2.manual etr300s v1.0 eng
DESCRIPTION
recloserTRANSCRIPT
Load Break Switch Control ETR300S
User’s Manual
ENTECELECTRIC & ELECTRONIC CO., LTD
ENTEC
Copyright © 2009 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
Release Date: Nov. 2009 / Manual Revision: 1.00
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 3 ENHANCED TECHNOLOGY
CONTENT
1. Product Introduction ..................................................................................................... 6
1.1. Introduction ......................................................................................................................... 6
1.2. Characteristic summary ....................................................................................................... 7
2. Technical Specification ................................................................................................. 10
2.1. Input and Output ................................................................................................................ 10
2.2. Environment Test ............................................................................................................... 12
2.3. Metering Accuracy ............................................................................................................ 13
2.4. Monitoring ......................................................................................................................... 14
2.5. Event Recorder .................................................................................................................. 18
2.6. Maintenance ...................................................................................................................... 21
2.7. Communication ................................................................................................................. 21
3. Dimension and structure ................................................................................................. 22
4. External Input/Output Connector ................................................................................... 23
4.1. Current Input(Connector type:STLZ960-10) .................................................................... 24
4.2. Voltage Input(Connector type:STLZ960-6P,8P) ............................................................... 24
4.3. Digital Output(DO) ........................................................................................................... 25
4.4. Digital Input(DI) ................................................................................................................ 25
4.5. Power supply input& Modem power supply output .......................................................... 26
4.6. Remote Communication Port(modem connection) ........................................................... 26
4.7. 485 Communication Port ................................................................................................... 27
4.8. Ethernet Port(RJ45) ........................................................................................................... 27
5. User Interface Panel .................................................................................................... 28
5.1. Construction ...................................................................................................................... 29
5.2. Operation Manual (LCD instruction) ................................................................................ 36
5.3. LCD Menu Use.................................................................................................................. 43
6. Global Setting ............................................................................................................... 47
6.1. System ............................................................................................................................... 47
6.2. Communication ................................................................................................................. 54
6.3. Event Recorder .................................................................................................................. 69
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
4 ENHANCED TECHNOLOGY
6.4. Monitoring ......................................................................................................................... 70
6.5. PLC .................................................................................................................................... 81
6.6. Other setting items ............................................................................................................. 86
7. Group Setting ................................................................................................................ 89
7.1. Fault pickup element ......................................................................................................... 90
7.2. Inrush Current Restraint Function ..................................................................................... 95
7.3. Directional Detection Function ......................................................................................... 98
7.4. SECTION ........................................................................................................................ 102
7.5. Phase angle synch detect ................................................................................................. 106
7.6. Line cut / Phase lost detect .............................................................................................. 106
7.7. Overcurrent detect element.............................................................................................. 107
8. EVENT ........................................................................................................................ 109
8.1. Operation Event ............................................................................................................... 109
8.2. Fault Event ...................................................................................................................... 110
8.3. Fault Cycle - Summary .................................................................................................... 112
8.4. System Events ................................................................................................................. 113
8.5. Set Change Event ............................................................................................................ 114
8.6. Aver. Load/Min ................................................................................................................ 115
8.7. Peak. Load/Hour .............................................................................................................. 115
8.8. Peak. Load/Day ............................................................................................................... 116
8.9. Diagnostic Event ............................................................................................................. 117
8.10. PQM .............................................................................................................................. 120
8.11. Clear Saved Data ........................................................................................................... 121
9. Maintenance ................................................................................................................ 122
9.1. Count ............................................................................................................................... 122
9.2. Interrupt Time .................................................................................................................. 129
9.3. Contact Wear ................................................................................................................... 130
9.4. Data Reset........................................................................................................................ 130
9.5. CCU Information ............................................................................................................. 131
10. Time ........................................................................................................................... 132
11. Status .......................................................................................................................... 133
11.1. Switch ............................................................................................................................ 133
11.2. Input Ports ..................................................................................................................... 135
11.3. Output Ports ................................................................................................................... 135
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 5 ENHANCED TECHNOLOGY
12. Metering .................................................................................................................... 136
12.1. Current ........................................................................................................................... 136
12.2. Voltage ........................................................................................................................... 137
12.3. Frequency ...................................................................................................................... 138
12.4. Power ............................................................................................................................. 138
12.5. Energy ............................................................................................................................ 139
12.6. Demand Current ............................................................................................................ 139
12.7. Unbalance ...................................................................................................................... 140
12.8. Harmonics ..................................................................................................................... 140
12.9. True R.M.S .................................................................................................................... 141
12.10. TD Monitoring ............................................................................................................. 141
12.11. CCU Reference ............................................................................................................ 141
13. PLC function ............................................................................................................ 142
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
6 ENHANCED TECHNOLOGY
1. Product Introduction
1.1. Introduction
ETR300-S01 is embedded in Distribution Automation 25.8kV SF6 gas insulated load break
switch(Pole mount) control box. It receives measurement information(3 phases current &
voltages) and status information from Switch, and meters current and voltage, detecs FI, Line cut,
Live line/Dead line, Unbalance, and send those information to SCADA(Master station).
As well as, controlling a swich by receiving Control Signal from SCADA, provides Distribution
Automation and minimize a fault area.
ETR300-S01 monitors not only electric quality of dirstirbution line but also, provides Section
operation in case of fault occurring and minimize its fault area.
All events occurring in the distribution line, are saved and provides fault analysis. With using
DNP3.0 Protocol, provides monitored status to SCADA for switch operation. Not only DNP3.0
Protocol, other communication protocols can beprovided by user‟s request.
Switch operation is available by operation buttion on front panel. Fault detect Enable/Diable,
Fault detect Enable/Disable, SECTION function Enable/Disable, operation selection
Local/Remote, Operation lock Lock/Unlock, ALTERNATE SETTING Enable/Disable, SEF
function Enable/Disable, SEC/TIE LOCKOUT Enable/Disable can be set.
INTERFACE SOFTWARE is very much convenient to have the maintenance of Set change and
Operation records in PC. It also has Zoom In/Out feature to analize Fault wave and Digital
operation signal with real time so that it provides much more uniq functions for the users.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 7 ENHANCED TECHNOLOGY
1.2. Characteristic summary
MONITORING
Phase fault detect(Permenant , Instantaneous)
Earth fault detect(Permenant, Instantaneous)
SEF fault detect(Permenant, Instantaneous)
Inrush current restraint (Phase/Earth/SEF)
Directional (Phase/Earth/ SEF)
SECTION operation function
Unbalance detect
Line cut/phase loss detect element
Live line detect
Operation counter limit
Switch contact wear monitoring
Battery auto load test
Power Quality Monitoring
- Interrupt
- Sag
- Swell
- Harmonics
- Current Unbalance
- Voltage Unbalance
- Under Voltage
- Over Voltage
- Under Frequency
- Over Current
DC Analog Input Monitoring
Zero Sequence voltage(V0) detect
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
8 ENHANCED TECHNOLOGY
EVENT RECORDER
Switch Operation Record –Last 256 events
Fault Event Record –Last 256 events
Fault Waves(20 cycles× 8EA) record – Last 8 events
System Event Record – Last 2048 events
Set Change Event – Last 100 events
Average Load Event Record –Last 1024 events
Max. Load per hour Event Record – Last 1024 events
Max Load per day Event Record –Last 1024 events
Diagnostic Event Record – Last 512 events
PQM Monitoring Event Record – Last 100 events
METERING
Phase Current and Phase Angle, Fault Current and Angle, SEF Current and Angle
Voltage and Angle between phases, Forward/Revserse/Zero Sequence and Angle
Frequency magnitude and changing rate per second
Real Power/Apparent Power/Reactive Power per phase
Power Factor per phase
Forward/Reverse Phase Energy
Demand
Source/Load side Voltage and Current Unbalance
Voltage and Current Harmonic rate
Phase True R.M.S voltage and current
DC Analog Input value
ETR300 Inside Temperature
MAINTENANCE
Number of Restart
Number of Diagnostic detec
Number of Switch fault occurred
Number of Instantaneous current fluctuation and its number per phase
Number of PQM occurred and accumulated time
Switch contact wear
COMMUNICATIONS
Side Panel PORT1 RS232 Serial port : DNP 3.0, Modbus and IEC60870-5-101 Protocol
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 9 ENHANCED TECHNOLOGY
Side Panel PORT2 RS485 Serial port : DNP 3.0, Modbus and IEC60870-5-101 Protocol
Side Panel PORT3 RJ45 port : DNP 3.0 및 IEC60870-5-104 Protocol
Side Panel PORTF RS232 Serial port : ETR300-R Interface Software
USER INTERFACE
Fault Indicator
Manual battery load test: Battery voltage and chaged voltage
Dual function keypad
20×4 character display (LCD or VFD: Vacuum Fluorescent Display)
43 LED indicator – Fault Indicator, Sequence Status, Battery status and so on
Fron Panel RS232 Port
Help Message
Security(Password)
AUXILIARY OUTPUTS
16 number of PLC Progoram available
AUXILIARY INPUTS
16 number of PLC Program available
Other
Fault Injection test available
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
10 ENHANCED TECHNOLOGY
2. Technical Specification
2.1. Input and Output
System
3 phases- 3 wires or 3 phases – 4 wires, Max.38kW, Max 800A
Frequency
50/60 Hz System and ABC/ACB phase rotation
Control voltage input
AC Power supply input 110V/220Vac or other voltage(+10%,-15%)
Rated battery voltage : 24Vdc
User DC Poer Output – Option
DC Power supply voltage : 12, 15, 24Vdc
Continuous DC Power supply : 30W
DC Power for 10 second: 70W
Voltage Transformer Input (VT) – Standard
V11, V12, V13, V21, V22, V23 and V10
Input voltage range : Phase-Neutral continuous < 6V
Load burden : 0.002VA(4V)
Voltage Transformer Input (VT) – Option
V11, V12, V13, V21, V22, V23 and V10
Input voltage range : Phase-Neutral continuous < 300V
Load burden : 0.6VA(300V), 0.2VA(220V), 0.05VA(120V), 0.02VA(67V)
Current Transformer (CT)
IA,IB,IC and IG, SEF, ZCT
IA,IB,IC,IG input current range
Nominal: AC 0.6Arms
Continuous: 2A
25A for 1 sec
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 11 ENHANCED TECHNOLOGY
Load burden : 0.38VA(1A)
SEF input current range
Rated current : 0.05A
Continuous current : 0.16A
0.6A for 1sec
Load burden : 0.0375VA(0.05A)
ZCT input current range – Option
Rated current : 1.5mA
Continuous ????????????????? mA
200mA for 1sec
Load burden : 0.0005VA(1.5mA)
Control Input – Option
Control Input 8 channel
Rated voltage and operation range
250Vdc(-15%,+20%)
125Vdc(-15%,+20%)
48Vdc(-15%,+20%)
24Vdc(-15%,+20%)
12Vdc(-10%,+30%)
Operation current: at rated voltage, < 5mA
Control Output Contact – Option
Control Input 8 channel
Open 5 channel
Close 5 channel
Alarm 1 channel
Auto surge protection Varistor 300Vac / 350Vdc
Operation and release time: at +20℃(+68℉) , < 5ms
Max operation power supply
Table 2-1. Max. Operation power supply
(L/R=7ms)
125Vdc 0.1A
48Vdc 0.8A
24Vdc 3A
(cosΦ=0.4) 250Vac 3A
125Vac 5A
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
12 ENHANCED TECHNOLOGY
2.2. Environment Test
Dielectric Strength
CT Input, VT Input, Control Power Input, Fiber-optic insulation Input and Relay output
AC 60㎐, 2㎸/1 minute
Impulse Voltage
IEEE C62.45 (1992) , 6㎸(1.2×50㎲), 3㎄(8×20㎲) of Relay System for Radio
Electromagnetic Interference Transceiver.
Surge Withstand Capability
Protection relay and Relay system protection purpsoe IEEE C37.90.1 - 1989 IEEE SWC test
(3㎸ Vibration1㎒ to 1.5㎒, 5㎸ fast saturation 1.2×50㎲)
IEEE C37.90.2 - 1987 IEEE Test, Test use standard, relay system for Radio Electromagnetic
Interface that comes from Transceiver, 10 V/m(150㎒ and 450㎒, 5 W transmitter 10㎝)
Vibration Test
IEC 255-21-1-1988 Electric Relay, Part 21: Metering relay and protection device vibration,
impact, crash and earthquake test, Section One - Vibration tests (sinusoidal), Class 2
IEC 255-21-1-1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on
measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2
Control Operating Temperature
Operation range위 : -25℃∼+70℃(-13℉∼+158℉)
LCD : -20℃∼+70℃(-4℉∼+158℉) – Standard
VFD(Vacuum Fluorescent Display-Vacuum florecense zero sequence output device) : -
40℃∼+85℃(-40℉∼+185℉) – optoin
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 13 ENHANCED TECHNOLOGY
2.3. Metering Accuracy
Measurement values for metering and protection are based on Input voltage and current which are
eliminated Harmonic.
Voltage metering
Rated voltage : AC voltage 4 V
Each phase voltage : ±0.2 %(Rated voltage 80 ~ 120 %), ±0.5˚
Zero sequence voltage(Vo) : ±0.2 %(Rated voltage 80 ~ 120%), ±0.5˚
3V1, 3V0, 3V2 : ±0.6 %(Rated voltage 80 ~ 120%), ±1˚
Current metering
Rated current : AC 0.6 Arms
IA, IB, IC, IG : ±0.5 mA ± 0.1 % of reading(0.03~1.5 A), ±0.5˚
IN : ±0.005 mA + ±0.5 % of reading(0.5~16.0 mA), ±1˚
3I1, 3I0, 3I2 : ±0.01 A ± 3 % of reading(0.003~1.5A ), ±1˚
Power metering
Power : ±1.2 %(at rated voltage>80 %, at rated current>0.03)
Rea Power : ±0.7 % PF=1, ±1% PF>0.87(at rated voltage>80%, at rated current>0.03)
Reactive Power : ±0.7 % PF=0, ±1% PF<0.5(at rated voltage>80%, at rated current>0.03)
Harmonic metering : ±5%
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
14 ENHANCED TECHNOLOGY
2.4. Monitoring
Fault detect function
Phase fault pickup level ................................................. OFF, 50 ~ 630A (step: 5A)
Earth fault pickup level ................................................. OFF, 25 ~ 315A (step: 5A)
SEF pickup level ........................................................... OFF, 0.1 ~ 10.0A (step: 0.1A)
Dropout.......................................................................... Pickup level 96 ~ 98%
Instantaneous FI detect time .......................................... 1 ~ 180sec (step: 1sec)
Instantaneous FI detect time .......................................... 1 ~ 180sec (step: 1sec)
Phase Directional detect function
Pole voltage ................................................................... normal voltage V1
Directional detect .......................................................... Disable, Enable
Max. Torque angle ......................................................... 0 ~ 345° (step: 15° )
Min. Operation voltage.................................................. 0, 10 ~ 80% (step: 1% )
Phase angle accuracy ..................................................... ± 2°
Internal operation delay ................................................. 1.5cycle
Ground/SEF Directional detect function
Pole voltage ................................................................... Zero sequence voltage Vo
Source side VTs must be Wye connection.
Directional detec ........................................................... Disable, Enable
Max. Torque Angle ........................................................ 0 ~ 345° (step: 15° )
Min. Operation voltage.................................................. 0, 10 ~ 80% (step: 1% )
Phase angle accuracy ..................................................... ± 2°
Internal operation delay ................................................. 1.5cycle
Phase/Ground/SEF Cold Load Pickup Blocking function
Pickup level ................................................................... 1 ~ 20 MTC (step: 1 MTC)
Pickup current restore time ........................................... 0.0 ~ 180.0sec (step: 0.1sec)
CLPU reset time ........................................................... 0.01 ~ 60.00sec (step: 0.01sec)
Pickup level accuracy .................................................... 5%
Timing accuracy ............................................................ ± 5% or ± 20msec
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 15 ENHANCED TECHNOLOGY
SECTION function
Function ......................................................................... Disable, Enable
Auto closing .................................................................. Disable, Enable
Section type ................................................................... V-T, O-T
Close direction ............................................................... Always, Source, Load
Open delay time ............................................................. 0.1 ~ 25.5sec (step: 0.1sec)
Close waiting time ......................................................... 1 ~ 255sec (step: 1sec)
Close delay time ............................................................ 1 ~ 255sec (step: 1sec)
Lockout time .................................................................. 1 ~ 255sec (step: 1sec)
Source side lockout time ............................................... 1 ~ 255sec (step: 1sec)
Source side reset time .................................................... 1 ~ 255sec (step: 1sec)
Block Time .................................................................... 1 ~ 255sec (step: 1sec)
Operation Time .............................................................. 1 ~ 4 time (step: 1 time)
Phase Unbalance
Angle difference ............................................................ OFF, 5 ~ 80° (step: 5°)
Detect delay time ........................................................... 0.0 ~ 180.0sec (step: 0.1sec)
Phase Open/Lost
On Level ........................................................................ phase voltaeg 70 ~ 85% (step: 5%)
Off Level ....................................................................... phase voltage 30 ~ 75% (step: 5%)
Detect delay time ........................................................... 0.0 ~ 180.0sec (step: 0.1sec)
Live line/Dead line detect(Communication)
Live line detect value .................................................... 0.10 ~ 0.90pu (step: 0.01pu)
Deect delay time ............................................................ 0.5sec fixed
Operation counter
Alarm function .............................................................. Off, On
Reset counter ................................................................ 0 ~ 65535 (step: 1)
Alarm counter ................................................................ 0 ~ 20000 (step: 1)
Battery auto load test
Test cycle ....................................................................... 1 ~ 72 hour (step: 1hour)
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
16 ENHANCED TECHNOLOGY
Power Quality Monitoring - PQM
PQM function ............................................................... Disable, Enable
Sag pickup level ............................................................ 0(OFF), 0.50 ~ 0.99pu (step: 0.01pu)
Sag delay time ............................................................... 0.5 ~ 10.0cycle (step: 0.5cycle)
Swell pickup level ......................................................... 0(OFF), 1.01 ~ 1.50pu (step: 0.01pu)
Swell delay time ............................................................ 0.5 ~ 10.0cycle (step: 0.5cycle)
Interruption .................................................................... 0(OFF), 0.10 ~ 0.49pu (step: 0.01pu)
Interruption .................................................................... 0.5 ~ 10.0cycle (step: 0.5cycle)
Voltage harmonic pickup level ...................................... 0(OFF), 0.5 ~ 100.0% (step: 0.1%)
Current harmonic pickup level ...................................... 0(OFF), 0.5 ~ 100.0% (step: 0.1%)
Harmonic delay time ..................................................... 0.2 ~ 60.0sec (step: 0.1sec)
Voltage unbalance pickup level ..................................... 0(OFF), 1 ~ 100% (step: 1%)
Voltaeg unbalance delay time ........................................ 0.1 ~ 60.0sec (step: 0.1sec)
Current unbalance pickup level ..................................... 0(OFF), 1 ~ 100% (step: 1%)
Current unbalance delay time ........................................ 0.1 ~ 60.0sec (step: 0.1sec)
Low voltage pickuip level ............................................. 0(OFF), 0.30 ~ 0.95pu (step: 0.01pu)
Low voltage delay time ................................................. 0.0 ~ 180.0sec (step: 0.1sec)
Over voltage picup level................................................ 0(OFF), 1.05 ~ 1.50pu (step: 0.01pu)
Over voltage delay time ................................................ 0.0 ~ 180.0sec (step: 0.1sec)
Low frequency pickup level .......................................... 0(OFF), 46.00 ~ 59.98Hz (step: 0.01Hz)
Low frequency delay time ............................................. 0.03 ~ 10.00sec (step: 0.01sec)
Phase overcurrent pickup level ...................................... 0(OFF), 50 ~ 630A (step: 5A)
Phase overcurrent delay time ........................................ 0.0 ~ 180.0sec (step: 0.1sec)
Ground overcurrent pickup level ................................... 0(OFF), 25 ~ 315A (step: 5A)
Ground overcurrent delay time ...................................... 0.0 ~ 180.0sec (step: 0.1sec)
Current unbalance/THD detect Min. value ................... 0 ~ 630A (step: 1A)
Switch Contact wear
Contact wear detect ....................................................... Off, On
Pickup wear ................................................................... 0.0 ~ 50.0% (step: 0.1%)
Rated system ................................................................. 15㎸, 27㎸, 38㎸
Rated interruption capacity(㎸) ..................................... 5.0 ~ 50.0㎸ (step: 0.1㎸)
Number of Max. interruption ........................................ 1 ~ 999 (step: 1)
Phase A contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)
Phase B contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)
Phase C contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 17 ENHANCED TECHNOLOGY
TD Monitoring
TD1 rating ..................................................................... 20, 200
TD1 ratio ............................................................... ....... 1 ~ 3000 (step: 1)
TD1 offset .............................................................. ....... -10000 ~ +10000 (step: 1)
TD1-1 type ............................................................ ....... Under or Over
TD1-1 pickup value .............................................. ....... 0(OFF), 0.1 ~ 35.0V (step: 0.1V)
TD1-1 delay time ................................................... ....... 0.01 ~ 600.00sec (step: 0.01sec)
TD1-2 type ............................................................ ....... Under or Over
TD1-2 pickup value .............................................. ....... 0(OFF), 0.1 ~ 35.0V (step: 0.1V)
TD1-2 delay time ................................................... ....... 0.01 ~ 600.00sec (step: 0.01sec)
※. NOTE : There are 4 more channels (TD2 ~ TD5) the same as above.
Zero Sequence Voltage(V0) detect
Pickup level detect ..................................................... ... 0(OFF), 0.05 ~ 1.20pu (step: 0.01pu)
Detect dela time ......................................................... ... 0.1 ~ 6000.0sec (step: 0.1sec)
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
18 ENHANCED TECHNOLOGY
2.5. Event Recorder
Operation event recording device
Trigger source
Switch CLOSE
Switch OPEN
Earth Close(ECLOSE)
Earth Open(EOPEN)
Storage capacity : Total 256 events
Fault event recording device
Trigger source
Taget A, B, C, N phases, SEF
Fault detect : Instantaneous fault, Permenant fault
Detect direction : Forward, Reverse direction
Fault Sequence
Data channel
Current 4, Voltage 3, Frequency, Logic input status 32, Output relay 16channel, Input
16channel
Storage capacity : Total 256 events
Fault wave capture
Trigger source
Fault wave capture point
Fault current
Sampling ratio : 128x20, 64x40, 32x80, 16x160
Storage capacity: 8 fault waves of 20 cycle (20cycles8EA).
