electrical system design_branch ckt
TRANSCRIPT
-
7/25/2019 Electrical System Design_branch Ckt
1/23
RESONANZ TG Inc.
making innovative solutions...CENTER FOR PROFESSIONAL DEVELOPMENT
IN ENGINEERING & TECHNOLGY
TRAINING WORKSHOP IN
ELECTRICAL SYSTEM DESIGN
Motor Circu i t Calculat ion
-
7/25/2019 Electrical System Design_branch Ckt
2/23
RESONANZ TG Inc. making innovative solutions...
About the Speaker: Gener G. Restubog
Registered Electrical Engineer
2009 President IIEE Northern Laguna Chapter
Education M. of Engg Elect Engg Adamson University, Manila
M.Sci in Elect Engg (Units Earned), University of the Phils Diliman QC
B.Sci in Elect Engg, Central Colleges of the Phils, QC
Current Job/Affiliations
Sr Partner & Head, Training & Consulting Resonanz TG Inc
Consultant - Tricore Solutions, Inc Engineering Faculty De Lasalle UniversityDasmarinas
Engineering Faculty Technological Inst of the Phils - Quezon City
Engineering Faculty University of Perpetual Help System Laguna
Former Electrical Design Manager GHD Pty Limited
Former Facility Design Manager Intel Technology Phils
Former Designer Proj Manager Trans-Asia Phils. Framegroup Mgt System
Former Electrical Design Engineer Trans-Asia Phils, Kinhill-Tan Spore, TCGI Engrs Former Engineering Faculty Member Lyceum Univ-Laguna, PLM, MFI, CCP
Experience
Over 24 years experience in engineering design, consultancy, construction, andteaching of electrical engineering
-
7/25/2019 Electrical System Design_branch Ckt
3/23
RESONANZ TG Inc. making innovative solutions...
Design CalculationMotor Branch Ckts & Feeders
-
7/25/2019 Electrical System Design_branch Ckt
4/23
RESONANZ TG Inc. making innovative solutions...
AC Motors
Branch Circuits & Feeders
Source: NEC Handbook: W.M. Earley
-
7/25/2019 Electrical System Design_branch Ckt
5/23
RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
Motor Circuit Conductor
Single Motor, PEC 4.30.2.2
Conductors that supply a single motor used in a continuous duty application shall have
an ampacity of not less than 125 percent of the motor full-load current rating, as
determined by 4.30.1.6(A)(1), or not less than specified in 4.30.2.2 (A) through (F).
Several Motors or a Motor(s) and Other Load(s). PEC 4.30.2.4
Conductors supplying several motors, or a motor(s) and other load(s), shall have an
ampacity not less than the sum of each of the following:
125 percent of the full-load current rating of the highest rated motor, plus the
sum of the full-load current ratings of all the other motors in the group, as
determined by 4.30.1. 6(A) plus the sum of other loads
-
7/25/2019 Electrical System Design_branch Ckt
6/23
RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
Motor and Branch-Circuit Overload Protection
Continuous-Duty Motors - More Than 1 Horsepower
A separate overload device that is responsive to motor current. This device shall be
selected to trip or shall be rated at no more than the following percent of the motor
nameplate full-load current rating:
Motors with a marked service factor 1.15 or greater 125%Motors with a marked temperature rise 40C or less 125%
All other motors 115%
Larger Than 1500 Horsepower.
For motors larger than 1500 hp, a protective device having embedded temperature
detectors that cause current to the motor to be interrupted when the motor attains a
temperature rise greater than marked on the nameplate in an ambient temperature of
40C.
