l90 complete agenda

Upload: samiahmedmansour

Post on 07-Aug-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/19/2019 l90 Complete Agenda

    1/64

    1

    L90 Line Differential Relay

    Digital Energy

    Multilin

     Agenda

  • 8/19/2019 l90 Complete Agenda

    2/64

  • 8/19/2019 l90 Complete Agenda

    3/64

    3

    Introduction

    1) Reliability: has two aspects:

    Dependability: the degree of certainty that the relay will operate

    correctly.

    Security: the relay will not operate incorrectly

    2) Speed: Very high power during fault conditions: delays translate intoincreased damage: faster protection tends to compromise relay system

    security and selectivity.

    3) Sensitivity: The minimum operating quantities allows the relay to detect

    an abnormal condition. High-impedance ground faults,voltage unbalance

    and high source- to- line impedance ratio affect the sensitivity

    4) Selectivity : or coordination: ability of the relay system to minimize

    outages as a result of a fault by operating as fast as possible within their

    primary zone.

    5) Simplicity and ergonomics: simple to apply and to obtain maximum

    protection for the minimum cost in one box

    Terms: Coordination, Unit Protection/None Unit Protection, Primary/Back up

    Transmission Line Protection Considerations

    High voltage transmission lines have extremely high level of fault current and

    low impedance characteristics. Over current protection can not be as fast as it’s

    needed.

    Solutions:

    • Current Differential:

    • Unit Protection

    Measure the current phasors at both ends of the line. If you have a line fault

    there will be a difference in the current magnitude at each end and/or a changein current phase angle with respect to applied voltage.

    • Distance or (Impedance):

    • None Unit Protection

    Impedance known as Distance: The distance relay operates by using bothvoltage and current to determine if a fault is in a relay’s zone of protection. At

    time of fault Current increases and voltage decreases which translates into a

    change in impedance.

    Introduction

    Transmission Line Protection Considerations

  • 8/19/2019 l90 Complete Agenda

    4/64

  • 8/19/2019 l90 Complete Agenda

    5/64

    5

    L90 Current Differential Relay:

    • Protection:

     – Segregated Line current differential (87L)

     – 87L Trip logic

     – Phase/Neutral/Ground TOCs

     – Phase/Neutral/Ground IOCs

     – Negative sequence TOC

     – Negative sequence IOC

     – Phase directional OCs

     – Neutral and negative sequence directional OC – Phase under- and overvoltage

     – 3-zone distance back-up with power swing detect,load encroachment, POTT and line pickup

     Features

    L90 Current Differential Relay:

    • Control:

     – Breaker Failure (phase/neutral amps)

     – Synchrocheck & Autoreclosure

     – Direct messaging (8 extra inter-relay DTT bits exchanged)

    • UR Metering:

     – Fault Locator 

     – Oscillography

     – Event Recorder 

     – Data Logger 

     – Phasors / true RMS / active, reactive and apparent power, powerfactor 

    • 87L Metering:

     – actual differential current

     – local and remote phasors

     – communication channel status

     Features

  • 8/19/2019 l90 Complete Agenda

    6/64

    6

    L90 Current Differential Relay:

     Features

    831706AS.CDR

    L90 Line Differential Relay

    52

    Monitoring CLOSE TRIP

    Data From/To Remote End(via Dedicated Communications) MeteringFlexElement

    TM   Transducer Inputs

    50DD   51N(2)50N(2)67P(2)87L 21P 68   7850BF(2)51_2(2)51P(2)50_2(2)

    79

    50P(2) 21G67N/G

    27P(2)

    27X

    59N

    59X

    59P

    25(2)

    3V_0

    51G(2)50G(2)

    L90 Current Differential Relay:

    Line Current Differential

    • Improved operation of the line current di fferential (87L)element:

     – Dynamic Restraint increasing security without jeopardizingsensitivity

     – Line Charging Current Compensation to increase sensitivity

     – Self-synchronization

     – Channel Asymmetry Compensation to compensate forasymmetrical channel delay on multiplexed channels

     – CT Saturation Detection

     – Zero sequence current removal for applications on lines witha tapped transformers with a primary wye neutral grounded.

     – Relay ID for secure applications on higher ordercommunication systems.

  • 8/19/2019 l90 Complete Agenda

    7/64

    7

    L90 Current Differential Relay:

    Line Current Differential

    L90 can be appliedon bo th 2-terminaland 3-terminalapllications:hardware andfirmware are thesame.

    Direct point-to-point Fiber

    (up to 100Km)

    ORVia SONET system telecom multiplexer

    (GE’s FSC)

    FSC

    (SONET)

    FSC

    (SONET)

    (64Kbps)

    (155Mbps)

    - G.703

    - RS422

    - G.703

    - RS422

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    8/64

  • 8/19/2019 l90 Complete Agenda

    9/64

    9

    FIBER - LED & ELED

    TRANSMITTERS

    The above figure shows the 2-Terminal

    configuration for the 7A, 7B, & 7C fiber-

    only modules.

    LASER FIBER MODULES

    WARNING: When using a 1300/1550 nm

    LASER Interface, attenuators may be

    necessary to ensure that you do not exceed

    Maximum Optical Input Power (-14 dBm) to

    the receiver.

    DIRECT FIBER

    L90 Current Differential Relay:

    Installation

    DIRECT FIBER

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    10/64

    10

    DIRECT FIBER OPTICAL POWER BUDGET

    L90 Current Differential Relay:

    Installation

    Typical pin interconnection between two G.703 interfaces back-to-

    back.

    G.703 CO-DIRECTIONAL INTERFACE

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    11/64

    11

    G.703 INTERFACE

    G.703 module dip switches..

