Demand control ventilation: maximize savings with practical approaches Scott Hackel, Principal Engineer February 23, 2015

Upload: others

Post on 23-Aug-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Demand control ventilation: maximize savings with practical approaches

Scott Hackel, Principal Engineer

February 23, 2015

Page 2: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Minnesota Conservation Applied Research and Development

(CARD) Grant Program

Acknowledgement

Page 3: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

•  Quality DCV design

•  Field study results

•  (Re)commissioning

Today’s topics

Page 4: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Background on DCV FIELD STUDY

Sensor

VAV Boxes

Central and/or Zone Control

AHU

Source: http://i.stack.imgur.com/4WKDC.jpg

SA OA

RA

Page 5: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Quality DCV design

Page 6: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

•  Specific sequence - CO2 setpoint - Outside airflow lower limit

•  CO2 sensor location

•  Airflow measurement req.

Choose responsible party Be complete:

Mechanical engineer Controls contractor Other (vendor, …)

Be thorough DCV DESIGN

Page 7: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

1. Direct OA flow control a.  Zone CO2 sensors

b. Return CO2 sensor

Slight potential for imperfect IAQ…

More potential for imperfect IAQ…

SA

OA

RA

BAS

BAS

Sequence options DCV DESIGN

Page 8: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

2. Ventilation reset a.  OA flow reset

b. Zone, then OA flow reset

c. Zone, then OA flow reset, with occupancy sensors

BAS

Sequence options DCV DESIGN

Page 9: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00

OAFlow

Rate(cfm

)

DesignOA

SeparationbetweenOAlowerlimit andDesignOAdrivesenergysavings

Upper limit Freeze protection Mitigates failures

Lower limit Save energy Maintain press.

Elements of sequence DCV DESIGN

Page 10: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

CO2 setpoint Setpoint(s) per: 𝐶↓𝑅 = 𝐶↓𝑂𝐴 + 8400𝐸↓𝑍 ×𝑚𝑒𝑡/𝑅↓𝑃 + 𝑅↓𝑎 ×(𝑠𝑓/𝑝 ) 

Proportional or single setpoint

Elements of sequence DCV DESIGN

Page 11: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Ideally in zone •  At breathing height (3-6 ft.) •  Not below a thermostat

Common return •  Limited situations

Show on drawings!

CO2 sensor location DCV DESIGN

Page 12: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Use occupancy sensors! •  Occ. sensor = VAV savings, aside from DCV

AFMS on drawings

Consider OA diversity in sizing

DCV: not just a ‘Yes / No’ choice •  Control portion of zones •  Strategically use common return •  Use 2-way dampers •  Mix approaches

Other considerations DCV DESIGN

Page 13: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Field study results

Page 14: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Characterization of approaches FIELD STUDY

96 systems around Minnesota:

Page 15: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Approaches (sequences):

1a. Direct OA flow control, return sens.

1b. Direct OA flow control

2a. Ventilation reset

2b. Zone box, then ventilation reset

2c. Zone min. reset, w/ occ. sensors 19%

22%

15%

26%

19%

Characterization of approaches FIELD STUDY

Page 16: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Measured savings per design OA rate (cfm) Occ. + CO2 sensing

High lower limit

With ERV

Median = $0.50/cfm

Results FIELD STUDY

Page 17: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Results FIELD STUDY

therms/cfm kWh/cfm $/cfmMedian 0.80 0.64 0.59

ChangefromMSPresults 27% -34% 18%

SavingsperDesignOAFlow

We also scaled the results to a Duluth climate

Page 18: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Deficiencies

Recommissioning FIELD STUDY

Page 19: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Recommissioning results FIELD STUDY

Half the systems saved more, an average of 54%

Page 20: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Economics FIELD STUDY

Page 21: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

(Re)commissioning

Page 22: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

•  Conduct when hot, or very cold outside •  Review CO2 and OA flow trends:

CO2 (ppm) OA flow (cfm)

Find lower limit (also look for upper)

CO2 follows occupancy

OA flow increases per sequence

Virtual performance checks Cx

Page 23: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

•  Determine control: 1) OA damper position vs. 2) OA flow measurement (if available)

•  Check for rogue DCV zones

•  Check CO2 sensor reading at unoccupied

•  Determine OA damper schedule

•  Recognize that savings is from heating (gas)

- Economizer negates cooling savings

•  Verify economizer operation

Virtual performance checks Cx

Page 24: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Meet the operator on-site; discuss system operation

Validate measured points: •  Temperatures: SA, MA, RA, OA (brief traverse) •  Valve positions (visual, temp) •  OA damper position (visual) •  Supply fan speed (VFD)

Spot checks Cx

Page 25: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

CO2 sensors •  Calibrate or replace

•  Recalculate setpoint per Standard 62.1 •  Auto calibration valid?

Sensors Cx

Page 26: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Perform basic system performance tests §  AHU §  Key VAV boxes Correct deficiencies found in tests Optimize:

à OA upper / lower limit, CO2 setpoint, OA schedule

SPT and Sequence Optimization Cx

Page 27: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Report any changes made Add any needed trending Complete handover missed at install •  Document the

sequence •  Plan for future

monitoring

4:00 6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00

OAFlow

Rate(cfm

)

DesignOA

SeparationbetweenOAlowerlimit andDesignOAdrivesenergysavings

Hand over to operators Cx

Page 28: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Sequences •  Basic: EDR 2007

•  Ventilation reset: Trane 2005

•  With occupancy sensors: Taylor 2014. Demand control ventilation for multiple zone VAV systems – problem solved (from ASHRAE Annual Meeting, Seattle 2014; seminar available for a fee)

Code requirements Code Notes 2012 IECC Demand Control Ventilation

AFMS: Fisk 2009

CO2 sensor performance: Shrestha 2009

For more information Cx

Page 29: Demand control ventilation · DCV DESIGN Other considerations . Field study results . FIELD STUDY Characterization of approaches 96 systems around Minnesota: Approaches (sequences):

Download the study Stay tuned for a fact sheet and the full report: seventhwave.org/dcv

Contact me [email protected] 608.210.7129

Learn about our work seventhwave.org/buildings