500 kv substation grounding presentation

Upload: mnotcool

Post on 03-Apr-2018

292 views

Category:

Documents


6 download

TRANSCRIPT

  • 7/28/2019 500 kv Substation Grounding presentation

    1/66

  • 7/28/2019 500 kv Substation Grounding presentation

    2/66

  • 7/28/2019 500 kv Substation Grounding presentation

    3/66

    Name: Roll No:Rabbia Khan 2010-EE-13

    Sidra Iqbal 2010-EE-17

    Anum Shafqat 2010-EE-49

  • 7/28/2019 500 kv Substation Grounding presentation

    4/66

    INTRODUCTION

  • 7/28/2019 500 kv Substation Grounding presentation

    5/66

    Definition:Earthing means a conducting connection by which an electric circuit or

    equipment is connected to the earth or some conducting body ofrelatively large extent that serves in place of the earth".

    Earthing means the connection of non-current carrying parts toground.

    Function:The function of an earthing system for an electrical installation can be

    split into three broad bands, To limit the potential of any part of an installation to a pre-determine

    value with respect to the general mass of earth.

    To permit the flow of current to earth.

    To ensure that, if a fault occurs, non-current carrying metal work

    associated with the equipment does not attain a dangerous potential

    with respect to the general mass of earth.

  • 7/28/2019 500 kv Substation Grounding presentation

    6/66

  • 7/28/2019 500 kv Substation Grounding presentation

    7/66

    Purpose of Earthing:Earthing system has 3 main purposes:

    1-Over voltage protection

    2-Voltage stabilization

    3-Currentt path in order to facilitate the operation of over

    current devices.

    Reasons:There are a number of good reasons of earthing but primary among

    them is to ensure personnel safety. A good earthing system willimprove the reliability of equipment and reduce the likelihood of

    damage as a result of lightning or fault currents.

  • 7/28/2019 500 kv Substation Grounding presentation

    8/66

    SAFETY:

    Main purpose of earthing is safety.

    That is the protection of:1. Personnel Safety

    2. Equipment Safety

    Personnel Safety:

    It is for human life safety.

    Personnel protection from electrical shocks, fire etc.

    Equipment Safety:

    It includes electrical circuit or equipment protection from

    failure, over current protection, fire, cable failures etc

  • 7/28/2019 500 kv Substation Grounding presentation

    9/66

    Grid Station Earthing:The sole purpose of substation grounding/earthing is to protect the

    equipment from surges and lightning strikes and to protect the

    operating persons in the substation.

    http://www.amper.com.tr/yukleme/Image/earthing_systems.jpg
  • 7/28/2019 500 kv Substation Grounding presentation

    10/66

    TYPES

  • 7/28/2019 500 kv Substation Grounding presentation

    11/66

    CLASSIFICATION OF EARTHINGEarthing can be classified into the following categories based on the

    purpose for which the part of the equipment connected to the general mass

    of earth.

    System Earthing

    Equipment Earthing

    SYSTEM EARTHINGEarthing associated with current carrying parts of the equipment is called system

    Earthing. The system security, reliability, performance, voltage stabilization, all

    relied only on the system Earthing. For example Earthing Neutral of

    Transformer, Surge arrester Earthing

    System Earthing Methods :

    a. Solid Earthing

    b. Resistance Earthing

    Solid EarthingThis type of grounding system is most commonly used in industrial and

    commercial power systems, where grounding conductors are connected to earth

    ground with no intentional added impedance in the circuit.

  • 7/28/2019 500 kv Substation Grounding presentation

    12/66

    Resistance EarthingIn resistance earthing the resistance is added along the earthing conductor to

    keep fault currents within limits. Thus protecting the insulation of the

    conductor.

