Measuring and monitoring 01 VAMP 96 and VAMP 260 Measuring and monitoring units CUSTOMER BENEFITS Intelligent measuring and monitoring units The VAMP meters come with an extensive selection of pre-configured data screens and measurements that you can use or customize to fit your metering requirements. Demand and Power Factor Control Avoid penalties with automated load shedding, scheduling, peak shaving or capacitor bank control. Equipment Monitoring and Control Improve process yields and extend equipment life. Extensive analog and digital I/O enables system monitoring and control. Power quality and Disturbance Analysis Capturing abnormal disturbances in power quality like harmonics, voltage interruptions, voltage sags/swells and unbalancing. Preventative Maintenance Set up alarms to warn of pending problems in advance. Extensive communication and SCADA connectivity IEC 61850, IEC 60870-5-101, IEC 60870-5-103, Modbus TCP, Profibus DP, DNP3.0, DNP TCP, SPA, MBus (VAMP 96). VAMP 96 and VAMP 260 metering devices are designed for remote or stand- alone monitoring of industrial and utility applications where energy consumption and billing shall be monitored by cost centers or individual feeder. Demand and power factor control, equipment monitoring, alarms for preventive maintenance and disturbance capturing are standard features in VAMP 96 and VAMP 260. As a member of VAMP protection relay family these meters come with an extensive communication capabilities.

Upload: others

Post on 01-Mar-2022

19 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring 01

VAMP 96 and VAMP 260 Measuring and monitoring units

CUSTOMER BENEFITS

• �Intelligent�measuring�and�monitoring�unitsThe VAMP meters come with an extensive selection of pre-configured data screens and measurements that you can use or customize to fit your metering requirements.

• �Demand�and�Power�Factor�ControlAvoid penalties with automated load shedding, scheduling, peak shaving or capacitor bank control.

• �Equipment�Monitoring�and�ControlImprove process yields and extend equipment life. Extensive analog and digital I/O enables system monitoring and control.

• �Power�quality�and�Disturbance�AnalysisCapturing abnormal disturbances in power quality like harmonics, voltage interruptions, voltage sags/swells and unbalancing.

• �Preventative�MaintenanceSet up alarms to warn of pending problems in advance.

• �Extensive�communication�and�SCADA�connectivityIEC 61850, IEC 60870-5-101, IEC 60870-5-103, Modbus TCP, Profibus DP, DNP3.0, DNP TCP, SPA, MBus (VAMP 96).

VAMP 96 and VAMP 260 metering devices are designed for remote or stand- alone monitoring of industrial and utility applications where energy consumption and billing shall be monitored by cost centers or individual feeder. Demand and power factor control, equipment monitoring, alarms for preventive maintenance and disturbance capturing are standard features in VAMP 96 and VAMP 260.

As a member of VAMP protection relay family these meters come with an extensive communication capabilities.

Page 2: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 02

VAMP 96 VAMP 260Operational segment Industrial and

utility substations Industrial and

utility substations

Application Power, energy, power quality metering,

event handling andI/O unit for SCADA and

process automation

Power, energy, power quality metering,

event handling,control, alarming,

temperature monitoring and

I/O unit for SCADA andprocess automation

CT and VT input connection

Metering core Metering or protection core

Auxiliary supply range 100 – 240 V ac100 – 330 V dc

or20 – 67 V dc

18 – 36 V dcor

40 – 265 V dc / ac

Number of digital inputs 3 6

Number of RTD inputs - Optionally 4 - 16

Number of heavy trip contacts - 2

Number of alarm contacts - 3 +1

Number of mA outputs - 4

Number of solid state outputs 1 pc NO

A RIGHT PRODUCT FOR EVERY APPLICATION

Product overviewVAMP 96 MEASURING AND MONITORING UNIT

The VAMP 96 is a modern basic multimeter used as a stand alone meter in industrial low and medium voltage power distribution distribution panels. This meter can be connected to SCADA or energy management system in order to provide required measurements, alarms, condition data, events to the opera-tor using various communication protocols. VAMP 96 shall be connected to measurement core of the current and voltage transformers Typical application of VAMP 96 is to measure energy by production cost centers and to show energy savings.

VAMP 260 POWER MONITORING UNIT

The VAMP 260 is designed for a heavy duty industrial applications where the environmental and disturbance conditions are demanding. This power monitor-ing unit can be connected to the protection cores of the current and voltage transformers as the design of the unit is equal to the requirements used in protection relays. Having six digital inputs, two circuit breaker controlling, four alarming duty contacts and four analogue ( mA ) outputs this unit is unique in the market.

