2.manual etr300s v1.0 eng

142
Load Break Switch Control ETR300S Users Manual ENTEC ELECTRIC & ELECTRONIC CO., LTD ENTEC Copyright © 2009 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation Release Date: Nov. 2009 / Manual Revision: 1.00

Upload: agustinus-phatub-kurniawan

Post on 21-Dec-2015

61 views

Category:

Documents


6 download

DESCRIPTION

recloser

TRANSCRIPT

Page 1: 2.Manual ETR300S V1.0 Eng

Load Break Switch Control ETR300S

User’s Manual

ENTECELECTRIC & ELECTRONIC CO., LTD

ENTEC

Copyright © 2009 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation

Release Date: Nov. 2009 / Manual Revision: 1.00

Page 2: 2.Manual ETR300S V1.0 Eng
Page 3: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 3 ENHANCED TECHNOLOGY

CONTENT

1. Product Introduction ..................................................................................................... 6

1.1. Introduction ......................................................................................................................... 6

1.2. Characteristic summary ....................................................................................................... 7

2. Technical Specification ................................................................................................. 10

2.1. Input and Output ................................................................................................................ 10

2.2. Environment Test ............................................................................................................... 12

2.3. Metering Accuracy ............................................................................................................ 13

2.4. Monitoring ......................................................................................................................... 14

2.5. Event Recorder .................................................................................................................. 18

2.6. Maintenance ...................................................................................................................... 21

2.7. Communication ................................................................................................................. 21

3. Dimension and structure ................................................................................................. 22

4. External Input/Output Connector ................................................................................... 23

4.1. Current Input(Connector type:STLZ960-10) .................................................................... 24

4.2. Voltage Input(Connector type:STLZ960-6P,8P) ............................................................... 24

4.3. Digital Output(DO) ........................................................................................................... 25

4.4. Digital Input(DI) ................................................................................................................ 25

4.5. Power supply input& Modem power supply output .......................................................... 26

4.6. Remote Communication Port(modem connection) ........................................................... 26

4.7. 485 Communication Port ................................................................................................... 27

4.8. Ethernet Port(RJ45) ........................................................................................................... 27

5. User Interface Panel .................................................................................................... 28

5.1. Construction ...................................................................................................................... 29

5.2. Operation Manual (LCD instruction) ................................................................................ 36

5.3. LCD Menu Use.................................................................................................................. 43

6. Global Setting ............................................................................................................... 47

6.1. System ............................................................................................................................... 47

6.2. Communication ................................................................................................................. 54

6.3. Event Recorder .................................................................................................................. 69

Page 4: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

4 ENHANCED TECHNOLOGY

6.4. Monitoring ......................................................................................................................... 70

6.5. PLC .................................................................................................................................... 81

6.6. Other setting items ............................................................................................................. 86

7. Group Setting ................................................................................................................ 89

7.1. Fault pickup element ......................................................................................................... 90

7.2. Inrush Current Restraint Function ..................................................................................... 95

7.3. Directional Detection Function ......................................................................................... 98

7.4. SECTION ........................................................................................................................ 102

7.5. Phase angle synch detect ................................................................................................. 106

7.6. Line cut / Phase lost detect .............................................................................................. 106

7.7. Overcurrent detect element.............................................................................................. 107

8. EVENT ........................................................................................................................ 109

8.1. Operation Event ............................................................................................................... 109

8.2. Fault Event ...................................................................................................................... 110

8.3. Fault Cycle - Summary .................................................................................................... 112

8.4. System Events ................................................................................................................. 113

8.5. Set Change Event ............................................................................................................ 114

8.6. Aver. Load/Min ................................................................................................................ 115

8.7. Peak. Load/Hour .............................................................................................................. 115

8.8. Peak. Load/Day ............................................................................................................... 116

8.9. Diagnostic Event ............................................................................................................. 117

8.10. PQM .............................................................................................................................. 120

8.11. Clear Saved Data ........................................................................................................... 121

9. Maintenance ................................................................................................................ 122

9.1. Count ............................................................................................................................... 122

9.2. Interrupt Time .................................................................................................................. 129

9.3. Contact Wear ................................................................................................................... 130

9.4. Data Reset........................................................................................................................ 130

9.5. CCU Information ............................................................................................................. 131

10. Time ........................................................................................................................... 132

11. Status .......................................................................................................................... 133

11.1. Switch ............................................................................................................................ 133

11.2. Input Ports ..................................................................................................................... 135

11.3. Output Ports ................................................................................................................... 135

Page 5: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 5 ENHANCED TECHNOLOGY

12. Metering .................................................................................................................... 136

12.1. Current ........................................................................................................................... 136

12.2. Voltage ........................................................................................................................... 137

12.3. Frequency ...................................................................................................................... 138

12.4. Power ............................................................................................................................. 138

12.5. Energy ............................................................................................................................ 139

12.6. Demand Current ............................................................................................................ 139

12.7. Unbalance ...................................................................................................................... 140

12.8. Harmonics ..................................................................................................................... 140

12.9. True R.M.S .................................................................................................................... 141

12.10. TD Monitoring ............................................................................................................. 141

12.11. CCU Reference ............................................................................................................ 141

13. PLC function ............................................................................................................ 142

Page 6: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

6 ENHANCED TECHNOLOGY

1. Product Introduction

1.1. Introduction

ETR300-S01 is embedded in Distribution Automation 25.8kV SF6 gas insulated load break

switch(Pole mount) control box. It receives measurement information(3 phases current &

voltages) and status information from Switch, and meters current and voltage, detecs FI, Line cut,

Live line/Dead line, Unbalance, and send those information to SCADA(Master station).

As well as, controlling a swich by receiving Control Signal from SCADA, provides Distribution

Automation and minimize a fault area.

ETR300-S01 monitors not only electric quality of dirstirbution line but also, provides Section

operation in case of fault occurring and minimize its fault area.

All events occurring in the distribution line, are saved and provides fault analysis. With using

DNP3.0 Protocol, provides monitored status to SCADA for switch operation. Not only DNP3.0

Protocol, other communication protocols can beprovided by user‟s request.

Switch operation is available by operation buttion on front panel. Fault detect Enable/Diable,

Fault detect Enable/Disable, SECTION function Enable/Disable, operation selection

Local/Remote, Operation lock Lock/Unlock, ALTERNATE SETTING Enable/Disable, SEF

function Enable/Disable, SEC/TIE LOCKOUT Enable/Disable can be set.

INTERFACE SOFTWARE is very much convenient to have the maintenance of Set change and

Operation records in PC. It also has Zoom In/Out feature to analize Fault wave and Digital

operation signal with real time so that it provides much more uniq functions for the users.

Page 7: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 7 ENHANCED TECHNOLOGY

1.2. Characteristic summary

MONITORING

Phase fault detect(Permenant , Instantaneous)

Earth fault detect(Permenant, Instantaneous)

SEF fault detect(Permenant, Instantaneous)

Inrush current restraint (Phase/Earth/SEF)

Directional (Phase/Earth/ SEF)

SECTION operation function

Unbalance detect

Line cut/phase loss detect element

Live line detect

Operation counter limit

Switch contact wear monitoring

Battery auto load test

Power Quality Monitoring

- Interrupt

- Sag

- Swell

- Harmonics

- Current Unbalance

- Voltage Unbalance

- Under Voltage

- Over Voltage

- Under Frequency

- Over Current

DC Analog Input Monitoring

Zero Sequence voltage(V0) detect

Page 8: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

8 ENHANCED TECHNOLOGY

EVENT RECORDER

Switch Operation Record –Last 256 events

Fault Event Record –Last 256 events

Fault Waves(20 cycles× 8EA) record – Last 8 events

System Event Record – Last 2048 events

Set Change Event – Last 100 events

Average Load Event Record –Last 1024 events

Max. Load per hour Event Record – Last 1024 events

Max Load per day Event Record –Last 1024 events

Diagnostic Event Record – Last 512 events

PQM Monitoring Event Record – Last 100 events

METERING

Phase Current and Phase Angle, Fault Current and Angle, SEF Current and Angle

Voltage and Angle between phases, Forward/Revserse/Zero Sequence and Angle

Frequency magnitude and changing rate per second

Real Power/Apparent Power/Reactive Power per phase

Power Factor per phase

Forward/Reverse Phase Energy

Demand

Source/Load side Voltage and Current Unbalance

Voltage and Current Harmonic rate

Phase True R.M.S voltage and current

DC Analog Input value

ETR300 Inside Temperature

MAINTENANCE

Number of Restart

Number of Diagnostic detec

Number of Switch fault occurred

Number of Instantaneous current fluctuation and its number per phase

Number of PQM occurred and accumulated time

Switch contact wear

COMMUNICATIONS

Side Panel PORT1 RS232 Serial port : DNP 3.0, Modbus and IEC60870-5-101 Protocol

Page 9: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 9 ENHANCED TECHNOLOGY

Side Panel PORT2 RS485 Serial port : DNP 3.0, Modbus and IEC60870-5-101 Protocol

Side Panel PORT3 RJ45 port : DNP 3.0 및 IEC60870-5-104 Protocol

Side Panel PORTF RS232 Serial port : ETR300-R Interface Software

USER INTERFACE

Fault Indicator

Manual battery load test: Battery voltage and chaged voltage

Dual function keypad

20×4 character display (LCD or VFD: Vacuum Fluorescent Display)

43 LED indicator – Fault Indicator, Sequence Status, Battery status and so on

Fron Panel RS232 Port

Help Message

Security(Password)

AUXILIARY OUTPUTS

16 number of PLC Progoram available

AUXILIARY INPUTS

16 number of PLC Program available

Other

Fault Injection test available

Page 10: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

10 ENHANCED TECHNOLOGY

2. Technical Specification

2.1. Input and Output

System

3 phases- 3 wires or 3 phases – 4 wires, Max.38kW, Max 800A

Frequency

50/60 Hz System and ABC/ACB phase rotation

Control voltage input

AC Power supply input 110V/220Vac or other voltage(+10%,-15%)

Rated battery voltage : 24Vdc

User DC Poer Output – Option

DC Power supply voltage : 12, 15, 24Vdc

Continuous DC Power supply : 30W

DC Power for 10 second: 70W

Voltage Transformer Input (VT) – Standard

V11, V12, V13, V21, V22, V23 and V10

Input voltage range : Phase-Neutral continuous < 6V

Load burden : 0.002VA(4V)

Voltage Transformer Input (VT) – Option

V11, V12, V13, V21, V22, V23 and V10

Input voltage range : Phase-Neutral continuous < 300V

Load burden : 0.6VA(300V), 0.2VA(220V), 0.05VA(120V), 0.02VA(67V)

Current Transformer (CT)

IA,IB,IC and IG, SEF, ZCT

IA,IB,IC,IG input current range

Nominal: AC 0.6Arms

Continuous: 2A

25A for 1 sec

Page 11: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 11 ENHANCED TECHNOLOGY

Load burden : 0.38VA(1A)

SEF input current range

Rated current : 0.05A

Continuous current : 0.16A

0.6A for 1sec

Load burden : 0.0375VA(0.05A)

ZCT input current range – Option

Rated current : 1.5mA

Continuous ????????????????? mA

200mA for 1sec

Load burden : 0.0005VA(1.5mA)

Control Input – Option

Control Input 8 channel

Rated voltage and operation range

250Vdc(-15%,+20%)

125Vdc(-15%,+20%)

48Vdc(-15%,+20%)

24Vdc(-15%,+20%)

12Vdc(-10%,+30%)

Operation current: at rated voltage, < 5mA

Control Output Contact – Option

Control Input 8 channel

Open 5 channel

Close 5 channel

Alarm 1 channel

Auto surge protection Varistor 300Vac / 350Vdc

Operation and release time: at +20℃(+68℉) , < 5ms

Max operation power supply

Table 2-1. Max. Operation power supply

(L/R=7ms)

125Vdc 0.1A

48Vdc 0.8A

24Vdc 3A

(cosΦ=0.4) 250Vac 3A

125Vac 5A

Page 12: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

12 ENHANCED TECHNOLOGY

2.2. Environment Test

Dielectric Strength

CT Input, VT Input, Control Power Input, Fiber-optic insulation Input and Relay output

AC 60㎐, 2㎸/1 minute

Impulse Voltage

IEEE C62.45 (1992) , 6㎸(1.2×50㎲), 3㎄(8×20㎲) of Relay System for Radio

Electromagnetic Interference Transceiver.

Surge Withstand Capability

Protection relay and Relay system protection purpsoe IEEE C37.90.1 - 1989 IEEE SWC test

(3㎸ Vibration1㎒ to 1.5㎒, 5㎸ fast saturation 1.2×50㎲)

IEEE C37.90.2 - 1987 IEEE Test, Test use standard, relay system for Radio Electromagnetic

Interface that comes from Transceiver, 10 V/m(150㎒ and 450㎒, 5 W transmitter 10㎝)

Vibration Test

IEC 255-21-1-1988 Electric Relay, Part 21: Metering relay and protection device vibration,

impact, crash and earthquake test, Section One - Vibration tests (sinusoidal), Class 2

IEC 255-21-1-1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on

measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2

Control Operating Temperature

Operation range위 : -25℃∼+70℃(-13℉∼+158℉)

LCD : -20℃∼+70℃(-4℉∼+158℉) – Standard

VFD(Vacuum Fluorescent Display-Vacuum florecense zero sequence output device) : -

40℃∼+85℃(-40℉∼+185℉) – optoin

Page 13: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 13 ENHANCED TECHNOLOGY

2.3. Metering Accuracy

Measurement values for metering and protection are based on Input voltage and current which are

eliminated Harmonic.

Voltage metering

Rated voltage : AC voltage 4 V

Each phase voltage : ±0.2 %(Rated voltage 80 ~ 120 %), ±0.5˚

Zero sequence voltage(Vo) : ±0.2 %(Rated voltage 80 ~ 120%), ±0.5˚

3V1, 3V0, 3V2 : ±0.6 %(Rated voltage 80 ~ 120%), ±1˚

Current metering

Rated current : AC 0.6 Arms

IA, IB, IC, IG : ±0.5 mA ± 0.1 % of reading(0.03~1.5 A), ±0.5˚

IN : ±0.005 mA + ±0.5 % of reading(0.5~16.0 mA), ±1˚

3I1, 3I0, 3I2 : ±0.01 A ± 3 % of reading(0.003~1.5A ), ±1˚

Power metering

Power : ±1.2 %(at rated voltage>80 %, at rated current>0.03)

Rea Power : ±0.7 % PF=1, ±1% PF>0.87(at rated voltage>80%, at rated current>0.03)

Reactive Power : ±0.7 % PF=0, ±1% PF<0.5(at rated voltage>80%, at rated current>0.03)

Harmonic metering : ±5%

Page 14: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

14 ENHANCED TECHNOLOGY

2.4. Monitoring

Fault detect function

Phase fault pickup level ................................................. OFF, 50 ~ 630A (step: 5A)

Earth fault pickup level ................................................. OFF, 25 ~ 315A (step: 5A)

SEF pickup level ........................................................... OFF, 0.1 ~ 10.0A (step: 0.1A)

Dropout.......................................................................... Pickup level 96 ~ 98%

Instantaneous FI detect time .......................................... 1 ~ 180sec (step: 1sec)

Instantaneous FI detect time .......................................... 1 ~ 180sec (step: 1sec)

Phase Directional detect function

Pole voltage ................................................................... normal voltage V1

Directional detect .......................................................... Disable, Enable

Max. Torque angle ......................................................... 0 ~ 345° (step: 15° )

Min. Operation voltage.................................................. 0, 10 ~ 80% (step: 1% )

Phase angle accuracy ..................................................... ± 2°

Internal operation delay ................................................. 1.5cycle

Ground/SEF Directional detect function

Pole voltage ................................................................... Zero sequence voltage Vo

Source side VTs must be Wye connection.

Directional detec ........................................................... Disable, Enable

Max. Torque Angle ........................................................ 0 ~ 345° (step: 15° )

Min. Operation voltage.................................................. 0, 10 ~ 80% (step: 1% )

Phase angle accuracy ..................................................... ± 2°

Internal operation delay ................................................. 1.5cycle

Phase/Ground/SEF Cold Load Pickup Blocking function

Pickup level ................................................................... 1 ~ 20 MTC (step: 1 MTC)

Pickup current restore time ........................................... 0.0 ~ 180.0sec (step: 0.1sec)

CLPU reset time ........................................................... 0.01 ~ 60.00sec (step: 0.01sec)

Pickup level accuracy .................................................... 5%

Timing accuracy ............................................................ ± 5% or ± 20msec

Page 15: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 15 ENHANCED TECHNOLOGY

SECTION function

Function ......................................................................... Disable, Enable

Auto closing .................................................................. Disable, Enable

Section type ................................................................... V-T, O-T

Close direction ............................................................... Always, Source, Load

Open delay time ............................................................. 0.1 ~ 25.5sec (step: 0.1sec)

Close waiting time ......................................................... 1 ~ 255sec (step: 1sec)

Close delay time ............................................................ 1 ~ 255sec (step: 1sec)

Lockout time .................................................................. 1 ~ 255sec (step: 1sec)

Source side lockout time ............................................... 1 ~ 255sec (step: 1sec)

Source side reset time .................................................... 1 ~ 255sec (step: 1sec)

Block Time .................................................................... 1 ~ 255sec (step: 1sec)

Operation Time .............................................................. 1 ~ 4 time (step: 1 time)

Phase Unbalance

Angle difference ............................................................ OFF, 5 ~ 80° (step: 5°)

Detect delay time ........................................................... 0.0 ~ 180.0sec (step: 0.1sec)

Phase Open/Lost

On Level ........................................................................ phase voltaeg 70 ~ 85% (step: 5%)

Off Level ....................................................................... phase voltage 30 ~ 75% (step: 5%)

Detect delay time ........................................................... 0.0 ~ 180.0sec (step: 0.1sec)

Live line/Dead line detect(Communication)

Live line detect value .................................................... 0.10 ~ 0.90pu (step: 0.01pu)

Deect delay time ............................................................ 0.5sec fixed

Operation counter

Alarm function .............................................................. Off, On

Reset counter ................................................................ 0 ~ 65535 (step: 1)

Alarm counter ................................................................ 0 ~ 20000 (step: 1)

Battery auto load test

Test cycle ....................................................................... 1 ~ 72 hour (step: 1hour)

Page 16: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

16 ENHANCED TECHNOLOGY

Power Quality Monitoring - PQM

PQM function ............................................................... Disable, Enable

Sag pickup level ............................................................ 0(OFF), 0.50 ~ 0.99pu (step: 0.01pu)

Sag delay time ............................................................... 0.5 ~ 10.0cycle (step: 0.5cycle)

Swell pickup level ......................................................... 0(OFF), 1.01 ~ 1.50pu (step: 0.01pu)

Swell delay time ............................................................ 0.5 ~ 10.0cycle (step: 0.5cycle)

Interruption .................................................................... 0(OFF), 0.10 ~ 0.49pu (step: 0.01pu)

Interruption .................................................................... 0.5 ~ 10.0cycle (step: 0.5cycle)

Voltage harmonic pickup level ...................................... 0(OFF), 0.5 ~ 100.0% (step: 0.1%)

Current harmonic pickup level ...................................... 0(OFF), 0.5 ~ 100.0% (step: 0.1%)

Harmonic delay time ..................................................... 0.2 ~ 60.0sec (step: 0.1sec)

Voltage unbalance pickup level ..................................... 0(OFF), 1 ~ 100% (step: 1%)

Voltaeg unbalance delay time ........................................ 0.1 ~ 60.0sec (step: 0.1sec)

Current unbalance pickup level ..................................... 0(OFF), 1 ~ 100% (step: 1%)

Current unbalance delay time ........................................ 0.1 ~ 60.0sec (step: 0.1sec)

Low voltage pickuip level ............................................. 0(OFF), 0.30 ~ 0.95pu (step: 0.01pu)

Low voltage delay time ................................................. 0.0 ~ 180.0sec (step: 0.1sec)

Over voltage picup level................................................ 0(OFF), 1.05 ~ 1.50pu (step: 0.01pu)

Over voltage delay time ................................................ 0.0 ~ 180.0sec (step: 0.1sec)

Low frequency pickup level .......................................... 0(OFF), 46.00 ~ 59.98Hz (step: 0.01Hz)

Low frequency delay time ............................................. 0.03 ~ 10.00sec (step: 0.01sec)

Phase overcurrent pickup level ...................................... 0(OFF), 50 ~ 630A (step: 5A)

Phase overcurrent delay time ........................................ 0.0 ~ 180.0sec (step: 0.1sec)

Ground overcurrent pickup level ................................... 0(OFF), 25 ~ 315A (step: 5A)

Ground overcurrent delay time ...................................... 0.0 ~ 180.0sec (step: 0.1sec)

Current unbalance/THD detect Min. value ................... 0 ~ 630A (step: 1A)

Switch Contact wear

Contact wear detect ....................................................... Off, On

Pickup wear ................................................................... 0.0 ~ 50.0% (step: 0.1%)

Rated system ................................................................. 15㎸, 27㎸, 38㎸

Rated interruption capacity(㎸) ..................................... 5.0 ~ 50.0㎸ (step: 0.1㎸)

Number of Max. interruption ........................................ 1 ~ 999 (step: 1)

Phase A contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)

Phase B contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)

Phase C contact wear ..................................................... 0.0 ~ 100.0 % (step: 0.1%)

Page 17: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 17 ENHANCED TECHNOLOGY

TD Monitoring

TD1 rating ..................................................................... 20, 200

TD1 ratio ............................................................... ....... 1 ~ 3000 (step: 1)

TD1 offset .............................................................. ....... -10000 ~ +10000 (step: 1)

TD1-1 type ............................................................ ....... Under or Over

TD1-1 pickup value .............................................. ....... 0(OFF), 0.1 ~ 35.0V (step: 0.1V)

TD1-1 delay time ................................................... ....... 0.01 ~ 600.00sec (step: 0.01sec)

TD1-2 type ............................................................ ....... Under or Over

TD1-2 pickup value .............................................. ....... 0(OFF), 0.1 ~ 35.0V (step: 0.1V)

TD1-2 delay time ................................................... ....... 0.01 ~ 600.00sec (step: 0.01sec)

※. NOTE : There are 4 more channels (TD2 ~ TD5) the same as above.

Zero Sequence Voltage(V0) detect

Pickup level detect ..................................................... ... 0(OFF), 0.05 ~ 1.20pu (step: 0.01pu)

Detect dela time ......................................................... ... 0.1 ~ 6000.0sec (step: 0.1sec)

Page 18: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

18 ENHANCED TECHNOLOGY

2.5. Event Recorder

Operation event recording device

Trigger source

Switch CLOSE

Switch OPEN

Earth Close(ECLOSE)

Earth Open(EOPEN)

Storage capacity : Total 256 events

Fault event recording device

Trigger source

Taget A, B, C, N phases, SEF

Fault detect : Instantaneous fault, Permenant fault

Detect direction : Forward, Reverse direction

Fault Sequence

Data channel

Current 4, Voltage 3, Frequency, Logic input status 32, Output relay 16channel, Input

16channel

Storage capacity : Total 256 events

Fault wave capture

Trigger source

Fault wave capture point

Fault current

Sampling ratio : 128x20, 64x40, 32x80, 16x160

Storage capacity: 8 fault waves of 20 cycle (20cycles8EA).

