natvent architect: khr a/s brf kredit headquarters back to “select a building” back to “select...
TRANSCRIPT
NatVent
Architect: KHR A/SArchitect: KHR A/SArchitect: KHR A/SArchitect: KHR A/S
BRF Kredit headquarters
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Building presentation (1...)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
BRF-kredit is a financing institute for property mortgages The company Headquarters is located in Lyngby, about 10 kilometres
north of Copenhagen City. The office building was completed in 1986
The main building has four storeys and incorporate an atrium The building consists of a main building and three office blocks (block
2, 3 and 4) The buildings are linked together At the connection points between the buildings there are staircases and
lifts
BRF-kredit is a financing institute for property mortgages The company Headquarters is located in Lyngby, about 10 kilometres
north of Copenhagen City. The office building was completed in 1986
The main building has four storeys and incorporate an atrium The building consists of a main building and three office blocks (block
2, 3 and 4) The buildings are linked together At the connection points between the buildings there are staircases and
lifts
Building presentation (2...)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
N
Main building
Office block 2
Office block 3
Office block 4
Building presentation (3...)
Office block 2
Office block 4
Main building
Office block 3
Main building Office block 2
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
The main building has four storeys and incorporate an atrium
The main building has four storeys and incorporate an atrium
Building presentation (4...)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Building presentation (5...)
Each office has a barrel-vaulted central arcade
Rooms on the 1st, 2nd and 3rd floors open onto this space
There is no access of daylight to the circulation area of the ground floor
Each office has a barrel-vaulted central arcade
Rooms on the 1st, 2nd and 3rd floors open onto this space
There is no access of daylight to the circulation area of the ground floor
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Building presentation (6...) sectional view
The barrel -vaulted central arcade is open through 1st, 2nd and 3rd floor
Skylights
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Of the total floor area of 20.000 m2
10.000 m2 (50%) is offices and meeting rooms 6.000 m2 (30%) is circulation area 4.000 m2 is toilets, cloakrooms and service area
The structural components include a vertical supporting system of reinforced concrete columns reinforced concrete girders at the balconies prefabricated facades
The facades of the building have a brickwork finish The windows have aluminium frames and are triple-glazed (standard float
glass). The windows in the skylights are double-glazed units
Of the total floor area of 20.000 m2
10.000 m2 (50%) is offices and meeting rooms 6.000 m2 (30%) is circulation area 4.000 m2 is toilets, cloakrooms and service area
The structural components include a vertical supporting system of reinforced concrete columns reinforced concrete girders at the balconies prefabricated facades
The facades of the building have a brickwork finish The windows have aluminium frames and are triple-glazed (standard float
glass). The windows in the skylights are double-glazed units
Building presentation (7...)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
The facades of the building have a brickwork finish
From the outside the building appears very compact and rather closed, but …
…from the inside it is very open and welcoming,due mainly to the large daylit circulation areas with skylights.
The facades of the building have a brickwork finish
From the outside the building appears very compact and rather closed, but …
…from the inside it is very open and welcoming,due mainly to the large daylit circulation areas with skylights.
Building presentation (8|)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Ventilation strategy (1...)
for summer comfort In summertime the risk of overheating is reduced by intensive ventilation:
High levels of natural ventilation. The ventilation is based on the occupants use of multi-position windows - so-called tilt and turn windows - in conjunction with the automatically skylights.
The intensive ventilation of the offices is based on cross ventilation and single sided ventilation (when the internal doors are closed).
When Tint. < 25°C the skylights are automatically opened at which point stack effects become one of the driving natural forces.
For security reasons all the windows on the ground floor and the 1st floor must be closed at night. In this zone of the building, the intensive ventilation is only used during day-time.
Automatically controlled external solar shading will help to reduce the risk of overheating from solar radiation.
In summertime the risk of overheating is reduced by intensive ventilation: High levels of natural ventilation. The ventilation is based on the
occupants use of multi-position windows - so-called tilt and turn windows - in conjunction with the automatically skylights.