Quick selection table

A VAMP 260 is a unique high accurate meter as it can be connected to either protection or measurement core of the current transformers.

VAMP 96 is a basic multimeter used either stand-alone or part of monitoring / SCADA system

Page 3: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260

VAMP 96 VAMP 260Operational segment Industrial and

utility substations Industrial and

utility substations

Application Power, energy, power quality metering,

event handling andI/O unit for SCADA and

process automation

Power, energy, power quality metering,

event handling,control, alarming,

temperature monitoring and

I/O unit for SCADA andprocess automation

CT and VT input connection

Metering core Metering or protection core

Auxiliary supply range 100 – 240 V ac100 – 330 V dc

or20 – 67 V dc

18 – 36 V dcor

40 – 265 V dc / ac

Number of digital inputs 3 6

Number of RTD inputs - Optionally 4 - 16

Number of heavy trip contacts - 2

Number of alarm contacts - 3 +1

Number of mA outputs - 4

Number of solid state outputs 1 pc NO

03

Communication

As VAMP 96 and VAMP 260 are members of VAMP protection relay family the meters benefit of the communication protocols widely used in other VAMP devices. The metering and control devices are often interfaced with Profibus DP, MODBUS TCP, Modbus RTU or SPA communication in industrial applications. Utilities request IEC 61850 , IEC 60870-5-101, IEC 60870-5-103, DNP 3.0 and SPA protocols.

In addition to this, the VAMP 96 has a MBus protocol in order to support connectivity with the Automatic Meter Management (AMM) systems.

VAMPSET setting and configuration tool

VARIOUS COMMUNICATION ALTERNATIVES TO OUR DEMAND

VAMPSET is a user-friendly, free-of-charge relay management software for setting parameters and configuring VAMP relays. Via the VAMPSET software, relay parameters, configurations and recorded data can be exchanged between PC and VAMP relays. Supporting the COMTRADE format, VAMPSET also incorporates tools for analysing relay events, waveforms and trends from data recorded by the relays, e.g. during a network fault situation.

Using a standard serial cable the PC running VAMPSET connects to the front port of the VAMP relays. The VAMPSET software also supports TCP/IP communication via an optional port. Featuring true multi-language support the software runs on Windows 7 / Vista / XP / 2000 / NT and Windows 98 / 95 without any need for configuration of the PC.

VAMP relays support standard COMTRADE type disturbance recording files which can be uploaded/downloaded for evaluation of any network event recorded.

The phase sequences for currents and voltages can be read on-line from the clear and explicit phasor diagram screen for easy commissioning of the relay .

Page 4: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 04

Functionality t

VAM

P 96

VAM

P 26

0

Symbol Function

Mea

sure

men

t and

mon

itorin

g fu

nctio

ns

IL1,IL2, IL3 Current, 10...30 min demandI1 Positive sequence currentI2 Negative sequence currentILav Average demand current, min, maxIo Neutral currentU12rms,U23rms,U31rms Phase to phase RMS voltage, min, maxUL1,UL2,UL3 Phase to ground voltageUL1rms,UL2rms,UL3rms Phase to ground RMS voltage, min, maxPhasors Phasor diagram of IL1, IL2, IL3, UL1, UL2, UL3, U12, U23, U31, Uo, IoU1 Positive sequence voltageU2 Negative sequence voltageU2/U1 Relative voltage unbalanceUo Residual voltageP, Pda, PL1, PL2, PL3 Active fundamental power, 10...30min demand, per phasePrms Active RMS power, 10...30min demandPrms Active RMS power, total, min, max, 10...30min demandQ, Qda, QL1, QL2, QL3 Reactive fundamental power, 15 min demand, per phaseQrms Reactive RMS power, 10...30min demandQrms Reactive RMS power, total, min, max, 10...30min demandS, Sda, SL1, SL2, SL3 Apparent fundamental power, 10...30min demand, per phaseSrms Apparent RMS power, total, min, max, 15 min demandPF, PFda, PFL1, PFL2, PFL3 Power factor, per phase

PQ-diagramCos Cosine phiiTan Tan phiiF, fda System frequency, 10...30 min demandE+, E- Active energy, imported / exportedEq+, Eq- Reactive energy, imported / exported