-
7/25/2019 Electrical System Design_branch Ckt
7/23RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
Motor and Branch-Circuit Short Circuit and Ground Fault Protection
PEC Section 4.30.4.2
In Accordance with Table 4.30.4.2. A protective device that has a rating or
setting not exceeding the value calculated according to the values given in
Table 4.30.4.2 shall be used. (With exceptions)
-
7/25/2019 Electrical System Design_branch Ckt
8/23RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design CalculationTable 4.30.4.2 Maximum Rating or Setting of Motor Branch-Circuit Short-Circuit and
Ground-Fault Protective Devices
-
7/25/2019 Electrical System Design_branch Ckt
9/23RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
Motor Feeder Short Circuit and Ground Fault Protection
Rating or Setting Motor Load and Other Load(s). Where a feeder supplies
a motor load and other load(s), the feeder protective device shall have a
rating not less than that required for the sum of the other load(s) plus the
following (PEC Section 4.30.5.3)
(1) For a single motor, the rating permitted by 4.30.4.2
(2) For a single hermetic refrigerant motor-compressor, the rating permitted
by 4.40.3.2
ICB
=< 175% - 225% of motor rated-load current or branch-circuit
selection current, whichever is greater
-
7/25/2019 Electrical System Design_branch Ckt
10/23RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
Motor Feeder Short Circuit and Ground Fault Protection
(3) For two or more motors, the rating permitted by 4.30.5.2
a) ICB= PEC Section 4.30.2.4)
Exception: Where the feeder overcurrent device provides the overcurrent
protection for a motor control center, the provisions of 4.30.8.3 shall apply.
-
7/25/2019 Electrical System Design_branch Ckt
11/23RESONANZ TG Inc. making innovative solutions...
Example 1
A three-phase, 460 volts, 60Hz, 25-Hp squirrel cage induction motor is to be
connected for full voltage starting. It has a full load current of 31.6 amperes, a
service factor of 1.15 and a Code Letter F in its nameplate. The ambienttemperature of the place of installation is 40C.
Total Load : (See Table 4.30.14.4)
Full load current of 3-phase, 25-Hp motor = 34 Amperes
Note : The full load current value used to determine the ampacity of conductors formotors shall be based on Table 4.30.14.4
Motor Branch Ckts & Feeders
-Design Calculation Single Motor
-
7/25/2019 Electrical System Design_branch Ckt
12/23RESONANZ TG Inc. making innovative solutions...
Table 4.30.14.4 Full-Load Current , Three Phase AC Motors
-
7/25/2019 Electrical System Design_branch Ckt
13/23
RESONANZ TG Inc. making innovative solutions...
AC Motors
Namplate Rating
-
7/25/2019 Electrical System Design_branch Ckt
14/23
RESONANZ TG Inc. making innovative solutions...
Branch Circuit Conductors : [See Section 4.30.2.2(a)]
125% of Full Load Current:
34 Amperes x 1.25 = 42 Amperes
Use 3-14mm THW wires
Note : Ampacity of 14mm THW at 40C ambient is 55 Amperes x 0.88 = 45
Amperes. See Table 3.10.1.16 for ampacity correction factors.
Motor and Branch Circuit Overload Protection : [See Section 4.30.3.2(a)]
125% of Rated Full Load Current :
31.6 Amperes x 1.25 = 39 Amperes (Maximum)
Motor Branch Ckts & Feeders
-Design Calculation Single Motor
-
7/25/2019 Electrical System Design_branch Ckt
15/23
RESONANZ TG Inc. making innovative solutions...
Branch Circuit Short-Circuit and ground Fault Protection:
(See Section 4.30.4.2)
The branch circuit maybe protected by any of the four common types of
protective devices, namely: Nontime delay fuse, Time delay fuse,
Instantaneous trip breaker and Inverse time breaker.
For the protection of a squirrel cage breaker with Code Letter F (See Table4.30.4.2) the protective device can be any of the following:
Nontime Delay (NTD) Fuses: ( See Table 4.30.4.2)
300% of Full Load Current:
34 Amperes x 3 = 102 Amperes Use 100 Amperes NTD fuse.
Note : If the 100-A fuse is not sufficient for the starting current of the motor, see
Section 4.30.4.2(c)(1) Exception No. 2a.
Motor Branch Ckts & Feeders
-Design Calculation Single Motor
-
7/25/2019 Electrical System Design_branch Ckt
16/23
RESONANZ TG Inc. making innovative solutions...
