Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 CEMENT PLASTERING 092400 - 1 SECTION 092400 - CEMENT PLASTERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Interior vertical plasterwork. 2. Interior horizontal and nonvertical plasterwork. 1.3 PREINSTALLATION MEETINGS A. Preinstallation Conference: Conduct conference at Project site. 1.4 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: Show locations and installation of control and expansion joints, including plans, elevations, sections, details of components, and attachments to other work. C. Samples: For each type of factory-prepared finish coat and for each color and texture specified. D. Samples for Initial Selection: For each type of factory-prepared finish coat and for each color and texture specified. E. Samples for Verification: For each type of factory-prepared finish coat and for each color and texture specified, 12 by 12 inches and prepared on rigid backing. 1.5 QUALITY ASSURANCE A. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate aesthetic effects, and to set quality standards for materials and execution. 1. Build mockups for each substrate and finish texture indicated for cement plastering, including accessories.

Upload: others

Post on 13-Feb-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

CEMENT PLASTERING 092400 - 1

SECTION 092400 - CEMENT PLASTERING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Interior vertical plasterwork. 2. Interior horizontal and nonvertical plasterwork.

1.3 PREINSTALLATION MEETINGS

A. Preinstallation Conference: Conduct conference at Project site.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product.

B. Shop Drawings: Show locations and installation of control and expansion joints, including plans, elevations, sections, details of components, and attachments to other work.

C. Samples: For each type of factory-prepared finish coat and for each color and texture specified.

D. Samples for Initial Selection: For each type of factory-prepared finish coat and for each color and texture specified.

E. Samples for Verification: For each type of factory-prepared finish coat and for each color and texture specified, 12 by 12 inches and prepared on rigid backing.

1.5 QUALITY ASSURANCE

A. Mockups: Build mockups to verify selections made under Sample submittals, to demonstrate aesthetic effects, and to set quality standards for materials and execution.

1. Build mockups for each substrate and finish texture indicated for cement plastering, including accessories.

Page 2: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

CEMENT PLASTERING 092400 - 2

a. Size: 100 sq. ft. in surface area.

2. For interior plasterwork, simulate finished lighting conditions for review of mockups. 3. Approval of mockups does not constitute approval of deviations from the Contract

Documents contained in mockups unless Architect specifically approves such deviations in writing.

4. Subject to compliance with requirements, approved mockups may become part of the completed Work if undisturbed at time of Substantial Completion.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Store materials inside under cover, and keep them dry and protected against damage from weather, moisture, direct sunlight, surface contamination, corrosion, construction traffic, and other causes.

1.7 FIELD CONDITIONS

A. Comply with ASTM C 926 requirements.

B. Interior Plasterwork: Maintain room temperatures at greater than 40 deg F for at least 48 hours before plaster application, and continuously during and after application.

1. Avoid conditions that result in plaster drying out during curing period. Distribute heat evenly; prevent concentrated or uneven heat on plaster.

2. Ventilate building spaces as required to remove water in excess of that required for hydrating plaster in a manner that prevents drafts of air from contacting surfaces during plaster application and until plaster is dry.

C. Factory-Prepared Finishes: Comply with manufacturer's written recommendations for environmental conditions for applying finishes.

PART 2 - PRODUCTS

2.1 METAL LATH

A. Expanded-Metal Lath: ASTM C 847, cold-rolled carbon-steel sheet with ASTM A 653/A 653M, G60 hot-dip galvanized-zinc coating.

1. Diamond-Mesh Lath: Flat, 3.4 lb/sq. yd.

2.2 ACCESSORIES

A. General: Comply with ASTM C 1063, and coordinate depth of trim and accessories with thicknesses and number of plaster coats required.

Page 3: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

CEMENT PLASTERING 092400 - 3

B. Metal Accessories:

1. Cornerite: Fabricated from metal lath with ASTM A 653/A 653M, G60, hot-dip

galvanized-zinc coating. 2. External- (Outside-) Corner Reinforcement: Fabricated from metal lath with

ASTM A 653/A 653M, G60, hot-dip galvanized-zinc coating. 3. Cornerbeads: Fabricated from zinc-coated (galvanized) steel.

a. Smallnose cornerbead with expanded flanges; use unless otherwise indicated.

2.3 MISCELLANEOUS MATERIALS

A. Water for Mixing and Finishing Plaster: Potable and free of substances capable of affecting plaster set or of damaging plaster, lath, or accessories.

B. Fiber for Base Coat: Alkaline-resistant glass or polypropylene fibers, 1/2 inch long, free of contaminants, manufactured for use in cement plaster.

C. Bonding Compound: ASTM C 932.

D. Fasteners for Attaching Metal Lath to Substrates: ASTM C 1063.

E. Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, not less than 0.0475-inch diameter unless otherwise indicated.

2.4 PLASTER MATERIALS

A. Masonry Cement: ASTM C 91, Type N.

1. Color for Finish Coats: White.

B. Lime: ASTM C 206, Type S; or ASTM C 207, Type S.

C. Sand Aggregate: ASTM C 897.

1. Color for Job-Mixed Finish Coats: White.

D. Acrylic-Based Finish Coatings: Factory-mixed acrylic-emulsion coating systems formulated with colorfast mineral pigments and fine aggregates; for use over cement plaster base coats. Include manufacturer's recommended primers and sealing topcoats for acrylic-based finishes.

1. Color: Match Architect's sample

2.5 PLASTER MIXES

A. General: Comply with ASTM C 926 for applications indicated.

Page 4: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

CEMENT PLASTERING 092400 - 4

1. Fiber Content: Add fiber to base-coat mixes after ingredients have mixed at least two minutes. Comply with fiber manufacturer's written instructions for fiber quantities in mixes, but do not exceed 1 lb of fiber/cu. Yd. of cementitious materials.

B. Base-Coat Mixes for Use over Metal Lath: Scratch and brown coats for three-coat plasterwork as follows:

1. Masonry Cement Mixes:

a. Scratch Coat: Mix 1 part masonry cement and 2-1/2 to 4 parts aggregate. b. Brown Coat: Mix 1 part masonry cement and 3 to 5 parts aggregate, but not less

than volume of aggregate used in scratch coat.

C. Job-Mixed Finish-Coat Mixes:

1. Portland Cement Mix: For cementitious materials, mix 1 part portland cement and 3/4 to 1-1/2 parts lime. Use 1-1/2 to 3 parts aggregate per part of cementitious material.

2. Masonry Cement Mix: Use 1 part masonry cement and 1-1/2 to 3 parts aggregate. 3. Portland and Masonry Cement Mix: For cementitious materials, mix 1 part portland

cement and 1 part masonry cement. Use 1-1/2 to 3 parts aggregate per part of cementitious material.

D. Factory-Prepared Finish-Coat Mixes: For ready-mixed finish-coat plasters, comply with manufacturer's written instructions.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Protect adjacent work from soiling, spattering, moisture deterioration, and other harmful effects caused by plastering.

B. Prepare smooth, solid substrates for plaster according to ASTM C 926.

3.3 INSTALLATION, GENERAL

A. Fire-Resistance-Rated Assemblies: Install components according to requirements for design designations from listing organization and publication indicated on Drawings.

Page 5: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

CEMENT PLASTERING 092400 - 5

B. Sound-Attenuation Blankets: Where required, install blankets before installing lath unless blankets are readily installed after lath has been installed on one side.

3.4 INSTALLING METAL LATH

A. Metal Lath: Install according to ASTM C 1063.

1. Partition Framing and Vertical Furring: Install flat-diamond-mesh lath. 2. Flat-Ceiling and Horizontal Framing: Install flat-diamond-mesh lath.

3.5 INSTALLING ACCESSORIES

A. Install according to ASTM C 1063 and at locations indicated on Drawings.

B. Reinforcement for External (Outside) Corners:

1. Install lath-type, external-corner reinforcement at exterior locations. 2. Install cornerbead at interior locations.

C. Control Joints: Locate as approved by Architect for visual effect and as follows:

1. As required to delineate plasterwork into areas (panels) of the following maximum sizes:

a. Vertical Surfaces: 144 sq. ft. b. Horizontal and Other Nonvertical Surfaces: 100 sq. ft.