System Event Recording device

Trigger source

52A contact

Input/Output status change

Front panel control

AC power supply

External control

Page 19: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 19 ENHANCED TECHNOLOGY

External input status

System alarm

Sleep mode

Trigger time : each 1/4 cycle

Trigger type : Pickup and Dropout

Storage capacity : Last 2048 events

Set Change Event Recording device

Trigger source

Global setting change

Primary group setting change

Alternate group setting change

Storage capacity : Total 100events

Load Profile

1) Average Load/ Minute

Trigger source

Demand current(A, B, C, G)

Demand real power(A, B, C, 3ф)

Demand reactive power (A, B, C, 3ф)

Trigger time : 1, 2, 3, 4, 5, 6, 10, 12, 15, 20 or 30 min.

Storage capacity : Total 1024events (Storage Capacity : Total 1024 Events)

2) Peak Load/ Hour

Trigger source

Demand current(A, B, C, G)

Demand real power(A, B, C, 3ф)

Demand reactive power(A, B, C, 3ф)

Trigger time : Every 1 hour

Storage capacity : Total 1024 events, 42 days

3) Peak Load/ Day

Trigger source

Demand current(A, B, C, G)

Demand real power(A, B, C, 3ф)

Demand reactive power(A, B, C, 3ф)

Trigger time : Daily

Page 20: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

20 ENHANCED TECHNOLOGY

Storage capacity : Total 1024 events, 1024days

DIAGNOSTIC EVENT RECORDER

Trigger source

DSP failure

ADC failure

RTC failure

Memory failure

Flash-Rom failure

Circuit voltage failure

Globlal setting failure

Primary setting failure

Alternate setting failure

Event failure

Count failure

DO failure

Close failure

Open failure

Trigger time : evey 1/4 cycle

Trigger type : Pickup and Dropout

Storage capacity : Last 512 events

PQM event recording device (PQM EVENT RECORDER)

Trigger source

PQM pickup element

Storage capacity : Total 100events

Page 21: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 21 ENHANCED TECHNOLOGY

2.6. Maintenance

COUNTER

Number of System restart : 0 ~ 65534

Number of maintenance : 0 ~ 65534

Number of Operation : 0 ~ 65534

Numer of fault: 0 ~ 65534

Number of Instantaneous current change detect : 0 ~ 65534

Number of PQM detect: 0 ~ 65534

Switch contact wear

Phase A wear: 0.0 ~ 100.0%

Phase B wear: 0.0 ~ 100.0%

Phase C wear: 0.0 ~ 100.0%

2.7. Communication

Table 2-2. Communication

Side panel Port1

RS232, 1200-19200bps, None, Odd or Even Parity, 7 or 8 Data bits, 1or 2

Stop bit

DNP 3.0, Modbus and IEC60870-5-101 protocol

Side panel Port2

RS485/422, 1200-19200bps, None, Odd or Even Parity, 7 or 8 Data bits,

1 or 2 Stop bit

DNP 3.0, Modbus and IEC60870-5-101 Protocol

Side panel Port3 RJ-45, 10BASE-T/100BASE-T

DNP 3.0, Modbus and IEC60870-5-104 Protocol

Front panel PortF RS232, 1200-57600bps, No Parity, 8 Data Bits, 1 Stop bit

ETR300 interface software

Page 22: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

22 ENHANCED TECHNOLOGY

3. Dimension and structure

OUT101

OUT102

OUT103

+ IN101

IN102

IN103

IN104

++

+OUT104

RCV

Antenna

GPS

PORT RF

Antenna

A04A05A06A07A08A09A10

A03

A02

A01

B05B06B07B08

B04

B03

B02

B01

TX

RX

N.C

LOCKED

CONTROL

ENABLED

REMOTE

SECTION

AUX1

TAG

HOT LINE

ENABLEDRESET

LOCKOUT

TIE CYCLE

SEC/TIE LOCKOUT

SEC CYCLE

ETR300 -S02

ABC / RST LIVE

A Phase Unbalance

C Phase Unbalance

VA / VR

VB / VS

VC / VT

CHECK

BATT'RESET

LAMP TEST

Control & Communication Unit

PORT F

BATTERY

CHARGER

ENT

ESC

FUN

FI

TEST

SEF

ENABLEDENABLED

GROUND

ENABLED

PROTECTION

SETTINGS

ALTERNATE

DOWN

UP

950-08

950-10

XP

OR

TR

J45

950

F01

F02

F03

F04

F05

F06

G01

G02

G03

G04

G05

G06

G07

G08

PORT1

PORT3

PORT2

1

9

LINK

12

32TX

2RX

1TX

1RX

5559

1

5559

1

5559

1

5559

1

5559

1

5559

1

POWER IN

K01

K02

K03

K04

-BAT

+BAT

AC 24V

AC 24V

POWER SUPPLY

INPUTS

OUTPUTS

MONITORS

12

34

CN7

1,3:P

2,4:N

N

P

J01J02J03J04

OUT205

OUT206

H01H02H03H04H05H06

TRIP & CLOSE

CN6

CN5

CN4

CN3

CN2

CN1

12

34

12

34

12

34

12

34

14

36

15

48

V11

V12

V13

V21

V22

V23

V0

+SG

-485

9:N/C

7:RTS

8:CTS

6:DSR

3:TXD

1:DCD

4:DTR

2:RXD

5:GND

485

10M/100M

1:DC02

2,4:COM

1:+12V

3,4:GND

1,3:DC(+)

2,4:DC(-)

3:IN201

2,5:+12V

3,6:GND

1:IN204

4,8:COM

3,7:OUT204

2,6:OUT202

1,5:N/C

3:DC03

2:DC01

4:IN205

2:IN202

4:+12V

1:IN203

I01

I02

I03

IN

Ise

E01

E02

E03

E04

E05

E06

E07

E08

E09

E10

5559

1

950

950

OPENCLOSE

REVERSE POWER

L1

L2

L3

L4

MANUAL LOCK

RX / TX

RUN

DIAG/ERROR

AC SUPPLY

GROUND

SEF

C FAULT

A FAULT

B FAULT

B Phase Unbalance

Figure 3-1. Dimension and Structure

Page 23: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 23 ENHANCED TECHNOLOGY

4. External Input/Output Connector

ETR300 provides terminals(connector) to connect control and modem, the termainal arrangement

is as belows;

5559

1

5559

1

5559

1

950

5559

1

5559

1

950

5559

1

POWER IN

K01 K02 K03 K04

-BAT

+BAT

AC 24V

AC 24V

POWER SUPPLYINPUTSOUTPUTSMONITORS

12

34

CN7

1,3:P

2,4:N

NP

J01 J02 J03 J04

OUT205 OUT206

H01 H02 H03 H04 H05 H06

TRIP & CLOSE

CN6 CN5 CN4 CN3 CN2 CN1

5559

1

12

34

12

34

12

34

12

34

1

4

3

6

1

5

4

8

V11 V12 V13 V21 V22 V23 V0

+ SG-485

9:N/C

7:RTS 8:CTS6:DSR

3:TXD1:DCD 4:DTR2:RXD

5:GND485

10M/100M

1:DC02

2,4:COM

1:+12V

3,4:GND

1,3:DC(+)

2,4:DC(-)

3:IN201

2,5:+12V

3,6:GND

1:IN204

4,8:COM

3,7:OUT204

2,6:OUT202

1,5:N/C

3:DC03

2:DC01

4:IN205

2:IN202

4:+12V

1:IN203

I01 I02 I03 IN Ise

E01 E02 E03 E04 E05 E06 E07 E08 E09 E10

OUT101 OUT102 OUT103

+

IN101 IN102 IN103 IN104

+ + +OUT104

RCV Antenna

GPS PORT RF

Antenna

A04 A05 A06 A07 A08 A09 A10A03A02A01 B05 B06 B07 B08B04B03B02B01

TX

RX

N.C

950-10 950-08

XPORTRJ45950

F01 F02 F03 F04 F05 F06 G01 G02 G03 G04 G05 G06 G07 G08

PORT1 PORT3PORT2

1

9

LINK

1 2 32TX

2RX

1TX

1RX

Figure 4-1. External Input/Output connector

Table 4-1.Cable size for connecter

Item Size( ㎟ ) Length( ㎜ ) Connecter name Remark

Current 1.25(50/0.18) 300 AkZ 960-10P

Power supply " " AkZ 960-4P

Digital Input 0.75(12/0.18) " Molex 5557-6P,4P

Digital Output " " AkZ 950-6P

Voltage " " AkZ 960-6P,8P

Page 24: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

24 ENHANCED TECHNOLOGY

4.1. Current Input(Connector type:STLZ960-10)

Current connecter‟s terminal no. 1 starts with phase A and follows by B, C, N, SEF phase turn.

ETR300 current terminal provides all phase name.

I01 I02 I03 IN Ise

E01 E02 E03 E04 E05 E06 E07 E08 E09 E10

Figure 4-2. Current connector

Table 4-2. Current connecter pin

IO1 IO2 IO3 IN Ise

A

phase

B

phase

C

phase

N

phase

SEF

4.2. Voltage Input(Connector type:STLZ960-6P,8P)

Voltage connector has source side 3 phases(A,B,C) and load side 3 phases(R,S,T) as belows;

I01 I02 I03 IN Ise

E01 E02 E03 E04 E05 E06 E07 E08 E09 E10

Figure 4-3. Voltage connector

Table 4-3. Voltage connecter Pin

V11 V12 V13

A

Phase

B

Phase

C

Phase

V21 V22 V23 V0

R

Phase

S

Phase

T

Phase

Zero

Sequence

Page 25: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 25 ENHANCED TECHNOLOGY

4.3. Digital Output(DO)

Digital Output has total 8 output relays. Digital Output connecter delivers the control single from

the controller and its construction is as belows.

950

OUT205 OUT206

H01 H02 H03 H04 H05 H06

Figure 4-4. Digital Output Connector

Table 4-4. Digital Output Connecter Pin

Pin

Number Signal

Pin

Number

2 Close 3

5 Open 6

4.4. Digital Input(DI)

Digital Input receives 16 status signals through insulated electric contacts. This is how increasing

DI part surge withstand capability and provide more insulation to Main module where signali is

connected but weak to surge voltage. Digital Input connector is the part where receiving status

signal from control part and its structure is as belows.

1 1

3:IN201

2,5:+12V

3,6:GND

1:IN204

4:IN205

2:IN202

4:+12V

1:IN203

CN3 CN2

12

34

1

4

3

6

Figure 4-5. Digital Input Connector

Table 4-5. Digital Input Connecter Pin

Connecter Pin

Number Signal Connecter

Pin

Number

CN2

01 Open

CN2

04

02 Close 04

03 Lock 04

CN3 01

Door

Open CN3 02,05

04 Spare 02,05

Page 26: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

26 ENHANCED TECHNOLOGY

4.5. Power supply input& Modem power supply output

Power supply connecter has ETR300 operation power supply terminal and modem power supply

terminal. Each connecter provides its name and pin number 1 is for +24V input and pin number 2

is Grond input.

NP

P : DC 24V +Terminal

N : DC 24V GND

Figure 4-6. Power Supply Connecter

4.6. Remote Communication Port(modem connection)

Modem communication port is D-SUB 9 pin male type and all pins are connected except the

number 9 pin (Ring Indicator)

5 1234

6789

Figure 4-7. Remote Communication Port

Table 4-6. Remote Communication Port Pin

Pin No. Signal Info

1 DTR : Data Terminal ready

2 RxD : Received Data

3 TxD : Transmitted Data

4 DTR : Data Terminal Ready

5 GND : Ground

6 DSR : Data Set Ready

7 RTS : Request To Send

8 CTS : Clear To Send

9 RI : Ring Indicator

Page 27: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 27 ENHANCED TECHNOLOGY

4.7. 485 Communication Port

485 Communication Port has 3 pins and its construction is as follows.

+ SG-485

1 2 3

2T

2R

485

Figure 4-8. 485Commnication Port

Table 4-7. 485Communication Port Pin

Pin No.

485+

485-

SG

4.8. Ethernet Port(RJ45)

Ethernet Port (RJ-45) has 8 pins and its constructions is as follows.

XPORTRJ45

LINKBPS

Figure 4-9. Ethernet Port

Table 4-8. EthernetPort Pin

Pin No. Wire Color 10Base-T Signal

100Base-TX Signal

1 White/Green Transmit+

2 Green Transmit-

3 White/Orange Receive+

4 Blue Unused

5 White/Blue Unused

6 Orange Receive-

7 White/Brown Unused

8 Brown Unused

Page 28: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

28 ENHANCED TECHNOLOGY

5. User Interface Panel

User Interface Panel uses LCD(204) and keypad to select functions and monitors switch status,

and also with LEDs, selected functions status and switch operation status can be checked.

User Interface Panel provides following functions;

Switch control

Control status check

System status check

Metering value check

Saved records check in ETR300

Set check and change in ETR300

OPENCLOSE

REVERSE POWER

L1

L2

L3

L4

RX / TX

RUN

DIAG/ERROR

AC SUPPLY

GROUND

SEF

C FAULT

A FAULT

B FAULT

B Phase Unbalance

A Phase Unbalance

C Phase Unbalance

VA / VR

VB / VS

VC / VT

CHECK

BATT'RESET

LAMP TEST

Control & Communication Unit

PORT F

BATTERY

CHARGER

ENT

ESC

FUN

FI

TEST

SEF

ENABLEDENABLED

GROUND

ENABLED

PROTECTION

SETTINGS

ALTERNATE

DOWN

UP

LOCKED

CONTROL

ENABLED

REMOTE

SECTION

AUX1

ENABLEDRESET

LOCKOUT

TIE CYCLE

SEC/TIE LOCKOUT

SEC CYCLE

ETR300 -S02

ABC / RST LIVE

AUX2

Figure 5-1. User Interface Panel

Page 29: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 29 ENHANCED TECHNOLOGY

5.1. Construction

Panel consists of following 12 parts ;

Operation section

Local control section

Menu control section

Other control section

Fault indication section

Line status indication section

Section status section

System diagnostic section

Battery status section

PCL status section

Other status section

Spare ports section

5.1.1. Operation Section

OPEN

Press [OPEN] button to send Trip signal to Switch.

CLOSE

Press [CLOSE] button to send Close signal to Switch.

ETR300 has close time delay and the close operation can be conducted after a set time. Set time

range is from 0.00 ~ 600.00 sec.

POSITION LED

Switch staus is indicated. Position LED is operated based on 52a contact.

Figure 5-2. Operation Selection

Page 30: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

30 ENHANCED TECHNOLOGY

5.1.2. Local Control Section

Control panel shows all the status of function. If a function is enabled, LED is ON, and when

disabled, LED is OFF. Button changes Enable to Disable vice versa.

SEF

ENABLEDENABLED

GROUND

ENABLED

PROTECTION

SETTINGS

ALTERNATE

LOCKED

CONTROL

ENABLED

REMOTE

SECTION

AUX1

ENABLEDRESET

LOCKOUT

AUX2

Figure 5-3. Local Control Section

Protection(Enable/Disable)

When Enable(LED ON), phase fault detecting is enabled and when Disable(LED OFF), phase

fault detecting is disabled.

NOTE : When Protection is enabled, all protection of ETR300 is on operation, however,

Ground fault and SEF(Sensitive Earth Fault) function shall be set individually on font panel.

Ground (Enable/Disable)

When LED is on, ground fault detecting is enabled and when LED is off, ground fault detecting is

disabled. It is only available when Protection is enabled. Although Ground LED is on, protection

is disabled, ground fault detection is not conducted.

SECTION(Enable/Disable)

When LED is ON, SECTION is enabled, and when LED is OFF, SECTION is disabled.

Page 31: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 31 ENHANCED TECHNOLOGY

Operation select(Local/Remote)

When LED is ON, Remote and Local operation are all available. When LED is OFF, only Local

operation is available.

Operation Lock(Lock/Unlock)

When it is Unlock, local and remote operations are all available. When it is Lock, local and

remote operations are not available.

NOTE : Even if operation lock status, Open, Lamp test, Battery load test and Menu

controlare all available.

ALTERNATE SETTINGS(Select)

When ALTERNATE SETTINGS LED is ON, Group setting becomes Alternate setting and the

Alternate setting is activated. When the LED is OFF,Group setting becomes Primary setting and

the primary setting is activated.

SEF(Enable/Disable)

When LED is ON, SEF is enabled. When LED is OFF, SEF is disabled. Although SEF is

enabled,Protoection is not enabled, SEF is not activated.

SEC/TIE LOCKOUT(Unlock)

SEC/TIE LOCKOUT is dismissed.

AUX(1/2)

Aux. function button.

Page 32: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

32 ENHANCED TECHNOLOGY

5.1.3. Menu Control Section

20×4 LCD is used to check setting, metering and

events, details informations are refer to “5. Operation

manual(How to use LCD)”.

20×4 character LCD

4 operation button(Increase, Decrease, Function

selection)

ENT

ESC

FUN

DOWN

UP

Figure 5-4. Menu Control Section

5.1.4. Other Control Section

CHECK

BATT'RESET

LAMP TEST

FI

TEST

Figure 5-5. Other Control Section

Lamp Test Button

Normal : Press the button to check all Lamps.

FI occurred : It resets FI Target by pressing the button.

Battery

It takes 5 seconds to check battery and charging circuit. When pressing the button and if AC

power supply is provided, charging circuit is disconnected and connects a load resister to battery

and check the charging circuit.

FI Test

When pressing FI Test button, trip test begins beased on set value.

Page 33: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 33 ENHANCED TECHNOLOGY

5.1.5. Fault Indication Section

In case of Permenant or Instantaneous fault, corresponding LED

is ON. LED lamp can be off by manually from local by pressing

FI Reset button or from remote by sending a signal. Otherwise,

LED lamp will be on although H.V. line becomes normal.

GROUND

SEF

C FAULT

A FAULT

B FAULT

Figure 5-6. Fault Indication

Section

5.1.6. H.V. line status indication section

Phase Unbalance lamp

Phase A,B,C Unbalance are indicated.

Under condition that source side and load side are all live line

and switch is open status, check angles, if it meets then, it is OK,

otherwise, it is unbalanced.

Although it is unbalanced, control is still available. Operater

shall decide an operation.

VA / VR

VB / VS

VC / VT

B Phase Unbalance

A Phase Unbalance

C Phase Unbalance

ABC / RST LIVE

Live line lamp

Source side and load side live line status are indicated.

More than one phase voltage is higher than an Off Level of

Disconnect line/Open phase, it is Live line. And all 3 phases are

less than that, it is Dead line. Operater shall decide an operation.

Figure 5-7. Disconnect/Open

phase Lamp

Phase Open/Loss lamp

Source and load side Phase A, B, C Open/Loss phase are

indicated. In case that 1 or 2 phases voltage is less than Off

Level of Disconnect/Open phase, it is determined as

Disconnet/Open phase. LED will be Off when the voltages are

higher than On Level.

Page 34: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

34 ENHANCED TECHNOLOGY

5.1.7. System Diagnostic Section

ETR300-R Diagnostic is displayed. RUN Lamp(green) indicates that ETR300 has passed the

internal diagnostic test and does not have any problem. RX/TX Lamp(Red) indicates the

communication state of ETR300

RUN : It indicates the operation status. In normal

operation, it flicker periodically. In system problem

case , it is lighting or turned off.

DIAG/ERROR : Turn on with abnormality of Self

Diagnostic.

RX : Turn on when transmit data

TX : Turn on when transmit data

RX / TX

RUN

DIAG/ERROR

Figure 5-8.System Diagnostic Lamp

5.1.8. Section Status Section

Indicates present staus of set section function process.

SEC Sequence: Indicates Section operation status.

TIE Sequence: Indicates Tie sequence operation status.

SEC/TIE Sequence End : Indicates sequence Lockout

status.

TIE CYCLE

SEC/TIE LOCKOUT

SEC CYCLE

Figure 5-9. Section Status Lamp

5.1.9. Battery Status Section

The system power status of ETR300 is displayed. When ETR300 is supplying external power, AC

SUPPLY Lamp is on. CHARGER lamp shows the charging status of ETR300 and the BATTERY

lamp shows the battery status of ETR300.

AC SUPPLY : Indicates the external AC power supply

status.

CHARGER : Turn on, when the charger status is

normal.

BATTERY : Turn on, when the battery status is

normal.

AC SUPPLY

BATTERY

CHARGER

Figure 5-10. Battery Status

Lamp

Page 35: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 35 ENHANCED TECHNOLOGY

5.1.10. User LED Section

LED can be indicated according to the user setting.

LED logic can be set in ‘ETR300 interface software‟

L1

L2

L3

L4

Figure 5-11. User Lamp

5.1.11. Other Status Section

REVER POWER

In reverse current case, the REVER POWER lamp becomes

On.

REVERSE POWER

Figure 5-12. Rever Power lamp

5.1.12. Port F Section

This connection port is for the communication with administration program. It obtains setting

change, control and others events.

TYPE : RS232C(male)

Pin 2 : RXD

Pin 3 : TXD

Pin 5 : GND

Pin 1,4,6,7,8,9 : N/G

Location : Front panel

PORT F

Figure 5-13. Port F

Page 36: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

36 ENHANCED TECHNOLOGY

5.2. Operation Manual (LCD instruction)

5.2.1. LCD Screen

20 4 character LCD which has back-light support, is used for a user to operate conveniently and

to check operation status clearly.

5.2.2. Control button

LCD Control button is composed of four basic keys(increase, decrease, function/cancel, ENT).

Following table is explanation of the keys.

Table 5-1.Control Button

Button Explanation

ESC

FUN

FUNC/CANCEL

Move to menu selection mode from display mode and move to prior menu from

sub-menu. When press the button in Main Menu it is changed into display

mode. When this key is operated after changed the value, all changed value are

reverted to original setting value.

ENT

ENT

It is used for menu selection or setting change. In menu selection screen this

button is used for menu selection function. In setting change status moves to

menu mode by pressing this button (it operates in toggle method in menu

selection.setting change)

UP

INCREASE

It is used to move the menu into above side or to increase the setting point. As

all menu has circulated function, from the top menu moves into the lowest

menu. In setting change case, after highest setting value comes the lowest

setting value. A level is increased by pressing the button and it is increased

quickly by pressing the button over 2 seconds.

DOWN

DECREASE

It is used to move the menu or to decrease the changed value.

This button has circulated function for menu change/setting change as

[increase] button. A level is decreased by pressing the button and it is decreased

quickly by pressing the button over 2 seconds.

Page 37: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 37 ENHANCED TECHNOLOGY

5.2.3. Menu structure tree

Screen structure consists Initial Logo and Main menu.

Initial screen and all menu are round robin algorithm.

Menu screen is composed of setting and event management menu.