Time Delay (TD) Fuses : (See Table 4.30.4.2)
175% of Full Load Current:
34 Amperes x 1.75 =59 Amperes
Use 60 Amperes TD fuse ( See section 4.30.4.2(c) Exception No. 2b).
Instantaneous Trip (IT) Breaker : (See Table 4.30.4.2)
175% of Full Load Current:34 Amperes x 7 =238 Amperes
Use 250 Amperes IT circuit breaker (See Section 4.30.4.2(c) Exception
No.1)
Inverse Time Delay (ITD) Breaker : (See Table 4.30.4.2)
250% of Full load Current :34 Amperes x 2.5 = 85 Amperes
Use 90 Amperes ITD circuit breaker.
Motor Branch Ckts & Feeders
-Design Calculation
-
7/25/2019 Electrical System Design_branch Ckt
17/23
RESONANZ TG Inc. making innovative solutions...
Example 2
Three squirrel cage induction motor: 25-Hp, 20-Hp and 10-Hp, all rated at 460
volts, 3-phase, 60-Hz are to be served by a feeder circuit. Ambient
temperature does not exceed 30C.
Total Load :( see Table 4.30.14.4)
One 3-phase, 460 volts, 25-Hp motor = 34 Amperes
One 3-phase, 460 volts, 20-Hp motor = 27 Amperes
One 3-phase, 460 volts, 10-Hp motor = 14 Amperes
25% of Largest Motor ( see Section 4.30.2.4)
34 Amperes x 0.25) = 8.5 Amperes
Net Computed Current = 83.5 Amperes
Feeder Conductors : ( See Table 3.10.1.16)
Use 3-22mm THW wires.
Motor Branch Ckts & Feeders
-Design Calculation Multiple Motors
-
7/25/2019 Electrical System Design_branch Ckt
18/23
RESONANZ TG Inc. making innovative solutions...
Feeder Circuit Protection : [See Section 4.30.4.3(c)]
Largest Protective Device:
The 25-Hp motor being the largest motor, has the largest protective device.
Nontime Delay (NTD) Fuses:
Largest NTD fuse = 100 Amperes
Full load current of 20-Hp motor = 27 Amperes
Full load current of 10-Hp motor = 14 Amperes
Total Computed Current = 141 Amperes
Use 150 Amperes NTD fuse.
Motor Branch Ckts & Feeders
-Design Calculation Multiple Motors
-
7/25/2019 Electrical System Design_branch Ckt
19/23
RESONANZ TG Inc. making innovative solutions...
Time Delay (TD) Fuses:
Largest TD fuse = 60 Amperes
Full load current of 20-Hp motor = 27 Amperes
Full load current of 10-Hp motor = 14 Amperes
Total Computed Current = 101 Amperes
Use 150 Amperes TD fuse.
Inverse Time Delay (ITD) Breaker:
Largest NTD fuse = 90 Amperes
Full load current of 20-Hp motor = 27 Amperes
Full load current of 10-Hp motor = 14 AmperesTotal Computed Current = 131 Amperes
Use 125 Amperes NTD breaker.Note : Only fuses and/or inverse time circuit breakers are allowed for this type of
installation. [(See Section 4.30.4.3(c)(1)].
Motor Branch Ckts & Feeders
-Design Calculation
-
7/25/2019 Electrical System Design_branch Ckt
20/23
RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
-
7/25/2019 Electrical System Design_branch Ckt
21/23
RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
-
7/25/2019 Electrical System Design_branch Ckt
22/23
RESONANZ TG Inc. making innovative solutions...
Motor Branch Ckts & Feeders
-Design Calculation
-
7/25/2019 Electrical System Design_branch Ckt
23/23
References:
1. IEEE Std 241-1990 Recommended Practice for Electric PowerSystem in Commercial Buildings
2. IEEE Std 141-1993 IEEE Recommended Practice for ElectricPower Distribution for Industrial Plants
3. Philippine Electrical Code 2009
4. National Electrical Code 2011
5. Eaton Cuttler-Hammer Catalogue
6. Designing Electrical System, James Stallcup
7. NEC Handbook, McPartland
8. NEC Handbook, W.M Earley