compact ns - schneider-electric.com · electromagnetic compatibility 28 degree of protection 29...

46
14 This international site allows you to access all the Merlin Gerin products in just 2 clicks via comprehensive range data-sheets, with direct links to: b complete library: technical documents, catalogs, certificates, FAQs, brochures… b selection guides from the e-catalog. b product discovery sites and their Flash animations. You will also find illustrated overviews, news to which you can subscribe, a discussion forum, the list of country contacts… These technical guides help you comply with installation standards and rules i.e.: the electrical installation guide, the protection guide, the switchboard implementation guide, the technical booklets and the co-ordination tables all form genuine reference tools for the design of high performance electrical installations. For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

Upload: others

Post on 27-Oct-2019

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

This international site allows you to access all the Merlin Gerin products in just 2 clicks via comprehensive range data-sheets, with direct links to:b complete library: technical documents, catalogs, certificates, FAQs, brochures…b selection guides from the e-catalog.b product discovery sites and their Flash animations.

You will also find illustrated overviews, news to which you can subscribe, a discussion forum, the list of country contacts…

These technical guides help you comply with installation standardsand rules i.e.:the electrical installation guide, the protection guide, the switchboard implementation guide,the technical booklets and the co-ordination tables all form genuine reference tools forthe design of high performance electrical installations.For example, the LV protection co-ordination guide - discrimination and cascading - optimises choice of protection and connection devices while also increasing markedly continuity of supply in the installations.

14

Page 2: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Compact NSMasterpact NW

Functions and characteristics

Presentation 6

Selection guide for DC circuit breakers 16Types of DC distribution systems 16Solutions depending on the distribution system and the voltage 17Series connection of poles 17Parallel connection of poles 18

Examples of circuit-breaker selection 19

Calculation of DC distribution-system characteristics 21Short-circuit currentsL/R time constant 21

Panorama of electrical and mechanical accessories 22Compact NS100 to NS630 22Masterpact NW10 to NW40 24

General characteristics 26Compliance with standards 26Pollution degree 26Tropicalisation 26Environmental protection 26Ambient temperature 27Altitude 27Positive contact indication 27Vibrations 28Installation in class II switchboards 28Electromagnetic compatibility 28Degree of protection 29

Circuit-breaker characteristics 30Compact NS100 to NS630 30Masterpact NW10 to NW40 32

Trip-unit characteristics 34Types of trip units 34Trip units for Compact NS 34Trip units for Masterpact NW 36

Communication 38COM option in Masterpact NW 38Compact NS 39

Electrical and mechanical accessories 40Compact NS100 to 630 40Masterpact NW10 to NW40 50

Dimensions and connection 61Electrical diagrams 87Installation recommendations 103Additional characteristics 121Catalogue numbers and order form 143

15

Page 3: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Selection guide for DC circuit breakers 0

Types of DC distribution systems

There are three types of DC distribution systems (see the table).The operational voltage in conjunction with one of the three systems determines the number of poles taking part in current interruption.

Selection of a circuit breaker depends essentially on the distribution-system parameters presented below which are used to determine the corresponding characteristics:b type of system - determines the type of product and the number of poles connected in series for each polarityb rated voltage - determines the number of series poles taking part in current interruptionb nominal current - determines the rated current of the circuit-breakerb maximum short-circuit current at the point of installation - determines the breaking capacity.

Types of systemsEarthed systems Isolated systemsThe source has one earthed polarity (1) The source has an earthed mid-point

Diagrams and different faultsD

B10

5016

DB

1050

17

DB

1050

18

Fault analysis (neglecting resistance of earth electrodes)Fault A b maximum Isc at U

b only protected polarity concernedb all poles of protected polarity must have breaking capacity u Isc max. at U

b maximum Isc at U/2b only positive polarity concernedb all poles of positive polarity must have breaking capacity u Isc max. at U/2

b no consequencesb the fault must be indicated by an IMD (insulation-monitoring device) and cleared (standard IEC/EN 60364)

Fault B b maximum Isc at Ub if only one polarity (the positive here) is protected, all poles of protected polarity must have breaking capacity u Isc max. at Ub if both polarities are protected, to enable disconnection, all poles of the two polarities must have breaking capacity u Isc max. at U

b maximum Isc at Ub both polarities are concernedb all poles of the two polarities must have breaking capacity u Isc max. at U

b maximum Isc at Ub both polarities are concernedb all poles of the two polarities must have breaking capacity u Isc max. at U

Fault C No consequences b same as fault Ab all poles of thenegative polarity must have breaking capacity u Isc max. at U/2

b same as fault A with the same obligations

Double faultA and D or C and E

Double fault not possible,system trips on first fault

Double fault not possible,system trips on first fault

b maximum Isc at Ub only positive polarity (cases A and D) or negative (C and E) concernedb all poles of each polarity must have breaking capacity u Isc max. at U

Most unfavourable casesFault A and fault B (if only one polarity is protected)

Fault B Double fault A and D or C and E

Conclusion: selection of number of poles and breaking capacityLayout of protection poles

b on only one polarity (1) b identical for each polarity b identical for each polarityNumber of series poles

Per polarity b all on same polarity b equal b equalTotal b 1, 2 or 3 without disconnection

b 2, 3 or 4 with disconnectionb 2 or 4 (2) b 2 or 4 (2)

Breaking capacityb all poles of the protected polarity u Isc max. at U

b all poles of both polarities u Isc max. at Ub all poles of each polarity u Isc max. at U/2

b all poles of each polarity u Isc max. at U

Disconnection of both polarities (3)

Possible by adding a pole to the non-protected polarity

b ensured b ensured

ImplementationSee the selection table opposite

(1) Positive or negative, depending on the polarity connected to the exposed conductive parts.(2) A 3P circuit breaker can be used if a 2P version does not exist. In this case, the central pole is not connected.(3) Disconnection made possible by multi-pole breaking.

16

Page 4: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Selection guide for DC circuit breakers 0

Solutions depending on the distribution system and the voltage

Series connection of polesType of distribution system

Type Earthed IsolatedSource One polarity (negative here) connected to earth

(or exposed conductive parts)Mid-point connected to earth Isolated polarities

Protected polarities 1 (disconnection of 1P) 2 (disconnection of 2P) 2 2Diagrams(and types of faults)

DB

1049

99

DB

1050

00

DB

1050

01

DB

1050

02

Selection of circuit breaker and pole connectionCompact NS

24 V y Un y 250 V

DB

1050

03

DB

1050

04

DB

1050

04

DB

1050

04

Single-pole. Two-pole (1). Two-pole (1). Two-pole (1).250 V < Un y 500 V

DB

1050

05

DB

1050

06

DB

1050

04

DB

1050

07

Two-pole (1). Three-pole. Two-pole (1). Four-pole.500 V < Un y 750 V

DB

1050

08

DB

1050

09

DB

1050

07

Three-pole. Four-pole. Four-pole.Masterpact NWType N

24 V y Un y 500 V

DB

1050

10

DB

1050

10

DB

1050

10

Version C. Version C. Version C.Type H

24 V y Un y 500 V

DB

1050

11

DB

1050

10

DB

1050

12

Version D. Version C. Version E.500 V < Un y 750 V

DB

1050

11

DB

1050

12

DB

1050

12

Version D. Version E. Version E.750 V < Un y 900 V

DB

1050

11

DB

1050

12

DB

1050

12

Version D. Version E. Version E.(1) A 3P circuit breaker can be used if a 2P version does not exist. In this case, the central pole is not connected.

17

Page 5: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Selection guide for DC circuit breakers 0

Solutions depending on the distribution system and the voltage

Parallel connection of polesType of distribution system

Type Earthed IsolatedSource One polarity (negative here) connected to earth

(or exposed conductive parts)Mid-point connected to earth Isolated polarities

Protected polarities 1 (disconnection of 1P) 2 (disconnection of 2P) 2 2

Diagrams(and types of faults)

DB

1049

99

DB

1050

00

DB

1050

01

DB

1050

02

Selection of circuit breaker and pole connectionCompact NS

Un y 250 V

DB

1050

13

DB

1050

14

DB

1050

14

DB

1050

14

Two, three-pole, 2, 3P in parallel, four-pole, 4P in parallel.

Four-pole, 2 x 2P in parallel. Four-pole, 2 x 2P in parallel. Four-pole, 2 x 2P in parallel.

250 V < Un y 500 V

DB

1050

15

DB

1050

14

Four-pole, 2 x 2P in parallel, connected in series.

Four-pole, 2 x 2P in parallel.

Breaking capacity of parallel solutionsUn y 250 V 250 V < Un y 500 VN H DC N H DC

Two-pole 2 poles in parallel 85 100 - - - -Three-pole 3 poles in parallel - - 100 - - -Four-pole 4 poles in parallel - - 100 - - -

2 x 2 poles in parallel, connected in series - - 100 - - 100

Comparison of series and parallel connection in terms of performance

Series connection of poles divides the voltage per pole and optimises breaking capacity for high-voltage systems.

Series connection of poles on a DC circuit breaker is the means to: b divide the system voltage by the number of polesb use the rated current for each poleb use the breaking capacity of the circuit breaker for all the poles.For example, a Compact NS630, 3P DC type, with the three poles connected in series, provides:b a maximum voltage of 750 V (250 V per pole)b a rated current of 630 Ab a breaking capacity of 100 kA / 750 V.Consequently, a 630 A / 250 V device can be used in a 750 V system.

Parallel connection of poles divides the current per pole and optimises the rated current for systems that do not exceed the withstand voltage of each pole.The maximum useable rating and the value of the magnetic setting are indicated on pages 110 and 111.

Parallel connection of poles, on the contrary, imposes the system voltage on each pole, but is the means to:b divide the current flowing through each pole by the number of polesb increase the rated current.For example, the same Compact NS630 DC 3P circuit breaker with three poles in parallel provides:b a maximum voltage of 250 V (250 V per pole)b a rated current of 1500 A (see table on page 111)b a breaking capacity of 100 kA / 250 V.Consequently, a 630 A device used in a 250 V system can handle 1500 A.

