Installation, Operation, Maintenance Instructions, and Parts List

Medical Hose ReelPart number 4107 9028 58.00November 9, 2020

U.S. Design Patent No. D734,854

Page 2: Installation, Operation, Maintenance Instructions, and
Page 3: Installation, Operation, Maintenance Instructions, and

Part number 4107 9028 58.00November 9, 2020

Installation, Operation, Maintenance Instructions, and Parts List

Medical Hose Reel

This unit is purchased from:

Date purchased:

Model number:

Serial number:

Option(s) included:

Any information, service or spare parts requests should include the machine serial number and be directed to:

BeaconMedæs USA1059 Paragon WayRock Hill, SC 29730United StatesPhone: (803) 817-5600Fax: (803) 817-5750www.beaconmedaes.com

BeaconMedæs reserves the right to make changes and improvements to update products sold previously without notice or obligation.

Page 4: Installation, Operation, Maintenance Instructions, and

Table of Contents

1.0 Introduction ................................................................1-12.0 Unpacking Hose Reel .................................................2-13.0 Mounting Box Installation .........................................3-14.0 Hose Reel Installation ................................................4-15.0 Cover Plate Installation .............................................5-16.0 Operating Instructions ...............................................6-17.0 Replacement Components ........................................7-1

Medical Hose Reel

4107 9028 58.00 i

Page 5: Installation, Operation, Maintenance Instructions, and

Revision Description Date00 Initial release November 9, 2020

Revision History

ii 4107 9028 58.00

Medical Hose Reel

Page 6: Installation, Operation, Maintenance Instructions, and

Definition of StatementsStatements in this manual preceded by the following words are of special significance.

WARNING: Means there is a possibility of injury or death to yourself or others.

CAUTION: Means there is a possibility of damage to the unit or other property.

NOTE: Indicates points of particular interest for more efficient and convenient operation.

Packing list

WARNING: Keep all parts and tools free of oil, grease, and dirt. Failure to do so may result in fire.

Description Single Service Qty Double Service QtyHose Reel - Complete Assembly with Rough-in Box 1 1Cover plate assembly 1 1Grommet half 2 4Retaining ring 1 2Panel plug 1 -Screw, 6-32 x 1 LG 4 4Tie plate (for gang mounting) - 1Screw, 1/4-20 x 5/8 LG (for gang mounting) - 4Nut, 1/4-20 (for gang mounting) - 4Screw, 6-32 x 1/4 LG (for gang mounting) - 4Speed nut, 6-32 (for gang mounting) - 4

Medical Hose Reel

4107 9028 58.00 iiiii

Page 7: Installation, Operation, Maintenance Instructions, and

1.0 IntroductionLocation, sequence of services and orientation of Hose Reels are specified on building plans. Be certain installation is in agreement with these specifications. All piping, testing, and verification of services should conform to National Fire Protection Association (NFPA) 99, “Standard for Health Care Facilities” and local codes where applicable. Reel mounting box must be installed before ceiling is finished.

Tools and Supplies Needed for Hose ReelInstallation• Wrenches:

11/16”, 3/4”, 13/16”, 7/8” AND 1/2” socket

• Phillips screwdriver• Copper tube silver brazing equipment

Before You Begin1. Notify facility you will be installing unit

into gas piping system.2. Verify interruption/connection into gas

piping system has been authorized

1-1 4107 9028 58.00

Medical Hose Reel

Page 8: Installation, Operation, Maintenance Instructions, and

2.0 Unpacking Hose Reel 1. Carefully open shipping carton and

remove contents. Verify complete contents per packing list.

2. Remove dust cover from mounting box (Figure1). Save for later use.

Figure 13. Remove two hex head anchor bolts

and washers holding reel assembly to mounting box (Figure 2).

4. Remove two acorn nuts from guide rods (Figure 2).

5. Lift reel assembly out of mounting box, sliding it up guide rods (Figure 3).

6. Reinstall anchor bolts with washers and acorn nuts on ends of guide rods in mounting box (Figure 4).

NOTE:

The following steps in this section detail how to remove the reel assembly from the mounting box (rough-in box). Installing the mounting box first may be easier, especially if the installation is performed by only one person. If the installation is performed by two people, it may not be necessary.

Anchor Bolt

Guide Rod

Acorn Nut

Lock Washer

Figure 2

Figure 3

Medical Hose Reel

4107 9028 58.00 2-1

Page 9: Installation, Operation, Maintenance Instructions, and

7. Place reel assembly and cover plate back into shipping carton. Close carton and store in a protected location until time to install.

Figure 4

Medical Hose Reel

4107 9028 58.00 2-2

Page 10: Installation, Operation, Maintenance Instructions, and

3.0 Mounting Box Installation

3. If gang mounting boxes, join support channels of ganged mounting boxes together as shown using 1/4-20 x 5/8 bolts, lockwashers, and nuts provided (Figure 8).