2. At distances between control joints of not greater than 18 feet o.c. 3. As required to delineate plasterwork into areas (panels) with length-to-width ratios of not

greater than 2-1/2:1. 4. Where control joints occur in surface of construction directly behind plaster. 5. Where plasterwork areas change dimensions, to delineate rectangular-shaped areas

(panels) and to relieve the stress that occurs at the corner formed by the dimension change.

3.6 PLASTER APPLICATION

A. General: Comply with ASTM C 926.

1. Do not deviate more than plus or minus 1/4 inch in 10 feet from a true plane in finished plaster surfaces when measured by a 10-foot straightedge placed on surface.

2. Finish plaster flush with metal frames and other built-in metal items or accessories that act as a plaster ground unless otherwise indicated. Where casing bead does not terminate plaster at metal frame, cut base coat free from metal frame before plaster sets and groove finish coat at junctures with metal.

3. Provide plaster surfaces that are ready to receive field-applied finishes indicated.

Page 6: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

CEMENT PLASTERING 092400 - 6

B. Walls; Base-Coat Mixes for Use over Metal Lath: For scratch and brown coats, for three-coat plasterwork with 3/4-inch total thickness, as follows:

1. Masonry cement mixes.

C. Ceilings; Base-Coat Mixes for Use over Metal Lath: For scratch and brown coats, for three-coat plasterwork and having 3/4-inch total thickness for metal lath on concrete, as follows:

1. Masonry cement mixes. 2. Portland and masonry cement mixes. 3. Plastic cement mixes. 4. Portland and plastic cement mixes.

D. Plaster Finish Coats: Apply to provide float finish to match Architect's sample.

E. Acrylic-Based Finish Coatings: Apply coating system, including primers, finish coats, and sealing topcoats, according to manufacturer's written instructions.

F. Concealed Interior Plasterwork:

1. Where plaster application is concealed behind built-in cabinets, similar furnishings, and equipment, apply finish coat.

2. Where plaster application is concealed above suspended ceilings and in similar locations, omit finish coat.

3. Where plaster application is used as a base for adhesive application of tile and similar finishes, omit finish coat.

3.7 PLASTER REPAIRS

A. Repair or replace work to eliminate cracks, dents, blisters, buckles, crazing and check cracking, dry outs, efflorescence, sweat outs, and similar defects and where bond to substrate has failed.

3.8 CLEANING AND PROTECTION

A. Remove temporary protection and enclosure of other work after plastering is complete. Promptly remove plaster from door frames, windows, and other surfaces not indicated to be plastered. Repair floors, walls, and other surfaces stained, marred, or otherwise damaged during plastering.

END OF SECTION 092400

Page 7: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 1

SECTION 093000 - TILING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1. Section 079200 "Joint Sealants" for sealing of expansion, contraction, control, and

isolation joints in tile surfaces. 2. Section 092400 "Cement Plastering" for scratch coat for thickset mortar setting-bed

installations.

1.2 SUMMARY

A. Section Includes:

1. Porcelain tile. 2. Crack isolation membrane. 3. Tile backing panels. 4. Metal edge strips.

1.3 DEFINITIONS

A. General: Definitions in the ANSI A108 series of tile installation standards and in ANSI A137.1 apply to Work of this Section unless otherwise specified.

B. ANSI A108 Series: ANSI A108.01, ANSI A108.02, ANSI A108.1A, ANSI A108.1B, ANSI A108.1C, ANSI A108.4, ANSI A108.5, ANSI A108.6, ANSI A108.8, ANSI A108.9, ANSI A108.10, ANSI A108.11, ANSI A108.12, ANSI A108.13, ANSI A108.14, ANSI A108.15, ANSI A108.16, and ANSI A108.17, which are contained in "American National Standard Specifications for Installation of Ceramic Tile."

C. Module Size: Actual tile size plus joint width indicated.

D. Face Size: Actual tile size, excluding spacer lugs.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product indicated.

Page 8: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 2

B. Shop Drawings: Show locations of each type of tile and tile pattern. Show widths, details, and locations of expansion, contraction, control, and isolation joints in tile substrates and finished tile surfaces.

C. Samples for Verification:

1. Full-size units of each type and composition of tile and for each color and finish required. 2. Full-size units of each type of trim and accessory for each color and finish required. 3. Metal edge strips in 6-inch (150-mm) lengths.

1.5 QUALITY ASSURANCE

A. Source Limitations for Tile: Obtain tile of each type and color or finish from one source or producer.

1. Obtain tile of each type and color or finish from same production run and of consistent quality in appearance and physical properties for each contiguous area.

B. Source Limitations for Setting and Grouting Materials: Obtain ingredients of a uniform quality for each mortar, adhesive, and grout component from one manufacturer and each aggregate from one source or producer.

C. Source Limitations for Other Products: Obtain each of the following products specified in this Section from a single manufacturer for each product:

1. Waterproof membrane. 2. Crack isolation membrane. 3. Joint sealants. 4. Cementitious backer units. 5. Metal edge strips.

D. Preinstallation Conference: Conduct conference at Project site.

1. Review requirements in ANSI A108.01 for substrates and for preparation by other trades.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver and store packaged materials in original containers with seals unbroken and labels intact until time of use. Comply with requirements in ANSI A137.1 for labeling tile packages.

B. Store tile and cementitious materials on elevated platforms, under cover, and in a dry location.

C. Store aggregates where grading and other required characteristics can be maintained and contamination can be avoided.

D. Store liquid materials in unopened containers and protected from freezing.

Page 9: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 3

E. Handle tile that has temporary protective coating on exposed surfaces to prevent coated surfaces from contacting backs or edges of other units. If coating does contact bonding surfaces of tile, remove coating from bonding surfaces before setting tile.

1.7 PROJECT CONDITIONS

A. Environmental Limitations: Do not install tile until construction in spaces is complete and ambient temperature and humidity conditions are maintained at the levels indicated in referenced standards and manufacturer's written instructions.

1.8 EXTRA MATERIALS

A. Furnish extra materials that match and are from same production runs as products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Tile and Trim Units: Furnish quantity of full-size units equal to 3 percent of amount installed for each type, composition, color, pattern, and size indicated.

2. Grout: Furnish quantity of grout equal to 3 percent of amount installed for each type, composition, and color indicated.

PART 2 - PRODUCTS

2.1 PORCELAIN PRODUCTS, GENERAL

A. ANSI Ceramic Tile Standard: Provide tile that complies with ANSI A137.1 for types, compositions, and other characteristics indicated.

1. Provide tile complying with Standard grade requirements unless otherwise indicated.

B. ANSI Standards for Tile Installation Materials: Provide materials complying with ANSI A108.02, ANSI standards referenced in other Part 2 articles, ANSI standards referenced by TCA installation methods specified in tile installation schedules, and other requirements specified.

C. Factory Blending: For tile exhibiting color variations within ranges, blend tile in factory and package so tile units taken from one package show same range in colors as those taken from other packages and match approved Samples.

D. Factory-Applied Temporary Protective Coating: Where indicated under tile type, protect exposed surfaces of tile against adherence of mortar and grout by precoating with continuous film of petroleum paraffin wax, applied hot. Do not coat unexposed tile surfaces.

Page 10: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 4

2.2 TILE PRODUCTS

A. Tile Type PT-1, PWT-1; unglazed porcelain tile. 1. Basis-of-Design Product: Subject to compliance with requirements, provide product

indicated on Drawings or comparable product by one of the following or equal product from another manufacturer:

a. Crossville, Inc. Basalt Porcelain Stone b. Or approved equal

2. Composition: Porcelain. 3. Module Size: As indicated on Drawings. 4. Thickness: 3/8” 5. Face: Plain. 6. Surface: Slip-resistant, with abrasive admixture. 7. Tile Color and Pattern: As selected by Architect and indicated on finish material

schedule. 8. Grout Color: As selected by Architect from manufacturer's full range. 9. Trim Units: Coordinated with sizes and coursing of adjoining flat tile where

applicable and matching characteristics of adjoining flat tile. Provide shapes as indicated on Drawings.

B. Tile Type CMT-1, CMT-2; concrete tile. 1. Basis-of-Design Product: Subject to compliance with requirements, provide product

indicated on Drawings or comparable product by one of the following or equal product from another manufacturer:

a. Betona Flexible Concrete Tile. b. Or approved equal

2. Composition: Porcelain. 3. Module Size: As indicated on Drawings. 4. Thickness: 3/8” 5. Face: Plain. 6. Surface: Smooth, without abrasive admixture. 7. Tile Color and Pattern: As selected by Architect and indicated on finish material

schedule. 8. Grout Color: As selected by Architect from manufacturer's full range. 9. Trim Units: Coordinated with sizes and coursing of adjoining flat tile where

applicable and matching characteristics of adjoining flat tile. Provide shapes as indicated on Drawings.