Energy doseNumber of energy pulse outputs 1 4

Pow

er q

ualit

yLo

ggin

g, m

athe

mat

ical

func

tions

THD of IL1,IL2,IL3 Total harmonic distortion of phase currentsH of IL1,IL2,IL3 Harmonics of phase currents up to 15thTHD of U Total harmonic distortion of phase to phase or phase to ground voltagesH of U Harmonics of phase to phase or phase to ground voltages up to 15th

Sag and swellVoltage interruptions

Rh Running hour counterAlarm channels 8 8

>, < ComparisonUser’s logic AND, AND+OR, CT, INVAND, INVOR, OR, OR+AND, RS, RS_D, XOR, delays

Number of day / week timers 4 4

Com

mun

icat

ion

EC 60870-5-101IEC 60870-5-103IEC 61850 Modbus RTU / TCPProfibus DPSPADNP 3.0 / DNP TCP Modbus RTU slave

Har

dwar

e

Number of phase current CT inputs, protection core 3Number of phase current CT inputs, measurement core 3Number of residual current CT inputs, measurement coreNumber of voltage inputs 3 3Number of digital inputs 3 6Number of heavy duty trip outputs 2Number of alarm outputs 1 3+1Number of mA outputs 4Number of RTD inputsNumber of optional RTD inputs 4-16