The intensive ventilation of the offices is based on cross ventilation and single sided ventilation (when the internal doors are closed).
When Tint. < 25°C the skylights are automatically opened at which point stack effects become one of the driving natural forces.
For security reasons all the windows on the ground floor and the 1st floor must be closed at night. In this zone of the building, the intensive ventilation is only used during day-time.
Automatically controlled external solar shading will help to reduce the risk of overheating from solar radiation.
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Skylights:Automatically controlled windows (open when Tint.<25°C) and exterior shading devices
Offices:Manually operated multi-position windows and automatically controlled exterior blinds
DAYTIME
Ventilation strategy (2...)
for summer comfort
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
DAYTIME: skylights open
Ventilation strategy (3...)
for summer comfort
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
NIGHTTIME
Ventilation strategy (4...)
for summer comfortOffices:Manually operated multi-position windows and automatically controlled exterior blinds
Windows can be left open
Windows must be closed (for security reasons)
Internal doors must be closed (for security reasons)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Ventilation strategy (5...)
for indoor air quality Indoor air quality during
office hours in winter and summer time is controlled by the occupants:
Occupants can improve the air quality by opening the windows.
There is no automatic control related to the IAQ.
Indoor air quality during office hours in winter and summer time is controlled by the occupants:
Occupants can improve the air quality by opening the windows.
There is no automatic control related to the IAQ.
In the offices there are manually operated multi-position windows (so-called tilt and turn windows) and ...
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
… automatically controlled exterior Venetian blinds
In some offices the occupants have installed internal blinds
Technology (6...)
shading devices - offices
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Control: The exterior Venetian blinds in front of the office windows are
automatically controlled by light sensors. The Venetian blinds can also be operated on an individual basis.
However, after a given period the automatic control overrides any manual adjustments. After some time the position will be changed according to the automatic control system.
In addition to the up/down operation of the blinds the control system can set the angle of the slats to one or two positions according to the altitude of the sun.
Security: For security reasons the Venetian blinds will close automatically at
20.00 hours and remain fully closed at night. Even if the blinds are closed they do not impede the flow of outdoor air through an open window.
Control: The exterior Venetian blinds in front of the office windows are
automatically controlled by light sensors. The Venetian blinds can also be operated on an individual basis.
However, after a given period the automatic control overrides any manual adjustments. After some time the position will be changed according to the automatic control system.
In addition to the up/down operation of the blinds the control system can set the angle of the slats to one or two positions according to the altitude of the sun.
Security: For security reasons the Venetian blinds will close automatically at
20.00 hours and remain fully closed at night. Even if the blinds are closed they do not impede the flow of outdoor air through an open window.
Technology (7...)
shading devices - offices
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
The central arcades have automatically controlled skylights
The central arcades have automatically controlled skylights
Technology (8...)
shading and ventilation - arcade rooms
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Exterior shading device
Temperatures in the roof-space are monitored and the skylights are opened accordingly.
The exterior shading is controlled with the aid of light sensors. There are individual light sensors for each of the four orientations of the skylights
Temperatures in the roof-space are monitored and the skylights are opened accordingly.