[BI-CCU(S) FOR DAS]

SECTION : DISABLE

S/W STATUS : OPEN

[ RESET ]

A:00000 00.0/00.0

B:00000 00.0/00.0

C:00000 00.0/00.0

N:00000[00.000-0000]

[초기 화면] [메뉴 화면]

[MAIN MENU]

>2.GROUP SETTING

>1.GLOBAL SETTING

>3.EVENT

>4.MAINTENANCE

>5.TIME

>6.STATUS

>7.METERING

기능

취소

Figure 5-14. Initial Logo and Main Menu

Page 38: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

38 ENHANCED TECHNOLOGY

[MAIN MENU] >1.SYSTEM

>1.POWER LINE

2.CURRNET SENSING

3.VOLTAGE SENSING

>2.COMMUNICATION >1.PROTOCOL SETUP

>1.DNP1

2.DNP2

3.IEC870-5-101

4.IEC870-5-104

5.MODBUS

>1.GLOBAL SETTING

>2.PORT SETUP >1.PORT1(232)

2.PORT2(485)

3.PORT3(ETHERNET)

4.PORTF(232)

>3.EVENT RECORDER

>4.MONITORING

>1.PQM FUNCTION

2.INTERRUPT

3.SAG

4.SWELL

5.HARMONICS

6.CURR UNBALANCE

7.VOLT UNBALANCE

8.UNDER VOLTAGE

9.OVER VOLTAGE

10.UNDER FREQUENCY

>1.COMMON

>1.LOGIC TIMER

2.PULSE TIMER

3.PULSE COUNTER >5.PLC

>2.DI/DO >1.INPUT DEBOUNCE

2.OUTPUT PULSE TIME

>1.FACTORY DEBUG >6.OTHERS

>2.GROUP SETTING >1.PRIMARY

>2.ALTERNATE >3.DIRECTION

>*.SAVE SETTING

>1.PHASE

2.GROUND

3.SEF

>4.F.I SETTING TIME

>5.F.I RESET

>7.DELTA I

>8.OVER CURRENT

>3.EVENT

>1.OPERATION

2.FAULT

3.FAULT CYCLE

4.SYSTEM

5.SET CHANGE

6.AVER.LOAD/MIN

7.PEAK.LOAD/HOUR

8.PEAK.LOAD/DAY

9.DIGNOSTIC

10.PQM

11.CLEAR SAVED DATA

>4.MAINTENANCE >1.COUNT

>2.INTERRUT TIME

>4.DATA RESET

>1.CCU

2.OPERATION

3.FAULT

4.DELTA I

5.PQM

>*.SAVE SETTING

>1.PICKUP CURRENT

>3.CONTACT WEAR >1.CCU COUNT

2.OPERATION COUNT

3.FAULT COUNT

4.DELTA I COUNT

5.PQM COUNT

6.COUNT ALL

7.INTERRUT TIME

8.CONTACT WEAR

9.ENERGY

10.ABOVE ALL

>5.CCU INFO

>6.F.I TEST

>1.SWITCH

2.INPUT PORTS

3.OUTPUT PORTS

>6.STATUS

>5.TIME

>7.METERING

>1.CURRENT

2.VOLTAGE

3.FREQUENCY

4.POWER

5.ENERGY

6.DEMAND

7.UNBALANCE

8.HARMONICS

9.TRUE R.M.S

10.TD

11.CCU SEF

>1.PHASE DIFF

>2.OPERATION COUNT

>3.CONTACT WEAR

>4.BATTERY TEST

>5.PQM

>6.TD MONITOR

>7.V0 DETECT

>6.SECTION

>2.INRUSH RESTRAINT

Figure 5-15. Menu Tree Structure

Page 39: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 39 ENHANCED TECHNOLOGY

[MAIN MENU] >1.SYSTEM >1.POWER LINE

2.CURRENT SENSING

3.VOLTAGE SENSING

4.CB OPENING TIME

>2.COMMUNICATION >1.PROTOCOL SETUP

>1.DNP3

2.IEC870-5-101

3.IEC870-5-104

4.MODBUS

>1.GLOBAL SETTING

>1.PORT1(232)

2.PORT2(485)

3.PORT3(ETHERNET)

4.PORTF(232)

>3.EVENT RECORDER

>4.MONITORING

>1.COMMON

>1.LOGIC TIMER

2.PULSE TIMER

3.PULSE COUNTER >6.PLC

>2.DI/DO >1.INPUT DEBOUNCE

2.OUTPUT PULSE TIME

>1.TIME DISP’TYPE

2.PANEL SLEEP TIME

3.FACTORY DEBUG

>7.OTHERS

>2.GROUP SETTING >1.SELECT SETBANK

>3.ALTERNATE

>18.DIRECTION

>*.SAVE SETTING

>1.PHASE

2.GROUND

3.SEF

4.NEG SEQ

>22.USER CURVE

>3.EVENT

>1.OPERATION

2.FAULT

3.FAULT CYCLE

4.SYSTEM

5.SET CHANGE

6.AVER.LOAD/MIN

7.PEAK.LOAD/HOUR

8.PEAK.LOAD/DAY

9.DIGNOSTIC

10.PQM

11.PD

>4.MAINTENANCE >1.COUNT

>2.INTERRUT TIME

>4.DATA RESET

>1.CCU

2.OPERATION

3.FAULT

4.DELTA I

5.PQM

6.PD >3.CONTACT WEAR

>1.CCU COUNT

2.OPERATION COUNT

3.FAULT COUNT

4.DELTA I COUNT

5.PQM COUNT

6.PD COUNT

7.COUNT ALL

8.INTERRUT TIME

9.CONTACT WEAR

10.ENERGY

11.ABOVE ALL

>5.CCU INFO

>1.RECLOSER

2.INPUT PORTS

3.OUTPUT PORTS

>6.STATUS

>5.TIME

>7.METERING

>1.CURRENT

2.VOLTAGE

3.FREQUENCY

4.POWER

5.ENERGY

6.DEMAND

7.UNBALANCE

8.HARMONICS

9.TRUE R.M.S

10.PD

11.TD

12.CCU SEF

>1.SYNCHROCHECK

2.OPERATION COUNT

3.CONTACT WEAR

4.BATTERY TEST

>5.PQM

>6.TD MONITOR

7.V0 DETECT

>1.DIAL1

2.DIAL2 >3.DIALUP MODEM

>2.PORT SETUP

>5.LOOP CONTROL

>1.OPERATION

2.INTERVALS

3.PICKUP CURRENT

4.PHASE FAST

5.PHASE DELAY

6.GROUND FAST

7.GROUND DELAY

8.SEF ELEMENT

9.NEG SEQ FAST

10.NEG SEQ DELAY

11.H/C TRIP-PHA

12.H/C TRIP-GND

13.H/C TRIP-NEG

14.H/C LOCKUOT-PHA

15.H/C LOCKUOT-GND

16.H/C LOCKUOT-NEG

17.COLD LOAD PICKUP

>1.PQM FUNCTION

2.INTERRUPT

3.SAG

4.SWELL

5.HARMONICS

6.CURR UNBALANCE

7.VOLT UNBALANCE

8.UNDER VOLTAGE

9.OVER VOLTAGE

10.UNDER FREQUENCY

>1.USER CURVE 1

2.USER CURVE 2

3.USER CURVE 3

4.USER CURVE 4

>23.LIVE LOAD BLOCK

*.SAVE SETTING

>12.CLEAR SAVED DATA

>1.OPERATION

2.FAULT

3.SYSTEM

4.SET CHANGE

5.LOAD PROFILE

6.DIGNOSTIC

7.PQM

8.PD

9.ABOVE ALL

>2.PRIMARY

>1.UNDER VOLTAGE 1

2.UNDER VOLTAGE 2

3.OVER VOLTAGE 1

4.OVER VOLTAGE 2

>1.UNDER FREQUENCY

2.OVER FREQUENCY

>21.OTHER ELEMENT

>20.FREQUENCY

>19.VOLTAGE

>4.EDITBANK

>5.AUTO SGRP CHANGE

Page 40: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

40 ENHANCED TECHNOLOGY

5.2.4. GLOBAL Setting

SYSTEM

Set items related to system elements. Consists of POWER LINE, CURRENT SENSING,

VOLTAGE SENSING and CB OPENING TIME.

COMMUNICATION

Set the items related to the communication elements. Consists of PROTOCOL SETUP and PROT

SETUP.

EVENT RECORDER

Set the items related to the event recorder elements.

MONITORING

Set the items related to metering and maintenance. Consist of OPERATION COUNT, CONTACT

WEAR, BATTERY TEST, PQM, TD MONITOR and V0 DETECTION.

PLC

Set the items related to PLC (Progamable Logic Control) elementsConsist of COMMON and

DI/DO.

OTHERS

Set the items related to the others elements.

SAVE SETTING

Save all changed setting value.

Page 41: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 41 ENHANCED TECHNOLOGY

5.2.5. GROUP Setting

This menu is divided into Primary Group and Alternate Group for the convenience of the user and

according to the ON/OFF of „ALTERNATE SETTINGS‟ lamp of ETR300 panel the applied

group is selected.

(1) Select Set-group

It is composed of Primary group and Alternate group.

PRIMARY group : When „ALTERNATE SETTINGS‟ lamp is OFF, the set point of

Primary group is applied in the line operating element.

ALTERNATE group : When „ALTERNATE SETTINGS‟ lamp is ON, the set point of

Alternate group is applied in the line operation element.

SETTINGS

ALTERNATE

Ficture 5-16. PRIMARY group and ALTERNATE group

By using [ALTERNATE SETTINGS] button, can change the applied group of current protective

unit.

(2) Primary Setting

This menu set the items related to the line operating elements.

(3) Alternate Setting

This menu set items related to the line operating elements. Setting items are same with

“PRIMARY SETTING”.

[GROUP SETTING]

>1.PRIMARY

2.ALTERNATE

Page 42: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

42 ENHANCED TECHNOLOGY

5.2.6. Event

This menu displays the event information of ETR300. For more details refer the “8. Event”

5.2.7. Maintenance

This menu displays the maintenance information of ETR300.

COUNTER : Indicates counter information related to the system.

INTERRUT TIME : Displays the occurring accumulated time if interruption.

CONTACT WEAR : Display the connect life of the switch.

DATA RESET : Reset the datas related to Maintenance.

CCU INFO : Display the current information of ETR300

For more details refer the “10. Maintenance” .

5.2.8. Time

Check and set the current time.

5.2.9. Status

Display the current status and input output port status of the switch.

5.2.10. Metering

This menu displays the metering value. For more details, refer to “12. METERING” .

Page 43: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 43 ENHANCED TECHNOLOGY

5.3. LCD Menu Use

5.3.1. INITING screen

The main information of ETR300 is displayed in the initial screen, for the easy access and

understanding of the user.

To move to other initial screen, press [▲] [▼] button.

Press [FUN] button in initial screen to move to Main menu.

INITNG LOGO

Start-up screen1

① SENTION: Indicate the section function status (DISABLE/ENABLE).

② S/W STATUS: Indicate the switch status (OPEN/CLOSE).

③ SENTION Indicate the operation status

- RESET

- RUNNING

- LOCKOUT

NOTE :

When “WARING SYSTEM ERROR” is displayed,means that the control

section is in bad status. Finisht the operation immediately and contact to the

manufacturer.

Starut-up screen2

① Indicate the current of each phase(A,B,C,N).[A].

② Indicate the voltage of each phase(A,B,C,R,S,T). [kV].

③ Indicate SEF current[A].

④ Indicate the zero phase voltage[V].

A: ① ② / ②

B: ① ② / ②

C: ① ② / ②

N: ① [ ③ - ④]

[BI-CCU(S) FOR DAS]

SECTION : ① S/W STATUS : ②

[ ③ ]

[BI-CCU(S) FOR DAS]

SECTION : DISABLE

S/W STATUS : OPEN

[ RESET ]

A:00000 00.0/00.0

B:00000 00.0/00.0

C:00000 00.0/00.0

N:00000[00.000-0000]

Page 44: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

44 ENHANCED TECHNOLOGY

5.3.2. Main Menu

In the initial menu, press [FUN] button, it is moved into Main menu. If press [FUN] button in

main menu, it is moved to the initial menu. Main menu has sub-menu as below.

MAIN MENU

Main Menu is composed of 7 submenus.

Select the submenu by using [▲] [▼] key.

Move to the submenu by pressing [ENT] key.

As the above explanation, you can move or select the submenu..

5.3.3. View Example

Move to “ MAIN MENU / STATUS / INPUT PORTS” to see the external input port status.

The following screen is displayed.

MAIN MENU/ STATUS/ INPUT PORTS

LO/DEASSERT : Shows External Input is de-asserted,

HI/ASSERT : Shows External Input is asserted.

4 lines are displayed in the LCD screen.

See next line by using [▲] [▼] key .

[INPUT PORT]

IN 101 :LO/DEASSERT

IN 102 :LO/DEASSERT

IN 103 :LO/DEASSERT

IN 104 :LO/DEASSERT

IN 105 :LO/DEASSERT

IN 106 :LO/DEASSERT

IN 107 :LO/DEASSERT

IN 108 :LO/DEASSERT

IN 201 : HI/ASSERT

IN 202 : HI/ASSERT

IN 203 : HI/ASSERT

IN 204 : HI/ASSERT

IN 205 : HI/ASSERT

IN 206 : HI/ASSERT

IN 207 : HI/ASSERT

IN 208 : HI/ASSERT

[MAIN MENU]

>1.GLOBAL SETTING

2.GROUP SETTING

3.EVENT

4.MAINTENANCE

5.TIME

6.STATUS

7.METERING

Page 45: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 45 ENHANCED TECHNOLOGY

5.3.4. Setting Example

Change of Phase Pickup Current of line operating element of Primary setting.

1) Move to“MAIN MENU/ GROUP SETTING/ PRIMARY/ PICKUP CURRENT / PHASE”.

The following screen is displayed.

MAIN MENU/ GROUP SETTING/ PRIMARY/ PICKUP CURRENT / PHASE

Range OFF, 50 ~ 630A

Default 300 Step 5A

Set the Phase Pickup Current.

2) In the above screen, locate the cursor on Phase by using choose [▲] [▼] key and then press

the [ENT] key to change the set point.

3) Change in new setting point by using [▲] [▼] key.

By pressing [ENT] key, you can see the changed phase setting point.

NOTE : Be sure to save all changed set point in the menu “*. Setting Save”.

[PICKUP CURRENT]

>Phase: 400

Ground: 70

S.E.F: OFF

Page 46: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

46 ENHANCED TECHNOLOGY

5.3.5. Setting Save

Follow the following step to save all changed set point.

Move to “MAIN MENU/ GROUP SETTING/ PRIMARY / SAVE SETTING” and follow the

following step. (“Global Setting” menu and “Group Setting or Alternate” menu have the

“*.Setting Save” menu).

MAIN MENU / PRIMARY SETTING / SAVE SETTING

To save the changed setting value, press [ENT] button in screen ①. If

the change has succeed screen ③ is appeared.

If, there is nothing changed and select “*. SAVE SETTING”, the

screen ② is displayed.

NOTE :

Changed set value is applied if the changed set value is saved.

If changed set value saving is cancelled, previous value is

remained.

SETTING CHANGED

PRESS <ENT> TO SAVE

* NOTHING CHANGED *

[SAVE SETTING]

* SUCCESS *

Page 47: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 47 ENHANCED TECHNOLOGY

6. Global Setting

Locate the cursor on “1.GLOBAL SETTING” in the main menu, and move to this menu by

pressing [ENT]. GLOBAL SETTING menu has the following submenu.

NOTE : The changed setting point works after being saved.

When cancel the save, setting point maintain the previous value.

6.1. System

Locate the cursor on “1.SYSETM” in GLOBAL SETTING menu and move to this menu by

pressing [ENT] button. In this menu, various elements related to the system can be set. It has the

following submenu.

NOTE : Do not change the setting elements of SYSTEM , as they are set according to the

characteristics of recloser.

[SYSTEM]

>1.POWER LINE

2.CURRENT SENSING

3.VOLTAGE SENSING

[GLOBAL SETTING]

>1.SYSTEM

2.COMMUNICATION

3.EVENT RECODER

4.MONITERING

5.PLC

6.OTHERS

*.SAVE SETTING

Page 48: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

48 ENHANCED TECHNOLOGY

6.1.1. Power Line

Locate the cursor on “1.POWER LINE” in SYSTEM menu, move to this menu by pressing [ENT]

button. In this menu, enter the Line information of the device installation location.

GLOBAL SETTING / SYSTEM / POWER LINE / Frequency

Range 50, 60 ㎐

Default 50 Step ~

Select the nominal power system frequency. This value is used as a

default to set the optimal digital sampling rate.

GLOBAL SETTING / SYSTEM / POWER LINE / Phase Rotation

Range ABC, ACB

Default ABC Step ~

Select the phase rotation of the power system.

GLOBAL SETTING / SYSTEM / POWER LINE / Nominal Volt

Range 1000 ~ 30000V

Default 11500 Step 10V

Set the rated voltage of the power system

6.1.2. Current Sensing

Locate the cursor on 2.CURRENT SENSING” in SYSTEM menu, move to this menu by pressing

[ENT] button.

Enter the exact CT rate for the accurate metering and monitoring.

Enter the CT rate after changing the second side in 1 Amp.

GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Ratio

Range 1 ~ 2000

Default 1000 Step 1

Enter the CT rate.

GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Polarity

[POWER LINE]

>Nominal Volt: 11500

[1000~30000:10V]

[CURRENT SENSING]

>CT-Ratio: 1000

CT-Polarity: FOR

[1~2000:1]

[POWER LINE]

>Frequency: 50

Phase Rotation: ABC

[50/60Hz]

[POWER LINE]

Frequency: 60

>Phase Rotation: ABC

[ABC/ACB]

Page 49: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 49 ENHANCED TECHNOLOGY

Range Forward, Reverse

Default Forward Step ~

Enter the CT polarity.

GLOBAL SETTING / SYSTEM / CURRENT SENSING / ZCT-Ratio

Range 0(OFF), 0.1 ~ 1000.0

Default 133.3 Step 0.1

Enter the ZCT rate..

GLOBAL SETTING / SYSTEM / CURRENT SENSING / CT-Polarity

Range Forward, Reverse

Default Forward Step ~

Enter the ZCT pole direction

[CURRENT SENSING]

CZCT-Ratio: 1.0

>ZCT-Polarity: FOR

[FOR/REV]

[CURRENT SENSING]

>ZCT-Ratio: 133.3

ZCT-Polarity: FOR

0(OFF),0~1000.0:0.1

[CURRENT SENSING]

CCT-Ratio: 1000

>CT-Polarity: FOR

[FOR/REV]

Page 50: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

50 ENHANCED TECHNOLOGY

6.1.3. Voltage Sensing

Locate the cursor on “3.VOLTAGE SENSING” in the SYSTEM menu, move to this menu by

pressing the [ENT] button.

ETR300 has 2 Voltage Connectors. Voltage connectors are receiving Source side and Load side

line voltages. To measure received voltages, set Voltage connectors‟ Connect Type, 2nd Nominal

Voltage and VT Ratio.

According to the installed line VT, ETR300 performs the voltage metering, power calculation and

direction control of over current, and the line VT can be used to perform the Phase Sync Fail.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V Connect Type

Range NONE, WYE, DELTA

Default WYE Step ~

Select 1V(1st voltage connector).

NONE : VT uninstalled. Select NONE if Voltage Sensing item is

not used.

WYE : If Voltage Connect type of 1V is Y type, select WYE.

DELTA : If Voltage Connect type of 1V is Δ-type, select DELTA.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / Reference Phase

Range A, B, C

Default A Step ~

Enter base voltage of Voltage connector.

※. NOTE ) The connect phase of main bushing changes according to

the „Base Voltage of Voltage connector‟ and „phase

rotation of power system(MAIN MENU(COM)/

GLOBAL SETTING/ SYSTEM/ POWER LINE/

Phase Rotation)‟. “Table 6-1. Refer to the phase

selection according to the base voltage and phase

rotation”.

[POWER LINE]

>1V CON-Type: WYE

>Reference Phase: A

[A/B/C]

[VOLTAGE SENSING]

>1V CON-Type: WYE

Reference Phase: A

[NONE/WYE/DELTY]

Page 51: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 51 ENHANCED TECHNOLOGY

Table 6-1. Phase selection according to the base voltage and phase rotation.

Setting

Terminal

Base

Voltage REF A REF B REF C

Phase

Rotation ABC ACB ABC ACB ABC ACB

Device A Bushing - A A B B C C

Device B Bushing - B C C A A B

Device C Bushing - C B A C B A

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V 2nd(V)

Range 2.0 ~ 350.0V

Default 4.0 Step 0.1V

Enter the second rated voltage(V) of 1V(1st Voltage connector).

This setting is the second rated voltage that entered in the relay about

line rated voltage.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 1V Ratio

Range 10.0 ~ 6500.0

Default 3300.0 Step 0.1

Enter the VT rated rate of 1V(1st Voltage connector).

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V Connect Type

Range NONE, WYE, DELTA

Default WYE Step ~

Select the voltage type of system that input to 2V(2nd Voltage

Connector) .

NONE : VT non installed. Select NON if Voltage Sensing item is

not used.

WYE : If Voltage Connect Type of 2V is Y-Type, Select WYE.

DELTA : If Voltage Connect Type of 2V is Δ-Type, Select DELTA.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V 2nd(V)

[VOLTAGE SENSING]

>2V CON-Type: WYE

2V 2nd(V): 4.0

[NONE/WYE/DELTY]

[VOLTAGE SENSING]

>1V 2nd(V): 4.0

>1V Ratio: 3300.0

[10.0~6500.0:0.1]

[VOLTAGE SENSING]

>1V 2nd(V): 4.0

>1V Ratio: 3300.0

[2.0~350.0:0.1V]

Page 52: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

52 ENHANCED TECHNOLOGY

Range 2.0 ~ 350.0V

Default 4.0 Step 0.1V

Enter the second rated voltage(V) of 2V(2nd Voltage Connector).

This setting is the second rated voltage that entered in the relay about

line rated voltage.

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / 2V Ratio

Range 10.0 ~ 6500.0

Default 3300.0 Step 0.1

Enter the VT Rated Rate of 2V(2nd Voltage Connector).

GLOBAL SETTING / SYSTEM / VOLTAGE SENSING / Source Side

Range 1V, 2V

Default 1V Step ~

Select the Source side of System.

According to the selected value the indication of “MAIN MENU/

METERING/ VOLTAGE” change. In the VOLTAGE screen, indicate

ABC in the Source Side, and RST in the Load Side.

[VOLTAGE SENSING]

>2V Ratio: 3300.0

>Source Side: 1V

[1V/2V]

[VOLTAGE SENSING]

>2V 2nd(V): 4.0

>2V Ratio: 3300.0

[10.0~6500.0:0.1]

[VOLTAGE SENSING]

>2V 2nd(V): 4.0

>2V Ratio: 3300.0

[2.0~350.0:0.1V]

Page 53: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 53 ENHANCED TECHNOLOGY

Setting Examples

In case of Y-type connection use, set VT2nd[V] for 4V initial value, and if the primary phase-

phase voltage is 15㎸ Ф-Ф, VT ratio is calculated as below.

VoltageФ-Ф = VoltageФ-N × 3

VoltageФ-N = VT 2nd

[V] × VT Ratio

8.66㎸Ф-N = 15㎸ Ф-Ф / 3

8.66㎸Ф-N = 4[V] × 2165

According to the above formula, VT rate is calculated in 2165.

