GEN-X Series Elegant Range - Engineering Data
Contents Sections Page
Introduction 3
Service Entry / Access Requirements 3
Dimensions 4
Typical Airfl ow Arrangement 5
Guide Specifi cations 6
Ancillaries and Options 8
General Details 11
Schematic Diagram 12
Cooling Performances 16
Electrical Details 17
3Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
The Product
The GEN-X Elegant Range of Precision Air Conditioning Units are compact and stylish with the better performance and quality demanded by today’s market.
These units are designed and built within a Quality Assurance System conforming to BS EN ISO 9001, using our unrivalled experience in Precision Air Conditioning, with extensive testing of components and complete systems. Every aspect is engineered to ensure maximum reliability, economy of operation and long working life, together with ease of installation and maintenance.
The Range
The GEN-X Elegant Range comprises four types of systems, fi ve models in fi ve cabinet sizes, with nominal capacities from 50 kW to 90 kW.
Key to Type Codes
Example: E X D 50 A
Model Type = A – Air Cooled (W – Water Cooled, DA/DW – Dual Coil)
Unit Size = Nominal Capacity in KW
Airfl ow type = D – Downfl ow (U – Upfl ow)
Series: X = GEN-X Series
Range: E = Elegant Range
800
Full Front Service
INTRODUCTION
SERVICE ENTRY / ACCESS REQUIREMENTS
4 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
1800 2050
2300 2550
2800
1954
885*
1954
885*
1954
885*
50
70
65
80
90
Model Size 50 65 70 80 90
Weight “A” (kgs) 620 725 810 910 985
“W” (kgs) 635 740 830 930 1015
“DA” (kgs) 685 802 898 1010 1098
“DW” (kgs) 700 817 918 1030 1128
DIMENSIONS
Notes: * For “DA” and “DW” version, unit depth shall be 985mm.
5Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
• Type “A” - Downfl ow, into raised fl oor return from room or ceiling.
• Type “B” - Upfl ow, with horizontal discharge plenum (as shown) or room/ceiling discharge, and front grille return.
• Type “C” - Upfl ow, with ceiling duct extension and underfl oor return.
TYPICAL AIRFLOW ARRANGEMENT
6 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Cabinet
The cabinets are modular design for fl exibility and scalability. The cabinets are attractively designed with rounded corners and perfect fi tting panels. All Units have a rigid powder coated frame for maximum strength and corrosion protection, with hinged front panels to provide easy access for installation and maintenance. Panels are lined with class “O” non-eroding insulation material with both thermal and acoustic properties. External panels are fi nished with epoxy coating in dark grey colors for corners and in light grey colors for access door and removable panels.
Cooling Coil
The coils shall be multi-row constructed from 3/8” OD copper tubes with aluminium fi ns. Large surface areas shall ensure high sensible heat ratios and low airside pressure drops, resulting in reduced fan power requirements and noise levels. Main and intermediate stainless steel drain trays shall be included to ensure effi cient removal of the condensate via factory fi tted traps.
Units shall have two independent refrigeration circuits, each with a liquid distributor, electronic expansion valve, ball valve, sight glass and fi lter drier; these components to be housed in the services section at the right hand end of the cabinet.
For Dual Coil units, the chilled water circuit shall be fi tted with a modulating 2 way valve with manual override facility and water pressure / temperature test points whilst the refrigeration section shall have two independent refrigeration circuits.
Fans
For downfl ow units, large, low speed, double inlet, double width fans with forward curved impellers and “sealed for life” ball or roller bearings shall be used to minimise noise levels. Units shall have one, two or three fans, depending on size, each fan to have its own TEFC motor and speed variation by manually adjustable pulley. Units shall include fan fail / airfl ow alarm which shall in the event of an alarm condition disable all outputs except unit run.
For upfl ow units, energy effi cient direct driven centrifugal plug fans with backward curve impellers shall be used. Units shall have one, two or three fans, depending on size, each fan to have its own integrated TEFC motor. Units shall include fan fail / airfl ow alarm which shall in the event of an alarm condition disable all outputs except unit run.