The exterior shading is controlled with the aid of light sensors. There are individual light sensors for each of the four orientations of the skylights
No shading
Technology (9|)
shading and ventilation - arcade rooms
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up N
Office 1
Office 2Office 3
Office 4
Monitored offices Four offices on the third floor of office block 3 were
chosen for monitoring: Office 1: 25 m2 cellular office Office 2: 12 m2 cellular office Office 3: 12 m2 cellular office Office 4: 50 m2 open plan office, 8 persons
Office 1, 2 and 3 are facing essentially east, office 4 is a corner office facing south-west
Four offices on the third floor of office block 3 were chosen for monitoring:
Office 1: 25 m2 cellular office Office 2: 12 m2 cellular office Office 3: 12 m2 cellular office Office 4: 50 m2 open plan office, 8 persons
Office 1, 2 and 3 are facing essentially east, office 4 is a corner office facing south-west
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
0
5
10
15
20
25
30
35
Mon 2
8.0
7.9
7
Mon 0
4.0
8.9
7
Mon 1
1.0
8.9
7
Mon 1
8.0
8.9
7
Mon 2
5.0
8.9
7
Mon 0
1.0
9.9
7
Mon 0
8.0
9.9
7
Mon 1
5.0
9.9
7
Mon 2
2.0
9.9
7
Mon 2
9.0
9.9
7
Summer monitoring (1...) Indoor (average of 4 offices) & outdoor
temperatures during three months period
Text.
Tint.
The internal temperatures is often > 25°C and sometimes > 28°C.T
emp
erat
ure
(°C
).
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
0
5
10
15
20
25
30
35
Wed
30.
07.9
7
Thu
31.07
.97
Fri 0
1.08
.97
Sat 0
2.08
.97
Sun
03.0
8.97
Mon
04.
08.9
7
Tue
05.08
.97
Wed
06.
08.9
7
Thu
07.08
.97
Fri 0
8.08
.97
Tem
pera
ture
[°C]
, Air
supp
ly [l·
s-1
·m-2
]
Summer monitoring (2...) results of measurements in office 2
Text.
Air Supply
weekend
Intensive ventilation is only applied during office hours (not at night and at weekends).
Tint.
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
0
10
20
30
40
50
Wed 3
0.0
7.9
7
Thu 3
1.0
7.9
7
Fri
01.0
8.9
7
Sat
02.0
8.9
7
Sun 0
3.0
8.9
7
Mon 0
4.0
8.9
7
Tue 0
5.0
8.9
7
Wed 0
6.0
8.9
7
Thu 0
7.0
8.9
7
Fri
08.0
8.9
7
0
100
200
300
400
500
Summer monitoring (3...) results of measurements in office 2
Tint.CO2-conc.
Air Supply
The IAQ during office hours is good: The CO2 -concentrations are very low: max.450 ppm (= far below the limit concentration of 1200ppm)
Tem
per
atur
e (°
C),
Air
supp
ly (
l.s-1.m
-2)
The air supply during office hours is very high (intensive ventilation). This leads to low CO2 - concentration. There is no ventilation outside office hours and at weekends for security reasons.
CO
2-c
once
ntra
tion
(pp
m)
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Summer monitoring (4...) Questionnaires
In addition to the measurements, the occupants filled in two questionnaires concerning their views on various environmental conditions in their office. One questionnaire concerned the summer season in general and the other concerned one week in particular (in the summer season), namely the one in which the questionnaires were handed out.
Each occupant indicated his/her rating of each of the conditions (temperature, air movement etc.) by placing vertical marks on dimensionless, horizontal lines of equal length ranging from most positive (comfortable, fresh etc.) to most negative (uncomfortable, stuffy etc.). The rating is quantified by measuring (in millimetres) the distance along each line from most positive to the occupant’s mark. For practical purposes, the ratings have been converted into the range 0-100.
The next slide summarises the occupants ratings of the summer season in general.
In addition to the measurements, the occupants filled in two questionnaires concerning their views on various environmental conditions in their office. One questionnaire concerned the summer season in general and the other concerned one week in particular (in the summer season), namely the one in which the questionnaires were handed out.
Each occupant indicated his/her rating of each of the conditions (temperature, air movement etc.) by placing vertical marks on dimensionless, horizontal lines of equal length ranging from most positive (comfortable, fresh etc.) to most negative (uncomfortable, stuffy etc.). The rating is quantified by measuring (in millimetres) the distance along each line from most positive to the occupant’s mark. For practical purposes, the ratings have been converted into the range 0-100.
The next slide summarises the occupants ratings of the summer season in general.
