natvent bre energy efficient office of the future presentation of the building presentation of the...
TRANSCRIPT
NatVent
BRE Energy Efficient Office of the Future
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Building presentation (1...)
The building was designed by Architects Fielden Clegg Design.
The building has three storeys in two blocks connected by an atrium at the west wall of the building. The main axis is running east-west.
The ground and first floor contain open plan and cellular offices. The second floor is a large open plan office.
On the ground floor there is a large lecture theatre to the north. This is connected to the main building by a circulating zone containing toilets and a display area.
The building was designed by Architects Fielden Clegg Design.
The building has three storeys in two blocks connected by an atrium at the west wall of the building. The main axis is running east-west.
The ground and first floor contain open plan and cellular offices. The second floor is a large open plan office.
On the ground floor there is a large lecture theatre to the north. This is connected to the main building by a circulating zone containing toilets and a display area.
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Building presentation (2|)
NLecture theatre
Plan view of ground floorPlan view of ground floor
Atrium
Circ
ula
tion
zo
ne
Main building
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
The Design Issue The design brief called for ‘outstanding energy performance’. The
Performance Specification, a key element of the building brief, dictates performance targets for energy consumption and carbon dioxide (CO2 ) emissions. The targets (47 kWh/m² for gas - 36 kWh/m² for electricity - 34 kg/m² CO2 emission) represent a 30% improvement on current best practice and were to be met by:
avoiding or minimising the use of air-conditioning maximising the benefits of the building fabric in terms of reducing the heating and
cooling loads minimising the use of artificial lighting while actively exploiting daylight applying the appropriate level of automatic and user control
However, energy efficiency is only acceptable within the parameters of a comfortable and healthy working environment. The internal design conditions for thermal comfort were:
For winter: 18°C minimum internal temperature For summer:
– 25°C is not to be exceeded for more than 5% and – 28°C is not to be exceeded for more than 1% of the year
The design brief called for ‘outstanding energy performance’. The Performance Specification, a key element of the building brief, dictates performance targets for energy consumption and carbon dioxide (CO2 ) emissions. The targets (47 kWh/m² for gas - 36 kWh/m² for electricity - 34 kg/m² CO2 emission) represent a 30% improvement on current best practice and were to be met by:
avoiding or minimising the use of air-conditioning maximising the benefits of the building fabric in terms of reducing the heating and
cooling loads minimising the use of artificial lighting while actively exploiting daylight applying the appropriate level of automatic and user control
However, energy efficiency is only acceptable within the parameters of a comfortable and healthy working environment. The internal design conditions for thermal comfort were:
For winter: 18°C minimum internal temperature For summer:
– 25°C is not to be exceeded for more than 5% and – 28°C is not to be exceeded for more than 1% of the year
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
The building concept (1...) natural ventilation
Natural ventilation has been utilised to minimise the use of fans.
The ground and 1st floors are stack driven using solar towers on the southern façade. The 2nd floor has cross ventilation via openable windows. (see next slides..)
Voids in the ceiling slab act as ducts bringing air in from outside and exhausting air out to ventilation stacks.
Natural ventilation has been utilised to minimise the use of fans.
The ground and 1st floors are stack driven using solar towers on the southern façade. The 2nd floor has cross ventilation via openable windows. (see next slides..)
Voids in the ceiling slab act as ducts bringing air in from outside and exhausting air out to ventilation stacks.
Natural ventilation is used to: Improve the thermal comfort:
Intensive (night) ventilation can be applied to cool down the thermal mass (exposed ceilings) of the building.
Control the IAQ:
The occupants can open windows to control the IAQ
Natural ventilation is used to: Improve the thermal comfort:
Intensive (night) ventilation can be applied to cool down the thermal mass (exposed ceilings) of the building.
Control the IAQ:
The occupants can open windows to control the IAQ
exposed ceilingsexposed ceilings
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
The building concept (2...) ventilation strategy
Voids in the ceiling slabVoids in the ceiling slab
Stack ventilation on hot still summer’s day
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
The building concept (3...) ventilation strategy
Cross ventilation on windy summer’s day
Many ventilation openings are automatically
controlled. However can override the
automatic settings for windows
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
The building concept (4|) shading and lighting
Solar gains are reduced by moveable external louvres on the South side of the building. These louvres improve the thermal summer comfort, but also control glare while still allowing daylight.
A fully integrated, intelligent and efficient lighting system has been installed which automatically compensates for daylight levels and occupancy, controlling each light separately. In this way the internal gains of lighting are minimised and linked to the available daylight. Reducing the internal gains of lighting is an important step toward summer comfort in office buildings.