    It has 2 types:

    Low resistance Earthing (voltages below 150V)

    High resistance Earthing (150-600V)

    EQUIPMENT EARTHINGEarthing associated with non-current carrying parts of Electrical Equipment

    are called as Equipment Earthing. Safety of operator, consumer, safety of

    their property are mainly based on Equipment Earthing.Eg.Body of the Transformer, Body of Motor

  • 7/28/2019 500 kv Substation Grounding presentation

    13/66

    EARTHING DESIGN

  • 7/28/2019 500 kv Substation Grounding presentation

    14/66

    Earthing DesignThe substation ground grid design is based on the substation layout

    plan. The following points serve as guidelines to start a earthinggrid design:

    The substation should surround the perimeter and take up as much

    area as possible. It reduces resistance of the earthing grid.Typically conductors are laid in parallel lines.Typical substation grid systems may include 4/0 bare copper

    conductor buried 0.3-0.5 m (12-18 in) below grade and spaced 3-7

    m (10-20 ft) apart in a grid pattern.All earth connections are to be made visible as far as possible.

  • 7/28/2019 500 kv Substation Grounding presentation

    15/66

    GROUND RODS (Electrodes)

    Materials are selected for

    corrosion resistance:

    Galvanized steel rods are

    cheap but have a relatively

    short service life

    Solid copper and stainless

    steel rods have a long service

    life but are considerably

    more expensive

    Copper bonded earth rods

    are less expensive than solid

    copper and can be deepdrivenComparison of life

    expectancy

  • 7/28/2019 500 kv Substation Grounding presentation

    16/66

  • 7/28/2019 500 kv Substation Grounding presentation

    17/66

    Earthing Conductors:

    The earthing conductor is commonly called the earthing lead. It

    joins the installation earthing terminal to the earth electrode or

    to the earth terminal provided by the Electricity Supply

    Company. It is a vital link in the protective system, so care must be taken

    to see that its integrity will be preserved at all times.

    Mostly copper is used for earthing conductors because it

    has the highest electrical conductivity of any of thecommercial metals. Copper is resistant to corrosion, that is,it will not rust. It is malleable, ductile and has long life.

  • 7/28/2019 500 kv Substation Grounding presentation

    18/66

    Earthing Conductors

  • 7/28/2019 500 kv Substation Grounding presentation

    19/66

    Types of earthing conductor

    Protective conductor Bonding concuctor

    Circuit Protective Conductor CPC

    This is a separate conductor installed with each circuit and is present toensure that some, or all, of the earth fault current will flow back to source

    along it.

    Bonding Conductor

    These ensure that exposed conductive parts (such as metal enclosures)

    remain at approximately the same potential during electrical faultconditions.

  • 7/28/2019 500 kv Substation Grounding presentation

    20/66

  • 7/28/2019 500 kv Substation Grounding presentation

    21/66

    Earth resistance:

    Earth Resistance is the resistance offered by the earth electrode to the

    flow of current in to the ground. The fault current is to be cleared as

    quickly as possible and this is done by having the earth resistancelow. Persons touching any of the non current carrying grounded parts

    shall not receive a dangerous shock during an earth fault. Each

    structure, transformer tank, body of equipment, etc, should be

    connected to earthing mat by their own earth connection.

    Generally lower earth resistance is preferable but for certainapplications following earth resistance are satisfactory

    In large power station - 0.5

    Major Substation above 110KV - 1.0

    Minor Substations Below 110KV - 2.0

  • 7/28/2019 500 kv Substation Grounding presentation

    22/66

    Monitoring the condition of earth

    For monitoring the healthiness of earth, the condition monitoring equipment

    used is EARTH MEGGER.

    The megger is a portable instrument used to measure resistance. It is used tomeasure very high resistance of the order of mega ohms.

    Checking and testing

    The Earthing systems are to be inspected regularly.

    Regular checking of joints and broken connections, if any and rectifying the

    same will prove to be of immense help in maintenance of earth grid and

    equipments.

    The condition of the electrodes, joints are also to be checked.

    Ifthe electrodes are corroded immediate

    steps for replacement are to be taken. The earth resistance is to be measured

    periodically.