System Event Recording device
Trigger source
52A contact
Input/Output status change
Front panel control
AC power supply
External control
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 19 ENHANCED TECHNOLOGY
External input status
System alarm
Sleep mode
Trigger time : each 1/4 cycle
Trigger type : Pickup and Dropout
Storage capacity : Last 2048 events
Set Change Event Recording device
Trigger source
Global setting change
Primary group setting change
Alternate group setting change
Storage capacity : Total 100events
Load Profile
1) Average Load/ Minute
Trigger source
Demand current(A, B, C, G)
Demand real power(A, B, C, 3ф)
Demand reactive power (A, B, C, 3ф)
Trigger time : 1, 2, 3, 4, 5, 6, 10, 12, 15, 20 or 30 min.
Storage capacity : Total 1024events (Storage Capacity : Total 1024 Events)
2) Peak Load/ Hour
Trigger source
Demand current(A, B, C, G)
Demand real power(A, B, C, 3ф)
Demand reactive power(A, B, C, 3ф)
Trigger time : Every 1 hour
Storage capacity : Total 1024 events, 42 days
3) Peak Load/ Day
Trigger source
Demand current(A, B, C, G)
Demand real power(A, B, C, 3ф)
Demand reactive power(A, B, C, 3ф)
Trigger time : Daily
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
20 ENHANCED TECHNOLOGY
Storage capacity : Total 1024 events, 1024days
DIAGNOSTIC EVENT RECORDER
Trigger source
DSP failure
ADC failure
RTC failure
Memory failure
Flash-Rom failure
Circuit voltage failure
Globlal setting failure
Primary setting failure
Alternate setting failure
Event failure
Count failure
DO failure
Close failure
Open failure
Trigger time : evey 1/4 cycle
Trigger type : Pickup and Dropout
Storage capacity : Last 512 events
PQM event recording device (PQM EVENT RECORDER)
Trigger source
PQM pickup element
Storage capacity : Total 100events
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 21 ENHANCED TECHNOLOGY
2.6. Maintenance
COUNTER
Number of System restart : 0 ~ 65534
Number of maintenance : 0 ~ 65534
Number of Operation : 0 ~ 65534
Numer of fault: 0 ~ 65534
Number of Instantaneous current change detect : 0 ~ 65534
Number of PQM detect: 0 ~ 65534
Switch contact wear
Phase A wear: 0.0 ~ 100.0%
Phase B wear: 0.0 ~ 100.0%
Phase C wear: 0.0 ~ 100.0%
2.7. Communication
Table 2-2. Communication
Side panel Port1
RS232, 1200-19200bps, None, Odd or Even Parity, 7 or 8 Data bits, 1or 2
Stop bit
DNP 3.0, Modbus and IEC60870-5-101 protocol
Side panel Port2
RS485/422, 1200-19200bps, None, Odd or Even Parity, 7 or 8 Data bits,
1 or 2 Stop bit
DNP 3.0, Modbus and IEC60870-5-101 Protocol
Side panel Port3 RJ-45, 10BASE-T/100BASE-T
DNP 3.0, Modbus and IEC60870-5-104 Protocol
Front panel PortF RS232, 1200-57600bps, No Parity, 8 Data Bits, 1 Stop bit
ETR300 interface software
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
22 ENHANCED TECHNOLOGY
3. Dimension and structure
OUT101
OUT102
OUT103
+ IN101
IN102
IN103
IN104
++
+OUT104
RCV
Antenna
GPS
PORT RF
Antenna
A04A05A06A07A08A09A10
A03
A02
A01
B05B06B07B08
B04
B03
B02
B01
TX
RX
N.C
LOCKED
CONTROL
ENABLED
REMOTE
SECTION
AUX1
TAG
HOT LINE
ENABLEDRESET
LOCKOUT
TIE CYCLE
SEC/TIE LOCKOUT
SEC CYCLE
ETR300 -S02
ABC / RST LIVE
A Phase Unbalance
C Phase Unbalance
VA / VR
VB / VS
VC / VT
CHECK
BATT'RESET
LAMP TEST
Control & Communication Unit
PORT F
BATTERY
CHARGER
ENT
ESC
FUN
FI
TEST
SEF
ENABLEDENABLED
GROUND
ENABLED
PROTECTION
SETTINGS
ALTERNATE
DOWN
UP
950-08
950-10
XP
OR
TR
J45
950
F01
F02
F03
F04
F05
F06
G01
G02
G03
G04
G05
G06
G07
G08
PORT1
PORT3
PORT2
1
9
LINK
12
32TX
2RX
1TX
1RX
5559
1
5559
1
5559
1
5559
1
5559
1
5559
1
POWER IN
K01
K02
K03
K04
-BAT
+BAT
AC 24V
AC 24V
POWER SUPPLY
INPUTS
OUTPUTS
MONITORS
12
34
CN7
1,3:P
2,4:N
N
P
J01J02J03J04
OUT205
OUT206
H01H02H03H04H05H06
TRIP & CLOSE
CN6
CN5
CN4
CN3
CN2
CN1
12
34
12
34
12
34
12
34
14
36
15
48
V11
V12
V13
V21
V22
V23
V0
+SG
-485
9:N/C
7:RTS
8:CTS
6:DSR
3:TXD
1:DCD
4:DTR
2:RXD
5:GND
485
10M/100M
1:DC02
2,4:COM
1:+12V
3,4:GND
1,3:DC(+)
2,4:DC(-)
3:IN201
2,5:+12V
3,6:GND
1:IN204
4,8:COM
3,7:OUT204
2,6:OUT202
1,5:N/C
3:DC03
2:DC01
4:IN205
2:IN202
4:+12V
1:IN203
I01
I02
I03
IN
Ise
E01
E02
E03
E04
E05
E06
E07
E08
E09
E10
5559
1
950
950
OPENCLOSE
REVERSE POWER
L1
L2
L3
L4
MANUAL LOCK
RX / TX
RUN
DIAG/ERROR
AC SUPPLY
GROUND
SEF
C FAULT
A FAULT
B FAULT
B Phase Unbalance
Figure 3-1. Dimension and Structure
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 23 ENHANCED TECHNOLOGY
4. External Input/Output Connector
ETR300 provides terminals(connector) to connect control and modem, the termainal arrangement
is as belows;
5559
1
5559
1
5559
1
950
5559
1
5559
1
950
5559
1
POWER IN
K01 K02 K03 K04
-BAT
+BAT
AC 24V
AC 24V
POWER SUPPLYINPUTSOUTPUTSMONITORS
12
34
CN7
1,3:P
2,4:N
NP
J01 J02 J03 J04
OUT205 OUT206
H01 H02 H03 H04 H05 H06
TRIP & CLOSE
CN6 CN5 CN4 CN3 CN2 CN1
5559
1
12
34
12
34
12
34
12
34
1
4
3
6
1
5
4
8
V11 V12 V13 V21 V22 V23 V0
+ SG-485
9:N/C
7:RTS 8:CTS6:DSR
3:TXD1:DCD 4:DTR2:RXD
5:GND485
10M/100M
1:DC02
2,4:COM
1:+12V
3,4:GND
1,3:DC(+)
2,4:DC(-)
3:IN201
2,5:+12V
3,6:GND
1:IN204
4,8:COM
3,7:OUT204
2,6:OUT202
1,5:N/C
3:DC03
2:DC01
4:IN205
2:IN202
4:+12V
1:IN203
I01 I02 I03 IN Ise
E01 E02 E03 E04 E05 E06 E07 E08 E09 E10
OUT101 OUT102 OUT103
+
IN101 IN102 IN103 IN104
+ + +OUT104
RCV Antenna
GPS PORT RF
Antenna
A04 A05 A06 A07 A08 A09 A10A03A02A01 B05 B06 B07 B08B04B03B02B01
TX
RX
N.C
950-10 950-08
XPORTRJ45950
F01 F02 F03 F04 F05 F06 G01 G02 G03 G04 G05 G06 G07 G08
PORT1 PORT3PORT2
1
9
LINK
1 2 32TX
2RX
1TX
1RX
Figure 4-1. External Input/Output connector
Table 4-1.Cable size for connecter
Item Size( ㎟ ) Length( ㎜ ) Connecter name Remark
Current 1.25(50/0.18) 300 AkZ 960-10P
Power supply " " AkZ 960-4P
Digital Input 0.75(12/0.18) " Molex 5557-6P,4P
Digital Output " " AkZ 950-6P
Voltage " " AkZ 960-6P,8P
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
24 ENHANCED TECHNOLOGY
4.1. Current Input(Connector type:STLZ960-10)
Current connecter‟s terminal no. 1 starts with phase A and follows by B, C, N, SEF phase turn.
ETR300 current terminal provides all phase name.
I01 I02 I03 IN Ise
E01 E02 E03 E04 E05 E06 E07 E08 E09 E10
Figure 4-2. Current connector
Table 4-2. Current connecter pin
IO1 IO2 IO3 IN Ise
A
phase
B
phase
C
phase
N
phase
SEF
4.2. Voltage Input(Connector type:STLZ960-6P,8P)
Voltage connector has source side 3 phases(A,B,C) and load side 3 phases(R,S,T) as belows;
I01 I02 I03 IN Ise
E01 E02 E03 E04 E05 E06 E07 E08 E09 E10
Figure 4-3. Voltage connector
Table 4-3. Voltage connecter Pin
V11 V12 V13
A
Phase
B
Phase
C
Phase
V21 V22 V23 V0
R
Phase
S
Phase
T
Phase
Zero
Sequence
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 25 ENHANCED TECHNOLOGY
4.3. Digital Output(DO)
Digital Output has total 8 output relays. Digital Output connecter delivers the control single from
the controller and its construction is as belows.
950
OUT205 OUT206
H01 H02 H03 H04 H05 H06
Figure 4-4. Digital Output Connector
Table 4-4. Digital Output Connecter Pin
Pin
Number Signal
Pin
Number
2 Close 3
5 Open 6
4.4. Digital Input(DI)
Digital Input receives 16 status signals through insulated electric contacts. This is how increasing
DI part surge withstand capability and provide more insulation to Main module where signali is
connected but weak to surge voltage. Digital Input connector is the part where receiving status
signal from control part and its structure is as belows.
1 1
3:IN201
2,5:+12V
3,6:GND
1:IN204
4:IN205
2:IN202
4:+12V
1:IN203
CN3 CN2
12
34
1
4
3
6
Figure 4-5. Digital Input Connector
Table 4-5. Digital Input Connecter Pin
Connecter Pin
Number Signal Connecter
Pin
Number
CN2
01 Open
CN2
04
02 Close 04
03 Lock 04
CN3 01
Door
Open CN3 02,05
04 Spare 02,05
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
26 ENHANCED TECHNOLOGY
4.5. Power supply input& Modem power supply output
Power supply connecter has ETR300 operation power supply terminal and modem power supply
terminal. Each connecter provides its name and pin number 1 is for +24V input and pin number 2
is Grond input.
NP
P : DC 24V +Terminal
N : DC 24V GND
Figure 4-6. Power Supply Connecter
4.6. Remote Communication Port(modem connection)
Modem communication port is D-SUB 9 pin male type and all pins are connected except the
number 9 pin (Ring Indicator)
5 1234
6789
Figure 4-7. Remote Communication Port
Table 4-6. Remote Communication Port Pin
Pin No. Signal Info
1 DTR : Data Terminal ready
2 RxD : Received Data
3 TxD : Transmitted Data
4 DTR : Data Terminal Ready
5 GND : Ground
6 DSR : Data Set Ready
7 RTS : Request To Send
8 CTS : Clear To Send
9 RI : Ring Indicator
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 27 ENHANCED TECHNOLOGY
4.7. 485 Communication Port
485 Communication Port has 3 pins and its construction is as follows.
+ SG-485
1 2 3
2T
2R
485
Figure 4-8. 485Commnication Port
Table 4-7. 485Communication Port Pin
Pin No.
485+
485-
SG
4.8. Ethernet Port(RJ45)
Ethernet Port (RJ-45) has 8 pins and its constructions is as follows.
XPORTRJ45
LINKBPS
Figure 4-9. Ethernet Port
Table 4-8. EthernetPort Pin
Pin No. Wire Color 10Base-T Signal
100Base-TX Signal
1 White/Green Transmit+
2 Green Transmit-
3 White/Orange Receive+
4 Blue Unused
5 White/Blue Unused
6 Orange Receive-
7 White/Brown Unused
8 Brown Unused
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
28 ENHANCED TECHNOLOGY
5. User Interface Panel
User Interface Panel uses LCD(204) and keypad to select functions and monitors switch status,
and also with LEDs, selected functions status and switch operation status can be checked.
User Interface Panel provides following functions;
Switch control
Control status check
System status check
Metering value check
Saved records check in ETR300
Set check and change in ETR300
OPENCLOSE
REVERSE POWER
L1
L2
L3
L4
RX / TX
RUN
DIAG/ERROR
AC SUPPLY
GROUND
SEF
C FAULT
A FAULT
B FAULT
B Phase Unbalance
A Phase Unbalance
C Phase Unbalance
VA / VR
VB / VS
VC / VT
CHECK
BATT'RESET
LAMP TEST
Control & Communication Unit
PORT F
BATTERY
CHARGER
ENT
ESC
FUN
FI
TEST
SEF
ENABLEDENABLED
GROUND
ENABLED
PROTECTION
SETTINGS
ALTERNATE
DOWN
UP
LOCKED
CONTROL
ENABLED
REMOTE
SECTION
AUX1
ENABLEDRESET
LOCKOUT
TIE CYCLE
SEC/TIE LOCKOUT
SEC CYCLE
ETR300 -S02
ABC / RST LIVE
AUX2
Figure 5-1. User Interface Panel
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 29 ENHANCED TECHNOLOGY
5.1. Construction
Panel consists of following 12 parts ;
Operation section
Local control section
Menu control section
Other control section
Fault indication section
Line status indication section
Section status section
System diagnostic section
Battery status section
PCL status section
Other status section
Spare ports section
5.1.1. Operation Section
OPEN
Press [OPEN] button to send Trip signal to Switch.
CLOSE
Press [CLOSE] button to send Close signal to Switch.
ETR300 has close time delay and the close operation can be conducted after a set time. Set time
range is from 0.00 ~ 600.00 sec.
POSITION LED
Switch staus is indicated. Position LED is operated based on 52a contact.
Figure 5-2. Operation Selection
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
30 ENHANCED TECHNOLOGY
5.1.2. Local Control Section
Control panel shows all the status of function. If a function is enabled, LED is ON, and when
disabled, LED is OFF. Button changes Enable to Disable vice versa.
SEF
ENABLEDENABLED
GROUND
ENABLED
PROTECTION
SETTINGS
ALTERNATE
LOCKED
CONTROL
ENABLED
REMOTE
SECTION
AUX1
ENABLEDRESET
LOCKOUT
AUX2
Figure 5-3. Local Control Section
Protection(Enable/Disable)
When Enable(LED ON), phase fault detecting is enabled and when Disable(LED OFF), phase
fault detecting is disabled.
NOTE : When Protection is enabled, all protection of ETR300 is on operation, however,
Ground fault and SEF(Sensitive Earth Fault) function shall be set individually on font panel.
Ground (Enable/Disable)
When LED is on, ground fault detecting is enabled and when LED is off, ground fault detecting is
disabled. It is only available when Protection is enabled. Although Ground LED is on, protection
is disabled, ground fault detection is not conducted.
SECTION(Enable/Disable)
When LED is ON, SECTION is enabled, and when LED is OFF, SECTION is disabled.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 31 ENHANCED TECHNOLOGY
Operation select(Local/Remote)
When LED is ON, Remote and Local operation are all available. When LED is OFF, only Local
operation is available.
Operation Lock(Lock/Unlock)
When it is Unlock, local and remote operations are all available. When it is Lock, local and
remote operations are not available.
NOTE : Even if operation lock status, Open, Lamp test, Battery load test and Menu
controlare all available.
ALTERNATE SETTINGS(Select)
When ALTERNATE SETTINGS LED is ON, Group setting becomes Alternate setting and the
Alternate setting is activated. When the LED is OFF,Group setting becomes Primary setting and
the primary setting is activated.
SEF(Enable/Disable)
When LED is ON, SEF is enabled. When LED is OFF, SEF is disabled. Although SEF is
enabled,Protoection is not enabled, SEF is not activated.
SEC/TIE LOCKOUT(Unlock)
SEC/TIE LOCKOUT is dismissed.
AUX(1/2)
Aux. function button.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
32 ENHANCED TECHNOLOGY
5.1.3. Menu Control Section
20×4 LCD is used to check setting, metering and
events, details informations are refer to “5. Operation
manual(How to use LCD)”.
20×4 character LCD
4 operation button(Increase, Decrease, Function
selection)
ENT
ESC
FUN
DOWN
UP
Figure 5-4. Menu Control Section
5.1.4. Other Control Section
CHECK
BATT'RESET
LAMP TEST
FI
TEST
Figure 5-5. Other Control Section
Lamp Test Button
Normal : Press the button to check all Lamps.
FI occurred : It resets FI Target by pressing the button.
Battery
It takes 5 seconds to check battery and charging circuit. When pressing the button and if AC
power supply is provided, charging circuit is disconnected and connects a load resister to battery
and check the charging circuit.
FI Test
When pressing FI Test button, trip test begins beased on set value.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 33 ENHANCED TECHNOLOGY
5.1.5. Fault Indication Section
In case of Permenant or Instantaneous fault, corresponding LED
is ON. LED lamp can be off by manually from local by pressing
FI Reset button or from remote by sending a signal. Otherwise,
LED lamp will be on although H.V. line becomes normal.
GROUND
SEF
C FAULT
A FAULT
B FAULT
Figure 5-6. Fault Indication
Section
5.1.6. H.V. line status indication section
Phase Unbalance lamp
Phase A,B,C Unbalance are indicated.
Under condition that source side and load side are all live line
and switch is open status, check angles, if it meets then, it is OK,
otherwise, it is unbalanced.
Although it is unbalanced, control is still available. Operater
shall decide an operation.
VA / VR
VB / VS
VC / VT
B Phase Unbalance
A Phase Unbalance
C Phase Unbalance
ABC / RST LIVE
Live line lamp
Source side and load side live line status are indicated.
More than one phase voltage is higher than an Off Level of
Disconnect line/Open phase, it is Live line. And all 3 phases are
less than that, it is Dead line. Operater shall decide an operation.
Figure 5-7. Disconnect/Open
phase Lamp
Phase Open/Loss lamp
Source and load side Phase A, B, C Open/Loss phase are
indicated. In case that 1 or 2 phases voltage is less than Off
Level of Disconnect/Open phase, it is determined as
Disconnet/Open phase. LED will be Off when the voltages are
higher than On Level.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
34 ENHANCED TECHNOLOGY
5.1.7. System Diagnostic Section
ETR300-R Diagnostic is displayed. RUN Lamp(green) indicates that ETR300 has passed the
internal diagnostic test and does not have any problem. RX/TX Lamp(Red) indicates the
communication state of ETR300
RUN : It indicates the operation status. In normal
operation, it flicker periodically. In system problem
case , it is lighting or turned off.
DIAG/ERROR : Turn on with abnormality of Self
Diagnostic.
RX : Turn on when transmit data
TX : Turn on when transmit data
RX / TX
RUN
DIAG/ERROR
Figure 5-8.System Diagnostic Lamp
5.1.8. Section Status Section
Indicates present staus of set section function process.
SEC Sequence: Indicates Section operation status.
TIE Sequence: Indicates Tie sequence operation status.
SEC/TIE Sequence End : Indicates sequence Lockout
status.
TIE CYCLE
SEC/TIE LOCKOUT
SEC CYCLE
Figure 5-9. Section Status Lamp
5.1.9. Battery Status Section
The system power status of ETR300 is displayed. When ETR300 is supplying external power, AC
SUPPLY Lamp is on. CHARGER lamp shows the charging status of ETR300 and the BATTERY
lamp shows the battery status of ETR300.
AC SUPPLY : Indicates the external AC power supply
status.
CHARGER : Turn on, when the charger status is
normal.
BATTERY : Turn on, when the battery status is
normal.
AC SUPPLY
BATTERY
CHARGER
Figure 5-10. Battery Status
Lamp
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 35 ENHANCED TECHNOLOGY
5.1.10. User LED Section
LED can be indicated according to the user setting.
LED logic can be set in ‘ETR300 interface software‟
L1
L2
L3
L4
Figure 5-11. User Lamp
5.1.11. Other Status Section
REVER POWER
In reverse current case, the REVER POWER lamp becomes
On.
REVERSE POWER
Figure 5-12. Rever Power lamp
5.1.12. Port F Section
This connection port is for the communication with administration program. It obtains setting
change, control and others events.
TYPE : RS232C(male)
Pin 2 : RXD
Pin 3 : TXD
Pin 5 : GND
Pin 1,4,6,7,8,9 : N/G
Location : Front panel
PORT F
Figure 5-13. Port F
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
36 ENHANCED TECHNOLOGY
5.2. Operation Manual (LCD instruction)
5.2.1. LCD Screen
20 4 character LCD which has back-light support, is used for a user to operate conveniently and
to check operation status clearly.
5.2.2. Control button
LCD Control button is composed of four basic keys(increase, decrease, function/cancel, ENT).
Following table is explanation of the keys.
Table 5-1.Control Button
Button Explanation
ESC
FUN
FUNC/CANCEL
Move to menu selection mode from display mode and move to prior menu from
sub-menu. When press the button in Main Menu it is changed into display
mode. When this key is operated after changed the value, all changed value are
reverted to original setting value.
ENT
ENT
It is used for menu selection or setting change. In menu selection screen this
button is used for menu selection function. In setting change status moves to
menu mode by pressing this button (it operates in toggle method in menu
selection.setting change)
UP
INCREASE
It is used to move the menu into above side or to increase the setting point. As
all menu has circulated function, from the top menu moves into the lowest
menu. In setting change case, after highest setting value comes the lowest
setting value. A level is increased by pressing the button and it is increased
quickly by pressing the button over 2 seconds.
DOWN
DECREASE
It is used to move the menu or to decrease the changed value.
This button has circulated function for menu change/setting change as
[increase] button. A level is decreased by pressing the button and it is decreased
quickly by pressing the button over 2 seconds.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 37 ENHANCED TECHNOLOGY
5.2.3. Menu structure tree
Screen structure consists Initial Logo and Main menu.