18

Page 6: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Selection guide for DC circuit breakers 0

Examples of circuit-breaker selection

Selection of a Compact NSExample 1

DB

1050

19

b type of system - mid-point connected to earthb system voltage - Un = 500 V DC with time constant L/R = 5 msb rated current required at point of installation In = 250 Ab short-circuit current at the point of installation Isc = 60 kA

Selection constraints - see page 16The system with the mid-point connected to earth requires (see conclusion page 16):b identical protection-pole layout for each polarityb an equal number of poles for each polarity, i.e. a total of two or fourb all poles of the two polarities must have breaking capacity u Isc max. at Un,i.e. 60 kA/500 V in this caseb all poles of the each polarity must have breaking capacity u Isc max. at Un/2,i.e. 60 kA/250 V in this case.

Selection possibilities - see pages 17 and 18The tables indicate for 250 V < Un y 500 V and for this system: b poles connected in series: two-pole 2P in series V selection 1b poles connected in parallel: four-pole 2 x 2P parallel connected in seriesV selection 2.

Circuit-breaker selection - see pages 30 and 110b selection 1: the 250 A rated current does not exist in 2P. It is possible to use a 250 A 3P DC type circuit breaker with the central pole not connected V selection 3b selection 2: the 160 A rated current (DC version) is suitable with a 2 x 2P assembly connected in parallel because (see table page 110): v the rated current of the 2 x 2P assembly connected in parallel is In = 288 A > 250 Av and for L/R = 5 ms:- breaking capacity of all poles = 100 kA/750 V > 60 kA/500 V- breaking capacity of poles of each polarity = 100 kA/250 V > 60 kA/250 V.The options are: b selection 1: Compact S250DC, 3P, 2 poles connectedb selection 3: Compact NS160DC, 4P, 2 x 2P parallel connected in series.Both solutions exist in fixed and withdrawable configurations.

Trip-unit selectionb Compact NS250DC 3P: the selection table on page 35 indicates 3 TM250DC trip units, which are interchangeableb Compact NS160DC, 4P (2 x 2P) 160 A: the selection table on page 110 indicates, for the 2 x 2P parallel configuration mounted in series and for 250 A, a TM125DC trip unit with the magnetic-protection threshold set to 2500 A.

DB

1050

20

DB

1050

21

Selection 1. Selection 2: Compact NS160 DC 4P2 x 2P parallel mounted in series.

DB

1050

22

Selection 3: Compact NS250 DC 3P with 2P connected.

Example 2

DB

1050

23

b type of system - one polarity earthedb system voltage - Un = 250 V DC with time constant L/R = 5 msb rated current required at point of installation In = 160 Ab short-circuit current at the point of installation Isc = 45 kA.

Selection constraints - see page 16 The system with one polarity connected to earth requires (see conclusion page 16):b protection poles on the protected polarityb all poles contribute to breaking for the polarity:v 1, 2 or 3P without disconnection of the two polaritiesv 2, 3 or 4P with disconnection of the two polaritiesb all poles of the protected polarity must have breaking capacity u Isc max. at Un, i.e. 45 kA/250 V in this case.

Selection possibilities - see pages 17 and 18 The tables indicate for 250 V < Un y 250 V and for this system: b poles connected in series: single-pole V selection 1 (or two-pole with disconnection V selection 2)b poles connected in parallel: two-pole V selection 3b other selections (parallel connection) are possible, but are of no particular interest.

Circuit-breaker selection - see page 30 and page 110b selection 1: Compact NS160N, 1P, 50 kA, available in fixed version (or selection 2: Compact NS160N 2P, 85 kA, if disconnection of the two polarities is desired)b selection 3: Compact NS100N, 2P in parallel, 50 kA, providing a rated current of 200 A (see table page 110), available in fixed version.

Trip-unit selectionb Compact NS160N, 1P: the selection table on page 35 indicates a built-in TM160DC trip unit with the magnetic-protection threshold set to 1250 Ab Compact NS100N, 2P in parallel: the selection table on page 110 indicates, for the 2P parallel configuration and for 160 A, a TM80D trip unit with the magnetic-protection threshold set to 1600 A.

DB

1050

24

DB

1050

25

Selection 1: Compact NS160N 1P. Selection 2.

DB

1050

26

Selection 3: Compact NS100N 2P in parallel.

19

Page 7: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Selection guide for DC circuit breakers 0

Examples of circuit-breaker selection

Selection of a Masterpact NW

Example 1

DB

1050

23

b type of system - isolated polaritiesb system voltage - Un = 750 V DC with time constant L/R = 30 msb rated current required at point of installation In = 2000 Ab short-circuit current at the point of installation Isc = 40 kA

Selection constraints - see page 16The system with isolated polarities requires (see conclusion page 16):b identical protection for each polarityb an equal number of poles for each polarity, i.e. a total of two or fourb all poles of each polarity must have breaking capacity u Isc max. at Un,i.e. 40 kA/750 V in this case.

Selection possibilities - see page 17The table for series poles indicates for a voltage 24 V < Un y 750 V and the type of system, use of a four-pole, version E circuit breaker.

Circuit-breaker selection - see page 32The Masterpact NW characteristics table indicates more specifically with a 2000 A a NW20 type H circuit breaker with a breaking capacity of 50 kA/750 V (L/R = 30 ms).The correct selection is a Masterpact NW20 type H version E, 2000 A, 50 kA, available in fixed and drawout versions.

DB

1050

27

Masterpact NW20H version E.

Example 2

DB

1050

23

b type of system - one polarity earthedb system voltage - Un = 500 V DC with time constant L/R = 15 msb rated current required at point of installation In = 1000 Ab short-circuit current at the point of installation Isc = 30 kA

Selection constraints - see page 16The system with one polarity connected to earth requires (see conclusion page 16):b protection poles on the protected polarityb all poles contribute to breaking for the polarity:v 1, 2 or 3P without disconnection of the two polaritiesv 2, 3 or 4P with disconnection of the two polaritiesb all poles of the protected polarity must have breaking capacityu Isc max. at Un, i.e. 30 kA/500 V in this case.

Selection possibilities - see page 17The table for series poles indicates for a voltage 24 V < Un y 500 V and the type of system, use of a three-pole, version C circuit breaker.

Circuit-breaker selection - see page 32The Masterpact NW characteristics table indicates more specifically with a 1000 Aa NW10 type N circuit breaker with a breaking capacity of 35 kA/500 V (L/R = 15 ms).The correct selection is a Masterpact NW10 type N version C, 1000 A, 35 kA, available in fixed and drawout versions.

DB

1050

28

Masterpact NW10N version C.

20

Page 8: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Calculation of DC distribution-system characteristics 0

Short-circuit currentsL/R time constant

Short-circuit currents

DB

1050

60

Calculation of the short-circuit current across the terminals of a batteryDuring a short-circuit, the battery discharges a current equal to

b Vb = maximum discharge voltage (battery 100 % charged)b Ri = internal resistance equivalent to all cells (a function of the capacity in ampere-hours).

Exampleb consider a set of four 500 Ah batteries connected in parallelb discharge voltage of one battery: 240 V (110 cells 2.2 V each)b discharge current of one battery: 300 A with a run-time of 30 minutesb discharge current of all four batteries: 1200 A with a run-time of 30 minutesb internal resistance 0.5 mΩ per cell, i.e. for one battery:Ri = 110 x 0.5 x 10-3 = 55 x 10-3 Ωb short-circuit current of one battery: Isc = 240 V / 55 x 10-3 Ω = 4.37 kAb neglecting the resistance of the connections, for all four batteries discharging the short-circuit current in parallel, the total short-circuit current is four times that of one battery, i.e. Isc = 4 x 4.37 kA = 17.5 kA.

Note: if the internal resistance is not known, it is possible to use the following rough approximation: Isc = kc where c is the capacity of the battery in ampere-hours and k is a coefficient close to 10 and always less than 20.

Other typical examplesb PABXs: Isc from 5 to 25 kA at 240 V DC with L/R = 5 msb submarine: Isc from 40 to 60 kA at 400 V DC with L/R = 5 ms.

L/R time constant

DB

1050

59

When a short-circuit occurs across the terminals of a DC circuit, the current rises from the load current (y In) to the short-circuit current Isc over a period of time that depends on the value of the resistance R and inductance L of the short-circuited loop.The equation determining the current in the loop is:u = Ri + L di/dtThe curve of I versus time is defined (neglecting In) by the equation:i = Isc (1 - exp(t/τ)) where τ = L/R is the time constant for the rise to Isc.Practically speaking, after a time t = 3τ, the short-circuit is considered to be established, because the value of exp(-3) = 0.05 is negligible compared to 1 (see the curve opposite).The lower the time constant (e.g. battery circuit), the shorter the time required for the current to rise to Isc.

To express breaking capacity, the interrupted short-circuit current with the following time constants is used:b L/R = 5 ms, fast short-circuitb L/R = 15 ms, standardised value used in standard IEC 60947-2b L/R = 30 ms, slow short-circuit.In general, the value of the system time constant is calculated under worst-case conditions, across the terminals of the generator.

Breaking-capacity values for:b Compact NS (table page 30) are the same for 5 ms and 15 msb Masterpact NW (table page 32) are indicated for 3 values, 5 ms, 15 ms and 30 ms.

DB

1050

56

Icc VbRi-------=

21

Page 9: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Panorama of electrical and mechanical accessories 0

Compact NS100 to NS630

DB

1050

29

The Compact range offers a wide number of installation possibilities:b fixed (front or rear connected)b plug-inb withdrawable.

With a minimum number of catalogue numbers, the Compact NS DC system offers a wide variety of solutions up to 630 A.

pushto

trip

125/160

compact

NB250NH

Ui 750V. Uimp 8kV.

220/240

380/415

440

500/525

660/690

250

1007065501085

cat A

IEC947-2

UTE VDE BS CEI UNE NEMA

Ue(V)

Icu(kA)

Ics=100% Icu

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

pushto

trip

125/160IEC947-2

UTE VDE BS CEI UNE NEMA

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

pushto

trip

125/160

compact

NB250NH

Ui 750V. Uimp 8kV.