  • 7/28/2019 500 kv Substation Grounding presentation

    23/66

  • 7/28/2019 500 kv Substation Grounding presentation

    24/66

    Earth Electrodes

    A conductor buried in the ground, used to maintain conductors

    connected to it at ground potential and dissipate current conducted

    to it into the earth, known as earth electrode; grounding electrode.

    Why must we have earth electrodes?

    The purpose of the earth electrode is to connect to the general mass

    of earth.The principle of earthing is to consider the general mass of

    earth as a reference (zero) potential. Thus, everything connecteddirectly to it will be at this zero potential.

    The effectiveness of an earth electrode in making good contact with

    the general mass of earth depends on factors such as soil type,

    moisture content, and so on. A permanently-wet situation may

    provide good contact with earth, but may also limit the life of theelectrode since corrosion is likely to be greater

  • 7/28/2019 500 kv Substation Grounding presentation

    25/66

    Earth electrode types

    Driven Rod

    Grounding Plates

    Electrolytic Electrode

    Driven Rod

    The standard driven rod or copper-cladrod consists of an 8 to 10 foot length of

    steel with a 5 to 10-ml coating of copper.This is by far the most commongrounding device used in the field today.

    Driven rods are relatively inexpensive topurchase, however ease of installation isdependent upon the type of soil and

    terrain where the rod is to be installed.The steel used in the manufacture of astandard driven rod tends to be relativelysoft.Purpose of copper on the rod is to

    provide corrosion protection for the steelunderneath.

  • 7/28/2019 500 kv Substation Grounding presentation

    26/66

    Grounding Plates

    Grounding plates are typically thin copper plates buried in direct

    contact with the earth. The National Electric Code requires that

    ground plates have at least 2 ft2 of surface area exposed to thesurrounding soil. Grounding plates should be buried at least 30

    inches below grade level. Non-ferrous materials (copper) need only

    be .060 inches thick. Grounding plates are typically placed under

    poles.

  • 7/28/2019 500 kv Substation Grounding presentation

    27/66

    Electrolytic Electrode

    The electrolytic electrode was specifically engineered to eliminate the

    drawbacks of other grounding electrodes. This active grounding

    electrode consists of a hollow copper shaft filled with natural earthsalts and desiccants whose hygroscopic nature draws moisture from

    the air. The moisture mixes with the salts to form an electrolytic

    solution that continuously seeps into the surrounding backfill material,

    keeping it moist and high in ionic content. The electrolytic electrode is

    installed into an augured hole and backfilled with a special highlyconductive product.

    The electrolytic solution and the special backfill

    material work together to provide a solid connection

    between the electrode and the surrounding soil that

    is free from the effects of temperature, environment,

    and corrosion

  • 7/28/2019 500 kv Substation Grounding presentation

    28/66

    Earthing ElectrodesA typical earthing electrode (left),

    consisting of a conductive rod driven

    into the ground

    Multiple Electrodes

  • 7/28/2019 500 kv Substation Grounding presentation

    29/66

  • 7/28/2019 500 kv Substation Grounding presentation

    30/66

    Soil Resistivity Soil resistivity is a measure of how much the soil resists the flow of

    electricity.

    It is a critical factor in design of systems that rely on passing current

    through the Earth's surface. An understanding of the soil resistivity and

    how it varies with depth in the soil is necessary to design thegrounding system in an electrical substation.

    In general there is some value above which the impedance of the earth

    connection must not rise, and some maximum step voltage which must

    not be exceeded to avoid endangering people and livestock.

  • 7/28/2019 500 kv Substation Grounding presentation

    31/66

    The soil resistivity value is subject to great variation, due to moisture,

    temperature and chemical content.

    Typical values are: Usual values: from 10 up to 1000 (m)

    Exceptional values: from 1 up to 10000 (m)

    SI unit of resistivity The SI unit of resistivity is the Ohm-meter (m); in the United States

    the Ohm-centimeter (cm) is often used instead.

