VAMP 50, VAMP 51, VAMP 52, VAMP 55Protection relays with native

IEC 61850 and arc flash protection

Page 2: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

2

VAMP 50 series protection relays

Robust and flexible hardware • Modular design with versatile hardware expansion for communication, arc protection and DI/DO extension

• Designed for demanding industrial conditions

• Withdrawable and slim fit models available

Common technology to gain volume benefits• Powerful CPU supporting native IEC 61850

• Utilisation of other Vamp platform accessories

• Improved safety with economical and fast arc flash protection (optional)

High user friendliness and functionality• Common firmware platform with VAMP 200 Series

• Active functions visible for the operator only

• Standard USB connection (type B) for the setting tool

Modern Human Machine Interface (HMI)• Large and clear LCD display

• Single line diagram mimic with control, indication and live measurements

• Programmable function keys and LEDs

• Standard USB front port (Type B)

The VAMP 50 series protection relay family is based on proven technology concepts developed in close co-operation with customers. User-friendliness describe VAMP products, the feature which receives a good grade in our customer satisfaction reports day after day.

The VAMP 50 over current and earth fault protection relay has been developed to cover basic protection needs for OEMs, utilities and industrial applications. Thanks to its cost-effective and flexible design, the VAMP 50 will provide an excellent alternative for vari-ous protection applications.

The VAMP 51 offers enhanced control functionality such as auto-reclose, VAMP 52 combines additional protection functions for feeders, motors, and with directional earth fault requirements.

Designed to be extremely fast, the exchange of arc flash fault data between a sensor and arc module can result in trip activation in less then 14 ms

VAMP 50 family – low and mid range relay series with IEC 61850

Page 3: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

User-friendliness has always been a feature of Vamp products, and the VAMP 50 series is no exception. A great deal of effort has gone into the design of the opera-tional aspects of the new products.

The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new level. Unicode support allows the menu view and setting tool translation to various international languages including for example Russian and Chinese. The informative human machine interface provides all of the required information to the user with support of customized legend texts.

Ease of use

The optional DI/DO, arc con-nection and communication modules can be added to the basic relay later on in order to extend the functionality of the relay during it’s life time.

Two optional module slots

• Extends the functionality of the relay

• Remote port, RS485, RS232 & Ethernet (RJ-45 or fiber)

• Arc, DI/DO

The template for user legend texts is a part of the product documentation. The texts printed on the transparency film allow customization of the relay.

VAMP 50 family HMI interface

3

128 x 64 LCD dot matrix display

• Single line diagram and freely assignable analogue values

• Unicode language support

Programmable LEDs

• User configurable legend texts

• 12 LEDs, 2 fixed (power, error) and 8 freely programmable (2 for push buttons)

Local port

• USB interface

Navigation push buttons

Function buttons with

• User configurable legend texts

• CB control

• Protection setting group selection

• Freely programmable

Page 4: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

4

VAMP 50 series protection relays

Expanded usability

The VAMP 50 protection relay concept has been extended with a number of features that make installation and testing of the relays even more efficient and user-friendly.

VAMP 50W – a withdrawable unit with ring-lug connectors

One of the latest VAMP 50 features is the withdrawable VAMP 50W relay version that can safely be removed from its frame for testing. Releasing and unlocking of the fixing handle automatically short-circuits the current trans-formers and isolates the tripping contacts, thus making installation, testing, and maintenance of the protection relay more flexible.

The withdrawable technology is optional for all VAMP 50 series current-based protection relays. It also allows the use of ring-lug connectors for relay inputs.

The withdrawable technology is optional for the VAMP 50 series of current measuring relays.

The rin-lug connectors are supported with VAMP 50W design

VAMP 50S – compact design for limited space

The VAMP 50 series is now also available as the VAMP 50S, which includes a more compact casing than the basic design. The VAMP 50S is an ideal choice for ring main unit switchgears and other applications where a flat relay is required.

In the VAMP 50S, the same protection, measurement and control functions and communication interfaces are sup-ported as in the basic 50 series of relays.