2.3 CRACK ISOLATION MEMBRANE

A. General: Manufacturer's standard product, selected from the following, that complies with ANSI A118.12 for standard performance and is recommended by the manufacturer for the application indicated. Include reinforcement and accessories recommended by manufacturer.

Page 11: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 5

B. Polyethylene Sheet: Polyethylene faced on both sides with fleece webbing; 0.008-inch nominal thickness.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include the following or equal product from another manufacturer.

a. Schluter Systems L.P.; KERDI.

2.4 SETTING MATERIALS

A. Latex-Portland Cement Mortar (Thin Set): ANSI A118.4.

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include the following or equal product from another manufacturer:

a. Boiardi Products; a QEP company. b. Bonsal American; an Oldcastle company. c. Bostik, Inc. d. C-Cure. e. Custom Building Products. f. Jamo Inc. g. Laticrete International, Inc. h. MAPEI Corporation. i. Mer-Kote Products, Inc. j. Southern Grouts & Mortars, Inc. k. Summitville Tiles, Inc. l. TEC; a subsidiary of H. B. Fuller Company.

2. For wall applications, provide mortar that complies with requirements for nonsagging mortar in addition to the other requirements in ANSI A118.4.

2.5 GROUT MATERIALS

A. Polymer-Modified Sanded Grout: ANSI A118.7.

1. Basis-of-Design Product: Subject to compliance with requirements, provide product indicated on Drawings or comparable product by one of the following or an equal product from another manufacturer:

a. Boiardi Products; a QEP company. b. Bonsal American; an Oldcastle company. c. Bostik, Inc. d. C-Cure. e. Custom Building Products. f. Jamo Inc. g. Laticrete International, Inc. h. MAPEI Corporation.

Page 12: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 6

i. Southern Grouts & Mortars, Inc. j. Summitville Tiles, Inc. k. TEC; a subsidiary of H. B. Fuller Company.

2.6 MISCELLANEOUS MATERIALS

A. Trowelable Underlayments and Patching Compounds: Latex-modified, portland cement-based formulation provided or approved by manufacturer of tile-setting materials for installations indicated.

B. Metal Edge Strips: Angle or L-shape, height to match tile and setting-bed thickness, metallic or combination of metal and PVC or neoprene base, designed specifically for flooring applications; stainless-steel, ASTM A 666, 300 Series exposed-edge material.

C. Temporary Protective Coating: Either product indicated below that is formulated to protect exposed surfaces of tile against adherence of mortar and grout; compatible with tile, mortar, and grout products; and easily removable after grouting is completed without damaging grout or tile.

1. Petroleum paraffin wax, fully refined and odorless, containing at least 0.5 percent oil with a melting point of 120 to 140 deg F (49 to 60 deg C) per ASTM D 87.

2. Grout release in form of manufacturer's standard proprietary liquid coating that is specially formulated and recommended for use as temporary protective coating for tile.

D. Tile Cleaner: A neutral cleaner capable of removing soil and residue without harming tile and grout surfaces, specifically approved for materials and installations indicated by tile and grout manufacturers.

E. Grout Sealer: Manufacturer's standard silicone product for sealing grout joints and that does not change color or appearance of grout.

1. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include the following or equal product by another manufacturer:

a. Bonsal American; an Oldcastle company; Grout Sealer. b. Bostik, Inc.; CeramaSeal c. C-Cure; Penetrating Sealer 978. d. Custom Building Products; Grout and Tile Sealer. e. Jamo Inc.; Penetrating Sealer. f. MAPEI Corporation; 004, Keraseal Penetrating Sealer for Unglazed Grout and

Tile. g. Southern Grouts & Mortars, Inc.; Silicone Grout Sealer. h. Summitville Tiles, Inc.; SL-15, Invisible Seal Penetrating Grout and Tile Sealer. i. TEC; a subsidiary of H. B. Fuller Company; TA-256 Penetrating Silicone Grout

Sealer.

Page 13: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 7

2.7 MIXING MORTARS AND GROUT

A. Mix mortars and grouts to comply with referenced standards and mortar and grout manufacturers' written instructions.

B. Add materials, water, and additives in accurate proportions.

C. Obtain and use type of mixing equipment, mixer speeds, mixing containers, mixing time, and other procedures to produce mortars and grouts of uniform quality with optimum performance characteristics for installations indicated.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions where tile will be installed, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of installed tile.

1. Verify that substrates for setting tile are firm, dry, clean, free of coatings that are incompatible with tile-setting materials including curing compounds and other substances that contain soap, wax, oil, or silicone; and comply with flatness tolerances required by ANSI A108.01 for installations indicated.

2. Verify that concrete substrates for tile floors installed with thin-set mortar comply with surface finish requirements in ANSI A108.01 for installations indicated.

a. Verify that surfaces that received a steel trowel finish have been mechanically scarified.

b. Verify that protrusions, bumps, and ridges have been removed by sanding or grinding.

3. Verify that installation of grounds, anchors, recessed frames, electrical and mechanical units of work, and similar items located in or behind tile has been completed.

4. Verify that joints and cracks in tile substrates are coordinated with tile joint locations; if not coordinated, adjust joint locations in consultation with Architect.

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Fill cracks, holes, and depressions in concrete substrates for tile floors installed with adhesives or thin-set mortar with trowelable leveling and patching compound specifically recommended by tile-setting material manufacturer.

B. Blending: For tile exhibiting color variations, verify that tile has been factory blended and packaged so tile units taken from one package show same range of colors as those taken from

Page 14: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 8

other packages and match approved Samples. If not factory blended, either return to manufacturer or blend tiles at Project site before installing.

C. Field-Applied Temporary Protective Coating: If indicated under tile type or needed to prevent grout from staining or adhering to exposed tile surfaces, precoat them with continuous film of temporary protective coating, taking care not to coat unexposed tile surfaces.

3.3 TILE INSTALLATION

A. Comply with TCA's "Handbook for Ceramic Tile Installation" for TCA installation methods specified in tile installation schedules. Comply with parts of the ANSI A108 Series "Specifications for Installation of Ceramic Tile" that are referenced in TCA installation methods, specified in tile installation schedules, and apply to types of setting and grouting materials used.

1. For the following installations, follow procedures in the ANSI A108 Series of tile installation standards for providing 95 percent mortar coverage:

a. Tile floors in wet areas. b. Tile floors composed of tiles 8 by 8 inches (200 by 200 mm) or larger.

B. Extend tile work into recesses and under or behind equipment and fixtures to form complete covering without interruptions unless otherwise indicated. Terminate work neatly at obstructions, edges, and corners without disrupting pattern or joint alignments.

C. Accurately form intersections and returns. Perform cutting and drilling of tile without marring visible surfaces. Carefully grind cut edges of tile abutting trim, finish, or built-in items for straight aligned joints. Fit tile closely to electrical outlets, piping, fixtures, and other penetrations so plates, collars, or covers overlap tile.

D. Provide manufacturer's standard trim shapes where necessary to eliminate exposed tile edges.

E. Jointing Pattern: Lay tile in grid pattern unless otherwise indicated. Lay out tile work and center tile fields in both directions in each space or on each wall area. Lay out tile work to minimize the use of pieces that are less than half of a tile. Provide uniform joint widths unless otherwise indicated.

1. For tile mounted in sheets, make joints between tile sheets same width as joints within tile sheets so joints between sheets are not apparent in finished work.

2. Where adjoining tiles on floor, base, walls, or trim are specified or indicated to be same size, align joints.

3. Where tiles are specified or indicated to be whole integer multiples of adjoining tiles on floor, base, walls, or trim, align joints unless otherwise indicated.

F. Joint Widths: Unless otherwise indicated, install tile with the following joint widths:

1. Porcelain Tile: 1/8 inch

Page 15: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 9

G. Lay out tile wainscots to dimensions indicated.

H. Expansion Joints: Provide expansion joints and other sealant-filled joints, including control, contraction, and isolation joints, where indicated. Form joints during installation of setting materials, mortar beds, and tile. Do not saw-cut joints after installing tiles.