    Measurement of soil resistivity

    Wenner method

    Schlumberger method

  • 7/28/2019 500 kv Substation Grounding presentation

    32/66

    Wenner method

    The Wenner method is one of the widely used methods for measuring soil

    resistivity.

    In this method, four test rods are inserted a short distance into the soil in a

    straight line with equal spacing between the probes. A test current is applied

    to the outer probes and the resulting potential difference between the inner

    probes, is measured.

    The potential difference divided by the test current give an apparent

    resistance in ohms. The apparent soil resistivity is obtained from the

    measured resistance.

  • 7/28/2019 500 kv Substation Grounding presentation

    33/66

    Using the Wenner method, the apparent soil resistivity value is:

    where

    E = measured apparent soil resistivity (m)

    a = electrode spacing (m)

    b = depth of the electrodes (m)

    RW = Wennerresistance measured as V/I in Figure ()

    If b is small compared to a, as is the case of probes penetrating the ground

    only for a short distance (as normally happens), the previous equation can

    be reduced to:

    E= 2aR

    S hl b h d

  • 7/28/2019 500 kv Substation Grounding presentation

    34/66

    Schlumberger method

    In the Schlumberger method the distance between the voltages probe is aand the distances from voltages probe and currents probe are c.

    Using the Schlumberger method, if b is small compared to a and c, andc>2a, the apparent soil resistivity value is:

    where

    E = measured apparent soil resistivity (m)

    a = electrode spacing (m)

    b = depth of the electrodes (m)

    c = electrode spacing (m)

    RS = Schlumberger resistance measured as V/I in Figure ()

  • 7/28/2019 500 kv Substation Grounding presentation

    35/66

    Measurement of soil resistivity

  • 7/28/2019 500 kv Substation Grounding presentation

    36/66

  • 7/28/2019 500 kv Substation Grounding presentation

    37/66

    EARTH MAT DESIGN

    Earthing System in a Sub Station comprises of Earth Mat or Grid,

    EarthElectrode, Earthing Conductor and Earth Connectors.

    Earth Mat or grid:

    Bonding all metal parts of the system to be earthed, the earth conductor andthe earth electrodes put all together form an Earth Grid.

    Primary requirement of Earthing is to have a low earth resistance.

    Substation involves many individual Electrodes, which will have fairly highresistance. But if these individual electrodes are inter linked inside the soil,

    it increases the area in contact with soil and creates number of parallel

    paths. Hence the value of the earth resistance in the interlinked state which

    is called combined earth value which will be much lower than the individual

    value.

    These Earth Mat and Earth electrode is connected to the equipment

    structures, neutral points for the purpose of Equipment earthing and neutral

    point earthing.It keeps the surface of substation equipment as nearly as

    absolute earth potential as possible.

  • 7/28/2019 500 kv Substation Grounding presentation

    38/66

    EARTH MAT

  • 7/28/2019 500 kv Substation Grounding presentation

    39/66

    Potential Hazards

  • 7/28/2019 500 kv Substation Grounding presentation

    40/66

    Potential Hazards In electrical engineering, earth potential rise (EPR) also

    called ground potential rise (GPR) occurs when a

    large current flows to earth. The potential relative to a distant point

    on the Earth is highest at the point where current enters the ground,

    and declines with distance from the source. Ground potential rise is

    a concern in the design of electrical substations because the high

    potential may be a hazard to people or equipment.

    The change of voltage over distance (potential gradient) may be so

    high that a person could be injured due to the voltage developed

    between two feet, or between the ground on which the person is

    standing and a metal object

  • 7/28/2019 500 kv Substation Grounding presentation

    41/66

    Electrical Shock Situations:There are three main electrical shock situations that can occur when a person is

    around a substation.

    foot-to-foot shockhand-to-feet shock

    hand-to-hand shock or metal-to-metal contact

  • 7/28/2019 500 kv Substation Grounding presentation

    42/66

    Step Potential:Step potential is the potential difference between the feet of a person

    standing on the floor of the substation, with 1m spacing between the feet

    (one step), through the flow of earth fault current through the grounding

    system.

