seasonal influences on safety of substation grounding systems seminar report

40
Seasonal Influence on Safety of Substation Grounding 1. INTRODUCTION With the development of modern power system to the direction of extra-high voltage, large capacity, far distance transmission and application of advanced technologies the demand on the safety, stability and economic operation of power system became higher. A good grounding system is the fundamental insurance to keep the safe operation of the power system. The good grounding system should ensure the following: To provide safety to personnel during normal and fault conditions by limiting step and touch potential. To assure correct operation of electrical devices. To prevent damage to electrical apparatus. To dissipate lightning strokes. Dept. of EEE MESCE Kuttippuram 1

Upload: iagoo

Post on 07-Mar-2015

672 views

Category:

Documents


22 download

TRANSCRIPT

Page 1: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

1. INTRODUCTION

With the development of modern power system to the direction of

extra-high voltage, large capacity, far distance transmission and application of

advanced technologies the demand on the safety, stability and economic

operation of power system became higher. A good grounding system is the

fundamental insurance to keep the safe operation of the power system. The

good grounding system should ensure the following:

To provide safety to personnel during normal and fault conditions by

limiting step and touch potential.

To assure correct operation of electrical devices.

To prevent damage to electrical apparatus.

To dissipate lightning strokes.

To stabilize voltage during transient conditions and therefore to

minimize the probability of flashover during the transients

As it is stated in the ANSI/IEEE Standard 80-1986 “IEEE Guide for

Safety in AC substation grounding,” a safe grounding design has two

objectives:

To provide means to carry electric currents into the earth under normal

and fault condition without exceeding any operational and equipment

limit or adversely affecting continuity of service.

Dept. of EEE MESCE Kuttippuram

1

Page 2: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

To assure that a person in the vicinity of grounded facilities is not

exposed to the danger of critical electrical shock.

A practical approach to safe grounding considers the interaction of

two grounding systems: The intentional ground, consisting of ground

electrodes buried at some depth below the earth surface, and the accidental

ground, temporarily established by a person exposed to a potential gradient at

a grounded facility.

An ideal ground should provide a near zero resistance to remote

earth. In practice, the ground potential rise at the facility site increases

proportionally to the fault current; the higher the current, the lower the value

of total system resistance which must be obtained. For most large substations

the ground resistance should be less than 1 Ohm. For smaller distribution

substations the usually acceptable range is 1-5 Ohms, depending on the local

conditions.

When a grounding system is designed, the fundamental method is to

ensure the safety of human beings and power apparatus is to control the step

and touch voltages in their respective safe region. step and touch voltage can

be defined as follows.

1.1 STEP VOLTAGE

It is defined as the voltage between the feet of the person standing in

near an energized object. It is equal to the difference in voltage given by the

Dept. of EEE MESCE Kuttippuram

2

Page 3: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

voltage distribution curve between two points at different distance from the

electrode.

1.2 TOUCH VOLTAGE

It is defined as the voltage between the energized object and the feet

of the person in contact with the object. It is equal to the difference in voltage

between the object and a point some distance away from it.

In different season, the resistivity of the surface soil layer would be

changed. This would affect the safety of grounding systems. The value of step

and touch voltage will move towards safe region or to the hazard side is the

main concerned question

The grounding system of power plants and substations is usually

formed by several vertical ground rods connected to each other and to all

equipment frames, neutrals and structures that are to be grounded. Such a

system that combines a horizontal grid and a number of vertical ground rods

penetrating lower soil layers has several advantages in comparison to a grid

alone. Sufficiently long ground rods stabilize the performance of such a

combined system making it less dependent on seasonal and weather variations

of soil resistivity. Rods are more efficient in dissipating fault currents because

the upper soil layer usually has a higher resistivity than the lower layers. The

current in the ground rods is discharged mainly in lower portion of the rods.

Dept. of EEE MESCE Kuttippuram

3

Page 4: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

Therefore, the touch and step voltages are reduced significantly compared to

that of the grid alone.