Electric Heaters
Electric heaters shall have Incoloy sheathed elements with stainless steel fi nning balanced over three phases and rated to operate at black heat. Control shall be in two or three stages, each being protected by a high temperature safety cut-out.
Compressor and Safety Controls
Fully hermetic high effi ciency scroll compressor(s) are located at the service section of the units. The compressor(s) is resiliently mounted on a robust frame, which assists to minimize noise and vibration transmission to the structure. Each compressor is fi tted with back-seating isolating valves and on larger models oil level sight glass is fi tted. Protection is provided by an internal self-setting overload device and pressure relief valve. An external adjustable high pressure cut off switch; with manual reset facility is provided for high pressure protection, in addition to the internal devices. To protect primarily against loss of refrigerant charge, a pressure transducer and temperature sensor is provided to monitor the system superheat.
Filtration
The fi lters shall have an effi ciency of 30% ASHRAE 52/76 Eurovent 4/5 arrestance value 90% (EU4). They shall be fi tted in the return air stream, held by quick release retaining clips, and be accessible from the front of the unit. A differential pressure switch shall be fi tted which, through the alarm facility in the microprocessor controller, shall indicate when the fi lters need changing.
Humidifi er
The humidifi er is a self contained, steam generating electrode boiler type with disposable cylinder, located in the bottom section of the unit. A humidifi er includes proportional steam output and microprocessor control with alarms and diagnostic facilities. The control system allows the use of a wide range of water conditions and optimizes drain down frequency for maximum operational economy. To avoid earth leakage, the power supply is disconnected from the electrodes when the system is in drain mode.
Electrical and Control Panel
The electrical panel is located within the unit and shall be accessible from the front. The electrical panel includes:
• Controller baseboard and interface cards (if applicable).
• MCB’s and contactors for fans, compressors, heaters, humidifi er as appropriate.
• Control circuit is 24VAC Class 2 low voltage including a circuit breaker protection (if applicable).
Low voltage, high voltage and grounding wires are color coded and numbered, and neatly run in trunking segregating high and low voltages.
GUIDE SPECIFICATIONS
7Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Electronic Expansion Valve (EEV)
Electronic Expansion Valve (EEV) shall be fi tted for each refrigerant circuit. EEV shall have a PID modulation control and shall be capable of responding quickly to changes in the system, ensuring a stable superheat.
Microprocessor Controls With In-house Program
Note: For more detailed information, refer to a separate - “Engineering Data - Genius Controller”.
A unit fi tted with the Genius III Controller, an advance microprocessor controlling system developed by CITEC to control and monitor the air conditioning unit. This provides maximum economy in operation, a comprehensive intelligent alarm system and a wide range of information for operators and service engineers. The controller provides a user-friendly environment to ease the system setup and operation.
In addition to precise control of temperature and humidity, the system includes the following features:
Graphical icon functions: Unit Run, Cooling, Heating, Humidifying, Dehumidifying and Alarm.
i) Auto Sequencing with either Automatic Rotation or Timezone Rotation.
ii) Coded security access for set point parameter adjustment.
iii) Supporting various communication protocols whilst maintaining a stable and reliable environment.
iv) Three choices of user interface, i.e. Liquid Crystal Display, Monochrome Touch Screen Display and Colour Touch Screen Display to satisfy wide range of application.
a) Basic LCD Display (CGD1) if selected indicates unit function via icons, display control conditions and report alarm events.
b) Touch Screen graphical display if selected allows the management of complex graphical images up to 320x240 pixels in size and with up to 256 colours (CGD3 only), indicating function via various animated icons, non-proportional fonts in Unicode format, alarms, and trend graphs of temperature and humidity.
