part 5 – indoor environmental qualityrachel-carson.arc.cmu.edu/uploads/singapore_ieq.pdf · part...
TRANSCRIPT
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
PART 5 – INDOOR ENVIRONMENTAL QUALITY
SGIEQP1// MINIMUM INDOOR AIR QUALITY PERFORMANCE
(Pre-Requisites/LEED V4)
Background No pre‑requisite was specified fro GreenMark standard, Singapore has its own code of practice for
Indoor air Quality for Air Conditioned Buildings, SS 554:2009, which also includes specification for
indoor and outdoor air supply quality. The code of practice was adopted from ASHRAE 62.1 and
therefore is very similar to the stated pre‑requisites in LEED 4.0. With its stringent rule and
enforcement, Singapore has maintained the code of law very effectively. Nevertheless, GreenPlan
adopted a minimum Indoor Air Quality Performance pre‑requisite to further boost and raise the
awareness of the importance of air quality performance.
Objectives
To contribute to the comfort and well‑being of building occupants by establishing minimum standards for Indoor
Air Quality (IAQ).
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
Requirement
Mechanically Ventilated Spaces
For mechanically ventilated spaces (and for mixed‑mode systems when the mechanical ventilation is
activated), determine the minimum outdoor air intake flow for mechanical ventilation systems using
the ventilation rate procedure from ASHRAE 62.1–2010 or a local equivalent, whichever is more
stringent.
Option 1. ASHRAE Standard 62.1–2010 or SS 553 : 2009
Meet the minimum requirements of ASHRAE Standard 62.1–2010, Sections 4–7, Ventilation for Acceptable
Indoor Air Quality (with errata), or a local equivalent, such as SS 553:2009, whichever is more stringent.
Option 2. CEN Standards EN 15251–2007 and EN 13779–2007
Meet the minimum requirements of Annex B of Comité Européen de Normalisation (CEN) Standard
EN 15251–2007, Indoor environmental input parameters for design and assessment of energy
performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics;
and the requirements of CEN Standard EN 13779–2007, Ventilation for nonresidential buildings,
Performance requirements for ventilation and room conditioning systems, excluding Section 7.3,
Thermal environment; 7.6, Acoustic environment; A.16; and A.17.
Mechanically Ventilated Spaces Monitoring
For mechanically ventilated spaces (and for mixed‑mode systems when the mechanical ventilation is
activated), monitor outdoor air intake flow as follows:
• For variable air volume systems, provide a direct outdoor airflow measurement device capable
of measuring the minimum outdoor air intake flow. This device must measure the minimum
outdoor air intake flow with an accuracy of +/–10% of the design minimum outdoor airflow
rate, as defined by the ventilation requirements above. An alarm must indicate when the
outdoor airflow value varies by 15% or more from the outdoor airflow setpoint.
• For constant‑volume systems, balance outdoor airflow to the design minimum outdoor airflow
rate defined by ASHRAE Standard 62.1–2010 (with errata but without addenda2), or higher.
Install a current transducer on the supply fan, an airflow switch, or similar monitoring device.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
Naturally Ventilated Spaces
For naturally ventilated spaces (and for mixed‑mode systems when the mechanical ventilation is
inactivated), determine the minimum outdoor air opening and space configuration requirements using
the natural ventilation procedure from ASHRAE Standard 62.1–2010 or a local equivalent, whichever is
more stringent. Confirm that natural ventilation is an effective strategy for the project by following the
flow diagram in the Chartered Institution of Building Services Engineers (CIBSE) Applications Manual
AM10, March 2005, Natural Ventilation in Nondomestic Buildings, Figure 2.8, and meet the requirements of
ASHRAE Standard 62.1–2010, Section 4, or a local equivalent, whichever is more stringent.
Naturally Ventilated Spaces Monitoring
For naturally ventilated spaces (and for mixed‑mode systems when the mechanical ventilation is
inactivated), comply with at least one of the following strategies.
• Provide a direct exhaust airflow measurement device capable of measuring the exhaust airflow.
This device must measure the exhaust airflow with an accuracy of +/–10% of the design
minimum exhaust airflow rate. An alarm must indicate when airflow values vary by 15% or
more from the exhaust airflow setpoint.