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Averages of about 100 occupants ratings of various environmental conditions in their office during the summer season
Summer monitoring (5...) Questionnaires
64
65
56
38
45
32
41
48
0 20 40 60 80 100
Temperature
Air movement
Air quality
Odour intensity
Acceptability
Light
Noise
Overall comfort
Comfortable
Fresh
Comfortable
Uncomfortable
Uncomfortable
Stuffy
Satisfactory
Satisfactory
Satisfactory
Unsatisfactory
Unsatisfactory
Unsatisfactory
Odourless Smelly
Acceptable Not acceptable
Temperature
Air movement
Air quality
Odour intensity
Acceptability
Light
Noise
Overall comfort
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Thermal comfort: During a three week period in the month of August, the indoor
temperature (average of simultaneous recordings in four offices) was constantly above 25°C. On extreme days the indoor temperature peaked close to 30°C.
Lower temperatures could be achieved by introducing night time ventilation. The impact of this can be significant when external air temperatures are low.
The IAQ is good due to the intensive day ventilation.
Questionnaires: The occupants reported some dissatisfaction regarding the indoor temperature (being too high) and internal air movements (being too low).
Thermal comfort: During a three week period in the month of August, the indoor
temperature (average of simultaneous recordings in four offices) was constantly above 25°C. On extreme days the indoor temperature peaked close to 30°C.
Lower temperatures could be achieved by introducing night time ventilation. The impact of this can be significant when external air temperatures are low.
The IAQ is good due to the intensive day ventilation.
Questionnaires: The occupants reported some dissatisfaction regarding the indoor temperature (being too high) and internal air movements (being too low).
Summer monitoring (6|) Findings
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
-5
0
5
10
15
20
25
30
Mon 1
0.1
1.9
7
Mon 1
7.1
1.9
7
Mon 2
4.1
1.9
7
Mon 0
1.1
2.9
7
Mon 0
8.1
2.9
7
Mon 1
5.1
2.9
7
Mon 2
2.1
2.9
7
Mon 2
9.1
2.9
7
Winter monitoring (1...) Indoor (average of 4 offices) & outdoor
temperatures during a two months period
Text.
Tint.
The internal temperatures are between 20 and 23°C and drops to 17°C at weekends
Tem
per
atur
e (°
C).
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
0
200
400
600
800
1000
1200
Fri
14.1
1.9
7
Sat
15.1
1.9
7
Sun 1
6.1
1.9
7
Mon 1
7.1
1.9
7
Tue 1
8.1
1.9
7
Wed 1
9.1
1.9
7
Thu 2
0.1
1.9
7
Fri
21.1
1.9
7
Sat
22.1
1.9
7
Sun 2
3.1
1.9
7
Mon 2
4.1
1.9
7
CO2 concentration indoors and outdoors. Indoor CO2 is averaged from recordings taken simultaneously in office 1, 2, 3 and 4)
Winter monitoring (2...) CO2 concentration
CO
2-c
once
ntra
tion
(pp
m)
Outdoor CO2-conc.
Indoor CO2-conc.
The IAQ during office hours is good: The CO2 - concentrations are below the limit concentration of 1200ppm.
At weekend the internal CO2 -concentration equals outdoor CO2 - concentration
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
0
10
20
30
40
50
Fri
14.1
1.9
7
Sat
15.1
1.9
7
Sun 1
6.1
1.9
7
Mon 1
7.1
1.9
7
Tue 1
8.1
1.9
7
Wed 1
9.1
1.9
7
Thu 2
0.1
1.9
7
Fri
21.1
1.9
7
Sat
22.1
1.9
7
Sun 2
3.1
1.9
7
Mon 2
4.1
1.9
7
0
200
400
600
800
1000
Winter monitoring (3...) results of measurements in office 2
CO
2-c
once
ntra
tion
(pp
m)
Tem
per
atur
e (°
C),
Air
supp
ly (
l.s-1.m
-2)
Air supply.