Vamp 50 default model

Vamp 50S

The VAMP 50S is an ideal choice for applications where a flat relay is required

Page 5: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

The IEC 61850 protocol can be used to read or write static data or to receive events sent spontaneously from the relay. In addition, the interface allows peer-to-peer communication between the relays, called GOOSE com-munication. The IEC 61850 interface is configured with familiar, user-friendly VAMPSET software. The IEC 61850 datamodel, data-sets, report control blocks and the Goose communication are configured according to the require-ments of the system configuration. VAMPSET is also used to produce ICD files, which may be needed for the substa-tion RTU configuration.

The VAMP 50 series contains native implementation, which means that the IEC 61850 functionality is embed-ded in the software.

Native IEC 61850

VAMP 50 Communication protocols

IEC 60870-5-101

IEC 60870-5-103

Modbus TCP

Modbus RTU

Profibus DP

DNP 3.0

SPA-bus communication

IEC 61850

DeviceNet

Human-Machine-Communication, display

Human-Machine-Communication, PC

Vamp is a communication expert with a wide experience in interfacing with different system integrators’ and SCADA suppliers’ RTUs, PLCs, gateways etc. using many different protocols. Flexible adaptation of the communication proto-cols together with powerful and easy to use software tools are the key of successful integration. VAMP 50 series and the VAMPSET tool provide access to practically any power system information you may need.

Communication

5

Page 6: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

6

VAMP 50 series protection relays

VAMPSET is a user-friendly, free-of-charge relay management software for setting, parameterising and con figuring of VAMP relays. Via the VAMPSET software, relay parameters, configurations and recorded relay data can be uploaded/downloaded between the operator’s PC and the VAMP relays. Supporting the COMTRADE format VAMPSET also incorporates tools for analyzing relay events, waveforms and trends from disturbance recordings caprured by the relays, e.g. during a network fault situation.

A standard USB cable connects a PC running the VAMPSET software to the front port of the VAMP 50 series relays. The VAMPSET software also supports TCP/IP communication via an optional communica-tion port. Featuring true multi-language support the software runs on Windows 7/Vista/XP/2000/NT and Windows 98/95 without any need for configuration of the PC. The VAMPSET software is future-proof, supporting future updates and new VAMP products.

VAMPSET Setting and Configuration Tool

The USB connection is much faster than serial communica-tion. Standard USB communica-tion cable can be used.

As a regular feature of the VAMP relays standard COMTRADE type disturbance recording files can be uploaded for subsequent evaluation of any network event recorded.

The phase sequences for currents and voltages can be read on-line from the clear and explicit phasor diagram screen for easy commissioning of the relay

Page 7: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

Arc flash protection

Traditional protection relay systems do not provide fast enough protection in an arc-fault situations.

Whether the time-grading or blocking based protec-tion coordination principle is used, the traditional protection systems may not provide fast enough pro-tection of substation faults. Further, high-impedance type of earth-faults may cause prolonged operation times of earth-fault relays leading to the significant release of the arcing energy. These facts pose a con-siderable risk to human beings and economical as-sets. By applying a modern, high-speed arc protection system the damage may be considerably reduced. Such an arc protection system is an optional feature incorporatable in all current measuring VAMP relays.

The VAMP relays measure the fault current. If the arc protection option is selected the relays also monitor light via arc sensor channels monitoring the whole switchgear. Should an arcing fault occur in the switchgear the arc protection system provides an extremely fast tripping for the circuit breaker. The fault will be prevented from spreading and quickly isolated, which may save human lives and valuable economical assets.

Arc flash protection, incorporating continuous self supervision for the sensors, is optional in VAMP 50 series current measuring relays.

Arc flash protection integrated in VAMP relays enables substation level, ultra-fast arc protection. The system uses protection relay hardware and separate arc sensors. Any possible arc flash fault in the cable compart-ment is selectively cleared by the feeder protection relay where as the fault in the circuit breaker or bus bar compartment is tripped by the incom-ing circuit breaker. The exact location of the arc flash will be detected by the arc flash and relay protection system.