    L90 Current Differential Relay:

    Installation

    G.703 INTERFACE

    Connection to higher order system

    G.703 Timing Selection

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    12/64

    12

    G.703 INTERFACE

    Minimum Remote Loopback Test mode data processing

    L90 Current Differential Relay:

    Installation

    G.703 INTERFACE

    Dual Loopback Test mode data processing

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    13/64

    13

    Back to Back: Correct

    Internal Timing mode

    (S1=Off, S5=On, S6=Off)

    Back to Back : Will work but not ideal.

    G.703 INTERFACE

    Loop Timing mode

    (S1=Off, S5=Off, S6=Off)

    Internal Timing mode

    (S1=Off, S5=On, S6=Off)

    Loop Timing mode (factory

    default for connections to

    higher order system

    (S1=On, S5=Off, S6=Off)

    L90 Current Differential Relay:

    Installation

    Point to Point using Modems (for example RAD modem):

    • Octet Timing

    Disabled

    • Loop Timing

    mode

    • Octet Timing

    Disabled

    •Internal

    Loop Timing

    mode

    Loop Timing

    mode

    Rad Modem Rad Modem

    Only one clock per system

    generated by right L90.

    G.703 INTERFACE

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    14/64

    14

    Connection via multiplexers (higher order system):

    The multiplexer provides the clock for all relays: again, one clock per

    system:

    Multiplexer Multiplexer  • Octet Timingenabled

    • Loop Timing

    mode

    • Octet Timing

    enabled

    • Loop Timing

    mode

    G.703 INTERFACE

    L90 Current Differential Relay:

    Installation

    Typical pin interconnection between two RS422 interfaces

    RS.422 INTERFACE

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    15/64

  • 8/19/2019 l90 Complete Agenda

    16/64

    16

    WARNING: When using a 1300 nm LASER Interface, attenuators may be

    necessary to ensure that you do not exceed Maximum Optical Input Power

    (-14 dBm) to the receiver.

    RS422 & FIBER INTERFACE CONFIGURATION

    MIXED INTERFACES

    L90 Current Differential Relay:

    Installation

    The IEEE C37.94 Standard defines a point to point opt ical link for

    synchronous data between a multiplexer and a teleprotection

    device. Designed to interface with IEEE C37.94 compliant digital multiplexer

    and/or an IEEE C37.94 compliant interface converter for use wi thL90.

    IEEE fiber C37.94 INTERFACE

    L90 Current Differential Relay:

    Installation

    Connected directly to

    MUX

    Connected to MUX

    via converter 

  • 8/19/2019 l90 Complete Agenda

    17/64

    17

    For the Internal Timing Mode, the system clock is generatedinternally; therefore, the timing switch selection should be Internal

    Timing for Relay 1 and Loop Timed for Relay 2. There must be only

    one timing source configured. For the Looped Timing Mode, the system clock is derived from the

    received line signal; therefore, the timing selection should be inLoop Timing Mode for connections to h igher order systems.

    IEEE fiber C37.94 INTERFACE

    L90 Current Differential Relay:

    Installation

    G7X

    G7R

    Transmitted

    data blocked

    Local Loopback Test Mode

    Local relay

    COMMS CHANNEL TESTING

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    18/64

    18

    G7X

    G7R

    Received data

    echoed back.Remote Loopback Test

    Local relay

    COMMS CHANNEL TESTING

    G7X

    G7R

    Remote

    relay

    L90 Current Differential Relay:

    Installation

    COMMS CHANNEL ON-LINE DIAGNOSTICS

    Current comms status is available

    in Actual Values.History of comms di sturbances is l ogged

    into event recorder .

    L90 Current Differential Relay:

    Installation

  • 8/19/2019 l90 Complete Agenda

    19/64

    19

    COMMS CHANNEL ON-LINE DIAGNOSTICS

    L90 Current Differential Relay:

    Installation

    MAJOR COMMS ALARMS

    1. 87L DIFF CH1/2 FAIL

    2. 87L DIFF PFLL FAIL

    3. 87L DIFF CH1/2 ID FAIL

    87L DIFF BLOCKED

    MINOR COMMS ALARMS

    1. 87L DIFF CH1/2 CRCFAIL

    2. 87L DIFF CH1/2 LOSTPKT

    3. 87L DIFF TIME CHANGED

    4. 87L DIFF ASYM DETECTED

    5. 87L DIFF 1/2 ASYM MAX

    6. 87L DIFF GPS1/2 FAIL

    COMMS CHANNEL ON-LINE DIAGNOSTICS

    CHANNEL ID FAIL

    1. Each packet carries relay

    ID number per channel

    2. Each received packet is

    compared with ID

    programmed L90 PowerSystem menu.

    3. “0” means NO Channel ID

    check is required (for

    direct fibers).

    L90 Current Differential Relay:

    Installation

    Protection against:

    1. Inadvertent loopback

    2. Inadvertent connection to awrong L90 relay.

  • 8/19/2019 l90 Complete Agenda

    20/64

    20

    Percent Current Differential

    L90 Current Differential Function

    IA @Timestamp2

    IB @Timestamp2

    IC@Timestamp2

    ChargingCurrent

    DATA FROMLOCALEND

    ACTUALVALUES

    SETTING

    CURRENTDIFFPICKUP:

    CURRENTDIFFRESTRAINT1:

    CURRENTDIFFRESTRAINT2:

    CURRENTDIFFBREAKPT:

    SETTING

    SETTING

    SETTING

    SETTING

    SETTING

    SETTING

    SETTING

    SETTINGS

    Channel 1OK=1

    Channel 2OK=1

    IA @Timestamp2

    IA @Timestamp2

    IB @Timestamp2

    IB @Timestamp2

    IC @Timestamp2

    IC @Timestamp2

    DTTPHASEA

    DTTPHASEA

    DTTPHASEB

    DTTPHASEB

    DTTPHASEC

    DTTPHASEC

    CURRENTDIFFDTT:

    CURRENTDIFFKEYDTT:

    L90POWER SYSTEMXC0& XC1:

    CURRENTDIFFSOURCE:

    CURRENTDIFFTAP1:

    CURRENTDIFFTAP2:

    L90POWERSYSTEMNUM.OFTERMINALS:

    L90POWERSYSTEMNUM.OFCHANNELS:

    RUN

    RUN

    RUN

    To RemoteRela yschannel 1& 2

    827056A9.CDR

    VCG

    IC

    VBG

    IB

    Enabled=1

    Off 

    DATA FROMREMOTE1

    DATA FROMREMOTE2

    RUN

    FLEXLOGICOPERANDS

    87LDIFFOPA

    87LDIFFOPB

    87LDIFFOPC

    87LDIFFRECVDDTTA

    87LDIFFRECVDDTTB

    87LDIFFRECVDDTTC

    87LDIFF CH2CRCFAIL

    87LDIFFKEYDTT

    87LDIFFCH1 CRCFAIL

    87LDIFF CH2LOSTPKT

    87LDIFF CH1LOSTPKT

    87LDIFFCH2FAIL

    87LDIFFCH1FAIL

    87LDIFFPFLLFAIL

    87LDIFFOP

    ORAND

    ORAND

    OR

    OR

    OR

    OR

    OR

    OR

    OR

    OR

    OR

    AND

    AND

    AND

    AND

    AND

    AND

    AND

    OR

    VAG

    IA

    ComputeChargingCurrent

    “3 ” =1

    “2” =1

    ComputePhasors& Variance(Local)

    ComputePhasors& Variance(Remote1)

    ComputePhasors& Variance(Remote2)

    IC

    IC

    IC

    IA

    IA

    IA

    IB

    IB

    IB

    IA Operate

    IARestraint>1

    2

    2

    IB Operate>1

    IBRestraint

    2

    2

    ICOperate>1

    ICRestraint

    2

    2

    FLEXLOGICOPERAND

    STUB BUSOP

    ToRemoteRelayschannel 1& 2

    RUN

    ProcessPhasorsComputations

    IC

    IA

    IB

    AND

    ND

    AND

    87LDIFFCH1IDFAIL

    87LDIFFCH2IDFAIL

    87LBLOCKED

    AND

    Channel 1IDFail

    Channel 2IDFail

    AND

    AND

    AND

    AND

    AND

    AND

    ANDOR

  • 8/19/2019 l90 Complete Agenda

    21/64

    21

    Restraint Current

       O  p  e  r  a   t  e   C  u  r  r  e  n   t

    K1

    K2

    L90 Current Differential Relay:

    Traditional Restraint Method

    • Traditional method is STATIC

    • Compromise between Sensitivity and Security

    L90 Current Differential Relay:

    Dynamic Restraint

    • Dynamic restraint uses an estimate of a

    measurement error to dynamically increase the

    restraint

    • On-line estimation of an error is possible owing to

    digital measuring techniques

    • In digital relaying to measure means to calculate or

    to estimate a given signal feature such as magnitude

    from the raw samples of the signal waveform

  • 8/19/2019 l90 Complete Agenda

    22/64

  • 8/19/2019 l90 Complete Agenda

    23/64

    23

    L90 Current Differential Relay:

    Digital Phasor MeasurementSliding Data Window

    waveform magnitude

    windo

    w

    timetime

    present

    time

    32 samples for

    Transmission

    of one phaselet

    32 samples for

    Transmission of

    next phaselet

    L90 Current Differential Relay:

    Phasor Goodness of Fit

    window

    time

    • A sum of squared differences between the actual

    waveform and an ideal sinusoid over last window is a

    measure of a “goodness of fit” (a measurement error)

  • 8/19/2019 l90 Complete Agenda

    24/64

    24

    L90 Current Differential Relay:

    Phasor Goodness of Fit

    • The goodness of fit is an accuracy index for the digital

    measurement

    • The goodness of fit reflects inaccuracy due to:

     – transients

     – CT saturation

     – inrush currents and other signal distortions

     – electrical noise

    • The goodness of fit is used by the L90 to alter the

    traditional restraint signal (dynamic restraint)

    L90 Current Differential Relay:

    Operate-Restraint Regions

    ILOC – local current

    IREM – remote end current

    Imaginary (ILOC /IREM)

    Real (ILOC /IREM)

    OPERATE

    OPERATE

    OPERATE

    OPERATE

    RESTRAINT

  • 8/19/2019 l90 Complete Agenda

    25/64

    25

    L90 Current Differential Relay:

    Dynamic RestraintDynamic restraint signal =

    Traditional restraint signal + Error factor Imaginary (ILOC /IREM)

    Real (ILOC /IREM)

    OPERATE

    REST.

    Error factor is high

    Error factor is low

    L90 Current Differential Relay:

    Charge Current Compensation

    • The L90 calculates the instantaneous values of the

    line charging current using the instantaneous values

    of the terminal voltage and shunt parameters of the

    line

    • The calculated charging current is subtracted from

    the actually measured terminal current

    • The compensation reduces the spurious differential

    current and allows for more sensitive settings

  • 8/19/2019 l90 Complete Agenda

    26/64

    26

    L90 Current Differential Relay:

    Charge Current Compensation

    • The compensating algorithm:

     – is accurate over wide range of frequencies

     – works with shunt reactors installed on the line

     – works in steady state and during transients

     – works with both wye- and delta-connected VTs

    (for delta VTs the accuracy of compensation is

    limited)

    L90 Current Differential Relay:

    Effect of Compensation

    0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18-200

    -150

    -100

    -50

    0

    50

    100

    150

    200

    0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18-200

    -150

    -100

    -50

    0

    50

    100

    150

    200

    Voltage, V

    time, sec

    Local and remote voltages

    Time ofenergization

    Time of out of zone fault

    ~

  • 8/19/2019 l90 Complete Agenda

    27/64

    27

    0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18-0.2

    -0.15

    -0.1

    -0.05

    0

    0.05

    0.1

    0.15

    0.2

    0.25

    0.3

    0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18-0.2

    -0.15

    -0.1

    -0.05

    0

    0.05

    0.1

    0.15

    0.2

    0.25

    0.3

    L90 Current Differential Relay:

    Effect of Compensation

    Current, A

    time, sec

    Traditional and compensated differential

    currents (waveforms)

    Time of

    energization

    Theoretical compensated

    current

     Actual none compensated

    current

    0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.180

    0.01

    0.02

    0.03

    0.04

    0.05

    0.06

    0.07

    0.08

    0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.180

    0.01

    0.02

    0.03

    0.04

    0.05

    0.06

    0.07

    0.08

    L90 Current Differential Relay:

    Effect of Compensation

    Current, A

    time, sec

    Traditional and compensated differential

    currents (magnitudes)

     Actual none compensated

    current after filtering and

    Fourier algorithm

     Actual compensated current

    after filtering and fourier

    algorithm

  • 8/19/2019 l90 Complete Agenda

    28/64

    28

    L90 Current Differential Relay:

    Self-Synchronization

    t0

    t1

    t2

    t3

    tf 

    tr 

    Forward

    travel

    time

    Return

    travel

    time

    Relay

    turn-around

    time

    RELAY 1 RELAY 2

    2

    1203  t t t t 

    t t  r  f 

    2

    1203  t t t t 

    t t  r  f 

    “ping-pong”

    L90 Current Differential Relay:

    Ping-Pong (example)

    Communication path

    Initial clocks mismatch=1.4ms or 30°

    8.33 ms

    8.33 ms

    8.33 ms

    Store T1i-2=5.1

    8.33 ms

    t1 t2

    Slow down

    Relay 1

    0

    5.1

    0

    2.3

    8.33

    8.33 Send T2i-2=2.3

    Send T1i-2=5.1

    Capture T1i-2=5.1

    8.33 ms

    Send start bit

    Store T1i-3=0Send start bit

    Store T2i-3=0

    13.4310.53

    Send T1i-1=16.66

    Capture T2i-2=2.3

    16.66

    21.76

    16.66

    18.96

    Send T2i-1=16.66

    Store T2i-1=16.66

    Capture T1i=21.76

    Store T2i-2=2.3

    Store T1i-1=8.33

    Capture T2i=18.96

    T2i-3=0

    T1i-2=5.1

    T1i-1=16.66

    T2i=18.96

    a2=5.1-0=5.1

     b2=18.96-16.66=2.3

    2=(5.1-2.3)/2=

    = +1.4ms (behind)

    T1i-3=0

    T2i-2=2.3

    T2i-1=16.66

    T1i=21.76

    a1=2.3-0=2.3

     b1=21.76-16.66=5.1

    1=(2.3-5.1)/2=

    = -1.4ms (ahead)

    Speed up

    Relay 2

    30°0°

  • 8/19/2019 l90 Complete Agenda

    29/64

    29

    L90 Current Differential Relay:

    Ping-Pong (example continued)

    8.52 ms

    8.14 ms

    8.14 ms

    Store T1i-2=38.28

    8.52 ms

    t1 t2

    Slow down

    Relay 1

    33.32

    38.28

    33.32

    35.62

    41.5541.55

    Send T2i-2=35.62Send T1i-2=38.28

    Capture T1i-2=38.28

    8.52 ms

    Store T1i-3=33.32

    Store T2i-3=33.32

    Send T1i-1=50.00

    Capture T2i-2=35.62

    50.00

    54.03

    49.93

    53.16

    Send T2i-1=49.93

    Store T2i-1=49.93Capture T1i=54.03

    Store T2i-2=35.62

    Store T1i-1=50.00

    Capture T2i=53.16

    T2i-3=33.32

    T1i-2=38.28

    T1i-1=50.00

    T2i=53.16

    a2=38.28-33.32=4.96

     b2=53.16-50.00=3.16

    2=(4.96-3.16)/2=

    = +0.9ms (behind)

    T1i-3=33.32

    T2i-2=35.62

    T2i-1=49.93

    T1i=54.03

    a1=35.62-33.32=2.3

     b1=54.03-49.93=4.1

    1=(2.3-4.1)/2=

    = -0.9ms (ahead)

    Speed up

    Relay 2

    30°19.5°0°

    8.14 ms

    L90 Current Differential Relay:

    Digital “Flywheel”

    clock 1 clock 2

    “Virtual Shaft”

     

    • If communications is lost, sample clocks continue

    to “free wheel”

    • Long term accuracy is only a function of the base

    crystal stability

  • 8/19/2019 l90 Complete Agenda

    30/64

  • 8/19/2019 l90 Complete Agenda

    31/64

    31

    L90 Current Differential Relay:

    Zero-sequence Current RemovalThe L90 protection system could be applied to lines with tapped

    transformer(s) even if the latter has its windings connected in a grounded

    wye on the line side and the transformer(s) currents are not measured by

    the L90 protection system..

    L90-1 L90-2

    I_0

    L90 Current Differential Relay:

    CT Saturation Detection

    Current differential protection is inherently dependent on adequate CT

    performance at all terminals of the protected line especially during

    external faults. CT saturation, particularly if happens at one terminal of

    the line only, introduces a spurious differential current that may cause the

    differential protection to misoperate.