In areas where the soil resistivity is rather high or the facility space

is at premium, it may be not possible to obtain the required low impedance of

the grounding system by spreading the ground rods and grid over a large area.

The possible solutions of that rather complicated problem may be summarized

as follows:

To change the soil resistivity in the limited area of interest by

implementation of the chemically charged ground rods with or without

an additional backfill.

To establish remote ground grid connected to the main ground system.

To use the deep-driven ground rods reaching underground water table or

lower soil layers with low resistivity.

To use main remote ground mats.

To analyze the technical and economical aspects of each one of

alternatives mentioned above, first one must examine the components of the

grounding electrode resistance. There are three general components affecting

grounding electrode resistance:

The resistance of the electrode

The resistance of the electrode-to-soil interface area

The soil resistivity.

Dept. of EEE MESCE Kuttippuram

4

Page 5: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

Out of which the resistance of the electrode itself is negligible,

although it varies with the length, diameter and deployment of the electrode.

The resistance of the electrode-to-soil interface area is nearly negligible at

temperatures above freezing. However, when the temperature of soil drops

below freezing point, a veneer of ice may form on the ground electrode,

adding resistance to the electrodeearth interface. Another that affects

electrode soil interface resistance is soil compactness around the ground

electrode. A loose backfill or non-compact soil around the electrode will

reduce the contact area and increase resistance. The soil resistivity is the

single most important factor affecting the resistance of the ground system.

That is why the most economically sound solution is lowering the soil

resistivity to the level required to obtain the specified resistance impedance of

the ground system. In order to work out a practical approach of the soil

treatment, the soil characteristics related to electrical conductivity at different

seasons are to be studied.

Dept. of EEE MESCE Kuttippuram

5

Page 6: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

2. INFLUENCE OF RAINING AND FREEZING SEASON

ON SOIL RESISTIVITY

The resistivity of soil in nature is decided by the following factors:

Soil type

Soil resistivity varies widely depending on soil type, from as low as

1 Ohm- meter for moist loamy topsoil to almost 10,000 Ohm-meters for

surface limestone.

Moisture content

It is one of the controlling factors in earth resistance because electrical

conduction in soil is essentially electrolytic. The resistivity of most soils

rises abruptly when moisture content is less than 15 to 20 percent by

weight, but is affected very little above 20 percent. It must be

recognized, however, that the moisture alone is not the predominant

factor influencing the soil resistivity. If the water is relatively pure, it

will be of high resistivity and may not provide the soil with adequate

conductivity.

The soluble salts, acids or alkali

The presence of these components influences considerably the soil

resistivity.The most commonly used salting materials are sodium

chloride (common salt), copper sulfate and magnesium sulfate (Epsom

salt). Different types of salts have varying depletion rates; consequently,

Dept. of EEE MESCE Kuttippuram

6

Page 7: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

different types may be combined to produce the optimum depletion and

conditioning characteristics. Sodium chloride and magnesium sulfate are

the most commonly used salting materials. Magnesium sulfate is

considered to be the least corrosive. Salting materials will inhibit the

formation of ice and will lower the resistivity of the soil. It may take

some time for the salting effects to be noticed, although the earth

connection will continue to improve over time until the salt content

reaches about six per cent by weight. Higher resistivity soils take longer

to condition. It takes topsoil about two months, clay four months and

sand gravel five months for the salt minerals concentration to reach

about six per cent. Such concentration of salts poses a negligible

corrosion threat.

The temperature

Effect on soil resistivity is almost negligible for temperatures above the

freezing points. When temperature drops below water freezing point the

resistivity increases rapidly.