Page 5: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 05

Connection diagrams

VAMP 260 VAMP 260

X1

1

23

45

6

X111

1213

1415

16

X2

12

34

56

789

AO1

AO2

AO3

AO4

L1

L2

L3

P2

P1

VAMP 260

VAMP 260 is connected to line voltages in a 400 V network

VAMP 260 is connected to phase voltages in a 400 V network

VAMP 260 VAMP 260

X1

1

23

45

6

X111

1213

1415

16

X2

12

34

56

789

AO1

AO2

AO3

AO4

L1

L2

L3

P2

P1

VAMP 260

VAMP 260 is connected to line voltages in a 400 V network

VAMP 260 is connected to phase voltages in a 400 V network

Energypulse outputDI

X2B:8 +12V

X2B:4 DI2

X2B:5 DI3

X2B:3 DI1

IL3X1:5

X1:6

IL1

IL2

X1:1

X1:2

X1:3

X1:4

X3

X4

Local

Remote

X2A:7

X2A:8

Relay out

V A Hz

VA W var

P.F cosfii tanfii

Wh varh THD

U&I harmonics

L1 L2 L3N

10/0.4kV

10kV

~

X2A:5

X2A:3

X2A:4

X2A:2 N

U1

U2

U3

X2B:1Uaux

X2B:2

R

VAMP96_LVCON_2

Generaldigital inputs

Measurement functions

VAMP 96

VAMP 260CONNECTION DIAGRAM

VAMP 96 CONNECTION DIAGRAM

Page 6: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 06

OK

Power

Error

Com

Alarm

TripABC

VAMP 255

1.0-100.04 - 0.39

1937.60

1395.47

24

5

PANEL MOUNTING VAMP 200 SERIES

3

SEMI-FLUSH VAMP 200 SERIES

41

1.0 -100.04 - 0.39

271.06

1817.13

281.10

B A

210.83

>

2a2b

1375.39

Panel mountingSemi-flush

mmin

2088.19

1556.10

1907.48

200.79

Raising frame B Fixing bracket

VYX076 40 mm /1.57″ 169 mm/ 6.65″ Standard for 200 series

VYX077 60 mm /2.36″ 149 mm/ 5.87″ Standard for 200 series

VYX233 100 mm / 3.94″ 109 mm/4.29″ 2 x VYX199 needed

A

OK

Power

Error

Com

Alarm

TripABC

OK

Power

Error

Com

Alarm

TripABC

OKOK

VAMP 255

Power

ErrorCom

Alarm

TripABC

VAMP 255

VAMP 255

Dimensional drawings

VAMP 260 PANEL MOUNTING

Page 7: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 07

1

ALARM POWER

3 4mmin

1

107,04.21

96,03.78

96,03.78

90,03.54

150,55.93

123,54.86

18,00.71

9,00.35

96,03.78

1 2 3 4 5

X36 7 8 9

X2A1 2 3 4 5 6 7 8 9

1 2 3 4 5 6X1

X2B1 2 3 4 5 6 7 8 9

VY091

90,03.54

107,04.21

96,03.78

88,03.46

mmin

2

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9X2A

1 2 3 4 5 6X1

X36 7 8 9

1 2 3 4 5

3b

3a

1.0-10mm0.04-0.39

151,36.0

91,03.58

89,03.50

ALARM POWER

VAMP 96Measuring and Monitoring Unit

EC

ø4,50.18

> 200.79

5

171,36.74

151,36.0

60,02.36

1234.84

VY2

80A

EC

ALARM POWER

VY2

80A

EC

C E

VY10C

ALARM POWER

EC

ALARM POWER

VY2

80A

EC

ALARM POWER

VY2

80A

EC

ALARM POWER

VY2

80A

EC

mmin

1,0-10mm0.04-0.39

89,03.50

91,03,58

21

3 4

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9X2A

1 2 3 4 5 6X1

X36 7 8 9

1 2 3 4 54a

4a

4b

4b

4b

> 20

0.79

5

mmin

107,04.21

96,03.78

96,03.78

90,03.54

150,55.93

123,54.8618,0

0.71

9,00.35

96,03.78

1 2 3 4 5

X36 7 8 9

X2A1 2 3 4 5 6 7 8 9

1 2 3 4 5 6X1

X2B1 2 3 4 5 6 7 8 9

VY091

90,03.54

107,04.21

96,03.78

88,03.46

mmin

ALARM POWER

VY2

80A

EC

ALARM POWERALARM POWER

VY2

80A

EC

ALARM POWER

VY2

80A

EC

ALARM POWER

VY2

80A

EC

ALARM POWER

VY2

80A

EC

C E

VY10C

ALARM POWER

EC

1

VAMP 96 PANEL MOUNTING

SEMI-FLUSH MOUNTING

Page 8: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 08

Typical applications

VAMP 260 power monitoring unit

applied for monitoring of power

and energy at industrial power

distribution. Energy pulses drive

Energy Management System

whereas the alarms and load

information goes via the serial

communication to the Control

Center. The mA outputs control

analogue meters of the switchgear.

VAMP 260

VAMP 96 is a basic metering and control device used for measuring power and

energy of production cost centers in industrial applications. The same meter can

be used by the utilities for detecting consumed energy per feeder.

VAMP 96

Serial communicationEnergy pulses

EnergyManagement System

RemoteControl Center

VAMP 260

VAMP 260

U

I Vamp96

U

I

110/10kV

10kV

Vamp96

Modbus, Profibus DP, TCP/IP

VAMP 96 VAMP 96

EnergyManagement System

3

3

3

3

10/0.4kV 10/0.4kV

Page 9: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 9

Order Codes

V 260 -

Nominal current [A] 1 = 1 A 5 = 5 ANominal Voltage [V] C = 100.. 240 VFrequency [Hz]7 = Standard relay Supply voltage [V] A = 40.. 265 Vac/dc B = 18.. 36 VdcOptional hardware (communication port 1) A = None B = Plastic/Plastic serial fibre interfaceC = Profibus interface D = RS 485 interface (4-wire)E = Glass/Glass serial fibre interfaceF = Rx Plastic/Tx Glass serial fibre interface G = Rx Glass/Tx Plastic serial fibre interfaceH = RJ-45 10Mbps ethernet interface M = RJ-45 10Mbps ethernet inc. IEC 61850O = LC 100 Mbps ethernet fibre interface inc. IEC 61850P = RJ-45 100Mbps ethernet interface inc. IEC 61850R = 2 x LC 100 Mbps ethernet fibre interface inc. IEC 61850S = 2 x RJ-45 100 Mbps ethernet interface inc. IEC 61850Analog Outputs & firmware E = None, standard firmwareF = 4 pcs, standard firmware

V 96 1 C 7 A

Accessories

V

AMP

96

VAM

P 26

0

Order code Description Note

VEA 3 CGi External Ethernet Interface Module

VPA 3 CG Profibus Interface Module

VSE001PP Fiber optic Interface Module

VSE002 RS485 Interface Module

VSE003 RS485 Interface Module, Ext I/O interface

VSE004 RS485 Interface Module, Ext I/O interface

VSE009 External DeviceNet interface module

VIO 12 AB RTD Module, 12pcs RTD inputs, RS 485 Communication (24-230 Vac/dc)

VIO 12 AC RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (24 Vdc)

VIO 12 AD RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (48-230 Vac/dc)