Point sensor VA1DA-x 1) (surface)

Point sensor VA1EH-x 1) (pipe)

Arc point sensors

1) x represents cable length (m)

Cable

CB

BB

Cable

L> (CB, BB)

L> (CB, BB)

CB CB

Cable

7

Page 8: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

8

VAMP 50 series protection relays

The VAMP 50 series offers a complete set of measurement functions to replace the conventional metering functions of switchgear and and controlgear installations. The measure-ment functions cover phase, line and residual currents, current unbalance, system frequency and harmonics from phase currents. Condition monitoring continuously monitors trip circuits, breaker wear and current transformers.

Measurements and condition monitoring

Mo

tor

pro

tect

ion

Spe

cial

app

licat

ionsFeeder protection

VA

MP

50

VA

MP

51

VA

MP

52

VA

MP

52

VA

MP

55

Type of measurement IEC Symbol Protection function/measurement

Primary current 3I Three-phase current n n n n

l0 Zero sequence current n n n n

I2 Current unbalance n n n n

IL Average and maximum demand current n n n n

Primary voltage U One/ three-phase and line voltage n1 n1 n3

U0 Zero sequence voltage n n n

U2 / U1 Relative voltage unbalance n

Frequency f System frequency n n n n n

Power P, Q, S Active, reactive, apparent power )1 n n

Energy E+, E-, Eq+, Eq- Active and reactive energy )1 n n

Harmonics I 2nd to 15th and THD of phase currents n n n n

Voltage sags / swells U Voltage sags / swells n

Analog mA output, 1 channel AO Any measured or calculated value, freely scalable n n n n n

Control

Digital inputs Number of digital inputs (max) 7 7 7 7 7

Output relays Number of trip relays (max) 5 5 5 5 5

Number of control relays (max) 1 1 1 1 1

Object status indication Single line diagram, 8 objects n n n n n

Local and remote control Number of controllable objects 6 6 6 6 6

Interlocking and logic Configurable n n n n n

Condition monitoring

Trip circuit TCS Trip Circuit Supervision n n n n n

TCS Trip Circuit Supervision with DI for T5 (optional) n n n n n

CT Supervision CT Supervision n n n n

VT Supervision VT Supervision/Fuse failure supervision n

CB Wear Breaker wear n n n n1) Based on single phase measurement

Input /Output options

VAMP 50 VAMP 51 VAMP 52 VAMP 55

Analog inputs 3 x I1 x Io

3 x I1 x Io

3 x I 1 x Io, 1 x U 4 x U

Digital inputs 2 (7) 2 (7) 2 (7) 2 (7)Trip relays 4 (5) 4 (5) 4 (5) 4 (5)Control relays 2 2 2 2mA output Option Option Option OptionArc protection Option Option Option -Front port USB USB USB USB

Optional rear port RS 485/RS 232/ Fibre/Ethernet

RS 485/RS 232/ Fibre/Ethernet

RS 485/RS 232/ Fibre/Ethernet

RS 485/RS 232/ Fibre/Ethernet

External RTD input module Option Option Option Option

The VAMP 50 series host various optional modules in order to up-grade the relay functionality from the basic protection unit to a more advanced protection relay.

Page 9: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

Feeder protection

Mo

tor

pro

tect

ion

Spe

cial

app

licat

ions

VA

MP

50

VA

MP

51

VA

MP

52

VA

MP

52

VA

MP

55

Type of fault IEEE Device No. IEC Symbol Protection function/measurement

Overcurrent fault 50/51 I > Three-phase non-directional overcurrent, low-set stage, definite or inverse time n n n n

50/51 l >> Three-phase non-directional overcurrent, high-set stage, definite time n n n n

50/51 l >>> Three-phase non-directional overcurrent, high-set stage, definite time n n n n

Earth-fault 50N/51N l0 >/ SEF Non-directional earth-fault, low-set stage, sensitive, definite or inverse time n n n n

50N/51N l0 >> Non-directional earth-fault, high-set stage, definite time n n n n

50N/51N l0 >>> Non-directional earth-fault,high-set stage, definite time n n n n

50N/51N l0 >>>> Non-directional earth-fault, high-set stage, definite time n n n n