Compactness and granularity

It affects soil resistivity in that denser soils generally have lower

resistivity. These factors do not vary over time. Once the resistivity has

been assessed these factors can usually be ignored. From all the factors

mentioned above, two factors—moisture and salt content—are the most

influential ones on soil resistivity for a given type of soil. Therefore the

Dept. of EEE MESCE Kuttippuram

7

Page 8: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

chemical treatment of soil surrounding ground rods is preferable and in

some cases the only economically sound solution in obtaining low

impedance of the ground system

The resistivity of affected soil layer and surface material used in the

analysis of this paper is shown in Table I. When the influence of season factor

is not considered, the soil is homogeneous, the resistivity of normal soil is

200Ώm.This is called as the normal condition, the ground resistance, step

voltage and touch voltage in the normal condition is used to measure the

influence of the raining and freezing season.

In raining season, there is a wet surface soil layer with decreased

resistivity; the resistivity of the affected surface soil layer is changed in the

range of 10 to 200 Ώ m to consider the influence of raining season on the

surface soil layer. In freezing season, there is a freezing surface soil layer with

increased resistivity, the resistivity of the affected surface soil layer is

changed in the range of 200 to 5000 Ώm to consider the influence of freezing

season on the surface soil layer. The resistivity of the granite layer in raining

season is assumed as 5000 Ώ m and its resistivity in normal condition and in

freezing season is assumed as 15000 Ώ m.

Dept. of EEE MESCE Kuttippuram

8

Page 9: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

3. ANALYSIS MODEL OF GROUNDING SYSTEM

For the analysis of the seasonal influence on the grounding system

we are considering two models. Model 1 and 2 which are as given in the

figure below:

Two different cases are analyzed in this paper as shown in Figs. I

and 2. There is not surface material with high resistivity in model I as shown

in Fig. 1. The surface material with high resistivity was considered in model

II as shown in Fig. 2. A granite layer with thickness of 0.1 m is used for the

surface material. A 100 x I00 m horizontal grounding system is assumed in

our analysis.

Dept. of EEE MESCE Kuttippuram

9

Page 10: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

The main function of the surface material with high resistivity is to

increase the limits of step and touch voltages. According to IEEE Standards

the limits of step and touch voltages in V for a body weight of 50 kg can be

calculated by using the formula given below

Estep = (1000+6 Cs Ps) 0.116/t

Etouch = (1000+1.5 Cs Ps) 0.116/t

Ps =resistivity of surface layer

t =time duration of shock current in seconds

Cs =surface layer derating factor

Cs =1- 0.09 (1-P/P)/2hs+0.09

hs =thickness of the surface material in meters

P =resistivity of earth beneath the surface material

The limit of step and touch voltage in different seasons when surface

material is used and not used is given below

Dept. of EEE MESCE Kuttippuram

10

Page 11: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

Considered limits of step and touch voltages decrease in raining

season and increase in freezing season. In normal condition, the grounding

grid is buried in homogeneous soil with resistivity of 200 Ώ m, the maximum

step and touch voltages are 547 and 1481 V. if the surface material is not

used, and the limits of step and touch voltages are 316 and 187 V, the

maximum step and touch voltages exceed limits. If a granite layer is used, the

limits of step and touch voltages are 9131 and 2890 V, the grounding system

is safe. So the surface granite layer should be used, then the grounding system

in normal condition is safe.

Dept. of EEE MESCE Kuttippuram

11

Page 12: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

4. INFLUENCES OF RAINING SEASON ON SAFETY

OF GROUNDING SYSTEMS

INFLUENCES ON GROUNDING RESISTANCE

The influence of the thickness it of the low-resistivity soil layer

formed in raining season on the grounding resistance is shown in Fig below

The vertical dot line illustrated in Fig. shows the burial depth of the

grounding system If the thickness of this low-resistivity soil layer is smaller

than the burial depth of the grounding system (left side of the vertical dot line

as shown in Fig.), the grounding resistance of the grounding system decreases

with the burial When the low-resistivity soil layer exits, if a current is injected

into the grounding system, a part of this current would disperse into the low-

resistivity surface soil layer, the thicker the low-resistivity soil layer is, the n

the dispersed current from the low-resistivity soil layer is, and the more the

Dept. of EEE MESCE Kuttippuram

12

Page 13: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

grounding resistance decreases. When the thickness of the low-resistivity soil

layer is very thin, its influence on the grounding resistance can be neglected.