  • 7/28/2019 500 kv Substation Grounding presentation

    43/66

    Touch Potential:Touch potential is a potential difference between the fingers of raised hand

    touching the faulted structure and the feet of the person standing on thesubstation floor. The Touch Potential should be very small.

  • 7/28/2019 500 kv Substation Grounding presentation

    44/66

    Point to be noted

    Tolerable touch potential of human body is less than tolerable

    step potential. Hence Touch potential is more critical for design while

    Step potential is usually academic.

    Step potential is independent of the diameter ( cross- section)

    of the earthing conductor.

    For 400% increase in diameter, reduction in Touch potential

    is only 35%.

    Thus cross- section has minor influence on Touch and Step

    potentials.

  • 7/28/2019 500 kv Substation Grounding presentation

    45/66

  • 7/28/2019 500 kv Substation Grounding presentation

    46/66

  • 7/28/2019 500 kv Substation Grounding presentation

    47/66

    Ensuring Proper Grounding

    The following steps, when put into practice, will

    ensure a reliable, safe and trouble-free substation

    grounding system:

    1. Size conductors for anticipated faults

    2. Use the right connections

    3. Ground rod selection

    4. Soil preparation5. Attention to step and touch potentials

  • 7/28/2019 500 kv Substation Grounding presentation

    48/66

    1-Size Conductors For Anticipated Faults

    Conductors must be large enough to handle any anticipated

    faults without fusing (melting).Failure to use proper fault time

    in design calculations creates a high risk of melted conductors.

    For example, a AWG conductor can withstand 42,700A for 0.5

    sec before fusing. However, this same conductor can withstand

    only 13,500A for 5 sec.

    Two aspects govern the choice of conductor size: the first is the

    fault current that will flow through the conductor and the

    second is the time for which it can flow.The IEEE 80 suggests using a time of 3.0 s for the design of

    small substations.

  • 7/28/2019 500 kv Substation Grounding presentation

    49/66

  • 7/28/2019 500 kv Substation Grounding presentation

    50/66

    2. Use the Right ConnectionsGrounding Connections, Resistance Test and Bonding Test

    It is very evident that the connections between conductors and the

    main grid and between the conductor and ground rods are asimportant as the conductors themselves in maintaining a permanentlow-resistance path to ground.

    Connections must maintain the integrity of the conductor and thesystem as a whole for up to 40 years.

    They must be of an appropriate material and mass to:

    carry prospective fault currents

    be able to resist corrosion

    maintain original low resistance

    The basic issues here are: The type of bond used for the

    connection of the conductor in its run,

    with the ground grid and with the ground rod.

  • 7/28/2019 500 kv Substation Grounding presentation

    51/66

    The temperature limits, which a joint can withstand.

    The most frequently used grounding connections are mechanical

    pressure type. Pressure-type connections produce a mechanical bond between

    conductor and connector by means of a tightened bolt-nut or by

    crimping using hydraulic or mechanical pressure.

    On the other hand, the exothermic process fuses the conductor endstogether to form a molecular bond between all strands of the

    conductor.

    Temperature limits are stated in standards such as IEEE 80 and IEEE

    837 for different types of joints based on the joint resistance

    normally obtainable with each type. Exceeding these temperaturesduring flow of fault currents may result in damage to the joint and

    cause the joint resistance to increase, which will result in further

    overheating.

  • 7/28/2019 500 kv Substation Grounding presentation

    52/66

  • 7/28/2019 500 kv Substation Grounding presentation

    53/66

  • 7/28/2019 500 kv Substation Grounding presentation

    54/66

  • 7/28/2019 500 kv Substation Grounding presentation

    55/66

    3. Ground Rod Selection

    In MV and HV substations, where the source and load are connected

    through long overhead lines, it often happens that the ground fault current

    has no metallic path and has to flow through the groundmass (earth). This

    means that the ground rods of both source and load side substations have to

    carry this current to or from the groundmass.