Solar gains are reduced by moveable external louvres on the South side of the building. These louvres improve the thermal summer comfort, but also control glare while still allowing daylight.
A fully integrated, intelligent and efficient lighting system has been installed which automatically compensates for daylight levels and occupancy, controlling each light separately. In this way the internal gains of lighting are minimised and linked to the available daylight. Reducing the internal gains of lighting is an important step toward summer comfort in office buildings.
Lighting: control sensor
Lighting: control sensor
External louvres
External louvres
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Monitoring the building The building was
monitored in summer and winter.
Two rooms on the 1st floor were monitored. The rooms were used normally by occupant.
Night cooling was utilised during the summer months.
The building was monitored in summer and winter.
Two rooms on the 1st floor were monitored. The rooms were used normally by occupant.
Night cooling was utilised during the summer months.
Room 1 Room 2
Open plan
Ventilation stacks
Corridor zone
AtriumN
The following parameters were measured: Internal and external CO2 concentration as an indicator of IAQ. Fresh air flow rates and local wind speed and direction. External air and internal air and globe temperatures.
The following parameters were measured: Internal and external CO2 concentration as an indicator of IAQ. Fresh air flow rates and local wind speed and direction. External air and internal air and globe temperatures.
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Winter monitoring (1...) air change rates
Air change rates are similar in both rooms. Higher ventilation rates coincide with periods of occupancy. There is some correlation of air change rate with wind speed and direction. Air change rates were adequate in both rooms: the CO2 -concentrations are not too
high (see next slide) and the air supply is almost zero outside the office hours (reduction of ventilation losses).
Air change rates are similar in both rooms. Higher ventilation rates coincide with periods of occupancy. There is some correlation of air change rate with wind speed and direction. Air change rates were adequate in both rooms: the CO2 -concentrations are not too
high (see next slide) and the air supply is almost zero outside the office hours (reduction of ventilation losses).
Winter, air change rate in the monitored rooms.
0
1
2
3
4
5
6
7
8
9
10
15:001/8/98
19:001/12/98
23:0016/01/1998
3:0021/01/1998
7:0025/01/1998
11:0029/01/1998
Date/Time
Air
ch
ang
e ra
te (
1/h
)
Room 2 ach
Room 1 ach
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
CO2 concentrations are generally below the limit of 1200 ppm. The IAQ is acceptable
Increased levels of CO2 coincide with occupancy.
CO2 concentrations are generally below the limit of 1200 ppm. The IAQ is acceptable
Increased levels of CO2 coincide with occupancy.
Winter monitoring (2...) CO2-concentrations
Winter, carbon dioxide concentration in the monitored rooms.
0
200
400
600
800
1000
1200
1400
1600
15:001/8/98
19:001/12/98
23:0016/01/1998
3:0021/01/1998
7:0025/01/1998
11:0029/01/1998
Date/Time
Car
bo
n d
ioxi
de
(pp
m)
External CO2
Room 2 CO2
Room 1 CO2
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Temperatures were between 2 to 5oC above the design minimum temperature (18°C).
There was little difference between air and globe temperatures.
Temperatures were between 2 to 5oC above the design minimum temperature (18°C).
There was little difference between air and globe temperatures.
Winter monitoring (3|) temperatures
air and globe temperatures in the monitored rooms.
-5
0
5
10
15
20
25
15:38:2614/01/98
23:38:2617/01/98
7:38:2621/01/98
16:29:2824/01/98
0:29:2828/01/98
Date/Time
Tem
per
atu
re (
deg
C) Room 1 globe temp
Room 2 globe temp
External temp
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Air change rates in room 1 were higher than those in room 2, possibly due to poor mixing as a result of opening windows.
Again higher ventilation rates coincide with occupancy. Air change rates were adequate during occupied periods. Both offices were closed and locked at night and so did not benefit from night
ventilation.
Air change rates in room 1 were higher than those in room 2, possibly due to poor mixing as a result of opening windows.
Again higher ventilation rates coincide with occupancy. Air change rates were adequate during occupied periods. Both offices were closed and locked at night and so did not benefit from night
ventilation.
Summer monitoring (1...) air change rates
air change rates in the monitored offices.