1. Where joints occur in concrete substrates, locate joints in tile surfaces directly above them.

I. Metal Edge Strips: Install where exposed edge of tile flooring meets carpet, wood, or other flooring that finishes flush with top of tile, where exposed edge of tile flooring meets carpet, wood, or other flooring that finishes flush with or below top of tile and no threshold is indicated.

J. Grout Sealer: Apply grout sealer to cementitious grout joints in tile floors and tile walls according to grout-sealer manufacturer's written instructions. As soon as grout sealer has penetrated grout joints, remove excess sealer and sealer from tile faces by wiping with soft cloth.

3.4 CRACK ISOLATION MEMBRANE INSTALLATION

A. Install crack isolation membrane to comply with ANSI A108.17 and manufacturer's written instructions to produce membrane of uniform thickness and bonded securely to substrate.

B. Do not install tile or setting materials over crack isolation membrane until membrane has cured.

3.5 CLEANING AND PROTECTING

A. Cleaning: On completion of placement and grouting, clean all ceramic tile surfaces so they are free of foreign matter.

1. Remove latex-portland cement grout residue from tile as soon as possible. 2. Clean grout smears and haze from tile according to tile and grout manufacturer's written

instructions but no sooner than 10 days after installation. Use only cleaners recommended by tile and grout manufacturers and only after determining that cleaners are safe to use by testing on samples of tile and other surfaces to be cleaned. Protect metal surfaces and plumbing fixtures from effects of cleaning. Flush surfaces with clean water before and after cleaning.

3. Remove temporary protective coating by method recommended by coating manufacturer and that is acceptable to tile and grout manufacturer. Trap and remove coating to prevent drain clogging.

B. Protect installed tile work with kraft paper or other heavy covering during construction period to prevent staining, damage, and wear. If recommended by tile manufacturer, apply coat of neutral protective cleaner to completed tile walls and floors.

C. Prohibit foot and wheel traffic from tiled floors for at least seven days after grouting is completed.

Page 16: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014 \

TILING 093000 - 10

D. Before final inspection, remove protective coverings and rinse neutral protective cleaner from tile surfaces.

3.6 INTERIOR TILE INSTALLATION SCHEDULE

A. Interior Floor Installations, Concrete Subfloor:

1. Tile Installation F113: Thin-set mortar; TCA F113.

a. Tile Type: PT1, PT2, GR-1, QT-1 b. Thin-Set Mortar: Latex portland cement mortar. c. Grout: Polymer-modified sanded grout.

B. Interior Wall Installations, Concrete or Masonry:

1. Tile Installation W202, Thin-set mortar TCA W202

a. Tile Type: PT1, PT2, GR-1, QT-1 b. Thin-set mortar for cured-bed method: latex-portland cement mortar c. Grout: Polymer-modified sanded grout.

END OF SECTION 093000

Page 17: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 1

SECTION 095113 - ACOUSTICAL PANEL CEILINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes acoustical panels and exposed suspension systems for ceilings.

B. Products furnished, but not installed under this Section, include anchors, clips, and other ceiling attachment devices to be cast in concrete at ceilings.

1.3 DEFINITIONS

A. AC: Articulation Class.

B. CAC: Ceiling Attenuation Class.

C. LR: Light Reflectance coefficient.

D. NRC: Noise Reduction Coefficient.

1.4 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Samples for Verification: For each component indicated and for each exposed finish required, prepared on Samples of size indicated below.

1. Acoustical Panel: Set of 6-inch- (150-mm-) square. Samples of each type, color, pattern, and texture.

2. Exposed Suspension System Members, Moldings, and Trim: Set of 12-inch- (300-mm-) long Samples of each type, finish, and color.

3. Statement of Compliance with Seismic Design Category Requirements: Statement indicating system minimum compliance for category specified for all system components and list products and systems being provide that demonstrates compliance with requirements.

Page 18: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 2

1.5 QUALITY ASSURANCE

A. Acoustical Testing Agency Qualifications: An independent testing laboratory, or an NVLAP-accredited laboratory, with the experience and capability to conduct the testing indicated. NVLAP-accredited laboratories must document accreditation, based on a "Certificate of Accreditation" and a "Scope of Accreditation" listing the test methods specified.

B. Source Limitations: Obtain each type of acoustical ceiling panel and supporting suspension system through one source from a single manufacturer.

C. Fire-Test-Response Characteristics: Provide acoustical panel ceilings that comply with the following requirements:

1. Surface-Burning Characteristics: Provide acoustical panels with the following surface-burning characteristics complying with ASTM E 1264 for Class A materials as determined by testing identical products per ASTM E 84:

D. Seismic Standard: Provide acoustical panel ceilings designed and installed to withstand the effects of earthquake motions according to the following:

1. Standard for Ceiling Suspension Systems Requiring Seismic Restraint: Comply with ASTM E 580.

2. CISCA's Recommendations for Acoustical Ceilings: Comply with CISCA's "Recommendations for Direct-Hung Acoustical Tile and Lay-in Panel Ceilings--Seismic Zones 0-2."

3. CISCA's Guidelines for Systems Requiring Seismic Restraint: Comply with CISCA's "Guidelines for Seismic Restraint of Direct-Hung Suspended Ceiling Assemblies--Seismic Zones 3 & 4."

4. ASCE 7, "Minimum Design Loads for Buildings and Other Structures": Section 9, "Earthquake Loads."

E. Seismic Requirements: Provide complete suspended acoustical panel ceilings system designed and installed to withstand the effects of earthquake motions according to the standards above and the following requirements:

1. Meet Requirements of Seismic Design Category D.

a. Section 1613.1 of the International Building Code 2009 Edition requires compliance with ASCE 7. In the event of conflicts with requirements with standards referenced above and ASCE 7, comply with ASCE 7.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Deliver acoustical panels, suspension system components, and accessories to Project site in original, unopened packages and store them in a fully enclosed, conditioned space where they will be protected against damage from moisture, humidity, temperature extremes, direct sunlight, surface contamination, and other causes.

Page 19: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 3

B. Before installing acoustical panels, permit them to reach room temperature and a stabilized moisture content.

C. Handle acoustical panels carefully to avoid chipping edges or damaging units in any way.

1.7 PROJECT CONDITIONS

A. Environmental Limitations: Do not install acoustical panel ceilings until spaces are enclosed and weatherproof, wet work in spaces is complete and dry, work above ceilings is complete, and ambient temperature and humidity conditions are maintained at the levels indicated for Project when occupied for its intended use.

1. Pressurized Plenums: Operate ventilation system for not less than 48 hours before beginning acoustical panel ceiling installation.

1.8 COORDINATION

A. Coordinate layout and installation of acoustical panels and suspension system with other construction that penetrates ceilings or is supported by them, including light fixtures, HVAC equipment, fire-suppression system, and partition assemblies.

1.9 EXTRA MATERIALS

A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Acoustical Ceiling Panels: Full-size panels equal to 2.0 percent of quantity installed. 2. Suspension System Components: Quantity of each exposed component equal to 2.0

percent of quantity installed.

PART 2 - PRODUCTS

2.1 ACOUSTICAL PANELS, GENERAL

A. Acoustical Panel Standard: Provide manufacturer's standard panels of configuration indicated that comply with ASTM E 1264 classifications as designated by types, patterns, acoustical ratings, and light reflectances, unless otherwise indicated.

1. Mounting Method for Measuring NRC: Type E-400; plenum mounting in which face of test specimen is 15-3/4 inches (400 mm) away from test surface per ASTM E 795.

B. Acoustical Panel Colors and Patterns: Match appearance characteristics indicated for each product type.

C. Antimicrobial Fungicide Treatment: Provide acoustical panels with face and back surfaces coated with antimicrobial treatment consisting of manufacturer's standard formulation with

Page 20: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 4

fungicide added to inhibit growth of mold and mildew and showing no mold or mildew growth when tested according to ASTM D 3273 and evaluated according to ASTM D 3274 or ASTM G 21.