  • 8/19/2019 l90 Complete Agenda

    32/64

    32

    L90 Current Differential Relay:

    Breaker-and-a-half The L90 has

    advantages on

    systems with breaker-

    and-a-half or ring bus

    configurations. In these

    applications, each of

    the two three-phase

    sets of individual

    phase currents (one

    associated with eachbreaker) can be used

    as an input to a

    breaker failure

    element.

    L90 Current Differential Relay:

    Breaker-and-a-half 

    Benefits:

    • For restraint forming, maximum of 2 (or more currents is

    used). Conventional sum might not provide enough

    restraint.

    • CTs matching is done

    internally, different CT

    ratios possible

    • Current are available

    individually for BF,

    metering etc

  • 8/19/2019 l90 Complete Agenda

    33/64

    33

    L90 Current Differential Relay:

    Breaker-and-a-half 

    Distributed bus

    differential

    Up to 4 CTs can be

    processed

    individually and

    summed up with

    L90. For application

    where buses are

    located remotely,this is beneficial as

    CT leads don’t allow

    applying bus

    differential.

    L90 Current Differential Relay:

    Channel asymmetry

    • On SONET/SDH system, transmit and receive channel

    delays can be different. Normally, Tx_delay=Rx_delay.

    • If one path is broken, it can be re-routed to another

     physical fiber, resulting in Tx_delayRx_delay.

    RELAY 1

    ADM-2 ADM-3

    ADM-4

    RELAY 2

    ADM-1

    Tx Rx

    TxRx

  • 8/19/2019 l90 Complete Agenda

    34/64

    34

    L90 Current Differential Relay:

    Channel asymmetry• Difference in transmit-receive paths is causing

    incorrect synchronization between relays as ping-pong is operating based on assumption that transmit-receive delays are the equal.

    • That results in apparent differential current,proportional to the value of the channel asymmetry.

    • If currents and channel asymmetry are high enough,relay misoperates.

    IDIFFIA IB

    Half of the channel

    asymmetry in

    electrical degrees

    L90 Current Differential Relay:

    Channel asymmetry

    • L90 can cope with channel asymmetry as high as upto 10 ms using GPS signal.

    • No additional input is required-GPS clock isconnected to the regular IRIG-B UR input, providingaccurate clock to both events time-stamping andchannel asymmetry compensation algorithm.

    RELAY 1

    ADM-2 ADM-3

    ADM-4

    RELAY 2

    ADM-1Tx Rx

    TxRx

    GPS clock GPS clock

  • 8/19/2019 l90 Complete Agenda

    35/64

    35

    L90 Current Differential Relay:

    Channel asymmetry

    | Ch1Assymetry | > MAX

    REALTIM ECLOCK:IRIG-B SIGNALTYPE

    None =0

       O   R 87LGPSStatus Fail

    To Remote RelaysChannels 1and 2

    DATA FROM REMOTE

    TERMINAL 1

    87LCh 1Status (OK=1)

    L90POWERSYSTEM:CHNLASYM COMP:

    Off = 0

       O   R

    GPS COMPENSATION

    Use CalculatedCorrection, Establish andUpdate Memory

    Use MemorizedCorrection

    RUN

    FLEXLOGICOPERAND

    87LDIFF GPS FAIL

    87LDIFFGPS1FAIL

       A   N   D

    SETTINGS

    L90POWER SYSTEM:MAX CHNLASYMMETRY:

    L90POWER SYSTEM:ROUND TRIPTI MECHANGE:

    RUN

    |Ch1T-Time New -Ch1T-TIMEOld| > CHANGE

    FLEXLOGICOPERAND

    87LDIFF1MAX ASYM

    FLEXLOGICOPERAND

    87LDIFF1TIME CHNG

    | Ch2Assymetry | > MAX

    RUN

    FLEXLOGICOPERAND

    87LDIFF2MAX ASYM

    FLEXLOGICOPERAND

    87LDIFF2TIME CHNG

       A   N   D

    Ch1Assymtery

    Ch1Round Trip Time

    SETTINGS

    L90POWERSYSTEM:BLOCK GPS TIMEREF:

    Off = 0

    FLEXLOGICOPERAND

    IRIG-B FAILURE

    87LGPS 1Status (OK=1)

    FLEXLOGICOPERAND

       A   N   D

       O   R

    |Ch2T-Time New -Ch2T-TIM EOld| > CHANGE

     ACTUALVALUES

    87LDIFFGPS2FAIL

    Ch2Assymtery

    FLEXLOGICOPERAND

     ACTUALVALUES

    DATA FROM REMOTE

    TERMINAL 1

       A   N   D

       O   R

    DATA FROM REMOTE

    TERMINAL 1

       A   N   D

       O   R

    DATA FROM REMOTE

    TERMINAL 2

    87LCh 2Status (OK=1)

    87LGPS2Status (OK=1)    A   N   D

       O   R

    RUN

     ACTUALVALUES

    RUN

    Ch2Round Trip Time

     ACTUALVALUES

    GPS function

    L90 Current Differential Relay:

    Channel asymmetry

    • Important consideration is fallback mode if GPS signal is

    lost: for example, relay can be programmed to continue

    to provide sensitive differential function using memorized

    value of last measured channel asymmetry until step

    change in the communications path is detected.

  • 8/19/2019 l90 Complete Agenda

    36/64

    36

    L90 Current Differential Relay:

    Channel asymmetry

    Asymmetry-disabled

    (about 3 ms of

    asymmetry present)

    Diff. Current

    high

    Asymmetry-enabled

    (about 3 ms of

    asymmetry present)Diff. Current

    low

    L90 Current Differential Relay:

    Channel asymmetry

    It’s beneficial to monitor

    differential current to

    raise an alarm if it

    becomes relatively high.