-10
-5
0
5
10
15
20
25
30
31/7/97 15:24 2/8/97 17:19 6/8/97 13:53 8/8/97 15:57 10/8/97 17:52 13/8/97 10:22 15/8/97 12:26
Date/Time
Air
Ch
ang
e R
ate
(1/h
)
Room 1
Room 2
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Summer monitoring (2...) CO2-concentrations
CO2 concentrations were generally below 1000 ppm. The IAQ is acceptable CO2 concentrations were generally below 1000 ppm. The IAQ is acceptable
carbon dioxide concentrations in monitored rooms.
0
300
600
900
31/7/97 15:21 2/8/97 17:16 6/8/97 13:50 8/8/97 15:54 10/8/97 17:49 13/8/97 10:19 15/8/97 12:23
Date/Time
Car
bo
n d
ioxi
de
con
cen
trat
ion
(p
pm
)
ExternalRoom 1Room 2
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
The 28°C design maximum temperature was not exceeded. The 25°C lower design temperature was exceeded on some occasions.
The 28°C design maximum temperature was not exceeded. The 25°C lower design temperature was exceeded on some occasions.
Summer monitoring (3|) temperatures
air temperatures in the monitored rooms.
10
12
14
16
18
20
22
24
26
28
30
31/7/97 16 2/8/97 08 4/8/97 00 7/8/97 10 9/8/97 02 10/8/97 18 12/8/97 10 14/8/97 17
Date/Time
Air
Tem
per
atu
re (
deg
C)
External air tempsRoom 1 air temps
Room 2 air temps
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Conclusions (1...)
Winter Indoor Climate: Adequate ventilation is provided. Internal air quality is acceptable. Comfortable internal temperatures are achieved.
Summer Indoor Climate Adequate ventilation is provided. Comfortable temperatures are maintained though the lower design
temperature was sometimes exceeded during warm spells.
The building has external louvres to reduce the solar gains. Moreover, the building makes use of night cooling. Cooler night time air is drawn in via the openable windows and ceiling voids. Fans in the ventilation towers can be used to assist purging. Ground water cooling can also be used.
Winter Indoor Climate: Adequate ventilation is provided. Internal air quality is acceptable. Comfortable internal temperatures are achieved.
Summer Indoor Climate Adequate ventilation is provided. Comfortable temperatures are maintained though the lower design
temperature was sometimes exceeded during warm spells.
The building has external louvres to reduce the solar gains. Moreover, the building makes use of night cooling. Cooler night time air is drawn in via the openable windows and ceiling voids. Fans in the ventilation towers can be used to assist purging. Ground water cooling can also be used.
NatVent
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Back to Back to “Select a “Select a building”building”
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Conclusions (2|)
The good solar control and combination of high thermal mass and night ventilation did result in lower temperatures and helped maintain comfort. By using ground water cooling the lower design temperature (25°C) could be met.
The good solar control and combination of high thermal mass and night ventilation did result in lower temperatures and helped maintain comfort. By using ground water cooling the lower design temperature (25°C) could be met.
one weeks external and internal air temperatures during August 1997.
15
17
19
21
23
25
27
29
31
33
06/08 07/08 08/08 09/08 10/08 11/08 12/08 13/08
Date/Time
Air
Te
mp
era
ture
de
gC
Office
External
More information...
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Building Building conceptconcept
ConclusionsConclusions
The Energy The Energy Efficient OfficeEfficient Office
More More information...information...
Design IssueDesign Issue
MonitoringMonitoring
SummerSummer
WinterWinter
Find more information on the PROBE building in the following documents:
\Reports \Monitoring Reports \Summary Reports\gb1summ.pdf global presentation of the buildings (4p./building) contents: building description - ventilation strategy and technology -
winter and summer monitoring results - conclusions
\Reports \Monitoring Reports \Detailed Reports\gb1det.pdf detailed reports of all 19 monitoring campaigns (20p./campaign) contents: monitoring set up - analysis of results - conclusions
Find more information on the PROBE building in the following documents:
\Reports \Monitoring Reports \Summary Reports\gb1summ.pdf global presentation of the buildings (4p./building) contents: building description - ventilation strategy and technology -
winter and summer monitoring results - conclusions
\Reports \Monitoring Reports \Detailed Reports\gb1det.pdf detailed reports of all 19 monitoring campaigns (20p./campaign) contents: monitoring set up - analysis of results - conclusions
You can read and print pdf-files with the Acrobat® Reader ®3.0. Program. This program is free.
Download it from the Acrobat web site: www.adobe.com OR run the installation file ar32e301(1).exe in the directory \Installation
You can read and print pdf-files with the Acrobat® Reader ®3.0. Program. This program is free.
Download it from the Acrobat web site: www.adobe.com OR run the installation file ar32e301(1).exe in the directory \Installation