Versions available:
• Monochrome Touch Screen Version (CGD2)
• Colour Touch Screen Version (CGD3)
GUIDE SPECIFICATIONS
8 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Ceiling Return Duct
Ceiling return duct comprises unit matched panels lined with 25mm thick insulation bolted to the top of the Precision Air Conditioning Unit on site. The duct is suitable for downfl ow units only. Information on the height between the top of the Precision Air Conditioning Unit and the underside of the suspended ceiling is needed when ordering. The overall height of the duct will be this dimension plus 50mm.
Horizontal Discharge Section (Upfl ow Models Only)
Horizontal discharge section consists of a double defl ection grille fi tted into a rigid sheet metal box. The complete assembly is bolted to the top of the Precision Air Conditioning Unit on site. The grille has two sets of blades, which allow for both vertical and horizontal directional adjustment of airfl ow. The standard height for this section is 500mm.
Ceiling Discharge Section
For upfl ow units, where the Precision Air Conditioning Unit is required to discharge into the ceiling void, a Ceiling Discharge Extension is available. This consists of a rigid riveted sheet metal assembly comprising of unit matched front; rear and end panels lined with 25mm thick insulation. The extension is bolted to the top of the Precision Air Conditioning Unit on site. Information on height between the top of the Precision Air Conditioning Unit and the underside of the suspended ceiling is needed when ordering. The overall height of the duct will be this dimension plus 50mm.
High Effi ciency Filters
High effi ciency fi lters can be provided in place of the standard fi lters, with an effi ciency of 80% ASHRAE52/76 (Eurovent F7). These fi lters are fi tted in the return air side of the Precision Air Conditioning Unit within the main cabinett.
Serviceable Type Humidifi er
The life of a humidifi er bottle is considered over when the build up of solid coats the electrodes such that full current levels can no longer be achieved. A serviceable system can reuse the humidifi er bottle, thereby dramatically increases the service life of the cylinder and hence provides much reduced maintenance costs, particularly in areas where the available water supply is a limitation.
L.P.H.W. Heating
Units may be fi tted with a Low Pressure Hot Water heating coil in place of the standard electrical heating. A modulating 2 way valve controls water fl ow through the coil.
Duties of these coils are nominally the same as standard electric heating, based on fl ow and return hot water temperatures of 82ºC and 71ºC respectively.
Note: Please consult factory before ordering.
Water Detection Kit
Water sensors, connected directly to the Precision Air Conditioning Unit microprocessor control system, are located in:-
• Condensate drain pan – detecting undue water level.
• Underfl oor water tape, supplied loose with suffi cient length of cable to cover the entire length of the respective unit.
When water is detected, the Precision Air Conditioning Unit’s alarm system is triggered and it shall stop the unit operation (selectable option).
Sump Pump
Where, due to location, it is not possible to gravity drain units, a sump pump can be fi tted to collect any condensate and pump it to the nearest convenient drain point (maximum available pump head 5.7 meters). For units fi tted with humidifi ers, a larger capacity sump pump is available to accommodate the additional discharge of hot water during humidifi er drain down cycles (maximum available pump head 7 meters).
Note: When using sump pump a minimum of a 200mm high plinth is required.
EC Fan
The Electronically Commutated Fan (EC Fan) is the state of the art high effi ciency direct driven backward curved fan with integrated variable speed control capability. EC fans enable fl exible air volume control with highest effi ciency operation. In addition, power consumption of EC fan is much lower than conventional AC fan and more reliable. In auto mode, fan speed will adjust accordingly to suit room’s cooling load, thereby providing further energy saving.
Differential Pressure Transmitter
The transmitter is used to detect the pressure difference between the room and the underfl oor. This option is usually used together with the frequency inverter or variable speed fan, to maintain a constant pressure difference between the room and the underfl oor.
ANCILLARIES AND OPTIONS
9Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Remote Control and Supervisory Systems
Note: For more detailed information, refer to separate - “Engineering Data - Genius Controller”.
The Control & Supervisory System is required to develop a balanced function between economics, operating costs, safety and comfort with human considerations being most important.
• Webgate
Webgate is an innovative electronic device that measures the same size as a normal desktop modem. It can connect the Genius controller to a local network based on the standard Ethernet and TCP/IP protocol.