Initial screen and all menu are round robin algorithm.
Menu screen is composed of setting and event management menu.
[BI-CCU(S) FOR DAS]
SECTION : DISABLE
S/W STATUS : OPEN
[ RESET ]
A:00000 00.0/00.0
B:00000 00.0/00.0
C:00000 00.0/00.0
N:00000[00.000-0000]
[초기 화면] [메뉴 화면]
[MAIN MENU]
>2.GROUP SETTING
>1.GLOBAL SETTING
>3.EVENT
>4.MAINTENANCE
>5.TIME
>6.STATUS
>7.METERING
기능
취소
Figure 5-14. Initial Logo and Main Menu
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
38 ENHANCED TECHNOLOGY
[MAIN MENU] >1.SYSTEM
>1.POWER LINE
2.CURRNET SENSING
3.VOLTAGE SENSING
>2.COMMUNICATION >1.PROTOCOL SETUP
>1.DNP1
2.DNP2
3.IEC870-5-101
4.IEC870-5-104
5.MODBUS
>1.GLOBAL SETTING
>2.PORT SETUP >1.PORT1(232)
2.PORT2(485)
3.PORT3(ETHERNET)
4.PORTF(232)
>3.EVENT RECORDER
>4.MONITORING
>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY
>1.COMMON
>1.LOGIC TIMER
2.PULSE TIMER
3.PULSE COUNTER >5.PLC
>2.DI/DO >1.INPUT DEBOUNCE
2.OUTPUT PULSE TIME
>1.FACTORY DEBUG >6.OTHERS
>2.GROUP SETTING >1.PRIMARY
>2.ALTERNATE >3.DIRECTION
>*.SAVE SETTING
>1.PHASE
2.GROUND
3.SEF
>4.F.I SETTING TIME
>5.F.I RESET
>7.DELTA I
>8.OVER CURRENT
>3.EVENT
>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.CLEAR SAVED DATA
>4.MAINTENANCE >1.COUNT
>2.INTERRUT TIME
>4.DATA RESET
>1.CCU
2.OPERATION
3.FAULT
4.DELTA I
5.PQM
>*.SAVE SETTING
>1.PICKUP CURRENT
>3.CONTACT WEAR >1.CCU COUNT
2.OPERATION COUNT
3.FAULT COUNT
4.DELTA I COUNT
5.PQM COUNT
6.COUNT ALL
7.INTERRUT TIME
8.CONTACT WEAR
9.ENERGY
10.ABOVE ALL
>5.CCU INFO
>6.F.I TEST
>1.SWITCH
2.INPUT PORTS
3.OUTPUT PORTS
>6.STATUS
>5.TIME
>7.METERING
>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.TD
11.CCU SEF
>1.PHASE DIFF
>2.OPERATION COUNT
>3.CONTACT WEAR
>4.BATTERY TEST
>5.PQM
>6.TD MONITOR
>7.V0 DETECT
>6.SECTION
>2.INRUSH RESTRAINT
Figure 5-15. Menu Tree Structure
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 39 ENHANCED TECHNOLOGY
[MAIN MENU] >1.SYSTEM >1.POWER LINE
2.CURRENT SENSING
3.VOLTAGE SENSING
4.CB OPENING TIME
>2.COMMUNICATION >1.PROTOCOL SETUP
>1.DNP3
2.IEC870-5-101
3.IEC870-5-104
4.MODBUS
>1.GLOBAL SETTING
>1.PORT1(232)
2.PORT2(485)
3.PORT3(ETHERNET)
4.PORTF(232)
>3.EVENT RECORDER
>4.MONITORING
>1.COMMON
>1.LOGIC TIMER
2.PULSE TIMER
3.PULSE COUNTER >6.PLC
>2.DI/DO >1.INPUT DEBOUNCE
2.OUTPUT PULSE TIME
>1.TIME DISP’TYPE
2.PANEL SLEEP TIME
3.FACTORY DEBUG
>7.OTHERS
>2.GROUP SETTING >1.SELECT SETBANK
>3.ALTERNATE
>18.DIRECTION
>*.SAVE SETTING
>1.PHASE
2.GROUND
3.SEF
4.NEG SEQ
>22.USER CURVE
>3.EVENT
>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.PD
>4.MAINTENANCE >1.COUNT
>2.INTERRUT TIME
>4.DATA RESET
>1.CCU
2.OPERATION
3.FAULT
4.DELTA I
5.PQM
6.PD >3.CONTACT WEAR
>1.CCU COUNT
2.OPERATION COUNT
3.FAULT COUNT
4.DELTA I COUNT
5.PQM COUNT
6.PD COUNT
7.COUNT ALL
8.INTERRUT TIME
9.CONTACT WEAR
10.ENERGY
11.ABOVE ALL
>5.CCU INFO
>1.RECLOSER
2.INPUT PORTS
3.OUTPUT PORTS
>6.STATUS
>5.TIME
>7.METERING
>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.PD
11.TD
12.CCU SEF
>1.SYNCHROCHECK
2.OPERATION COUNT
3.CONTACT WEAR
4.BATTERY TEST
>5.PQM
>6.TD MONITOR
7.V0 DETECT
>1.DIAL1
2.DIAL2 >3.DIALUP MODEM
>2.PORT SETUP
>5.LOOP CONTROL
>1.OPERATION
2.INTERVALS
3.PICKUP CURRENT
4.PHASE FAST
5.PHASE DELAY
6.GROUND FAST
7.GROUND DELAY
8.SEF ELEMENT
9.NEG SEQ FAST
10.NEG SEQ DELAY
11.H/C TRIP-PHA
12.H/C TRIP-GND
13.H/C TRIP-NEG
14.H/C LOCKUOT-PHA
15.H/C LOCKUOT-GND
16.H/C LOCKUOT-NEG
17.COLD LOAD PICKUP
>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY
>1.USER CURVE 1
2.USER CURVE 2
3.USER CURVE 3
4.USER CURVE 4
>23.LIVE LOAD BLOCK
*.SAVE SETTING
>12.CLEAR SAVED DATA
>1.OPERATION
2.FAULT
3.SYSTEM
4.SET CHANGE
5.LOAD PROFILE
6.DIGNOSTIC
7.PQM
8.PD
9.ABOVE ALL
>2.PRIMARY
>1.UNDER VOLTAGE 1
2.UNDER VOLTAGE 2
3.OVER VOLTAGE 1
4.OVER VOLTAGE 2
>1.UNDER FREQUENCY
2.OVER FREQUENCY
>21.OTHER ELEMENT
>20.FREQUENCY
>19.VOLTAGE
>4.EDITBANK
>5.AUTO SGRP CHANGE
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
40 ENHANCED TECHNOLOGY
5.2.4. GLOBAL Setting
SYSTEM
Set items related to system elements. Consists of POWER LINE, CURRENT SENSING,
VOLTAGE SENSING and CB OPENING TIME.
COMMUNICATION
Set the items related to the communication elements. Consists of PROTOCOL SETUP and PROT
SETUP.
EVENT RECORDER
Set the items related to the event recorder elements.
MONITORING
Set the items related to metering and maintenance. Consist of OPERATION COUNT, CONTACT
WEAR, BATTERY TEST, PQM, TD MONITOR and V0 DETECTION.
PLC
Set the items related to PLC (Progamable Logic Control) elementsConsist of COMMON and
DI/DO.
OTHERS
Set the items related to the others elements.
SAVE SETTING
Save all changed setting value.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 41 ENHANCED TECHNOLOGY
5.2.5. GROUP Setting
This menu is divided into Primary Group and Alternate Group for the convenience of the user and
according to the ON/OFF of „ALTERNATE SETTINGS‟ lamp of ETR300 panel the applied
group is selected.
(1) Select Set-group
It is composed of Primary group and Alternate group.
PRIMARY group : When „ALTERNATE SETTINGS‟ lamp is OFF, the set point of
Primary group is applied in the line operating element.
ALTERNATE group : When „ALTERNATE SETTINGS‟ lamp is ON, the set point of
Alternate group is applied in the line operation element.
SETTINGS
ALTERNATE
Ficture 5-16. PRIMARY group and ALTERNATE group
By using [ALTERNATE SETTINGS] button, can change the applied group of current protective
unit.
(2) Primary Setting
This menu set the items related to the line operating elements.
(3) Alternate Setting
This menu set items related to the line operating elements. Setting items are same with
“PRIMARY SETTING”.
[GROUP SETTING]
>1.PRIMARY
2.ALTERNATE
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
42 ENHANCED TECHNOLOGY
5.2.6. Event
This menu displays the event information of ETR300. For more details refer the “8. Event”
5.2.7. Maintenance
This menu displays the maintenance information of ETR300.
COUNTER : Indicates counter information related to the system.
INTERRUT TIME : Displays the occurring accumulated time if interruption.
CONTACT WEAR : Display the connect life of the switch.
DATA RESET : Reset the datas related to Maintenance.
CCU INFO : Display the current information of ETR300
For more details refer the “10. Maintenance” .
5.2.8. Time
Check and set the current time.
5.2.9. Status
Display the current status and input output port status of the switch.
5.2.10. Metering
This menu displays the metering value. For more details, refer to “12. METERING” .
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 43 ENHANCED TECHNOLOGY
5.3. LCD Menu Use
5.3.1. INITING screen
The main information of ETR300 is displayed in the initial screen, for the easy access and
understanding of the user.
To move to other initial screen, press [▲] [▼] button.
Press [FUN] button in initial screen to move to Main menu.
INITNG LOGO
Start-up screen1
① SENTION: Indicate the section function status (DISABLE/ENABLE).
② S/W STATUS: Indicate the switch status (OPEN/CLOSE).
③ SENTION Indicate the operation status
- RESET
- RUNNING
- LOCKOUT
NOTE :
When “WARING SYSTEM ERROR” is displayed,means that the control
section is in bad status. Finisht the operation immediately and contact to the
manufacturer.
Starut-up screen2
① Indicate the current of each phase(A,B,C,N).[A].
② Indicate the voltage of each phase(A,B,C,R,S,T). [kV].
③ Indicate SEF current[A].
④ Indicate the zero phase voltage[V].
A: ① ② / ②
B: ① ② / ②
C: ① ② / ②
N: ① [ ③ - ④]
[BI-CCU(S) FOR DAS]
SECTION : ① S/W STATUS : ②
[ ③ ]
[BI-CCU(S) FOR DAS]
SECTION : DISABLE
S/W STATUS : OPEN
[ RESET ]
A:00000 00.0/00.0
B:00000 00.0/00.0
C:00000 00.0/00.0
N:00000[00.000-0000]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
44 ENHANCED TECHNOLOGY
5.3.2. Main Menu
In the initial menu, press [FUN] button, it is moved into Main menu. If press [FUN] button in
main menu, it is moved to the initial menu. Main menu has sub-menu as below.
MAIN MENU
Main Menu is composed of 7 submenus.
Select the submenu by using [▲] [▼] key.
Move to the submenu by pressing [ENT] key.
As the above explanation, you can move or select the submenu..
5.3.3. View Example
Move to “ MAIN MENU / STATUS / INPUT PORTS” to see the external input port status.
The following screen is displayed.
MAIN MENU/ STATUS/ INPUT PORTS
LO/DEASSERT : Shows External Input is de-asserted,
HI/ASSERT : Shows External Input is asserted.
4 lines are displayed in the LCD screen.
See next line by using [▲] [▼] key .
[INPUT PORT]
IN 101 :LO/DEASSERT
IN 102 :LO/DEASSERT
IN 103 :LO/DEASSERT
IN 104 :LO/DEASSERT
IN 105 :LO/DEASSERT
IN 106 :LO/DEASSERT
IN 107 :LO/DEASSERT
IN 108 :LO/DEASSERT
IN 201 : HI/ASSERT
IN 202 : HI/ASSERT
IN 203 : HI/ASSERT
IN 204 : HI/ASSERT
IN 205 : HI/ASSERT
IN 206 : HI/ASSERT
IN 207 : HI/ASSERT
IN 208 : HI/ASSERT
[MAIN MENU]
>1.GLOBAL SETTING
2.GROUP SETTING
3.EVENT
4.MAINTENANCE
5.TIME
6.STATUS
7.METERING
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 45 ENHANCED TECHNOLOGY
5.3.4. Setting Example
Change of Phase Pickup Current of line operating element of Primary setting.
1) Move to“MAIN MENU/ GROUP SETTING/ PRIMARY/ PICKUP CURRENT / PHASE”.
The following screen is displayed.
MAIN MENU/ GROUP SETTING/ PRIMARY/ PICKUP CURRENT / PHASE
Range OFF, 50 ~ 630A
Default 300 Step 5A
Set the Phase Pickup Current.
2) In the above screen, locate the cursor on Phase by using choose [▲] [▼] key and then press
the [ENT] key to change the set point.
3) Change in new setting point by using [▲] [▼] key.
By pressing [ENT] key, you can see the changed phase setting point.
NOTE : Be sure to save all changed set point in the menu “*. Setting Save”.
[PICKUP CURRENT]
>Phase: 400
Ground: 70
S.E.F: OFF
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
46 ENHANCED TECHNOLOGY
5.3.5. Setting Save
Follow the following step to save all changed set point.
Move to “MAIN MENU/ GROUP SETTING/ PRIMARY / SAVE SETTING” and follow the
following step. (“Global Setting” menu and “Group Setting or Alternate” menu have the
“*.Setting Save” menu).
MAIN MENU / PRIMARY SETTING / SAVE SETTING
①
②
③
To save the changed setting value, press [ENT] button in screen ①. If
the change has succeed screen ③ is appeared.
If, there is nothing changed and select “*. SAVE SETTING”, the
screen ② is displayed.
NOTE :
Changed set value is applied if the changed set value is saved.
If changed set value saving is cancelled, previous value is
remained.
SETTING CHANGED
PRESS <ENT> TO SAVE
* NOTHING CHANGED *
[SAVE SETTING]
* SUCCESS *
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 47 ENHANCED TECHNOLOGY
6. Global Setting
Locate the cursor on “1.GLOBAL SETTING” in the main menu, and move to this menu by
pressing [ENT]. GLOBAL SETTING menu has the following submenu.
NOTE : The changed setting point works after being saved.
When cancel the save, setting point maintain the previous value.
6.1. System
Locate the cursor on “1.SYSETM” in GLOBAL SETTING menu and move to this menu by
pressing [ENT] button. In this menu, various elements related to the system can be set. It has the
following submenu.
NOTE : Do not change the setting elements of SYSTEM , as they are set according to the
characteristics of recloser.
[SYSTEM]
>1.POWER LINE
2.CURRENT SENSING
3.VOLTAGE SENSING
[GLOBAL SETTING]
>1.SYSTEM
2.COMMUNICATION
3.EVENT RECODER
4.MONITERING
5.PLC
6.OTHERS
*.SAVE SETTING
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
48 ENHANCED TECHNOLOGY
6.1.1. Power Line
Locate the cursor on “1.POWER LINE” in SYSTEM menu, move to this menu by pressing [ENT]
button. In this menu, enter the Line information of the device installation location.
GLOBAL SETTING / SYSTEM / POWER LINE / Frequency
Range 50, 60 ㎐
Default 50 Step ~
Select the nominal power system frequency. This value is used as a
default to set the optimal digital sampling rate.
GLOBAL SETTING / SYSTEM / POWER LINE / Phase Rotation
Range ABC, ACB
Default ABC Step ~
Select the phase rotation of the power system.
GLOBAL SETTING / SYSTEM / POWER LINE / Nominal Volt
Range 1000 ~ 30000V
Default 11500 Step 10V
Set the rated voltage of the power system
6.1.2. Current Sensing
Locate the cursor on 2.CURRENT SENSING” in SYSTEM menu, move to this menu by pressing
[ENT] button.
Enter the exact CT rate for the accurate metering and monitoring.
Enter the CT rate after changing the second side in 1 Amp.
GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Ratio
Range 1 ~ 2000
Default 1000 Step 1
Enter the CT rate.
GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Polarity
[POWER LINE]
>Nominal Volt: 11500
[1000~30000:10V]
[CURRENT SENSING]
>CT-Ratio: 1000
CT-Polarity: FOR
[1~2000:1]
[POWER LINE]
>Frequency: 50
Phase Rotation: ABC
[50/60Hz]
[POWER LINE]
Frequency: 60
>Phase Rotation: ABC
[ABC/ACB]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 49 ENHANCED TECHNOLOGY
Range Forward, Reverse
Default Forward Step ~
Enter the CT polarity.
GLOBAL SETTING / SYSTEM / CURRENT SENSING / ZCT-Ratio
Range 0(OFF), 0.1 ~ 1000.0
Default 133.3 Step 0.1
Enter the ZCT rate..
GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Polarity
Range Forward, Reverse
Default Forward Step ~
Enter the ZCT pole direction
[CURRENT SENSING]
CZCT-Ratio: 1.0
>ZCT-Polarity: FOR
[FOR/REV]
[CURRENT SENSING]
>ZCT-Ratio: 133.3
ZCT-Polarity: FOR
0(OFF),0~1000.0:0.1
[CURRENT SENSING]
CCT-Ratio: 1000
>CT-Polarity: FOR
[FOR/REV]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
50 ENHANCED TECHNOLOGY
6.1.3. Voltage Sensing
Locate the cursor on “3.VOLTAGE SENSING” in the SYSTEM menu, move to this menu by
pressing the [ENT] button.
ETR300 has 2 Voltage Connectors. Voltage connectors are receiving Source side and Load side
line voltages. To measure received voltages, set Voltage connectors‟ Connect Type, 2nd Nominal
Voltage and VT Ratio.
According to the installed line VT, ETR300 performs the voltage metering, power calculation and
direction control of over current, and the line VT can be used to perform the Phase Sync Fail.
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V Connect Type
Range NONE, WYE, DELTA
Default WYE Step ~
Select 1V(1st voltage connector).
NONE : VT uninstalled. Select NONE if Voltage Sensing item is
not used.
WYE : If Voltage Connect type of 1V is Y type, select WYE.
DELTA : If Voltage Connect type of 1V is Δ-type, select DELTA.
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / Reference Phase
Range A, B, C
Default A Step ~
Enter base voltage of Voltage connector.
※. NOTE ) The connect phase of main bushing changes according to
the „Base Voltage of Voltage connector‟ and „phase
rotation of power system(MAIN MENU(COM)/
GLOBAL SETTING/ SYSTEM/ POWER LINE/
Phase Rotation)‟. “Table 6-1. Refer to the phase
selection according to the base voltage and phase
rotation”.
[POWER LINE]
>1V CON-Type: WYE
>Reference Phase: A
[A/B/C]
[VOLTAGE SENSING]
>1V CON-Type: WYE
Reference Phase: A
[NONE/WYE/DELTY]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 51 ENHANCED TECHNOLOGY
Table 6-1. Phase selection according to the base voltage and phase rotation.
Setting
Terminal
Base
Voltage REF A REF B REF C
Phase
Rotation ABC ACB ABC ACB ABC ACB
Device A Bushing - A A B B C C
Device B Bushing - B C C A A B
Device C Bushing - C B A C B A
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V 2nd(V)
Range 2.0 ~ 350.0V
Default 4.0 Step 0.1V
Enter the second rated voltage(V) of 1V(1st Voltage connector).
This setting is the second rated voltage that entered in the relay about
line rated voltage.
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V Ratio
Range 10.0 ~ 6500.0
Default 3300.0 Step 0.1
Enter the VT rated rate of 1V(1st Voltage connector).
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V Connect Type
Range NONE, WYE, DELTA
Default WYE Step ~
Select the voltage type of system that input to 2V(2nd Voltage
Connector) .
NONE : VT non installed. Select NON if Voltage Sensing item is
not used.
WYE : If Voltage Connect Type of 2V is Y-Type, Select WYE.
DELTA : If Voltage Connect Type of 2V is Δ-Type, Select DELTA.
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V 2nd(V)
[VOLTAGE SENSING]
>2V CON-Type: WYE
2V 2nd(V): 4.0
[NONE/WYE/DELTY]
[VOLTAGE SENSING]
>1V 2nd(V): 4.0
>1V Ratio: 3300.0
[10.0~6500.0:0.1]
[VOLTAGE SENSING]
>1V 2nd(V): 4.0
>1V Ratio: 3300.0
[2.0~350.0:0.1V]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
52 ENHANCED TECHNOLOGY
Range 2.0 ~ 350.0V
Default 4.0 Step 0.1V
Enter the second rated voltage(V) of 2V(2nd Voltage Connector).
This setting is the second rated voltage that entered in the relay about
line rated voltage.
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V Ratio
Range 10.0 ~ 6500.0
Default 3300.0 Step 0.1
Enter the VT Rated Rate of 2V(2nd Voltage Connector).
GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / Source Side
Range 1V, 2V
Default 1V Step ~
Select the Source side of System.
According to the selected value the indication of “MAIN MENU/
METERING/ VOLTAGE” change. In the VOLTAGE screen, indicate
ABC in the Source Side, and RST in the Load Side.
[VOLTAGE SENSING]
>2V Ratio: 3300.0
>Source Side: 1V
[1V/2V]
[VOLTAGE SENSING]
>2V 2nd(V): 4.0
>2V Ratio: 3300.0
[10.0~6500.0:0.1]
[VOLTAGE SENSING]
>2V 2nd(V): 4.0
>2V Ratio: 3300.0
[2.0~350.0:0.1V]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 53 ENHANCED TECHNOLOGY
Setting Examples
In case of Y-type connection use, set VT2nd[V] for 4V initial value, and if the primary phase-
phase voltage is 15㎸ Ф-Ф, VT ratio is calculated as below.
VoltageФ-Ф = VoltageФ-N × 3
VoltageФ-N = VT 2nd
[V] × VT Ratio
8.66㎸Ф-N = 15㎸ Ф-Ф / 3
8.66㎸Ф-N = 4[V] × 2165
According to the above formula, VT rate is calculated in 2165.
With the same VT2nd[V] and VT ratio, if the primary phase-phase voltage(VoltageФ-Ф) is 11kV,
the primary phase voltage is 6.35㎸Ф-N (=11㎸ Ф-Ф / 3 ), VT secondary input voltage is
3V(=6.35㎸Ф-N /2165)
In case that Δ-type connection is used, if VT2nd[V] is 4V and the primary phase to phase to phase
is 15㎸ Ф-Ф, VT ratio is 3750(15㎸ Ф-Ф /4V = 3750).