220/240

380/415

440

500/525

660/690

250

1007065501085

cat A

IEC947-2

UTE VDE BS CEI UNE NEMA

Ue(V)

Icu(kA)

Ics=100% Icu

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

pushto

trip

125/160IEC947-2

UTE VDE BS CEI UNE NEMA

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

Withdrawable

Plug-in

22

Page 10: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Panorama of electrical and mechanical accessories 0

Compact NS100 to NS630

DB

1050

30

pushto

trip

125/160IEC947-2

UTE VDE BS CEI UNE NEMA

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

O OFFdischarged

Opush OFF

Ipush ON

23

Page 11: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Panorama of electrical and mechanical accessories 0

Masterpact NW10 to NW40

All Masterpact NW DC devices exist in circuit-breaker (equipped with Micrologic DC 1.0 control unit) and switch-disconnector versions. All auxiliaries are common from 1000 to 4000 A.

DB

1051

08

1 OFF pushbutton.2 ON pushbutton.3 Closing mechanism charging handle.4 Operation counter.5 Operating mechanism charged and "ready to close"

indication:b spring charged b spring discharged.

DB

1045

22

6 Main contact position indication:b ON b OFF.

DB

1045

23

7 Fault trip indication and reset button.8 Micrologic 1.0 DC control unit.9 Racking interlock.10 Racking-handle storage.11 Shutter position indication and locking.12 "Connected / test / disconnected"

position indication.13 Racking-handle port.14 Reset pushbutton.15 Padlock locking.16 Keylock locking.

PB

1011

36-4

0

Circuit breakers and switch-disconnectorsMasterpact NW exists in fixed and withdrawable versions: b circuit breaker equipped with Micrologic 1.0 DC control unitb switch-disconnector without the control unit.

Common auxiliaries from 1000 to 4000 AAll accessories are:b accessible from the front in a compartment isolated from the power circuitsb secured by a single screwb no adjustmentsb adaptable on site.

CommunicationCircuit-breaker or switch-disconnector integration in a supervision system requires the COM option.Masterpact is designed for integration in the SMS PowerLogic electrical-installation management system and communicates using the Digipact and Modbus protocols.An external gateway is available for communication with other networks (Profibus, Ethernet, etc.).

Connectionsb rear connection (horizontal or vertical)b prefabricated series connectionsb optional accessories:v bare-cable connectors and connector shieldsv terminal shieldsv vertical-connection adaptersv cable-lug adaptersv interphase barriersv spreadersv disconnectable front-connection adaptersv safety shutters, shutter locking blocksv shutter position indication and locking.

Vertical rear connection.

PB

1007

91-3

2

Connection accessories.

DB

1011

56

DB

1011

47

DB

1011

49

DB

1011

50

24

Page 12: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Panorama of electrical and mechanical accessories 0

Masterpact NW10 to NW40

Lockingb pushbutton locking by padlockable transparent coverb OFF-position locking by padlock or keylockb chassis locking: v in disconnected position by keylockv in connected, disconnected and test positionsb door interlock (inhibits door opening with breaker in connected position)b racking interlock (inhibits racking with door open)b racking interlock between crank and OFF pushbuttonb automatic spring discharge before breaker removalb mismatch protection.

PB

1007

96-2

9

PB

1007

95-3

0

PB

1007

80-3

2

Locking in disconnected position by keylock or padlock. Door interlock (inhibits door opening with breaker in connected position).

Indication contactsb standard or low-level contacts:v ON/OFF indication (OF)v "fault-trip" indication (SDE)v carriage switches for connected (CE), disconnected (CD) and test (CT) positionsb programmable contacts:v two contacts (M2C)v six contacts (M6C).

PB

1008

06-1

9

PB

1008

07-1

2

PB

1008

20-1

9

BP

1008

16-1

9

PB

1007

74-1

9P

B10

0781

-19

OF contact(microswitch).

OF contact(rotary).

SDE contact. Combined contact(connected/closed).

Programmable contacts (M2C and M6C).

Remote operationb remote ON/OFF:v gear motorv XF closing or MX opening voltage releasesv PF ready-to-close contactv options:- RAR automatic or Res electrical remote reset- BPFE electrical closing pushbuttonb remote tripping function:v MN voltage release:- standard- adjustable or non-adjustable delayv or 2nd MX voltage release.

PB

1007

65-4

8

PB

1008

08-2

2

PB

1008

09-1

1

PB

1008

18-1

1

Remote ON/OFF. Gear motor. Voltage releases(MX and XF).

PF ready-to-close contact.

Accessoriesb auxiliary terminal shieldb operation counterb escutcheonb transparent cover for escutcheonb escutcheon blanking plate.

PB

1008

22-2

2

DB

1045

24

PB

1007

76-2

9

Operation counter. Escutcheon with blanking plate. Transparent cover.

25

Page 13: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

General characteristics 0

Compliance with standards

DB

1044

61

Compact NS and Masterpact NW DC circuit breakers and auxiliaries comply with the following:b international recommendations:v IEC 60947-1 - general rulesv IEC 60947-2 - circuit breakersv IEC 60947-3 - switches, disconnectors, switch-disconnectors, etc.v IEC 60947-4 - contactors and motor startersv IEC 60947-5.1 and following - control-circuit devices and switching elements; automatic control componentsb European (EN 60947-1 and EN 60947-2) and the corresponding national standards:v France NFv Germany VDEv UK BSv Australia ASv Italy CEIb the specifications of marine classification companies (Veritas, Lloyd's Register of Shipping, Det Norske Veritas, etc.)b French standard NF C 79-130 and the recommendations issued by the CNOMO organisation for the protection of machine tools.For United States UL, Canadian CSA, Mexican NOM and Japanese JIS standards, please consult us.

Compact NS250.

DB

1044

62

Pollution degreeCompact NS and Masterpact NW DC circuit breakers are certified for operation under pollution conditions in industrial environments, as per standard IEC 60947, corresponding to: b pollution degree 3 (Compact NS)b pollution degree 4 (Masterpact NW).

TropicalisationCompact NS and Masterpact NW DC circuit breakers have successfully passed the tests prescribed by the following standards for extreme atmospheric conditions:b IEC 60068-2-1 - dry cold (-55 °C)b IEC 60068-2-1 - dry heat (+85 °C)b IEC 60068-2-30 - damp heat (95 % relative humidity at +55 °C)b IEC 68-2-52 (level 2) - salt mist.

Masterpact NW20 HDC-D.

Environmental protectionCompact NS and Masterpact NW DC circuit breakers take into account important concerns for environmental protection. Most components are recyclable. Insulating parts making up the Compact NS and Masterpact NW are marked as specified in applicable environmental standards.

26

Page 14: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

General characteristics 0

Ambient temperature

Operating-temperature rangeb Compact NS and Masterpact NW circuit breakers may be used between -25 °C and +70 °Cb circuit breakers should be put into service under the normal, ambient operating temperatures indicated above. Exceptionally, they may be put into service when the ambient temperature is between -35 °C and -25 °C.

DeratingAbove 40 °C (50 °C for Masterpact with vertical connections), it is necessary to take into account the derating values indicated on pages 108 (Compact NS) and 119 (Masterpact NW).

Storage-temperature rangeb Compact NS circuit breakers may be stored in their original packing between -50 °C and +85 °Cb Masterpact NW circuit breakers may be stored without the control unit between -35 °C and +85 °C. The control unit must be stored at a temperature between -25 °C and +85 °C.

AltitudeCompact NS and Masterpact NW circuit breakers are designed to operate at their rated values at altitudes under 2000 metres.Above 2000 metres, the changes in the characteristics of the ambient air (electrical resistance, cooling capacity) result in a reduction of the characteristics below.Altitude (m) 2000 3000 4000 5000

Dielectric resistance voltage (V) 3500 3150 2500 2100Compact NS

Rated insulation voltage (V) 750 700 600 500Maximum utilisation voltage (V) 690 550 480 420Rated current (A) at 40 °C 1 x In 0.96 In 0.93 In 0.9 In

Masterpact NWRated insulation voltage (V) 1000 900 700 600Maximum utilisation voltage (V) 900 770 680 420

Rated current (A) at 40 °C 1 x In 0.99 In 0.96 In 0.94 In

Positive contact indication

PB

1008

81-5

5

Compact NS and Masterpact NW circuit breakers are suitable for isolation as defined by IEC 60947-1 and 60947-2:b the isolation position corresponds to the O (OFF) positionb the operating handle and the indicators cannot indicate the OFF position unless the contacts are effectively openb padlocks may not be installed unless the contacts are open.The isolation function is certified by tests guaranteeing:b the mechanical reliability of the position-indication systemb the absence of leakage currentsb overvoltage withstand capacity between upstream and downstream connections.For Compact NS, installation of a rotary handle or a motor mechanism does not alter the reliability of the position-indication system.

DB

1045

27

27

Page 15: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

General characteristics 0

VibrationsCompact NS and Masterpact NW circuit breakers are guaranteed against electromagnetic or mechanical vibrations.Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd's, etc.):b 2 to 13.2 Hz: amplitude ±1 mmb 13.2 to 100 Hz: constant acceleration 0.7 g.Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts.

Installation in class II switchboardsAll Compact NS and Masterpact NW circuit breakers are class II front-face devices. They may be installed through the door of class II switchboards (as per standard IEC 60664) without downgrading switchboard insulation. Installation requires no special operations even when the circuit breaker is equipped with a rotary handle or a motor mechanism.

Electromagnetic compatibilityCompact NS and Masterpact NW circuit breakers are protected against:b overvoltages caused by devices that generate electromagnetic disturbancesb overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system) and devices emitting radio waves (radios, walkie-talkies, radar, etc.)b electrostatic discharges produced by users. The circuit breakers have successfully passed the electromagnetic-compatibility tests (EMC) defined by international standard IEC 60947-2, appendix F.The above tests guarantee that:v no nuisance tripping occursv tripping times are respected.Compact NS and Masterpact NW circuit breakers comply with the following electromagnetic-compatibility standards:b IEC/EN 61000-4-2 - electrostatic immunity discharge test, part 2 (circuit breakers)b IEC/EN 61000-4-3 - electromagnetic-field immunity testb IEC/EN 61000-4-4 - electrical fast transient/burst immunity testb IEC/EN 61000-4-5 - surge immunity testb IEC/EN 61000-4-6 - immunity to conducted disturbances, induced by radiofrequency fieldsb CISPR 11 - radio-frequency conducted and radiated emission tests required for CE markingv EN 61000-6-2 - immunity standard for industrial environmentsv EN 50081-1-2 - emissions in commercial and industrial environments.