With the same VT2nd[V] and VT ratio, if the primary phase-phase voltage(VoltageФ-Ф) is 11kV,

the primary phase voltage is 6.35㎸Ф-N (=11㎸ Ф-Ф / 3 ), VT secondary input voltage is

3V(=6.35㎸Ф-N /2165)

In case that Δ-type connection is used, if VT2nd[V] is 4V and the primary phase to phase to phase

is 15㎸ Ф-Ф, VT ratio is 3750(15㎸ Ф-Ф /4V = 3750).

Table 6-2. VT Rated Rate

Line-Line

Votage

Wye connection Delta connection

VT 2nd (v) VT Ratio VT 2nd (v) VT Ratio

15㎸ 4 2165 100 150

27㎸ 4 3897.1 100 270

38㎸ 4 5484.8 100 380

Page 54: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

54 ENHANCED TECHNOLOGY

6.2. Communication

Locate the cursor on “2. COMMUNICATION” in GLOBAL SETTING, move to this menu by

pressing [ENT] button. In this menu, all elements related to the communication can be set and has

the following submenu.

6.2.1. Protocol Setup

Locate the cursor on “1. PROTOCOL SETUP” in COMMUNICATION menu, move to this menu

by pressing [ENT] button. In this menu, set the communication protocol that is supported ETR300.

This menu has the following submenu.

ETR300 supports DNP3, IEC60870-5-101, IEC60870-5-104 and MODBOUS according to the

communication conditions of the user. Each supported protocol can be set.

6.2.1.1. DNP3.0 Protocol Setup

ETR300 can DNP3.0 communicate by using the communication port1, port2, port3 or port4. For

more information refer the “DNP3.0 Protocol Technical Manual”.

DNP3.0 protocol setting menu is as following.

[PROTOCOL SETUP]

>1.DNP3

[COMMUNICATION]

>1.PROTOCOL SETUP

2.PORT SETUP

Page 55: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 55 ENHANCED TECHNOLOGY

(1) DNP3

To setting DNP3 Protocol move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/

PROTOCOL SETUP/ DNP3”.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Function

Range ON, OFF

Default ON Step ~

Toselect DNP3, set ON.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ COM Port

Range PORT1, PORT2, PORT3

Default PORT1 Step ~

Select DNP3 communication port.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Confirm

Range NO, YES, SOMETIME

Default SOMETIME Step ~

Choose whether Data Link Confirm is used or not.

NO : Data Link Confirm is not used.

YES : Data Link Confirm is used

SOMETIME : Use Data Link Confirm in case of multi frame.

When set the use of Data Link Confirm, check the setting status of

host and set same with the host. If the setting status is different with

the host can be occur an communication error because of Data Link

Reset.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L FrameDly

Range 10 ~ 5000msec

Default 100 Step 10msec

Set Data Link frame Delay time.

If the D/L Confirm setting is OFF, means the transmission distance

between Frame when occurs multi frame.

[DNP3]

>D/L Confirm: SOME

>D/L FrameDly: 100

[10~5000:10ms]

[DNP3]

>Function: ON

COM Port: PORT1

[OFF/ON]

[DNP3]

>D/L Confirm: SOME

D/L FrameDly: 100

[NO/YES/SOME]

[DNP3]

>COM Port: PORT1

D/L Confirm: SOME

[PORT1/PORT2/PORT3]

Page 56: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

56 ENHANCED TECHNOLOGY

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Retries

Range 0, 1, 2

Default 0 Step 1

Set the retry number of Data Link.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ D/L Timeout

Range 1 ~ 255 sec

Default 10 Step 1 sec

Set the waiting time of Data Link Frame transmission to the Data Link

Confirm (ACK) receiveing of the master side. ETR300 resends the

Data Link Frame, when the Data Link Confirm has not received

during the setting time and it is possible to retry the Data Link.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ A/L Retries

Range 0, 1, 2

Default 0 Step 1

Set the retry number of Application Link Layer.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ A/L Timeout

Range 1 ~ 255 sec

Default 15 Step 1 sec

In case that request Confirm during the data transmission from Slave

Application to Master Application, set the maximum time of A/L

Confirm(ACK) receiving from Mast Application to Slave Application.

[DNP3]

>A/L Timeout: 15

Fault I Report: YES

[1~255:1s]

[DNP3]

>A/L Retries: 0

A/L Timeout: 15

[0~2:1]

[DNP3]

>D/L Timeout: 10

A/L Retries: 0

[1~255:1s]

[DNP3]

>D/L Retries: 0

D/L Timeout: 10

[0~2:1]

Page 57: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 57 ENHANCED TECHNOLOGY

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Fault I Report

Range NO, YES, 1SHOT

Default YES Step -

NO : Do not send the all Fault Current Sequence to Event.

YES : Send all Fault Current Sequence to Event.

1SHOT : Send the first Sequence Fault Current of Fualt Sequence

to Event.

NOTE :

The Fault Current occurrence time of each Sequence is when

becomes no voltage after experience the Fault Current.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Fault I Reset

Range NO, YES

Default NO Step -

Set the Fault Current Initialization.

NO : Final Fault Current Value is maintained till the next fault

occurrence even the fault detection information is reseted.

YES : Fault Current Value is initialized in 0 at the time that

current detect information is canceld.

NOTE :

Fault Current is handled in RMS maximum value of each

Sequence Fault Current Waveform.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Master Addr

Range 0 ~ 65534

Default 65534 Step 1

Enter the DNP address of Master station. ETR300 refer this address

when send Unsol message.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ DNP Address

Range 0 ~ 65534

Default 0 Step 1

Enter the address of Slave(ETR300).

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ SBO Time

[DNP3]

>Fault I Report: YES

>Fault I Resec: NO

[NO/YES]

[DNP3]

>A/L Timeout: 15

>Fault I Report: YES

[NO/YES/1SHOT]

[DNP3]

>DNP Address: 0

SBO Time: 15

[0~65534:1]

[DNP3]

>Master Addr: 65534

DNP Address: 0

[0~65534:1]

Page 58: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

58 ENHANCED TECHNOLOGY

Range 1 ~ 255 sec

Default 15 Step 1 sec

Set the time interval between Select Function and Operate Function.

It is time that maintain the Select order after receiving it, if there is not

an operation order during setting value the select order is canceled.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Debounce Time

Range 10 ~ 100 msec

Default 20 Step 5 msec

Set the connection debounce time

But, the debounce time of door open information it is fixed in 1

second.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Aver. Load Calc T

Range 1/2/3/4/5/6/10/12/15/20/30 min

Default 15 Step -

Set the time interval for the calculation of average load current.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Daily Max I

Range DISABLE, ENABLE

Default ENABLE Step -

Select the [DISABLE/ENABLE] of Daily Maximum Load Current

transmission.

DISABLE : Do not process Daily Maximum Load Current Event..

ENABLE : Process Daily Maximum Load Current.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Init Unsol

Range DISABLE, ENABLE

Default ENABLE Step ~

Select [DISABLE/ENABLE] of Initial Unsolicited Response Use

when Power Up.

Enable : When Power Up, transmit the Initial Unsolicited

Response Message.

Disable : When Power Up, do not transmit Initial Unsolicited

Response Message.

[DNP3]

>Daily Max I: ENABLE

>Init Unsol: ENABLE

[DISABLE/ENABLE]

[DNP3]

>Aver.Load Calc T:15

>Daily Max I: ENABLE

[DISABLE/ENABLE]

[DNP3]

>Aver.Load Calc T:15

>Daily Max I: ENABLE

1~6/10/12/15/20/30m

[DNP3]

>SBO Time: 15

>Debounce Time: 20

[10~100:20ms]

[DNP3]

>SBO Time: 15

Debounce Time: 20

[1~255:1s]

Page 59: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 59 ENHANCED TECHNOLOGY

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 1

Range DISABLE, ENABLE

Default ENABLE Step ~

Select [ENABLE/DESABLE] of Unsolicied Response transmission to

the master station when occurs an Event in Class 1.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 2

Range DISABLE, ENABLE

Default ENABLE Step ~

Select [ENABLE/DESABLE] of Unsolicied Response transmission to

the master station when occurs an Event in Class 2.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Class 3

Range DISABLE, ENABLE

Default ENABLE Step ~

Select [ENABLE/DESABLE] of Unsolicied Response transmission to

the master station when occurs an Event in Class 3.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ Unsol Time

Range 0 ~ 60 sec

Default 5 Step 1 sec

Set the delay time of Unsolicited mode event transmission to the

master station. It is transmitted if new event does not happen during

this time.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Leve1(%)

Range 0(OFF), 1 ~ 50 %

Default OFF Step 1 %

Set the detect level of VOC(Value Of Change) Event1.

When set in OFF, does not occur Event information.

Display the analog input regulation in percentage, in case that the

regulation is higher than the setting point it is reported by

communication.

[DNP3]

>Class 3: ENABLE

>Unsol Time: 5

[0~60:1s]

[DNP3]

>Class 2: ENABLE

>Class 3: ENABLE

[DISABLE/ENABLE]

[DNP3]

>Class 1: ENABLE

>Class 2: ENABLE

[DISABLE/ENABLE]

[DNP3]

>Class 1: ENABLE

Class 2: ENABLE

[DISABLE/ENABLE]

[DNP3]

>VOC Level(%): OFF

>VOC Min: 100

[0(OFF),1~50:1%]

Page 60: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

60 ENHANCED TECHNOLOGY

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Min

Range 0 ~ 630 A

Default 100 Step 1A

Set VOC level to detect VOC Event.

In case that analog input value is under minimum value, does not

transmit communication to the superior.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ VOC Select

Range RMS, AVER

Default AVER Step -

Select current used for the VOC decision.

RMS : Apply virtual value current to VOC detection.

AVER : Apply average current to VOC detection.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ TCP/IP Port

Range 0 ~ 65535

Default 0 Step 1

Set TCP/IP port of ETR300.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ DNP3/ IP Addr‟1~4

Range 0 ~ 255

Default 0 Step 1

Select the master station IP address for DNP3.0 communication.

IP Address : 192.xxx.xxx.xxx ① ② ③ ④

IP Addr 1́,2,3,4 means ①,②,③,④.

For example, in case that the IP address is „255.255.255.255‟, set as

the following.

Master IP Oct1 : 255

Master IP Oct2 : 255

Master IP Oct3 : 255

Master IP Oct4 : 255

[DNP3]

>IP Addr’1: 0

IP Addr’2: 0

IP Addr’3: 0

>IP Addr’4: 0

[DNP3]

>TCP/IP Port: 0

IP Addr’1: 0

[1~65535:1]

[DNP3]

>VOC Min: 100

>VOC Select: AVER

[RMS/AVER]

[DNP3]

VOC Level(%): OFF

>VOC Min: 100

[0~630:1A]

Page 61: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 61 ENHANCED TECHNOLOGY

6.2.2. Port Setup

Locate the cursor on “2. PORT SETUP” in COMMUNICATION menu, move to this menu by

pressing [ENT] button. In this menu, set the communication port and related elements of ETR300.

It has the following submenu.

6.2.2.1. PORT1(232) Setup

Set elements related to PORT1 which is located in the side panel of ETR300.

Move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT

SETUP/PORT1(232)” to set Port 1.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Baud Rate

Range 1200, 2400, 4800, 9600, 19200 bps

Default 1200 Step ~

Select the baud rate of PORT1.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Parity Bit

Range NONE, ODD, EVEN

Default NONE Step ~

Select the use of Parity Bit and its type.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Data Bit

Range 7, 8

Default 8 Step ~

Select the Data bit number which will be used for the communication.

[PROT1(232)]

Parity Bit: NONE

>Data Bit: 8

[7~8:1]

[PROT1(232)]

Baud Rate: 1200

>Parity Bit: NONE

[NONE/ODD/EVEN]

[PROT1(232)]

>Baud Rate: 1200

Parity Bit: NONE

[1200 ~ 19200 bps]

[PORT SETUP]

>1.PORT1(232)

2.PORT2(485)

3.PORT3(ETHERNET)

4.PORTF(232)

Page 62: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

62 ENHANCED TECHNOLOGY

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Stop Bit

Range 1, 2

Default 1 Step ~

Slect the Stop bit number which will be used for the communication.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ Modem Sel

Range 2W, 4W, D1, D2, NONE

Default 4W Step ~

Select a modem for communication.

2W : 2 wire private line is used and continuously Carrier is monitored

to control data flow by DCD(Data Carrier Detect).

4W : 4 wire private line is used and RTS(Request To Send) and

CTS(clear to Send) signal are used to control data flow.

D1 : Dial-Up1 modem is used.

D2 : Dial-Up2 modem is used.

NONE : Not used.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ CTS Usage

Range ON, OFF

Default ON Step ~

Set the [OFF/ON] of CTS signal usage.

ON : Transfer the transmission data after checking that the CTS

signal is Assert.

OFF : Transfer the transmission data regardless of the CTS sign.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ DCD Usage

Range ON, OFF

Default ON Step ~

Set the [OFF/ON] of DCD signal usage.

ON : Transfer the transmission data checking that the DCD signal

is Deassert.

OFF : Transfor the transmission data regardless of the DCD signal.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ RTS Usage

[PROT1(232)]

>DCD Usage: OFF

>RTS Usage: AUTO

[OFF/ON]

[PROT1(232)]

>Modem Sel: 4W

>CTS Usage: ON

[OFF/ON]

[PROT1(232)]

>Modem Sel: 4W

>CTS Usage: ON

[2W/4W/D1/D2/NONE]

[PROT1(232)]

Data Bit: 8

>Stop Bit: 1

[1~2:1]

Page 63: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 63 ENHANCED TECHNOLOGY

Range OFF, ON, AUTO

Default AUTO Step ~

ON : RTS sign of ETR is always ON(Assert).

OFF : RTS sign of ETR300 is always OFF(Deassert).

AUTO : When request a data transmission to modem the RTS sign

of ETR300 is ON and when finish the transmission the RTS sign of

ETR300 is OFF.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ CTS CheckOut

Range 1 ~ 255 sec

Default 2 Step 1 sec

Set a waiting time that waits Modems confirmation on RTS signal

which informs that ETR300 is ready to transfer a data. If there is no

CTS response within a set time, RTU confirms CTS Fail and does not

transfer the data.

It is available if „CTS Usage‟ setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ DCD CheckOut

Range 10 ~ 30000 msec

Default 5000 Step 5 msec

Set a delay time of DCD signal check which determine modem status

before sending RTS signal in 2 wire communication type. After a set

time, if DCD signal is ON, ETR300 does not transfer the data and

treat it as DCD Fail. It is available if „DCD Usage‟ setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT1(232)/ RTS OffDelay

Range 10 ~ 500 msec

Default 50 Step 5 msec

RTS Off Delay Time set the delay time of RTS sign that becom Off

after the data transmission.

It is time delay to prevent the liss if last data after sending the data.

Commonly, RTS Off Delay Time is set in 1 or 2 Byte transmission

occur time.

[PROT1(232)]

DCD CheckOut: 5000

>RTS Off Dly: 50

[10~500:5ms]

[PROT1(232)]

>CTS CheckOut: 2

>DCD CheckOut: 5000

[10~30000:5ms]

[PROT1(232)]

>CTS CheckOut: 2

>DCD CheckOut: 5000

[1~255:1s]

[PROT1(232)]

>DCD Usage: OFF

>RTS Usage: AUTO

[OFF/ON/AUTO]

Page 64: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

64 ENHANCED TECHNOLOGY

6.2.2.2. PORT2(485) Setup

Set items related to the PORT2 located in the side panel of ETR300.

To set PORT2 move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT

SETUP/PORT2(485)”.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Baud Rate

Range 1200, 2400, 4800, 9600, 19200 bps

Default 1200 Step ~

Select the Baud Rate of PORT2 .

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Parity Bit

Range NONE, ODD, EVEN

Default NONE Step ~

Select the use of Parity Bit and its type.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Data Bit

Range 7, 8

Default 8 Step ~

Select the Data Bit number used for the communication..

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Stop Bit

Range 1, 2

Default 1 Step ~

Select the Stop Bit number used for the communication.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ Line Type

Range RS422, RS485

Default RS422 Step ~

Select the Line Type used for the communication..

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORT2(485)/ CA Delay

Range 0.00 ~ 240.00

Default 1.00 Step 0.01 sec

Set the Delay type of the answer data transmission after data receipt.

[PROT2(485)]

>Line Type: RS422

>CA Delay: 1.00

[0.00~240.00:0.01]

[PROT2(485)]

>Line Type: RS422

CA Delay: 1.00

[RS422/RS485]

[PROT2(485)]

Data Bit: 8

>Stop Bit: 1

[1~2:1]

[PROT2(485)]

Parity Bit: NONE

>Data Bit: 8

[7~8:1]

[PROT2(485)]

Baud Rate: 1200

>Parity Bit: NONE

[NONE/ODD/EVEN]

[PROT2(485)]

>Baud Rate: 1200

Parity Bit: NONE

[1200 ~ 19200 bps]

Page 65: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 65 ENHANCED TECHNOLOGY

6.2.2.3. PORT3(EHTERNET) Setup

Set items related to the PORT3 located in the side panel of ETR300

To set PORT3 move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT

SETUP/PORT3(ETHERNET)”.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ IP Addr Oct1 ~ 4

Range 0 ~ 255

Default 0 Step 1

Select IP address of ETR300.

IP Address : 192.xxx.xxx.xxx ① ② ③ ④

IP Addr 1́,2,3,4 means ①,②,③,④.

For example, in case that the IP address is „255.255.255.255‟, set as

the following.

IP Addr Oct1 : 255

IP Addr Oct2 : 255

IP Addr Oct3 : 255

IP Addr Oct4 : 255

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ Gateway Oct1 ~ 4

Range 0 ~ 255

Default 0 Step 1

Select Gateway adress.

Gateway Address : 192.xxx.xxx.xxx ① ② ③ ④

Gateway Addr 1́,2,3,4 means ①,②,③,④.

GLOBAL SETTING/ COMMUNICATION/ PROTOCOL SETUP/ PORT3/ SubnetMask Oct1 ~ 4

Range 0 ~ 255

Default 0 Step 1

Select Subnet Mask address of ETR300.

Subnet Mask Address : 192.xxx.xxx.xxx

① ② ③ ④

Subnet Mask Addr 1́,2,3,4 means ①,②,③,④.

[PORT3(ETHERNET)]

>SubnetMask Oct1: 0

SubnetMask Oct2: 0

SubnetMask Oct3: 0

SubnetMask Oct4: 0

[PORT3(ETHERNET)]

>Gateway Oct1: 0

Gateway Oct2: 0

Gateway Oct3: 0

Gateway Oct4: 0

[PORT3(ETHERNET)]

>IP Addr Oct1: 0

IP Addr Oct2: 0

IP Addr Oct3: 0

IP Addr Oct4: 0

Page 66: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

66 ENHANCED TECHNOLOGY

6.2.2.4. PORTF(232) Setup

Set items related to the PORTF located in the front panel of ETR300

To set the PORTF move to “MAIN MENU/ GLOBAL SETTING/ COMMUNICATION/ PORT

SETUP/PORTF(232)” .

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Wireless

Range DISABLE, ENABLE

Default DISABLE Step ~

Select the use[DISABLE/ENABLE] of Wireless communication.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Slave Addr

Range 0 ~ 65534

Default 1 Step 1

Enter Slave(ETR300) adress.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Master Addr

Range 0 ~ 65534

Default 1 Step 1

Enter Master station adress.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Baud Rate

Range 1200, 2400, 4800, 9600, 19200, 38400, 57600 bps

Default 1200 Step ~

Select Baud Rate of PORTF.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ Modem Sel

Range 2W, 4W, D1, D2, NONE

Default 4W Step ~

Select a modem for communication.

2W : 2 wire private line is used and continuously Carrier is monitored

to control a data flow by DCD(Data Carrier Detect) signal.

4W : 4 wire private line is used and RTS(Request To Send) and

CTS(Clear To Send) signal is used to control a data flow.

[PROTF(232)]

>Modem Sel: 4W

>CTS Usage: ON

[2W/4W/D1/D2/NONE]

[DNP3]

>Slave Addr: 1

>Master Addr: 65534

[0~65534:1]

[DNP3]

>Slave Addr: 1

>Master Addr: 65534

[0~65534:1]

[PORTF(232)]

>Wireless: DISABLE

Slave Addr: 1

[DISABLE/ENABLE]

[PROTF(232)]

>Baud Rate: 1200

Modem Sel: 4W

[1200 ~ 57600 bps]

Page 67: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 67 ENHANCED TECHNOLOGY

D1 : Dial-Up1 modem is used.

D2 : Dial-Up2 modem is used.

NONE : Not used.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ CTS Usage

Range ON, OFF

Default ON Step ~

Set the use [OFF/ON] of CTS sign.

ON : Transmit the sending data after check that the CTS sign is

Assert.

OFF : Transmit the sending data regardless of CTS sign.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ DCD Usage

Range ON, OFF

Default ON Step ~

Set the use [OFF/ON] of DCD sign.

ON : Transmit the sending data after check that the DCD sign is

Desassert.

OFF : Transmit the sending data regardless of DCD sign.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ RTS Usage

Range OFF, ON, AUTO

Default AUTO Step ~

ON : RTS sign of ETR300-R is always ON(Assert).

OFF : RTS sign of ETR300-R is always OFF(Deassert).

AUTO : When request a data transmission to modem the RTS sign

of ETR300 is ON and when finish the transmission the RTS sign of

ETR300 is OFF.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ CTS CheckOut

[PROTF(232)]

>DCD Usage: OFF

>RTS Usage: AUTO

[OFF/ON/AUTO]

[PROTF(232)]

>DCD Usage: OFF

>RTS Usage: AUTO

[OFF/ON]

[PROTF(232)]

>Modem Sel: 4W

>CTS Usage: ON

[OFF/ON]

Page 68: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

68 ENHANCED TECHNOLOGY

Range 1 ~ 255 sec

Default 2 Step 1 sec

Set a waiting time that waits for a modem response on RTS signal

which informs ETR300 is ready to transfer a data. If no response

within a set time, RTU treats CTS Fail and does not transfer a data.

It is available if „CTS Usage‟ setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ DCD CheckOut

Range 10 ~ 30000 msec

Default 5000 Step 5 msec

Set a delay time of DCD signal to check modem status before transfer

a RTS signal in 2 wire communication type. If DCD signal is ON after

set time, ETR300 does not transfer a data and treats DCD Fail.

It is available if „DCD Usage‟ setting is ON.

GLOBAL SETTING/ COMMUNICATION/ PORT SETUP/ PORTF(232)/ RTS OffDelay

Range 10 ~ 500 msec

Default 50 Step 5 msec

RTS Off Delay Time is a time delay after transfer a data till RTS

signal Off. It is a time delay to prevent a last data loss during a data

transfer.

Generally, RTS Off Delay Time is set for 1 or 2 Byte.

