power system modeling and fault analysis of nampower’s 330 kv hvac transmission line
TRANSCRIPT
Journal of Energy and Power Engineering 8 (2014) 1432-1442
Power System Modelling and Fault Analysis of
NamPower’s 330 kV HVAC Transmission Line
Innocent Davidson and Immanuel Mbangula
HVDC/Smart Grid Research Centre, University of KwaZulu-Natal, Durban 4041, South Africa
Received: December 20, 2013 / Accepted: March 21, 2014 / Published: August 31, 2014.
Abstract: Electric power systems usually cover large geographical areas and transmission facilities are continuously increasing. These power systems are exposed to different environmental conditions which may cause faults to occur on the system. Different types of studies are usually done on electric power systems to determine how the system behaves before, during and after a fault condition. The behaviour of variables of interest such as currents, voltage, rotor angle and active and reactive power under fault conditions are studied and observed to help determine possible causes of faults in a power system. The objective of this paper is to investigate a fault that occurred on the 330 kV transmission line between Ruacana power station and Omburu sub-station, the fault caused all the generators at Ruacana power station to trip and consequently caused a blackout at the power station that lasted for 6 h. Preliminary findings showed that the observed fault was an earth fault but the exact type of earth fault was however not known at the time. This research investigation sets out to determine the exact fault that occurred; the most probable cause of the fault, and propose possible solutions to prevent reoccurrence of such a fault. The section of the power network in which the fault occurred was modelled using DigSilent Power Factory software tool, and transient fault analysis was carried out on the model for different fault conditions. Results obtained were then compared with data obtained from NamPower records to ascertain the type of fault. Key words: Fault analysis, power system, transient stability.
1. Introduction
A disturbance in one section of the power network
propagates to remote points of the system. Fault
analysis aims to quantify waveforms of interest, such
as currents and voltages, under extraordinary
operating conditions [1]. The magnitude of the fault
currents give the engineer the current settings for the
protection to be used and the ratings of the circuit
breakers [2]. A fault occurred on the 330 kV
transmission line between Ruacana power station and
Omburu substation, causing the line to trip on March
18, 2012. Omburu substation is the hub that evacuates
power generated from the 330 MW Ruacana Hydro
power station into the Namibian grid.
Preliminary investigations of the fault suggest that
the line trip was caused by an earth fault. The fault
Corresponding author: Innocent Davidson, director,
research fields: modern electric power systems, smart grids and clean energy technologies. E-mail: [email protected].
caused the CB (circuit breaker) at Omburu sub-station
to trip, 1.7 s later the CB near Ruacana power station
tripped as well. The tripping of the transmission line
caused all the generators at the power station to go
out of step and trip and therefore caused a major
power outage which lasted for 6 h, before the
generators were re-excited, ran up and power supply
restored.
The observed fault was classified as transient
disturbance on the power network, and it caused
transient instability of the power system. Faults that
occur on power networks are usually of different
origins, a fault may originate from a mechanical,
electrical or operational error [3]. Various methods are
used for mitigation against faults that occur on electric
power networks. These methods are therefore used to
increase the stability of the power system. Ruacana
hydro power station is Namibia’s only hydro-electric
power station [4]. It has Namibia’s single largest
D DAVID PUBLISHING
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1433
installed generation capacity of 332 MW, which
makes up 67% of the total power generated. Any
major disturbance that occurs at or affects Ruacana
power station will have a negative impact on the
Namibian power system. It is therefore crucial to
ensure that severe faults on the national grid are
minimal, especially those that might significantly
affect the generators at Ruacana or any other power
stations in Namibia.
A reliable and stable network ensures that the
security of power supply is not compromised.
Reliability is the ability of the power system to supply
the aggregate electric power and energy requirements
of the customer at all times [5]. The stability of a
power system is its ability to return to normal or stable
operation after having being subjected to some form
of disturbance [3]. This is achieved with a significant
reduction in power outages due to any various
disturbances on the network such as major faults.
Section 2 of this paper gives a brief review of
literature on faulted power systems and power systems
stability. In Section 3, the modelling of the faulted
section of the power system is done. Presentation and
analysis of the simulation results is done in Section 4.