28

Page 16: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

General characteristics 0

Degree of protectionCompact NS and Masterpact NW circuit breakers offer the following protection characteristics depending on the installation conditions: b IP: degree of protection (standard IEC 60529)b IK: protection against external mechanical impacts (standard EN 50102).

Compact NSBare circuit breaker with terminal shields

DB

1045

28

With toggle IP40 IK07

DB

1045

29

With direct rotary handle,standard or VDE

IP40 IK07

Circuit breaker installed in a switchboard

DB

1045

30

With toggle IP40 IK07

DB

1045

31

With direct rotary handle,standard or VDE

IP40 IK07

CCM IP43 IK07

CNOMO IP54 IK07

DB

1045

32

With extended rotary handle IP55 IK08

DB

1045

33

With motor mechanism IP40 IK07

Masterpact NWCircuit breaker installed in a switchboard

DB

1045

34

Bare circuit breaker IP30

Escutcheon (CDP) for fixed and drawout versions, with blanking plate

IP40 IK07

PB

1007

76-2

0

Transparent cover (CCP) for escutcheon for fixed and drawout versions

IP54 IK10

29

Page 17: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Circuit-breaker characteristics 0

Compact NS100 to NS630

PB

1010

47-1

4

Compact circuit breakerNumber of poles

Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2Rated current at 40 °C In (A)Rated insulation voltage Ui (V)

Rated impulse withstand voltage Uimp (kV peak)Rated operational voltage Ue (V DC)Type of circuit breaker

Ultimate breaking capacity(L/R = 5 ms and L/R = 15 ms)

Icu (kA rms) V DC 48-125 V (1P) (1)

250 V (1P) (1)

500 V (2P) (1)

750 V (3P) (1)

PB

1010

48-2

0

Service breaking capacity Ics % IcuRated making capacity Icm % Icu

Utilisation categoryBreaking time (ms)Suitability for isolation

Pollution degree (as per IEC 60664-1)Protection against overcurrents (see trip-unit table page 34)

Trip units Built-in

InterchangeableProtection Overloads

Short-circuits

Durability

PB

1010

55-2

7

(O/F cycles) MechanicalElectrical 250 V In

250 V In/2500 V In

500 V In/2750 V In750 V In/2

Indication and control auxiliariesAuxiliary contacts

Voltage release MX shunt releaseMN undervoltage release

Installation and connectionsFixed Front connection

PB

1009

05-3

6

Rear connection

Plug-in (base) Front connectionRear connection

Withdrawable (chassis) Front connection

Rear connection

Dimensions and weightDimensionsH x W x D (mm) connected in series

Fixed 1P2P3P

4PWeight (kg)connected in series

Fixed 1P2P

3P4P

(1) Number of poles taking part in current interruption.Example. The NS100N circuit breaker exists in the following versions:- 1 pole with an Icu of 50 kA, for systems y 250 V- 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.

30

Page 18: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Circuit-breaker characteristics 0

Compact NS100 to NS630

NS100 NS160 NS250 NS400 NS6301 2 3/4 1 2 3/4 3/4 3/4 3/4

100 160 250 400 550800 800 800 800 800

8 8 8 8 8250 500 750 250 500 750 750 750 750N H N H DC N H N H DC DC DC DC50 85 85 100 100 50 85 85 100 100 100 100 10050 85 85 100 100 50 85 85 100 100 100 100 100- - 85 100 100 - - 85 100 100 100 100 100

- - - - 100 - - - - 100 100 100 100100 %100 %

A< 10 msbIII

b b b b - b b b b - - b b - - - - b - - - - b b - -b b b b b b b b b b - - -b b b b b b b b b b b b b

10000 50005000 1000

10000 20005000 1000

10000 20005000 100010000 2000

bbb

bb - - - - b - - - - b b b b - - - - b - - - - b b b b - - - - b - - - - b b b b - - - - b - - - - b b b b

161 x 35 x 86 - - 161 x 35 x 86 - - - - 161 x 70 x 86 - - 161 x 70 x 86 - - - - 161 x 105 x 86 - - 161 x 105 x 86 255 x 140 x 110

- - 161 x 140 x 86 - - 161 x 140 x 86 225 x 185 x 1100.7 - - 0.7 - - - - 1.2 - - 1.2 - -

- - 1.6 to 1.9 - - 1.6 to 1.9 6.0 - - 2.1 to 2.3 - - 2.1 to 2.3 7.8

31

Page 19: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Circuit-breaker characteristics 0

Masterpact NW10 to NW40

E88

193-

31

Masterpact circuit breakerNumber of poles Version C or D

Version E

Electrical characteristics as per IEC 60947-1/ 60947-2 and EN 60947-1 / 60947-2Rated current at 40 °C / 50 °C (1) In (A)

Rated insulation voltage Ui (V)Rated impulse withstand voltage Uimp (kV peak)Rated operational voltage Ue (V DC)

Type of circuit breakerUltimate breaking capacity L/R = 5 ms Icu (kA) V DC 500

NW10DC 4P.

750

PB

1011

29-3

4

900L/R = 15 ms Icu 500

750

900L/R = 30 ms Icu 500

750

900Service breaking capacity Ics % IcuRated making capacity Icm % Icu

Short-time withstand current Icw 1 sUtilisation categoryBreaking time (ms)

Making time (ms)Suitability for isolationPollution degree (as per IEC 60664-1)

Protection against overcurrents (see trip-unit table page 36)Trip units Built-in

Protection OverloadsShort-circuits

Durability(O/F cycles) Mechanical With maintenance

Without maintenanceElectrical Without maintenance 500 V CC

900 V CCIndication and control auxiliaries

Auxiliary contacts

Voltage release MX shunt releaseMN undervoltage release

Characteristics of switch-disconnectors as per IEC 60947-3 and EN 60947-3Type of switch-disconnector

Rated making capacity Icm (kA)

Rated short-time withstand current Icw (kA) 1 s

Installation and connectionsConnection Drawout 3P RC Horizontal

4P VerticalFixed 3P RC Horizontal

4P Vertical

Dimensions and weightDimensionsH x W x D (mm) connected in series

Drawout 3P4P

Fixed 3P

4PWeight (kg)connected in series (approximate values)

Drawout 3P4P

Fixed 3P4P

(1) 50 °C - see the derating table for the NW40.

32

Page 20: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Circuit-breaker characteristics 0

Masterpact NW10 to NW40

NW10 NW20 NW403 3 34 4 4

1000 2000 4000

1000 1000 100012 12 12500/900 500/900 500/900

N H N H N H85 100 85 100 85 100- 85 - 85 - 85

- 85 - 85 - 8535 85 35 85 35 85- 50 - 50 - 50

- 35 - 35 - 3525 50 25 50 25 50- 50 - 50 - 50

- 25 - 25 - 25100 %100 %

50 85 50 85 50 85B30 to 75

< 70b b b b b b4

b b b b b b- - - - - -b b b b b b

20000100008500 5000 2000

- 2000 - 2000 - 1000

b b b b b bb b b b b bb b b b b b

HA HA HA- 85 - 85 - 85

- 85 - 85 - 85

b b b b - -b b b b b bb b b b - -

b b b b b b

439 x 441 x 494 439 x 441 x 594439 x 556 x 494 439 x 556 x 594352 x 422 x 427 352 x 422 x 527

352 x 537 x 427 352 x 537 x 52790 to 116125 to 146

60 to 8685 to 106

33

Page 21: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Trip-unit characteristics 0

Types of trip unitsTrip units for Compact NS

Depending on the version, Compact NS DC circuit breakers are equipped with:b 1P/2P: TM-D built-in thermal-magnetic trip unitsb 3P/4P: v up to 250 A, TM-D, TM-DC or TM-G interchangeable thermal-magnetic trip unitsv for 400 and 630 A, MP1, MP2, MP3 built-in magnetic trip units.

Masterpact NW DC circuit breakers, 3 or 4-pole, use built-in Micrologic 1.0 DC control units with instantaneous pick-ups.

Types of trip units

DB

1050

52

see page 34see page 110 (parallel connection of

poles)

see page 36

Trip units for Compact NS

TM thermal-magnetic trip unit up to 250 A

DB

1045

36

DB

1045

37

Up to 250 A for Compact NS, protection is provided by thermal-magnetic trip units.

For 1 or 2 poles, trip units are built inb TM-D up to 160 A: fixed thermal threshold and magnetic pick-up

For 3 or 4 poles, trip units are interchangeableb TM-D up to 63 A: adjustable thermal threshold and fixed magnetic pick-upb TM-DC from 80 to 250 A: fixed or adjustable (for 200 and 250 A) magnetic pick-up and adjustable thermal thresholdb TM-G, up to 63 A: adjustable thermal threshold and fixed low magnetic pick-up to protect long cables.

1 overload protection threshold.2 short-circuit protection pick-up.

34

Page 22: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Trip-unit characteristics 0

Trip units for Compact NS

Trip units for Compact NS100 - NS160 - NS250Single-pole and two-pole (built-in trip units)Type of trip unit TM-D

Rating In (A) at 40 °C 16 20 25 32 40 50 63 80 100 125 160Compact circuit breaker NS100N/H b b b b b b b b b - -

NS160N/H - - - - - - - - - b bOverload protection (thermal)

Tripping threshold Ir (A) at 40 °C Fixed

16 20 25 32 40 50 63 80 100 125 160Protection against short-circuits (magnetic)

Pick-up Im (A) Fixed

Compact circuit breaker NS100/160N/H Marked AC value (1) 190 190 300 300 500 500 500 640 800 1000 1250True DC value 260 260 400 400 700 700 700 800 1000 1200 1250

Three-pole 3P-3d and four-pole 4P-4d (interchangeable trip units)Type of trip unit TM-D TM-DC TM-G

Rating (A) In (A) at 40 °C 16 25 32 40 50 63 80 100 125 160 200 250 16 25 40 63

Compact circuit breaker NS100DC b b b b b b b b - - - - b b b bNS160DC b b b b b b b b b b - - b b b bNS250DC - - - - - - b b b b b b - - - -

Overload protection (thermal)Tripping threshold (A) Ir (at 40 °C) Adjustable

0.8 to 1 x In

Protection against short-circuits (magnetic)Pick-up (A) Im Fixed Adjustable FixedCompact circuit breaker NS100/160/250DC Marked AC value (1) 190 300 400 500 500 500 - - - - - - 63 80 80 125

True DC value 260 400 550 700 700 700 800 800 1250 1250 5 to 10 x In 80 100 100 150(1) The pick-up values for single-pole and two-pole, TMD and TMG magnetic trip units up to 63 A are marked with AC values. A correction coefficient is required to obtain the DC pick-up values indicated on the next line.The magnetic-protection pick-up values for TM-DC trip units are indicated directly in DC values.