• pCOWEB
pCOWEB is an add-on card that allows communication between the Genius controller with BACnet Ethernet, BACnet over IP, SNMP protocol (v1 & v2c), HTTP protocol, FTP and DHCP protocol.
• pCONET
pCONET is an add-on card that allows communication with the BACnet MS/TP protocol.
• Telemon
Telemon designed to proactively monitor and control Precision Air Conditioning Units in a critical environment. It monitors and changes the parameters of a precision air conditioning unit such as temperature, humidity, cooling & heating demands, rotation confi guration and time control.
• PlantVisor
Plantvisor, with its web server function, can work on PCs connected in an TCP/IP network. This allows sharing the data and information dealt with by the plantvisor with more than one user at the same time.
• RS485 Serial Card
This is an add-on card which allows the Genius controller to interface directly with a RS485 supervisory network.
• LonWorks Interface Card
This is an add-on card that allows the Genius controller to interface with LonWork network.
• PlantWatch Pro
PlantWatch PRO is a new solution for the supervision of Precision Air Conditioning installations, with the possibility to connect and control up to 100 units in a serial network. It comes with a colour LCD touch screen and practical easy to use menus that enables simple and convenient navigation by the users. In addition, its supervisory task can be performed without the use of a PC (although a PC can be connected if necessary), thus providing a perfect solution for environments that do not use a dedicated computer system for this purpose. For alerting purpose, alarm messages can be send via SMS, fax or e-mail.
Fan Speed Controller (Air Cooled System Only)
Use to maintain the condensing pressure and thus condensing temperature of the refrigerant system by modulating the fan speed of the outdoor air cooled condenser. This is to ensure that the condensing pressure does not drop below the operational limit of the compressor thereby damaging it. A pressure sensing probe is attached to the discharge line to measure the condensing pressure and send its reading to the controller which in turn gives a 0 to 10Vdc analogue signal to the FSC module to modulate the fan speed of the air cooled condenser.
Frequency Inverter
The purpose of the frequency inverter is to vary the fan speed of the unit by changing the frequency of the power supply to the fan. In auto mode, fan speed will adjust accordingly to suit room’s cooling load.
Split Units
The coil/fan section & the compressor section of the unit can be split into 2 separate sections to allow transportation / access to areas with limited space. All access panels could also be removed & packaged separately. The 2 sections & the panels could then be reassembled at site. All electrical cables crossing the 2 sections should also be reconnected at site. These cables are coiled in a tidy fashion for transit & will be labeled for easy identifi cation. For the pipework, some brazing work would be required at site. All piping will be solder type by default unless specifi ed otherwise. The 2 sections could also be placed & crated separately as an additional option.
Floor Sealing Plate (Upfl ow Models Only)
A sealing plate can be provided to seal the bottom section of the upfl ow models to prevent air from being bypassed through the bottom of the unit instead of from front grille. This would not be necessary if unit is sitting on a solid fl oor.
Water Flow Detection (Chilled Water System Only)
A differential pressure switch is used to detect the availability of water fl ow through the system. Alarm shall be activated when there is no water fl ow detected across the system.
ANCILLARIES AND OPTIONS
10 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
Water Temperature Sensor (Chilled Water and Water Cooled Systems Only)
The water temperature sensor is use for sensing the water in from the cooling water source and water out temperature reading from the unit.
Double Skin Panels
To reduce sound “break-out”, double skin panels are available. The standard double skin panel consist of standard 25mm class “O” insulation glued to the inside of the external panels which is sandwiched between external panel and a 1mm thick galzanised sheet. Double skin panels should preferably be specifi ed with Compression Locks because of their extra weight and to ensure tight closure.
Fire Alarm Relay
A 24Vdc relay is used to receive external signal 24Vdc, probably from fi re control panel. When the signal is received, unit shall stop operation.