• Monitor carbon dioxide (CO2) concentrations within each thermal zone. CO2 monitors must be
between 3 and 6 feet (90 and 180 centimeters) above the floor and within the thermal zone. CO2
monitors must have an audible or visual indicator or alert the building automation system if the
sensed CO2 concentration exceeds the setpoint by more than 10%. Calculate appropriate CO2
setpoints using the methods in ASHRAE 62.1–2010, Appendix C.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SGIEQ5.1// THERMAL COMFORT
(BEAM Plus for New Buildings 2012/LEED V4/GreenMark 2013)
Reason Given Singapore’s hot and humid climate and high average annual insolation levels of 1,150
kWh/kWp/year (about 50% more solar radiation than temperate climates) (NEA , EMA 2010), air
conditioning is typically functional in commercial buildings during the day to maintain occupancy
thermal comfort. However, the current green building standard (GreenMark 4.0) allocates points as
long as the indoor operative temperature is between 24°C to 26°C and relative humidity is less than
65%. Thermal comfort however is not only dependent on these parameters but on a wide variety of
other factors (ASHRAE Standard 55, 2010). In addition, studies in Singapore have shown Singaporeans
to find an operative temperature range of 26.3 – 31.7°C to be acceptable in outdoor spaces (Yang, Wong
et al. 2013), indicating thermal adaptability to the warmer climate. In addition, the study also showed
respondents in air‑conditioned spaces to have higher thermal sensation votes than those in naturally
ventilated spaces for the same temperature. To ensure occupant thermal comfort is accurately
accounted for, it is imperative that thermal comfort indices be tailored to fit spaces depending on
whether the space is conditioned or naturally ventilated.
Objectives
To promote occupants’ productivity, comfort, and well‑being by providing quality thermal comfort
measured through appropriate metrics.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
Rating System
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SGIEQ5.2// ACOUSTIC PERFORMANCE
(BEAM Plus for New Buildings 2012/LEED V4/GreenMark 2013)
Reason Due to the high building density in Singapore (Phua, Goh et al. 2012) and limit on plot ratio (defined as
Gross Floor Area / Site Area) placed on buildings in Singapore (URA), indoor acoustical performance
can be easily affected by noise from outside environment since these regulations causes buildings to
located close to roads and adjacent buildings. Together with internal noise typically generated by
building services equipment such as decentralized air conditioning and mechanical systems, they may
affect occupant well‑being and communication by decreasing speech intelligibility.
Objectives
To provide workspaces and classrooms that promote occupants’ well‑being, productivity, and
communications through effective acoustic design, improving acoustical properties of rooms where
speech intelligibility is important.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
Rating System
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SGIEQ5.3// INDOOR AIR POLLUTANTS
(LEED V4/GreenMark 2013)
Reason According to a recent 2012 survey of
multiple office buildings in Singapore,
the effect of Indoor Air Quality (IAQ)
not only potentially affect the property
value by 1.28% to 3.85% but majority of
both tenants and owners agree that IAQ
has an impact on both health and
productivity (Addae‑Dapaah 2012).
Objectives
To establish better quality indoor air in the building after construction and during occupancy.
Rating System
Rating is based on performance‑based criteria. Client is responsible of the products that are potential
emitters or absorbers (e.g. furniture, cleaning products, indoor plants etc. Requirement must be met.
Refer to next page.
The Table on the left illustrates the air
quality standards for the Air Testing
Accreditation.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SGIEQ5.4//
INTERIOR LIGHTING
(LEED V4)
Reason
High performance interior lighting
has been to proven to increase health
and productivity in many studies
(Küller & Laike 1998, Wilkins et al.
1989, etc.). Aside from the benefits of
the building occupants, interior
lighting is also one of the major
industries in Singapore (Ministry of
Communication and Information
2002). The high number of interior
design establishments has a great
influence in the current standards of
interior lighting and therefore
becomes vital in building
performance. Last but not least,
according to a survey on multiple
office building in Singapore, Lighting
system made up of approximately
11.79% of total building consumption
(Lee et al. 2004). This number can be
significantly reduced with better and
more effective interior lighting design.