MP magnetic trip unit for 400 and 630 A

DB

1045

38

Above 250 A, the protection of Compact NS 400 A and 630 A circuit breakers is ensuredby built-in magnetic trip units supplied mounted on the circuit breaker and offering one of three protection levels MP1, MP2 and MP3.

Compact NS400 - NS630 trip unitsThree-pole 3P-3D and four-pole 4P-3d (built-in trip units)Type of trip unit MP1 MP2 MP3

Circuit breaker Compact NS400DC b b -Compact NS630DC b b b

Protection against short-circuits (magnetic)Pick-up (A) Im Adjustable - -

800…1600 1250…2500 2000…4000

35

Page 23: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Trip-unit characteristics 0

Trip units for Masterpact NW

All Masterpact NW DC devices are equipped with a Micrologic 1.0 DC control unit.

Protection using the Micrologic 1.0 DC control unitMasterpact NW DC circuit breakers use Micrologic 1.0 DC control units. These interchangeable units with instantaneous thresholds, operating with electromagnetic sensors, can be adjusted on site.The circuit breakers can be used with the three versions of sensors,defined by their setting range.

PB

1011

39-3

2 Type of sensor 1250/2500 A 2500/5400 A 5000/11000 AMasterpact NW10 b b bMasterpact NW20 - b bMasterpact NW40 - - b

Adjustments Settings for Masterpact NW circuit breakers may be accessed from the front, with the switchboard door open.b Settings are made for the input (+ pole) and the output (- pole).b The setting range comprises eleven positions, plus five preferential settings marked A, B, C, D and E.b The setting values for the two corresponding sensors must be identical.

DB

1045

41

DB

1045

40

Magnetic pick-up value.

Two identical settings.

36

Page 24: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Trip-unit characteristics 0

Trip units for Masterpact NW

Setting values for magnetic pick-up Im

DB

1045

42

Settings marked A, B, C, D and EMinimum Maximum

Sensor versions SettingsA1 and A2

SettingsB1 and B2

SettingsC1 and C2

SettingsD1 and D2

SettingsE1 and E2

1250/2500 1250 A 1500 A 1600 A 2000 A 2500 A2500/5400 2500 A 3300 A 4000 A 5000 A 5400 A5000/11000 5000 A 8000 A 10000 A 11000 A 11000 A

Tolerances ±8 % ±10 % ±10 % ±10 % ±10 %

DB

1045

43

Intermediate settingsIt is possible to set eleven other (unmarked) intermediate values.

DB

1045

44

37

Page 25: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Communication 0

COM option in Masterpact NW

The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system.Masterpact uses the Digipact or Modbus communications protocol for full compatibility with the SMS PowerLogic power-monitoring system. An external gateway is available for communication on other networks:b Profibusb Ethernet…

The COM option in Masterpact is made up of:

For fixed devicesb a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases.

For drawout devicesb a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releasesb a "chassis" communication module supplied separately with its set of sensors (CE, CD and CT contacts).Status indication by the COM option is independent of the device indication contacts. These contacts remain available for conventional uses.

Digipact or Modbus "device" communication moduleThis module is independent of the control unit. It receives and transmits information on the communication network.

Digipact or Modbus "chassis" communication moduleThis module is independent of the control unit. The Modbus "chassis" communication module makes it possible to address the chassis and to conserve the address when the circuit breaker is in the disconnected position. Consumption: 30 mA, 24 V.

XF and MX communicating voltage releasesThe XF and MX communicating voltage releases are equipped for connection to the "device" communication module.Remote-tripping functions (second MX or MN) are independent of the communication option. These releases are therefore not equipped for connection to the "device" communication module.

PB

1007

82-2

6

PB

1007

77-2

6

DB

1050

53Digipact "device" communication module.

Digipact "chassis" communication module.

PB

1007

82-2

6

PB

1008

02-2

7

Modbus "device" communication module.

Modbus "chassis" communication module.

1 "Device" communication module.2 "Chassis" communication module.3 OF, SDE, PF and CH "device" sensors.4 CE, CD and CT "chassis" sensors.5 DMX and XF release.

DB

1045

95 : hard wiring.: communication bus.

Communication functionsThe Digipact or Modbus COM option may be used to:b identify the deviceb indicate status conditionsb control the device ON/OFF.

Switch-disconnectorand circuit breakerwith communication busDigipact Modbus

Device identificationAddress b bRating - -Type of device - -Type of control unit - -Status indications

ON/OFF (OF) b bSpring charged (CH) b bReady to close (PF) b bFault-trip (SDE) b bConnected/disconnected/test position (CE/CD/CT) b bControls

ON/OFF (MX/XF) b bSpring charging - -Reset of the mechanical indicator - -

38

Page 26: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Communication 0

Compact NS

Communication with the circuit breaker Compact NS is possible using a number of hardware solutions:b Advantys OTB Modbus interface module with built-in inputs/outputsb SC150 interfaceb communicating auxiliary contacts.

A number of hardware solutions are available for the range:b Advantys OTB Modbus interface module with 12 inputs/8 outputs built in and expandable by adding optional modules from the Twido rangeb communicating auxiliariesThey replace the standard auxiliaries and connect directly to the Digipact bus, with three equipment levels:v communicating auxiliary contacts, comprising:- OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts- electronic module- prefabricated wiring.v communicating auxiliary contacts and motor-mechanism module, comprising:- OF (on/off), SD (trip indication) and SDE (fault-trip indication) contacts- MCH motor-mechanism module (220 V AC) (1)

- electronic module- prefabricated wiring.v communicating carriage switches for the chassis, comprising:- CE / CD (connected/disconnected position) contacts- electronic module- wiring connectorb SC150 interfaceUsing the SC150 interface, it is possible to integrate a device equipped with non-communicating auxiliaries into a supervison system.The SC150 interface is used to connect:v the auxiliary contacts on the circuit breaker (OF, SD, SDE, SDV, CD, CE)v the remote-operation system (on, off, reset) v one unassigned digital input.

SoftwareTo make use of the information provided by the communicating devices, it is necessary to use software incorporating a Modbus driver. Schneider Electric offers two solutions: the RCU utility and SMS software.

RCU utilityThis is a set of Modbus drivers that, in conjunction with a PC, can be used to:b view device status (on/off and fault trip)b view variables: currents, voltages, power, energy (instantaneous and maximum values)b remotely open and close the device.

SMS (System Management Software)SMS is power-management software to control and monitor LV and MV electrical installations.The SMS family includes a number of products offering different features for all types of applications.SMS can communicate with all intelligent devices in the electrical installation.

Communication functions

PB

1010

38-2

5

Advantys OTB Modbus.

PB

1008

83-2

5

PB

1008

84-2

2

Compact NS equipped with communicating auxiliary contacts and motor-mechanism module.

Withdrawable Compact NS on its chassis equipped with communicating auxiliary contacts.

PB

1008

85-1

0

SC150 indication and control interface.

DB

1050

54

Compact equipped with:Advantys OTB Modbus

communicating auxiliaries

SC150

Device identificationAddress b b bIndication of status conditions

OF (on/off) b b bSD (trip indication) b b bSDE (fault-trip indication) b b bCE/CD(connected/disconnected position)

b b b

ControlsON/OFF MX/XF - b bLED reset - b bOperating and maintenance aids

Reading of the protection settings - - bOperation counter - - b

DB

1045

93 : hard wiring.: communication bus.: Modbus bus.

pushto

trip

125/160IEC947-2

UTE VDE BS CEI UNE NEMA

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

O OFFdischarged

Opush OFF

Ipush ON

pushto

trip

125/160IEC947-2

UTE VDE BS CEI UNE NEMA

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

O OFFdischarged

Opush OFF

Ipush ON

pushto

trip

125/160IEC947-2

UTE VDE BS CEI UNE NEMA

8

9

105

6

7

x 250A

Im

.81

x 250A

Ir

TM 250 D

250A/40˚C

ImIr

.9

39

Page 27: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

The plug-in configuration makes it possible to:b extract and/or rapidly replace the circuit breaker without having to touch connectionsb allow for the addition of future circuits at a later date.

Installation

Fixed circuit breakersCompact circuit breakers may be mounted vertically, horizontally or flat on their back without any derating of characteristics. They are designed for easy installation in the various types of switchboards of each market and country.

DB

1045

52

DB

1045

53

DB

1045

54

PB

1008

86-3

2

Mounting on a backplate (solid or slotted).

Mounting on rails. Mounting on DIN rail(with adapter).

DB

1045

55Fixed Compact NS250H.

DB

1045

50

Installation positions.Mounting on a Prisma functional mounting plate.

PB

1008

87-3

2

Circuit breaker on a plug-in base

DB

1045

56

DB

1045

57

DB

1045

58

Compact NS250H on a plug-in base.

Mounting on a backplate. Mounting through a front panel.

Mounting on rails.

DB

1045

51

Installation positions.

Protection against direct contacts with power circuitsb circuit breaker plugged in = IP4b circuit breaker removed = IP2b circuit breaker removed, base equipped with shutters = IP4

Parts of a plug-in configurationb Compact circuit breakerb set of power connectors added to the circuit breakerb plug-in base for mounting on a backplate or on railsb insulating screen, for use when the circuit breaker is installed on a backplate with front connectionsb safety trip, installed on the circuit breaker, that causes automatic tripping if the circuit breaker is ON, before engaging or withdrawing it. The safety trip does not prevent circuit breaker operation, even when it has been removedb mandatory short terminal shields.

AccessoriesInsulating accessories can be used to:b protect against direct contactb increase insulation between phases.

40

Page 28: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

b disconnected position - the power circuits are disconnected, but the circuit breaker is still on the chassis and may still be operated (ON, OFF, push-to-trip)b the circuit breaker may be locked using 1 to 3 padlocks (shackle diameter 5 to 8 mm), to prevent connectionb the auxiliaries can be tested (with manual auxiliary connector).