67NI l0 int>Directional transient intermittent earth-fault protection n n

67N or 50N/51N l0j >/ SEF Directional or non dir. earth-fault, low-set stage, sensitive, definite or inverse time n n

67N or 50N/51N l0j >> Directional or non dir. earth-fault, high-set stage, definite or inverse time n n

59N U0> Zero sequence voltage, low-set stage n n n

59N U0>> Zero sequence voltage, high-set stage n n n

Overload 49M T> n

49F T> Three-phase thermal overload (feeders & cables) n n n

Voltage

* = number of voltage channels

59 U> One-/three-phase overvoltage, low-set stage n1 * n1 * n3 *

59 U>> One-/three-phase overvoltage, high-set stage n1 * n1 * n3 *

59 U>>> One-/three-phaseovervoltage, high-set stage n1 * n1 * n3 *

24 U / f> Volts/hertz overexcitation protection n

27 U< One-/three-phase undervoltage, low-set stage n1 * n1 * n3 *

27 U<< One-/three-phase undervoltage, high-set stage n1 * n1 * n3 *

27 U<<< One-/three-phaseundervoltage, instantaneous stage n1 * n1 * n3 *

27P U1 <, U1 << Positive sequence undervoltage n

47 U2 > Negative sequence overvoltage (pgr stage) n

Arc flash protection 50ARC/50NARCArcI> / ArcI01> /

ArcI02 > Electrical arc flash protection stage, point sensors, optional n n n n

Other functions 79 O --> I Auto-reclosure n n

68 Inrush and cold load detection n n n n

46 I2 / I1 > Current unbalance protection (in feeder mode) n n n

46 I2 > Phase unbalance protection n

47 I2 >> Phase sequence / incorrect phase sequence protection n

48 IST > Stall protection n

37 3I< Loss of load / under current protection n n

86 Latched trip n n n n n

66 N> Frequent start protection n

51F2 If2> Second harmonic O/C stage n n n n

50BF CBFP Circuit breaker failure protection n n n n n

81 f ><, f >><< Frequency protection n

81L f<, f<< Underfrequency protection n

25 df/dv Synchrocheck n

99 8 Programmable stages n n n n

DR Disturbance recorder n n n n n

User-friendliness is also a built-in feature of protection stages, where setting views are graphically displayed in the relay and VAMPSET HMI. Disabled protection stages are hidden from the menu in order to display only the necessary information. Protection stages come with two setting groups to enable automatic transfer from main setting to alternative setting. This change can be univer-

sal for the entire relay or protection function based. The relay has a large number of standard inverse curves to adopt various protection requirements. Unique protec-tion curves can be applied for protection applications where standard IEC or IEEE curves do not provide required protection selectivity.

Protection stages

9

Page 10: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

BB

CB

Cable

3I>

3I>>

3I>>>

50 / 51

T >

49F

I >f2

68

I >,0 I >>0

I >>>0

I >>>>0

50N/51N

I >2/I1

46R

50NARC

ArcI >0

CBFP

50BF

TCS

74TC

Lockout

86

ArcI>

50ARC

3 I

Io

VAMP 50

BB

CB

lCab e

3I>

3I>>

3I>>>

50 / 51

T >

49F

I >f2

68

I >2/I1

46R

50NARC

ArcI >01

TCS

74TC

Lockout

86

3 I

Io

VAMP 51

8 pgr79

O > 1

I >,0 I >02

I >>,0 I >>02

50N/51N

+

D

CBFP

50BF

ArcI>

50ARC

Typical application / VAMP 51, feeder mode with auto-reclose

10

VAMP 50 series protection relays

VAMP 50 is a basic protection relay used for LV and MV feeders in industrial and utility applications as well as for back-up protection. Limited amount of protection functions make this unit cost efficient, user friendly and simple to use. The hardware design allow easy addition of integrated optional modules like arc sensor interface, extension of DI / DO channels and various communica-tion module adapters.