Conclusions drawn based on the simulation results are
given in Section 5. Fig. 1 shows Namibia’s
transmission grid and the major power generation and
transmission stations. Table 1 shows NamPower’s
plant portfolio.
Table 1 NamPower’s generation portfolio [4].
Power station Installed generation capacity (MW)
Ruacana hydroelectric power station 332
Van Eck coal fired power station 120
Paratus diesel generator power station 24
Anixas heavy-fuel power station 22.5
Fig. 1 Namibia’s high voltage electric power transmission system [4].
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1434
2. Literature Review
2.1 Faulted Power Systems
A fault in electrical power systems is the
unintentional and undesirable creation of a conducting
path (a short circuit) or blockage of current (an open
circuit) [6]. Some indicators of an abnormal condition
on the power system are: over speed of generators and
motors, overvoltage and under-voltage, under
frequency, loss of excitation of generators,
overheating stator and rotor of an alternator [3]. Faults
are divided into two main classes: symmetrical faults
and unsymmetrical faults [7]. Three phase faults are
called symmetrical faults [8]. In a three phase fault, all
the three phases of the transmission line are short
circuited. The three phases may either be short
circuited without being short-circuited to ground
(L-L-L fault) or they may be short circuited to ground
(L-L-L-G). Symmetrical faults are usually treated as
standard faults for determining the fault level of the
electrical power system. Open circuit faults occur
when one or more phase conductor breaks or a joint
on the overhead lines fails. Such situations may also
arise when all three phases of a circuit breaker fails [9].
The most severe type of fault is a three-phase short
circuit [10].
2.2 Power Systems Stability
The observed fault is said to have caused transient
instability on the system. The cost of losing
synchronous through transient instability is extremely
high in modern power systems. Consequently, utility
engineers often perform a large number of stability
studies in order to avoid the problem from reoccurring
[11]. Under steady state condition, there is equilibrium
between the input mechanical torque and the output
electrical torque of each machine and the speed
remains constant [12]. It is important for the system to
be stable because the maximum power transmittable,
the stability limit under a fault condition, is less than
that for the corresponding steady-state condition [9]. It
is therefore important to ensure that the electric power
system is stable at all times in order to allow for
maximum power flow and the generation of voltage at
system frequency and at the same phase angle for all
the machines [6].
Power system stability is classified into three main
classes, namely: steady state stability, transient
stability and small-signal or dynamic stability. Steady
state stability relates to the response of a synchronous
machine to a gradually increasing load [10]. Transient
stability involves the response of synchronous
machines to large disturbances [13]. A power system
is transiently stable if it reaches an acceptable steady
state operating condition following a large disturbance
[14]. Dynamic stability is the ability of the power
system, when operating under given load conditions,
to retain synchronism when subjected to small
disturbances [2].
When a fault occurs, a number of measures can be
taken to prevent the instability limit from being
crossed: when these measures are taken at generator,
network or load level, they either prevent instability
due to the fault or help fight against it effectively right
from the start [15]. Examples of methods used to
enhance transient stability of a power system are: the
use of high mechanical inertia of generator sets, high
speed re-closure of circuit breakers [16], high speed
fault clearing, reduction of transmission system
reactance, regulated shunt compensation, reactor
switching, controlled system separation and load
shedding [17].
Stability assessment of power systems involves the
study of a set of non-linear differential equations
describing the fault on system and post fault system
[14]. Such analysis will aid both system planners and
system operators in evaluating the power system
networks ability to withstand any disturbance [18]. In
simple network cases, i.e., networks containing only
one machine (possibly two) and passive loads, the
analytical description of machine parameter evolution
if a fault occurs are feasible [15]. In large complex
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1435
networks, the digital simulation approach is used to
carry out power system stability analysis. This method
is the one universally used today, whereby a computer
digitally solves the equation systems describing the
network behaviour [15]. The different methods used
for power system stability analysis are integrated into
different software, which allows the digital simulation
approach to be used to analyse power system stability
with the use of a digital computer. Some of the
methods used for dynamic and transient stability
analysis of a power system network are: TD (time
domain) approach, EEAC (extended equal area
criterion), and the Lyapunov’s direct method. With the
time-domain approach, numerical integration methods,
such as Runge-Kutta methods, are used iteratively to
approximate the solution of ordinary differential
equations [18].
