltage feedback

    from the system.

    Unbalance (negative sequence) correction:

    The PCS100 STATCOM can selectively correct either unbalanced voltages or currents.Negative sequence current correction is limited to 30% of the nominal unit current. This feature

    is available in every control mode and requires current and voltage feedback from the system.

    Figure 1: Negative sequence current cancellation example

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    13/20

    PCS100 STATCOM Technical CatalogueRev B 13

    Typical Installations

    Each mode has different sensor requirements. In any application the PCS100 can

    accommodate an optional transformer (eg MV-LV) between the control-point and the unit.

    Voltage, Reactive Current and Voltage-

    Unbalance Modes

    These modes only require VT feedback.

    Feedback can be from internal VT or

    external Point of Common Coupling.

    Harmonics Feedforward

    Harmonics feedforward cancelation

    measures the load current with a CT to

    cancel it at the Point of Common Coupling.

    Power Factor, Current-Unbalance, and

    Harmonics Feedback Modes

    These modes only require both VTs and

    CTs located at the Point of Common

    Coupling.

    Flicker Cancelation

    Flicker cancelation employs both voltage

    correction and current-feedforward. Current

    feedforward minimizes the effect of the load

    flicker source, and voltage correction fixes

    any residue voltage flicker.

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    14/20

    14 2UCD180000E002

    Control Connections

    Can I/O Board

    1

    2

    3

    4

    5

    6

    7

    GDM

    Ethernet

    USB

    SCADA

    Interface

    Service /

    Commissioning

    1NO

    2NO

    1C

    3NO

    4NO

    2C

    3C

    4C

    3NC

    2NC

    1NC

    4NC

    0V

    0V

    0V

    0V

    0V

    0V

    +

    +

    +

    +

    -

    -

    -

    in

    Aout 1

    Aout 2

    A

    B

    +24V

    COM

    Ref V

    Input 2

    Input 1

    Outputs

    Relay

    1

    Relay

    2

    Relay

    3

    Relay

    4

    Master

    Module

    1

    3

    2

    NC

    C

    NO

    7

    9

    8

    NC

    C

    NO

    NC

    CNO

    4

    6

    5

    12

    13

    14

    15

    16

    17

    18

    0 VSTART

    Factory

    only

    Stop/Reset/

    Inhibit

    0VLoop

    10

    11

    PTC

    Transformer

    Run

    Warning

    Fault

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    15/20

    PCS100 STATCOM Technical CatalogueRev B 15

    Examples

    PCS100 18-06A-A10

    STATCOM cabinet with 6 power modules.

    Aux. supply and master controller in the bottom right corner.

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    16/20

    16 2UCD180000E002

    Container Layout

    Layout for a 2 MVA system with integrated dry type transformer in a 20 foot container

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    17/20

    PCS100 STATCOM Technical CatalogueRev B 17

    Sizing

    The sizing of a STATCOM is depending on the application. Based on the needed VAr amount and the grid

    requirements the number of modules required can be defined.

    Applications like repetitive flicker (e.g. welder or crasher) or LVRT (low voltage ride through) support canoften be targeted by using the overload capability of the system.

    Power factor cont rol:

    PF control very seldom requires dynamic behavior. Therefore most PF applications can be solved with

    passive elements switched together with main loads. For cost reasons only the dynamic part of the PF

    fluctuations should be targeted by a STATCOM. Switching limitations for the passive elements may cause

    the need for a STATCOM. The relation between displacement PF and power can be described by the

    following equations:

    with: S = apparent power,

    P= real power &Q = reactive power.

    Voltage control:

    A STATCOM delivers reactive current only.

    Therefore the potential voltage support is

    limited by the impedance and power rating of

    the next coupling transformer. If we have a

    wind farm at 33 kV and the coupling

    transformer to the HV is e.g. rated with 50MVA & uk= 10% we can achieve a maximum

    voltage support of 10% by using a 50 MVA

    STATCOM. Most voltage fluctuations are only

    short term events. Therefore we often can use

    overload capability of the STATCOM (e.g.

    LVRT support for a wind farm).Statcom Load orGeneration

    PCC

    LV or MV bus

    HV bus

    S transformer (VA)

    Uk transformer (%)

    Q Statcom (VA)

    dV (%) =

    Q Statcom

    S transformer x Uk transformer

  • 8/10/2019 2UCD180000E002_b STATCOM Technical Catalogue.pdf

    18/20

    18 2UCD180000E002

    For more information and local contact details please refer to:

    www.abb.com/powerelectronics, Power Protection, VAr Compensation