[PROTF(232)]

>CTS CheckOut: 2

>DCD CheckOut: 5000

[10~30000:5ms]

[PROTF(232)]

>CTS CheckOut: 2

>DCD CheckOut: 5000

[1~255:1s]

[PROTF(232)]

DCD CheckOut: 5000

>RTS OffDelay: 50

[10~500:5ms]

Page 69: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 69 ENHANCED TECHNOLOGY

6.3. Event Recorder

Locate the cursor on “3. EVENT RECORDER” in GLOBAL SETTING, press [ENT] button to

move to this menu. In this menu, items related to the wave record are set.

GLOBAL SETTING / EVENT RECORDER / Wave Capture

Range ON, OFF

Default ON Step ~

Set whether to use Wave capture.

GLOBAL SETTING / EVENT RECORDER / Wave S/R

Range 16, 32, 64, 128 sample

Default 64 sample Step ~

If record the wave, select the wave sampling capture.

The recorded wave cycle number is 20cycle per 128 sampling and it is

changeable according to the sampling number.

GLOBAL SETTING / EVENT RECORDER / Wave Pre-Cycle

Range 1 ~ 5 cycle

Default 5 Step 1 cycle

Pre-cycle is to record(capture) a number of wave cycle before fault

pickup occurring.

GLOBAL SETTING / EVENT RECORDER / Wave Post-Cycle

Range 1 ~ 5 cycle

Default 5 Step 1 cycle

Post-cycle is to record(capture) a number of wave cycle after Trip.

GLOBAL SETTING / EVENT RECORDER / Wave Head-Cycle

Range 1 ~ 10 cycle

Default 5 Step 1 cycle

Head-Cycle is to record(capture) a number of wave cycle before Trip.

[EVENT RECORDER]

>Wave Post-Cycle: 5

>Wave Head-Cycle: 5

[1~10:1cycel]

[EVENT RECORDER]

>Wave Pre-Cycle: 5

>Wave Post-Cycle: 5

[1~5:1cycel]

[EVENT RECORDER]

>Wave Pre-Cycle: 5

>Wave Post-Cycle: 5

[1~5:1cycel]

[EVENT RECORDER]

>Wave Capture: OFF

>Wave S/R: 64

[16/32/64/128]

[EVENT RECORDER]

>Wave Capture: OFF

>Wave S/R: 64

[OFF/ON]

Page 70: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

70 ENHANCED TECHNOLOGY

6.4. Monitoring

Locate the cursor on “4. MONITORING” in GLOBAL SETTING, push [ENT] button and move

to this menu.

6.4.1. Operation Count

Locate the cursor on “1. OPERATION COUNT” in MONITORING menu, press [ENT] button

and move to this men. In this menu, set the elements related to Operation Count Monitering of

switch.

GLOBAL SETTING / MONITORING / OPERATION COUNT / Function

Range OFF, ON

Default ON Step ~

Set whether to use Operation Caunt Monitering

GLOBAL SETTING / MONITORING / OPERATION COUNT / Limit

Range 1 ~ 20000

Default 10000 Step 1

Ring the Alarm when Switch operation count (“MAINENANCE/

COUNT/ OPERATION”) reach the setting value.

GLOBAL SETTING / MONITORING / OPERATION COUNT / Count set

Range 0 ~ 65535

Default 0 Step 1

Use to set the same the Operation Count with the main device.

Set value is available after Operation Counter is reset. You can reset

the counter in “MAINENANCE/ DATA RESET / OPERATION

COUNT or COUNT ALL”

[TRIP COUNTER]

Limit: 10000

>Count set: 0

[0~65535:1]

[OPERATION COUNT]

>Function: OFF

>Limit: 10000

[1~20000:1]

[OPERATION COUNT]

>Function: ON

Limit: 10000

[OFF/ON]

[MONITERING]

>1.OPERATION COUNT

2.CONTACT WEAR

3.BATTERY TEST

4.PQM

5.TD MONITOR

6.V0 DETEC

Page 71: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 71 ENHANCED TECHNOLOGY

6.4.2. Contact Wear

Place the curser on “3. CONTACT WEAR” in MONITORING menu, press [ENT] button to move

into this menu. Switch contact wear and monitoring elements are set in this menu.

GLOBAL SETTING / MONITORING / CONTACT WEAR / Function

Range OFF, ON

Default OFF Step ~

Select whether to use Switch contact wear monitoring.

GLOBAL SETTING / MONITORING / CONTACT WEAR / Pickup(%)

Range 0.0 ~ 50.0 %

Default 20.0 Step 0.1 %

Set a pickup value to alarm when switch contact wear

(“MAINENANCE/ CONTACT WEAR”) reaches set value.

GLOBAL SETTING / MONITORING / CONTACT WEAR / Rated Volt(kV)

Range 15, 27, 38 ㎸

Default 27 ㎸ Step ~

Set Rated Voltage of System.

GLOBAL SETTING / MONITORING / CONTACT WEAR / Interrupt(kA)

Range 5.0 ~ 50.0 kA

Default 12.5 Step 0.1 kA

Set the maximum rated interrupt.

GLOBAL SETTING / MONITORING / CONTACT WEAR / No. Max I

Range 1 ~ 999

Default 100 Step 1

Enter the capacity of rated Interrupter.

GLOBAL SETTING / MONITORING / CONTACT WEAR / A Wear Set

Range 0.00 ~ 100.00 % [CONTACT WEAR]

>A Wear Set: 100.00

>B Wear Set: 100.00

[0.00~100.00:0.01%]

[CONTACT WEAR]

>Function: OFF

>Pickup(%): 20.0

[0.0~50.0:0.1%]

[CONTACT WEAR]

>Function: OFF

Pickup(%): 20.0

[OFF/ON]

[CONTACT WEAR]

Pickup(%): 20.0

>Rated Volt(kV): 38

[15/27/38kV]

[CONTACT WEAR]

Rated Volt(kV): 15

>Interrupt(kA): 12.5

[5.0~50.0:0.1kA]

[CONTACT WEAR]

Interrupt(kA): 12.5

>No. Max I: 100

[1~999:1]

Page 72: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

72 ENHANCED TECHNOLOGY

Default 100.00 Step 0.01%

It is to set Switch phase A contact wear value in ETR300. Set value is

available after Contact Wear Rset. Contact wear reset refers to

“MAINENANCE/ DATA RESET / CONTACT WEAR”.

GLOBAL SETTING / MONITORING / CONTACT WEAR / B Wear Set

Range 0.00 ~ 100.00 %

Default 100.00 Step 0.01%

It is to set Switch phase B contact wear value in ETR300. Set value is

available after Contact Wear Rset. Contact wear reset refers to

“MAINENANCE/ DATA RESET / CONTACT WEAR”.

GLOBAL SETTING / MONITORING / CONTACT WEAR / C Wear Set

Range 0.00 ~ 100.00 %

Default 100.00 Step 0.01%

It is to set Switch phase C contact wear value in ETR300. Set value is

available after Contact Wear Rset. Contact wear reset refers to

“MAINENANCE/ DATA RESET / CONTACT WEAR”.

6.4.3. Battery Test

Locate the cursor on “3. BATTERY TEST” in MONITORING menu, press [ENT] button and

move to this menu.

GLOBAL SETTING / MONITORING / BATTERY TEST / Period

Range 1 ~ 720 hour

Default 24 Step 1 hour

Set the Battery Test Hour Period.

[BATTERY TEST]

>Period: 24

[1~720:1hour]

[CONTACT WEAR]

>B Wear Set: 100.00

>C Wear Set: 100.00

[0.00~100.00:0.01%]

[CONTACT WEAR]

>A Wear Set: 100.00

>B Wear Set: 100.00

[0.00~100.00:0.01%]

Page 73: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 73 ENHANCED TECHNOLOGY

6.4.4. PQM

Locate the cursor on “4. PQM” in MONITERING menu, press [ENT] button and move to this

menu. In this menu, set the elements of PQM and has the following submenu.

6.4.4.1. PQM Function

Locate the cursor on “1. PQM FUNCTION” in PQM Menu, press [ENT] button and move to this

menu.

GLOBAL SETTING / MONITORING / PQM / PQM FUNCTION / Function

Range DISABLE, ENABLE

Default DISABLE Step ~

Select [DISABLE/ENABLE] of PQ.

6.4.4.2. Interrupt

Locate the cursor on PQM “2. INTERRUPT” in the menu, press [ENT] button and move to this

menu.

GLOBAL SETTING / MONITORING / PQM / INTERRUPT / Level

Range 0(OFF), 0.10 ~ 0.49 pu

Default 0.10 Step 0.01 pu

Set the Interrupt Detect Level of PQ.

Detect Level shall be set in multiple of rated voltage of source side

user.

[PQM]

>1.PQM FUNCTION

2.INTERRUPT

3.SAG

4.SWELL

5.HARMONICS

6.CURR UNBALANCE

7.VOLT UNBALANCE

8.UNDER VOLTAGE

9.OVER VOLTAGE

10.UNDER FREQUENCY

11.UBI/THD MIN.I

[INTERRUPT]

>Level: 0.10

>Time: 2.0

[0(OFF),0.10~0.49pu]

[PQM FUNCTION]

>Function: DISABLE

[DISABLE/ENABLE]

Page 74: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

74 ENHANCED TECHNOLOGY

GLOBAL SETTING / MONITORING / PQM / INTERRUPT / Time

Range 0.5 ~ 10.0 cycle

Default 2.0 Step 0.5 cycle

Set Interrupt Detect Time.

6.4.4.3. Sag

Locate the cursor on “3. SAG” in PQM menu, press [ENT] key and move to this menu.

GLOBAL SETTING / MONITORING / PQM / SAG / Level

Range 0(OFF), 0.50 ~ 0.99 pu

Default 0.80 Step 0.01 pu

Set the Voltage Sag Detect Level of PQ.

Detect Level shall be set in multiple of rated voltage of source side

user.

GLOBAL SETTING / MONITORING / PQM / SAG / Time

Range 0.5 ~ 10.0 cycle

Default 2.0 Step 0.5 cycle

Set Voltage Sag Detect Time.

6.4.4.4. Swell

Locate the cursor on “4. SWELL” in PQM menu, press [ENT] button and move to this menu.

GLOBAL SETTING / MONITORING / PQM / SWELL / Level

Range 0(OFF), 1.01 ~ 1.50 pu

Default 1.20 Step 0.01 pu

Set the Voltage Swell Detect Level of PQ.

Detect Level shall be set in multiple of rated voltage of source side

user..

GLOBAL SETTING / MONITORING / PQM / SWELL / Time

Range 0.5 ~ 10.0 cycle

Default 2.0 Step 0.5 cycle

[SWELL]

>Level: 1.20

>Time: 2.0

[0.5~10.0:0.5cycle]

[SWELL]

>Level: 1.20

>Time: 2.0

[0(OFF),1.01~1.50pu]

[SAG]

>Level: 0.80

>Time: 2.0

[0.5~10.0:0.5cycle]

[SAG]

>Level: 0.80

>Time: 2.0

[0(OFF),0.50~0.99pu]

[INTERRUPT]

>Level: 0.10

>Time: 2.0

[0.5~10.0:0.5cycle]

Page 75: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 75 ENHANCED TECHNOLOGY

Set Voltage Swell Detect Time.

6.4.4.5. Harmonics

Locate the cursor on “5. HARMONICS” in PQM menu, press [ENT] button and move to this

menu.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / VTHD Pickup

Range 0(OFF), 0.5 ~ 100.0 %

Default OFF Step 0.1%

Set a detect level of voltage harmonic distortion.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / VTHD Delay

Range 0.2 ~ 60.0 sec

Default 1.0 Step 0.1 sec

Set a detect time to detect voltage harmonic distortion.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / ITHD Pickup

Range 0(OFF), 0.5 ~ 100.0 %

Default OFF Step 0.1%

Set a detect level of current harmonic distortion.

GLOBAL SETTING / MONITORING / PQM / HARMONICS / ITHD Delay

Range 0.2 ~ 60.0 sec

Default 1.0 Step 0.1 sec

Set a detect time to detect current harmonic distortion.

6.4.4.6. Current Unbalance

Locate the cursor on “6. CURR UNBALANCE” in PQM menu, press [ENT] button and move to

this menu.

GLOBAL SETTING / MONITORING / PQM / CURR UNBALANCE / Level

Range 0(OFF), 1 ~ 100 %

Default 30 Step 1 %

[HARMONICS]

>ITHD Pickup: OFF

>ITHD Delay: 1.0

[OFF,0.5~100.0:0.01]

[HARMONICS]

>VTHD Pickup: OFF

>VTHD Delay: 1.0

[OFF,0.5~100.0:0.01]

[CURR UNBALANCE]

>Level: 30

>Time: 1.0

[0(OFF),1~100:1%]

[HARMONICS]

>ITHD Pickup: OFF

>ITHD Delay: 1.0

[0.2~60.0:0.1s]

[HARMONICS]

>VTHD Pickup: OFF

>VTHD Delay: 1.0

[0.2~60.0:0.1s]

Page 76: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

76 ENHANCED TECHNOLOGY

Set a detect level of Current Unbalance for Power Quality.

GLOBAL SETTING / MONITORING / PQM / CURR UNBALANCE / Time

Range 0.1 ~ 60.0 sec

Default 1.0 Step 0.1 sec

Set a detect time of current unbalance.

6.4.4.7. Voltage Unbalance

Locate the cursor on “7. VOLT UNBALANCE” in PQM menu, press [ENT] button and move to

this menu.

GLOBAL SETTING / MONITORING / PQM / VOLT UNBALANCE / Level

Range 0(OFF), 1 ~ 100 %

Default 30 Step 1 %

Set Voltage Unbalance Detect Level of PQ.

GLOBAL SETTING / MONITORING / PQM / VOLT UNBALANCE / Time

Range 0.1 ~ 60.0 sec

Default 1.0 Step 0.1 sec

Set Voltage Unbalance Detect Time.

6.4.4.8. Under Voltage

Place the curser on “8. UNDER VOLTAGE” in PQM menu, press [ENT] button to move into this

menu.

GLOBAL SETTING / MONITORING / PQM / UNDER VOLTAGE / Level

Range 0(OFF), 0.30 ~ 0.95 pu

Default 0.80 Step 0.01 pu

Set Under Voltage Detect Level of PQ.

Detect Level shall be set in multiple of rated voltage of source side

user..

GLOBAL SETTING / MONITORING / PQM / UNDER VOLTAGE / Time

Range 0.0 ~ 180.0 sec [UNDER VOLTAGE]

>Level: 0.80

>Time: 60.0

[0.0~180.0:0.1s]

[UNDER VOLTAGE]

>Level: 0.80

>Time: 60.0

[0(OFF),0.30~0.95pu]

[VOLT UNBALANCE]

>Level: 30

>Time: 1.0

[0.1~60.0:0.1s]

[VOLT UNBALANCE]

>Level: 30

>Time: 1.0

[0(OFF),1~100:1%]

[CURR UNBALANCE]

>Level: 30

>Time: 1.0

[0.1~60.0:0.1s]

Page 77: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 77 ENHANCED TECHNOLOGY

Default 60.0 Step 0.1 sec

Set Under Voltage Detect Time.

6.4.4.9. Over Voltage

Locate the cursor on “9. OVER VOLTAGE” in PQM menu, press [ENT] button and move to this

menu.

GLOBAL SETTING / MONITORING / PQM / OVER VOLTAGE / Level

Range 0(OFF), 1.05 ~ 1.50 pu

Default 1.20 Step 0.01 pu

Set Over Voltage Detect Level of PQ.

Detect Level shall be set in multiple of rated voltage of source side

user.

GLOBAL SETTING / MONITORING / PQM / OVER VOLTAGE / Time

Range 0.0 ~ 180.0 sec

Default 60.0 Step 0.1 sec

Set Over Voltage Detect Time.

6.4.4.10. Under Frequency

Locate the cursor on “10. UNDER FREQUENCY” in PQM menu, press [ENT] button and move

to this menu.

GLOBAL SETTING / MONITORING / PQM / UNDER FREQUENCY / Level

Range 0(OFF), 46.00 ~ 59.98 Hz

Default 59.50 Step 0.01 Hz

Set Under Frequency Detect Level of PQ..

GLOBAL SETTING / MONITORING / PQM / UNDER FREQUENCY / Time

Range 0.03 ~ 10.00 sec

Default 0.10 Step 0.01 sec

Set Under Frequency Detect Time.

[UNDER FREQUENCY]

>Level: 59.50

>Time: 0.10

[0.03~10.00:0.01s]

[UNDER FREQUENCY]

>Level: 59.50

>Time: 0.10

0(OFF),46.00~59.98Hz

[OVER VOLTAGE]

>Level: 1.20

>Time: 60.0

[0.0~180.0:0.1s]

[OVER VOLTAGE]

>Level: 1.20

>Time: 60.0

[0(OFF),1.05~1.50pu]

Page 78: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

78 ENHANCED TECHNOLOGY

6.4.4.11. Current Unbalance/THD Detect Limit

Locate the cursor on “11. UBI/THD MIN.” in PQM menu, select [ENT] button and move to this

menu.

GLOBAL SETTING / MONITORING / PQM / UBI/THD MIN. / Min. I

Range 0 ~ 630 A

Default 60 Step 1A

Set in minimum current to detect the Current Unbalance and THD.

6.4.5. TD MONITOR

Locate the cursor on “5. TD Monitor” in MONITERING menu, press [ENT] button and move to

this menu.

. In this menu, set operation elements of transducer which can be used for the moditoring of DC

analog input.

It has 5 channels of transducer, each transducer has 2 pickup setting values to detects the

signal size of input, monitoring in 2 levels the input sinal which is over than pickup setting

value and give the alarm.

The no. 1 and 2 transducer can detect the battery and charger status by receiving the battery

voltage and charge section voltage in input signal and sending to the controller.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Rate

Range 20, 200

Default 20 Step -

Enter TD1 monitoring rate.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Ratio

Range 1 ~ 3000

Default 1 Step 1

Enter TD1 ratio.

[UBI/THD MIN.I]

>Min. I: 60

[0~630:1A]

[TD MONITOR]

>TD1 Rate: 20

>TD1 Ratio: 1

[1~3000:1]

[TD MONITOR]

>TD1 Rate: 20

>TD1 Ratio: 1

[20/200]

Page 79: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 79 ENHANCED TECHNOLOGY

GLOBAL SETTING / MONITORING / TD MONITOR / TD1 Offset

Range -10000 ~ +10000

Default 0 Step 1

Enter TD1 off set.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 Type

Range UNDER, OVER

Default UNDER Step ~

Set the 1st monitoring type of TD1.

UNDER is set to give the alarm when input value is reduced under

pickup setting value, OVER is to give the alarm when input value is

increased over pickup setting value.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 PU(V)

Range 0(OFF), 1.0 ~ 35.0 V

Default OFF Step 0.1V

Set the 1st Pickup value of TD1.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-1 Delay

Range 0.01 ~ 600.00 sec

Default 2.00 Step 0.01 sec

Set the 1st Delay time of TD1.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 Type

Range UNDER, OVER

Default UNDER Step ~

Set the 2nd

monitoring type of TD1

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 PU

Range 0(OFF), 1.0 ~ 35.0 V

Default OFF Step 0.1V

[TD MONITOR]

>TD1-1 PU(V): OFF

>TD1-1 Delay: 2.00

[OFF,1.0~35.0:0.1V]

[TD MONITOR]

>TD1-2 Type: UNDER

>TD1-2 PU(V): OFF

[UNDER/OVER]

[TD MONITOR]

>TD1-1 PU(V): OFF

>TD1-1 Delay: 2.00

[0.01~600.00:0.01s]

[TD MONITOR]

>TD1-1 Type: UNDER

>TD1-1 PU: OFF

[UNDER/OVER]

[TD MONITOR]

>TD1 Ratio: 1

>TD1 Offset: +0

[-10000 ~ +10000:1]

Page 80: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

80 ENHANCED TECHNOLOGY

Set the 2nd

Pickup value of TD1.

GLOBAL SETTING / MONITORING / TD MONITOR / TD1-2 Delay

Range 0.01 ~ 600.00 sec

Default 2.00 Step 0.01 sec

Set the 2nd

Delay time of TD1.

※. NOTE : TD2 ~ TD5 have the same setting items with TD1.

6.4.6. V0 Detect

Locate the cursor on “6. V0 DETECT” in MONITERING menu, press [ENT] button and move to

this menu. In this menu, set the Zero Voltage detection.

GLOBAL SETTING / MONITORING / PQM / V0 DETECT / Detect Level

Range 0(OFF), 0.05 ~ 1.20 pu

Default OFF Step 0.01 pu

Set V0 Detect Level.

GLOBAL SETTING / MONITORING / V0 DETECT / Detect Time

Range 0.1 ~ 6000.0 sec

Default 1.0 Step 0.1 sec

Set V0 Detect Time.

[TD MONITOR]

>TD1-2 PU(V): OFF

>TD1-2 Delay: 2.00

[OFF,1.0~35.0:0.1V]

[V0 DETECT]

>Detect Level: OFF

>Detect Time: 1.0

[0.1~6000.0:0.1s]

[V0 DETECT]

>Detect Level: OFF

>Detect Time: 1.0

[0(OFF),0.05~1.20pu]

[TD MONITOR]

>TD1-2 PU: OFF

>TD1-2 Delay: 2.00

[0.01~600.00:0.01s]

Page 81: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 81 ENHANCED TECHNOLOGY

6.5. PLC

Locate the cursor on “5. PLC” in GLOBAL SETTING menu, press[ENT] button and move to this

menu.

6.5.1. COMMON

Locate the cursor on “1. COMMON” in PLC menu, press [ENT] button amd move to this menu.

6.5.1.1. Logic Timer

Locate the cursor on “1. LOGIC TIMER” in COMMON menu, press [ENT] button amd move to

this menu.

There are 16 logictimer inside the PLC.

When occurs input A in logictimer, output B becomes 1 after time X and when input A

disappears output B becomes 0 after time Y. Refer to “Ficture 5-1. Logic Timer symbol”.

X is Pick up time and Y is Dropout time.

In PLC, enter A in user logic TMI□.

In PLC, B is output in TMO□.

A

0s/0s

TM□

BY

X

Ficture 6-1. Logic Timer Symbol

[OMMON]

>1.LOGIC TIMER

2.PULSE TIMER

3.PULSE COUNTER

[PLC]

>1.COMMON

2.DI/DO

Page 82: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

82 ENHANCED TECHNOLOGY

GLOBAL SETTING / PLC / COMMON / LOGIC TIMER / TM1-PU

Range 0.01 ~ 600.00 sec

Default 0.01 Step 0.01 sec

Set Pickup Time of logic timer 1.

GLOBAL SETTING / PLC / COMMON / LOGIC TIMER / TM1-DO

Range 0.01 ~ 600.00 sec

Default 0.01 Step 0.01 sec

Set Dropout Time of logic timer 1.

※. NOTE : The setting of TM2 ~ TM16 are same with TM1.

6.5.1.2. Pulse Timer

Locate the cursor on “2. PULSE TIMER” in COMMON menu, press [ENT] button and move to

this menu.

There are 16 pulse timer inside the PLC

When input A becomes 1 in pulse timer, output B becomes 1 and it output during Y time.

Refer to “Figure 5-2. Pulse Timer symbol”.

In PLC, enter A in user logic PTMI□.