Newton-Raphson method is a numerical method for
finding the solution to a set of simultaneous nonlinear
equations [19]. The Newton-Raphson method is more
efficient and practical for large power systems. Main
advantage of this method is that the number of
iterations required to obtain a solution is independent
of the size of the problem and computationally it is
very fast [20]. The Newton-Raphson recursion
formula for iterative estimates is given by:
1
( )
'( )n
n nn
f xx x
f x (1)
In DigSilent Power Factory, the nodal equations
used to represent the analysed networks are
implemented using two different formulations:
Newton-Raphson (current equations);
Newton-Raphson (power equations, classical).
In both formulations, the resulting non-linear
equation systems must be solved by an iterative
method. Power Factory uses the Newton-Raphson
method as its non-linear equation solver. The selection
of the method used to formulate the nodal equations is
user-defined, and should be selected based on the type
of network to be calculated. For large transmission
systems, especially when heavily loaded, the standard
Newton-Raphson algorithm using the “Power
Equations” formulation usually converges best [21].
3. Model Development
System modelling for stability analysis purposes is
one of the most critical issues in the field of power
system analysis. Depending on the accuracy of the
implemented model, large-signal validity, available
system parameters and applied faults or tests, nearly
any result could be produced and arguments could be
found for its justification [21].
Given the complexity of a transient analysis
problem, the Power Factory modelling philosophy is
targeted towards a strictly hierarchical system
modelling approach, which combines both graphical
and script-based modelling methods.
The basis for the modelling approach is formed by
the basic hierarchical levels of time-domain
modelling:
The DSL (DigSilent Simulation Language) block
definitions, based on the “DSL”, form the basic
building blocks to represent transfer functions and
differential equations for the more complex transient
models;
The built-in models and common models. The
built-in models or elements are the transient Power
Factory models for standard power system equipment,
such as generators, motors, static VAr compensators,
The common models are based on the DSL block
definitions and are the front-end of the user-defined
transient models;
The composite models are based on composite
frames and are used to combine and interconnect
several elements (built-in models) and/or common
models. The composite frames enable the reuse of the
basic structure of the composite model [21].
The aim was to create a model that accurately
represents the physical existing power network, using
the DigSilent software. Fig. 2 shows a one-line
diagram of the modelled power network. The software
was used to carry out load flow and fault analysis of
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1436
Fig. 2 One-line diagram of NamPower’s electric power grid (Ruacana power station and Omburu substation).
the power network. The mathematical formulation of
the power flow problem is given by:
0 1,
n ni ii i j i j Jj j
i
P jQV y y V j i
v
(2)
3.1 Modelling Procedure
The different components needed to build the
electrical network were created in the equipment
library in DigSilent power factory software by using
the equipment basic data for each component. The
summarized basic equipment data and parameters
used for modelling are shown in Tables 2-4.
The model comprises of four main parts:
Ruacana hydroelectric power station;
Omburu transmission substation;
Ruacana transmission substation;
330 kV high voltage transmission line.
The NamPower transmission grid was created and
the various generation and transmission stations were
built on it using the components in the equipment and
global libraries. The power station and substations
were then connected to each other using the 330 kV
transmission line.
All simulations were carried using the stability tool
box in DigSilent Powerfactory. Since the
hydro-turbine generators at Ruacana power station are
low speed machines, they were modelled with salient
pole rotors. Additional control models were added to
the generators during modelling of the power station.
These are the software inbuilt control models and they
include the governor and turbine controllers (IEEE
pcu_HYGOV) as well as the automatic voltage
regulator (vco_IEEET1). These additional control
models were added to make the analysis of the
observed transient fault more realistic as the machines
in the physical network have controls.
3.2 Model Validation
An accuracy analysis of the modelled power system
Table 2 Transformer parameters.
Name Rated power (MVA)
Tap position (Max)
Additional voltage/tap (%)
Positive sequence impedance (%)
Vector group
Gen Transformer 1, 2 and 3 11/330 (kV)
90 17 1.25 12.3 YNd1
Gen Transformer 4 11/330 (kV) 100 17 1.25 1.24 YNd1
Ruacana TRFR11 66/11 (kV) 2.5 17 1.25 9.52 YNd1
Omburu Coupling TRFR1 315/315/40 17 1.25 10.8/18.413/20.063 YN0yn0d1
Omburu Coupling TRFR2 315/315/40 17 1.25 10.2/20.19/20.44 YN0yn0d1
Omburu SVC1 TRFR 60 17 1.25 8 YNd7
Table 3 Transmission line parameters.