1. Construct rigid framework to support mounting box. Framework must place bottom edge of box flush with finished ceiling line (Figure 5). Figure 6 shows required rough ceiling openings and single box dimensions. Figure 7 shows required dimensions for gang mounting of boxes. This is important for proper alignment of cover plates when gang mounting several hose reel assemblies.

2. Orient mounting boxes to ensure gas service inlet tubes agree with building plans.

Finished Ceiling Line

Hose ReelMounting Box

Rigid Framework(furnished by others)

10-1/2”

9/16” Dia Hole

Support Channel

Inlet Tube

10-5/8” 13-3/8”

10-1/2”

5”

6-1/2”

13-3/8”

Single/Double 11-3/4”

5-Gang6-Gang 35-1/4”

Triple/Quad 23-1/2”

Bolt Here

Figure 5

Figure 7

Figure 6

Figure 8

3-1 4107 9028 58.00

Medical Hose Reel

Page 11: Installation, Operation, Maintenance Instructions, and

4. If gang mounting boxes, install (4) speed nuts onto mounting box as shown (Figure 9). Place tie plate onto mounting box as shown in Figure 10 and secure using (4) 6-32 x 1/4” screws provided.

5. Securely anchor mounting box(es) to framework installed in Step 1 of this section. Make certain box(es) are correctly oriented.

6. Connect system piping drops to corresponding copper inlet tubes.

Figure 9

Figure 10

Figure 11

Speed Nuts

Tie Plate

WARNING:

It is the installer’s responsibility to verify all gas piping systems are correctly connected and tested per NFPA 99 and applicable local codes.

7. Securely install test caps on vacuum and WAGD DISS fitting of inlet tube. Pressure gas services do not require test caps.

8. Complete initial pressure tests for all pressure gas, vacuum and WAGD services per NFPA-99.

9. Install dust cover(s) on mounting box(es) to prevent dust and debris from entering box during finishing of ceiling (Figure 11).

10. Retain these instructions for use when installing reel assembly and cover plate after ceiling has been finished.

Medical Hose Reel

4107 9028 58.00 3-2

Page 12: Installation, Operation, Maintenance Instructions, and

4.0 Hose Reel Installation

WARNING:

It is the installer’s responsibility to verify all gas piping systems are correctly connected and tested per NFPA 99 and applicable local codes.

1. Remove dust cover from mounting box and discard.

2. Remove acorn nuts from ends of guide rods, and anchor bolts and washers from mounting box.

3. Orient reel assembly to ensure gas labeling on reel assembly matches DISS fittings inside mounting box.

4. Align diagonal holes on base of reel assembly with guide rods, and slide reel assembly up guide rods. Hold reel assembly in place while installing two acorn nuts on end of each guide rod (Figure 12). Allow reel assembly to rest on acorn nuts (Figure 13).

Figure 12

Figure 13

Figure 14

Figure 15

5. Push reel assembly up into mounting box until it rests against top of box. Secure reel assembly to top of mounting box using two anchor bolts with lockwashers (Figure 14).

Anchor Bolt

6. Verify gas service label on hose assembly matches gas indexing of DISS valve. Connect hoses (Figure 15).

NOTE:

The following steps in this section detail how to reinstall the reel assembly if it was previously removed from the mounting box.

4-1 4107 9028 58.00

Medical Hose Reel

Page 13: Installation, Operation, Maintenance Instructions, and

7. Perform Standing Pressure Test for Positive Pressure Medical Gas Piping as outlined in NFPA-99 at 20% above normal pipeline pressure. Perform Standing Vacuum Test for Vacuum System as Outlined in NFPA-99 on all Vacuum and WAGD services.

CAUTION:

Pressurization of vacuum or WAGD finish assemblies may damage swivel seals. Perform vacuum tests on these assemblies as outlined in NFPA-99, Standing Vacuum test for Vacuum System.

4-2 4107 9028 58.00

Medical Hose Reel

Page 14: Installation, Operation, Maintenance Instructions, and

NOTE:

Cover plates require some assembly. Cover plate inner panel and hose guide grommets must be installed before mounting cover plate.

1. Remove cover plate assembly from shipping carton. Remove two screws holding inner panel in center of cover plate (Figure 16).

2. Extend hose(s) several feet from mounting box.

3. Route each hose-end valve and adjustment stop on hose assembly through opening in cover plate and into circular openings on each side of cover plate (Figure 17). Be certain cover plate is oriented properly to mounting box.

Screws

Inner Panel

Figure 16

Figure 17

Figure 18

Adjustment Stop

Hose End Valve

4. Reinstall inner panel back onto cover plate.

5. Remove two-piece hose guide grommet and retaining ring from plastic shipping bag.

6. Install hose guide grommet(s) from front of cover plate and secure to cover plate assembly using retaining ring(s) (Figure 18).