In PLC, B is output in PTMO□.

BAY

0s

PTM□

Ficture 6-2. Pulse Timer Symbol

GLOBAL SETTING / PLC / COMMON / PULSE TIMER / PTM1

Range 0.01 ~ 600.00 sec

Default 0.01 Step 0.01 sec

Set output time of Pulse Timer 1.

※. NOTE : Setting of TM2 ~ PTM16 is same with PTM1.

[PULSE TIMER]

>PTM1 : 0.01

PTM2 : 0.01

[0.01~600.00:0.01s]

[LOGIC TIMER]

>TM1-PU: 0.01

>TM1-DO: 0.01

[0.01~600.00:0.01s]

[LOGIC TIMER]

>TM1-PU: 0.01

TM1-DO: 0.01

[0.01~600.00:0.01s]

Page 83: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 83 ENHANCED TECHNOLOGY

6.5.1.3.Pulse Counter

Locate the cursor on “3. PULSE COUNTER” in COMMON menu, press [ENT] button and move

to this menu.

There are 16 Pulse Counter in PLC.

When input B is 0 and input A becomes 1 it increases once and output C becomes 1 when it is

over setting number X. When input B becomes 1 output C becomes 0 and the increased count

becomes 0. Refer to “Figure 5-3. Pulse Counter symbol”

In PLC, enter A in user logic PCI□.

In PLC, enter B in user logic PCR□.

In PLC, C is output in PCO□.

A

B

0

PC□

QR

XC

Ficture 6-3. Pulse Counter Symbol

GLOBAL SETTING / PLC / COMMON / PULSE COUNTER / PC1

Range 1 ~ 60000

Default 1000 Step 1

Set the utput value(X) of Pulse Counter(PC1).

※. NOTE : The setting item of PC2 ~ PC16 is same with PC1.

[PULSE TIMER]

>PC1 : 1000

PC2 : 1000

[1~60000:1]

Page 84: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

84 ENHANCED TECHNOLOGY

6.5.2. DI/DO

Locate the cursor on “2. DI/DO” in PLC menu, press [ENT] button and move to this menu.

6.5.2.1. Input Debounce Timer

Locate the cursor on “1. INPUT DEBOUNCE ” in DI/DO menu, press [ENT] button and move to

this menu.

Input Debounce Timer is provided individually in Control Input.

Input Debounce Timer st the time to eliminate the Chattering of INPUT signal.

When input A becomes 1 in Input Debounce Timer output B becomes 1 after X time and

when input A disappears output B becomes 0 after X time. Refer to “Figure 5-4. Input

Debounce Timer symbol”.

In PLC, A is IN01~IN□ of Control Input and B is output in IN□.

A

0s

X

X

IN□

B

Ficture 6-4. Input Debounce Timer Symbol

GLOBAL SETTING / PLC / DI/DO / INPUT DEBOUNCE / IN101

Range 0.005 ~ 10.000 sec

Default 0.020 Step 0.001 sec

Set Input Debounce time of IN101.

※. NOTE : Setting items of IN102 ~ IN108 and IN201 ~ IN208 are same with IN101.

[INPUT DEBOUNCE]

>IN101 : 0.020

IN102 : 0.020

0.005~10.000:0.001s

[DI/DO]

>1.INPUT DEBOUNCE

2.OUTPUT PULSE TIME

Page 85: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 85 ENHANCED TECHNOLOGY

6.5.2.2. Output Pulse Timer

Locate the cursor on “2. OUTPUT PULSE TIME” in DI/DO menu, press [ENT] button and move

to this menu.

Output Pulse Timer is provided individually in Control Output.

When input B is 0 in Output Pulse Timer, output C becomes 1 according to the input A. When

input A becomes 1output C becomes 1 during Y time. But if set the Y time in 0, they react at

the same time according to input A. When A is 1 C becomes 1 and when A is 0 C becomes 0, it

is Buffer. Refer to“Figure 5-5. Output Pulse Timer symbol” .

In PLC, enter A in user logic OUT□.

In PLC, enter B in user logic BKOUT□.

In PLC, C is output in OUT□ and this output runs RELAY.

A

B

0s

RY C

OUT□

Ficture 6-5. Output Pulse Timer Symbol

GLOBAL SETTING / PLC / DI/DO / OUTPUT PULSE TIME / OUT101

Range 0(BUFF), 0.01 ~ 100.00 sec

Default 0.01 Step 0.01 sec

Set Output Pulse Time of OUT101.

※. NOTE : The setting item of OUT102 ~ OUT 108 and OUT201 ~ OUT208 are same with OUT101.

[OUTPUT PULSE TIME]

>OUT101 : 0.01

OUT102 : 0.01

0(BUFF),0.01~100.00s

Page 86: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

86 ENHANCED TECHNOLOGY

6.6. Other setting items

Locate the cursor on “7. OTHERS” in GLOBAL SETTING menu, press [ENT] button and move

to this menu.

6.6.1. F.I TEST

ETR 300 has F.I Test in LCD menu to test the fault detect element and normal operation of fault

count. F.I Test function are same as the following.

(1) Basic Operation of F.I Test

Select which phase among A,B,C,N will be produced F.I (plural selection is possible)

After starting FI Test, produces F.I regardless of Pickup Current of Group Setting Menu.

For F.I Test, Sequence is set in the range of 1~3.

F.I Test is Disable when all A,B,C,N phase are OFF or Sequence is 0.

Produce 1000A Fault current for 10 cycle as the setting number. Eacg Sequence interval is 2

second.

After 2 seconds of FI test, temporary fault is generated.

When do the FI test, fault indication lamp of the front panel is lighted and send related

information to the main device without saving as internal event or increasing fault count.

Fault Current Transmission send the faul current to Event according to Fault I Report setting.

At this time, phase that has not done the FI test indicates present load current value.

After the test, fault indication (front panel lamo and BI point) is maintained until FI Reset.

When do the FI test in the status that fault indication is remained, cancel the prior fault

indication and shows “FI information”

(2) FI Setting Value Storage

Selected phase for F.I Test Target and Setting Value for F.I Test Sequence are saved at the started

time of F.I Test.

(3) Setting Basic Value

F.I Test initial value is sames as the following.

[OTHERS]

>1.F.I TEST

2.FACTORY DEBUG

Page 87: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 87 ENHANCED TECHNOLOGY

Targer : A,B,C,N all ON

Sequence : 3

(4) End of F.I Test

When F.I test starts, consider as “F.I test mode” the simulated fault current (1000A) permission,

F.I logic performance as much as the sequence setting and LED lighting after F.I set. End the test

mode after finishing these process.

FI Test Start

1000A

(10cycle)

1000A

(10cycle)

1000A

(10cycle)

1000A

(10cycle)

1000A

(10cycle)

1000A

(10cycle)

2sec

2sec 2sec

2sec 2sec 2sec

Fault Detect

Case: Sequence

Setting 1

Temporary

Fault Detected

Fault Detect Fault DetectTemporary

Fault Detected

Case: Sequence

Setting 2

FI Test Start

FI Test Start

Case: Sequence

Setting 3

Fault Detect Fault Detect Fault DetectTemporary

Fault Detected

Ficture 6-6. F.I Test according to Sequence Setting

Locate the cursor on “1. F.I TEST” in OTHERS menu, press [ENT] button and move to this menu.

In this menu, set the FI occur phase for the F.I mock test,and Sequence number.

[F.I TEST]

>1.F.I TEST TARGET

2.F.I TEST SEQ.

3.F.I TEST START

Page 88: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

88 ENHANCED TECHNOLOGY

6.6.1.1. F.I TEST TARGET

Locate the cursor on “1. F.I TEST TARGET” in F.I TEST menu, press [ENT] button and move to

this menu. In this menu, set the target phasefor the occurance of F.I.

GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST TARGET / IA TEST

Range OFF, ON

Default ON Step -

When select ON, F.I occurs in A phase.

※. NOTE : Setting of IB TEST, IC TEST and IN TEST ar same with IA TEST.

6.6.1.2.F.I TEST SEQUENCE

Locate the cursor on “2. F.I TEST SEQ.” in F.I TEST menu, press [ENT] button and move to this

menu.

GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST SEQUENCE / SEQ. COUNT

Range DISABLE, 1 ~ 3

Default 3 Step 1

Set F.I Sequence.

6.6.1.3.F.I TEST START

Locate the cursor on “3. F.I TEST START” in F.I TEST menu, press [ENT] button and move to

this menu.

GLOBAL SETTING / OTHERS / F.I TEST / F.I TEST SEQUENCE / F.I TEST START

Press [ENT] button if wants to Start the F.I test.

6.6.2. Factory Debug

This menu is for Manufacturer‟s maintenance purpose.

*F.I TEST START*

PRESS <ENT> TO START

[F.I TEST SEQUENCE]

>SEQ. COUNT: 3

>

[DISABLE,1~3:1]

[F.I TEST TARGET]

>IA TEST: ON

>IB TEST: ON

[OFF/ON]

Page 89: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 89 ENHANCED TECHNOLOGY

7. Group Setting Locate the cursor on “2.GROUP SETTING” in main menu, press [ENT] button and move to this

menu. In this menu, set line operating items.

Ficture 7-1. PRIMARY and ALTERNATE group

GROUP SETTING menu is divided in PRIMARY group and ALTERNATE group for the

convenience of user and it is applied according to the ON/OFF of „ALTERNATE SETTINGS

Lamp‟. When „ALTERNATE SETTINGS Lamp” is OFF, PRIMARY group setting is applied

and when „ALTERNATE SETTINGS Lamp‟ is ON, ALTERNATE group setting is applied.

The submenu of PRIMARY group and ALTERNATE group are same, as the following.

NOTE : Changed setting value are available only when they are saved.

Setting value can be saved by „Setting value save massage‟ indicated when depart to “*.

Setting Save” menu or topmenu.

[PRIMARY SETTING]

>1.PICKUP CURRENT

2.COLD LOAD PICKUP

3.DIRECTION

4.F.I SETTING TIME

5.F.I RESET

6.SECTION

7.PHASE DIFF

8.ON/OFF LEVEL

9.OVER CURRNET

*.SAVE SETTING

[GROUP SETTING]

>1.PRIMARY

2.ALTERNATE

Page 90: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

90 ENHANCED TECHNOLOGY

7.1. Fault pickup element

When occurs a fault in line, ETR300 detects and indicates the fault of each phase (A, B, C, N,

SEF). The fault type are permanent and temporary.

(1) Permanent FI Detect

It is used for the permanent FI detection of distribution line and it operates according to following

condition.

Permanent FI

TemporaryFI SETTING TIME

PermanentFI SETTING TIME

Temporary FI

Pickup Level

Voltage

Current

CLEAR

Permanent Fault

FI SETAUTORESET

Ficture 7-2. Permanent FI Detection(1)

Occurrence Condition

FI information is set when becomes dead line status after fault current over the minim. pickup

current flowed in Hot line status, and set the fault type in FI if dead line status is maintained

during setting time (permanent FI Set Time, 1sec~180sec possible to change, Default: 20 second).

But, when returns to Hot line status by reclosing before the permanent FI Set Time, FI Set Time is

initialized and returned to the first permanent FI occurrence condition.

Cancel Condition

If normal current is detected in hot line status after the permanent FI, permanent FI is cancelled

Page 91: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 91 ENHANCED TECHNOLOGY

automatically at the time that passed the permanent FI Set Time. Before the automatic FI cancel, it

can be cancelled by Fault Indicator Reset button or remote FI reset control. But, Reset order is not

working before the end of fault judgement after fault detection.

A,N B,N

0.6s 2s

①FI(A, N)

Fault Current(A,B,C,N,SEF)

FI(B)

⑤Fault Permanent

15s

A,N B,N

Permanent Fault

Detect Time

Pickup Level

Normal Current

Ficture 7-3. Permanent Fault Detection PickupOperation(2)

Fault is experienced in normal stats and FI is occurred in no voltage status (①②③④ time :

additional occurrence phase update

Fault Current Size is maximum RMS from the fault detection to no voltage and Event time is

no-voltage detect time.

※ Fault Current Event is occurred at the first fault(When Fault 'I' Report Evnet setting is

1Shot)

Additional FI is not set when fault has been detected in the same phaset during Sequence

operation(②④t). When detects fault of other phase during Sequence, FI is set. (③)

After finishing Sequence (Permanent Fault Judge time), “Permanent Fault Set” is sent to main

device(⑤)

“Permanent FI set” and “FI set” is cancelled after “FI Reset” order or Temporary FI judge

time after normal line reset.

Page 92: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

92 ENHANCED TECHNOLOGY

(2) Temporary FI Detection

It is used for Temporary fault monitoring of distribution line and operates based on the following

condition.

Temporary Fault

CLEAR

FI SET

Permanant FI

Temporary FI SETTING TIME

PermanantFI SETTING TIME

Temporary FI

Pickup Level

Voltage

Current

Ficture 7-4. Temporary Fault Detect Operation(1)

Set Condition

Temporary Fault set FI information when becomes dead line status after flowed fault current over

minimum pickup current. Temporary FI is set when pass the setting time (Temporary FI Set Time,

1sec~180sec possible to change, Default:2sec) after reset to nomal current from hot line status by

reclosing in source side.

Cancel Condition

FI and Fault Type(Temporary) are cleared only in FI Reset case. If FI is set again before the reset

status, delete prior FI and indicates the latest FI. Handle the existing FI Clear time at first than

new FI Set time

Page 93: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 93 ENHANCED TECHNOLOGY

Pickup Level

Normal Current

A,N B,N

0.6s 2s

①FI(A, N)

Fault Current(A,B,C,N,SEF)

② FI(B)

③Fault Temporary

Temporary Fault

Detect Time

Ficture 7-5. Temporary Fault Detect Operation( (2)

Fault is experienced in normal stats and FI is occurred in no voltage status (①② time :

additional occurrence phase update

Fault Current Size is maximum RMS from the fault detection to no voltage and Event time is

no-voltage detect time.

※ Fault Current Event is occurred at the first fault(When Fault 'I' Report Evnet setting is

1Shot)

Additional FI is not set when fault has detected in the same phase during Sequence operation.

When detects fault of other phase during Sequence, FI is set(②)

After normal line reset, send :Temporary Fault Set” information to main device when pass

Temporary FI judge time) (③)

When order “FI Reset", “Temporary FI Set” and “FISet” information is cancelled.

Fault Detect element setting items are same as following.

7.1.1. Pickup Current Setting

Move to “GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT” menu to set

Pickup Current.

GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / Phase

Range 0(OFF), 50 ~ 630A

Default 400 Step 5A

[PICKUP CURRENT]

>Phase: 400

Ground: 70

[OFF,50~630:5A]

Page 94: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

94 ENHANCED TECHNOLOGY

Set Pickup Current of phase.

GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / Ground

Range 0(OFF), 25 ~ 315A

Default 70 Step 5A

Set Pickup Current of ground.

GROUP SETTING / PRIMARY or ALTERNATE / PICKUP CURRENT / SEF

Range 0(OFF), 0.1 ~ 10.0A

Default 0.2 Step 0.1A

Set Pickup Current of SEF.

7.1.2. F.I Detect Time Setting

Move to “GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME” menu to set

F.I Detect Time Setting.

GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME / Permanent

Range 1 ~ 180sec

Default 20 Step 1sec

It is Delay time for Permanent Fault Detection.

GROUP SETTING / PRIMARY or ALTERNATE / F.I SETTING TIME / Temporary

Range 1 ~ 180sec

Default 20 Step 1sec

It is Delay time for Temporary Fault Detection.

[F.I SETTING TIME]

>Permanent : 20

>Temporary : 2

[1~180:1s]

[F.I SETTING TIME]

>Permanent : 20

>Temporary : 2

[1~180:1s]

[PICKUP CURRENT]

>Ground: 70

>SEF: 0.2

[OFF,0.1~10.0:0.1A]

[PICKUP CURRENT]

>Phase: 400

>Ground: 70

[OFF,25~315:5A]

Page 95: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 95 ENHANCED TECHNOLOGY

7.2. Inrush Current Restraint Function

ETR300 has restraint function to prevent the malfunction by inrush current, occurred by switch

closing by reclosing and local and remote after fault occurance. Inrush current restraint function

can be corrected in phase, ground and SEF.

Inrush current restraint function is applied when both Source side and Load side becomes hot

status from dead status or when close the switch. When transient current is over CLPU Pickup

level as Inrush current 1, fault pickup element operates normally instead of inrush current restraint

function. If it is under CLPU Pickup level as Inrushc current 2, restraint during RMT time and

operates the normal fault pickup element. But, if it is under Pickup current as Inrush current 3,

inrush current restraint function is cancelled after Reset time.

Time

Current

Overcurrent

CLPU

Pickup Level

Pickup Level

Trip

Outage time Restore Minimum Time

Trip

Inrush current 1

Inrush current 2

Inrush current 3

Ficture 7-6. Cold Load Pickup Characteristic

Page 96: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

96 ENHANCED TECHNOLOGY

Move to “GROUP SETTING / PRIMARY or ALTERNATE / Cold Load Pickup” menu to set

Inrush Current Restraint Function.

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / PHA(xCT)

Range 1 ~ 20 xMTC

Default 4 Step 1 xMTC

It is Phase Inrush Current Retraint multiple, this setting point is

multiple of Pickup Current(Phase)

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / GND(xCT)

Range 1 ~ 20 xMTC

Default 4 Step 1 xMTC

It is Ground Inrush Current Retraint multiple, this setting point is

multiple of Pickup Current(Ground)

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / SEF(xCT)

Range 1 ~ 20 xMTC

Default 4 Step 1 xMTC

It is SEF Inrush Current Retraint multiple, this setting point is multiple

of Pickup Current(SEF)

GROUP SETTING / PRIMARY or ALTERNATE / COLD LOAD PICKUP / RMT Time-PHA

Range 0.0 ~ 180.0 sec

Default 0.2 Step 0.1 sec

Set Reset time of Pickup Current (Phase).

When passes the setting time the inrush current restraint algorithm is

cancelled and operates normal phase fault pickup element, when

source side and load side becomes hot status from dead status or after

switch closing. (Pickup level resets tofault pickup current in Cold load

pickup level.)

※. NOTE : The setting item of RMT Time-GND and RMT Time-SEF are same with RMT Time-

PHA setting.

[ COLD LOAD PICKUP ]

>PHA(xMTC): 4

>GND(xMTC): 4

[1~20: 1xMTC]

[ COLD LOAD PICKUP ]

>RMT Time-PHA: 0.2

>RMT Time-GND: 0.2

[0.0~180.0:0.1s]

[ COLD LOAD PICKUP ]

>PHA(xMTC): 4

>GND(xMTC): 4

[1~20: 1xMTC]

[ COLD LOAD PICKUP ]

>GND(xMTC): 4

>SEF(xMTC): 4

[1~20: 1xMTC]

Page 97: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 97 ENHANCED TECHNOLOGY

Page 98: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

98 ENHANCED TECHNOLOGY

7.3. Directional Detection Function

When detect fault, ETR300 distinguish fault current direction and indicates the fault direction in

fault events. Directional Detection setting is composed of Phase, Ground, and SEF elements.

7.3.1. Phase Directional Detection

The direction distinction of phase fault current use normal voltage (V1) and normal current(I1) of

symmetry, and operation are as following.

Distinguish in Forward if I1 pahse about V1 is within ±90° according M.T.A basis and if not

in Reverse.

When fault is occurred in Voltage Metering nearby V1 value can be lost. In this case, use the

saved V1 and performs the directional detection

To operates in direction, V1 detected in fault status shall be bigger than min. polarizing

voltage. If V1 is smaller than this setting value does not detect direction, even the fault current

is over the minimum pickup current

RE

VE

RS

E

FO

RW

OR

D

V1

M.T.A= 60° LagI1

Zero

Torq

ue L

ine

Maximum Torque Line

Typical Fault Angle

Polarizing Referance

Voltage:

Ficture 7-7. Phase directional detection element characteristic

Page 99: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 99 ENHANCED TECHNOLOGY

Move to “GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE” menu to

set Phase Directional Detection Element.

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / Function

Range DISABLE, ENABLE

Default DISABLE Step -

Set [DISABLE/ENABLE] of Directional Detection, when occurs

phase fault.

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / M.T.A

Range 0 ~ 345˚

Default 60 Step 15˚

Set Maximum Torque Angle of normal current (I1) about normal

voltage (V1), when occurs phase fault.

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / M.P.V

Range 0(NONE), 10~80 %

Default 30 Step 1%

Set Minimum Polarizing Voltage about normal voltage(V1) to

distinguish the direction.

If is under normal voltage(V1), it does not distinguish the direction.

[PHASE]

>Function: DISABLE

>M.T.A: 60

[DISABLE/ENABLE]

[PHASE]

>M.T.A: 60

>M.P.V: 30

[0~345:1deg]

[PHASE]

M.T.A: 300

>M.P.V: 30

[NONE,10~80:1%]

Page 100: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

100 ENHANCED TECHNOLOGY

7.3.2. Ground and SEF Directional Detection

Directional Detection of Ground and SEF fault current use Zero Seq. Voltage(V0) and Zero Seq.

Current(I0).

REVERSE

FORW

ORD

-V0

M.T.A= 45° Lag

InZero Torque Line

Max

imum

Tor

que

Line

Typical Fault Angle

Polarizing Referance

Voltage:

V0

Ficture 7-8. Ground and SEF Directional Detection element characteristic

IF phase angle of I0 about –V0 is within ±90° based on Max. Torque Angle is Forword, if not

is Reverse.

To operates in direction, V0 detected in fault status shall be biggenr than min. polarizing

voltage. If V0 is smaller than each element setting does not detect direction, even fault current

and SEF are over min. pickup current setting value.

Move to “GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND” menu

to set Groud Directional Detection Element.

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / PHASE / Function

Range DISABLE, ENABLE

Default DISABLE Step -

Set [DISABLE/ENABLE] of directional detection, when occurs a

ground fault.

[PHASE]

>Function: DISABLE

>M.T.A: 60

[DISABLE/ENABLE]

Page 101: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 101 ENHANCED TECHNOLOGY

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND / M.T.A

Range 0 ~ 345˚

Default 60 Step 15˚

Set Maximum Torque Angle of zero current (I0) about zero

voltage(V0).

GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / GROUND / M.P.V

Range 0(NONE), 10 ~ 80%

Default 30 Step 1%

Set Minimum Polarizing Voltage about zero voltage (V0) to

distinguish the direction.

If is zero voltage (V0), it does not distinguish the direction.

※. NOTE : Move to “GROUP SETTING / PRIMARY or ALTERNATE / DIRECTION / SEF”

to set SEF Directional Detection element, and the SEF directional setting items are

same with phase direction setting item.

[GROUND]

>M.T.A: 60

>M.P.V: 30

[0~345:15deg]

[GROUND]

M.T.A: 60

>M.P.V: 30

[NONE,10~80:1%]

Page 102: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

102 ENHANCED TECHNOLOGY

7.4. SECTION

Locate the cursor on “6. SECTION” in PRIMARY or ALTERNATE menu, push [ENT] button

and move to this menu. Submenu is same as following.