But when the thickness of the low-resistivity soil layer changes from smaller

than the burial depth of the grounding g to higher than the burial depth (right

side of the vertical dot as shown in Fig.), the grounding resistance would

decrease sharply.

INFLUENCE ON TOUCH VOLTAGE

The influence of the thickness of the low resistivity soil layer formed

on the touch voltage is shown in figure below.

The maximum touch voltage on the ground surface in normal

condition is 1481 V. When the thickness of the low-resistivity soi1 layer is

smaller than the burial depth (left side of the vertical dot line as shown in

Fig.) the touch voltage on the ground surface wou1d increase comparing with

the normal condition, the smaller the thickness of the affected soil layer is, the

higher the influence is. When the thickness of the low-resistivity soil layer

changes from smaller than the burial depth of the grounding systems to higher

Dept. of EEE MESCE Kuttippuram

13

Page 14: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

than the burial depth. The touch voltage would decrease rapidly, and be

smaller than the respective value in normal condition.

INFLUENCE ON STEP VOLTAGE

The influence of the thickness of the low resistivity soil layer formed

in raining season on the step voltage is shown in the figure below:

The step voltage decreases with increase of the thickness of the low

resistivity soil layer. The higher the resistivity smaller is the influence on step

voltage. If the resistivity of the affected soil layer is small, and its thickness h

is smaller than 0.5H ( H is the burial depth of the grounding system. 0.8 m is

used in this paper), the step voltage decreases very quickly. In raining season,

the step voltage is smaller than the respective normal value; it is safe for

human beings

Dept. of EEE MESCE Kuttippuram

14

Page 15: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

5 . INFLUENCES OF FREEZING SEASON ON SAFETY

OF GROUNDING SYSTEMS

INFLUENCE ON GROUNDING RESISTANCE

In freezing season, a high-resistivity surface soil layer is formed,

which is called as freezing soil layer in this paper. The influence of the

thickness of the freezing soil layer on the grounding resistance of the

grounding system is shown in figure below:

The grounding resistance increases with the thickness of the freezing

soil layer. When its thickness is less than the burial depth of the horizontal

grounding system (the left side of the vertical dot line in figure), if a current is

injected-into the grounding system, the current would mainly flow into the

bottom normal soil with resistivity of 200 Ώ m, and there is a very small part

of current that would flow through the upper freezing soil layer with high

Dept. of EEE MESCE Kuttippuram

15

Page 16: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

resistivity formed in freezing season, so the grounding resistance is almost

kept unchanged.

When the thickness of the high resistivity soil layer exceeds the

burial depth of the grounding grid (the right side of the vertical dot line in

figure), if a current is injected into the grounding system, the current has to

flow through the freezing soil layer with high resistivity to the bottom normal

soil layer with resistivity of 200 Ώ m, so the grounding resistance increases

with the thickness of the freezing soil layer. We observed that the grounding

resistance increases with the resistivity of the high resistivity soil layer. When

the thickness of the freezing soil layer is in the range of 1 to 1.6 m, and the

resistivity Pa of the freezing soil layer is 5000 m, in this case, the grounding

resistance will increase to 1.7 to 3.0 times of that of grounding system in

normal condition, so the influence of freezing season on the grounding

resistance is very high and we have to pay attention to it.

INFLUENCE OF FREEZING SEASON ON THE

TOUCH VOLTAGE

Influence of the thickness h of the freezing soil layer on the touch

voltage on the grounding surface is shown below

Dept. of EEE MESCE Kuttippuram

16

Page 17: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

When thickness h is less than the burial depth of the grounding

resistance (the left side of the vertical dot line in figure), the influence of the

freezing surface soil layer on the touch voltages very small. And touch

voltage also increases slightly. When the thickness of the freezing soil layer

exceeds the burial depth of the grounding grid, the touch voltage increases

quickly with the thickness of the freezing soil layer.