Hot Gas Bypass (Air Cooled and Water Cooled Systems Only)
DX models can be fi tted with hot gas bypass compressor capacity control. This consists of a solenoid valve & a hot gas bypass valve located in between the discharge line & at a point after the EEV & before the coil inlet. A sensing line will be fi tted to the suction & the hot gas valve can be adjusted to bypass discharge gas accordingly to maintain the pressure at the suction line above the preset level.
Water Regulating Valve (Water Cooled Systems Only)
Used to maintain the condensing pressure and thus condensing temperature of the refrigerant system by modulating the amount of water fl ow into the water cooled condenser. This is to ensure that the condensing pressure does not drop below the operational limit of the compressor thereby damaging it. A pressure line from the valve is attached to the discharge line to sense the condensing pressure.
ANCILLARIES AND OPTIONS
Note: Please note that certain combinations of options are not available while some other combinations might require further upgrades or additional accessories to be added. To check whether a certain combination of options is available, please consult factory.
11Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
MODELS 50 65 70 80 90
Coil Face AreaNo. of FansAirfl ow
Fan MotorsSPL
m2
-m3/sm3/hrkW
dB(A)
1.62
3.5126002 x 3.0
71
1.92
4.2151202 x 3.0
72
2.32
5.0180002 x 4.0
72
2.73
5.820880 3 x 3.0
73
3.03
6.7241203 x 4.0
74
Electric Reheat:No. of Heater BanksCapacity
-kW
212
218
318
318
327
Humidifi er:Capacity PowerFeed ConnectionDrain Connection
kg/hrkWmmmm
86.003/4”32
1511.253/4”32
1511.253/4”32
1511.253/4”32
1511.253/4”32
“A” Version
Compressors ModelNo. of CompressorsAir Cooled Condensers ModelNo. of Air Cooled Condensers
ZR
CACR
1082
3262
1252
3262
1442
5062
1602
5062
1902
5062
Connections:Liquid LineDischarge LineCondensate Drain
inchinchinch
5/8”1 1/8”
22
5/8”1 1/8”
22
3/4”1 1/8”
22
3/4”1 1/8”
22
7/8”1 3/8”
22
“W” Version
Compressors ModelNo. of CompressorsAir Cooled Condensers ModelNo. of Water Cooled Condensers
ZR
B
1082
10/602
1252
10/602
1442
10/802
1602
10/802
1902
80/602
Connections:Condenser Water InCondenser Water OutCondensate Drain
mmmminch
424222
424222
545422
545422
545422
“DA” and “DW” Version
Connections:Chilled Water InChilled Water OutCondensate Drain
mmmminch
424222
424222
545422
545422
545422
Air Filter Size
Downfl ow:310X700X100372X700X100
mmmm
4-
-4
23
42
-6
Upfl ow:390X800X100640X800X100
mmmm
11
-2
21
12
-3
Notes: (1) For “DA” and “DW” Version DX system details, please refer to “A” and “W” Version.(2) SPL measured at 1m distance, free fi eld, with fans running, download version.
GENERAL DETAILS
12 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
SCHEMATIC DIAGRAM: “A” VERSIONS
Notes: This schematic depicts a single circuit only.Refer to General Details for actual number of circuits per model.
Eva
por
ator
Coi
l.
Con
den
sate
tray
Hum
idifi
er(if
fitt
ed)
Con
den
sate
Dra
in
Hum
idifi
erD
rain
H
umid
ifier
Wat
er S
upp
ly(if
fitt
ed)
400v
3ph
+ N
sup
ply
PS
DD
isch
arge
line
Liq
uid
line
AIR
CO
OLE
D C
ON
DE
NS
ER
PR
EC
ISIO
N A
IR C
ON
DIT
ION
ING
UN
IT
Pre
cisi
on U
nit
Cas
ing
2.5m
m s
q 3
cor
ein
terc
onne
ctin
g ca
ble
per
circ
uit.
