Substation Grounding- Sahadeo Latchmepersad, T&TEC 1
T&T SubsectionLocal IAS Chapter
GROUNDING-DESIGN AND CONSTRUCTIONSaturday 12th November 2005
Presented by
Eng. Sahadeo Latchmepersad, MIEEE, MAPETT, R. Eng.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 2
ACKNOWLEDGEMENT
The Trinidad and Tobago Electricity Commission
Substation Grounding- Sahadeo Latchmepersad, T&TEC 3
Range of Large Industrial Customers
Rate D3- 4-25 MVA at 33, 66 or 132 kV
Rate E > 25 MVA at 66 or 132kV
Substation Grounding- Sahadeo Latchmepersad, T&TEC 4
Substation Grounding- Sahadeo Latchmepersad, T&TEC 5
Transmission
B.C/Union Estate Schematic
Substation Grounding- Sahadeo Latchmepersad, T&TEC 6
Objectives of Grounding
To provide means to carry electric currents to earth under normal and fault conductors without exceeding any operating and equipment limits or adversely affecting continuity of service.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 7
Objectives of Grounding-
To ensure that a person in the vicinity of grounded facilities is not exposed to the danger of critical electric shock.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 8
Basic Shock Situations
Substation Grounding- Sahadeo Latchmepersad, T&TEC 9
BRIGHTON 66kV SUBSTATION
Substation Grounding- Sahadeo Latchmepersad, T&TEC 10
Ventricular Fibrillation
The most dangerous consequence of electric current passing through the vital parts of a human body is a heart condition – ventricular fibrillation –immediate arrest of blood circulation.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 11
Design Algorithm
Substation Grounding- Sahadeo Latchmepersad, T&TEC 12
Measuring Soil Resistivity
Procedure depends on the instrument
Substation Grounding- Sahadeo Latchmepersad, T&TEC 13
Substation Grounding- Sahadeo Latchmepersad, T&TEC 14
Soil Resistivity Calculation
ρ = 2 x Pi x a x RWhere R is Maximum measured Value
Substation Grounding- Sahadeo Latchmepersad, T&TEC 15
Tolerable Step Voltage
Step Voltage Limit 50 kgE Step 50 = (1000 + 6 Cs ρs) 0.116
√ts
E Step 70 = (1000 + 6 Cs ρs) 0.157√ts
Substation Grounding- Sahadeo Latchmepersad, T&TEC 16
Tolerable Touch Voltage Limit
E touch50 = (1000 + 1.5 Cs ρs) 0.116√ts
E touch70 = (1000 + 1.5 Cs ρs) 0.157√ts
Substation Grounding- Sahadeo Latchmepersad, T&TEC 17
Constants
Cs = 1 – [0.09 (1 - ρ/ ρ s)][2 hs + 0.09]
ρ = soil resitivityρ s = surface layer resistivityTs = duration of shock current in seconds including clearance time of circuit breaker plus relay
Substation Grounding- Sahadeo Latchmepersad, T&TEC 18
Conductor Sizing
I = Amm2 [TCAP.10-4] Ln Ko + Tm
[tc αr ρr] Ko + Ta
Substation Grounding- Sahadeo Latchmepersad, T&TEC 19
Grid Resistance
burial of depth theish conductor oflength total theis
/20111
2011
T
Tg
LyresistivitsoiltheisWhere
AhALR
ρ
ρ
+
++=
Substation Grounding- Sahadeo Latchmepersad, T&TEC 20
Substation Grounding- Sahadeo Latchmepersad, T&TEC 21
Calculated Step Voltage
Es = ρKs Ki IGLs
Ls = 0.75Lc + 0.85 LR
Substation Grounding- Sahadeo Latchmepersad, T&TEC 22
Calculated Mesh Voltage
Em = ρ Km Ki IG WhereLM
Lm = Lc + 1.55 +1.22 Lr LR
LX2 + Ly
2
LR = total length of ground rodsLc = length of conductor
Substation Grounding- Sahadeo Latchmepersad, T&TEC 23
Earthing Designs
Nitrogen 2000 66kV Substation
Substation Grounding- Sahadeo Latchmepersad, T&TEC 24
Output file
Nitrogen 2000 substation
Substation Grounding- Sahadeo Latchmepersad, T&TEC 25
Exothermic Joints
Step 1Position clean, dry cables in mold and close clamp.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 26
Insert disk, insert pour weld metal and starter material into crucible, and ignite to
form the weld.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 27
Remove finished connection. Clean mold
Substation Grounding- Sahadeo Latchmepersad, T&TEC 28
FENCE EARTHING
1. Inclusion of the fence within the ground grid area. Under this philosophy, the perimeter conductor of the grid will parallel the fence at a short distance of 1.0m outside. The crushed rock covering will also be required outside the fence.
Substation Grounding- Sahadeo Latchmepersad, T&TEC 29
FENCE EARTHING
2. Placement of the fence outside the ground grid area with close electric coupling between fence and adjacent earth along its length, but with no electrical tie between the fence and the main station grid
Substation Grounding- Sahadeo Latchmepersad, T&TEC 30
ANSI STANDARD 80-2000 Date: November 11, 2005Date:
Line-to-line Voltage V 66000 Volts Touch voltage limit E touch 70 1792 VoltsMaximum fault curent HV side 20000 Amps Step voltage limit E step 70 5678 VoltsMaximum Fault Current LV side 20000 AmpsSoil resistivity ρ 15 Ωm Touch voltage limit E touch 50 1324 VoltsSubstation Length L 34 metre Step voltage limit E step 50 4195 VoltsSubstation Width W 30 metreSpacing D 4 metre GPR = 4944 VoltsNumber of ground rods 28 Ea Em= 606 VoltsLength of ground rod 2.44 metres Es= 619 VoltsDepth of grid burial h 0.5 metresFault Duration tf 0.1 s Length of 4/0 Copper Required 574 metresCurrent Division Factor Sf 1 Size of Copper d = 0.01 metresX/R Ratio 7.20 No. of Copper Rods 28 EaCrushed Rock Resistivity ρs 2500 ΩmAmbient temp Ta 40 oC Grid Resistance 0.23 ΩThickness of crushed rock hs 0.102 metresGrid shape (Square=S, Rect.=R, L- shaped=L) rSubstation L-shape Length l 0 metreSubstation L-shape width w 0 metre
50kg Design O.K70kg Design O.K
INPUT DATA RESULTST&TEC Grounding Program
Substation Grounding- Sahadeo Latchmepersad, T&TEC 31
Development Program
Substation Grounding- Sahadeo Latchmepersad, T&TEC 32
AutoGrid Pro
Substation Grounding- Sahadeo Latchmepersad, T&TEC 33
Connection to Customer’s Substation
Fence eathingNumber of TailsIncreased area-lower RgIncreased amount of copper
Substation Grounding- Sahadeo Latchmepersad, T&TEC 34
The End
Questions?