Table 6-2. VT Rated Rate
Line-Line
Votage
Wye connection Delta connection
VT 2nd (v) VT Ratio VT 2nd (v) VT Ratio
15㎸ 4 2165 100 150
27㎸ 4 3897.1 100 270
38㎸ 4 5484.8 100 380
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
54 ENHANCED TECHNOLOGY
6.2. Communication
Locate the cursor on “2. COMMUNICATION” in GLOBAL SETTING, move to this menu by
pressing [ENT] button. In this menu, all elements related to the communication can be set and has
the following submenu.
6.2.1. Protocol Setup
Locate the cursor on “1. PROTOCOL SETUP” in COMMUNICATION menu, move to this menu
by pressing [ENT] button. In this menu, set the communication protocol that is supported ETR300.
This menu has the following submenu.
ETR300 supports DNP3, IEC60870-5-101, IEC60870-5-104 and MODBOUS according to the
communication conditions of the user. Each supported protocol can be set.
6.2.1.1. DNP3.0 Protocol Setup
ETR300 can DNP3.0 communicate by using the communication port1, port2, port3 or port4. For
more information refer the “DNP3.0 Protocol Technical Manual”.
DNP3.0 protocol setting menu is as following.
[PROTOCOL SETUP]
>1.DNP3
[COMMUNICATION]
>1.PROTOCOL SETUP
2.PORT SETUP
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 55 ENHANCED TECHNOLOGY
(1) DNP3
To setting DNP3 Protocol move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/
PROTOCOL SETUP/ DNP3”.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Function
Range ON, OFF
Default ON Step ~
Toselect DNP3, set ON.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ COM Port
Range PORT1, PORT2, PORT3
Default PORT1 Step ~
Select DNP3 communication port.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Confirm
Range NO, YES, SOMETIME
Default SOMETIME Step ~
Choose whether Data Link Confirm is used or not.
NO : Data Link Confirm is not used.
YES : Data Link Confirm is used
SOMETIME : Use Data Link Confirm in case of multi frame.
When set the use of Data Link Confirm, check the setting status of
host and set same with the host. If the setting status is different with
the host can be occur an communication error because of Data Link
Reset.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L FrameDly
Range 10 ~ 5000msec
Default 100 Step 10msec
Set Data Link frame Delay time.
If the D/L Confirm setting is OFF, means the transmission distance
between Frame when occurs multi frame.
[DNP3]
>D/L Confirm: SOME
>D/L FrameDly: 100
[10~5000:10ms]
[DNP3]
>Function: ON
COM Port: PORT1
[OFF/ON]
[DNP3]
>D/L Confirm: SOME
D/L FrameDly: 100
[NO/YES/SOME]
[DNP3]
>COM Port: PORT1
D/L Confirm: SOME
[PORT1/PORT2/PORT3]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
56 ENHANCED TECHNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Retries
Range 0, 1, 2
Default 0 Step 1
Set the retry number of Data Link.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Timeout
Range 1 ~ 255 sec
Default 10 Step 1 sec
Set the waiting time of Data Link Frame transmission to the Data Link
Confirm (ACK) receiveing of the master side. ETR300 resends the
Data Link Frame, when the Data Link Confirm has not received
during the setting time and it is possible to retry the Data Link.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ A/L Retries
Range 0, 1, 2
Default 0 Step 1
Set the retry number of Application Link Layer.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ A/L Timeout
Range 1 ~ 255 sec
Default 15 Step 1 sec
In case that request Confirm during the data transmission from Slave
Application to Master Application, set the maximum time of A/L
Confirm(ACK) receiving from Mast Application to Slave Application.
[DNP3]
>A/L Timeout: 15
Fault I Report: YES
[1~255:1s]
[DNP3]
>A/L Retries: 0
A/L Timeout: 15
[0~2:1]
[DNP3]
>D/L Timeout: 10
A/L Retries: 0
[1~255:1s]
[DNP3]
>D/L Retries: 0
D/L Timeout: 10
[0~2:1]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 57 ENHANCED TECHNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Fault I Report
Range NO, YES, 1SHOT
Default YES Step -
NO : Do not send the all Fault Current Sequence to Event.
YES : Send all Fault Current Sequence to Event.
1SHOT : Send the first Sequence Fault Current of Fualt Sequence
to Event.
NOTE :
The Fault Current occurrence time of each Sequence is when
becomes no voltage after experience the Fault Current.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Fault I Reset
Range NO, YES
Default NO Step -
Set the Fault Current Initialization.
NO : Final Fault Current Value is maintained till the next fault
occurrence even the fault detection information is reseted.
YES : Fault Current Value is initialized in 0 at the time that
current detect information is canceld.
NOTE :
Fault Current is handled in RMS maximum value of each
Sequence Fault Current Waveform.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Master Addr
Range 0 ~ 65534
Default 65534 Step 1
Enter the DNP address of Master station. ETR300 refer this address
when send Unsol message.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ DNP Address
Range 0 ~ 65534
Default 0 Step 1
Enter the address of Slave(ETR300).
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ SBO Time
[DNP3]
>Fault I Report: YES
>Fault I Resec: NO
[NO/YES]
[DNP3]
>A/L Timeout: 15
>Fault I Report: YES
[NO/YES/1SHOT]
[DNP3]
>DNP Address: 0
SBO Time: 15
[0~65534:1]
[DNP3]
>Master Addr: 65534
DNP Address: 0
[0~65534:1]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
58 ENHANCED TECHNOLOGY
Range 1 ~ 255 sec
Default 15 Step 1 sec
Set the time interval between Select Function and Operate Function.
It is time that maintain the Select order after receiving it, if there is not
an operation order during setting value the select order is canceled.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Debounce Time
Range 10 ~ 100 msec
Default 20 Step 5 msec
Set the connection debounce time
But, the debounce time of door open information it is fixed in 1
second.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Aver. Load Calc T
Range 1/2/3/4/5/6/10/12/15/20/30 min
Default 15 Step -
Set the time interval for the calculation of average load current.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Daily Max I
Range DISABLE, ENABLE
Default ENABLE Step -
Select the [DISABLE/ENABLE] of Daily Maximum Load Current
transmission.
DISABLE : Do not process Daily Maximum Load Current Event..
ENABLE : Process Daily Maximum Load Current.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Init Unsol
Range DISABLE, ENABLE
Default ENABLE Step ~
Select [DISABLE/ENABLE] of Initial Unsolicited Response Use
when Power Up.
Enable : When Power Up, transmit the Initial Unsolicited
Response Message.
Disable : When Power Up, do not transmit Initial Unsolicited
Response Message.
[DNP3]
>Daily Max I: ENABLE
>Init Unsol: ENABLE
[DISABLE/ENABLE]
[DNP3]
>Aver.Load Calc T:15
>Daily Max I: ENABLE
[DISABLE/ENABLE]
[DNP3]
>Aver.Load Calc T:15
>Daily Max I: ENABLE
1~6/10/12/15/20/30m
[DNP3]
>SBO Time: 15
>Debounce Time: 20
[10~100:20ms]
[DNP3]
>SBO Time: 15
Debounce Time: 20
[1~255:1s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 59 ENHANCED TECHNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 1
Range DISABLE, ENABLE
Default ENABLE Step ~
Select [ENABLE/DESABLE] of Unsolicied Response transmission to
the master station when occurs an Event in Class 1.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 2
Range DISABLE, ENABLE
Default ENABLE Step ~
Select [ENABLE/DESABLE] of Unsolicied Response transmission to
the master station when occurs an Event in Class 2.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 3
Range DISABLE, ENABLE
Default ENABLE Step ~
Select [ENABLE/DESABLE] of Unsolicied Response transmission to
the master station when occurs an Event in Class 3.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Unsol Time
Range 0 ~ 60 sec
Default 5 Step 1 sec
Set the delay time of Unsolicited mode event transmission to the
master station. It is transmitted if new event does not happen during
this time.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Leve1(%)
Range 0(OFF), 1 ~ 50 %
Default OFF Step 1 %
Set the detect level of VOC(Value Of Change) Event1.
When set in OFF, does not occur Event information.
Display the analog input regulation in percentage, in case that the
regulation is higher than the setting point it is reported by
communication.
[DNP3]
>Class 3: ENABLE
>Unsol Time: 5
[0~60:1s]
[DNP3]
>Class 2: ENABLE
>Class 3: ENABLE
[DISABLE/ENABLE]
[DNP3]
>Class 1: ENABLE
>Class 2: ENABLE
[DISABLE/ENABLE]
[DNP3]
>Class 1: ENABLE
Class 2: ENABLE
[DISABLE/ENABLE]
[DNP3]
>VOC Level(%): OFF
>VOC Min: 100
[0(OFF),1~50:1%]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
60 ENHANCED TECHNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Min
Range 0 ~ 630 A
Default 100 Step 1A
Set VOC level to detect VOC Event.
In case that analog input value is under minimum value, does not
transmit communication to the superior.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Select
Range RMS, AVER
Default AVER Step -
Select current used for the VOC decision.
RMS : Apply virtual value current to VOC detection.
AVER : Apply average current to VOC detection.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ TCP/IP Port
Range 0 ~ 65535
Default 0 Step 1
Set TCP/IP port of ETR300.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ IP Addr‟1~4
Range 0 ~ 255
Default 0 Step 1
Select the master station IP address for DNP3.0 communication.
IP Address : 192.xxx.xxx.xxx ① ② ③ ④
IP Addr 1́,2,3,4 means ①,②,③,④.
For example, in case that the IP address is „255.255.255.255‟, set as
the following.
Master IP Oct1 : 255
Master IP Oct2 : 255
Master IP Oct3 : 255
Master IP Oct4 : 255
[DNP3]
>IP Addr’1: 0
IP Addr’2: 0
IP Addr’3: 0
>IP Addr’4: 0
[DNP3]
>TCP/IP Port: 0
IP Addr’1: 0
[1~65535:1]
[DNP3]
>VOC Min: 100
>VOC Select: AVER
[RMS/AVER]
[DNP3]
VOC Level(%): OFF
>VOC Min: 100
[0~630:1A]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 61 ENHANCED TECHNOLOGY
6.2.2. Port Setup
Locate the cursor on “2. PORT SETUP” in COMMUNICATION menu, move to this menu by
pressing [ENT] button. In this menu, set the communication port and related elements of ETR300.
It has the following submenu.
6.2.2.1. PORT1(232) Setup
Set elements related to PORT1 which is located in the side panel of ETR300.
Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORT1(232)” to set Port 1.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Baud Rate
Range 1200, 2400, 4800, 9600, 19200 bps
Default 1200 Step ~
Select the baud rate of PORT1.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Parity Bit
Range NONE, ODD, EVEN
Default NONE Step ~
Select the use of Parity Bit and its type.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Data Bit
Range 7, 8
Default 8 Step ~
Select the Data bit number which will be used for the communication.
[PROT1(232)]
Parity Bit: NONE
>Data Bit: 8
[7~8:1]
[PROT1(232)]
Baud Rate: 1200
>Parity Bit: NONE
[NONE/ODD/EVEN]
[PROT1(232)]
>Baud Rate: 1200
Parity Bit: NONE
[1200 ~ 19200 bps]
[PORT SETUP]
>1.PORT1(232)
2.PORT2(485)
3.PORT3(ETHERNET)
4.PORTF(232)
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
62 ENHANCED TECHNOLOGY
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Stop Bit
Range 1, 2
Default 1 Step ~
Slect the Stop bit number which will be used for the communication.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Modem Sel
Range 2W, 4W, D1, D2, NONE
Default 4W Step ~
Select a modem for communication.
2W : 2 wire private line is used and continuously Carrier is monitored
to control data flow by DCD(Data Carrier Detect).
4W : 4 wire private line is used and RTS(Request To Send) and
CTS(clear to Send) signal are used to control data flow.
D1 : Dial-Up1 modem is used.
D2 : Dial-Up2 modem is used.
NONE : Not used.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ CTS Usage
Range ON, OFF
Default ON Step ~
Set the [OFF/ON] of CTS signal usage.
ON : Transfer the transmission data after checking that the CTS
signal is Assert.
OFF : Transfer the transmission data regardless of the CTS sign.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ DCD Usage
Range ON, OFF
Default ON Step ~
Set the [OFF/ON] of DCD signal usage.
ON : Transfer the transmission data checking that the DCD signal
is Deassert.
OFF : Transfor the transmission data regardless of the DCD signal.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ RTS Usage
[PROT1(232)]
>DCD Usage: OFF
>RTS Usage: AUTO
[OFF/ON]
[PROT1(232)]
>Modem Sel: 4W
>CTS Usage: ON
[OFF/ON]
[PROT1(232)]
>Modem Sel: 4W
>CTS Usage: ON
[2W/4W/D1/D2/NONE]
[PROT1(232)]
Data Bit: 8
>Stop Bit: 1
[1~2:1]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 63 ENHANCED TECHNOLOGY
Range OFF, ON, AUTO
Default AUTO Step ~
ON : RTS sign of ETR is always ON(Assert).
OFF : RTS sign of ETR300 is always OFF(Deassert).
AUTO : When request a data transmission to modem the RTS sign
of ETR300 is ON and when finish the transmission the RTS sign of
ETR300 is OFF.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ CTS CheckOut
Range 1 ~ 255 sec
Default 2 Step 1 sec
Set a waiting time that waits Modems confirmation on RTS signal
which informs that ETR300 is ready to transfer a data. If there is no
CTS response within a set time, RTU confirms CTS Fail and does not
transfer the data.
It is available if „CTS Usage‟ setting is ON.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ DCD CheckOut
Range 10 ~ 30000 msec
Default 5000 Step 5 msec
Set a delay time of DCD signal check which determine modem status
before sending RTS signal in 2 wire communication type. After a set
time, if DCD signal is ON, ETR300 does not transfer the data and
treat it as DCD Fail. It is available if „DCD Usage‟ setting is ON.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ RTS OffDelay
Range 10 ~ 500 msec
Default 50 Step 5 msec
RTS Off Delay Time set the delay time of RTS sign that becom Off
after the data transmission.
It is time delay to prevent the liss if last data after sending the data.
Commonly, RTS Off Delay Time is set in 1 or 2 Byte transmission
occur time.
[PROT1(232)]
DCD CheckOut: 5000
>RTS Off Dly: 50
[10~500:5ms]
[PROT1(232)]
>CTS CheckOut: 2
>DCD CheckOut: 5000
[10~30000:5ms]
[PROT1(232)]
>CTS CheckOut: 2
>DCD CheckOut: 5000
[1~255:1s]
[PROT1(232)]
>DCD Usage: OFF
>RTS Usage: AUTO
[OFF/ON/AUTO]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
64 ENHANCED TECHNOLOGY
6.2.2.2. PORT2(485) Setup
Set items related to the PORT2 located in the side panel of ETR300.
To set PORT2 move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORT2(485)”.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Baud Rate
Range 1200, 2400, 4800, 9600, 19200 bps
Default 1200 Step ~
Select the Baud Rate of PORT2 .
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Parity Bit
Range NONE, ODD, EVEN
Default NONE Step ~
Select the use of Parity Bit and its type.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Data Bit
Range 7, 8
Default 8 Step ~
Select the Data Bit number used for the communication..
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Stop Bit
Range 1, 2
Default 1 Step ~
Select the Stop Bit number used for the communication.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Line Type
Range RS422, RS485
Default RS422 Step ~
Select the Line Type used for the communication..
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ CA Delay
Range 0.00 ~ 240.00
Default 1.00 Step 0.01 sec
Set the Delay type of the answer data transmission after data receipt.
[PROT2(485)]
>Line Type: RS422
>CA Delay: 1.00
[0.00~240.00:0.01]
[PROT2(485)]
>Line Type: RS422
CA Delay: 1.00
[RS422/RS485]
[PROT2(485)]
Data Bit: 8
>Stop Bit: 1
[1~2:1]
[PROT2(485)]
Parity Bit: NONE
>Data Bit: 8
[7~8:1]
[PROT2(485)]
Baud Rate: 1200
>Parity Bit: NONE
[NONE/ODD/EVEN]
[PROT2(485)]
>Baud Rate: 1200
Parity Bit: NONE
[1200 ~ 19200 bps]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 65 ENHANCED TECHNOLOGY
6.2.2.3. PORT3(EHTERNET) Setup
Set items related to the PORT3 located in the side panel of ETR300
To set PORT3 move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORT3(ETHERNET)”.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ IP Addr Oct1 ~ 4
Range 0 ~ 255
Default 0 Step 1
Select IP address of ETR300.
IP Address : 192.xxx.xxx.xxx ① ② ③ ④
IP Addr 1́,2,3,4 means ①,②,③,④.
For example, in case that the IP address is „255.255.255.255‟, set as
the following.
IP Addr Oct1 : 255
IP Addr Oct2 : 255
IP Addr Oct3 : 255
IP Addr Oct4 : 255
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ Gateway Oct1 ~ 4
Range 0 ~ 255
Default 0 Step 1
Select Gateway adress.
Gateway Address : 192.xxx.xxx.xxx ① ② ③ ④
Gateway Addr 1́,2,3,4 means ①,②,③,④.
GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ SubnetMask Oct1 ~ 4
Range 0 ~ 255
Default 0 Step 1
Select Subnet Mask address of ETR300.
Subnet Mask Address : 192.xxx.xxx.xxx
① ② ③ ④
Subnet Mask Addr 1́,2,3,4 means ①,②,③,④.
[PORT3(ETHERNET)]
>SubnetMask Oct1: 0
SubnetMask Oct2: 0
SubnetMask Oct3: 0
SubnetMask Oct4: 0
[PORT3(ETHERNET)]
>Gateway Oct1: 0
Gateway Oct2: 0
Gateway Oct3: 0
Gateway Oct4: 0
[PORT3(ETHERNET)]
>IP Addr Oct1: 0
IP Addr Oct2: 0
IP Addr Oct3: 0
IP Addr Oct4: 0
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
66 ENHANCED TECHNOLOGY
6.2.2.4. PORTF(232) Setup
Set items related to the PORTF located in the front panel of ETR300
To set the PORTF move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT
SETUP/PORTF(232)” .
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Wireless
Range DISABLE, ENABLE
Default DISABLE Step ~
Select the use[DISABLE/ENABLE] of Wireless communication.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Slave Addr
Range 0 ~ 65534
Default 1 Step 1
Enter Slave(ETR300) adress.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Master Addr
Range 0 ~ 65534
Default 1 Step 1
Enter Master station adress.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Baud Rate
Range 1200, 2400, 4800, 9600, 19200, 38400, 57600 bps
Default 1200 Step ~
Select Baud Rate of PORTF.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Modem Sel
Range 2W, 4W, D1, D2, NONE
Default 4W Step ~
Select a modem for communication.
2W : 2 wire private line is used and continuously Carrier is monitored
to control a data flow by DCD(Data Carrier Detect) signal.
4W : 4 wire private line is used and RTS(Request To Send) and
CTS(Clear To Send) signal is used to control a data flow.
[PROTF(232)]
>Modem Sel: 4W
>CTS Usage: ON
[2W/4W/D1/D2/NONE]
[DNP3]
>Slave Addr: 1
>Master Addr: 65534
[0~65534:1]
[DNP3]
>Slave Addr: 1
>Master Addr: 65534
[0~65534:1]
[PORTF(232)]
>Wireless: DISABLE
Slave Addr: 1
[DISABLE/ENABLE]
[PROTF(232)]
>Baud Rate: 1200
Modem Sel: 4W
[1200 ~ 57600 bps]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 67 ENHANCED TECHNOLOGY
D1 : Dial-Up1 modem is used.
D2 : Dial-Up2 modem is used.
NONE : Not used.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ CTS Usage
Range ON, OFF
Default ON Step ~
Set the use [OFF/ON] of CTS sign.
ON : Transmit the sending data after check that the CTS sign is
Assert.
OFF : Transmit the sending data regardless of CTS sign.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ DCD Usage
Range ON, OFF
Default ON Step ~
Set the use [OFF/ON] of DCD sign.
ON : Transmit the sending data after check that the DCD sign is
Desassert.
OFF : Transmit the sending data regardless of DCD sign.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ RTS Usage
Range OFF, ON, AUTO
Default AUTO Step ~
ON : RTS sign of ETR300-R is always ON(Assert).
OFF : RTS sign of ETR300-R is always OFF(Deassert).
AUTO : When request a data transmission to modem the RTS sign
of ETR300 is ON and when finish the transmission the RTS sign of
ETR300 is OFF.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ CTS CheckOut
[PROTF(232)]
>DCD Usage: OFF
>RTS Usage: AUTO
[OFF/ON/AUTO]
[PROTF(232)]
>DCD Usage: OFF
>RTS Usage: AUTO
[OFF/ON]
[PROTF(232)]
>Modem Sel: 4W
>CTS Usage: ON
[OFF/ON]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
68 ENHANCED TECHNOLOGY
Range 1 ~ 255 sec
Default 2 Step 1 sec
Set a waiting time that waits for a modem response on RTS signal
which informs ETR300 is ready to transfer a data. If no response
within a set time, RTU treats CTS Fail and does not transfer a data.
It is available if „CTS Usage‟ setting is ON.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ DCD CheckOut
Range 10 ~ 30000 msec
Default 5000 Step 5 msec
Set a delay time of DCD signal to check modem status before transfer
a RTS signal in 2 wire communication type. If DCD signal is ON after
set time, ETR300 does not transfer a data and treats DCD Fail.
It is available if „DCD Usage‟ setting is ON.
GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ RTS OffDelay
Range 10 ~ 500 msec
Default 50 Step 5 msec
RTS Off Delay Time is a time delay after transfer a data till RTS
signal Off. It is a time delay to prevent a last data loss during a data
transfer.
Generally, RTS Off Delay Time is set for 1 or 2 Byte.
[PROTF(232)]
>CTS CheckOut: 2
>DCD CheckOut: 5000
[10~30000:5ms]
[PROTF(232)]
>CTS CheckOut: 2
>DCD CheckOut: 5000
[1~255:1s]
[PROTF(232)]
DCD CheckOut: 5000
>RTS OffDelay: 50
[10~500:5ms]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 69 ENHANCED TECHNOLOGY
6.3. Event Recorder
Locate the cursor on “3. EVENT RECORDER” in GLOBAL SETTING, press [ENT] button to
move to this menu. In this menu, items related to the wave record are set.
GLOBAL SETTING / EVENT RECORDER / Wave Capture
Range ON, OFF
Default ON Step ~
Set whether to use Wave capture.
GLOBAL SETTING / EVENT RECORDER / Wave S/R
Range 16, 32, 64, 128 sample
Default 64 sample Step ~
If record the wave, select the wave sampling capture.