VX003-3 RS232 programming cable (Vampset, VEA 3CGi) Cable length 3 m

VX028-3 Interface cable to VPA 3 CG (Profibus module) Cable length 3 m

VX032-3 Back panel programming cable Cable length 3 m

VX030-3 Interface cable to VEA 3 CGi (Ethernet module) Cable length 3 m

VX004-M3 TTL/RS232 converter cable (PLC, VEA 3CGi) Cable length 3 m

VX007-F3 TTL/RS232 converter cable (VPA 3CG) Cable length 3 m

VAM 16D External LED module Disables rear local communication

VYX076 Raising Frame for 200-serie Height 40 mm

VYX077 Raising Frame for 200-serie Height 60 mm

VYX233 Raising Frame for 200-serie Height 100 mm

V200WAF V200 wall assembly frame

VYX420 Raising frame for Vamp 96 and Wimo6CP10

VAM

P 26

0

VAMP 260VAMP 96

Nominal current [A] 1 = 1 A / 5 ANominal Voltage [V] C = 100.. 240 VFrequency [Hz]7 = 50/60 Hz Supply voltage [V] A = 100.. 240 Vac/dc B = 18 .. 75 VdcG = 9 .. 36 VdcOptional hardware A = None O = LC 100 Mbps ethernet fiber inter- face inc. IEC 61850 and M-busP = RJ-45 100 Mbps ethernet interface inc. IEC 61850 and M-busOptional hardware A = Version 6 firmware * B = Standard firmware

* Only optional hardware, A available

Page 10: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 10

Technical data, tests and environmental conditions

Measuring circuitry VAMP 96 VAMP 260

Rated current In 1 A or 5 A 1 A or 5 A

- Current measuring range 1 x In 0 - 5 x In

- Thermal withstand 1,2 x In (continuously) 4 x In (continuously)20 x In (for 10 s)100 x In (for 1 s)

- Burden < 0.1 VA (In = 1 A)< 0.2 VA (In = 5 A)

< 0.1 VA (In = 1 A)< 0.2 VA (In = 5 A)

Rated voltage Un 0 – 264 V 50 - 240 V (configurable)

- Voltage measuring range 90 – 264 V 0 – 265 V

- Continuous voltage withstand 264 V 275 V

- Burden < 0.5V A < 0.5V A

Rated frequency fn 45 – 65 Hz 45 – 65 Hz

- Frequency measuring range 16 – 75 Hz 16 – 75 Hz

Terminal Block:- Solid or stranded wire

Max. wire dimension: 2,5 mm2 (13-14 AWG) Max. wire dimension: 4 mm2 (10-12 AWG)

Auxiliary voltage

Rated voltage UauxType A (standard) Type B (option) Type A (standard) Type B (option)

100 – 240 V ac/dc24 V dc100 - 330 V dc

20 – 67 V dc110/120/220/240 V ac/dc

40 - 265 V ac/dc 24 V dc48/60/110/125/220 V dc

18 - 36 V dc 100 - 330 V dc

Power consumption 5 W (normal conditions) < 7 W (normal conditions)< 15 W (output relays activated)

Max. permitted interruption time < 50 ms (110 V dc)

Terminal Block:- Phoenix MVSTBW or equivalent Max. wire dimension: 2.5 mm2 (13-14 AWG) Max. wire dimension: 2.5 mm2 (13-14 AWG)

Digital inputs

Number of inputs 3 6

Operation time 0.00 – 60.00 s (step 0.01 s) 0.00 – 60.00 s (step 0.01 s)

Polarity NO (normal open) or NC (normal closed) NO (normal open) or NC (normal closed)

Inaccuracy:- Operate time +/- 1 % +/- 1 %

Internal operating voltage 12 V dc 48 V dc

Current drain when active (max.) Approx. 5mA Approx. 20 mA

Current drain, average value < 1 mA

Terminal block:- Phoenix MVSTBW or equivalent Max. wire dimension: 2.5 mm2 (13-14 AWG) Max. wire dimension: 2.5 mm2 (13-14 AWG)

Trip contacts

Number of contacts - 2 making contacts

Rated voltage - 250 V ac/dc

Continuous carry - 5 A

Max. making current - 15 A

Breaking capacity, AC - 2 000 VA

Breaking capacity, DC (L/R=40ms) - 50 W

Contact material - AgNi 90/10

Terminal Block:- Phoenix MVSTBW or equivalent

-Max. wire dimension: 2.5 mm2 (13-14 AWG)