Circuit breaker on a withdrawable chassis

DB

1045

59

Connected. Disconnected. Removed.

The chassis is made up of two side plates installed on the base and two other plates mounted on the circuit breaker.

Accessoriesb auxiliary contacts for installation on the fixed part, indicating the "connected" and "disconnected" positionsb toggle collar for circuit breakers with a toggle mounted through a front panel, intended to maintain the degree of protection whatever the position of the circuit breaker (supplied with a toggle extension)b keylock which, depending on the bolt fitted, can be used to:v prevent insertion for connectionv lock the circuit breaker in the connected or disconnected positionsb telescopic shaft for extended rotary handles.

PB

1008

88-3

4

Compact NS250H on a withdrawable chassis.

DB

1045

51

Installation positions.

DB

1045

60

DB

1045

61

Connection of fixed devices

Front connection of bars or cables with lugsThe Compact NS100 to NS630 devices are equipped as standard with terminals comprising snap-in nuts with screws (M8 for NS100 to 250, M10 for NS400 to 630) for direct connection to insulated bars or cables with lugs.Additional terminal extensions (right-angle, edgewise, spreaders) are available for all connection requirements.

LugsLugs are different for copper and aluminium cables. They are supplied with interphase barriers and are compatible with the long terminal shields.b the small lugs for copper cables may be used for cables with the following cross-sectional areas:v 120, 150 or 185 mm2 (NS100 to 250)v 240 or 300 mm2 (NS400 to 630).Crimping by hexagonal barrels or punching.b the small lugs for aluminium cables may be used for cables with the following cross-sectional areas:v 150 or 185 mm2 (NS100 to 250)v 240 or 300 mm2 (NS400 to 630).Crimping by hexagonal barrels.

DB

1045

64

Right-angle terminal extensions.

DB

1045

65

Straight terminal extensions for NS100 to 250.

DB

1045

66

DB

1045

62

DB

1045

63

Edgewise terminal extensions for NS400 to 630.

DB

1045

67

Small lug for copper cables.

DB

1045

68

Small lug for aluminium cables.

41

Page 29: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Insulation of live parts

DB

1045

78

Terminal shieldsTerminal shields are sealable insulating accessories used for protection against direct contact with power circuits (degree of protection IP40, IK07). They are supplied with sealing accessories.

Terminal-shield selectionb fixed circuit breaker, front connection - long terminal shieldsb fixed circuit breaker, rear connection - short terminal shieldsb for voltages u 500 V, terminal shields are mandatoryb for voltages > 600 V, special connection kit with terminal shields and insulating screensb for withdrawable circuit breaker (plug-in and chassis type), short terminal shields on the device are mandatory. Terminal shields on the base are possible.

Long terminal shields for plug-in bases are used to:b protect against direct contact with power circuits (degree of protection IP40, IK07)b increase insulation between phases.

Insulating accessories for plug-in bases include:b an adapter offering the same connection possibilities as the circuit breakerb long terminal shields for the plug-in base.

Interphase barriersSafety accessories for maximum insulation at the power-connection points:b they clip easily onto the circuit breakerb not compatible with terminal shieldsb special version for plug-in bases.

DB

1045

69

Terminal shields.

DB

1045

70

Compact NS equipped with terminal shields.

Interphase barriers.

Accessories for series and parallel connection

A limited number of accessories can be used to optimise series and parallel connection of poles.

Accessories for series connectionThese include series connection plates, equipped with heat sinks.

Accessories for parallel connectionParallel pole connection accessories are identical to those for series connections. The are equipped with heat sinks. Customer connections are made directly to the connection plates after removing the heat sinks.

DB

1047

26

DB

1047

27

Series connection plates equipped with heat sinks.

DB

1047

28

DB

1047

29

DB

1047

30

Parallel connection plates.

42

Page 30: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Connection of electrical auxiliaries

DB

1049

73

Fixed configurationAuxiliary circuits exit the device through a knock-out in the front cover.

DB

1045

73

Compact NS100/160/250.

DB

1049

74

Plug-in and withdrawable configurations

DB

1045

74

Compact NS400/630.

Automatic auxiliary connectorsAuxiliary circuits exit the circuit breaker via one to three automatic auxiliary connectors (nine wires each). These are made up of:b a moving part, connected to the circuit breaker via a support (one support per circuit breaker)b a fixed part, mounted on the plug-in base, equipped with connectors for bare cables up to 2.5 mm2.

Selection of automatic auxiliary connectorsFor Compact NS400 to 630, connection wires for the options installed with trip unit STR53UE also exit via the automatic auxiliary connectors.

DB

1049

75

DB

1049

76

Compact NS100 to NS250. Compact NS400 to NS630.

Manual auxiliary connector for withdrawable configurationsWithdrawable circuit breakers may be equipped with one to three plugs with nine wires each. In "disconnected" position, the auxiliaries remain connected and can therefore be tested by operating the circuit breaker.

Each auxiliary is equipped with a terminal block with numbered terminals for connection of wires up to:b 1.5 mm2 for auxiliary contacts and voltage releasesb 2.5 mm2 for the motor-mechanism module.

DB

1045

77

Nine-wire manual auxiliary connector.

43

Page 31: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Indication contacts

PB

1010

33-1

8

Common-point changeover contacts are used to remote circuit-breaker status information and can thus be used for indications, electrical locking, relaying, etc.They comply with the IEC 60947-5 international recommendation.

Functionsb OF (ON/OFF) - indicates the position of the circuit breaker contactsb SD (trip indication) - indicates that the circuit breaker has tripped due to:v an overloadv a short-circuitv an earth-leakage faultv operation of a voltage releasev operation of the "push to trip" buttonv disconnection when the device is ON.Returns to de-energised state when the circuit breaker is resetb SDE (fault indication) - indicates that the circuit breaker has tripped due to:v an overloadv a short-circuit.Returns to de-energised state when the circuit breaker is resetb CAM (early-make or early-break function) - indicates the position of the rotary handle. Used in particular for advanced opening of safety trip devices (early break) or to energise a control device prior to circuit-breaker closing (early make)b CE / CD (connected/disconnected position) - microswitch type carriage switches for withdrawable circuit breakers.

Installationb OF, SD and SDE functions - a single type of contact provides all these different indication functions, depending on where it is inserted in the device. The contacts clip into slots behind the front cover of the circuit breaker.The SDE function on a circuit breaker equipped with a thermal-magnetic trip unit requires the SDE actuator.b CAM function - the contact fits into the rotary-handle unit (direct or extended).b CE / CD (connected/disconnected) function - two parts must be fitted on the fixed and moving parts of the chassis.

Changeover contacts.

All the auxiliary contacts opposite are also available in "low-level" versions capable of switching very low loads (e.g. for the control of PLCs or electronic circuits).

Caractéristiques électriques des contacts auxiliaires

Contacts Standard Low levelRated thermal current (A) 6 5

Minimum load 100 mA at 24 V 1 mA at 4 VUtilisation cat. (IEC 60947-5-1) AC12 AC15 DC12 DC14 AC12 AC15 DC12 DC14Operational current (A) 24 V 6 6 6 1 5 3 5 1

48 V 6 6 2.5 0.2 5 3 2.5 0.2110 V 6 5 0.6 0.05 5 2.5 0.6 0.05220/240 V 6 4 - - 5 2 - -

250 V - - 0.3 0.03 5 - 0.3 0.03380/440 V 6 2 - - 5 1.5 - -480 v 6 1.5 - - 5 1 - -

660/690 V 6 0.1 - - - - - -

44

Page 32: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Remote tripping

PB

1010

36-2

8

MX or MN voltage releases are used to trip the circuit breaker.

MN undervoltage releaseThis release trips the circuit breaker when the control voltage drops below a tripping threshold:b tripping threshold between 0.35 and 0.7 times the rated voltageb circuit breaker closing is possible if the voltage exceeds 0.85 times the rated voltage. For a lower value, circuit breaker closing cannot be guaranteed.Circuit breaker tripping by an MN release meets the requirements of standard IEC 60947-2.

Time-delay unit for an MN releaseEliminates nuisance tripping due to transient voltage dips lasting 200 ms.It is used in conjunction with:b a 250 V DC MN release, control voltage 220/240 V ACb a 48 V DC MN release, control voltage 48 V AC.

MX shunt releaseTrips the circuit breaker when the control voltage rises above 0.7 x Un.Control signals can be of the impulse type (u 20 ms) or maintained.

OperationWhen the circuit breaker has been tripped by an MN or MX release, it must be reset locally.MN or MX tripping takes priority over manual closing.In the presence of a standing trip order, closing of the contacts, even temporary, is not possible.

Mechanical characteristicsb endurance is equal to 50 % of the mechanical endurance of the circuit breakerb the releases clip in behind the front coverb connection using wires up to 1.5 mm2, to integrated terminal blocks.

Electrical characteristicsb consumption:v pick-up (MX): < 10 VAv seal-in (MN and MNR): < 5 VA.b response time: < 50 ms.

MX or MN voltage release.

45

Page 33: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Rotary handles

PB

1010

34-3

0

There are two types of rotary handle:b direct rotary handleb extended rotary handle.

There are two models:b standard with a black handleb VDE with a red handle and yellow front for machine-tool control.

Direct rotary handleDegree of protection IP40, IK07.

The direct rotary handle maintains:b visibility of and access to trip unit settingsb suitability for isolationb indication of the three positions O (OFF), I (ON) and trippedb access to the "push to trip" buttonb circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied).It replaces the circuit-breaker front cover.

Accessories transform the standard direct rotary handle for the following situations:b motor control centre (MCC) switchboards:v door opening disabled when the circuit breaker is ONv circuit-breaker closing is disabled if the door is openb a higher degree of protection (IP43, IK07)b machine-tool control, complying with CNOMO E03.81.501, IP54, IK08.

Compact NS250L with a direct rotary handle.

PB

1010

35-5

5

Extended rotary handleDegree of protection IP 55, IK08.This handle makes it possible to operate circuit breakers installed at the back of switchboards, from the switchboard front.

It maintains:b suitability for isolationb indication of the three positions O (OFF), I (ON) and trippedb access to trip unit settings, when the switchboard door is openb circuit breaker locking capability in the OFF position by one to three padlocks, shackle diameter 5 to 8 mm (not supplied).The door cannot be opened if the circuit breaker is ON or locked.