We can observe from figure, the higher the resistivity of the freezing

soil layer is, the more largely the touch voltage increases. When its thickness

exceeds 1 m and its resistivity is 5000 Ώ m. then the touch voltage would

increase to 12 times of the respective value in normal condition, the influence

is very serious, this condition must he considered in the design of grounding

system.

Dept. of EEE MESCE Kuttippuram

17

Page 18: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

INFLUENCE OF FREEZING SEASON ON THE STEP

VOLTAGE

The influence of the thickness h of the freezing soil layer on the step

voltage is illustrated in figure below:

The step voltage increases with the thickness, when there is a

freezing surface layer, the step voltage would be higher than the normal value.

When the thickness of the freezing soil layer is smaller than the burial depth

of the grounding system (left side of the vertical dot line in figure), the

influence of the freezing soil layer on the step voltage is very small. When the

thickness of the freezing soil layer exceeds the burial depth of the grounding

grid (right side of the vertical dot line in figure), the step voltage increases

rapidly.

So, in the highly freezing area, the design of the grounding grids

should strictly analyze whether the step and touch voltages are smaller than

the safe values, and reduce the safety of the grounding grids. The influence of

the freezing soil layer on step and touch voltages is very weak when its

thickness is smaller than the burial depth of the grounding grid, and the safety

of the grounding grid is not affected. When its thickness is larger than the

burial depth of the grounding grid, the safe characteristics of the grounding

grid would he reduced strongly.

Dept. of EEE MESCE Kuttippuram

18

Page 19: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

6. MEASURES TO BE TAKEN

In raining season the low resistivity soil layer formed leads the

ground resistance and step voltage smaller than the respective value in normal

condition .it is good for human beings but the raining season perhaps leads the

touch voltage higher than its limit values. When the surface soil layer forms

high resistivity layer in freezing season, the grounding resistance of

grounding grid increases with the thickness of the high resistivity layer. In

order to nullify the effect the effect we can use the following methods:

6.1 USE OF LONG VERTICAL GROUNDING ELECTRODES

The use of long electrodes will effectively increace the burial depth

and hence decreases the effect of seasonal influence

6.2 THE CHEMICAL TREATMENT OF THE SOIL

It may be implemented by any one of the following three ways:

TO USE CONDUCTIVE BACKFILL MATERIALS

Several materials exist on the market that are used to replace poorly

conducting soil near the ground electrodes. The impact of putting these

materials around the electrodes is significant, since that is where the majority

of connection to the earth takes place. Four such materials used for conductive

backfills around ground electrodes are described below.

Dept. of EEE MESCE Kuttippuram

19

Page 20: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

Concrete: has a resistivity range of 30 to 90 Ohm-meters. Since it is

hydroscopic by nature it will tend to absorb moisture when available and keep

it up to 30 days, thus maintaining a resistivity lower than the surrounding soil.

However, during a long dry season concrete will dry out with a subsequent

rise in resistivity. Also, if a substantial amount of fault or lightning current is

injected into a concrete encased electrode, the moisture in the concrete may

become steam, dramatically increasing in volume and placing a substantial

stress on the concrete.

Carbon-based backfills materials: have generally a resistivity lower than

clay-based mixtures. Some of these materials can be mixed with concrete to

make concrete more conductive. However, these materials tend to be the most

expensive and do not retain moisture nearly as well as clay-based materials.

The amount of the backfill material required is determined in most cases by

the Interfacing Volume and Critical Cylinder principles. A ground electrode

establishes a connection to earth by affecting only a certain volume of earth,

called the Interfacing

Dept. of EEE MESCE Kuttippuram

20

Page 21: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

TO USE THE CHEMICALLY CHARGED GROUND RODS

(CCGR)

Used instead of the conventional ground rods. A CCGR is a copper

tube of 2-2.5 inches in diameter with several small holes perforated along the

length of the tube. The tube is filled with metallic salt evenly distributed along

the entire length of the tube. The moisture absorbed from the air and soil form

a solution of the contained metallic salt within the CCGR which seeps out

through the holes into the surrounding soil, thus lowering the soil’s resistivity

and increasing the efficiency of the electrode.