The recorded wave cycle number is 20cycle per 128 sampling and it is
changeable according to the sampling number.
GLOBAL SETTING / EVENT RECORDER / Wave Pre-Cycle
Range 1 ~ 5 cycle
Default 5 Step 1 cycle
Pre-cycle is to record(capture) a number of wave cycle before fault
pickup occurring.
GLOBAL SETTING / EVENT RECORDER / Wave Post-Cycle
Range 1 ~ 5 cycle
Default 5 Step 1 cycle
Post-cycle is to record(capture) a number of wave cycle after Trip.
GLOBAL SETTING / EVENT RECORDER / Wave Head-Cycle
Range 1 ~ 10 cycle
Default 5 Step 1 cycle
Head-Cycle is to record(capture) a number of wave cycle before Trip.
[EVENT RECORDER]
>Wave Post-Cycle: 5
>Wave Head-Cycle: 5
[1~10:1cycel]
[EVENT RECORDER]
>Wave Pre-Cycle: 5
>Wave Post-Cycle: 5
[1~5:1cycel]
[EVENT RECORDER]
>Wave Pre-Cycle: 5
>Wave Post-Cycle: 5
[1~5:1cycel]
[EVENT RECORDER]
>Wave Capture: OFF
>Wave S/R: 64
[16/32/64/128]
[EVENT RECORDER]
>Wave Capture: OFF
>Wave S/R: 64
[OFF/ON]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
70 ENHANCED TECHNOLOGY
6.4. Monitoring
Locate the cursor on “4. MONITORING” in GLOBAL SETTING, push [ENT] button and move
to this menu.
6.4.1. Operation Count
Locate the cursor on “1. OPERATION COUNT” in MONITORING menu, press [ENT] button
and move to this men. In this menu, set the elements related to Operation Count Monitering of
switch.
GLOBAL SETTING / MONITORING / OPERATION COUNT / Function
Range OFF, ON
Default ON Step ~
Set whether to use Operation Caunt Monitering
GLOBAL SETTING / MONITORING / OPERATION COUNT / Limit
Range 1 ~ 20000
Default 10000 Step 1
Ring the Alarm when Switch operation count (“MAINENANCE/
COUNT/ OPERATION”) reach the setting value.
GLOBAL SETTING / MONITORING / OPERATION COUNT / Count set
Range 0 ~ 65535
Default 0 Step 1
Use to set the same the Operation Count with the main device.
Set value is available after Operation Counter is reset. You can reset
the counter in “MAINENANCE/ DATA RESET / OPERATION
COUNT or COUNT ALL”
[TRIP COUNTER]
Limit: 10000
>Count set: 0
[0~65535:1]
[OPERATION COUNT]
>Function: OFF
>Limit: 10000
[1~20000:1]
[OPERATION COUNT]
>Function: ON
Limit: 10000
[OFF/ON]
[MONITERING]
>1.OPERATION COUNT
2.CONTACT WEAR
3.BATTERY TEST
4.PQM
5.TD MONITOR
6.V0 DETEC
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 71 ENHANCED TECHNOLOGY
6.4.2. Contact Wear
Place the curser on “3. CONTACT WEAR” in MONITORING menu, press [ENT] button to move
into this menu. Switch contact wear and monitoring elements are set in this menu.
GLOBAL SETTING / MONITORING / CONTACT WEAR / Function
Range OFF, ON
Default OFF Step ~
Select whether to use Switch contact wear monitoring.
GLOBAL SETTING / MONITORING / CONTACT WEAR / Pickup(%)
Range 0.0 ~ 50.0 %
Default 20.0 Step 0.1 %
Set a pickup value to alarm when switch contact wear
(“MAINENANCE/ CONTACT WEAR”) reaches set value.
GLOBAL SETTING / MONITORING / CONTACT WEAR / Rated Volt(kV)
Range 15, 27, 38 ㎸
Default 27 ㎸ Step ~
Set Rated Voltage of System.
GLOBAL SETTING / MONITORING / CONTACT WEAR / Interrupt(kA)
Range 5.0 ~ 50.0 kA
Default 12.5 Step 0.1 kA
Set the maximum rated interrupt.
GLOBAL SETTING / MONITORING / CONTACT WEAR / No. Max I
Range 1 ~ 999
Default 100 Step 1
Enter the capacity of rated Interrupter.
GLOBAL SETTING / MONITORING / CONTACT WEAR / A Wear Set
Range 0.00 ~ 100.00 % [CONTACT WEAR]
>A Wear Set: 100.00
>B Wear Set: 100.00
[0.00~100.00:0.01%]
[CONTACT WEAR]
>Function: OFF
>Pickup(%): 20.0
[0.0~50.0:0.1%]
[CONTACT WEAR]
>Function: OFF
Pickup(%): 20.0
[OFF/ON]
[CONTACT WEAR]
Pickup(%): 20.0
>Rated Volt(kV): 38
[15/27/38kV]
[CONTACT WEAR]
Rated Volt(kV): 15
>Interrupt(kA): 12.5
[5.0~50.0:0.1kA]
[CONTACT WEAR]
Interrupt(kA): 12.5
>No. Max I: 100
[1~999:1]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
72 ENHANCED TECHNOLOGY
Default 100.00 Step 0.01%
It is to set Switch phase A contact wear value in ETR300. Set value is
available after Contact Wear Rset. Contact wear reset refers to
“MAINENANCE/ DATA RESET / CONTACT WEAR”.
GLOBAL SETTING / MONITORING / CONTACT WEAR / B Wear Set
Range 0.00 ~ 100.00 %
Default 100.00 Step 0.01%
It is to set Switch phase B contact wear value in ETR300. Set value is
available after Contact Wear Rset. Contact wear reset refers to
“MAINENANCE/ DATA RESET / CONTACT WEAR”.
GLOBAL SETTING / MONITORING / CONTACT WEAR / C Wear Set
Range 0.00 ~ 100.00 %
Default 100.00 Step 0.01%
It is to set Switch phase C contact wear value in ETR300. Set value is
available after Contact Wear Rset. Contact wear reset refers to
“MAINENANCE/ DATA RESET / CONTACT WEAR”.
6.4.3. Battery Test
Locate the cursor on “3. BATTERY TEST” in MONITORING menu, press [ENT] button and
move to this menu.
GLOBAL SETTING / MONITORING / BATTERY TEST / Period
Range 1 ~ 720 hour
Default 24 Step 1 hour
Set the Battery Test Hour Period.
[BATTERY TEST]
>Period: 24
[1~720:1hour]
[CONTACT WEAR]
>B Wear Set: 100.00
>C Wear Set: 100.00
[0.00~100.00:0.01%]
[CONTACT WEAR]
>A Wear Set: 100.00
>B Wear Set: 100.00
[0.00~100.00:0.01%]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 73 ENHANCED TECHNOLOGY
6.4.4. PQM
Locate the cursor on “4. PQM” in MONITERING menu, press [ENT] button and move to this
menu. In this menu, set the elements of PQM and has the following submenu.
6.4.4.1. PQM Function
Locate the cursor on “1. PQM FUNCTION” in PQM Menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / PQM FUNCTION / Function
Range DISABLE, ENABLE
Default DISABLE Step ~
Select [DISABLE/ENABLE] of PQ.
6.4.4.2. Interrupt
Locate the cursor on PQM “2. INTERRUPT” in the menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / INTERRUPT / Level
Range 0(OFF), 0.10 ~ 0.49 pu
Default 0.10 Step 0.01 pu
Set the Interrupt Detect Level of PQ.
Detect Level shall be set in multiple of rated voltage of source side
user.
[PQM]
>1.PQM FUNCTION
2.INTERRUPT
3.SAG
4.SWELL
5.HARMONICS
6.CURR UNBALANCE
7.VOLT UNBALANCE
8.UNDER VOLTAGE
9.OVER VOLTAGE
10.UNDER FREQUENCY
11.UBI/THD MIN.I
[INTERRUPT]
>Level: 0.10
>Time: 2.0
[0(OFF),0.10~0.49pu]
[PQM FUNCTION]
>Function: DISABLE
[DISABLE/ENABLE]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
74 ENHANCED TECHNOLOGY
GLOBAL SETTING / MONITORING / PQM / INTERRUPT / Time
Range 0.5 ~ 10.0 cycle
Default 2.0 Step 0.5 cycle
Set Interrupt Detect Time.
6.4.4.3. Sag
Locate the cursor on “3. SAG” in PQM menu, press [ENT] key and move to this menu.
GLOBAL SETTING / MONITORING / PQM / SAG / Level
Range 0(OFF), 0.50 ~ 0.99 pu
Default 0.80 Step 0.01 pu
Set the Voltage Sag Detect Level of PQ.
Detect Level shall be set in multiple of rated voltage of source side
user.
GLOBAL SETTING / MONITORING / PQM / SAG / Time
Range 0.5 ~ 10.0 cycle
Default 2.0 Step 0.5 cycle
Set Voltage Sag Detect Time.
6.4.4.4. Swell
Locate the cursor on “4. SWELL” in PQM menu, press [ENT] button and move to this menu.
GLOBAL SETTING / MONITORING / PQM / SWELL / Level
Range 0(OFF), 1.01 ~ 1.50 pu
Default 1.20 Step 0.01 pu
Set the Voltage Swell Detect Level of PQ.
Detect Level shall be set in multiple of rated voltage of source side
user..
GLOBAL SETTING / MONITORING / PQM / SWELL / Time
Range 0.5 ~ 10.0 cycle
Default 2.0 Step 0.5 cycle
[SWELL]
>Level: 1.20
>Time: 2.0
[0.5~10.0:0.5cycle]
[SWELL]
>Level: 1.20
>Time: 2.0
[0(OFF),1.01~1.50pu]
[SAG]
>Level: 0.80
>Time: 2.0
[0.5~10.0:0.5cycle]
[SAG]
>Level: 0.80
>Time: 2.0
[0(OFF),0.50~0.99pu]
[INTERRUPT]
>Level: 0.10
>Time: 2.0
[0.5~10.0:0.5cycle]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 75 ENHANCED TECHNOLOGY
Set Voltage Swell Detect Time.
6.4.4.5. Harmonics
Locate the cursor on “5. HARMONICS” in PQM menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / HARMONICS / VTHD Pickup
Range 0(OFF), 0.5 ~ 100.0 %
Default OFF Step 0.1%
Set a detect level of voltage harmonic distortion.
GLOBAL SETTING / MONITORING / PQM / HARMONICS / VTHD Delay
Range 0.2 ~ 60.0 sec
Default 1.0 Step 0.1 sec
Set a detect time to detect voltage harmonic distortion.
GLOBAL SETTING / MONITORING / PQM / HARMONICS / ITHD Pickup
Range 0(OFF), 0.5 ~ 100.0 %
Default OFF Step 0.1%
Set a detect level of current harmonic distortion.
GLOBAL SETTING / MONITORING / PQM / HARMONICS / ITHD Delay
Range 0.2 ~ 60.0 sec
Default 1.0 Step 0.1 sec
Set a detect time to detect current harmonic distortion.
6.4.4.6. Current Unbalance
Locate the cursor on “6. CURR UNBALANCE” in PQM menu, press [ENT] button and move to
this menu.
GLOBAL SETTING / MONITORING / PQM / CURR UNBALANCE / Level
Range 0(OFF), 1 ~ 100 %
Default 30 Step 1 %
[HARMONICS]
>ITHD Pickup: OFF
>ITHD Delay: 1.0
[OFF,0.5~100.0:0.01]
[HARMONICS]
>VTHD Pickup: OFF
>VTHD Delay: 1.0
[OFF,0.5~100.0:0.01]
[CURR UNBALANCE]
>Level: 30
>Time: 1.0
[0(OFF),1~100:1%]
[HARMONICS]
>ITHD Pickup: OFF
>ITHD Delay: 1.0
[0.2~60.0:0.1s]
[HARMONICS]
>VTHD Pickup: OFF
>VTHD Delay: 1.0
[0.2~60.0:0.1s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
76 ENHANCED TECHNOLOGY
Set a detect level of Current Unbalance for Power Quality.
GLOBAL SETTING / MONITORING / PQM / CURR UNBALANCE / Time
Range 0.1 ~ 60.0 sec
Default 1.0 Step 0.1 sec
Set a detect time of current unbalance.
6.4.4.7. Voltage Unbalance
Locate the cursor on “7. VOLT UNBALANCE” in PQM menu, press [ENT] button and move to
this menu.
GLOBAL SETTING / MONITORING / PQM / VOLT UNBALANCE / Level
Range 0(OFF), 1 ~ 100 %
Default 30 Step 1 %
Set Voltage Unbalance Detect Level of PQ.
GLOBAL SETTING / MONITORING / PQM / VOLT UNBALANCE / Time
Range 0.1 ~ 60.0 sec
Default 1.0 Step 0.1 sec
Set Voltage Unbalance Detect Time.
6.4.4.8. Under Voltage
Place the curser on “8. UNDER VOLTAGE” in PQM menu, press [ENT] button to move into this
menu.
GLOBAL SETTING / MONITORING / PQM / UNDER VOLTAGE / Level
Range 0(OFF), 0.30 ~ 0.95 pu
Default 0.80 Step 0.01 pu
Set Under Voltage Detect Level of PQ.
Detect Level shall be set in multiple of rated voltage of source side
user..
GLOBAL SETTING / MONITORING / PQM / UNDER VOLTAGE / Time
Range 0.0 ~ 180.0 sec [UNDER VOLTAGE]
>Level: 0.80
>Time: 60.0
[0.0~180.0:0.1s]
[UNDER VOLTAGE]
>Level: 0.80
>Time: 60.0
[0(OFF),0.30~0.95pu]
[VOLT UNBALANCE]
>Level: 30
>Time: 1.0
[0.1~60.0:0.1s]
[VOLT UNBALANCE]
>Level: 30
>Time: 1.0
[0(OFF),1~100:1%]
[CURR UNBALANCE]
>Level: 30
>Time: 1.0
[0.1~60.0:0.1s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 77 ENHANCED TECHNOLOGY
Default 60.0 Step 0.1 sec
Set Under Voltage Detect Time.
6.4.4.9. Over Voltage
Locate the cursor on “9. OVER VOLTAGE” in PQM menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / OVER VOLTAGE / Level
Range 0(OFF), 1.05 ~ 1.50 pu
Default 1.20 Step 0.01 pu
Set Over Voltage Detect Level of PQ.
Detect Level shall be set in multiple of rated voltage of source side
user.
GLOBAL SETTING / MONITORING / PQM / OVER VOLTAGE / Time
Range 0.0 ~ 180.0 sec
Default 60.0 Step 0.1 sec
Set Over Voltage Detect Time.
6.4.4.10. Under Frequency
Locate the cursor on “10. UNDER FREQUENCY” in PQM menu, press [ENT] button and move
to this menu.
GLOBAL SETTING / MONITORING / PQM / UNDER FREQUENCY / Level
Range 0(OFF), 46.00 ~ 59.98 Hz
Default 59.50 Step 0.01 Hz
Set Under Frequency Detect Level of PQ..
GLOBAL SETTING / MONITORING / PQM / UNDER FREQUENCY / Time
Range 0.03 ~ 10.00 sec
Default 0.10 Step 0.01 sec
Set Under Frequency Detect Time.
[UNDER FREQUENCY]
>Level: 59.50
>Time: 0.10
[0.03~10.00:0.01s]
[UNDER FREQUENCY]
>Level: 59.50
>Time: 0.10
0(OFF),46.00~59.98Hz
[OVER VOLTAGE]
>Level: 1.20
>Time: 60.0
[0.0~180.0:0.1s]
[OVER VOLTAGE]
>Level: 1.20
>Time: 60.0
[0(OFF),1.05~1.50pu]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
78 ENHANCED TECHNOLOGY
6.4.4.11. Current Unbalance/THD Detect Limit
Locate the cursor on “11. UBI/THD MIN.” in PQM menu, select [ENT] button and move to this
menu.
GLOBAL SETTING / MONITORING / PQM / UBI/THD MIN. / Min. I
Range 0 ~ 630 A
Default 60 Step 1A
Set in minimum current to detect the Current Unbalance and THD.
6.4.5. TD MONITOR
Locate the cursor on “5. TD Monitor” in MONITERING menu, press [ENT] button and move to
this menu.
. In this menu, set operation elements of transducer which can be used for the moditoring of DC
analog input.
It has 5 channels of transducer, each transducer has 2 pickup setting values to detects the
signal size of input, monitoring in 2 levels the input sinal which is over than pickup setting
value and give the alarm.
The no. 1 and 2 transducer can detect the battery and charger status by receiving the battery
voltage and charge section voltage in input signal and sending to the controller.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Rate
Range 20, 200
Default 20 Step -
Enter TD1 monitoring rate.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Ratio
Range 1 ~ 3000
Default 1 Step 1
Enter TD1 ratio.
[UBI/THD MIN.I]
>Min. I: 60
[0~630:1A]
[TD MONITOR]
>TD1 Rate: 20
>TD1 Ratio: 1
[1~3000:1]
[TD MONITOR]
>TD1 Rate: 20
>TD1 Ratio: 1
[20/200]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 79 ENHANCED TECHNOLOGY
GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Offset
Range -10000 ~ +10000
Default 0 Step 1
Enter TD1 off set.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 Type
Range UNDER, OVER
Default UNDER Step ~
Set the 1st monitoring type of TD1.
UNDER is set to give the alarm when input value is reduced under
pickup setting value, OVER is to give the alarm when input value is
increased over pickup setting value.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 PU(V)
Range 0(OFF), 1.0 ~ 35.0 V
Default OFF Step 0.1V
Set the 1st Pickup value of TD1.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 Delay
Range 0.01 ~ 600.00 sec
Default 2.00 Step 0.01 sec
Set the 1st Delay time of TD1.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 Type
Range UNDER, OVER
Default UNDER Step ~
Set the 2nd
monitoring type of TD1
GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 PU
Range 0(OFF), 1.0 ~ 35.0 V
Default OFF Step 0.1V
[TD MONITOR]
>TD1-1 PU(V): OFF
>TD1-1 Delay: 2.00
[OFF,1.0~35.0:0.1V]
[TD MONITOR]
>TD1-2 Type: UNDER
>TD1-2 PU(V): OFF
[UNDER/OVER]
[TD MONITOR]
>TD1-1 PU(V): OFF
>TD1-1 Delay: 2.00
[0.01~600.00:0.01s]
[TD MONITOR]
>TD1-1 Type: UNDER
>TD1-1 PU: OFF
[UNDER/OVER]
[TD MONITOR]
>TD1 Ratio: 1
>TD1 Offset: +0
[-10000 ~ +10000:1]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
80 ENHANCED TECHNOLOGY
Set the 2nd
Pickup value of TD1.
GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 Delay
Range 0.01 ~ 600.00 sec
Default 2.00 Step 0.01 sec
Set the 2nd
Delay time of TD1.
※. NOTE : TD2 ~ TD5 have the same setting items with TD1.
6.4.6. V0 Detect
Locate the cursor on “6. V0 DETECT” in MONITERING menu, press [ENT] button and move to
this menu. In this menu, set the Zero Voltage detection.
GLOBAL SETTING / MONITORING / PQM / V0 DETECT / Detect Level
Range 0(OFF), 0.05 ~ 1.20 pu
Default OFF Step 0.01 pu
Set V0 Detect Level.
GLOBAL SETTING / MONITORING / V0 DETECT / Detect Time
Range 0.1 ~ 6000.0 sec
Default 1.0 Step 0.1 sec
Set V0 Detect Time.
[TD MONITOR]
>TD1-2 PU(V): OFF
>TD1-2 Delay: 2.00
[OFF,1.0~35.0:0.1V]
[V0 DETECT]
>Detect Level: OFF
>Detect Time: 1.0
[0.1~6000.0:0.1s]
[V0 DETECT]
>Detect Level: OFF
>Detect Time: 1.0
[0(OFF),0.05~1.20pu]
[TD MONITOR]
>TD1-2 PU: OFF
>TD1-2 Delay: 2.00
[0.01~600.00:0.01s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 81 ENHANCED TECHNOLOGY
6.5. PLC
Locate the cursor on “5. PLC” in GLOBAL SETTING menu, press[ENT] button and move to this
menu.
6.5.1. COMMON
Locate the cursor on “1. COMMON” in PLC menu, press [ENT] button amd move to this menu.
6.5.1.1. Logic Timer
Locate the cursor on “1. LOGIC TIMER” in COMMON menu, press [ENT] button amd move to
this menu.
There are 16 logictimer inside the PLC.
When occurs input A in logictimer, output B becomes 1 after time X and when input A
disappears output B becomes 0 after time Y. Refer to “Ficture 5-1. Logic Timer symbol”.
X is Pick up time and Y is Dropout time.
In PLC, enter A in user logic TMI□.
In PLC, B is output in TMO□.
A
0s/0s
TM□
BY
X
Ficture 6-1. Logic Timer Symbol
[OMMON]
>1.LOGIC TIMER
2.PULSE TIMER
3.PULSE COUNTER
[PLC]
>1.COMMON
2.DI/DO
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
82 ENHANCED TECHNOLOGY
GLOBAL SETTING / PLC / COMMON / LOGIC TIMER / TM1-PU
Range 0.01 ~ 600.00 sec
Default 0.01 Step 0.01 sec
Set Pickup Time of logic timer 1.
GLOBAL SETTING / PLC / COMMON / LOGIC TIMER / TM1-DO
Range 0.01 ~ 600.00 sec
Default 0.01 Step 0.01 sec
Set Dropout Time of logic timer 1.
※. NOTE : The setting of TM2 ~ TM16 are same with TM1.
6.5.1.2. Pulse Timer
Locate the cursor on “2. PULSE TIMER” in COMMON menu, press [ENT] button and move to
this menu.
There are 16 pulse timer inside the PLC
When input A becomes 1 in pulse timer, output B becomes 1 and it output during Y time.
Refer to “Figure 5-2. Pulse Timer symbol”.
In PLC, enter A in user logic PTMI□.
In PLC, B is output in PTMO□.
BAY
0s
PTM□
Ficture 6-2. Pulse Timer Symbol
GLOBAL SETTING / PLC / COMMON / PULSE TIMER / PTM1
Range 0.01 ~ 600.00 sec
Default 0.01 Step 0.01 sec
Set output time of Pulse Timer 1.
※. NOTE : Setting of TM2 ~ PTM16 is same with PTM1.