2.2 ACOUSTICAL PANELS FOR ACOUSTICAL PANEL CEILING (APC1):

A. Basis-of-Design Product: Subject to compliance with requirements, provide 15/16" Beveled Tegular, Armstrong Ultima 1911 or comparable product by one of the following or equal product from another manufacturer:

1. CertainTeed Corp. 2. USG Interiors, Subsidiary of USG Corporation

B. Color: White.

C. LR: Not less than 0.90

D. NRC: Not less than 0.70.

E. CAC: Not less than 35.

F. Edge/Joint Detail: Beveled Tegular

G. Thickness: 15/16 inch (19 mm).

H. Modular Size: 24 by 24 inches (610 by 610 mm).

I. Antimicrobial Treatment: Antimicrobial Fungicide Treatment BioBlock Plus.

J. Humidity Sag Resistance: HumiGuard Plus

K. VOC Formaldehyde: Low

L. Metal Suspension System Standard: Provide manufacturer's standard direct-hung metal suspension systems of types, structural classifications, and finishes indicated that comply with applicable requirements in ASTM C 635.

M. Finishes and Colors, General: Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes. Provide manufacturer's standard factory-applied finish for type of system indicated.

N. Attachment Devices: Size for five times the design load indicated in ASTM C 635, Table 1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements.

O. Attachment Devices: Size for five times the design load indicated in ASTM C 635, Table 1, "Direct Hung," unless otherwise indicated. Comply with seismic design requirements.

P. Wire Hangers, Braces, and Ties: Provide wires complying with the following requirements:

Page 21: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 5

1. Zinc-Coated, Carbon-Steel Wire: ASTM A 641/A 641M, Class 1 zinc coating, soft temper.

2. Size: Select wire diameter so its stress at 3 times hanger design load (ASTM C 635, Table 1, "Direct Hung") will be less than yield stress of wire, but provide not less than 0.135-inch- (3.5-mm-) diameter wire.

2.3 METAL SUSPENSION SYSTEM FOR ACOUSTICAL PANEL CEILING (APC1, APC2)

A. Basis-of-Design Product: Subject to compliance with requirements, provide Armstrong Prelude XL 15/16" or comparable product by one of the following or equal product from another manufacturer:

1. CertainTeed Corp. 2. USG Interiors, Subsidiary of USG Corporation

B. Wide-Face, Capped, Double-Web, Hot-Dip Galvanized, G60 (Z180), Steel Suspension System: Main and cross runners roll formed from cold-rolled steel sheet, hot-dip galvanized according to ASTM A 653/A 653M, G60 (Z180) coating designation, with prefinished, cold-rolled, 15/16-inch- (24-mm-) wide, aluminum caps on flanges.

1. Structural Classification: Heavy duty system. 2. Face Design: Flat, flush. 3. Face Finish: Painted white.

2.4 METAL EDGE MOLDINGS AND TRIM

A. Basis-of-Design Product: Subject to compliance with requirements, provide 2" wide 7823 Shadow Molding by Armstrong for seismic restraint.

B. Extruded-Aluminum Edge Moldings and Trim: Where indicated, provide manufacturer's extruded-aluminum edge moldings and trim of profile indicated or referenced by manufacturer's designations, including splice plates, corner pieces, and attachment and other clips, complying with seismic design requirements and the following:

1. Baked-Enamel Finish: AA-C12C42R1x (Chemical Finish: cleaned with inhibited chemicals; Chemical Finish: acid-chromate-fluoride-phosphate conversion coating; organic coating: as specified below). Apply baked enamel complying with paint manufacturer's written instructions for cleaning, conversion coating, and painting.

a. Organic Coating: Thermosetting, primer/topcoat system with a minimum dry film thickness of 0.8 to 1.2 mils (0.02 to 0.03 mm).

2.5 ACOUSTICAL SEALANT

A. Available Products: Subject to compliance with requirements, products that may be incorporated into the Work include the following or an equal product by another manufacturer:

Page 22: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 6

B. Products: Subject to compliance with requirements, provide one of the following:

1. Acoustical Sealant for Exposed and Concealed Joints:

a. Pecora Corporation; AC-20 FTR Acoustical and Insulation Sealant.

C. Acoustical Sealant for Exposed and Concealed Joints: Manufacturer's standard nonsag, paintable, nonstaining latex sealant, with a VOC content of 250 g/L or less when calculated according to 40 CFR 59, Subpart D (EPA Method 24), complying with ASTM C 834 and effective in reducing airborne sound transmission through perimeter joints and openings in building construction as demonstrated by testing representative assemblies according to ASTM E 90.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, including structural framing to which acoustical panel ceilings attach or abut, with Installer present, for compliance with requirements specified in this and other Sections that affect ceiling installation and anchorage and with requirements for installation tolerances and other conditions affecting performance of acoustical panel ceilings.

1. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Measure each ceiling area and establish layout of acoustical panels to balance border widths at opposite edges of each ceiling. Avoid using less-than-half-width panels at borders, and comply with layout shown on reflected ceiling plans.

3.3 INSTALLATION

A. General: Install acoustical panel ceilings to comply with ASTM C 636 and seismic design requirements indicated, per manufacturer's written instructions and CISCA's "Ceiling Systems Handbook."

B. Suspend ceiling hangers from building's structural members and as follows:

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structure or of ceiling suspension system.

2. Splay hangers only where required to miss obstructions; offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

3. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with location of hangers at spacings required to support standard

Page 23: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 7

suspension system members, install supplemental suspension members and hangers in form of trapezes or equivalent devices.

4. Secure wire hangers to ceiling suspension members and to supports above with a minimum of three tight turns. Connect hangers directly either to structures or to inserts, eye screws, or other devices that are secure and appropriate for substrate and that will not deteriorate or otherwise fail due to age, corrosion, or elevated temperatures.

5. Do not support ceilings directly from permanent metal forms or floor deck. Fasten hangers to cast-in-place hanger inserts, postinstalled mechanical or adhesive anchors, or power-actuated fasteners that extend through forms into concrete.

6. When steel framing does not permit installation of hanger wires at spacing required, install carrying channels or other supplemental support for attachment of hanger wires.

7. Do not attach hangers to steel deck tabs. 8. Do not attach hangers to roof deck. Attach hangers to structural members. 9. Space hangers not more than 48 inches (1200 mm) o.c. along each member supported

directly from hangers, unless otherwise indicated; provide hangers not more than 8 inches (200 mm) from ends of each member.

10. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced standards and publications.

C. Secure bracing wires to ceiling suspension members and to supports with a minimum of four tight turns. Suspend bracing from building's structural members as required for hangers, without attaching to permanent metal forms, steel deck, or steel deck tabs. Fasten bracing wires into concrete with cast-in-place or postinstalled anchors.

D. Install edge moldings and trim of type indicated at perimeter of acoustical ceiling area and where necessary to conceal edges of acoustical panels.

1. Apply acoustical sealant in a continuous ribbon concealed on back of vertical legs of moldings before they are installed.

2. Screw attach moldings to substrate at intervals not more than 16 inches (400 mm) o.c. and not more than 3 inches (75 mm) from ends, leveling with ceiling suspension system to a tolerance of 1/8 inch in 12 feet (3.2 mm in 3.6 m). Miter corners accurately and connect securely.

3. Do not use exposed fasteners, including pop rivets, on moldings and trim.

E. Install suspension system runners so they are square and securely interlocked with one another. Remove and replace dented, bent, or kinked members.

F. Install acoustical panels with undamaged edges and fit accurately into suspension system runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat, precise fit.

1. Arrange directionally patterned acoustical panels as follows:

a. As indicated on reflected ceiling plans.

2. For square-edged panels, install panels with edges fully hidden from view by flanges of suspension system runners and moldings.

3. For reveal-edged panels on suspension system runners, install panels with bottom of reveal in firm contact with top surface of runner flanges.

Page 24: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

ACOUSTICAL PANEL CEILINGS 095113 - 8

4. For reveal-edged panels on suspension system members with box-shaped flanges, install panels with reveal surfaces in firm contact with suspension system surfaces and panel faces flush with bottom face of runners.

5. Paint cut edges of panel remaining exposed after installation; match color of exposed panel surfaces using coating recommended in writing for this purpose by acoustical panel manufacturer.

6. Protect lighting fixtures and air ducts to comply with requirements indicated for fire-resistance-rated assembly.

3.4 FIELD QUALITY CONTROL

A. Special Inspections: Owner will engage a qualified special inspector to perform the following special inspections:

1. Compliance of seismic design.

a. Suspended Ceiling Grid Clips: Periodic, three times each week. b. Suspended Ceiling wire spacing, (Seismic); Periodic, three times each week.