Objectives
To promote occupants’ productivity, comfort, and well‑being by providing high‑performance lighting.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
Rating System
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SGIEQ5.5// DAYLIGHTING
(LEED V4)
Reason Singapore has great daylight opportunity that
potentially becomes great alternative to electric
lighting. With almost 4423 hours of daylight in a
year and a daily average of 12 hours of daylight
between 6am to 6pm, the country can utilize it to
not only generate power but also provide natural
lighting to major offices and commercial
buildings. Additionally its equatorial
geographical location also provides ease for
daylighting, as building orientation is almost a
negligible factor to the amount of daylight that
penetrates through. Proper glazing and shading
system should be selected to avoid overheating.
Daylighting has been proven to increase
occupant’s health and productivity (Heschong et
al 2002).
Objectives
To provide workspaces and classrooms that promote occupants’ well‑being, productivity, and
communications through effective acoustic design, improving acoustical properties of rooms where
speech intelligibility is important.
Rating System
Refer to next page.
The Table on the left illustrates the
months where illuminance
measurement should take place. Refer
to Measurement accreditation below.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SGIEQ5.6// CONSTRUCTION IAQ MANAGEMENT PLAN
(LEED V4)
Reason Singapore new building construction rate has tripled since 2005. With the amount of construction
happening, it is important that construction IAQ management is maintained for both contractors and
neighboring occupants. Although the National Environmental Agency (NEA) controls noise level and
pollution standard, no standard can be found to maintain the IAQ for occupants during construction.
The adaptation of the standard will help improve health and productivity of occupants, thus increasing
speed of construction and economic benefits.
Objectives
To promote the well‑being of construction workers and building occupants by minimizing indoor air
quality problems associated with construction and renovation.
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
Rating System
FALL 2013// 48795 A2// LEED: Green Design
& Building Rating in a Global Context SINGAPORE GREENPLAN RATING SYSTEM
SUMMARY OF INDOOR ENVIRONMENTAL QUALITY
PART 5 INDOOR ENVIRONMENTAL QUALITY POSSIBLE POINTS
SGIEQ 5‐1 THERMAL COMFORT 1
SGIEQ 5‐2 ACOUSTIC PERFORMANCE 5
SGIEQ 5‐3 INDOOR AIR POLLUTANTS 3
SGIEQ 5‐4 INTERIOR LIGHTING 5
SGIEQ 5‐5 DAYLIGHTING 6
SGIEQ 5‐6 CONSTRUCTION IAQ MANAGEMENT PLAN 1
Total 21
The indoor environmental quality from Greenmark 2013 seems to have a less stringent
standard in comparison to LEED 4.0; GreenPlan therefore decides to increase its current
standard by adopting most standard from the latter. Improvements in standard includes the
focus in high performance quality interior lighting instead of high frequency ballast, and the
consideration of natural ventilation versus mechanically condition thermal comfort standard.
Greenplan also includes daylighting and construction IAQ management plan in the new IEQ
standards to improve occupant’s health and productivity.
Singapore’s IEQ is mostly set by the National Environmental Agency, an organization
responsible for environmental safety and comfort of occupants. NEA not only ensures
allowable noise level from both construction and buildings, but also manages pollutants from
both indoor and outdoor sources (as mentioned in SS 554:2009). GreenPlan decides to omit
some pre-requisites from LEED 4.0, such as cigarette smoking due to its stringent law and
extremely expensive taxes that are implemented. Other omission includes low-emitting interior,
as VOC levels are designed to be performance-based, consequently allow for greater
flexibility for designers and challenge for newer innovation to reduce harmful particulate-
emitting furniture.
According to 2012 World Health Organization (WHO)
data, Singapore’s annual mean ppm10 is
approximately 32, which is considered to be good.
Additionally, all other primary pollutants such as NOx,
SOx, and CO2 have been maintained under the WHO
standards. GreenPlan plans to not only maintain but
also reduce all the pollutants, which in effect helps
increase the indoor-outdoor relationship, allowing for
healthier and productive occupants.