    The ground rod system should be adequate to carry this current and ground

    resistance of the grounding system assumes importance.

    The length, number and placement of ground rods affect the resistance of

    the path to earth. Doubling of ground rod length reduces resistance by a

    value of 45%, under uniform soil conditions. Usually, soil conditions are not

    uniform and it is vital to obtain accurate data by measuring ground rod

    resistance with appropriate instruments.

  • 7/28/2019 500 kv Substation Grounding presentation

    56/66

    For maximum efficiency, grounding rods should be placed no closer

    together than the length of the rod. Normally, this is 10 ft (3 m).

    It should be noted that as the number of rods is increased, thereduction of ground resistance is not in inverse proportion. Twenty

    rods do not result in 1/20th of the resistance of a single rod but only

    reduce it by a factor of 1/10th.

    For economic reasons, there is a limit to the maximum distance

    between rods.

    Normally, this limit is taken as 6 m. At more than 6 m, the cost of

    additional conductor needed to connect the rods.

  • 7/28/2019 500 kv Substation Grounding presentation

    57/66

  • 7/28/2019 500 kv Substation Grounding presentation

    58/66

  • 7/28/2019 500 kv Substation Grounding presentation

    59/66

    4. Soil Preparation

    Soil resistivity is an important consideration in substation grounding system

    design. The lower the resistivity, the easier it is to get a good groundresistance.

    Areas of high soil resistivity and those with ground frost need special

    consideration. The highest ground resistivity during the annual weather

    cycle should form the basis of the design since the same soil will have much

    higher resistivity during dry weather when percentage of moisture in theground becomes very low.

    One approach to take care of this problem is to use deep driven ground rods

    so that they are in contact with the soil zone deep enough to remain

    unaffected by surface climate.

    The other approach is to treat the soil around the ground rod with chemicalsubstances that have the capacity to absorb atmospheric/soil moisture.

    Use of chemical rods is one such solution

  • 7/28/2019 500 kv Substation Grounding presentation

    60/66

  • 7/28/2019 500 kv Substation Grounding presentation

    61/66

  • 7/28/2019 500 kv Substation Grounding presentation

    62/66

    5. Attention to Step and Touch Potentials

    Limiting step and touch potential to safe values in a substation is vital topersonnel safety.

    Step potential is the voltage difference between a persons feet and is causedby the voltage gradient in the soil. The potential gradient is steepest near thefault location and thereafter reduces gradually.

    Touch potential represents the same basic hazard, except the potential exists

    between the persons hand and his or her feet. This happens when a personstanding on the ground touches a structure of the substation, which isconducting the fault current into ground .

    In both situations, the potential can essentially be greatly reduced by anequipotential wire mesh safety mat installed.

    Such an equipotential mesh will equalize the voltage along the workers pathand between the equipment and his or her feet. With the voltage difference(potential) thus essentially eliminated, the safety of personnel is virtuallyguaranteed.

    To ensure continuity across the mesh, all wire crossings are brazed with a 35%silver alloy. Interconnections between sections of mesh should be made so as

    to provide a permanent low-resistance high-integrity connection.

  • 7/28/2019 500 kv Substation Grounding presentation

    63/66

  • 7/28/2019 500 kv Substation Grounding presentation

    64/66

    CONCLUSION

  • 7/28/2019 500 kv Substation Grounding presentation

    65/66

    CONCLUSION:

    For good earthing following considerations must befollowed:

    Size conductors

    Selection of right connector

    Pay attention to ground rod length, number, placement, andspacing

    Prepare the soil

    Eliminate step and touch potential

    Ground the foundation

    Ground all disconnects switch handles

    Ground all surge arrestors

    Pay attention to temporary grounding

  • 7/28/2019 500 kv Substation Grounding presentation

    66/66