3.5 CLEANING

A. Clean exposed surfaces of acoustical panel ceilings, including trim, edge moldings, and suspension system members. Comply with manufacturer's written instructions for cleaning and touchup of minor finish damage. Remove and replace ceiling components that cannot be successfully cleaned and repaired to permanently eliminate evidence of damage.

END OF SECTION 095113

Page 25: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

EXTERIOR PAINTING 099113 - 1

SECTION 099113 - EXTERIOR PAINTING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes surface preparation and the application of paint systems on the following exterior substrates:

1. Steel. 2. Galvanized metal.

B. Related Sections include the following:

1. Division 05 Sections for shop priming of metal substrates with primers specified in this Section.

2. Division 09 Section "Interior Painting" for surface preparation and the application of paint systems on interior substrates.

3. Division 09 Section "High-Performance Coatings" for surface preparation and the application of paint systems on interior and exterior substrates.

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Samples for Verification: For each type of paint system and each color and gloss of topcoat indicated.

1. Submit Samples on rigid backing, 8 inches (200 mm) square. 2. Step coats on Samples to show each coat required for system.

1.4 QUALITY ASSURANCE

A. MPI Standards:

1. Products: Complying with MPI standards indicated and listed in "MPI Approved Products List."

2. Preparation and Workmanship: Comply with requirements in "MPI Architectural Painting Specification Manual" for products and paint systems indicated.

Page 26: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

EXTERIOR PAINTING 099113 - 2

B. Mockups: Apply benchmark samples of each paint system indicated and each color and finish selected to verify preliminary selections made under sample submittals and to demonstrate aesthetic effects and set quality standards for materials and execution.

1. Final approval of color selections will be based on benchmark samples.

a. If preliminary color selections are not approved, apply additional benchmark samples of additional colors selected by Architect at no added cost to Owner.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Store materials not in use in tightly covered containers in well-ventilated areas with ambient temperatures continuously maintained at not less than 45 deg F (7 deg C).

1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily.

1.6 PROJECT CONDITIONS

A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 50 and 95 deg F (10 and 35 deg C).

B. Do not apply paints in snow, rain, fog, or mist; when relative humidity exceeds 85 percent; at temperatures less than 5 deg F (3 deg C) above the dew point; or to damp or wet surfaces.

1.7 EXTRA MATERIALS

A. Furnish extra materials described below that are from same production run (batch mix) as materials applied and that are packaged for storage and identified with labels describing contents.

1. Quantity: Furnish an additional 5 percent, but not less than 1 gal. (3.8 L) of each material and color applied.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

B. Manufacturers: Subject to compliance with requirements, provide products by one of the following or an equal product from another manufacturer:

1. Benjamin Moore & Co. 2. Duron, Inc.

Page 27: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

EXTERIOR PAINTING 099113 - 3

3. ICI Paints. 4. Miller Paint. 5. Porter Paints. 6. PPG Architectural Finishes, Inc. 7. Rose Talbert 8. Sherwin-Williams Company (The).

2.2 PAINT, GENERAL

A. Material Compatibility:

1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience.

2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated.

B. Colors: Match exterior prefinished material as identified on Exterior Finish Notes on A4.1 and as approved by architect.

2.3 PRIMERS/SEALERS

A. Bonding Primer (Water Based): MPI #17.

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

2.4 METAL PRIMERS

A. Cementitious Galvanized-Metal Primer (For Galvanized Metal): MPI #26.

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

B. Epoxy Zinc Primer (For Steel Substrates) MPI#20.

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

2.5 EXTERIOR LATEX PAINTS

A. Exterior Latex (Gloss): MPI #119 (Gloss Level 6, except minimum gloss of 65 units at 60 deg).

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

Page 28: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

EXTERIOR PAINTING 099113 - 4

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of work.

B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows:

C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers.

D. Begin coating application only after unsatisfactory conditions have been corrected and surfaces are dry.

1. Beginning coating application constitutes Contractor's acceptance of substrates and conditions.

3.2 PREPARATION

A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual" applicable to substrates and paint systems indicated.

B. Remove plates, machined surfaces, and similar items already in place that are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting.

1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection if any.

2. Do not paint over labels of independent testing agencies or equipment name, identification, performance rating, or nomenclature plates.

C. Clean substrates of substances that could impair bond of paints, including dirt, oil, grease, and incompatible paints and encapsulants.

1. Remove incompatible primers and reprime substrate with compatible primers as required to produce paint systems indicated.

D. Concrete Masonry Substrates: Remove efflorescence and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces to be painted exceeds that permitted in manufacturer's written instructions.

E. Steel Substrates: Remove rust and loose mill scale. Clean using methods recommended in writing by paint manufacturer.

Page 29: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

EXTERIOR PAINTING 099113 - 5

F. Galvanized-Metal Substrates: Remove grease and oil residue from galvanized sheet metal fabricated from coil stock by mechanical methods to produce clean, lightly etched surfaces that promote adhesion of subsequently applied paints.

3.3 APPLICATION

A. Apply paints according to manufacturer's written instructions.

1. Use applicators and techniques suited for paint and substrate indicated. 2. Paint surfaces behind movable items same as similar exposed surfaces. Before final

installation, paint surfaces behind permanently fixed items with prime coat only.

B. Tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Tint undercoats to match color of topcoat, but provide sufficient difference in shade of undercoats to distinguish each separate coat.

C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance.

D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.

3.4 FIELD QUALITY CONTROL

A. Testing of Paint Materials: Owner reserves the right to invoke the following procedure at any time and as often as Owner deems necessary during the period when paints are being applied:

1. Owner will engage the services of a qualified testing agency to sample paint materials being used. Samples of material delivered to Project site will be taken, identified, sealed, and certified in presence of Contractor.

2. Testing agency will perform tests for compliance of paint materials with product requirements.

3. Owner may direct Contractor to stop applying paints if test results show materials being used do not comply with product requirements. Contractor shall remove noncomplying-paint materials from Project site, pay for testing, and repaint surfaces painted with rejected materials. Contractor will be required to remove rejected materials from previously painted surfaces if, on repainting with complying materials, the two paints are incompatible.

3.5 CLEANING AND PROTECTION

A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site.

B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces.

Page 30: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

EXTERIOR PAINTING 099113 - 6

C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition.

D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces.

3.6 EXTERIOR PAINTING SCHEDULE

A. Steel Substrates:

1. Polyurethane, Pigmented, Over High Build Epoxy Coating System MPI EXT 5.1G.

a. Prime Coat: Epoxy Zinc Primer MPI #20 b. Intermediate Coat: High-Build Epoxy marine coating, low gloss MPI #108 c. First Topcoat: Polyurethane, two-component, pigmented, gloss, MPI #72 d. Second Topcoat: Polyurethane, two-component, pigmented, gloss, MPI #72

B. Galvanized-Metal Substrates:

1. Latex System: MPI EXT 5.3A.

a. Prime Coat: Cementitious galvanized-metal primer. b. Intermediate Coat: Exterior latex matching topcoat. c. Topcoat: Exterior latex gloss

END OF SECTION 099113

Page 31: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 1

SECTION 099123 - INTERIOR PAINTING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. This Section includes surface preparation and the application of paint systems on the following interior substrates:

1. Steel. 2. Concrete Masonry Units (CMU) 3. Plaster

1.3 SUBMITTALS

A. Product Data: For each type of product indicated.

B. Samples for Verification: For each type of paint system and in each color and gloss of topcoat indicated.

1. Submit Samples on rigid backing, 8 inches (200 mm) square. 2. Step coats on Samples to show each coat required for system.

1.4 QUALITY ASSURANCE

A. MPI Standards:

1. Products: Complying with MPI standards indicated and listed in "MPI Approved Products List."

2. Preparation and Workmanship: Comply with requirements in "MPI Architectural Painting Specification Manual" for products and paint systems indicated.

1.5 DELIVERY, STORAGE, AND HANDLING

A. Store materials not in use in tightly covered containers in well-ventilated areas with ambient temperatures continuously maintained at not less than 45 deg F (7 deg C).

1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily.

Page 32: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 2

1.6 PROJECT CONDITIONS

A. Apply paints only when temperature of surfaces to be painted and ambient air temperatures are between 50 and 95 deg F (10 and 35 deg C).