7.4.1. SECTION FUNCTION

Locate the cursor on “1. FUNCTION” in SECTION menu, push [ENT] button and move to this

menu. Submenu is same as following. In this menu, set the use of Section Function and Section

Type.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Function

Range DISABLE, ENABLE

Default DISABLE Step -

Set [DISABLE/ENABLE] of Section Function.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Auto Close

Range DISABLE, ENABLE

Default DISABLE Step -

DISABLE : Auto opening is possible but auto closing is restraint.

ENABLE : Auto closing is possible by section reclosing function.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Section Type

Range V-T, O-T

Default V-T Step -

V-T : Operates in V-T mode(Section).

O-T : Operates in O-T mode(Tie).

[SECTION FUNCTION]

>Section Type: V-T

>Close Dir: ALWAYS

[V-T/O-T]

[SECTION FUNCTION]

>Function: DISABLE

>Auto Close: DISABLE

[DISABLE/ENABLE]

[SECTION FUNCTION]

>Function: DISABLE

>Auto Close:DISABLE

[DISABLE/ENABLE]

[SECTION]

1.FUNCTION

2.TIME

3.OPERATION COUNT

Page 103: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 103 ENHANCED TECHNOLOGY

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / FUNCTION / Close Direction

Range ALWAYS, SOURCE, LOAD

Default ALWAYS Step -

Set the voltage side applided in section function closing. Switch

operates by judging the voltage of selected side.

ALWAYS : Close by judging source side or load side voltage.

SOURCE : Close by judging source side voltage.

LOAD : Close by judging load side voltage.

7.4.2. SECTION TIME

Locate the cursor on “2. TIME” in SECTION menu, select [ENT] button and move to this menu.

In this menu, set time elements related to section function.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Open Delay

Range 0.1 ~ 25.5 sec

Default 3.0 Step 0.1 sec

Set Open Delay time. It is delay time to order an opening, when

detects fault in V-T mode and became no-voltage.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Close Wait

Range 1 ~ 255 sec

Default 17 Step 1 sec

Set Close Wait Time.

After opening by section on V-T mode, if it does not became hot

during Closing wait time Lockout.

But, it is only available when Autp Close setting is ENABLE status. In

other words, if Auto Close Setting is DISABLE status, it Lockout at

the sime time of opening by section function.

[SECTION TIME]

>Open Delay: 3.0

>Close Wait: 17

[1~255:1s]

[SECTION TIME]

>Open Delay: 3.0

>Close Wait: 17

[0.1~25.5:0.1s]

[SECTION FUNCTION]

>Section Type: V-T

>Close Dir: ALWAYS

[ALWAYS/SOURCE/LOAD]

Page 104: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

104 ENHANCED TECHNOLOGY

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Close Delay

Range 1 ~ 255 sec

Default 2 Step 1 sec

Set Close Delay Time.

It is delay time to order closing when becomes hot status before

Lockout after the opening by section in V-T mode.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Lockout

Range 1 ~ 255 sec

Default 1 Step 1 sec

Close by section in V-T mode, If there isn‟t a fault during Lockout

time Lockout in close status. If becomes no voltage by experience a

fault within Lockout time, Lockout the close after close delay.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Source Lockout

Range 1 ~ 255 sec

Default 4 Step 1 sec

Set Lockout Time of Source Side.

In normal condition(Live line), if Dead voltage is detected and it goes

in O-T(Outage Time) and within this O-T time, Live line comes back,

then, Source Lock time is applied and during this srouce locktime, if

Live line keeps last, it goes back to Home, however, During Source

Lock Time, if Deadline comes back again, automatically it does

Lockout

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Source Lockout

Range 1 ~ 255 sec

Default 4 Step 1 sec

Set Reset Time of Source Side.

In O-T mode, under automatic Lockout condition, if Live line is

detected, Source reset time is started and if the live line keeps last

until Source reset time, Lock is released.

[SECTION TIME]

>Source Lock: 4

>Source Reset: 4

[1~255:1s]

[SECTION TIME]

>Source Lock: 4

>Source Reset: 4

[1~255:1s]

[SECTION TIME]

>Close Delay: 2

>Lockout: 1

[1~255:1s]

[SECTION TIME]

>Close Delay: 2

>Lockout: 1

[1~255:1s]

Page 105: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 105 ENHANCED TECHNOLOGY

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / TIME / Resetraint

Range 1 ~ 255 sec

Default 60 Step 1 sec

In O-T mode, close after pass the Open Delay Time + Restraint Time

+ Close Time if becomes Dead line in Hot line status .

7.4.3. OPERATION COUNT

Locate the cursor on “3. OPERATION COUNT” in SECTION menu, press [ENT] button and

move to this menu. This menu set the use of section function and section type.

GROUP SETTING / PRIMARY or ALTERNATE / SECTION / OPERATION COUNT / Count

Range 1 ~ 4

Default 2 Step 1

Set operation count of section function.

[OPERATION COUNT]

>Count: 2

>

[1~4:1]

[SECTION TIME]

>Source Reset: 4

>Resetraint: 60

[1~255:1s]

Page 106: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

106 ENHANCED TECHNOLOGY

7.5. Phase angle unbalance

Locate the cursor on “7. PHASE DIFF” in PRIMARY or ALTERNATE menu, press [ENT] button

and move into this menu. In this menu, set phase angle difference elements.

Compare the phase of source side and phase of load side, in hot line status and open condition. It

is Phase angle inconsistency of is over set angle and normal if is under the set angle. But, phase

angle difference is not detected when source side or load side circuit is dead line.

GROUP SETTING / PRIMARY or ALTERNATE / PHASE DIFF / Level

Range 0(OFF), 5 ~ 80˚

Default 30 Step 5˚

Set phase angle difference.

GROUP SETTING / PRIMARY or ALTERNATE / PHASE DIFF / Time

Range 0.0 ~ 180.0sec

Default 4.0 Step 0.1sec

Set delay time of phase angle difference element.

7.6. Phase open/loss

Locate the cursor on “8. ON/OFF LEVEL”in PRIMARY or ALTERNATE menu, press [ENT]

button and move into this menu. In this menu, set phase open/loss elements.

If 1 or more than 2 phase among 3phase are over the Off Level of phase voltage, is phase

open/loss. If all 3 phase are Over On Level, they are normal voltage and phase open/loss detect is

cancelled. If all 3 phase are under Off Level, does not indicate phase open/loss as they are

normal(dead line)

GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / On Level

Range 70 ~ 85%

Default 80 Step 5%

Set normal voltage Level.

[PHASE DIFF]

>Level: 30

>Time : 4.0

[0.0~180.0:0.1s]

[ON/OFF LEVEL]

>On Level: 80

>Off Level: 50

[70~85:5deg]

[PHASE DIFF]

>Level: 30

Time : 4.0

[0(OFF),5~80:5deg]

Page 107: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 107 ENHANCED TECHNOLOGY

GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / Off Level

Range 30 ~ 75%

Default 50 Step 5%

Set phase open/loss Level.

GROUP SETTING / PRIMARY or ALTERNATE / ON/OFF LEVEL / Time

Range 0.1 ~ 180.0sec

Default 4.0 Step 0.1sec

Set delay time of line phase open/loss element.

7.7. Overcurrent detect element

Locate the cursor “10. OVER CURRENT”in PRIMARY or ALTERNATE menu, press [ENT]

button and move into this menu. In this menu, set overcurrent detect element.

Overcurrent detect element is managed as PQ monitoring function item.

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / PHA-Pickup

Range 0(OFF), 50 ~ 630A

Default 400 Step 5A

Set pickup level of over current for phase.

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / PHA-Time

Range 0.0 ~ 180.0 sec

Default 2.0 Step 0.1sec

Set detection time of over current for phase.

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / GND-Pickup

Range 0(OFF), 25 ~ 315A

Default 100 Step 5A

Set pickup level of over current for ground.

[ON/OFF LEVEL]

>Off Level: 50

>Time : 4.0

[0.1~180.0:0.1s]

[OVER CURRENT]

>PHA-Pickup: 400

>PHA-Time: 2.0

[0.0~180.0:0.1s]

[OVER CURRENT]

>GND-Pickup: 100

>GND-Time: 2.0

[0(OFF),25~315:5A]

[OVER CURRENT]

>PHA-Pickup: 400

>PHA-Time: 2.0

[0(OFF),50~630:5A]

[ON/OFF LEVEL]

>On Level: 80

>Off Level: 50

[30~75:5deg]

Page 108: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

108 ENHANCED TECHNOLOGY

GROUP SETTING / PRIMARY or ALTERNATE / OVER CURRENT / GND-Time

Range 0.0 ~ 180.0 sec

Default 2.0 Step 0.1sec

Set detection time of over current for ground.

[OVER CURRENT]

>GND-Pickup: 100

>GND-Time: 2.0

[0.0~180.0:0.1s]

Page 109: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 109 ENHANCED TECHNOLOGY

8. EVENT Place the cursorn on

Place the curser on “3.EVENT”, press [ENT] button to move into this menu.

ETR300-R records all events during the operation, occurred events are recorded separately such as

operation event, fault event, system event, set change event, load event and diagnostic event. All

events are recorded in order(FIFO). In this menu, all events can be checked and deleted.

This menu has sub-menu as below. Press [ENT] to move into sub-menu.

.

8.1. Operation Event

Operation event records max. 256 events. When Recloser operates(OPEN/CLOSE), operation

status and control signal(LOCAL/REMOTE) is recorded in operation event.

Move to “MAIN MENU / EVENT / OPERATION” to confirm operation events.

[003/256] CLOSE

CONTROL : REMOTE

2007/10/01 00:00:01

[002/256] OPEN

CONTROL : REMOTE

2007/10/01 00:00:02

[001/256] CLOSE

CONTROL : REMOTE

2007/10/01 00:00:03

[▼][▲] are used to check event. [001/256] is the latest event record.

Trigger Source

[EVENT]

>1.OPERATION

2.FAULT

3.FAULT CYCLE

4.SYSTEM

5.SET CHANGE

6.AVER.LOAD/MIN

7.PEAK.LOAD/HOUR

8.PEAK.LOAD/DAY

9.DIGNOSTIC

10.PQM

11.CLEAR SAVED DATA

Page 110: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

110 ENHANCED TECHNOLOGY

STATUS

- CLOSE

- OPEN

- EARTH CLOSE (ECLOSE)

- EARTH OPEN (EOPEN)

CONTROL

- MANUAL: Switch mechanical manual operation.

- LOCAL: Operation at local

- REMOTE: Remote operation.

Trigger Time

Monitor changes of Trigger source status in every 5 msec.

Trigger Capacity

Save maximum 256 events.

8.2. Fault Event

Fault event records maximum 256 events. Fault event records fault detection time, fault current

sixe of each phase, fault direction and fault events of each phase can be checked.

Move to “MAIN MENU / EVENT / FAULT” to confirm fault events.

[003/256] TO

Target : A B C T

2008/10/01 00:01:00

[002/256] 2 EV

Target : A B C F

2008/10/01 00:02:00

[001/256] 1 EV

Target : A B C R

2008/10/01 00:03:01

[003/256] TO

A:00440T B:00440T

C:00446T N:00006

SEF:00000mA

[002/256] 1 EV

A:00440FF B:00440FF

C:00446FF N:00006

SEF:00000mA

[001/256] 1 EV

A:00440FR B:00440FR

C:00446FR N:00006

SEF:00000mA

ENT ENT ENT

[▼][▲] buttons are used to check fault events. Press [ENT] button in fault event screen to check

fault current value. And press [ENT] again to return to fault event screen. [001/256] is the latest

event record.

Page 111: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 111 ENHANCED TECHNOLOGY

Fault Event Information(EV)

Information before deciding the Fault type(permanent, temporary) is recorded.

SEQUENCE Sequence is recoded from one [FAULT].

TARGET Record Fault detection phase and Fault Direction.

001/256 Shows the latest event in order and records 100 events.

FAULT

CURRENT

Max fault current is displayed on fault occurring. Fault Detection phase and Fault

Current Direction are indicated.

- F: Fault Detection

- FF: Forward Fault Detection

- FR: Reverse Fault Detection

Total Information(TO)

Fault type (PermanentFault/Temporary Fault) and time, maximum current are recorded.

TARGET Record Fault detect phase and Fault type( P: Permanent fault, T: Temporary fault)

001/256 Shows the latest event in order and max.256 events are recorded.

FAULT

CURRENT

Shows maximum current value when occurs fault and indicates fault detection

fault type.

Trigger Source

Taget Element

- A: A phase

- B: B phase

- C: C phase

- N: N phase

- S: SEF

Fault Detect Element

- T: Temporary fault (TEMPORARY)

- P: Permanent fault (PERMANENT)

Detect direction

- F: FORWARD

- R: REVERSE

Fault Current[A]: A phase, B phase, C phase, N phase, SEF

Page 112: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

112 ENHANCED TECHNOLOGY

Trigger Time

Moniters changes of Trigger source status in every 1/4 cycle.

Trigger Capacity

Save maximum 256 events.

8.3. Fault Cycle - Summary

Fault wave is recorded up to 8 fault waves. Fault wave information is displayed on LCD.

Captured waveform can be checked in interface software.

Move to “MAIN MENU / EVENT / FAULT CYCLE” to confirm fault cycle summary.

[003/ 8] PU

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 01:00:00

[002/ 8] PU

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 02:00:00

[001/ 8] PU

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 03:00:00

[▼][▲] is used to check the fault event. [001/008] is the latest event record.

Trigger Source

Fault wave captured time.

- PU: Pick up time.

- TR: Trip time.

- PU&TR: Picku up & Trip time

Fault current [A]: A phase, B phase, C phase, N phase

Trigger Time

Moniters changes of Trigger source status in every 1/4 cycle.

Trigger Capacity

Maximum 8 events are recorded. (20cycles 8EA).

Page 113: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 113 ENHANCED TECHNOLOGY

8.4. System Events

System events records maximum 2048 events.

Move to “MAIN MENU / EVENT / SYSTEM” to confirm system events.

[003/2048] CPULINK

STATUS : HI/ASSERT

2008/10/01 00:00:01

[002/2048] CPULINK

STATUS : HI/ASSERT

2008/10/01 00:00:02

[001/2048] CPULINK

STATUS : HI/ASSERT

2008/10/01 00:00:03

[▼][▲] button is used to check the records. [001/2048] is the latest event record.

Trigger Source

52A Contact

Front panel control

AC supply

External control

Fail operation

External input/output status

System alarm

Sleep Mode

GAS STATUS

※. NOTE : Refer to “Appendix C.LOGIC BIT Attributes & Description” for mored details

about trigger source.

Trigger Time

Monitors changes of Trigger source status in every 1/4 cycle.

Trigger type

Record when Pickup(HI/ASSERT) or Dropout(LO/DEASSERT).

Storage Capacity

Save maximum 2048 events.

Page 114: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

114 ENHANCED TECHNOLOGY

8.5. Set Change Event

Set Change Event records maximum 100 events.

Move to “MAIN MENU / EVENT / SET CHANGE” to confirm set change events.

[001/100] LOCAL

TARGET : GLOBAL

2008/10/01 00:00:01

[002/100] LOCAL

TARGET : GLOBAL

2008/10/01 00:00:02

[001/100] LOCAL

TARGET : GLOBAL

2008/10/01 00:00:03

[▼][▲] button is used to check the records. [001/100] is the latest event record.

Trigger Source

Changed set menu

- GLOBAL SETTING

- PRIMARY SETTING

- ALTERNATE SETTING

Change method

- LOCAL: Set change at local

- REMOTE: Set change in remote

- PROGRAM: Set change by Interface software

※. NOTE : Refer to “Appendix C.LOGIC BIT Attributes & Description” for more details

about trigger source

Trigger Time

Monitoring change of Trigger source status in every 5msec.

Storage Capacity

Saves maximum 100 events.

Page 115: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 115 ENHANCED TECHNOLOGY

8.6. Aver. Load/Min

Records Average load value every 15 minutes. As records maximum 1024 values, about 10 days

events can be recorded.

Move to “MAIN MENU / EVENT / AVER. LOAD/MIN” to confirm aver. load/min events.

[0003/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 00:00:15

[0002/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 00:00:30

[0001/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 00:00:45

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

ENT ENT ENT

[▼][▲] button is used to check the events. To check real active power and reactive power, press

[ENT] button. To return back to previous screen, press [ENT] again. [0001/1024] is the latest

event record.

Trigger Source

Measured current [A]: A phase, B phase, C phase, N phase

Measured active power [kW]: 3 phases, A phase, B phase, C phase

Measured reactive power [kVar]: 3phases, A phase, B phase, C phase

Trigger Time

Monitors changes of Trigger source status in every 15min.

Storage Capacity

Saves maximum 1024 events.

8.7. Peak. Load/Hour

Records Peak load event.As records maximum 1024 events, about 43 days events can be recorded.

Page 116: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

116 ENHANCED TECHNOLOGY

Move to “MAIN MENU / EVENT / PEAK. LOAD/HOUR” to confirm peak. load/hour events.

[0003/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 01:00:00

[0002/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 02:00:00

[0001/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 03:00:00

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

ENT ENT ENT

[▼][▲] button is used to check the events. To check real active power and reactive power, press

[ENT] button in Current display screen. To return back to current display screen, press [ENT]

again. [0001/1024] is the latest event record.

Trigger Source

Measured current [A]: A phase, B phase, C phase, N phase

Measured active power [kW]: 3 phases, A phase, B phase, C phase

Measured reactive power [kVar]: 3phases, A phase, B phase, C phase

Trigger Time

Monitors changes of Trigger source status in every 1hour..

Storage Capacity

Saves maximum 1024 events.

8.8. Peak. Load/Day

Records Peak Load/Day events.As saves maximum 1024 events, about 1024 days event can be

recorded.

Move to “MAIN MENU / EVENT / PEAK. LOAD/DAY” to confirm peak. load/day events.

Page 117: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 117 ENHANCED TECHNOLOGY

[0003/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/01 00:00:00

[0002/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/02 00:00:00

[0001/1024]

A: 00000 B: 00000

C: 00000 N: 00000

2008/10/03 00:00:00

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

P3: 00000/ 00000

PA: 00000/ 00000

PB: 00000/ 00000

PC: 00000/ 00000

ENT ENT ENT

[▼][▲] button is used to check the events. To check real active power and reactive power, press

[ENT] button in Current display screen. To return back to current display screen, press [ENT]

again. [0001/1024] is the latest event record.

Trigger Source

Measured current [A]: A phase, B phase, C phase, N phase

Measured active power [kW]: 3 phases, A phase, B phase, C phase

Measured reactive power [kVar]: 3phases, A phase, B phase, C phase

Trigger Time

Monitors changes of Trigger source status in every 1 day.

Storage Capacity

Saves maximum 1024 events.

8.9. Diagnostic Event

Diagnostic event records and shows maximum 512 events.

Move to “MAIN MENU / EVENT / DIGNOSTIC” to confirm Diagnostic Event.

[003/512] SELFTOK

STATUS : HI/ASSERT

2008/10/01 00:00:01

[002/512] SELFTOK

STATUS : HI/ASSERT

2008/10/01 00:00:02

[001/512] SELFTOK

STATUS : HI/ASSERT

2008/10/01 00:00:03

Page 118: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

118 ENHANCED TECHNOLOGY

[▼][▲] button is used to check the events. [001/512] is the latest event record.

Trigger Source

DSP Failure

ADC Failure

RTC Failure

Memory Failure

Flash-Rom Failure

Circuit Voltage Failure

Globlal Setting Failure

Primary Setting Failure

Alternate Setting Failure

Event Failure

Count Failure

DO Failure

Closing Failure

Opening Failure

※. NOTE : Refer to “Appendix C.LOGIC BIT Attributes & Description” for more details

about trigger source.

Trigger Time

Monitors status of Trigger source in every 5msec.

Trigger type

Records Dignostic event Pickup(HI/ASSERT) or Dropout(LO/DEASSERT).

Storage Capacity

Saves maximum 512 events.

When occurs Self Diagnosis Fault, handle as following

Table 8-1.Treatment method of Self Diagnosis Failure

No. Diagnosis item Treatment Period Treatment Method

1 DSP within 200msec Change to FI Detect Restrain

Page 119: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 119 ENHANCED TECHNOLOGY

2 ADC 1/4 cycle Change to FI Detect Restrain

3 RTC 1hour, when booting Change the date to Jan. 1st, 1970

4 Memory 1hour, when booting Restart

5 Flash-Rom When Read and WriteFlash-

Rom , when booting Restart

6 Circuit Voltage 1/4 cycle Change to FI Detect Restrain

7 Global Setting When change setting, when

booting Change to Global setting value

Default value

8 Primary Setting When change setting, when

booting Change to Primary Setting value

Default value

9 Alternate Setting When change setting, when

booting Change to Alternate Setting value

Default value

10 Event When save and read event Event initialization

11 Count When write and read count Counter initialization

12 DO Signal 50msec Block the output power

13 Close/Opem When Closing and Openning Need to check in local

Page 120: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

120 ENHANCED TECHNOLOGY

8.10. PQM

Power Quality Management (PQM) detect event records 100 events.

Move to “MAIN MENU / EVENT / PQM” to confirm PQM events.

[003/100] UBI

TARGET : 1WAY

DATA: 102%

2008/10/01 08:10:20

[002/100] OVS

TARGET : 1WAY A

DATA: 1668V

2008/10/01 09:00:00

[001/100] SWL&TEMP

TARGET : 1WAY A

DATA: 1670V 337 Cyc

2008/10/01 10:00:03

[▼][▲] button is used to check the event. [001/100] is the latest event record.

Trigger Source

PQM detect element.

- Sag(SAG): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),

Long Time(LONG)

- Swell(SWL): Instantaneous(INST), Momentary(MOME), Temporary(TEMP),

Long Time(LONG)

- Interruption(INT): Momentary(MOME), Temporary(TEMP), Sustained(LONG)

- Source side Unbalance Voltage(UBV)

- Load side Unbalance Voltage (UBL)

- Current Unbalance(UBI)

- Source side Over voltage (OVS)

- Load side Over voltage (OVL)

- Over Current

- Voltage Harmonic distortion (VTH)

- Current Harmonic distortion (ITH)

PQM element detected phase: Aphase, Bphase, Cphase

PQM element related measured value

PQM detect time(cycle)

Trigger Time

Monitors status of Trigger source in every 5msec.

Page 121: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 121 ENHANCED TECHNOLOGY

Storage Capacity

Saves maximum 100 events.

8.11. Clear Saved Data

Move to “EVENT / CLEAR SAVED DATA” to clear saved data.

EVENT / CLEAR SAVED DATA

Clear Saved Data

Select an item to delete and press[ENT] button.

If deleting is completed, “EVENT CLEAR SUCCESS”

message is displayed.

8. ABOVE ALL

1 ~ 7 items are all deleted.

[EVENT CLEAR]

EVENT CLEAR SUCCESS

[CLEAR SAVED DATA]

>1.OPERATION

2.FAULT

3.SYSTEM

4.SET CHANGE

5.LOAD PROFILE

6.DIGNOSTIC

7.PQM

8.ABOVE ALL

Page 122: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

122 ENHANCED TECHNOLOGY

9. Maintenance

Place the curser on “4. MAINTENANCE” in Main menu, press [ENT] button to move into this

menu. This menu displays Maintenance information.