The extended rotary handle is made up of:b a unit that replaces the front cover of the circuit breaker (secured by screws)b an assembly (handle and front plate) on the door that is always secured in the same position, whether the circuit breaker is installed vertically or horizontallyb an extension shaft that must be adjusted to the distance. The min/max distance between the back of circuit breaker and door is:v 185 to 600 mm for Compact NS100 to 250v 210 to 625 mm for Compact NS400 to 630.For withdrawable configurations, the extended rotary handle is also available with a telescopic shaft with two stable positions.

Compact NS250L with an extended rotary handle.

46

Page 34: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Motor-mechanism module

PB

1010

37-4

0

When equipped with a motor-mechanism module, Compact NS circuit breakers feature very high mechanical endurance as well as easy and sure operation:b all circuit-breaker indications and information remain visible and accessible, including trip-unit settings and indicationsb suitability for isolation is maintained and padlocking remains possibleb double insulation of the front face.

Applicationsb local motor-driven operation, centralised operation, automatic distribution controlb normal/standby source changeover or switching to a replacement source to optimise energy costsb load shedding and reconnection.

Automatic operationb circuit-breaker ON and OFF controlled by two impulse-type or maintained control signalsb automatic spring charging following voluntary tripping (by MN or MX), with standard wiringb mandatory manual reset following tripping due to an electrical fault.

Manual operationb transfer to manual mode using a switch (9) with possibility of remote mode indicationb circuit-breaker ON and OFF controlled by 2 pushbuttonsb recharging of stored-energy system by pumping the lever 9 timesb padlocking in OFF position.

Installation and connectionAll installation (fixed, plug-in/withdrawable) and connection possibilities are maintained.Motor-mechanism module connections are made behind its front cover to integrated terminals, for cables up to 2.5 mm2.

Accessoriesb keylock for locking in OFF positionb operations counter for the Compact NS400 and NS630, indicating the number of ON and OFF cycles. The counter must be installed on the front of the motor-mechanism module.

Compact NS250H with motor mechanism.

DB

1045

79

Characteristics1 Contact position indicator (suitability for isolation).2 Outgoing-circuit identification labels.3 Spring status indicator (charged, discharged).4 Locking device (keylock).5 Locking device (OFF position), using 1 to 3 padlocks,

shackle diameter 5 to 8 mm, not supplied.6 Manual spring-charging lever.7 I (ON) pushbutton.8 O (OFF) pushbutton.9 Manual/auto mode selection switch. The position of this

switch can be indicated remotely.10 Operations counter (Compact NS400/630).

Motor mechanism MT100 to MT630Response time (ms) Opening < 600

Closing < 80Rate Cycles/minute max. 4Control voltage (V) DC 24/30 - 48/60 - 110/130 - 250

AC 50/60 Hz 48 (50 Hz) - 110/130220/240 - 380/440

Consumption (W) (1) DC (W) Opening y 500Closing y 500

AC (VA) Opening y 500Closing y 500

(1) For NS100/250, motor "vibratory" type consider inrush current as 2 In during 10 ms cycling.

Electrical enduranceCircuit breaker + motor-mechanism module, in thousands of operations (IEC 60947-2), at 500 V - 2P, 750 V - 3P.

DB

1050

55

47

Page 35: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Locking systemsLocking in the OFF position guarantees isolation as per IEC 60947-2.Padlocking systems can receive up to three padlocks with shackle diameters ranging from 5 to 8 mm (padlocks not supplied).

Control device Function Meansrequired AccessoriesToggle Lock in OFF position padlock removable device

Lock in OFF or ON position

padlock fixed device

Direct rotary handle Lock in OFF position padlock -keylock keylocklocking device

+ keylockMCC rotary handle Lock in OFF position padlock -

Rotary handle Lock in OFF position padlock -Extended rotary handle Lock in OFF position,

door opening prevented

keylock keylock

Motor mechanism Lock in OFF position motor mechanism locked out

padlock -keylock keylocklocking device

+ keylock

DB

1045

81

DB

1045

82

DB

1045

83

Locking of the toggle using a removable device.

Locking of the toggle using a fixed device.

Locking of the rotary handle using a padlock or a keylock.

EscutcheonsEscutcheons are an optional feature mounted on the switchboard door. They increase the degree of protection to at least IP40, IK07.

DB

1045

86

DB

1045

84

DB

1045

85

DB

1045

87

Front-panel escutcheons for toggle. Secures to the panel, from the front.

Toggle cover:b degree of protection IP43, IK07 b fits on the front of the circuit breaker.

Front-panel escutcheon for rotary handle.Secures to the panel by four screws, from the front.

ONI

profalux

OOFF

profalux

OOFF

ONI

pushto

trip

48

Page 36: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Compact NS100 to 630

Protection collar for toggleProtection collars maintain the degree of protection, whatever the position of the device (connected, disconnected).b front-panel escutcheons are mandatory (same as those for rotary handles and ammeter modules)b collars are mounted on the device using two screwsb escutcheons are attached to the switchboardb a toggle extension is supplied with the collar.

Front-panel escutcheons for motor mechanism, rotary handles, ammeter modulesSame as for fixed devices.

DB

1045

89

Outgoing-circuit identificationCompact NS100 to 630 devices come with clip-in labels for hand-written indications.It is also possible to use pre-printed Telemecanique labels part number AB1-**: b Compact NS100 to 250: 8 digitsb Compact NS400 to 630: 16 digits.

DB

1045

90

Identification accessories.

Sealing accessoriesThis option includes the elements required to fit lead seals to prevent:b front removalb rotary-handle removalb opening of the motor-mechanism moduleb access to auxiliariesb access to trip-unit settingsb trip-unit removalb access to earth-leakage protection settingsb terminal-shield removalb access to power connections.

DB

1045

91

Sealing accessories.

49

Page 37: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Locking on the device

DB

1048

04

1 Fault trip indication andreset button.

2 OFF position locking.3 Electrical closing

pushbutton.4 ON pushbutton.5 OFF pushbuton.6 Operating mechanism

charged and "ready toclose" indication.

7 Pushbutton locking.8 Main contact position

indication.9 Operation counter.

PB

1008

11-3

2

Pushbutton lockingb The transparent cover blocks access to the pushbuttons used to open and close the device.It is possible to independently lock the opening button and the closing button. The locking device is often combined with a remote operating mechanism.The pushbuttons may be locked using either:b three padlocks (not supplied)b lead sealb two screws.

Device locking in the OFF positionThe circuit breaker is locked in the OFF position by physically maintaining the opening pushbutton pressed down:b using padlocks (one to three padlocks, not supplied)b using keylocks (one or two different keylocks, supplied).Keys may be removed only when locking is effective (Profalux or Ronis type locks). The keylocks are available in any of the following configurations:b one keylockb one keylock mounted on the device + one identical keylock supplied separately for interlocking with another deviceb two different key locks for double locking.Profalux and Ronis keylocks are compatible with each other.A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell).

Accessory-compatibility 3 padlocks and/or 2 keylocks.

Cable-type door interlockThis option prevents door opening when the circuit breaker is closed and prevents circuit breaker closing when the door is open.For this, a special plate associated with a lock and a cable is mounted on the right side of the circuit breaker.With this interlock installed, the source changeover function cannot be implemented.

Access to pushbuttons protected by transparent cover.

PB

1008

10-3

2

Pushbutton locking using a padlock.

PB

1008

12-3

2

OFF position locking using a padlock.

PB

1008

13-3

0

OFF position locking using a keylock.

50

Page 38: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Locking on the chassis

DB

1048

05

1 Racking-handle port.2 "Connected/test/

disconnected" position indication.

3 Racking interlock.4 Racking-handle storage.5 Reset pushbutton.6 Padlock locking.7 Keylock locking.8 Chassis front plate

(accessible with cubicle door closed).

9 "Disconnected" position door interlock.

10 Mismatch protection.

"Disconnected" position lockingMounted on the chassis and accessible with the door closed, these devices lock the circuit breaker in the "disconnected" position in two manners:b using padlocks (standard), up to three padlocks (not supplied)b using keylocks (optional), one or two different keylocks are available.Profalux and Ronis keylocks are available in different options:b one keylockb two different keylocks for double lockingb one (or two) keylocks mounted on the chassis + one (or two) identical keylocks supplied separately for interlocking with another device.A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell).

Connected", "disconnected" and "test" position lockingThe "connected", "disconnected" and "test" positions are shown by an indicator. The exact position is obtained when the racking handle blocks. A release button is used to free it.On request, the "disconnected" position locking system may be modified to lock the circuit breaker in any of the three positions, "connected", "disconnected" and "test".

Door interlock catchMounted on the right or left-hand side of the chassis, this device inhibits opening of the cubicle door when the circuit breaker is in "connected" or "test" position. It the breaker is put in the "connected" position with the door open, the door may be closed without having to disconnect the circuit breaker.

E89

585

Racking interlockThis device prevents insertion of the racking handle when the cubicle door is open.

Cable-type door interlockThis option is identical for fixed and drawout versions.

Racking interlock between crank and OFF pushbuttonThis option makes it necessary to press the OFF pushbutton in order to insert the racking handle and holds the device open until the handle is removed.

Racking interlock.

PB

1008

15-3

2

Automatic spring discharge before breaker removalThis option discharges the springs before the breaker is removed from the chassis.

Mismatch protectionMismatch protection ensures that a circuit breaker is installed only in a chassis with compatible characteristics. It is made up of two parts (one on the chassis and one on the circuit breaker) offering twenty different combinations that the user may select.

Mismatch protection.

51

Page 39: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Indication contacts are available:b in the standard version for relay applicationsb in a low-level version for control of PLCs and electronic circuits.

ON/OFF indication contacts (OF) (microswitch type).

ON/OFF indication contacts (OF) (rotary type).

Additional "fault-trip" indication contacts (SDE).

Combined contacts.

Indication contacts

ON/OFF indication contacts (OF)Rotary type changeover contacts directly driven by the mechanism. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached.

OFSupplied as standard 4

PB

1008

06-3

2

Maximum number 12Breaking capacity (A)p.f.: 0.3AC12/DC12

Standard minimum load: 100 mA/24 VV AC 240/380 10/6 (1)

480 10/6 (1)

690 6V DC 24/48 10/6 (1)

125 10/6 (1)

250 3Low-level minimum load: 2 mA/15 V DC

V AC 24/48 6240 6380 3

V DC 24/48 6125 6250 3

(1) Standard contacts: 10 A; optional contacts: 6 A.