In VAMP 51, the autorecloser function extends the protection application to overhead line feeder protec-tion in substation or secondary substation systems where the network is low-impedance or rigidly earthed. Programable stages enables the user to configure new protection elements and create new triggering condi-tions in the disturbance recorder.

VAMP 50 and 51 overcurrent & earth fault relays

Typical application / VAMP 50 In addition to the default model, VAMP 50 series relays are also available as a slim fit (S) and withdrawable (W) version.

Page 11: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

VAMP 255

L1

L2

L3

0

1

-

-+

+

+

IL1

IL2

IL3

I05A

1A

~

DI

Blocking andoutput matrix

Remote

Front

X1:1

X1:2

X1:3

X1:4

X1:5

X1:6

X1:7

X1:8

X1:9

X2:1

X2:2

X3:12

X3:13

T2 X3:15

X3:14

T1X3:16

X3:17

X3:11

X3:10

IF X3:18X3:19

X3:20

X3:3 DI1 -

X3:4 DI1+

X3:5 DI2 -

X3:6 DI2+

Protection functionsComm. option

I/O extension module

X6:1X6:2X6:3X6:4X6:5X6:6X6:7X6:8

mA

mA out option

T1T1

T3

T4

C 1 X3:7

X3:9

X3:8

X3:2 AO -X3:1 AO+

CBFP

50BF

3I>

3I>>

3I>>>

50 / 51

T >

49F

I >f2

68

I >,0 I >02

I >>,0 I >>02

50N/51N

TCS

74TC

ArcI>

50ARCI >2/I1

46R

50NARC

ArcI >01

Lockout

86

A rc option

or

DI / DO module

I/O extension module

X6:1X6:2X6:3 DI3X6:4 C ommX6:5 DI4X6:6 DI5X6:7 C ommX6:8 Di6

DI / DO moduleT5

DI

DI

VAMP 50 / VAMP 51

A rc option

L>

BI/OX6:1 B O+X6:2 B O-X6:3 B I+X6:4 B I-X6:5 L1+X6:6 L1-X6:7 L2+X6:8 L2-

Arc option module 1

Auto Reclose

79 8 pgr

Additional protection functions/VAMP 51

VAMP 50/VAMP 51 connection diagram

Arc module 1 has two arc sensor interfaces and con-nectivity from/to other relays via BI/O channel. The oper-atiing time for arc flash fault trip is 15 ms.

11

Page 12: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

12

VAMP 50 series protection relays

VAMP 52 is a multi-function protection relay used for LV and MV feeders in industrial or utility applications.

Extensive thermal protection functions make this relay optimal for low and medium sized asynchro-nous motors. Directional earth fault protection in association with an auto-recloser makes this relay cost effective for feeder protection applications where automatic fault clearance is needed.

This relay is flexible, user friendly and simple to use. The hardware design allows easy addition of integrated optional modules like arc sensor interface, extension of DI / DO channels and various communication module adapters.