[PULSE TIMER]
>PTM1 : 0.01
PTM2 : 0.01
[0.01~600.00:0.01s]
[LOGIC TIMER]
>TM1-PU: 0.01
>TM1-DO: 0.01
[0.01~600.00:0.01s]
[LOGIC TIMER]
>TM1-PU: 0.01
TM1-DO: 0.01
[0.01~600.00:0.01s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 83 ENHANCED TECHNOLOGY
6.5.1.3.Pulse Counter
Locate the cursor on “3. PULSE COUNTER” in COMMON menu, press [ENT] button and move
to this menu.
There are 16 Pulse Counter in PLC.
When input B is 0 and input A becomes 1 it increases once and output C becomes 1 when it is
over setting number X. When input B becomes 1 output C becomes 0 and the increased count
becomes 0. Refer to “Figure 5-3. Pulse Counter symbol”
In PLC, enter A in user logic PCI□.
In PLC, enter B in user logic PCR□.
In PLC, C is output in PCO□.
A
B
0
PC□
QR
XC
Ficture 6-3. Pulse Counter Symbol
GLOBAL SETTING / PLC / COMMON / PULSE COUNTER / PC1
Range 1 ~ 60000
Default 1000 Step 1
Set the utput value(X) of Pulse Counter(PC1).
※. NOTE : The setting item of PC2 ~ PC16 is same with PC1.
[PULSE TIMER]
>PC1 : 1000
PC2 : 1000
[1~60000:1]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
84 ENHANCED TECHNOLOGY
6.5.2. DI/DO
Locate the cursor on “2. DI/DO” in PLC menu, press [ENT] button and move to this menu.
6.5.2.1. Input Debounce Timer
Locate the cursor on “1. INPUT DEBOUNCE ” in DI/DO menu, press [ENT] button and move to
this menu.
Input Debounce Timer is provided individually in Control Input.
Input Debounce Timer st the time to eliminate the Chattering of INPUT signal.
When input A becomes 1 in Input Debounce Timer output B becomes 1 after X time and
when input A disappears output B becomes 0 after X time. Refer to “Figure 5-4. Input
Debounce Timer symbol”.
In PLC, A is IN01~IN□ of Control Input and B is output in IN□.
A
0s
X
X
IN□
B
Ficture 6-4. Input Debounce Timer Symbol
GLOBAL SETTING / PLC / DI/DO / INPUT DEBOUNCE / IN101
Range 0.005 ~ 10.000 sec
Default 0.020 Step 0.001 sec
Set Input Debounce time of IN101.
※. NOTE : Setting items of IN102 ~ IN108 and IN201 ~ IN208 are same with IN101.
[INPUT DEBOUNCE]
>IN101 : 0.020
IN102 : 0.020
0.005~10.000:0.001s
[DI/DO]
>1.INPUT DEBOUNCE
2.OUTPUT PULSE TIME
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 85 ENHANCED TECHNOLOGY
6.5.2.2. Output Pulse Timer
Locate the cursor on “2. OUTPUT PULSE TIME” in DI/DO menu, press [ENT] button and move
to this menu.
Output Pulse Timer is provided individually in Control Output.
When input B is 0 in Output Pulse Timer, output C becomes 1 according to the input A. When
input A becomes 1output C becomes 1 during Y time. But if set the Y time in 0, they react at
the same time according to input A. When A is 1 C becomes 1 and when A is 0 C becomes 0, it
is Buffer. Refer to“Figure 5-5. Output Pulse Timer symbol” .
In PLC, enter A in user logic OUT□.
In PLC, enter B in user logic BKOUT□.
In PLC, C is output in OUT□ and this output runs RELAY.
A
B
0s
RY C
OUT□
Ficture 6-5. Output Pulse Timer Symbol
GLOBAL SETTING / PLC / DI/DO / OUTPUT PULSE TIME / OUT101
Range 0(BUFF), 0.01 ~ 100.00 sec
Default 0.01 Step 0.01 sec
Set Output Pulse Time of OUT101.
※. NOTE : The setting item of OUT102 ~ OUT 108 and OUT201 ~ OUT208 are same with OUT101.
[OUTPUT PULSE TIME]
>OUT101 : 0.01
OUT102 : 0.01
0(BUFF),0.01~100.00s
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
86 ENHANCED TECHNOLOGY
6.6. Other setting items
Locate the cursor on “7. OTHERS” in GLOBAL SETTING menu, press [ENT] button and move
to this menu.
6.6.1. F.I TEST
ETR 300 has F.I Test in LCD menu to test the fault detect element and normal operation of fault
count. F.I Test function are same as the following.
(1) Basic Operation of F.I Test
Select which phase among A,B,C,N will be produced F.I (plural selection is possible)
After starting FI Test, produces F.I regardless of Pickup Current of Group Setting Menu.
For F.I Test, Sequence is set in the range of 1~3.
F.I Test is Disable when all A,B,C,N phase are OFF or Sequence is 0.
Produce 1000A Fault current for 10 cycle as the setting number. Eacg Sequence interval is 2
second.
After 2 seconds of FI test, temporary fault is generated.
When do the FI test, fault indication lamp of the front panel is lighted and send related
information to the main device without saving as internal event or increasing fault count.
Fault Current Transmission send the faul current to Event according to Fault I Report setting.
At this time, phase that has not done the FI test indicates present load current value.
After the test, fault indication (front panel lamo and BI point) is maintained until FI Reset.
When do the FI test in the status that fault indication is remained, cancel the prior fault
indication and shows “FI information”
(2) FI Setting Value Storage
Selected phase for F.I Test Target and Setting Value for F.I Test Sequence are saved at the started
time of F.I Test.
(3) Setting Basic Value
F.I Test initial value is sames as the following.
[OTHERS]
>1.F.I TEST
2.FACTORY DEBUG
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 87 ENHANCED TECHNOLOGY
Targer : A,B,C,N all ON
Sequence : 3
(4) End of F.I Test
When F.I test starts, consider as “F.I test mode” the simulated fault current (1000A) permission,
F.I logic performance as much as the sequence setting and LED lighting after F.I set. End the test
mode after finishing these process.
FI Test Start
1000A
(10cycle)
1000A
(10cycle)
1000A
(10cycle)
1000A
(10cycle)
1000A
(10cycle)
1000A
(10cycle)
2sec
2sec 2sec
2sec 2sec 2sec
Fault Detect
Case: Sequence
Setting 1
Temporary
Fault Detected
Fault Detect Fault DetectTemporary
Fault Detected
Case: Sequence
Setting 2
FI Test Start
FI Test Start
Case: Sequence
Setting 3
Fault Detect Fault Detect Fault DetectTemporary
Fault Detected
Ficture 6-6. F.I Test according to Sequence Setting
Locate the cursor on “1. F.I TEST” in OTHERS menu, press [ENT] button and move to this menu.
In this menu, set the FI occur phase for the F.I mock test,and Sequence number.
[F.I TEST]
>1.F.I TEST TARGET
2.F.I TEST SEQ.
3.F.I TEST START
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
88 ENHANCED TECHNOLOGY
6.6.1.1. F.I TEST TARGET
Locate the cursor on “1. F.I TEST TARGET” in F.I TEST menu, press [ENT] button and move to
this menu. In this menu, set the target phasefor the occurance of F.I.
GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST TARGET / IA TEST
Range OFF, ON
Default ON Step -
When select ON, F.I occurs in A phase.
※. NOTE : Setting of IB TEST, IC TEST and IN TEST ar same with IA TEST.
6.6.1.2.F.I TEST SEQUENCE
Locate the cursor on “2. F.I TEST SEQ.” in F.I TEST menu, press [ENT] button and move to this
menu.
GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST SEQUENCE / SEQ. COUNT
Range DISABLE, 1 ~ 3
Default 3 Step 1
Set F.I Sequence.
6.6.1.3.F.I TEST START
Locate the cursor on “3. F.I TEST START” in F.I TEST menu, press [ENT] button and move to
this menu.
GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST SEQUENCE / F.I TEST START
Press [ENT] button if wants to Start the F.I test.
6.6.2. Factory Debug
This menu is for Manufacturer‟s maintenance purpose.
*F.I TEST START*
PRESS <ENT> TO START
[F.I TEST SEQUENCE]
>SEQ. COUNT: 3
>
[DISABLE,1~3:1]
[F.I TEST TARGET]
>IA TEST: ON
>IB TEST: ON
[OFF/ON]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 89 ENHANCED TECHNOLOGY
7. Group Setting Locate the cursor on “2.GROUP SETTING” in main menu, press [ENT] button and move to this
menu. In this menu, set line operating items.
Ficture 7-1. PRIMARY and ALTERNATE group
GROUP SETTING menu is divided in PRIMARY group and ALTERNATE group for the
convenience of user and it is applied according to the ON/OFF of „ALTERNATE SETTINGS
Lamp‟. When „ALTERNATE SETTINGS Lamp” is OFF, PRIMARY group setting is applied
and when „ALTERNATE SETTINGS Lamp‟ is ON, ALTERNATE group setting is applied.
The submenu of PRIMARY group and ALTERNATE group are same, as the following.
NOTE : Changed setting value are available only when they are saved.
Setting value can be saved by „Setting value save massage‟ indicated when depart to “*.
Setting Save” menu or topmenu.
[PRIMARY SETTING]
>1.PICKUP CURRENT
2.COLD LOAD PICKUP
3.DIRECTION
4.F.I SETTING TIME
5.F.I RESET
6.SECTION
7.PHASE DIFF
8.ON/OFF LEVEL
9.OVER CURRNET
*.SAVE SETTING
[GROUP SETTING]
>1.PRIMARY
2.ALTERNATE
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
90 ENHANCED TECHNOLOGY
7.1. Fault pickup element
When occurs a fault in line, ETR300 detects and indicates the fault of each phase (A, B, C, N,
SEF). The fault type are permanent and temporary.
(1) Permanent FI Detect
It is used for the permanent FI detection of distribution line and it operates according to following
condition.
Permanent FI
TemporaryFI SETTING TIME
PermanentFI SETTING TIME
Temporary FI
Pickup Level
Voltage
Current
CLEAR
Permanent Fault
FI SETAUTORESET
Ficture 7-2. Permanent FI Detection(1)
Occurrence Condition
FI information is set when becomes dead line status after fault current over the minim. pickup
current flowed in Hot line status, and set the fault type in FI if dead line status is maintained
during setting time (permanent FI Set Time, 1sec~180sec possible to change, Default: 20 second).
But, when returns to Hot line status by reclosing before the permanent FI Set Time, FI Set Time is
initialized and returned to the first permanent FI occurrence condition.
Cancel Condition
If normal current is detected in hot line status after the permanent FI, permanent FI is cancelled
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 91 ENHANCED TECHNOLOGY
automatically at the time that passed the permanent FI Set Time. Before the automatic FI cancel, it
can be cancelled by Fault Indicator Reset button or remote FI reset control. But, Reset order is not
working before the end of fault judgement after fault detection.
A,N B,N
0.6s 2s
①FI(A, N)
Fault Current(A,B,C,N,SEF)
③
FI(B)
⑤Fault Permanent
②
15s
④
A,N B,N
Permanent Fault
Detect Time
Pickup Level
Normal Current
Ficture 7-3. Permanent Fault Detection PickupOperation(2)
Fault is experienced in normal stats and FI is occurred in no voltage status (①②③④ time :
additional occurrence phase update
Fault Current Size is maximum RMS from the fault detection to no voltage and Event time is
no-voltage detect time.
※ Fault Current Event is occurred at the first fault(When Fault 'I' Report Evnet setting is
1Shot)
Additional FI is not set when fault has been detected in the same phaset during Sequence
operation(②④t). When detects fault of other phase during Sequence, FI is set. (③)
After finishing Sequence (Permanent Fault Judge time), “Permanent Fault Set” is sent to main
device(⑤)
“Permanent FI set” and “FI set” is cancelled after “FI Reset” order or Temporary FI judge
time after normal line reset.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
92 ENHANCED TECHNOLOGY
(2) Temporary FI Detection
It is used for Temporary fault monitoring of distribution line and operates based on the following
condition.
Temporary Fault
CLEAR
FI SET
Permanant FI
Temporary FI SETTING TIME
PermanantFI SETTING TIME
Temporary FI
Pickup Level
Voltage
Current
Ficture 7-4. Temporary Fault Detect Operation(1)
Set Condition
Temporary Fault set FI information when becomes dead line status after flowed fault current over
minimum pickup current. Temporary FI is set when pass the setting time (Temporary FI Set Time,
1sec~180sec possible to change, Default:2sec) after reset to nomal current from hot line status by
reclosing in source side.
Cancel Condition
FI and Fault Type(Temporary) are cleared only in FI Reset case. If FI is set again before the reset
status, delete prior FI and indicates the latest FI. Handle the existing FI Clear time at first than
new FI Set time
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 93 ENHANCED TECHNOLOGY
Pickup Level
Normal Current
A,N B,N
0.6s 2s
①FI(A, N)
Fault Current(A,B,C,N,SEF)
② FI(B)
③Fault Temporary
Temporary Fault
Detect Time
Ficture 7-5. Temporary Fault Detect Operation( (2)
Fault is experienced in normal stats and FI is occurred in no voltage status (①② time :
additional occurrence phase update
Fault Current Size is maximum RMS from the fault detection to no voltage and Event time is
no-voltage detect time.
※ Fault Current Event is occurred at the first fault(When Fault 'I' Report Evnet setting is
1Shot)
Additional FI is not set when fault has detected in the same phase during Sequence operation.
When detects fault of other phase during Sequence, FI is set(②)
After normal line reset, send :Temporary Fault Set” information to main device when pass
Temporary FI judge time) (③)
When order “FI Reset", “Temporary FI Set” and “FISet” information is cancelled.
Fault Detect element setting items are same as following.
7.1.1. Pickup Current Setting
Move to “GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT” menu to set
Pickup Current.
GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / Phase
Range 0(OFF), 50 ~ 630A
Default 400 Step 5A
[PICKUP CURRENT]
>Phase: 400
Ground: 70
[OFF,50~630:5A]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
94 ENHANCED TECHNOLOGY
Set Pickup Current of phase.
GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / Ground
Range 0(OFF), 25 ~ 315A
Default 70 Step 5A
Set Pickup Current of ground.
GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / SEF
Range 0(OFF), 0.1 ~ 10.0A
Default 0.2 Step 0.1A
Set Pickup Current of SEF.
7.1.2. F.I Detect Time Setting
Move to “GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME” menu to set
F.I Detect Time Setting.
GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME / Permanent
Range 1 ~ 180sec
Default 20 Step 1sec
It is Delay time for Permanent Fault Detection.
GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME / Temporary
Range 1 ~ 180sec
Default 20 Step 1sec
It is Delay time for Temporary Fault Detection.
[F.I SETTING TIME]
>Permanent : 20
>Temporary : 2
[1~180:1s]
[F.I SETTING TIME]
>Permanent : 20
>Temporary : 2
[1~180:1s]
[PICKUP CURRENT]
>Ground: 70
>SEF: 0.2
[OFF,0.1~10.0:0.1A]
[PICKUP CURRENT]
>Phase: 400
>Ground: 70
[OFF,25~315:5A]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 95 ENHANCED TECHNOLOGY
7.2. Inrush Current Restraint Function
ETR300 has restraint function to prevent the malfunction by inrush current, occurred by switch
closing by reclosing and local and remote after fault occurance. Inrush current restraint function
can be corrected in phase, ground and SEF.
Inrush current restraint function is applied when both Source side and Load side becomes hot
status from dead status or when close the switch. When transient current is over CLPU Pickup
level as Inrush current 1, fault pickup element operates normally instead of inrush current restraint
function. If it is under CLPU Pickup level as Inrushc current 2, restraint during RMT time and
operates the normal fault pickup element. But, if it is under Pickup current as Inrush current 3,
inrush current restraint function is cancelled after Reset time.
Time
Current
Overcurrent
CLPU
Pickup Level
Pickup Level
Trip
Outage time Restore Minimum Time
Trip
Inrush current 1
Inrush current 2
Inrush current 3
Ficture 7-6. Cold Load Pickup Characteristic
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
96 ENHANCED TECHNOLOGY
Move to “GROUP SETTING / PRIMARY or ALTERNATE / Cold Load Pickup” menu to set
Inrush Current Restraint Function.
GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / PHA(xCT)
Range 1 ~ 20 xMTC
Default 4 Step 1 xMTC
It is Phase Inrush Current Retraint multiple, this setting point is
multiple of Pickup Current(Phase)
GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / GND(xCT)
Range 1 ~ 20 xMTC
Default 4 Step 1 xMTC
It is Ground Inrush Current Retraint multiple, this setting point is
multiple of Pickup Current(Ground)
GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / SEF(xCT)
Range 1 ~ 20 xMTC
Default 4 Step 1 xMTC
It is SEF Inrush Current Retraint multiple, this setting point is multiple
of Pickup Current(SEF)
GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / RMT Time-PHA
Range 0.0 ~ 180.0 sec
Default 0.2 Step 0.1 sec
Set Reset time of Pickup Current (Phase).
When passes the setting time the inrush current restraint algorithm is
cancelled and operates normal phase fault pickup element, when
source side and load side becomes hot status from dead status or after
switch closing. (Pickup level resets tofault pickup current in Cold load
pickup level.)
※. NOTE : The setting item of RMT Time-GND and RMT Time-SEF are same with RMT Time-
PHA setting.
[ COLD LOAD PICKUP ]
>PHA(xMTC): 4
>GND(xMTC): 4
[1~20: 1xMTC]
[ COLD LOAD PICKUP ]
>RMT Time-PHA: 0.2
>RMT Time-GND: 0.2
[0.0~180.0:0.1s]
[ COLD LOAD PICKUP ]
>PHA(xMTC): 4
>GND(xMTC): 4
[1~20: 1xMTC]
[ COLD LOAD PICKUP ]
>GND(xMTC): 4
>SEF(xMTC): 4
[1~20: 1xMTC]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 97 ENHANCED TECHNOLOGY
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
98 ENHANCED TECHNOLOGY
7.3. Directional Detection Function
When detect fault, ETR300 distinguish fault current direction and indicates the fault direction in
fault events. Directional Detection setting is composed of Phase, Ground, and SEF elements.
7.3.1. Phase Directional Detection
The direction distinction of phase fault current use normal voltage (V1) and normal current(I1) of
symmetry, and operation are as following.
Distinguish in Forward if I1 pahse about V1 is within ±90° according M.T.A basis and if not
in Reverse.
When fault is occurred in Voltage Metering nearby V1 value can be lost. In this case, use the
saved V1 and performs the directional detection
To operates in direction, V1 detected in fault status shall be bigger than min. polarizing
voltage. If V1 is smaller than this setting value does not detect direction, even the fault current
is over the minimum pickup current
RE
VE
RS
E
FO
RW
OR
D
V1
M.T.A= 60° LagI1
Zero
Torq
ue L
ine
Maximum Torque Line
Typical Fault Angle
Polarizing Referance
Voltage:
Ficture 7-7. Phase directional detection element characteristic
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 99 ENHANCED TECHNOLOGY
Move to “GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE” menu to
set Phase Directional Detection Element.
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / Function
Range DISABLE, ENABLE
Default DISABLE Step -
Set [DISABLE/ENABLE] of Directional Detection, when occurs
phase fault.
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / M.T.A
Range 0 ~ 345˚
Default 60 Step 15˚
Set Maximum Torque Angle of normal current (I1) about normal
voltage (V1), when occurs phase fault.
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / M.P.V
Range 0(NONE), 10~80 %
Default 30 Step 1%
Set Minimum Polarizing Voltage about normal voltage(V1) to
distinguish the direction.
If is under normal voltage(V1), it does not distinguish the direction.
[PHASE]
>Function: DISABLE
>M.T.A: 60
[DISABLE/ENABLE]
[PHASE]
>M.T.A: 60
>M.P.V: 30
[0~345:1deg]
[PHASE]
M.T.A: 300
>M.P.V: 30
[NONE,10~80:1%]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
100 ENHANCED TECHNOLOGY
7.3.2. Ground and SEF Directional Detection
Directional Detection of Ground and SEF fault current use Zero Seq. Voltage(V0) and Zero Seq.
Current(I0).
REVERSE
FORW
ORD
-V0
M.T.A= 45° Lag
InZero Torque Line
Max
imum
Tor
que
Line
Typical Fault Angle
Polarizing Referance
Voltage:
V0
Ficture 7-8. Ground and SEF Directional Detection element characteristic
IF phase angle of I0 about –V0 is within ±90° based on Max. Torque Angle is Forword, if not
is Reverse.
To operates in direction, V0 detected in fault status shall be biggenr than min. polarizing
voltage. If V0 is smaller than each element setting does not detect direction, even fault current
and SEF are over min. pickup current setting value.
Move to “GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND” menu
to set Groud Directional Detection Element.
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / Function
Range DISABLE, ENABLE
Default DISABLE Step -
Set [DISABLE/ENABLE] of directional detection, when occurs a
ground fault.
[PHASE]
>Function: DISABLE
>M.T.A: 60
[DISABLE/ENABLE]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 101 ENHANCED TECHNOLOGY
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND / M.T.A
Range 0 ~ 345˚
Default 60 Step 15˚
Set Maximum Torque Angle of zero current (I0) about zero
voltage(V0).
GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND / M.P.V
Range 0(NONE), 10 ~ 80%
Default 30 Step 1%
Set Minimum Polarizing Voltage about zero voltage (V0) to
distinguish the direction.
If is zero voltage (V0), it does not distinguish the direction.
※. NOTE : Move to “GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / SEF”
to set SEF Directional Detection element, and the SEF directional setting items are
same with phase direction setting item.
[GROUND]
>M.T.A: 60
>M.P.V: 30
[0~345:15deg]
[GROUND]
M.T.A: 60
>M.P.V: 30
[NONE,10~80:1%]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
102 ENHANCED TECHNOLOGY
7.4. SECTION
Locate the cursor on “6. SECTION” in PRIMARY or ALTERNATE menu, push [ENT] button
and move to this menu. Submenu is same as following.
7.4.1. SECTION FUNCTION
Locate the cursor on “1. FUNCTION” in SECTION menu, push [ENT] button and move to this
menu. Submenu is same as following. In this menu, set the use of Section Function and Section
Type.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Function
Range DISABLE, ENABLE
Default DISABLE Step -
Set [DISABLE/ENABLE] of Section Function.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Auto Close
Range DISABLE, ENABLE
Default DISABLE Step -
DISABLE : Auto opening is possible but auto closing is restraint.