Indoor CO2-conc.
The air supply during office hours is sufficient The IAQ is acceptable (CO2 - conc.< 1200ppm.). There are no ventilation losses outside office hours
Tint.
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Winter monitoring (4...) Questionnaires
In addition to the measurements, the occupants filled in two questionnaires concerning their views on various environmental conditions in their office. One questionnaire concerned the winter season in general and the other concerned one week in particular (in the winter season), namely the one in which the questionnaires were handed out.
Each occupant indicated his/her rating of each of the conditions (temperature, air movement etc.) by placing vertical marks on dimensionless, horizontal lines of equal length ranging from most positive (comfortable, fresh etc.) to most negative (uncomfortable, stuffy etc.). The rating is quantified by measuring (in millimetres) the distance along each line from most positive to the occupant’s mark. For practical purposes, the ratings have been converted into the range 0-100.
The next slide summarises the ratings concerning the winter season in general.
In addition to the measurements, the occupants filled in two questionnaires concerning their views on various environmental conditions in their office. One questionnaire concerned the winter season in general and the other concerned one week in particular (in the winter season), namely the one in which the questionnaires were handed out.
Each occupant indicated his/her rating of each of the conditions (temperature, air movement etc.) by placing vertical marks on dimensionless, horizontal lines of equal length ranging from most positive (comfortable, fresh etc.) to most negative (uncomfortable, stuffy etc.). The rating is quantified by measuring (in millimetres) the distance along each line from most positive to the occupant’s mark. For practical purposes, the ratings have been converted into the range 0-100.
The next slide summarises the ratings concerning the winter season in general.
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Averages of about 100 occupants ratings of various environmental conditions in their office during the winter season
46
55
62
45
41
36
41
45
0 20 40 60 80 100
Temperature
Air movement
Air quality
Odour intensity
Acceptability
Light
Noise
Overall comfort
Comfortable
Fresh
Comfortable
Uncomfortable
Uncomfortable
Stuffy
Satisfactory
Satisfactory
Satisfactory
Unsatisfactory
Unsatisfactory
Unsatisfactory
Odourless Smelly
Acceptable Not acceptable
Temperature
Air movement
Air quality
Odour intensity
Acceptability
Light
Noise
Overall comfort
Winter monitoring (5...) Questionnaires
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
During the winter, the indoor conditions are comfortable: During occupancy periods, indoor temperatures were between 20 and
23 ºC, the CO2-concentrations were between 1000 and 1200 ppm and in office 2, given here as an example, the fresh air supplied gave about 7 air changes per hour.
Out of office hours the indoor temperature dropped to 17-18 ºC, the CO2-concentration to near background level, 400 ppm, and the air supply to nearly zero (= no ventilation losses).
Questionnaires The Indications are that the occupants found the indoor environment
to be more comfortable during the winter-time than in the summer-time.
In the summer-time, thermal comfort is more critical than during the winter.
During the winter, the indoor conditions are comfortable: During occupancy periods, indoor temperatures were between 20 and
23 ºC, the CO2-concentrations were between 1000 and 1200 ppm and in office 2, given here as an example, the fresh air supplied gave about 7 air changes per hour.
Out of office hours the indoor temperature dropped to 17-18 ºC, the CO2-concentration to near background level, 400 ppm, and the air supply to nearly zero (= no ventilation losses).
Questionnaires The Indications are that the occupants found the indoor environment
to be more comfortable during the winter-time than in the summer-time.
In the summer-time, thermal comfort is more critical than during the winter.
Winter monitoring (6|) Findings
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
Conclusions (1...)
Findings from summer monitoring
Thermal comfort in summer: During a three week period in the month of August, the indoor
temperature (average of simultaneous recordings in four offices) was constantly above 25°C. On extreme days the indoor temperatures peaked close to 30°C.