T
Filte
r /
Drie
r
Sig
ht G
lass
Acc
ess
Valv
e
Com
pre
ssor
Ele
ctro
nic
Exp
ansi
onVa
lve
LEG
EN
D
S D
P
Bal
l Val
ve
Pre
ssur
eTr
ansd
ucer
Com
pre
ssor
Suc
tion
Valv
e
Com
pre
ssor
Dis
char
ge V
alve
Tem
per
atur
e S
enso
rT
13Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
SCHEMATIC DIAGRAM: “W” VERSIONS
Notes: This schematic depicts a single circuit only.Refer to General Details for actual number of circuits per model.
Eva
por
ator
Coi
l
Con
den
sate
tray
Hum
idifi
er(if
fitt
ed)
Con
den
sate
Dra
in
Hum
idifi
erD
rain
H
umid
ifier
Wat
er S
upp
ly(if
fitt
ed)
400v
3ph
+ N
sup
ply
PS
D
Dis
char
ge li
ne
Liq
uid
line
PR
EC
ISIO
N A
IR C
ON
DIT
ION
ING
UN
IT
Pre
cisi
on U
nit
Cas
ing
Con
den
ser
Wat
er O
ut
Con
den
ser
Wat
er In
Wat
erC
oole
dC
ond
ense
r
T
Filte
r /
Drie
r
Sig
ht G
lass
Acc
ess
Valv
e
Com
pre
ssor
Ele
ctro
nic
Exp
ansi
onVa
lve
LEG
EN
D
S D
P
Bal
l Val
ve
Pre
ssur
eTr
ansd
ucer
Com
pre
ssor
Suc
tion
Valv
e
Com
pre
ssor
Dis
char
ge V
alve
Tem
per
atur
e S
enso
rT
14 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
SCHEMATIC DIAGRAM: “DA” VERSIONS
A - Chilled Water In
B - Chilled Water Out
A B
CW
DX
CW
DX
Liquid line
Dischargeline
Dischargeline
Liquid line
AIR COOLED CONDENSERAIR COOLED CONDENSER
Filter / Drier
Sight Glass
Access Valve
Compressor
Electronic ExpansionValve
Modulating 2 wayChilled Water control Valve
LEGEND
S
D
P
Ball Valve
Pressure Transducer
Compressor SuctionValve
Compressor DischargeValve
Temperature Sensor
Pressure / Test Point
P
P
S D
S D
PRECISION AIR CONDITIONING UNIT
Precision Unit Casing
2.5mm sq 3 coreinterconnecting cableper circuit.
2.5mm sq 3 coreinterconnecting cableper circuit.
400v3ph + N supply
Humidifier(if fitted)
T
T
Condensate tray
Condensate Drain HumidifierDrain
HumidifierWaterSupply (if fitted)
T
15Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
SCHEMATIC DIAGRAM: “DW” VERSIONS
A B
CW
DX
CW
DX
P
P
S D
S D
Cooling Tower
(Field Supplied)
WATER COOLED CONDENSER
PRECISION AIR CONDITIONING UNIT
Precision Unit Casing
T
T
Condensatetray
Condensate Drain
A - Chilled Water In
B - Chilled Water Out
Filter / Drier
Sight Glass
Access Valve
Compressor
Electronic ExpansionValve Modulating 2 wayChilled Water control Valve
LEGEND
S
D
P
Ball Valve
Pressure Transducer
Compressor SuctionValve Compressor DischargeValve
Temperature Sensor
Pressure / Test Point
400v3ph + N supply
Humidifier(if fitted)
HumidifierDrain
HumidifierWaterSupply (if fitted)
T
16 Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
MODELS 50 65 70 80 90
Airfl owm3/sm3/hr
3.5012600
4.20 15120
5.00 18000
5.8020880
6.70 24120
“A” Version
Air On: 22oC, 50 %RHTotalSensibleS.H.R.
kWkW-
48.1840.810.85
55.0647.520.86
68.0657.890.85
72.5463.610.88
84.9773.830.87
Air On: 24oC, 45 %RHTotalSensibleS.H.R.