ENABLE : Auto closing is possible by section reclosing function.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Section Type
Range V-T, O-T
Default V-T Step -
V-T : Operates in V-T mode(Section).
O-T : Operates in O-T mode(Tie).
[SECTION FUNCTION]
>Section Type: V-T
>Close Dir: ALWAYS
[V-T/O-T]
[SECTION FUNCTION]
>Function: DISABLE
>Auto Close: DISABLE
[DISABLE/ENABLE]
[SECTION FUNCTION]
>Function: DISABLE
>Auto Close:DISABLE
[DISABLE/ENABLE]
[SECTION]
1.FUNCTION
2.TIME
3.OPERATION COUNT
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 103 ENHANCED TECHNOLOGY
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Close Direction
Range ALWAYS, SOURCE, LOAD
Default ALWAYS Step -
Set the voltage side applided in section function closing. Switch
operates by judging the voltage of selected side.
ALWAYS : Close by judging source side or load side voltage.
SOURCE : Close by judging source side voltage.
LOAD : Close by judging load side voltage.
7.4.2. SECTION TIME
Locate the cursor on “2. TIME” in SECTION menu, select [ENT] button and move to this menu.
In this menu, set time elements related to section function.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Open Delay
Range 0.1 ~ 25.5 sec
Default 3.0 Step 0.1 sec
Set Open Delay time. It is delay time to order an opening, when
detects fault in V-T mode and became no-voltage.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Close Wait
Range 1 ~ 255 sec
Default 17 Step 1 sec
Set Close Wait Time.
After opening by section on V-T mode, if it does not became hot
during Closing wait time Lockout.
But, it is only available when Autp Close setting is ENABLE status. In
other words, if Auto Close Setting is DISABLE status, it Lockout at
the sime time of opening by section function.
[SECTION TIME]
>Open Delay: 3.0
>Close Wait: 17
[1~255:1s]
[SECTION TIME]
>Open Delay: 3.0
>Close Wait: 17
[0.1~25.5:0.1s]
[SECTION FUNCTION]
>Section Type: V-T
>Close Dir: ALWAYS
[ALWAYS/SOURCE/LOAD]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
104 ENHANCED TECHNOLOGY
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Close Delay
Range 1 ~ 255 sec
Default 2 Step 1 sec
Set Close Delay Time.
It is delay time to order closing when becomes hot status before
Lockout after the opening by section in V-T mode.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Lockout
Range 1 ~ 255 sec
Default 1 Step 1 sec
Close by section in V-T mode, If there isn‟t a fault during Lockout
time Lockout in close status. If becomes no voltage by experience a
fault within Lockout time, Lockout the close after close delay.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Source Lockout
Range 1 ~ 255 sec
Default 4 Step 1 sec
Set Lockout Time of Source Side.
In normal condition(Live line), if Dead voltage is detected and it goes
in O-T(Outage Time) and within this O-T time, Live line comes back,
then, Source Lock time is applied and during this srouce locktime, if
Live line keeps last, it goes back to Home, however, During Source
Lock Time, if Deadline comes back again, automatically it does
Lockout
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Source Lockout
Range 1 ~ 255 sec
Default 4 Step 1 sec
Set Reset Time of Source Side.
In O-T mode, under automatic Lockout condition, if Live line is
detected, Source reset time is started and if the live line keeps last
until Source reset time, Lock is released.
[SECTION TIME]
>Source Lock: 4
>Source Reset: 4
[1~255:1s]
[SECTION TIME]
>Source Lock: 4
>Source Reset: 4
[1~255:1s]
[SECTION TIME]
>Close Delay: 2
>Lockout: 1
[1~255:1s]
[SECTION TIME]
>Close Delay: 2
>Lockout: 1
[1~255:1s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 105 ENHANCED TECHNOLOGY
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Resetraint
Range 1 ~ 255 sec
Default 60 Step 1 sec
In O-T mode, close after pass the Open Delay Time + Restraint Time
+ Close Time if becomes Dead line in Hot line status .
7.4.3. OPERATION COUNT
Locate the cursor on “3. OPERATION COUNT” in SECTION menu, press [ENT] button and
move to this menu. This menu set the use of section function and section type.
GROUP SETTING / PRIMARY or ALTERNATE / SECTION / OPERATION COUNT / Count
Range 1 ~ 4
Default 2 Step 1
Set operation count of section function.
[OPERATION COUNT]
>Count: 2
>
[1~4:1]
[SECTION TIME]
>Source Reset: 4
>Resetraint: 60
[1~255:1s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
106 ENHANCED TECHNOLOGY
7.5. Phase angle unbalance
Locate the cursor on “7. PHASE DIFF” in PRIMARY or ALTERNATE menu, press [ENT] button
and move into this menu. In this menu, set phase angle difference elements.
Compare the phase of source side and phase of load side, in hot line status and open condition. It
is Phase angle inconsistency of is over set angle and normal if is under the set angle. But, phase
angle difference is not detected when source side or load side circuit is dead line.
GROUP SETTING / PRIMARY or ALTERNATE / PHASE DIFF / Level
Range 0(OFF), 5 ~ 80˚
Default 30 Step 5˚
Set phase angle difference.
GROUP SETTING / PRIMARY or ALTERNATE / PHASE DIFF / Time
Range 0.0 ~ 180.0sec
Default 4.0 Step 0.1sec
Set delay time of phase angle difference element.
7.6. Phase open/loss
Locate the cursor on “8. ON/OFF LEVEL”in PRIMARY or ALTERNATE menu, press [ENT]
button and move into this menu. In this menu, set phase open/loss elements.
If 1 or more than 2 phase among 3phase are over the Off Level of phase voltage, is phase
open/loss. If all 3 phase are Over On Level, they are normal voltage and phase open/loss detect is
cancelled. If all 3 phase are under Off Level, does not indicate phase open/loss as they are
normal(dead line)
GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / On Level
Range 70 ~ 85%
Default 80 Step 5%
Set normal voltage Level.
[PHASE DIFF]
>Level: 30
>Time : 4.0
[0.0~180.0:0.1s]
[ON/OFF LEVEL]
>On Level: 80
>Off Level: 50
[70~85:5deg]
[PHASE DIFF]
>Level: 30
Time : 4.0
[0(OFF),5~80:5deg]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 107 ENHANCED TECHNOLOGY
GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / Off Level
Range 30 ~ 75%
Default 50 Step 5%
Set phase open/loss Level.
GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / Time
Range 0.1 ~ 180.0sec
Default 4.0 Step 0.1sec
Set delay time of line phase open/loss element.
7.7. Overcurrent detect element
Locate the cursor “10. OVER CURRENT”in PRIMARY or ALTERNATE menu, press [ENT]
button and move into this menu. In this menu, set overcurrent detect element.
Overcurrent detect element is managed as PQ monitoring function item.
GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / PHA-Pickup
Range 0(OFF), 50 ~ 630A
Default 400 Step 5A
Set pickup level of over current for phase.
GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / PHA-Time
Range 0.0 ~ 180.0 sec
Default 2.0 Step 0.1sec
Set detection time of over current for phase.
GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / GND-Pickup
Range 0(OFF), 25 ~ 315A
Default 100 Step 5A
Set pickup level of over current for ground.
[ON/OFF LEVEL]
>Off Level: 50
>Time : 4.0
[0.1~180.0:0.1s]
[OVER CURRENT]
>PHA-Pickup: 400
>PHA-Time: 2.0
[0.0~180.0:0.1s]
[OVER CURRENT]
>GND-Pickup: 100
>GND-Time: 2.0
[0(OFF),25~315:5A]
[OVER CURRENT]
>PHA-Pickup: 400
>PHA-Time: 2.0
[0(OFF),50~630:5A]
[ON/OFF LEVEL]
>On Level: 80
>Off Level: 50
[30~75:5deg]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
108 ENHANCED TECHNOLOGY
GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / GND-Time
Range 0.0 ~ 180.0 sec
Default 2.0 Step 0.1sec
Set detection time of over current for ground.
[OVER CURRENT]
>GND-Pickup: 100
>GND-Time: 2.0
[0.0~180.0:0.1s]
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 109 ENHANCED TECHNOLOGY
8. EVENT Place the cursorn on
Place the curser on “3.EVENT”, press [ENT] button to move into this menu.
ETR300-R records all events during the operation, occurred events are recorded separately such as
operation event, fault event, system event, set change event, load event and diagnostic event. All
events are recorded in order(FIFO). In this menu, all events can be checked and deleted.
This menu has sub-menu as below. Press [ENT] to move into sub-menu.
.
8.1. Operation Event
Operation event records max. 256 events. When Recloser operates(OPEN/CLOSE), operation
status and control signal(LOCAL/REMOTE) is recorded in operation event.
Move to “MAIN MENU / EVENT / OPERATION” to confirm operation events.
[003/256] CLOSE
CONTROL : REMOTE
2007/10/01 00:00:01
[002/256] OPEN
CONTROL : REMOTE
2007/10/01 00:00:02
[001/256] CLOSE
CONTROL : REMOTE
2007/10/01 00:00:03
[▼][▲] are used to check event. [001/256] is the latest event record.
Trigger Source
[EVENT]
>1.OPERATION
2.FAULT
3.FAULT CYCLE
4.SYSTEM
5.SET CHANGE
6.AVER.LOAD/MIN
7.PEAK.LOAD/HOUR
8.PEAK.LOAD/DAY
9.DIGNOSTIC
10.PQM
11.CLEAR SAVED DATA
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
110 ENHANCED TECHNOLOGY
STATUS
- CLOSE
- OPEN
- EARTH CLOSE (ECLOSE)
- EARTH OPEN (EOPEN)
CONTROL
- MANUAL: Switch mechanical manual operation.
- LOCAL: Operation at local
- REMOTE: Remote operation.
Trigger Time
Monitor changes of Trigger source status in every 5 msec.
Trigger Capacity
Save maximum 256 events.
8.2. Fault Event
Fault event records maximum 256 events. Fault event records fault detection time, fault current
sixe of each phase, fault direction and fault events of each phase can be checked.
Move to “MAIN MENU / EVENT / FAULT” to confirm fault events.
[003/256] TO
Target : A B C T
2008/10/01 00:01:00
[002/256] 2 EV
Target : A B C F
2008/10/01 00:02:00
[001/256] 1 EV
Target : A B C R
2008/10/01 00:03:01
[003/256] TO
A:00440T B:00440T
C:00446T N:00006
SEF:00000mA
[002/256] 1 EV
A:00440FF B:00440FF
C:00446FF N:00006
SEF:00000mA
[001/256] 1 EV
A:00440FR B:00440FR
C:00446FR N:00006
SEF:00000mA
ENT ENT ENT
[▼][▲] buttons are used to check fault events. Press [ENT] button in fault event screen to check
fault current value. And press [ENT] again to return to fault event screen. [001/256] is the latest
event record.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 111 ENHANCED TECHNOLOGY
Fault Event Information(EV)
Information before deciding the Fault type(permanent, temporary) is recorded.
SEQUENCE Sequence is recoded from one [FAULT].
TARGET Record Fault detection phase and Fault Direction.
001/256 Shows the latest event in order and records 100 events.
FAULT
CURRENT
Max fault current is displayed on fault occurring. Fault Detection phase and Fault
Current Direction are indicated.
- F: Fault Detection
- FF: Forward Fault Detection
- FR: Reverse Fault Detection
Total Information(TO)
Fault type (PermanentFault/Temporary Fault) and time, maximum current are recorded.
TARGET Record Fault detect phase and Fault type( P: Permanent fault, T: Temporary fault)
001/256 Shows the latest event in order and max.256 events are recorded.
FAULT
CURRENT
Shows maximum current value when occurs fault and indicates fault detection
fault type.
Trigger Source
Taget Element
- A: A phase
- B: B phase
- C: C phase
- N: N phase
- S: SEF
Fault Detect Element
- T: Temporary fault (TEMPORARY)
- P: Permanent fault (PERMANENT)
Detect direction
- F: FORWARD
- R: REVERSE
Fault Current[A]: A phase, B phase, C phase, N phase, SEF
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
112 ENHANCED TECHNOLOGY
Trigger Time
Moniters changes of Trigger source status in every 1/4 cycle.
Trigger Capacity
Save maximum 256 events.
8.3. Fault Cycle - Summary
Fault wave is recorded up to 8 fault waves. Fault wave information is displayed on LCD.
Captured waveform can be checked in interface software.
Move to “MAIN MENU / EVENT / FAULT CYCLE” to confirm fault cycle summary.
[003/ 8] PU
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 01:00:00
[002/ 8] PU
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 02:00:00
[001/ 8] PU
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 03:00:00
[▼][▲] is used to check the fault event. [001/008] is the latest event record.
Trigger Source
Fault wave captured time.
- PU: Pick up time.
- TR: Trip time.
- PU&TR: Picku up & Trip time
Fault current [A]: A phase, B phase, C phase, N phase
Trigger Time
Moniters changes of Trigger source status in every 1/4 cycle.
Trigger Capacity
Maximum 8 events are recorded. (20cycles 8EA).
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 113 ENHANCED TECHNOLOGY
8.4. System Events
System events records maximum 2048 events.
Move to “MAIN MENU / EVENT / SYSTEM” to confirm system events.
[003/2048] CPULINK
STATUS : HI/ASSERT
2008/10/01 00:00:01
[002/2048] CPULINK
STATUS : HI/ASSERT
2008/10/01 00:00:02
[001/2048] CPULINK
STATUS : HI/ASSERT
2008/10/01 00:00:03
[▼][▲] button is used to check the records. [001/2048] is the latest event record.
Trigger Source
52A Contact
Front panel control
AC supply
External control
Fail operation
External input/output status
System alarm
Sleep Mode
GAS STATUS
※. NOTE : Refer to “Appendix C.LOGIC BIT Attributes & Description” for mored details
about trigger source.
Trigger Time
Monitors changes of Trigger source status in every 1/4 cycle.
Trigger type
Record when Pickup(HI/ASSERT) or Dropout(LO/DEASSERT).
Storage Capacity
Save maximum 2048 events.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
114 ENHANCED TECHNOLOGY
8.5. Set Change Event
Set Change Event records maximum 100 events.
Move to “MAIN MENU / EVENT / SET CHANGE” to confirm set change events.
[001/100] LOCAL
TARGET : GLOBAL
2008/10/01 00:00:01
[002/100] LOCAL
TARGET : GLOBAL
2008/10/01 00:00:02
[001/100] LOCAL
TARGET : GLOBAL
2008/10/01 00:00:03
[▼][▲] button is used to check the records. [001/100] is the latest event record.
Trigger Source
Changed set menu
- GLOBAL SETTING
- PRIMARY SETTING
- ALTERNATE SETTING
Change method
- LOCAL: Set change at local
- REMOTE: Set change in remote
- PROGRAM: Set change by Interface software
※. NOTE : Refer to “Appendix C.LOGIC BIT Attributes & Description” for more details
about trigger source
Trigger Time
Monitoring change of Trigger source status in every 5msec.
Storage Capacity
Saves maximum 100 events.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 115 ENHANCED TECHNOLOGY
8.6. Aver. Load/Min
Records Average load value every 15 minutes. As records maximum 1024 values, about 10 days
events can be recorded.
Move to “MAIN MENU / EVENT / AVER. LOAD/MIN” to confirm aver. load/min events.
[0003/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:15
[0002/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:30
[0001/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:45
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
ENT ENT ENT
[▼][▲] button is used to check the events. To check real active power and reactive power, press
[ENT] button. To return back to previous screen, press [ENT] again. [0001/1024] is the latest
event record.
Trigger Source
Measured current [A]: A phase, B phase, C phase, N phase
Measured active power [kW]: 3 phases, A phase, B phase, C phase
Measured reactive power [kVar]: 3phases, A phase, B phase, C phase
Trigger Time
Monitors changes of Trigger source status in every 15min.
Storage Capacity
Saves maximum 1024 events.
8.7. Peak. Load/Hour
Records Peak load event.As records maximum 1024 events, about 43 days events can be recorded.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
116 ENHANCED TECHNOLOGY
Move to “MAIN MENU / EVENT / PEAK. LOAD/HOUR” to confirm peak. load/hour events.
[0003/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 01:00:00
[0002/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 02:00:00
[0001/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 03:00:00
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
ENT ENT ENT
[▼][▲] button is used to check the events. To check real active power and reactive power, press
[ENT] button in Current display screen. To return back to current display screen, press [ENT]
again. [0001/1024] is the latest event record.
Trigger Source
Measured current [A]: A phase, B phase, C phase, N phase
Measured active power [kW]: 3 phases, A phase, B phase, C phase
Measured reactive power [kVar]: 3phases, A phase, B phase, C phase
Trigger Time
Monitors changes of Trigger source status in every 1hour..
Storage Capacity
Saves maximum 1024 events.
8.8. Peak. Load/Day
Records Peak Load/Day events.As saves maximum 1024 events, about 1024 days event can be
recorded.
Move to “MAIN MENU / EVENT / PEAK. LOAD/DAY” to confirm peak. load/day events.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 117 ENHANCED TECHNOLOGY
[0003/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/01 00:00:00
[0002/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/02 00:00:00
[0001/1024]
A: 00000 B: 00000
C: 00000 N: 00000
2008/10/03 00:00:00
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
P3: 00000/ 00000
PA: 00000/ 00000
PB: 00000/ 00000
PC: 00000/ 00000
ENT ENT ENT
[▼][▲] button is used to check the events. To check real active power and reactive power, press
[ENT] button in Current display screen. To return back to current display screen, press [ENT]
again. [0001/1024] is the latest event record.
Trigger Source
Measured current [A]: A phase, B phase, C phase, N phase
Measured active power [kW]: 3 phases, A phase, B phase, C phase
Measured reactive power [kVar]: 3phases, A phase, B phase, C phase
Trigger Time
Monitors changes of Trigger source status in every 1 day.
Storage Capacity
Saves maximum 1024 events.
8.9. Diagnostic Event
Diagnostic event records and shows maximum 512 events.
Move to “MAIN MENU / EVENT / DIGNOSTIC” to confirm Diagnostic Event.
[003/512] SELFTOK
STATUS : HI/ASSERT
2008/10/01 00:00:01
[002/512] SELFTOK
STATUS : HI/ASSERT
2008/10/01 00:00:02
[001/512] SELFTOK
STATUS : HI/ASSERT
2008/10/01 00:00:03
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
118 ENHANCED TECHNOLOGY
[▼][▲] button is used to check the events. [001/512] is the latest event record.
Trigger Source
DSP Failure
ADC Failure
RTC Failure
Memory Failure
Flash-Rom Failure
Circuit Voltage Failure
Globlal Setting Failure
Primary Setting Failure
Alternate Setting Failure
Event Failure
Count Failure
DO Failure
Closing Failure
Opening Failure
※. NOTE : Refer to “Appendix C.LOGIC BIT Attributes & Description” for more details
about trigger source.
Trigger Time
Monitors status of Trigger source in every 5msec.
Trigger type
Records Dignostic event Pickup(HI/ASSERT) or Dropout(LO/DEASSERT).
Storage Capacity
Saves maximum 512 events.
When occurs Self Diagnosis Fault, handle as following
Table 8-1.Treatment method of Self Diagnosis Failure
No. Diagnosis item Treatment Period Treatment Method
1 DSP within 200msec Change to FI Detect Restrain
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 119 ENHANCED TECHNOLOGY
2 ADC 1/4 cycle Change to FI Detect Restrain
3 RTC 1hour, when booting Change the date to Jan. 1st, 1970
4 Memory 1hour, when booting Restart
5 Flash-Rom When Read and WriteFlash-
Rom , when booting Restart
6 Circuit Voltage 1/4 cycle Change to FI Detect Restrain
7 Global Setting When change setting, when
booting Change to Global setting value
Default value
8 Primary Setting When change setting, when
booting Change to Primary Setting value
Default value
9 Alternate Setting When change setting, when
booting Change to Alternate Setting value
Default value
10 Event When save and read event Event initialization
11 Count When write and read count Counter initialization
12 DO Signal 50msec Block the output power
13 Close/Opem When Closing and Openning Need to check in local
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
120 ENHANCED TECHNOLOGY
8.10. PQM
Power Quality Management (PQM) detect event records 100 events.
Move to “MAIN MENU / EVENT / PQM” to confirm PQM events.
[003/100] UBI
TARGET : 1WAY
DATA: 102%
2008/10/01 08:10:20
[002/100] OVS
TARGET : 1WAY A
DATA: 1668V
2008/10/01 09:00:00
[001/100] SWL&TEMP
TARGET : 1WAY A
DATA: 1670V 337 Cyc
2008/10/01 10:00:03
[▼][▲] button is used to check the event. [001/100] is the latest event record.
Trigger Source
PQM detect element.
- Sag(SAG): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),
Long Time(LONG)
- Swell(SWL): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),
Long Time(LONG)
- Interruption(INT): Momentary(MOME), Temporary(TEMP), Sustained(LONG)
- Source side Unbalance Voltage(UBV)
- Load side Unbalance Voltage (UBL)
- Current Unbalance(UBI)
- Source side Over voltage (OVS)
- Load side Over voltage (OVL)
- Over Current
- Voltage Harmonic distortion (VTH)
- Current Harmonic distortion (ITH)
PQM element detected phase: Aphase, Bphase, Cphase
PQM element related measured value
PQM detect time(cycle)
Trigger Time
Monitors status of Trigger source in every 5msec.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 121 ENHANCED TECHNOLOGY
Storage Capacity
Saves maximum 100 events.
8.11. Clear Saved Data
Move to “EVENT / CLEAR SAVED DATA” to clear saved data.
EVENT / CLEAR SAVED DATA
Clear Saved Data
Select an item to delete and press[ENT] button.
If deleting is completed, “EVENT CLEAR SUCCESS”
message is displayed.
8. ABOVE ALL
1 ~ 7 items are all deleted.
[EVENT CLEAR]
EVENT CLEAR SUCCESS
[CLEAR SAVED DATA]
>1.OPERATION
2.FAULT
3.SYSTEM
4.SET CHANGE
5.LOAD PROFILE
6.DIGNOSTIC
7.PQM
8.ABOVE ALL
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
122 ENHANCED TECHNOLOGY
9. Maintenance
Place the curser on “4. MAINTENANCE” in Main menu, press [ENT] button to move into this
menu. This menu displays Maintenance information.
This menu has sub-menu as below and by pressing [ENT] button, move into sub-menu.
9.1. Count
This menu displays counter information and has submenus as following.
9.1.1. CCU Count
Move to “MAINTENANCE / COUNT / CCU” to confirm CCU (ETR 300)count.