VAMP 52 feeder and motor protection relay

Typical applications

Feeder mode with auto-reclose Motor mode

BB

CB

Cable

3I>

3I>>

3I>>>

50 / 51

T >

49F

I >f2

68

I >,0 I >>0

I >>>0

I >>>>0

50N/51N

I >2/I1

46R

8 pgr

50NARC

ArcI >0

CBFP

50BF

TCS

74TC

Lockout

86

3 I

Uo, UL or U

Io

I >0

I >>0

67N

U >0 >

U >0

59N

I >0T

67NT

+

79

O > 1

1>>>>>

U>1U1U

59 (1

1 <1U<<1U<<<

U

27 (1

1) Alternative to Uo protection

VAMP 52

ArcI>

50ARC

1) Alternative to Uo protection

3I>

3I>>

3I>>>

50 / 51

T >

49M

I >f2

68

I >,0 I >>0

I >>>0

I >>>>0

50N/51N

8 pgr

I >2

46

50NARC

ArcI >0

CBFP

50BF

TCS

74TC

Lockout

86

3 I

Uo, UL or U

Io

M

I >0

I >>0

67N

U >0 >

U >0

59N

I >0T

67NT

1>>>>>

U>1U1U

59 (1

1 <1U<<1U<<<

U

27 (1

I >>2

47

I >st

48N>

66

+

Fiber orRS485

RTD

1...12

VIO

12A_

DI

VAMP 52

BB

CB

Cable

ArcI>

50ARC

3I

37

<

Page 13: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

L1

L2

L3

0

1

-

-

U0

IL1

IL2

IL3

I05A

1A

~

DI

Blocking andoutput matrix

VAMP 52

Remote

Front

X1: 1

X1: 2

X1: 3

X1: 4

X1: 5

X1: 6

X1: 7

X1:8

X1: 9

X2: 1

X2: 2

X3:12

X3:13

T2 X3:15

X3:14

T1X3:16

X3:17

X3: 11

X3:10

IF X3:18X3:19

X3:20

X3:3 DI1 -X3:4 DI1+X3:5 DI2 -X3:6 DI2+

Comm. option

mA

mA out option

T1T1

T3

T4

C1 X3: 7

X3: 9

X3: 8

X1:10

X1: 11U /U /U

0 L 1

12

Autoreclosermatrix

Protection functions

+

+

Auto Reclose

79

I >f2

68TCS

74TC

Lockout

86

3I>

3I>>

3I>>>

50 / 51

I >2/I1

46R

3I<

37

I >>2

47

I >2

46

I >st

48

N>

66

CBFP

50BF

ArcI>

50ARC

50NARC

ArcI01>

U<

U<<

U<<<

27

U>

U>>

U>>>

59

T >

49

I >,0 I >02

I >>,0 I >>02

50N/51N

I >0

67N

I >>0

U >0

U0>>

59N

U >0

U0>>

59N

I >0T

67NT

X6: 1X6: 2X6: 3X6: 4X6: 5X6: 6X6: 7X6: 8

Arc option

or

DI / DO module

I/O extensionmodule

A rc option

L>

BI/OX6:1 B O+X6:2 B O-X6:3 B I+X6:4 B I-X6:5 L1+X6:6 L1-X6:7 L2+X6:8 L2-

X6:1X6:2X6:3 DI3X6:4 C ommX6:5 DI4X6:6 DI5X6:7 C ommX6:8 Di6

DI / DO moduleT5

DI

DI

Arc option module 1 I/O extension module

L>

RJ-45RJ-45

X6:1 L1+X6:2 L1-X6:3 L2+X6:4 L2-X6:5 L3+X6:6 L3-

Arc option module 2

X1:11 X1:10

X1:11 X1:10

VAMP 52 connection diagram

When the voltage trans-former is connected to transform the phase to ground voltage, the volt-age measuring mode shall be 1LN

Should the voltage transformer connection be phase to phase the voltage measuring mode is selected 1LL

U12

UL1

13

Page 14: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

14

VAMP 50 series protection relays

The VAMP 55 is a multi-function relay suitable for voltage and frequency protection for both utility and industrial applications and also for synchrocheck ap-plications.

The relay is equipped with 4 voltage inputs that can be configured with any of the available predefined voltage mode setups.

3LN+LLy / LNy = phase voltage and synchrocheck

3LN + Uo = Line to neutral and zero sequence voltage

VAMP 55 voltage protection relay

Typical application

The VAMP 55 relay is also available as a slim fit (S) version.

The VAMP 50 series is supplemented by VAMP 59 designed for the protection of medium voltage over-head lines and cables. Versatile firmware enables this relay to be used in applications with in-zone transform-ers as well. The relay includes back-up protection functions for basic overcurrent and earth fault func-tions with three pole auto reclosing.

The characteristics of VAMP 59 are expalained in detail in its own product brochure or at www.vamp.fi.