Name Voltage (kV) Rated current (kA) Max operation temperature (°C)
Conductor material Line length (km)
Ruacana-Omburu 330 1 80 Aluminium 570
Omburu sub. line 1 22 1 80 Aluminium -
Omburu sub. line 2 22 1 80 Aluminium -
Ruacana station
330 kV Ruacana-Omburu sun-station line
Omburu
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1437
Table 4 Generator parameters.
Name Nominal apparent power (MVA) Nominal voltage (kV) Power factor (%) Frequency (Hz)
Ruacana Gen 1, 2 and 3 88.888 11 90 50
Ruacana Gen 4 100 11 90 50
is carried out in order to validate the modelled
electrical network (see Table 5). The accuracy of a
modelled component in the electrical network is given
by the following formula:
1 t m
T
A AA
A
(3)
where,
A = relative accuracy;
At = true value of quantity;
Am = measured value of quantity.
The percentage accuracy is given by:
100%a A x (4)
From Table 5, it can be seen that the power system
has been modelled to a relative accuracy level of
0.935 and a percentage accuracy of 93.5%. This is
fairly accurate and the results obtained as well as the
conclusions drowned based on those results are valid.
The following steps were taken to set up the
transient simulations:
setting initial conditions;
defining short circuit event;
defining switching events;
defining results objects and variable sets;
executing transient simulation and creating
plotted curves.
4. Simulation Results
The simulation results for various short circuit
scenarios are presented to show the system behaviour
in steady state, during fault conditions and post-fault
conditions (transient state). The busbar voltage at
Ruacana is 330 kV and of interest to be analysed. The
simulation results are presented in Figs. 3-8. All the
results except Fig. 9 were generated using the
transient stability toolbox (DigSilent Powerfactory
simulation software). Fig. 9 was retrieved from
NamPower’s SCADA (supervisory control and data
acquisition) system. A comparison is made between
the simulation result curves and the graphs obtained
from NamPower records in order to determine
which fault scenario best fits the behaviour of the 330
kV busbar voltage from the simulation results.
From Fig. 3, it is observed that during steady-state
the busbar voltage is constant at approximately 330
kV.
Fig. 4 shows that before the fault occurred, the
busbar voltage was constant at 330 kV. When the fault
occurred at 0.6 s, the busbar voltage instantly dropped
to zero. The Ruacana breaker then opened at 0.8 s and
the voltage sharply went up to 280 kV, after which it
started to increase gradually until it reached a
maximum value of 350 kV at 1 s. The generating units
then began to trip on over voltage and the voltage
began to drop until if eventually dropped to zero when
all generators fell out of step and tripped.
Fig. 5 shows that before the fault, the 330 kV
busbar voltage was constant at 327 kV. When the fault
occurred at 200 ms, the voltages remained at its steady
state value and only dropped at 300 ms when the
Omburu breaker opened. This result was however
unexpected. At 600 ms, the 330 kV busbar voltage
steadily rose to approximately 327 kV, it then started
to drop as the generators lost synchronism and started
to trip. The voltage ultimately drops to zero when all
the generators tripped.
Fig. 6 shows that when the three phase fault
occurred at 300 ms, the 330 kV busbar voltage
instantly drops to zero. When the breaker at Omburu
opened, the busbar voltage remained at zero. After the
breaker at Ruacana opened at 800 ms, the 330 kV
busbar voltage went up to approximately 100 kV, it
remained constant for 400 ms after which it then started
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1438
Table 5 Power system model accuracy.