This menu has sub-menu as below and by pressing [ENT] button, move into sub-menu.

9.1. Count

This menu displays counter information and has submenus as following.

9.1.1. CCU Count

Move to “MAINTENANCE / COUNT / CCU” to confirm CCU (ETR 300)count.

MAINTENANCE / COUNT / CCU

Restart Count

ETR300-R restart number is displayed.

Diagnostic Count

ETR300-R Diagnostic Count is displayed.

[COUNT]

>1.CCU

2.OPERATION

3.FAULT

4.PQM

[CCU]

RESTART : 30

DIAGNOSTIC : 0

[MAINTENANCE]

>1.COUNT

2.INTERRUT TIME

3.CONTACT WEAR

4.DATA RESET

5.CCU INFO

Page 123: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 123 ENHANCED TECHNOLOGY

9.1.2. Operation Count

Move to “MAINTENANCE / COUNT / OPERATION” to confirm operation count.

MAINTENANCE / COUNT / OPERATION

Displays operation counter of switch.

9.1.3. Fault Count

Move to “MAINTENANCE / COUNT / FAULT” to confirm fault count.

MAINTENANCE / COUNT / FAULT

[FAULT] 1/3

TOT: 0 SEF: 0

A : 0 B : 0

C : 0 N : 0

[FAULT-P] 2/3

TOT: 0 SEF: 0

A : 0 B : 0

C : 0 N : 0

[FAULT-T] 3/3

TOT: 0

A : 0 B : 0

C : 0 N : 0

Number of fault is displayed. This COUNT menu consists in 3

pages. Use [▼][▲] button to move into sub-menu.

FAULT(1/3)

Total number of fault detection and fault detection number per phase

ard displayed.

FAULT(2/3)

Total number of PERMANENT fault and number of fault per phase

are displayed.

FAULT(3/3)

Total number of TEMPORARY fault and number of fault per phase

are displayed.

9.1.4. PQM Count

This menu displays PQM count information and has the following submenu.

[OPERATION]

COUNT : 0

Page 124: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

124 ENHANCED TECHNOLOGY

9.1.4.1. INTERRUPT

Move to “MAINTENANCE / PQM / INTERRUPT” to confirm interrupt count.

MAINTENANCE / COUNT / PQM / INTERRUPT

[INTERRUPT] 1/2

TOTAL: 0

A : 0 B : 0

C : 0

[INTERRUPT] 2/2

MOMENTARY : 0

TEMPORARY : 0

SUSTAINED : 0

Number of Interruption is displayed. This COUNT menu consists in 2

pages and use [▼][▲] button to move into each pages.

INTERRUPT(1/2)

Total number of Interruption and number of interruption per phase are

displayed.

INTERRUPT(2/2)

Number of fault per type is displayed on Interruption.

[PQM COUNT]

>1.INTERRUT

2.SAG

3.SWELL

4.HARMONICS

5.CURR UNBALANCE

6.VOLT UNBALANCE

7.UNDER VOLTAGE

8.OVER VOLTAGE

9.OVER CURRENT

10.UNDER FREQUNCY

Page 125: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 125 ENHANCED TECHNOLOGY

9.1.4.2. Sag

Move to “MAINTENANCE / COUNT / PQM / SAG” to confirm sag count.

MAINTENANCE / COUNT / PQM / SAG

[SAG] 2/2

INS: 0 MOM: 0

TMP: 0 LON: 0

[SAG] 1/2

TOTAL: 0

A : 0 B : 0

C : 0

Number of Sag is displayed. This COUNT menu consists 2 pages and

use [▼][▲] buttons to move into sub-menu.

SAG(1/2)

Total number of Sag occurred and number of Sag per phase are

displayed.

SAG(2/2)

Number of Sag per type is displayed.

9.1.4.3.Swell

Move to “MAINTENANCE / COUNT / PQM / SWELL” to confirm swell count.

MAINTENANCE / COUNT / PQM / SWELL

[SWELL] 1/2

TOTAL: 0

A : 0 B : 0

C : 0

[SWELL] 2/2

INS: 0 MOM: 0

TMP: 0 LON: 0

Number of Swell occurred is displayed. This COUNT menu consists

of 2 pages and use [▼][▲] button to move into sub-menu.

SWELL(1/2)

Total number of Swell and number of Swell per phase are displayed.

SWELL(2/2)

Number of Swell per type is displayed.

Page 126: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

126 ENHANCED TECHNOLOGY

9.1.4.4. Harmonics

Move to “MAINTENANCE / COUNT / PQM / HARMONIC” to confirm sag count.

MAINTENANCE / COUNT / PQM / SWELL

[VTHD] 1/2

TOTAL: 0

A : 0 B : 0

C : 0

[ITHD] 2/2

TOTAL: 0

A : 0 B : 0

C : 0

Number of Harmonic distortion is displayed. The COUNT menu

consists 2 pages and use [▼][▲] buttons to move into sub-menu.

VTHD(1/2)

Total number of Voltage Harmonic distortion and number of voltage

harmonic distortion per phase are displayed.

ITHD(2/2)

Total number of current harmonic distortion and number of current

harmonic distortion per phase are displayed.

9.1.4.5. Current Unbalance

Move to “MAINTENANCE / COUNT / PQM / CURRENT UNBALANCE” to confirm current

unbalance count.

MAINTENANCE / COUNT / PQM / CURRENT UNBALANCE

Number of Current Unbalance occurred is displayed.

[CURRENT UNBALANCE]

COUNT : 0

Page 127: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 127 ENHANCED TECHNOLOGY

9.1.4.6. Voltage Unbalance

Move to “MAINTENANCE / COUNT / PQM / VOLTAGE UNBALANCE” to confirm voltage

unbalance count.

MAINTENANCE / COUNT / PQM / VOLTAGE UNBALANCE

Number of voltage unbalance occurred is displayed.

SOURSE SIDE

Number of voltage unbalance at source side is displayed.

LOAD SIDE

Number of voltage unbalance at load side is displayed.

9.1.4.7. Under Voltage

Move to “MAINTENANCE / COUNT / PQM / UNDER VOLTAGE” to confirm under voltage

count.

MAINTENANCE / COUNT / PQM / UNDER VOLTAGE

[LS-UNDER VOLT] 2/2

TOTAL: 0

A : 0 B : 0

C : 0

[VS-UNDER VOLT] 1/2

TOTAL: 0

A : 0 B : 0

C : 0

Number of under-voltage is displayed. This COUNT menu consists 2

pages and use [▼][▲] button to move into sub-menu.

VS-UNDER VOLT(1/2)

Total number of undervoltage at source side and number of

undervoltage per phase are displayed.

LS-UNDER VOLT (2/2)

Total number of undervoltage at load side and number of

undervoltage at load side per phase are displayed.

[VOLTAGE UNBALANCE]

SOURCE SIDE : 0

LOAD SIDE : 0

Page 128: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

128 ENHANCED TECHNOLOGY

9.1.4.8. Over Voltage

Move to “MAINTENANCE / COUNT / PQM / OVER VOLTAGE” to confirm over voltage

count.

MAINTENANCE / COUNT / PQM / OVER VOLTAGE

[VS-OVER VOLT] 1/2

TOTAL: 0

A : 0 B : 0

C : 0

[LS-OVER VOLT] 2/2

TOTAL: 0

A : 0 B : 0

C : 0

Number of over-voltage is displayed. This COUNT menu consists 2

pages and use [▼][▲] button to move into sub-menu.

.

VS-OVER VOLT(1/2)

Total number of overvoltage at source side and number of

undervoltage per phase are displayed.

LS-OVER VOLT (2/2)

Total number of overvoltage at load side and number of overvoltage

at load side per phase are displayed.

9.1.4.9.Under Frequency

Move to “MAINTENANCE / COUNT / PQM / Under Frequency” to confirm under frequency

count.

MAINTENANCE / COUNT / PQM / UNDER FRQUENCY

Number of underfrequency is displayed.

[UNDER FREQUENCY]

COUNT : 0

Page 129: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 129 ENHANCED TECHNOLOGY

9.2. Interrupt Time

Move to “MAINTENANCE / INTERRUPT TIME” to confirm interrupt time.

MAINTENANCE / INTERRUPT TIME

[INTERRUP TIME] 1/2

TOTAL: 0

A : 0 B : 0

C : 0 N : 0

[INTERRUP TIME] 2/2

MOMENTARY : 0

TEMPORARY : 0

SUSTAINED : 0

Accumulated interrupt time is displayed. This COUNT menu consists

2 pages and use [▼][▲] button to move into sub-menu.

INTERRUPT TIME(1/2)

Total accumulated time and accumulated time per phase are

displayed. Time unit is Cycle.

INTERRUPT TIME(2/2)

Accumulated time per interrupt type is displayed, time unit is cycle.

Page 130: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

130 ENHANCED TECHNOLOGY

9.3. Contact Wear

Move to “MAINTENANCE / CONTACT WEAR” to confirm contact wear.

MAINTENANCE / CONTACT WEAR

Displays switch contact wear in percentage.

9.4. Data Reset

Move to “MAINTENANCE / DATA RESET”. This menu resets COUNT and Maintenance data.

MAINTENACE / DATA RESET

Saved data reset

Select an item to delete and press[ENT] button.

If deleting is completed, “EVENT CLEAR SUCCESS”

message is displayed.

※. NOTE :

1) „OPERATION COUNT‟ is reset by a set value in „MAIN MENU/

GLOBLA SETTING/ MONITERING/ OPERATION COUNT‟.

2) „CONTACT WEAR‟ is reset by a set value in „MAIN MENU/

GLOBLA SETTING/ MONITERING/ CONTACT WEAR‟.

3) Except „OPERATION COUNT‟ and „CONTACT WEAR, all data

is reset for 0.

10. ABOVE ALL

1 ~ 9 item data are all reset.

[CONTACT WEAR-%]

A : 100.00

B : 100.00

C : 100.00

[EVENT CLEAR]

EVENT CLEAR SUCCESS

[DATA RESET]

>1.CCU COUNT

2.OPERATION COUNT

3.FAULT COUNT

4.DELTA I COUNT

5.PQM COUNT

6.COUNT ALL

7.INTERRUPT COUNT

8.CONTACT WEAR

9.ENERGY

10.ABOVE ALL

Page 131: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 131 ENHANCED TECHNOLOGY

9.5. CCU Information

Move to “MAINTENANCE / CCU INFO” to confirm ccu information.

MAINTENANCE / CCU INFO

ENT

Present CCU(ETR300-S) information is displayed.

Prog Opt:ox70310156

MPU Ver: 1.0

DSP Ver: 1.0

CPU Ver: 1.0

TYPE:ETR300S-11D-40-

24-11D-1FF-DMN

61-0101-0000-KR-1000

Page 132: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

132 ENHANCED TECHNOLOGY

10. Time Place the curser on “5.TIME” in Main menu, press [ENT] button to move in this menu.

TIME

Set present date and time.

1) Press [ENT] button to select and change a setting.

2) To change a number, use [▲][▼] button and to move next item,

press [ENT] button.

3) To save all changed setting, press [ENT].

[CURRENT TIME]

2006/11/05 21:02:38

PRESS <ENT> TO SET

[SETTING TIME]

2006/11/05 21:02:38

USE [UP/DOWN/ENTER]

PRESS <FUNC> : ABORT

[SAVE TIME]

2006/11/06 15;01:50

PRESS <ENT> TO SAVE

Page 133: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 133 ENHANCED TECHNOLOGY

11. Status

Place the curser on “6. STATUS” in Main menu, press [ENT] button to move in this menu. This

menu has sub-menu as below. Press [ENT] to move into sub-menu.

11.1. Switch

You can confirm in “MAIN MENU / STATUS / RECLOSER”

STATUS/ SWITCH

Present switch and ETR300 status are displayed.

Use [▼] [▲] button to check all items.

SWITCH

Displays main device status.

OPEN, CLOSE, TROUBLE(Device Trouble status)

PANEL LOCK

Displays panel lock status.

LOCK, UNLOCK

CONTROL

Operation control select is displayed.

REMOTE, LOCAL, TROUBLE(Device Trouble Status)

SECTION

Display whether to use section function.

DISABLE, ENABLE

PHA-PROTECT

Phase protection function status is displayed.

DISABLE, ENABLE

GND-PROTECT

[SWITCH]

>SWITCH :TROUBLE

PANEL LOCK : UNLOCK

CONTROL : LOCAL

SECTION :DISABLE

PHA-PROTECT:DISABLE

GND-PROTECT:DISABLE

LOCKOUT :LOCKOUT

POWER : OFF

BATTERY : NORMAL

BAT’CHRGER : NORMAL

DOOR : CLOSE

CCU ADDRESS: 0

MASTER ADDR: 65534

HANDLE LOCK:LOCKOUT

GAS : NORMAL

[STATUS]

>1.SWITCH

2.INPUT PORTS

3.OUTPUT PORTS

Page 134: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

134 ENHANCED TECHNOLOGY

STATUS/ SWITCH

Ground protection function status is displayed.

DISABLE, ENABLE

LOCKOUT

Section operation status is displayed.

RESET, RUNNING, LOCKOUT

POWER

External power supply status is displayed.

ON, OFF

BATTERY

Battery status is displayed.

NORMAL, FAIL

BAT‟ CHARGER

Battery charger status is displayed.

NORMAL, FAIL

DOOR

Door status is displayed.

OPEN, CLOSE

CCU ADDRESS

DNP set address of ETR300 is displayed.(0~65535)

MASTER ADDR

DNP Host Address (0~65534:65535 is used for Broadcast)

GAS

Circuit breaker gas pressure status is displayed.

NORMAL, LOW

Page 135: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 135 ENHANCED TECHNOLOGY

11.2. Input Ports

You can confirm in “MAIN MENU / STATUS / INPUT PORTS”

STATUS/ INPUT PORTS

Displays 16 input terminal(IN101 ~ IN108 and IN208 ~ IN208) status

Depending on input signal, “HI/ASSERT” or “LO/DEASSERT”is

displayed.

[▼] [▲] button is used to check all input terminal status.

11.3. Output Ports

You can confirm in “MAIN MENU / STATUS / OUTPUT PORTS”

STATUS/ OUTPUT PORTS

Displays 16 output terminal(OUT101 ~ OUT108 and OUT208 ~

OUT208) status.

Depending on output signal, “HI/ASSERT” or “LO/DEASSERT”is

displayed.

[▼] [▲] button is used to check all input terminal status.

[OUTPUT PORTS]

OUT 101:LO/DEASSERT

OUT 102:LO/DEASSERT

OUT 103:LO/DEASSERT

OUT 104:LO/DEASSERT

OUT 105:LO/DEASSERT

OUT 208: HI/ASSERT

[INPUT PORTS]

IN 101 :LO/DEASSERT

IN 102 :LO/DEASSERT

IN 103 :LO/DEASSERT

IN 104 :LO/DEASSERT

IN 105 :LO/DEASSERT

IN 208 : HI/ASSERT

Page 136: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

136 ENHANCED TECHNOLOGY

12. Metering

Place the curser on “7. MERING” in Main menu, press [ENT] button to move in this menu. This

menu displays present measured value and has sub-menu as following. Press [ENT] to move into

sub-menu.

12.1. Current

ETR300 metering and indicates the following current items.

IA : Displays the measured phase A RMS current and phase (A, deg°)

IB : Displays the measured phase B RMS current and phase (A, deg°)

IC : Displays the measured phase C RMS current and phase (A, deg°)

IN : Displays the measured ground RMS current and phase (A, deg°)

SEF: Displays the measured sensitive earth RMS current and phase (A, deg°)

You can confirm in “MAIN MENU / METERING / CURRENT”

MAIN MENU / METERING / CURRENT

Current per phase and angle per phase are displayed.

Use [▲] [▼] keys to move to next value.

[CURRENT]

IA: 0 A 000.0°

IB: 0 A 000.0°

IC: 0 A 000.0°

IN: 0 A 000.0°

SEF: 0mA 000.0°

[METERING]

>1.CURRENT

2.VOLTAGE

3.FREQUENCY

4.POWER

5.ENERGY

6.DEMAND

7.UNBALANCE

8.HARMONICS

9.TRUE R.M.S

10.TD

11.CCU SEF

Page 137: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 137 ENHANCED TECHNOLOGY

12.2. Voltage

ETR300 metering and indicates the following voltage items.

VS-PN: Voltage per phase and angle per phase at source side, are displayed(㎸, deg°).

VS-PP: Phase to phase voltage and angle at source side, are displayed(㎸, deg°).

VS-SEQ: Forward/Reverse/Zero sequence voltage and angle at source side, are displayed(㎸,

deg°).

VL-PN: Voltage per phase and angle per phase at load side, are displayed (㎸, deg°).

VL-PP: Phase to phase voltage and angle at load side, are displayed (㎸, deg°).

VL-SEQ: Forward/Reverse/Zero sequence voltage and angle at load side, are displayed (㎸,

deg°).

You can confirm in “MAIN MENU / METERING / VOLTAGE”

MAIN MENU / METERING / VOLTAGE

[VS-PN]

A : 00.00 kV ∠000.0°

B : 00.00 kV ∠000.0°

C : 00.00 kV ∠000.0°

[VL-PP]

RS: 00.00 kV ∠000.0°

ST: 00.00 kV ∠000.0°

TR: 00.00 kV ∠000.0°

[VL-SEQ]

V1: 00.00 kV ∠000.0°

V2: 00.00 kV ∠000.0°

V3: 00.00 kV ∠000.0°

[GPT]

VN: 00.00 kV ∠000.0°

[VS-PP]

AB: 00.00 kV ∠000.0°

BC: 00.00 kV ∠000.0°

CA: 00.00 kV ∠000.0°

[VS-SEQ]

V1: 00.00 kV ∠000.0°

V2: 00.00 kV ∠000.0°

V0: 00.00 kV ∠000.0°

[VL-PN]

R : 00.00 kV ∠000.0°

S : 00.00 kV ∠000.0°

T : 00.00 kV ∠000.0°

Voltage and angle per phase are displayed. Use [▼][▲] button to check it.

Page 138: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

138 ENHANCED TECHNOLOGY

12.3. Frequency

ETR300 metering and indicates the following frequency items.

;

Hz: Present frequency is displayed.

You can confirm in “MAIN NEMU / METERING / FREQUENCY”

MAIN MENU / METERING / FREQUENCY

Frequency measured value is displayed.

12.4. Power

ETR300 metering and indicates the following power items.

POWER-KW/KVAR/KVA: Per phase, active power/apparent power/reactive power are

displayed.

POWER FACTOR: Power factor per phase is displayed.

You can confirm in “MAIN NEMU / METERING / POWER”

MAIN MENU / METERING / POWER

[POWER- KW/KVAR/KVA]

A : 0000 0000 0000

B : 0000 0000 0000

C : 0000 0000 0000

[POWER FACTOR]

A : 000

B : 000

C : 000

Per phase, power and power factor are displayed.

Use [▼][▲] button to check the power metering information.

[FREQUENCY]

0.00 Hz

Page 139: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 139 ENHANCED TECHNOLOGY

12.5. Energy

ETR300 metering and indicates the following energy items.

FORWARD – KWh/KVARh: Energy per phase in forward is displayed.

REVERSE – KWh/KVARh: Energy per phase in reverse is displayed.

You can confirm in “MAIN NEMU / METERING / ENERGY”

MAIN MENU / METERING / ENERGY

[FORWARD- KWh/KVARh]

A : 000000 000000

B : 000000 000000

C : 000000 000000

[REVERSE- KWh/KVARh]

A : 000000 000000

B : 000000 000000

C : 000000 000000

Energy is displayed. Use [▼][▲] button to check the energy

metering information.

12.6. Demand Current

You can confirm in “MAIN MENU / METERING / DEMAND”

MAIN MENU / METERING / DEMAND

Load current per phase are displayed.

[DEMAND CURRENT]

A: 0000 A B: 0000 A

C: 0000 A N: 0000 A

SEF :00.000 A

Page 140: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

140 ENHANCED TECHNOLOGY

12.7. Unbalance

ETR300 metering and indicates the following unbalance items.

SOURCE-VOLT: Voltage unbalance at source side is displayed.

LOAD-VOLT: Voltage unbalance at load side is displayed.

CURRENT: Current unbalance is displayed.

.

You can confirm in “MAIN MENU / METERING / UNBALANCE”

MAIN MENU / METERING / UNBALANCE

Unbalance of metering value is displayed.

12.8. Harmonics

You can confirm in “MAIN MENU / METERING / HARMONICS”

MAIN MENU / METERING / HARMONICS

[%V-Harm. A/B/C]

THD : 0.0 0.0 0.0

02H : 0.0 0.0 0.0

03H : 0.0 0.0 0.0

[%V-Harm. A/B/C]

04H : 0.0 0.0 0.0

05H : 0.0 0.0 0.0

06H : 0.0 0.0 0.0

[%V-Harm. A/B/C]

31H : 0.0 0.0 0.0

[%I-Harm. 31H]

A : 0.0 B : 0.0

C : 0.0 N : 0.0

[%I-Harm. 02H]

A : 0.0 B : 0.0

C : 0.0 N : 0.0

[%I-Harm. THD]

A : 0.0 B : 0.0

C : 0.0 N : 0.0

Voltage and current harmonic rate are displayed. Use [▼][▲] button to check harmonic rate

information.

[UNBALANCE- %]

SOURCE-VOLT: 0.00

LOAD-VOLT: 0.00

CURRENT: 0.00

Page 141: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

- 141 ENHANCED TECHNOLOGY

12.9. True R.M.S

You can confirm in “MAIN NEMU / METERING / TRUE R.M.S”

MAIN MENU / METERING / TRUE R.M.S

[VOLTAGE-TURE R.M.S]

A : 000 V

B : 000 V

C : 000 V

[ CURRENT- TURE R.M.S]

A : 0.0A B : 0.0A

C : 0.0A N : 0.0A

TRUE R.M.S voltage and current per phase are displayed. Use

[▼][▲] button to check TURE R.M.S. information .

12.10. TD Monitoring

You can confirm in “MAIN MENU / METERING / TD MONITORING”

MAIN MENU / METERING / TD MONITORING

TD input value is displayed.

12.11. CCU Reference

You can confirm in “MAIN MENU / METERING / CCU REF”

MAIN MENU / METERING / CCU REF

ETR300 reference values are displayed.

[CCU Rer]

+5V: 4.9 -5V:-4.8

Temp: 37°

[TD MONITERRING]

TD1: 00.0 TD2: 00.0

TD3: 00.0 TD4: 00.0

TD5: 00.0

Page 142: 2.Manual ETR300S V1.0 Eng

SWITCH CONTROL ETR300-S01 http://www.entecene.co.kr

142 ENHANCED TECHNOLOGY

13. PLC function

ETR300 has changeable PLC for user. PLC has Timer, Counter and Event to control input and

output. Circuit can be optimized to omit unnecessary timer and aux. relay. During ETR300

running, in case the circuit needs to be changed, PLC can be used to meet user‟s need. PLC is

programmed in “ETR300 Interface Software”.

Ficture 13-1. PLC Edit Screen