Sizing Formula Required Variables: A. Desired/ Minimum boiler runtime* B. Boiler/system minimum input (BTU/Hr) C. Minimum system heat load (BTU/Hr) D. System Water Supply Temp (°F) = Buffer Tank Sizing Formula Controllers Vaughn Thermal Corporation Water Heaters How is a Buffer Tank Sized? A Buffer Tank is sized to provide a minimum runtime for the boiler plant. Use the equation below to find the properly sized tank for your specific application. Tank connection diameters should be sized to meet the maximum flow requirements of the application. Controllers Vaughn Thermal Corporation Water Heaters Tel: (978) 462-6683 Fax: (978) 462-6497 www.vaughncorp.com 26 Old Elm Street P.O. Box 5431 Salisbury, MA 01952-5431 MADE IN THE USA A buffer tank is a cost effective solution to prevent short cycling in various boiler applications, while also serving as a hydraulic separator, ensuring that the heating system flow and boiler flow do not affect one another. Both of these issues if left unchecked can lead to excessive boiler cycling, reduced efficiencies, and premature equipment failure. Made with heavy guage steel on site in Massachusetts, the Vaughn D4B is designed to provide years of reliable service. What is a Buffer Tank? Tank Capacity Vaughn Buffer Tanks (Model D4B) Buffer Tank Capacity = Run Time x (Boiler/System Minimum Input - Minimum System Load) E. F. System Return Water Temp (°F) Calculate system T (temp rise) by subtracting E from D in °F) *Minimum boiler runtime (Industry suggestion is a 10 minutes at a minimum) 10 (20,000 - 10,000) 20 x 500 (System supply temp-system return temp) X 500 A x (B-C) F x 500 Example: } Tank Capacity = = Model S 10 D4B

Upload: others

Post on 21-Oct-2021

11 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Vaughn Buffer Tank Sizing Guide - vaughncorp.com

Sizing Formula

Required Variables: A.Desired/ Minimum boiler runtime*

B.Boiler/system minimum input (BTU/Hr)

C. Minimum system heat load (BTU/Hr)

D.System Water Supply Temp (°F)

=

Buffer Tank Sizing Formula

Controllers

Vaughn Thermal Corporation

Water Heaters

How is a Buffer Tank Sized?A Buffer Tank is sized to provide a minimum runtime for the boiler plant. Use the equation below to find the properly sized tank for your specific application. Tank connection diameters should be sized to meet the maximum flow requirements of the application.

Controllers

Vaughn Thermal Corporation

Water HeatersTel: (978) 462-6683 Fax: (978) 462-6497

www.vaughncorp.com

26 Old Elm Street P.O. Box 5431 Salisbury, MA 01952-5431 MADE IN THEUSA

A buffer tank is a cost effective solution to prevent short cycling in various boiler applications, while also serving as a hydraulic separator, ensuring that the heating system flow and boiler flow do not affect one another. Both of these issues if left unchecked can lead to excessive boiler cycling, reduced efficiencies, and premature equipment failure.Made with heavy guage steel on site in Massachusetts, the Vaughn D4B is designed to provide years of reliable service.

What is a Buffer Tank?

Tank Capacity

Vaughn Buffer Tanks (Model D4B)

Buffer Tank Capacity = Run Time x (Boiler/System Minimum Input - Minimum System Load)

E.F.

System Return Water Temp (°F)

Calculate system ∆T (temp rise) by subtracting E from D in °F)

*Minimum boiler runtime (Industry suggestion is a 10 minutes at a minimum)

10 (20,000 - 10,000) 20 x 500

(System supply temp-system return temp) X 500

A x (B-C)F x 500

Example:} Tank Capacity =

= Model S 10 D4B