Component name At Am A a
Ruacana 330 kV busbar 330 327 0.991 99.1
Omburu 220 kV busbar 220 225 0.977 97.7
Gen 1 active power MW 82 80.9 0.987 98.7
Gen 2 active power MW 82 80 0.976 97.6
Gen 3 active power MW 82 80 0.976 97.6
Gen 4 active power MW 90 90 1 100
Gen 1 reactive power MVAr 9.8 9 0.918 91.8
Gen 2 reactive power MVAr 9.8 8 0.816 81.6
Gen 3 reactive power MVAr 9.8 9 0.918 91.8
Gen 4 reactive power MVAr 35 10 0.286 28.6
Gen 1 stator terminal kV 11 11 1 100
Gen 2 stator terminal kV 11 11 1 100
Gen 3 stator terminal kV 11 11 1 100
Gen 4 stator terminal kV 11 11 1 100
Gen 1 stator current kA 4.67 4.25 0.910 91.0
Gen 2 stator current kA 4.67 4.25 0.910 91.0
Gen 3 stator current kA 4.67 4.25 0.910 91.0
Gen 4 stator current kA 4.8 4.75 0.99 99.0
Gen 1 frequency Hz 50 50 1 100
Gen 2 frequency Hz 50 50 1 100
Gen 3 frequency Hz 50 50 1 100
Gen 4 frequency Hz 50 50 1 100
Mean accuracy 0.935 93.5
Fig. 3 Ruacana power station 330 kV busbar voltage, steady state.
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1439
Fig. 4 Ruacana power station 330 kV busbar voltage, two phases to ground fault.
Fig. 5 Ruacana power station 330 kV busbar voltage, three phases to neutral to ground fault.
to drop as the generators started to fall out of step and
tripped, the busbar voltage eventually dropped to zero
at 1.4 s when all the generators fell out of step and
tripped.
Fig. 7 illustrates the behaviour of the Ruacana 330
kV busbar voltage pre-fault, during fault conditions
and post fault. Before the fault, the 330 kV busbar
voltage was constant at its steady state value of 327 kV.
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1440
Fig. 6 Ruacana power station 330 kV busbar voltage, three phase fault.
Fig. 7 Ruacana power station 330 kV busbar voltage, two phase fault.
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1441
Fig. 8 Ruacana power station 330 kV busbar voltage (single phase to ground fault).
When the two phase fault occurred at 400 ms, the 330
kV busbar voltage instantly dropped to zero. When the
breaker at Omburu opened at 700 ms, the busbar
voltage remained at zero. After the breaker at Ruacana
opened at 1.4 s, the 330 kV busbar voltage sharply
went up to approximately 395 kV, it then began to
drop slowly from 395 kV to approximately 220 kV
after which it instantly dropped to zero at 2.4 s when
all the generators lost synchronism and tripped. The
Ruacana 330 kV busbar voltage remained at zero volts
until all the generating units in the power station were
re-exited and ran up and power supply restored.
Fig. 8 illustrates the behaviour of the 330 kV busbar
voltage when subjected to a single phase to ground
fault. Before the fault occurred, the voltage was
constant at 327 kV. When the single phase to ground
fault occurred at 300 ms, the busbar voltage then
dropped to 168 kV. At 400 ms both breakers at
Omburu and Ruacana opened, this caused the voltage
to rise to approximately 293 kV. The breakers at
Ruacana and Omburu then auto-reclosed after 100 ms
and the busbar voltage began to drop again. At 600 ms
the Omburu breaker opened and the Ruacana 330 kV
busbar voltage began to increase steadily until 1.7 s
later when the breaker at Ruacana also opened. After
the breaker at Ruacana opened, the 330 kV busbar
voltage sharply went up to 421 kV. A few
milliseconds later, the generators at Ruacana began to
lose synchronism and trip. The 330 kV busbar voltage
then began to drop until it eventually dropped to zero
at 3.4 s when all the generators fell out of step and
tripped. The voltage remained at zero until all
generators were re-exited and ran up and power
supply restored.
Fig. 9 shows actual SCADA data illustrating the
behaviour of the 330 kV busbar voltage at Ruacana.
From the Figure, it can be observed that the 330 kV
busbar voltage remains constant at approximately 330
kV before the fault occurs. When the fault occurs, the
voltage dips to approximately 290 kV. After the
breakers open to isolate the fault, the voltage
increased sharply to approximately 412 kV. Thereafter,
it began to decrease when the generators were out of
step and began to trip. It ultimately goes to zero when
Fig. 9 Ruacana power station 330 kV busbar voltage, from NamPower records.