kWkW-
49.5544.100.89
56.8551.430.90
70.0262.570.89
74.5468.530.92
87.2379.440.91
“W” Version
Air On: 22oC, 50 %RHTotalSensibleS.H.R.Condenser Water Flow RateUnit Pressure Drop
kWkW-
l/skPa
50.9442.290.832.3515.70
59.8150.050.843.2621.40
69.4158.600.844.3020.90
76.4965.930.865.2825.50
92.7478.450.857.6051.90
Air On: 24oC, 45 %RHTotalSensibleS.H.R.Condenser Water Flow RateUnit Pressure Drop
kWkW-
l/skPa
52.2545.620.873.1316.30
61.3954.020.883.6922.30
71.3363.290.894.2522.00
78.9671.360.904.7126.80
95.3284.740.895.6554.50
Chilled Water Coil Performance of “DA” and “DW” Version
Air On: 22oC, 50 %RHTotalSensibleS.H.R.Chilled Water Flow RateUnit Pressure Drop
kWkW-
l/skPa
43.4838.780.892.0818.20
51.7846.260.892.4829.70
61.1254.680.902.9220.80
72.1664.360.893.4430.90
79.6071.580.903.8014.20
Air On: 24oC, 45 %RHTotalSensibleS.H.R.Chilled Water Flow RateUnit Pressure Drop
kWkW-
l/skPa
50.3045.200.902.4024.30
59.9653.960.902.8638.60
70.9864.000.903.4027.30
83.5075.020.903.9840.80
93.7884.700.904.4819.60
Notes:
Cooling performances are GROSS and based on: (1) Standard EU4 fi ltration and 50 Pa external static. (2) Performance at ambient temperature 35ºC.(3) Standard matching condenser.(4) 0.5ºC suction line loss.(5) R407C Refrigerant.(6) Chilled water in/out based on 7/12ºC, Condenser water in/out based on 30/35ºC.
COOLING PERFORMANCES
17Version: 1.0/2009/Gen-X/E02
GEN-X Series Elegant Range - Engineering Data
17Version: 1.0/2008/Gen-X/E02
MODELS 50 65 70 80 90
Operating Amps † FLA 49.3 60.9 69.3 77.2 93.3
Connected Loads Amps† CLA 60.0 76.0 86.1 95.0 112.8
Maximum Inrush Amps † LRA 158.3 182.6 190.7 238.5 281.2
Operating kW kW 26.8 35.1 39.2 42.9 52.5
Connected Load kW kW 34.2 45.1 50.7 55.0 63.6
“A” / “DA” Versions
Due to our policy of continuous development and improvements, the specifi cations and data herein are subject to change without prior notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated herein.All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however, should independently evaluate the suitability of each product for their own application. CITEC makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding this use.
MODELS 50 65 70 80 90
Operating Amps † FLA 46.8 58.4 64.3 72.2 88.3
Connected Loads Amps† CLA 57.5 73.5 81.1 90.0 107.8
Maximum Inrush Amps † LRA 155.8 180.1 185.7 233.5 276.2
Operating kW kW 26.2 35.1 38.1 41.8 51.4
Connected Load kW kW 33.6 44.5 49.6 53.8 62.5
“W” / “DW” Versions
† - Refer to Note 3.
Notes:
(1) Controls are 24 volt. (2) Data may vary slightly depending on operating conditions. (3) Maximum values depend on worst condition when operating automatically and could be:
(a) Fans + Cooling + Humidifying (b) Fans + Heating + Humidifying (c) Fans + Cooling + Reheating (Dehum)
ELECTRICAL DETAILS: 400 VOLT / 3 PH+N / 50 HZ
18 Version: 1.0/2009/Gen-X/E02
NOTE
19Version: 1.0/2009/Gen-X/E02
NOTE
CITEC INTERNATIONAL SDN. BHD. (372827-H) No. 47, (PT 63846), Lorong Jala 14/KS10, Telok Gong,
42000 Port Klang, Selangor Darul Ehsan, Malaysia .Tel: +603 3134 2668 Fax: +603 3134 2648
Website: www.citec.com.myEmail: [email protected]
Version: 1.0/2009/Gen-X/E02