"Fault-trip" indication contacts (SDE)Circuit-breaker tripping due to a fault is signalled by:b a red mechanical fault indicator (reset)b one changeover contact (SDE).Following tripping, the mechanical indicator must be reset before the circuit breakermay be closed.

PB

1008

07-2

0

SDESupplied as standard 1Maximum number 2Breaking capacity (A)p.f.: 0.3AC12/DC12

Standard minimum load: 100 mA/24 VV AC 240/380 5

480 5690 3

V DC 24/48 3125 0.3

PB

1008

20-3

2

250 0.15Low-level minimum load: 2 mA/15 V DC

V AC 24/48 3240 3380 3

V DC 24/48 3125 0.3250 0.15

Combined "connected/closed" contacts (EF)The contact combines the "device connected" and the "device closed" information to produce the "circuit closed" information.Supplied as an option for Masterpact NW, it is mounted in place of the connector of an additional OF contact.

PB

1008

16-3

2

EFMaximum number 8Breaking capacity (A)p.f.: 0.3AC12/DC12

Standard minimum load: 100 mA/24 VV AC 240/380 6

480 6690 6

V DC 24/48 2.5125 0.8250 0.3

Low-level minimum load: 2 mA/15 V DCV AC 24/48 5

240 5380 5

V DC 24/48 2.5125 0.8250 0.3

52

Page 40: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

P

B10

0817

-32

CE, CD and CT "connected/disconnected/test" position carriage switches.

"Connected", "disconnected" and "test" position carriage switchesThree series of optional auxiliary contacts are available for the chassis:b changeover contacts to indicate the "connected" position (CE)b changeover contacts to indicate the "disconnected" position (CD). This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached.b changeover contacts to indicate the "test" position (CT). In this position, the power circuits are disconnected and the auxiliary circuits are connected.

Additional actuatorsA set of additional actuators may be installed on the chassis to change the functions of the carriage switches.

Contacts CE CD CTMaximum number Standard with additional

actuators3966

3030

3003

Breaking capacity (A)p.f.: 0.3AC12/DC12

Standard minimum load: 100 mA/24 VV AC 240 8

380 8480 8690 6

V DC 24/48 2.5125 0.8250 0.3

Low-level minimum load: 2 mA/15 V DC

V AC 24/48 5

240 5380 5

V DC 24/48 2.5

125 0.8250 0.3

53

Page 41: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Two solutions are available for remote operation of Masterpact devices:b a point-to-point solutionb a bus solution with the COM communication option.

Remote operation: remote ON / OFFThe remote ON / OFF function is used to remotely open and close the circuit breaker. It is made up of:b an electric motor (MCH) equipped with a "springs charged" limit switch contact (CH)b two voltage releases:v a closing release (XF)v an opening release (MX).Optionally, other functions may be added:b a "ready to close" contact (PF)b an electrical closing pushbutton (BPFE)b remote reset following a fault.A remote-operation function is generally combined with:b device ON / OFF indication (OF)b "fault-trip" indication (SDE).

PB

1007

65-6

8

Wiring diagram of a point-to-point remote ON / OFF functionNote: An opening order always takes priority over a closing order.If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit breaker remains in the open position (OFF).In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position.Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker.When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or blocking the circuit breaker in the open position.

DB

1051

91

Wiring diagram of a bus-type remote ON / OFF functionNote: MX communicating releases are of the impulse type only and cannot be used to lock a circuit breaker in OFF position. For locking in OFF position, use the remote tripping function (2nd MX or MN).

DB

1011

65

54

Page 42: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

P

B10

0808

-32

Electric motor (MCH) for Masterpact NW.

XF and MX voltage releases.

"Ready to close" contacts (PF).

Electric motor (MCH)The electric motor automatically charges and recharges the spring mechanism when the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible following opening. The spring-mechanism charging handle is used only as a backup if auxiliary power is absent.The electric motor (MCH) is equipped as standard with a limit switch contact (CH) that signals the "charged" position of the mechanism (springs charged).

CharacteristicsPower supply V AC 50/60 Hz 48/60 - 100/130 - 200/240 - 277 - 380/415 - 400/440 - 480

V DC 24/30 - 48/60 - 100/125 - 200/250Operating threshold 0.85 to 1.1 UnConsumption (VA or W) 180Motor overcurrent 2 to 3 In for 0.1 sCharging time maximum 4 secondsOperating frequency maximum 3 cycles per minuteCH contact 10 A at 240 V

DB

1011

79

Voltage releases (XF and MX)Their supply can be maintained or automatically disconnected.

Closing release (XF)The XF release remotely closes the circuit breaker if the spring mechanism is charged.

Opening release (MX)The MX release instantaneously opens the circuit breaker when energised. It locks the circuit breaker in OFF position if the order is maintained (except for MX "communicating" releases).

Note: whether the operating order is maintained or automatically disconnected (pulse-type), XF or MX "communicating" releases ("bus" solution with "COM" communication option) always have an impulse-type action.

Characteristics XF MXPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480

V DC 12 - 24/30 - 48/60 - 100/130 - 200/250Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un

PB

1008

09-1

6

Consumption (VA or W) pick-up: 200 (during 200 ms)hold: 4.5

pick-up: 200 (during 200 ms)hold: 4.5

Circuit-breaker response time at Un 70 ms ± 10 (NW y 4000 A)80 ms ± 10 (NW > 4000 A)

50 ms ± 10 (NW)

"Ready to close" contact (PF)The "ready to close" position of the circuit breaker is indicated by a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid:b the circuit breaker is in the OFF positionb the spring mechanism is chargedb a maintained opening order is not present:v MX energisedv fault tripv remote tripping (second MX or MN)v device not completely racked inv device locked in OFF positionv device interlocked with a second device.P

B10

0818

-16

CharacteristicsSupplied as standard -Maximum number 1Breaking capacityp.f.: 0.3AC12/DC12

Standard minimum load: 100 mA/24 VV AC 240/380 5

480 5690 3

V DC 24/48 3125 0.3250 0.15

Low-level minimum load: 2 mA/15 V DCV AC 24/48 3

240 3380 3

V DC 24/48 3125 0.3250 0.15

55

Page 43: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Electrical closing pushbutton (BPFE)Located on the front panel, this pushbutton carries out electrical closing of the circuit breaker. It is generally associated with the transparent cover that protects access to the closing pushbutton.Electrical closing via the BPFE pushbutton takes into account all the safety functions that are part of the control/monitoring system of the installation.The BPFE connects to the closing release (XF) in place of the COM module.

DB

1011

67

Remote reset after fault tripElectrical reset after fault trip (Res)Following tripping, this function resets the "fault trip" indication contacts (SDE) and the mechanical indicator and enables circuit breaker closing.Power supply: 110 / 130 V AC and 200 / 240 V AC.

DB

1011

69

Automatic reset after fault trip (RAR)Following tripping, a reset of the mechanical indicator (reset button) is no longer required to enable circuit-breaker closing. The mechanical (reset button) and electrical (SDE) indications remain in fault position until the reset button is pressed.

56

Page 44: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Remote operation: remote tripping

PB

1008

19-6

8

This function opens the circuit breaker via an electrical order. It is made up of:b a shunt release (second MX)b or an undervoltage release (MN)b or a delayed undervoltage release (MN + delay unit).These releases (2nd MX or MN) cannot be operated by the communication bus.The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker.

Wiring diagram for the remote-tripping function

DB

1011

72

DB

1011

75

DB

1011

77

PB

1008

09-1

6

Voltage releases (second MX)When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the second MX locks the circuit breaker in the OFF position.

CharacteristicsPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480

V DC 24/30 - 48/60 - 100/130 - 200/250Operating threshold 0.7 to 1.1 UnPermanent locking function 0.85 to 1.1 UnConsumption (VA or W) pick-up: 200 (during 200 ms) hold: 4.5

MX or MN voltage release. Circuit-breaker response time at Un 50 ms ±10

Instantaneous voltage releases (MN)The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuit-breaker closing is enabled again when the supply voltage of the release returns to 85 % of its rated value.

CharacteristicsPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480

V DC 12 - 24/30 - 48/60 - 100/130 - 200/250Operating threshold opening 0.35 to 0.7 Un

closing 0.85 UnConsumption (VA or W) pick-up: 200 (during 200 ms) hold: 4.5MN consumption with delay unit pick-up: 400 (during 200 ms) hold: 4.5Circuit-breaker response time at Un 90 ms ±5

MN delay unitsTo eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable.

CharacteristicsPower supply non-adjustable 100/130 - 200/250VAC 50-60 Hz/DC adjustable 48/60 - 100/130 - 200/250 - 380/480Operating threshold opening 0.35 to 0.7 Un

closing 0.85 UnConsumption of delay unit alone (VA or W) pick-up: 200 (during 200 ms) hold: 4.5Circuit-breaker response time at Un

non-adjustable 0.25 sadjustable 0.5 s - 0.9 s - 1.5 s - 3 s

57

Page 45: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

Functions and characteristics

Electrical and mechanical accessories 0

Masterpact NW10 to NW40

Shields, blanking plates, counters

PB

1008

21-6

8

Auxiliary terminal shield (CB)Optional equipment mounted on the chassis, the shield prevents access to the terminal block of the electrical auxiliaries.

PB

1008

22-3

2

Operation counter (CDM)The operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions.

DB

1011

73

Escutcheon (CDP)Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP 40 (circuit breaker installed free standing: IP30) . It is available in fixed and drawout versions.

Blanking plate (OP) for escutcheonUsed with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices.

Transparent cover (CP) for escutcheonOptional equipment mounted on the escutcheon, the cover is hinged and secured by a screw. It increases the degree of protection to IP 54, IK10. It adapts to drawout devices.

Escutcheon (CDP) with blanking plate.

PB

1007

76-4

2

Transparent cover (CP) for escutcheon.

58

Page 46: Compact NS - schneider-electric.com · Electromagnetic compatibility 28 Degree of protection 29 Circuit-breaker characteristics 30 Compact NS100 to NS630 30 Masterpact NW10 to NW40

59