Power System Modelling and Fault Analysis of NamPower’s 330 kV HVAC Transmission Line
1442
all the generators lost synchronism and tripped. The
busbar voltage remained at zero voltage until the
generating units were re-excited and ran up and
electric power supply was restored.
5. Conclusion
Based on the qualitative analysis of the obtained
results, it can be concluded that the observed fault is
most probably a single phase to ground fault. This
conclusion was arrived at on the basis of close
correlation in the observed behaviour of the Ruacana
power station 330 kV busbar voltage in the plots
obtained from the single phase to ground fault
simulations and the behaviour of that same variable as
shown in the graph of the behavioural pattern of the
330 kV busbar voltage in Fig. 9 which was obtained
from NamPower records. This is however not the case
for the two phases to ground fault, three phase fault,
two phase fault and the three phases to neutral to
ground fault scenarios, hence the conclusion is a
single phase to ground fault.
Acknowledgments
This work has been supported in part by the Faculty
of Engineering & Information Technology Research
Centre at the University of Namibia NamPower, the
University of KwaZulu-Natal Research/Publications
Office, and the HVDC/Smart Grid Research Centre.
References
[1] Stankovic, A. M., and Aydin, T. 2000. “Analysis of Symmetrical Faults in Power Systems Using Dynamic Phasors.” IEEE Transection on Power System 15 (3): 1063-8.
[2] Weedy, B. M., and Cory, B. J. 1999. Electric Power Systems. London: John Wiley & Sons, Inc..
[3] Pre've', C. 2006. Protection of Electrical Networks. London: ISTE Ltd..
[4] Shilamba, P. 2011. NamPower Annual Report, 2011. Annual report.
[5] Kundur, P., Perseba, J., Ajjarapu, V., Anderson, G., Bose, A., and Canizares, C. 2004. “Definition and Classification of Power System Stability.” IEEE Transection on Power System Stability 19 (2): 1387-93.
[6] Gross, C. A. 1986. Power System Analysis. New York:
John Wiley & Sons.
[7] Ram, B., and Vishwakarna, D. N. 1995. Power System
Protection and Switchgear. New Delhi: Tata
McGraw-Hill.
[8] Anderson, P. M. 1995. Analysis of Faulted Power
Systems. New York: Wiley-IEEE Press.
[9] Tleis, A. N. 2008. Power System Modelling and Fault
Analysis. USA: Elsvier Ltd..
[10] Nasar, S. A., and Trutt, F. C. 1999. Electric Power
Systems. Florida: CRC Press LLC.
[11] Gan, D., Thomas, R. J., and Zimmerman, R. D. 2000.
“Stability-Constrained Optimal Power Flow.” IEEE
Transections on Power Systems 15 (2): 535-40.
[12] Kundur, P. 1994. Power Systems Stability and Control.
USA: McGraw-Hill Professional.
[13] Elmore, W. A. 1994. Protective Relaying Theory and
Applications. New York: Marcel Dekker. Inc..
[14] Chiang, H., Wu, F. F., and Varaiya, P. P. 1994. “A BCU
Method for Direct Analysis of Power System Transient
Stability.” IEEE Transection on Power Systems 9 (3):
1-5.
[15] Demetz, N., and Jeanjean, G. 1997. “Dynamic Stability
of Electrical Industrial Networks.” Cashier Techniques
185: 1-14.
[16] Glover, J. D., Sarma, M. S., and Overbye, T. J. 2008.
Power Systems Analysis and Design. Toronto: Chris
Carson.
[17] Song, Y. H., and Johns, A. T. 1999. FACTS (Flexible AC
Transmission Systems). London: The Institution of
Electrical Engineers.
[18] Choo, Y. C., Muttaqi, K. M., and Negnevitsky, M. 2006.
“Transient Stability Assesment of a Small Power System
Subjected to Large Disturbances.” In Proceedings of the
Australasian Universities Power Engineering Conference,
1-13.
[19] Ortega, J. M., and Rheinboldt, W. C. 1970. Iterative
Solutions of Nonlinear Equations in Several Variables.
New York: Academic Press.
[20] Das, D. 2006. Electrical Power Systems. New Delhi:
New Age International (P) Limited.
[21] DigSilent PowerFactory. 2011. User’s Manual. Germany:
DigSilent GmbH Heinrich-Hertz.