MAINTENANCE / COUNT / CCU
Restart Count
ETR300-R restart number is displayed.
Diagnostic Count
ETR300-R Diagnostic Count is displayed.
[COUNT]
>1.CCU
2.OPERATION
3.FAULT
4.PQM
[CCU]
RESTART : 30
DIAGNOSTIC : 0
[MAINTENANCE]
>1.COUNT
2.INTERRUT TIME
3.CONTACT WEAR
4.DATA RESET
5.CCU INFO
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 123 ENHANCED TECHNOLOGY
9.1.2. Operation Count
Move to “MAINTENANCE / COUNT / OPERATION” to confirm operation count.
MAINTENANCE / COUNT / OPERATION
Displays operation counter of switch.
9.1.3. Fault Count
Move to “MAINTENANCE / COUNT / FAULT” to confirm fault count.
MAINTENANCE / COUNT / FAULT
[FAULT] 1/3
TOT: 0 SEF: 0
A : 0 B : 0
C : 0 N : 0
[FAULT-P] 2/3
TOT: 0 SEF: 0
A : 0 B : 0
C : 0 N : 0
[FAULT-T] 3/3
TOT: 0
A : 0 B : 0
C : 0 N : 0
Number of fault is displayed. This COUNT menu consists in 3
pages. Use [▼][▲] button to move into sub-menu.
FAULT(1/3)
Total number of fault detection and fault detection number per phase
ard displayed.
FAULT(2/3)
Total number of PERMANENT fault and number of fault per phase
are displayed.
FAULT(3/3)
Total number of TEMPORARY fault and number of fault per phase
are displayed.
9.1.4. PQM Count
This menu displays PQM count information and has the following submenu.
[OPERATION]
COUNT : 0
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
124 ENHANCED TECHNOLOGY
9.1.4.1. INTERRUPT
Move to “MAINTENANCE / PQM / INTERRUPT” to confirm interrupt count.
MAINTENANCE / COUNT / PQM / INTERRUPT
[INTERRUPT] 1/2
TOTAL: 0
A : 0 B : 0
C : 0
[INTERRUPT] 2/2
MOMENTARY : 0
TEMPORARY : 0
SUSTAINED : 0
Number of Interruption is displayed. This COUNT menu consists in 2
pages and use [▼][▲] button to move into each pages.
INTERRUPT(1/2)
Total number of Interruption and number of interruption per phase are
displayed.
INTERRUPT(2/2)
Number of fault per type is displayed on Interruption.
[PQM COUNT]
>1.INTERRUT
2.SAG
3.SWELL
4.HARMONICS
5.CURR UNBALANCE
6.VOLT UNBALANCE
7.UNDER VOLTAGE
8.OVER VOLTAGE
9.OVER CURRENT
10.UNDER FREQUNCY
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 125 ENHANCED TECHNOLOGY
9.1.4.2. Sag
Move to “MAINTENANCE / COUNT / PQM / SAG” to confirm sag count.
MAINTENANCE / COUNT / PQM / SAG
[SAG] 2/2
INS: 0 MOM: 0
TMP: 0 LON: 0
[SAG] 1/2
TOTAL: 0
A : 0 B : 0
C : 0
Number of Sag is displayed. This COUNT menu consists 2 pages and
use [▼][▲] buttons to move into sub-menu.
SAG(1/2)
Total number of Sag occurred and number of Sag per phase are
displayed.
SAG(2/2)
Number of Sag per type is displayed.
9.1.4.3.Swell
Move to “MAINTENANCE / COUNT / PQM / SWELL” to confirm swell count.
MAINTENANCE / COUNT / PQM / SWELL
[SWELL] 1/2
TOTAL: 0
A : 0 B : 0
C : 0
[SWELL] 2/2
INS: 0 MOM: 0
TMP: 0 LON: 0
Number of Swell occurred is displayed. This COUNT menu consists
of 2 pages and use [▼][▲] button to move into sub-menu.
SWELL(1/2)
Total number of Swell and number of Swell per phase are displayed.
SWELL(2/2)
Number of Swell per type is displayed.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
126 ENHANCED TECHNOLOGY
9.1.4.4. Harmonics
Move to “MAINTENANCE / COUNT / PQM / HARMONIC” to confirm sag count.
MAINTENANCE / COUNT / PQM / SWELL
[VTHD] 1/2
TOTAL: 0
A : 0 B : 0
C : 0
[ITHD] 2/2
TOTAL: 0
A : 0 B : 0
C : 0
Number of Harmonic distortion is displayed. The COUNT menu
consists 2 pages and use [▼][▲] buttons to move into sub-menu.
VTHD(1/2)
Total number of Voltage Harmonic distortion and number of voltage
harmonic distortion per phase are displayed.
ITHD(2/2)
Total number of current harmonic distortion and number of current
harmonic distortion per phase are displayed.
9.1.4.5. Current Unbalance
Move to “MAINTENANCE / COUNT / PQM / CURRENT UNBALANCE” to confirm current
unbalance count.
MAINTENANCE / COUNT / PQM / CURRENT UNBALANCE
Number of Current Unbalance occurred is displayed.
[CURRENT UNBALANCE]
COUNT : 0
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 127 ENHANCED TECHNOLOGY
9.1.4.6. Voltage Unbalance
Move to “MAINTENANCE / COUNT / PQM / VOLTAGE UNBALANCE” to confirm voltage
unbalance count.
MAINTENANCE / COUNT / PQM / VOLTAGE UNBALANCE
Number of voltage unbalance occurred is displayed.
SOURSE SIDE
Number of voltage unbalance at source side is displayed.
LOAD SIDE
Number of voltage unbalance at load side is displayed.
9.1.4.7. Under Voltage
Move to “MAINTENANCE / COUNT / PQM / UNDER VOLTAGE” to confirm under voltage
count.
MAINTENANCE / COUNT / PQM / UNDER VOLTAGE
[LS-UNDER VOLT] 2/2
TOTAL: 0
A : 0 B : 0
C : 0
[VS-UNDER VOLT] 1/2
TOTAL: 0
A : 0 B : 0
C : 0
Number of under-voltage is displayed. This COUNT menu consists 2
pages and use [▼][▲] button to move into sub-menu.
VS-UNDER VOLT(1/2)
Total number of undervoltage at source side and number of
undervoltage per phase are displayed.
LS-UNDER VOLT (2/2)
Total number of undervoltage at load side and number of
undervoltage at load side per phase are displayed.
[VOLTAGE UNBALANCE]
SOURCE SIDE : 0
LOAD SIDE : 0
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
128 ENHANCED TECHNOLOGY
9.1.4.8. Over Voltage
Move to “MAINTENANCE / COUNT / PQM / OVER VOLTAGE” to confirm over voltage
count.
MAINTENANCE / COUNT / PQM / OVER VOLTAGE
[VS-OVER VOLT] 1/2
TOTAL: 0
A : 0 B : 0
C : 0
[LS-OVER VOLT] 2/2
TOTAL: 0
A : 0 B : 0
C : 0
Number of over-voltage is displayed. This COUNT menu consists 2
pages and use [▼][▲] button to move into sub-menu.
.
VS-OVER VOLT(1/2)
Total number of overvoltage at source side and number of
undervoltage per phase are displayed.
LS-OVER VOLT (2/2)
Total number of overvoltage at load side and number of overvoltage
at load side per phase are displayed.
9.1.4.9.Under Frequency
Move to “MAINTENANCE / COUNT / PQM / Under Frequency” to confirm under frequency
count.
MAINTENANCE / COUNT / PQM / UNDER FRQUENCY
Number of underfrequency is displayed.
[UNDER FREQUENCY]
COUNT : 0
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 129 ENHANCED TECHNOLOGY
9.2. Interrupt Time
Move to “MAINTENANCE / INTERRUPT TIME” to confirm interrupt time.
MAINTENANCE / INTERRUPT TIME
[INTERRUP TIME] 1/2
TOTAL: 0
A : 0 B : 0
C : 0 N : 0
[INTERRUP TIME] 2/2
MOMENTARY : 0
TEMPORARY : 0
SUSTAINED : 0
Accumulated interrupt time is displayed. This COUNT menu consists
2 pages and use [▼][▲] button to move into sub-menu.
INTERRUPT TIME(1/2)
Total accumulated time and accumulated time per phase are
displayed. Time unit is Cycle.
INTERRUPT TIME(2/2)
Accumulated time per interrupt type is displayed, time unit is cycle.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
130 ENHANCED TECHNOLOGY
9.3. Contact Wear
Move to “MAINTENANCE / CONTACT WEAR” to confirm contact wear.
MAINTENANCE / CONTACT WEAR
Displays switch contact wear in percentage.
9.4. Data Reset
Move to “MAINTENANCE / DATA RESET”. This menu resets COUNT and Maintenance data.
MAINTENACE / DATA RESET
Saved data reset
Select an item to delete and press[ENT] button.
If deleting is completed, “EVENT CLEAR SUCCESS”
message is displayed.
※. NOTE :
1) „OPERATION COUNT‟ is reset by a set value in „MAIN MENU/
GLOBLA SETTING/ MONITERING/ OPERATION COUNT‟.
2) „CONTACT WEAR‟ is reset by a set value in „MAIN MENU/
GLOBLA SETTING/ MONITERING/ CONTACT WEAR‟.
3) Except „OPERATION COUNT‟ and „CONTACT WEAR, all data
is reset for 0.
10. ABOVE ALL
1 ~ 9 item data are all reset.
[CONTACT WEAR-%]
A : 100.00
B : 100.00
C : 100.00
[EVENT CLEAR]
EVENT CLEAR SUCCESS
[DATA RESET]
>1.CCU COUNT
2.OPERATION COUNT
3.FAULT COUNT
4.DELTA I COUNT
5.PQM COUNT
6.COUNT ALL
7.INTERRUPT COUNT
8.CONTACT WEAR
9.ENERGY
10.ABOVE ALL
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 131 ENHANCED TECHNOLOGY
9.5. CCU Information
Move to “MAINTENANCE / CCU INFO” to confirm ccu information.
MAINTENANCE / CCU INFO
ENT
Present CCU(ETR300-S) information is displayed.
Prog Opt:ox70310156
MPU Ver: 1.0
DSP Ver: 1.0
CPU Ver: 1.0
TYPE:ETR300S-11D-40-
24-11D-1FF-DMN
61-0101-0000-KR-1000
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
132 ENHANCED TECHNOLOGY
10. Time Place the curser on “5.TIME” in Main menu, press [ENT] button to move in this menu.
TIME
Set present date and time.
1) Press [ENT] button to select and change a setting.
2) To change a number, use [▲][▼] button and to move next item,
press [ENT] button.
3) To save all changed setting, press [ENT].
[CURRENT TIME]
2006/11/05 21:02:38
PRESS <ENT> TO SET
[SETTING TIME]
2006/11/05 21:02:38
USE [UP/DOWN/ENTER]
PRESS <FUNC> : ABORT
[SAVE TIME]
2006/11/06 15;01:50
PRESS <ENT> TO SAVE
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 133 ENHANCED TECHNOLOGY
11. Status
Place the curser on “6. STATUS” in Main menu, press [ENT] button to move in this menu. This
menu has sub-menu as below. Press [ENT] to move into sub-menu.
11.1. Switch
You can confirm in “MAIN MENU / STATUS / RECLOSER”
STATUS/ SWITCH
Present switch and ETR300 status are displayed.
Use [▼] [▲] button to check all items.
SWITCH
Displays main device status.
OPEN, CLOSE, TROUBLE(Device Trouble status)
PANEL LOCK
Displays panel lock status.
LOCK, UNLOCK
CONTROL
Operation control select is displayed.
REMOTE, LOCAL, TROUBLE(Device Trouble Status)
SECTION
Display whether to use section function.
DISABLE, ENABLE
PHA-PROTECT
Phase protection function status is displayed.
DISABLE, ENABLE
GND-PROTECT
[SWITCH]
>SWITCH :TROUBLE
PANEL LOCK : UNLOCK
CONTROL : LOCAL
SECTION :DISABLE
PHA-PROTECT:DISABLE
GND-PROTECT:DISABLE
LOCKOUT :LOCKOUT
POWER : OFF
BATTERY : NORMAL
BAT’CHRGER : NORMAL
DOOR : CLOSE
CCU ADDRESS: 0
MASTER ADDR: 65534
HANDLE LOCK:LOCKOUT
GAS : NORMAL
[STATUS]
>1.SWITCH
2.INPUT PORTS
3.OUTPUT PORTS
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
134 ENHANCED TECHNOLOGY
STATUS/ SWITCH
Ground protection function status is displayed.
DISABLE, ENABLE
LOCKOUT
Section operation status is displayed.
RESET, RUNNING, LOCKOUT
POWER
External power supply status is displayed.
ON, OFF
BATTERY
Battery status is displayed.
NORMAL, FAIL
BAT‟ CHARGER
Battery charger status is displayed.
NORMAL, FAIL
DOOR
Door status is displayed.
OPEN, CLOSE
CCU ADDRESS
DNP set address of ETR300 is displayed.(0~65535)
MASTER ADDR
DNP Host Address (0~65534:65535 is used for Broadcast)
GAS
Circuit breaker gas pressure status is displayed.
NORMAL, LOW
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 135 ENHANCED TECHNOLOGY
11.2. Input Ports
You can confirm in “MAIN MENU / STATUS / INPUT PORTS”
STATUS/ INPUT PORTS
Displays 16 input terminal(IN101 ~ IN108 and IN208 ~ IN208) status
Depending on input signal, “HI/ASSERT” or “LO/DEASSERT”is
displayed.
[▼] [▲] button is used to check all input terminal status.
11.3. Output Ports
You can confirm in “MAIN MENU / STATUS / OUTPUT PORTS”
STATUS/ OUTPUT PORTS
Displays 16 output terminal(OUT101 ~ OUT108 and OUT208 ~
OUT208) status.
Depending on output signal, “HI/ASSERT” or “LO/DEASSERT”is
displayed.
[▼] [▲] button is used to check all input terminal status.
[OUTPUT PORTS]
OUT 101:LO/DEASSERT
OUT 102:LO/DEASSERT
OUT 103:LO/DEASSERT
OUT 104:LO/DEASSERT
OUT 105:LO/DEASSERT
:
OUT 208: HI/ASSERT
[INPUT PORTS]
IN 101 :LO/DEASSERT
IN 102 :LO/DEASSERT
IN 103 :LO/DEASSERT
IN 104 :LO/DEASSERT
IN 105 :LO/DEASSERT
:
IN 208 : HI/ASSERT
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
136 ENHANCED TECHNOLOGY
12. Metering
Place the curser on “7. MERING” in Main menu, press [ENT] button to move in this menu. This
menu displays present measured value and has sub-menu as following. Press [ENT] to move into
sub-menu.
12.1. Current
ETR300 metering and indicates the following current items.
IA : Displays the measured phase A RMS current and phase (A, deg°)
IB : Displays the measured phase B RMS current and phase (A, deg°)
IC : Displays the measured phase C RMS current and phase (A, deg°)
IN : Displays the measured ground RMS current and phase (A, deg°)
SEF: Displays the measured sensitive earth RMS current and phase (A, deg°)
You can confirm in “MAIN MENU / METERING / CURRENT”
MAIN MENU / METERING / CURRENT
Current per phase and angle per phase are displayed.
Use [▲] [▼] keys to move to next value.
[CURRENT]
IA: 0 A 000.0°
IB: 0 A 000.0°
IC: 0 A 000.0°
IN: 0 A 000.0°
SEF: 0mA 000.0°
[METERING]
>1.CURRENT
2.VOLTAGE
3.FREQUENCY
4.POWER
5.ENERGY
6.DEMAND
7.UNBALANCE
8.HARMONICS
9.TRUE R.M.S
10.TD
11.CCU SEF
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 137 ENHANCED TECHNOLOGY
12.2. Voltage
ETR300 metering and indicates the following voltage items.
VS-PN: Voltage per phase and angle per phase at source side, are displayed(㎸, deg°).
VS-PP: Phase to phase voltage and angle at source side, are displayed(㎸, deg°).
VS-SEQ: Forward/Reverse/Zero sequence voltage and angle at source side, are displayed(㎸,
deg°).
VL-PN: Voltage per phase and angle per phase at load side, are displayed (㎸, deg°).
VL-PP: Phase to phase voltage and angle at load side, are displayed (㎸, deg°).
VL-SEQ: Forward/Reverse/Zero sequence voltage and angle at load side, are displayed (㎸,
deg°).
You can confirm in “MAIN MENU / METERING / VOLTAGE”
MAIN MENU / METERING / VOLTAGE
[VS-PN]
A : 00.00 kV ∠000.0°
B : 00.00 kV ∠000.0°
C : 00.00 kV ∠000.0°
[VL-PP]
RS: 00.00 kV ∠000.0°
ST: 00.00 kV ∠000.0°
TR: 00.00 kV ∠000.0°
[VL-SEQ]
V1: 00.00 kV ∠000.0°
V2: 00.00 kV ∠000.0°
V3: 00.00 kV ∠000.0°
[GPT]
VN: 00.00 kV ∠000.0°
[VS-PP]
AB: 00.00 kV ∠000.0°
BC: 00.00 kV ∠000.0°
CA: 00.00 kV ∠000.0°
[VS-SEQ]
V1: 00.00 kV ∠000.0°
V2: 00.00 kV ∠000.0°
V0: 00.00 kV ∠000.0°
[VL-PN]
R : 00.00 kV ∠000.0°
S : 00.00 kV ∠000.0°
T : 00.00 kV ∠000.0°
Voltage and angle per phase are displayed. Use [▼][▲] button to check it.
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
138 ENHANCED TECHNOLOGY
12.3. Frequency
ETR300 metering and indicates the following frequency items.
;
Hz: Present frequency is displayed.
You can confirm in “MAIN NEMU / METERING / FREQUENCY”
MAIN MENU / METERING / FREQUENCY
Frequency measured value is displayed.
12.4. Power
ETR300 metering and indicates the following power items.
POWER-KW/KVAR/KVA: Per phase, active power/apparent power/reactive power are
displayed.
POWER FACTOR: Power factor per phase is displayed.
You can confirm in “MAIN NEMU / METERING / POWER”
MAIN MENU / METERING / POWER
[POWER- KW/KVAR/KVA]
A : 0000 0000 0000
B : 0000 0000 0000
C : 0000 0000 0000
[POWER FACTOR]
A : 000
B : 000
C : 000
Per phase, power and power factor are displayed.
Use [▼][▲] button to check the power metering information.
[FREQUENCY]
0.00 Hz
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 139 ENHANCED TECHNOLOGY
12.5. Energy
ETR300 metering and indicates the following energy items.
FORWARD – KWh/KVARh: Energy per phase in forward is displayed.
REVERSE – KWh/KVARh: Energy per phase in reverse is displayed.
You can confirm in “MAIN NEMU / METERING / ENERGY”
MAIN MENU / METERING / ENERGY
[FORWARD- KWh/KVARh]
A : 000000 000000
B : 000000 000000
C : 000000 000000
[REVERSE- KWh/KVARh]
A : 000000 000000
B : 000000 000000
C : 000000 000000
Energy is displayed. Use [▼][▲] button to check the energy
metering information.
12.6. Demand Current
You can confirm in “MAIN MENU / METERING / DEMAND”
MAIN MENU / METERING / DEMAND
Load current per phase are displayed.
[DEMAND CURRENT]
A: 0000 A B: 0000 A
C: 0000 A N: 0000 A
SEF :00.000 A
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
140 ENHANCED TECHNOLOGY
12.7. Unbalance
ETR300 metering and indicates the following unbalance items.
SOURCE-VOLT: Voltage unbalance at source side is displayed.
LOAD-VOLT: Voltage unbalance at load side is displayed.
CURRENT: Current unbalance is displayed.
.
You can confirm in “MAIN MENU / METERING / UNBALANCE”
MAIN MENU / METERING / UNBALANCE
Unbalance of metering value is displayed.
12.8. Harmonics
You can confirm in “MAIN MENU / METERING / HARMONICS”
MAIN MENU / METERING / HARMONICS
[%V-Harm. A/B/C]
THD : 0.0 0.0 0.0
02H : 0.0 0.0 0.0
03H : 0.0 0.0 0.0
[%V-Harm. A/B/C]
04H : 0.0 0.0 0.0
05H : 0.0 0.0 0.0
06H : 0.0 0.0 0.0
[%V-Harm. A/B/C]
31H : 0.0 0.0 0.0
[%I-Harm. 31H]
A : 0.0 B : 0.0
C : 0.0 N : 0.0
[%I-Harm. 02H]
A : 0.0 B : 0.0
C : 0.0 N : 0.0
[%I-Harm. THD]
A : 0.0 B : 0.0
C : 0.0 N : 0.0
Voltage and current harmonic rate are displayed. Use [▼][▲] button to check harmonic rate
information.
[UNBALANCE- %]
SOURCE-VOLT: 0.00
LOAD-VOLT: 0.00
CURRENT: 0.00
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
- 141 ENHANCED TECHNOLOGY
12.9. True R.M.S
You can confirm in “MAIN NEMU / METERING / TRUE R.M.S”
MAIN MENU / METERING / TRUE R.M.S
[VOLTAGE-TURE R.M.S]
A : 000 V
B : 000 V
C : 000 V
[ CURRENT- TURE R.M.S]
A : 0.0A B : 0.0A
C : 0.0A N : 0.0A
TRUE R.M.S voltage and current per phase are displayed. Use
[▼][▲] button to check TURE R.M.S. information .
12.10. TD Monitoring
You can confirm in “MAIN MENU / METERING / TD MONITORING”
MAIN MENU / METERING / TD MONITORING
TD input value is displayed.
12.11. CCU Reference
You can confirm in “MAIN MENU / METERING / CCU REF”
MAIN MENU / METERING / CCU REF
ETR300 reference values are displayed.
[CCU Rer]
+5V: 4.9 -5V:-4.8
Temp: 37°
[TD MONITERRING]
TD1: 00.0 TD2: 00.0
TD3: 00.0 TD4: 00.0
TD5: 00.0
SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr
142 ENHANCED TECHNOLOGY
13. PLC function
ETR300 has changeable PLC for user. PLC has Timer, Counter and Event to control input and
output. Circuit can be optimized to omit unnecessary timer and aux. relay. During ETR300
running, in case the circuit needs to be changed, PLC can be used to meet user‟s need. PLC is
programmed in “ETR300 Interface Software”.
Ficture 13-1. PLC Edit Screen