B. Do not apply paints when relative humidity exceeds 85 percent; at temperatures less than 5 deg F (3 deg C) above the dew point; or to damp or wet surfaces.

1.7 EXTRA MATERIALS

A. Furnish extra materials described below that are from same production run (batch mix) as materials applied and that are packaged for storage and identified with labels describing contents.

1. Quantity: Furnish an additional 5 percent, but not less than 1 gal. (3.8 L) of each material and color applied.

PART 2 - PRODUCTS

2.1 MANUFACTURERS

A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include the following or an equal product by another manufacturer:

1. Benjamin Moore & Co. 2. Duron, Inc. 3. ICI Paints. 4. Miller Paint. 5. Porter Paints. 6. PPG Architectural Finishes, Inc. 7. Rose Tablert 8. Sherwin-Williams Company (The).

2.2 PAINT, GENERAL

A. Material Compatibility:

1. Provide materials for use within each paint system that are compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience.

2. For each coat in a paint system, provide products recommended in writing by manufacturers of topcoat for use in paint system and on substrate indicated.

B. Chemical Components of Field-Applied Interior Paints and Coatings: Provide topcoat paints and anti-corrosive and anti-rust paints applied to ferrous metals that comply with the following

Page 33: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 3

chemical restrictions; these requirements do not apply to paints and coatings that are applied in a fabrication or finishing shop:

1. Aromatic Compounds: Paints and coatings shall not contain more than 1.0 percent by weight of total aromatic compounds (hydrocarbon compounds containing one or more benzene rings).

2. Restricted Components: Paints and coatings shall not contain any of the following:

a. Acrolein. b. Acrylonitrile. c. Antimony. d. Benzene. e. Butyl benzyl phthalate. f. Cadmium. g. Di (2-ethylhexyl) phthalate. h. Di-n-butyl phthalate. i. Di-n-octyl phthalate. j. 1,2-dichlorobenzene. k. Diethyl phthalate. l. Dimethyl phthalate. m. Ethylbenzene. n. Formaldehyde. o. Hexavalent chromium. p. Isophorone. q. Lead. r. Mercury. s. Methyl ethyl ketone. t. Methyl isobutyl ketone. u. Methylene chloride. v. Naphthalene. w. Toluene (methylbenzene). x. 1,1,1-trichloroethane. y. Vinyl chloride.

C. Colors: As indicated on Drawings and Finish Materials Legend.

2.3 BLOCK FILLERS

A. Interior/Exterior Latex Block Filler: MPI #4.

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

2.4 PRIMERS/SEALERS

A. Interior Latex Primer/Sealer: MPI #50.

Page 34: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 4

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

2. Environmental Performance Rating: EPR 3.

2.5 METAL PRIMERS

A. Waterbourne Galvanized Metal Primer (Galvanized Metal Substrates) MPI #134

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

B. Rust-Inhibitive Primer (Water Based): MPI #107.

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

2. Environmental Performance Rating: EPR 3.

2.6 LATEX PAINTS

A. Institutional Low-odor/VOC Interior Latex (Semi Gloss Level 3) MPI #145

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

B. Modified Water Based Epoxy, MPI #115 (Gloss Level 6)

1. VOC Content: Refer to LEED Reference Guide for allowable VOC limits by product type and ensure compliance.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of work.

B. Maximum Moisture Content of Substrates: When measured with an electronic moisture meter as follows: 1. Gypsum Board: 12 percent. 2. Masonry (CMU): 12 percent. 3. Wood: 15 percent 4. Plaster: 12 percent

C. Verify suitability of substrates, including surface conditions and compatibility with existing finishes and primers.

Page 35: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 5

D. Begin coating application only after unsatisfactory conditions have been corrected and surfaces are dry.

1. Beginning coating application constitutes Contractor's acceptance of substrates and conditions.

3.2 PREPARATION

A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual" applicable to substrates indicated.

B. Remove plates, machined surfaces, and similar items already in place that are not to be painted. If removal is impractical or impossible because of size or weight of item, provide surface-applied protection before surface preparation and painting.

1. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection if any.

2. Do not paint over labels of independent testing agencies or equipment name, identification, performance rating, or nomenclature plates.

C. Clean substrates of substances that could impair bond of paints, including dirt, oil, grease, and incompatible paints and encapsulants.

1. Remove incompatible primers and reprime substrate with compatible primers as required to produce paint systems indicated.

D. Steel Substrates: Remove rust and loose mill scale. Clean using methods recommended in writing by paint manufacturer.

E. Wood Substrates:

1. Scrape and clean knots, and apply coat of knot sealer before applying primer. 2. Sand surfaces that will be exposed to view, and dust off. 3. Prime edges, ends, faces, undersides, and backsides of wood. 4. After priming, fill holes and imperfections in the finish surfaces with putty or plastic

wood filler. Sand smooth when dried.

F. Concrete Masonry Substrates: Remove efflorescence and chalk. Do not paint surfaces if moisture content or alkalinity of surfaces to be painted exceeds that permitted in manufacturer's written instructions.

G. Gypsum Board Substrates: Do not begin paint application until finishing compound is dry and sanded smooth.

H. Cotton or Canvas Insulation Covering Substrates: Remove dust, dirt, and other foreign material that might impair bond of paints to substrates.

Page 36: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 6

3.3 APPLICATION

A. Apply paints according to manufacturer's written instructions.

1. Use applicators and techniques suited for paint and substrate indicated. 2. Paint surfaces behind movable equipment and furniture same as similar exposed surfaces.

Before final installation, paint surfaces behind permanently fixed equipment or furniture with prime coat only.

3. Paint front and backsides of access panels, removable or hinged covers, and similar hinged items to match exposed surfaces.

B. Tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of same material are to be applied. Tint undercoats to match color of topcoat, but provide sufficient difference in shade of undercoats to distinguish each separate coat.

C. If undercoats or other conditions show through topcoat, apply additional coats until cured film has a uniform paint finish, color, and appearance.

D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks, roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color breaks.

3.4 CLEANING AND PROTECTION

A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site.

B. After completing paint application, clean spattered surfaces. Remove spattered paints by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces.

C. Protect work of other trades against damage from paint application. Correct damage to work of other trades by cleaning, repairing, replacing, and refinishing, as approved by Architect, and leave in an undamaged condition.

D. At completion of construction activities of other trades, touch up and restore damaged or defaced painted surfaces.

3.5 INTERIOR PAINTING SCHEDULE

A. Steel Substrates:

1. Institutional Low-Odor/VOC Latex System MPI INT 5.1S

a. Prime Coat: Rust-inhibitive primer (water based). b. Intermediate Coat: Institutional low-odor/VOC interior latex matching topcoat c. Topcoat: Institutional low-odor/VOC interior latex (semi-gloss)

Page 37: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP NoConstruction Documents September 19, 2014

INTERIOR PAINTING 099123 - 7

B. Galvanized Metal Substrates:

1. Institutional Low-Odor/VOC Latex System: MPI INT 5.3N

a. Prime Coat: Waterborne galvanized metal primer. b. Inermediate coat: institutional low-odor/VOC interior latex matching topcoat c. Topcoat: institutional low-odor/VOC interior latex (Semigloss)

C. CMU Substrates:

1. Institutional Low-Odor/VOC Latex System: MPI INT 4.2E

a. Prime Coat: Interior/exterior latex block filler. b. Intermediate Coat: Institutional low-odor/VOC interior latex matching topcoat c. Topcoat: Institutional low-odor/VOC interior latex (semigloss)

D. Gypsum Board/Plaster Substrates:

1. Institutional Low-Odor/VOC Latex System: MPI Int 9.2M

a. Prime Coat: Interior latex primer/sealer. b. Intermediate Coat: Institutional low-odor/VOC interior latex matching topcoat c. Topcoat: Institutional low-odor/VOC interior latex (semigloss)

END OF SECTION 099123

Page 38: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

HIGH-PERFORMANCE COATINGS 099600 - 1

SECTION 099600 - HIGH-PERFORMANCE COATINGS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes surface preparation and the application of high-performance coating systems on the following substrates:

1. Exterior Substrates: a. Steel.

2. Interior Substrates: a. Steel.

B. Related Requirements:

1. Section 099113 "Exterior Painting" for general field painting. 2. Section 099123 "Interior Painting" for general field painting.