Lower temperatures could be achieved by introducing night-time ventilation. The impact of this can be significant when external air temperatures are low.
At the present time, night ventilation is not applied for security reasons. This problem could be solved by installing burglar-proof ventilation grilles in the facade. Also the problem of closed internal doors can be solved by installing transfer grilles above the internal doors.
Findings from summer monitoring
Thermal comfort in summer: During a three week period in the month of August, the indoor
temperature (average of simultaneous recordings in four offices) was constantly above 25°C. On extreme days the indoor temperatures peaked close to 30°C.
Lower temperatures could be achieved by introducing night-time ventilation. The impact of this can be significant when external air temperatures are low.
At the present time, night ventilation is not applied for security reasons. This problem could be solved by installing burglar-proof ventilation grilles in the facade. Also the problem of closed internal doors can be solved by installing transfer grilles above the internal doors.
NatVent
Back to Back to “Select a “Select a building”building”
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More informationinformation...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up
NatVent
Conclusions (2|)
Findings from winter monitoring
Winter indoors conditions are comfortable: During occupancy periods, indoor temperatures were about 20 and
23ºC, the CO2-concentration between 1000 and 1200 ppm and in office 2, given here as an example, the fresh air supply gave about 7 air change per hour.
Out of office hours the indoor temperatures dropped to 17-18ºC, the CO2-concentration to near background level, 400 ppm, and the air supply to nearly zero (= no ventilation losses).
Questionnaires The indications are that the occupants found the indoor environment
to be more comfortable during the winter-time than in the summer-time.
Regarding air quality, the occupants rated summer conditions higher than winter conditions.
Findings from winter monitoring
Winter indoors conditions are comfortable: During occupancy periods, indoor temperatures were about 20 and
23ºC, the CO2-concentration between 1000 and 1200 ppm and in office 2, given here as an example, the fresh air supply gave about 7 air change per hour.
Out of office hours the indoor temperatures dropped to 17-18ºC, the CO2-concentration to near background level, 400 ppm, and the air supply to nearly zero (= no ventilation losses).
Questionnaires The indications are that the occupants found the indoor environment
to be more comfortable during the winter-time than in the summer-time.
Regarding air quality, the occupants rated summer conditions higher than winter conditions.
NatVent
Back to Back to “Select a “Select a building”building”
More information...Find more information on the PROBE building in the following documents:
\Reports \Monitoring Reports \Summary Reports\dk2summ.pdf global presentation of the buildings (4p./building) contents: building description - ventilation strategy and technology -
winter and summer monitoring results - conclusions
\Reports \Monitoring Reports \Detailed Reports\dk2det.pdf detailed reports of all 19 monitoring campaigns (20p./campaign) contents: monitoring set up - analysis of results - conclusions
Find more information on the PROBE building in the following documents:
\Reports \Monitoring Reports \Summary Reports\dk2summ.pdf global presentation of the buildings (4p./building) contents: building description - ventilation strategy and technology -
winter and summer monitoring results - conclusions
\Reports \Monitoring Reports \Detailed Reports\dk2det.pdf detailed reports of all 19 monitoring campaigns (20p./campaign) contents: monitoring set up - analysis of results - conclusions
You can read and print pdf-files with the Acrobat® Reader ®3.0. Program. This program is free.
Download it from the Acrobat web site: www.adobe.com OR run the installation file ar32e301(1).exe in the directory \Installation
You can read and print pdf-files with the Acrobat® Reader ®3.0. Program. This program is free.
Download it from the Acrobat web site: www.adobe.com OR run the installation file ar32e301(1).exe in the directory \Installation
Presentation Presentation of the buildingof the building
Ventilation Ventilation strategy & strategy & technologytechnology
ConclusionsConclusions
BRF Kredit BRF Kredit BuildingBuilding
More More information...information...
Summer Summer monitoringmonitoring
Winter Winter monitoringmonitoring
Monitoring Monitoring set-upset-up