    This can happen due toasymmetry is present,

    problems in CT

    secondary. Flexelements

    are used for that.

  • 8/19/2019 l90 Complete Agenda

    37/64

    37

    L90 Current Differential Relay:

    Synchronization

    +

    ( 2 – 1)/2

    time stamps

    SystemFrequency

     ComputeFrequencyDeviation

    Ping-PongPhase

    Deviation

      Phase FrequencyLoop Filter 

    +

    +

    +

     _ 

    RELAY 1 RELAY 2

    f1f – f1

    GPSClock

    GPSPhaseDeviation

    1

    ( 2 – 1)/2

    +

    +

    +

    +

     _ 

    f2 f – f2

    2

    time stamps

    ComputeFrequencyDeviation

     Phase FrequencyLoop Filter 

    Ping-PongPhase

    Deviation

    GPSPhaseDeviation

    GPSClock

    ( 2 – 1)/2

    ( 2 – 1)/2

    Overall Relays synchronizationdiagram

    L90 Current Differential Relay:

    Synchronization

  • 8/19/2019 l90 Complete Agenda

    38/64

    38

    L90 Current Differential Relay:

    Frequency Tracking1. It is important for current differential to track the

    frequency to fit exactly 64 samples within one powercycle and to provide synchronized sampling at eachL90 relay.

    2. L90 starts tracking the frequency if current at anyterminal is above 0.125 pu

    3. L90 tracks the frequency from positive- sequencecurrent from all terminals.

    4. If positive-sequence current is below 0.125 pu, allrelays track to nominal frequency, 50 Hz or 60 Hz.

    5. Tracking frequency is displayed in ActualValues\Metering menu.

    L90 Current Differential Relay:

    Benefits

    • Increased Sensitivity w ithout sacrif icing Security:

     – Fast operation (11.5 cycles)

     – Lower restraint settings / higher sensitivity

     – Charging current compensation

     – Unique precise synchronization with frequency tracking

     – Channel Asymmetry Compensation

     – CT saturation detection

     – Dynamic restraint ensures security during noise, harmonics,CT saturation or transient conditions

     – Reduced CT requirements

     – Direct messaging

     – Increased redundancy due to master-master configuration

     – Reliable CRC-32 communication packet protection againstnoise

     – Breaker-and-a half applications

  • 8/19/2019 l90 Complete Agenda

    39/64

    39

    Lab: setting up 87L

    Direct point-to-point Fiber

    Test Set 1 Test Set 2

    L90 Current Differential Relay:

    Lab 1: Setting up 87L

    (64Kbps)

    Tx Rx

    Rx Tx

  • 8/19/2019 l90 Complete Agenda

    40/64

    40

    L90 Power System menu.

    L90 Current Differential Relay:

    Lab 1: Setting up 87L

    L90 system ischosen

    Charging currentenabled/disabled

    Channel IDenabled/disabled

    Channel IDenabled/disabled

    87L Current Differential menu.

    87L enabled

    Source chosen

    Pickup

    CT Tap

    L90 Current Differential Relay:

    Lab 1: Setting up 87L

  • 8/19/2019 l90 Complete Agenda

    41/64

    41

    L90 Current Differential Relay:

    Lab 1: Setting up 87L

    87L Current Differential menu.

    Slope 1

    Slope 2

    DTT

    External DTT

    L90 can accommodate CT ratios mismatch

    up to 5 times even if CTs secondary

    nominal current is different.

    1000/1 2000/5

    L90 Current Differential Relay:

    Lab 1: Setting up 87L

    (64Kbps)

    Tx Rx

    Rx Tx

  • 8/19/2019 l90 Complete Agenda

    42/64

    42

    Pickup

    Breakpoint

    (200% of I nominal)

    Restraint 1

    Restraint 2

    Current Differential major

    settings

    L90 Current Differential Relay:

    Lab 1: Setting up 87L

    This portion of logic will not

    reset for a continuous

    disturbance.

    Disturbance Detector-logic

    diagram

    L90 Current Differential Relay:

    Lab 1: Setting up 50DD

  • 8/19/2019 l90 Complete Agenda

    43/64

    43

    Disturbance Detector-element’s menu

    L90 Current Differential Relay:

    Lab 1: Setting up 50DD

    L90 Current Differential Relay:

    Lab 1 Comms Channel Check

    Channel Status menu- Actual

    Values\Statis\Channel Tests

  • 8/19/2019 l90 Complete Agenda

    44/64

    44

    L90 Current Differential Relay:

    Lab 1: Faults Simulation

    Direct point-to-point Fiber

    Test Set

    (64Kbps)

    Tx Rx

    Rx Tx

    87L should

    operate at the

    current…

    Direct point-to-point Fiber

    Test Set

    (64Kbps)

    Tx Rx

    Rx Tx

    87L should

    NOT operate

    L90 Current Differential Relay:

    Lab 1: 87L Characteristics Check

    Direct point-to-point Fiber

    Test Set 1 Test Set 2

    (64Kbps)

    Tx Rx

    Rx Tx

    Operate /

    Restraint

    Characteristics

  • 8/19/2019 l90 Complete Agenda

    45/64

    45

    L90 Current Differential Relay:

    Lab 1: 87L Characteristics Check

    User 87L settings

    Operate currentRestraint current

    Injected currents

    Relays response

    87LTRIPOP

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    87LTRIPOPA

    87LTRIPOPB

    87LTRIPOPC

    87LTRIP FUNCTION:

    AND

    AND

    AND

    AND

    SETTING

    SETTING SETTING

    SETTING

    SETTING

    SETTING

    IA IA >PICKUP

    IB IB >PICKUP

    IC IC> PICKUP

    Enable=1

    50DDSV

    1-Pole=0

    3-Pole=1

    87L TRIP SOURCE: 87L TRIP SEAL-IN PICKUP:

    87LTRIPSEAL-IN:

    87LTRIPSUPV:

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    87LDIFFOPA

    87LRECVDDTT A

    87LRECVDDTT B

    87LRECVDDTT C

    87LDIFFOPB

    87LDIFFOPC

    87LTRIPMODE:

    Enable=1

    Disable=0

    OR

    OR

    OR

    OR

    AND

    AND

    AND

    AND

    SETTING

    Off=0

    87LTRIPFORCE3- :

    FLEXLOGICOPERAND

    OPEN POLEOP

    OR

    OR

    OR

    OR

    OR0

    50

    OR

    OR

    OR

    OR

    AND

    AND

    AND

    L90 Current Differential Relay:

    87L Trip element

    87L Trip Logic

    87L and DTTare OR-ed

    Mode is hosen:

    1P or 3P

    Supervisingelement 50DD

  • 8/19/2019 l90 Complete Agenda

    46/64

    46

    87LTRIPOP

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    87LTRIPOPA

    87LTRIPOPB

    87LTRIPOPC

    87LTRIP FUNCTION:

    AND

    AND

    AND

    AND

    SETTING

    SETTING SETTING

    SETTING

    SETTING

    SETTING

    IA IA >PICKUP

    IB IB >PICKUP

    IC IC> PICKUP

    Enable=1

    50DDSV

    1-Pole=0

    3-Pole=1

    87L TRIP SOURCE: 87L TRIP SEAL-IN PICKUP:

    87LTRIPSEAL-IN:

    87LTRIPSUPV:

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    87LDIFFOPA

    87LRECVDDTT A

    87LRECVDDTT B

    87LRECVDDTT C

    87LDIFFOPB

    87LDIFFOPC

    87LTRIPMODE:

    Enable=1

    Disable=0

    OR

    OR

    OR

    OR

    AND

    AND

    AND

    AND

    SETTING

    Off=0

    87LTRIPFORCE3- :

    FLEXLOGICOPERAND

    OPEN POLEOP

    OR

    OR

    OR

    OR

    OR0

    50

    OR

    OR

    OR

    OR

    AND

    AND

    AND

    L90 Current Differential Relay:

    87L Trip element

    87L Trip Logic

    Logic to detectmulti-phaseevolving and

    sequential faults

    Seal-in outputs if

    desirable

    Open Poleforces 3P trip

    if anotherfault occursduring open

    poleconditions

    Outputs perphase or 3-phase

    Grouped elements

  • 8/19/2019 l90 Complete Agenda

    47/64

    47

    L90 Current Differential Relay:

    Grouped elements

    L90 Current Differential Relay:

    Grouped: Stub bus

    Line disconnect

    switch 52b contact

    IOC trigger 

  • 8/19/2019 l90 Complete Agenda

    48/64

    48

    Breaker Breaker  

    LineStub Bus

    zone

    + IOC

    L90 Current Differential Relay:

    Grouped: Stub bus

    L90 Current Differential Relay:

    Grouped: Distance

    L90 phase and ground distance is the same as D60 elements.

  • 8/19/2019 l90 Complete Agenda

    49/64

    49

    L90 backup distance is complimented by line pickup, power swing

    detection, POTT and load encroachment.

    L90 Current Differential Relay:

    Grouped: Distance

    L90 Current Differential Relay:

    Grouped: Breaker Failure

  • 8/19/2019 l90 Complete Agenda

    50/64

    50

    L90 Current Differential Relay:

    Grouped: Breaker Failure

    3- Pole Breaker Failure

    3- Pole Breaker Failure

    L90 Current Differential Relay:

    Grouped: Breaker Failure

  • 8/19/2019 l90 Complete Agenda

    51/64

    51

    3- Pole Breaker Failure

    L90 Current Differential Relay:

    Grouped: Breaker Failure

    3- Pole Breaker Failure

    L90 Current Differential Relay:

    Grouped: Breaker Failure

  • 8/19/2019 l90 Complete Agenda

    52/64

    52

    1- Pole Breaker Failure

    L90 Current Differential Relay:

    Grouped: Breaker Failure

    1- Pole Breaker Failure

    L90 Current Differential Relay:

    Grouped: Breaker Failure

  • 8/19/2019 l90 Complete Agenda

    53/64

    53

    L90 Current Differential Relay:

    Grouped: Open Pole Detector 

    Control elements

  • 8/19/2019 l90 Complete Agenda

    54/64

    54

    L90 Current Differential Relay:

    Control Elements

    Control elements

    available in L90

    Synchrocheck

    Logic

    L90 Current Differential Relay:

    Control: Synchrocheck

  • 8/19/2019 l90 Complete Agenda

    55/64

    55

    L90 Current Differential Relay:

    Control: Synchrocheck

    3-phase

    line VT

    1-phase

    bus VT

    Time that the twovoltages remain withinthe admissible angledifference

     AutoReclose sequence

    L90 Current Differential Relay:

    Control: AutoReclose

  • 8/19/2019 l90 Complete Agenda

    56/64

    56

     AutoReclose

    logic

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

     AR3-P/2RIP

    SETTING

    SETTING

     AND

    OR

    OR

    OR

    OR

    OR

    OR AND

    OR

     AND

     AND

     AND

     AND

     AND

    OR

    OR

     ARINCOMPLETESEQ.