Accuracy

Current +/- 0.4 % of value when I > 0.5 x In +/- 0.3 % of In

Voltage +/- 0.5 % of value +/- 0.5 %

Frequency: +/- 10 mHz +/- 10 mHz

Active power +/- 1 % of value +/- 1 % of value

Reactive power +/- 1 % of value +/- 1 % of value

Active energy +/- 1 % of value +/- 1 % of value

Reactive energy +/- 1 % of value +/- 1 % of value

Page 11: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 11

Alarm contacts VAMP 96 VAMP 260Number of contacts 1 normally open

1 change-over contact (IF relay)3 change-over contacts (relays A1, A2 and A3)x

Rated voltage 48 V ac/dc 250 V ac/dc

Max. make current 120 mA 15 A

Continuous carry 3 A 5 A

Breaking capacity, AC - 2 000 VA

Contact material - AgNi 0.15 goldplated

Terminal Block:- Phoenix MVSTBW or equivalent

Max. wire dimension: 2.5 mm2 (13-14 AWG) Max. wire dimension: 2.5 mm2 (13-14 AWG)

Local serial communication portNumber of ports 1 on front and 1 shared with remote on rear panel 1 on front and 1 on rear panel

Electrical connection RS 232 RS 232

Data transfer rate 9 600 - 38 400 kb/s 9 600 - 38 400 kb/s

Remote control connectionNumber of ports 1 shared with local port on rear panel 1 on rear panel

Electrical connection RS 232 (standard)TTL RS 485 (with external module)Plastic fibre connection (with ext. module)

TTL (standard)RS 485 (option)RS 232 (option)Plastic fibre connection (option)

Data transfer rate 9 600 kb/s 9 600 kb/s

Protocols ModBus‚ RTU masterModBus / TCPSpaBus, slaveIEC 61850IEC 60870-5-101IEC 60870-5-103Profibus DP (option)MBusDNP or Ethernet

ModBus‚ RTU masterModBus / TCPSpaBus, slaveIEC 61850IEC 60870-5-101IEC 60870-5-103Profibus DP (option)DNP or Ethernet

Analogue outputsNumber of Ports - 4 (Note: common +pole)

Electrical connection: - Current output

- Range - 0 – 20 mA (min & max configurable)

- Load - <800 W

- Accuracy - <±20mA

Isolation te9st voltage - 500 Vdc

Test voltagesInsulation test voltage(IEC 60255-5)

2 kV, 50 Hz, 1 min 2 kV, 50 Hz, 1 min

Surge voltage (IEC 60255-5) 5 kV, 1.2/50 ms, 0.5 J 5 kV, 1.2/50 ms, 0.5 J

Environmental conditionsOperating temperature -25 to +50 oC -10 to +55 oC

Operating temperature (display) 0 to +50 oC

Transport and storage temperature -10 to +60 oC -40 to +70 oC

Relative humidity < 75 % (1 year, average value) < 75% (1 year, average value)

< 90 % (30 days per year, no condensation permitted)

< 90% (30 days per year, no condensation permitted)

CasingDegree of protection (IEC 60529) IP20 IP20 / Flush mounted IP54

Dimensions (W x H x D) 96 x 96 x 151 mm 208 x 155 x 236 mm

Material Polyphenylene Oxide 1 mm steel plate

Weight 0.6 kg 4.2 kg

Color code RAL 7032 (Casing) / RAL 7035 (Back plate)

PackageDimensions (W x H x D) 180 x 100 x 101 mm 215 x 160 x 275 mm

Weight (relay, package and manual)

0.7 kg 5.2 kg

Page 12: VAMP 96 and VAMP 260 - Welcome to Schneider Electric Vamp …

Measuring and monitoring VAMP 96, VAMP 260 12

DEVICE TRACK RECORD

• Schneider Electric’s VAMP Range specialises in protection protection relays, arc flash protection and measuring and monitoring units for power systems.

• VAMP’s medium-voltage and sub-transmission protection relays are used in numerous applications, from overhead line feeders and substations to power plants and industrial power system. Their unique integrated arc flash fault protection functionality enhances the safety of both people and property and has made VAMP a leading manufacturer in arc flash protection worldwide. All VAMP products meet the latest international standards and regulations.

• Our success is based on competitive standard products, constant development by our designers possessing experience from three protection relay generations, our long-term partnerships, flexibility and 24 h care of the customers.

01-2013 © 2

013

Sch

neid

er E

lect

ric In

dust

ries

SA

S -

All

right

s re

serv

ed

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Design: Schneider Electric Industries SAS - WILMAPhotos: Schneider Electric Industries SAS Printed:

NRJED112388EN

This document has been printed on recycled paper.

Schneider Electric Industries SAS

35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France)Tel.: +33 (0) 1 41 29 70 00RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com