1.3 ACTION SUBMITTALS

A. Product Data: For each type of product. Include preparation requirements and application instructions.

1. Include printout of current "MPI Approved Products List" for each product category specified, with the proposed product highlighted.

2. Indicate VOC content.

B. Samples for Initial Selection: For each type of topcoat product indicated.

C. Samples for Verification: For each type of coating system and each color and gloss of topcoat indicated.

1. Submit Samples on rigid backing, 8 inches square. 2. Apply coats on Samples in steps to show each coat required for system. 3. Label each coat of each Sample. 4. Label each Sample for location and application area.

Page 39: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

HIGH-PERFORMANCE COATINGS 099600 - 2

D. Product List: Cross-reference to coating system and locations of application areas. Use same designations indicated on Drawings and in schedules. Include color designations.

1.4 MAINTENANCE MATERIAL SUBMITTALS

A. Furnish extra materials, from the same product run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.

1. Coatings: 5 percent, but not less than 1 gal. of each material and color applied.

1.5 QUALITY ASSURANCE

A. Mockups: Apply mockups of each coating system indicated to verify preliminary selections made under Sample submittals and to demonstrate aesthetic effects and set quality standards for materials and execution.

1. Architect will select one surface to represent surfaces and conditions for application of each coating system.

a. Architect will designate items or areas required.

2. Subject to compliance with requirements, approved mockups may become part of the

completed Work if undisturbed at time of Substantial Completion.

1.6 DELIVERY, STORAGE, AND HANDLING

A. Store materials not in use in tightly covered containers in well-ventilated areas with ambient temperatures continuously maintained at not less than 45 deg F

1. Maintain containers in clean condition, free of foreign materials and residue. 2. Remove rags and waste from storage areas daily.

1.7 FIELD CONDITIONS

A. Apply coatings only when temperature of surfaces to be coated and ambient air temperatures are between 50 and 95 deg F.

B. Do not apply coatings when relative humidity exceeds 85 percent; at temperatures less than 5 deg F above the dew point; or to damp or wet surfaces.

C. Do not apply exterior coatings in snow, rain, fog, or mist.

Page 40: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

HIGH-PERFORMANCE COATINGS 099600 - 3

PART 2 - PRODUCTS

2.1 MANUFACTURERS

1. Sherwin-Williams Company (The). 2. PPG Architectural Finishes, Inc. 3. Benjamin Moore & Co.

B. Products: Subject to compliance with requirements, provide one of the products listed in the Exterior High-Performance Coating Schedule or Interior High-Performance Coating Schedule for the coating category indicated.

2.2 HIGH-PERFORMANCE COATINGS, GENERAL

A. MPI Standards: Products shall comply with MPI standards indicated and shall be listed in its "MPI Approved Products Lists."

B. Material Compatibility:

1. Materials for use within each paint system shall be compatible with one another and substrates indicated, under conditions of service and application as demonstrated by manufacturer, based on testing and field experience.

2. For each coat in a paint system, products shall be recommended in writing by topcoat manufacturers for use in paint system and on substrate indicated.

3. Products shall be of same manufacturer for each coat in a coating system.

2.3 SOURCE QUALITY CONTROL

A. Testing of Coating Materials: Owner reserves the right to invoke the following procedure:

1. Owner will engage the services of a qualified testing agency to sample coating materials. Contractor will be notified in advance and may be present when samples are taken. If coating materials have already been delivered to Project site, samples may be taken at Project site. Samples will be identified, sealed, and certified by testing agency.

2. Testing agency will perform tests for compliance with product requirements. 3. Owner may direct Contractor to stop applying coatings if test results show materials

being used do not comply with product requirements. Contractor shall remove noncomplying coating materials from Project site, pay for testing, and recoat surfaces coated with rejected materials. Contractor will be required to remove rejected materials from previously coated surfaces if, on recoating with complying materials, the two coatings are incompatible.

Page 41: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

HIGH-PERFORMANCE COATINGS 099600 - 4

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates and conditions, with Applicator present, for compliance with requirements for maximum moisture content and other conditions affecting performance of the Work.

B. Proceed with coating application only after unsatisfactory conditions have been corrected.

1. Application of coating indicates acceptance of surfaces and conditions.

3.2 PREPARATION

A. Comply with manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual" applicable to substrates and coating systems indicated.

B. After completing painting operations, use workers skilled in the trades involved to reinstall items that were removed. Remove surface-applied protection if any.

C. Clean substrates of substances that could impair bond of coatings, including dust, dirt, oil, grease, and incompatible paints and encapsulants.

1. Remove incompatible primers and reprime substrate with compatible primers or apply tie coat as required to produce coating systems indicated.

D. Steel Substrates: Remove rust, loose mill scale, and shop primer if any. Clean using methods recommended in writing by paint manufacturer.

1. SSPC-SP 7/NACE No. 4. 2. SSPC-SP 11. 3. SSPC-SP 6/NACE No. 3. 4. SSPC-SP 10/NACE No. 2. 5. SSPC-SP 5/NACE No. 1.

3.3 APPLICATION

A. Apply high-performance coatings according to manufacturer's written instructions and recommendations in "MPI Architectural Painting Specification Manual."

1. Use applicators and techniques suited for coating and substrate indicated. 2. Coat surfaces behind movable equipment and furniture same as similar exposed surfaces.

Before final installation, coat surfaces behind permanently fixed equipment or furniture with prime coat only.

3. Coat backsides of access panels, removable or hinged covers, and similar hinged items to match exposed surfaces.

4. Do not apply coatings over labels of independent testing agencies or equipment name, identification, performance rating, or nomenclature plates.

Page 42: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

HIGH-PERFORMANCE COATINGS 099600 - 5

B. Tint each undercoat a lighter shade to facilitate identification of each coat if multiple coats of the same material are to be applied. Tint undercoats to match color of finish coat, but provide sufficient difference in shade of undercoats to distinguish each separate coat.

C. If undercoats or other conditions show through final coat, apply additional coats until cured film has a uniform coating finish, color, and appearance.

D. Apply coatings to produce surface films without cloudiness, spotting, holidays, laps, brush marks, runs, sags, ropiness, or other surface imperfections. Produce sharp glass lines and color breaks.

3.4 FIELD QUALITY CONTROL

A. Dry Film Thickness Testing: Owner may engage the services of a qualified testing and inspecting agency to inspect and test coatings for dry film thickness.

1. Contractor shall touch up and restore coated surfaces damaged by testing. 2. If test results show that dry film thickness of applied coating does not comply with

coating manufacturer's written recommendations, Contractor shall pay for testing and apply additional coats as needed to provide dry film thickness that complies with coating manufacturer's written recommendations.

3.5 CLEANING AND PROTECTION

A. At end of each workday, remove rubbish, empty cans, rags, and other discarded materials from Project site.

B. After completing coating application, clean spattered surfaces. Remove spattered coatings by washing, scraping, or other methods. Do not scratch or damage adjacent finished surfaces.

C. Protect work of other trades against damage from coating operation. Correct damage to work of other trades by cleaning, repairing, replacing, and recoating, as approved by Architect, and leave in an undamaged condition.

D. At completion of construction activities of other trades, touch up and restore damaged or defaced coated surfaces.

3.6 EXTERIOR HIGH-PERFORMANCE COATING SCHEDULE

A. Steel Substrates:

1. Epoxy System:

a. Prime Coat: Primer, epoxy, anti-corrosive, for metal.

b. Intermediate Coat: Epoxy, high build, low gloss.

c. Topcoat: Epoxy, gloss.

Page 43: Coastal Carolina University C-744-13-2 SECTION 092400 ... · Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents

Coastal Carolina University C-744-13-2 Williams-Brice Building Renovations State PIP No. H17-9599-FW Construction Documents September 19, 2014

HIGH-PERFORMANCE COATINGS 099600 - 6

3.7 INTERIOR HIGH-PERFORMANCE COATING SCHEDULE

A. Steel Substrates:

1. High-Build Epoxy over Epoxy Zinc-Rich Primer System (galvanizing):

a. Prime Coat: Primer, zinc-rich, epoxy.

b. Intermediate Coat: Epoxy, high build, low gloss.

c. Topcoat: Epoxy, gloss.

d. Topcoat: Epoxy, high-build, low gloss.

END OF SECTION 099600