    TIMER:

     ARLO

     ARINCOMPLETESEQ

     ARFORCE3PTRIP

     ARZONE1EXTENT

     RESET(tosheet 2)

    827089AD.CDR

     AR3-PDEADTIME2:

    0

    0

    OR

    OR

    SETTING

    SETTING

    Off =0

     AND

    OR

    OR

     AREXTENDDEADTIME

     1:

    CLOSE(topage 2)

     ARDEADTIME1

    EXTENSION:

    0

      (Topage2, Reset ARTRANSFERTIMER)

    To:ARFORCE3PTRIP 

    (Evolvingfault)

     ARINITIATE

    Evolvingfault

    BKRFAILTORECLS(fromsheet 2)

     ARDISABLED

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    FLEXLOGICOPERANDS

     AR1-PRIP

     AR3-P/1RIP

     ARENABLED

     ARDISABLED

    SETTING

    SETTING

    LO

    OR

    OR

    OR

     AND

    OR

     AND

     AND

    OR

    OR

    OR

     AND

     AND

     AR3-PDEADTIME1:

     AR1-PDEADTIME:

    0

    0

    SETTING

    0

     ARBLKTIMEUPON MAN

    CLS:

    FLEXLOGICOPERAND

     ARRIP

    0.5cycle

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    SETTING

     ARSHOTCOUNT>0

    PHASESELECTMULTI-P

    D60Relay OnlyFromPhaseSelector 

     ARPAUSE

    SETTING

    SETTING

    SETTING

    SETTING

    SETTING

    BKRONEPOLEOPEN:

    BKR3POLE OPEN:

     ARRESET:

     ARMULTI-PFAULT:

     ARM0DE:

    Off =0

    Off =0

    Off =0

    Off =0

    Off =0

    1& 3Pole

    1Pole

    3Pole- A

    3Pole-B

    OR

    OR

    SHOTCOUNT=MAX

    CLOSEBKR1ORBKR2

    RESET

    BKRONEPOLE OPEN

    BKR3POLE OPEN

       F  r  o  m  s   h  e  e   t   3

       D   6   0   R  e   l  a  y   O  n   l  y   F  r  o  m   T  r   i  p   O  u   t  p  u   t

    D60RelayOnly

       F  r  o  m   S   h  e  e   t   2

    FLEXLOGICOPERAND

    FLEXLOGICOPERAND

    SETTING

    TRIP1-POLE

    LINEPICKUP OP

    TRIPARINIT3-POLE

     AR3PTDINIT:

    SETTING

    SETTING

    SETTING

    SETTING

    Enable=1

    Disable=0

     ARFUNCTION:

     ARBLOCK:

     ARBKRMANCLOSE:

    BKRMA NUALCLOSE:

     AR1PINIT:

    Off =0

    Off =0

    Off =0

    SETTING

     AR3PINIT:

    Off =0

    Off=0

    OR

    (Fromsheet3)

    FLEXLOGICOPERAND

    5ms

    0

     ANDOR

    L90 Current Differential Relay:

    Control: AutoReclose

     AutoReclose

    logic

    BKRCLOSED(frompage3)

    RESET

    Tosheet 3

    LO

    LO

    LO

    LO

    AND

    AND

    827090A9.CDR

    2ms

    2ms

    OR

    OR

    OR

    OR

    S

    ROR

    Latch

    AND

    AND

    AND

    AND

    OR

    OR

    OR

    AND

    AND

    AND

    AND

    AND

    AND

    OR

    AND

    AND

    L90 Current Differential Relay:

    Control: AutoReclose

  • 8/19/2019 l90 Complete Agenda

    57/64

    57

     AutoReclose

    logic

    L90 Current Differential Relay:

    Control: AutoReclose

    This piece of the AR is

    reading status of

    breaker(s) and feeds

    main AR logic to

    proceed action further

    accordingly number of

    breakers, mode chosen

    and sequence chosen.

    Breaker Function AutoReclosure Function

    LEDs

    L90 Current Differential Relay:

    Control: AutoReclose

    Breakers are set inSystem Setup\

    Breakers

     AR is set per user ’srequirements (reads

    breakers status

    automatically) LEDs are needed to

    know AR ststus

  • 8/19/2019 l90 Complete Agenda

    58/64

    58

    CT Fail Detector is designed to detect

    failures in CT secondary circui try

    L90 Current Differential Relay:

    Control: CT Fail Detector 

    L90 Current Differential Relay:

    Control: VT Fuse Fail

  • 8/19/2019 l90 Complete Agenda

    59/64

    59

    POTT scheme requires 1-bit

    comms channel, for example

    PLC.

    L90 Current Differential Relay:

    Control: POTT

    L90 1

    Line 2

    Line 1

    C60 3

    L90 1-2 LAN

    L90 2

    B3

    B2

    B1

    B4

    Substation 1

    Ethernet

    Substation

    2

    B5

    Ethernet

    L90 Current Differential Relay:

    Direct Inputs and Outputs

  • 8/19/2019 l90 Complete Agenda

    60/64

    60

    L90 Current Differential Relay:

    Direct Inputs and Outputs

    This is activein 3-terminal

    only

    Defaultmeans state

    whenchannel is

    brokenDirect

    Outputs areassigned with

    Flexlogicoperands

    L90 Current Differential Relay:

    Direct Inputs and Outputs

    Channel statuscontrols either

    Direct Input is readfrom the received

    data or set todefault

  • 8/19/2019 l90 Complete Agenda

    61/64

    61

    Local Relay Remote Relay

    L90 Current Differential Relay:

    Direct Inputs and Outputs

    Direct Input 1-1 (BFat remote S/S) isassigned to a trip

    gate.

    Example

    Breaker Fail isassigned to Direct

    Output 1-1

    Monitoring & Metering

  • 8/19/2019 l90 Complete Agenda

    62/64

    62

    L90 Current Differential Relay:

    Metering: 87L

    L90 Current Differential Relay:

    Oscillography: 87L analogs

  • 8/19/2019 l90 Complete Agenda

    63/64

  • 8/19/2019 l90 Complete Agenda

    64/64

    Thank you.