7. Place plastic panel plug over unused hole in cover plate assembly if applicable.

Retaining Ring

Grommet Half (2 per service)

5.0 Cover Plate Installation

Medical Hose Reel

4107 9028 58.00 5-1

Page 15: Installation, Operation, Maintenance Instructions, and

8. Slide cover plate assembly up hose(s) to mounting box. Be certain hoses are hanging straight down and not looped around guide rods or anchor bolts. Fasten cover plate assembly to mounting box using (4) 6-32 x 1 screws provided (Figure 19).

9. Adjust hose length per operating instructions.

WARNING:

It is the installer’s responsibility to verify all gas piping systems are correctly connected and tested per NFPA 99 and applicable local codes.

Cover plateMounting

Screws(2 per side)

Figure 19

5-2 4107 9028 58.00

Medical Hose Reel

Page 16: Installation, Operation, Maintenance Instructions, and

6.0 Operating InstructionsTo Extend HosePull hose out slightly past desired length and allow it to slowly retract until reel catches and holds.

To Retract HosePull hose out a few inches to disengage reel and let it retract. Hold onto hose to control rate of ascent.

To Adjust Hose Hanging LengthExtend hose. Slide stop up or down hose until desired hanging length is achieved.

Adjust Stop for Desired Length

Figure 20

Medical Hose Reel

4107 9028 58.00 6-1

Page 17: Installation, Operation, Maintenance Instructions, and

7.0 Replacement ComponentsItem Part Number Description

1. 10” long hose assembly between mounting box DISS valve fitting and swivel joint assembly (Item 3) with a DISS nut and nipple on one end and 1/4” NPT male on the other.

132330-00 Oxygen132331-00 Nitrous Oxide132332-00 Medical Air132333-00 Vacuum132347-00 WAGD132334-00 Nitrogen132335-00 Carbon Dioxide132336-00 Instrument Air

2. 12’ long hose assembly for reel with a DISS nut and nipple on one end and hose end valve on the other. Assembly includes Item 8.

ServiceModel Number of Hose Assembly with Hose-End Valve Type

DISS Puritan-Bennet Quick Connect

Chemetron Quick Connect

Medaes Quick Connect

Schrader Quick Connect

Oxygen 132610-00 132510-00 132810-00 132710-00 ---Nitrous Oxide 132611-00 132511-00 132811-00 132711-00 ---Medical Air 132612-00 132512-00 132812-00 132712-00 ---Vacuum 132613-00 132513-00 132813-00 132713-00 ---WAGD 132619-00 132519-00 132819-00 132719-00 N/ANitrogen 132614-00 --- --- --- 132314-00Carbon Dioxide 132620-00 --- --- --- ---Instrument Air 132618-00 --- --- --- ---

3. Swivel joint assembly:230676-00 Oxygen, nitrous oxide, medical air, nitrogen, carbon dioxide and instrument air.230677-00 Vacuum and WAGD

4. Adapter (no check valve). DISS male x 1/4” NPT male.513001-00 Oxygen520395-00 Nitrous Oxide520396-00 Medical Air520287-00 Vacuum515606-00 WAGD511554-00 Nitrogen520288-00 Carbon Dioxide515558-00 Instrument Air

5. 4107 6567 50 90° compression elbow (1/4-18 NPT female x 3/8 OD tube)6. 4107 6567 51 Tubing connector (3/8 OD tube)7. 4107 6567 49 90° compression elbow (1/4-18 NPT male x 3/8 OD tube)8. 655000-00 Hose stop9. 4107 6567 30 Grommet-half (2 required per service)

10. 4107 6567 31 Retaining ring11. 1310 0464 34 Spring lock washer (for 5/16 screw; 2 required per assembly)12. 4107 6568 03 Acorn nut (5/16-18; 2 required per assembly)13. 4107 6568 02 Anchor bolt assembly (5/16-18 x 10 long; 2 required per assembly)14. See 4107 4021 15 below Cover plate inner panel15. See 4107 4021 15 below Cover plate16. 0160 3590 65 Phillips head screw (6-32 x 1 long; 4 required per assembly)17. See 4107 4021 15 below Phillips head screw (6-32 x 1/4 long; 2 required per assembly)

--- 4107 4021 15 Cover plate assembly (includes items 14, 15, and 17, as well as cover plate inner panel service instructions decal and cover plate BeaconMedaes logo decal)

--- 836835-00 Panel plug (for single service assemblies)

7-1 4107 9028 58.00

Medical Hose Reel

Page 18: Installation, Operation, Maintenance Instructions, and

1

5

4

3

2

6

7

18

17

16

15

14

13

12

11

8

9

10

Medical Hose Reel

4107 9028 58.00 7-2

Page 19: Installation, Operation, Maintenance Instructions, and
Page 20: Installation, Operation, Maintenance Instructions, and

BeaconMedaes USA1059 Paragon WayRock Hill, SC 29730United StatesPhone: (803) 817-5600Fax: (803) 817-5750