TO IMPLEMENT A COMBINATION OF THE CCGR WITH

BACKFILL.

Grounding system based on the implementation of the CCGRs with

backfill appears to be the most economical solution in the given conditions of

poor conducting soil and low values of the required ground resistance, even

without taking into consideration the cost of real estate. Where the appropriate

space is not available or too expensive, the CCGRs the only solution in

establishing required ground system.

Dept. of EEE MESCE Kuttippuram

21

Page 22: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

7. CONCLUSION

The use of long vertical electrodes and chemically charged ground

electrodes (CCGR) with or with out backfills establishes relatively low

ground resistance and ground impedances which are not subjected to seasonal

and weather variations much.

Dept. of EEE MESCE Kuttippuram

22

Page 23: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

8. REFERENCES

Grounding of AC electrical devices, electrical power industry

ministry.19997,98

IEEE Guide for safety in AC substations grounding ANSI/IEEE 80-

2000

R.S GUSTAFSONS,R.PURSELY “Seasonal grounding resistance

variation on grounding system” IEEE transaction on power delivery.

Roy B.CARPENTER ,DRABKIN “BETTER GROUNDING ”

Lightning eliminator and consultants inc,USA

WWW.OSHA.GOV

Dept. of EEE MESCE Kuttippuram

23

Page 24: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

ABSTRACT

The low or high resistivity soil layer formed in raining or freezing

season affects the safety of grounding system, and leads the changes of

grounding resistance of the grounding system, step and touch voltages on the

ground surface. This paper systematically discusses the seasonal influence on

the safety of grounding system and the different methods to be adopted

inorder to nullify the effect of seasonal changes.

Inorder to nullify the effect of the seasonal changes we can use long

vertical grounding electrodes or by using chemically charged ground

electrodes (CCGR) with or without backfill which can effectively attenuate

the seasonal influence and improve the safety of the grounding system.

Dept. of EEE MESCE Kuttippuram

24

Page 25: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

ACKNOWLEDGEMENT

I express my sincere gratitude to Dr.Nambissan, Prof. & Head,

Department of Electrical and Electronics Engineering, MES College of

Engineering, Kuttippuram, for his cooperation and encouragement.

I would also like to thank my seminar guide Mrs. Sobha M (Asst.

Professor, Department of EEE), Asst. Prof. Gylson Thomas. (Staff in-charge,

Department of EEE) for their invaluable advice and wholehearted cooperation

without which this seminar would not have seen the light of day.

Gracious gratitude to all the faculty of the department of EEE &

friends for their valuable advice and encouragement.

Dept. of EEE MESCE Kuttippuram

25

Page 26: Seasonal Influences on Safety of Substation Grounding Systems Seminar Report

Seasonal Influence on Safety of Substation Grounding

CONTENTS

1. INTRODUCTION 1

1.1 STEP VOLTAGE 2

1.2 TOUCH VOLTAGE 3

2. INFLUENCE OF RAINING AND FREEZING 6

SEASON ON SOIL RESISTIVITY

3. ANALYSIS MODEL OF GROUNDING SYSTEM 9

4. INFLUENCES OF RAINING SEASON ON 12

SAFETY OF GROUNDING SYSTEMS

5 . INFLUENCES OF FREEZING SEASON ON 15

SAFETY OF GROUNDING SYSTEMS

6. MEASURES TO BE TAKEN 19

6.1 USE OF LONG VERTICAL GROUNDING ELECTRODES 19

6.2 THE CHEMICAL TREATMENT OF THE SOIL 19

7. CONCLUSION 22

8. REFERENCES 23