VAMP 59 line differential relay

BB

VT

f><f>><<

81H/81L

f<f<<

81L

df/dt

81R

∆f, ∆v

25

8 pgr

CBFP

50BF

TCS

74TC

Lockout

86

3U>

3U>>

3U>>>

59

3U<

3U<<

3U<<<

27

U1<

U1<<

27P

U2>

U2>>

47

Uo>

Uo>>

59N

VAMP 55

Cable

CB

VT

Page 15: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

VAMP 55 connection diagram

* 3LN+LLy

VAMP 55

X6:1X6:2X6:3 DI3X6:4 C ommX6:5 DI4X6:6 DI5X6:7 C ommX6:8 Di6

DI / DO moduleT5

DI

DI

I/O extension module

VAMP 55 is applied in 3LN+LLy mode. The phase voltage (line to neutral) is measured from the bus bar and the realy calcu-lates phase-to-phase and zero sequence voltage. The U4 voltage channel is used for synchrocheck in the feeder side.

15

Page 16: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

16

VAMP 50 series protection relays

Order Codes

Relay type0 = Overcurrent & earth fault relay1 = Overcurrent & earth fault relay2 = Feeder and motor protection relay5 = Voltage protection relay

Relay type = DefaultS = Slim fitW = Withdrawable modelPhase current inputs [A] 3 = 5 AEarth-fault current input [A] A = 1 A / 5 A B = 0.2 A / 1 A Supply Voltage [V] A = 40.. 265 Vac/dc B = 18 ... 36 VdcmA output option A = None B = mA outputDI nominal activation voltage 1 = 24 Vdc / 110 Vac 2 = 110 Vdc / 220Vac 3 = 220 VdcOptional I/O extension modules A = None B = Digital I/O; 4 x DI, 1 x DO C = Arc Protection; 2xSensor, BIO

Optional communication module 1A = None D = Plastic/Plastic serial fibre interfaceE = Glass/Glass serial fibre interfaceF = Rx Plastic/Tx Glass serial fibre interfaceG = Rx Glass/Tx Plastic serial fibre interfaceK = RJ-45 10Mbps ethernet interface inc. IEC 61850 P = Profibus interfaceR = 2 x ST 100Mbps ethernet fibre interface

inc. IEC 61850 !! S = 2 x RJ-45 100Mbps ethernet interface inc. IEC 61850T = RS 485 interface (4-wire) + RJ-45 10Mbs ethernet interface inc. IEC 61850 *U = RS 485 interface (4-wire) + LC 100Mbs ethernet fibre interface inc. IEC 61850 *V = RS 232 interface + RJ-45 10Mbs ethernet interface inc. IEC 61850 *X = RS 232 interface + LC 100Mbs ethernet fibre interface inc. IEC 61850 *B = RS 485 interface (4-wire) with option for module 2 L = RS232 interface with option for module 2Optional communication module 2 A = NoneB = IRIG-B time syncronisation input **C = RTD interface (Glass fibre) **E = RJ-45 10 Mbps ethernet interface inc. IEC 61850 **G = LC 100 Mbps ethernet fibre interface inc. IEC 61850 **PCP coating = Default

Relay type = DefaultS = Slim fit

Nominal voltage [V] 4 = 50...400 V (default size)X = none

Supply Voltage [V] A = 40.. 265 Vac/dc B = 18 ... 36 VdcmA output option A = None B = mA outputDI nominal activation voltage 1 = 24 Vdc / 110 Vac 2 = 110 Vdc / 220Vac 3 = 220 VdcOptional I/O extension modules A = None B = Digital I/O; 4 x DI, 1 x DO

Optional communication module 1A = None D = Plastic/Plastic serial fibre interfaceE = Glass/Glass serial fibre interfaceF = Rx Plastic/Tx Glass serial fibre interfaceG = Rx Glass/Tx Plastic serial fibre interfaceK = RJ-45 10Mbps ethernet interface inc. IEC 61850 P = Profibus interfaceR = 2 x ST 100Mbps ethernet fibre interface

inc. IEC 61850 !! S = 2 x RJ-45 100Mbps ethernet interface inc. IEC 61850

B = RS 485 interface (4-wire) with option for module 2 L = RS232 interface with option for module 2Optional communication module 2 A = NoneB = IRIG-B time syncronisation input **C = RTD interface (Glass fibre) **E = RJ-45 10 Mbps ethernet interface inc. IEC 61850 **G = LC 100 Mbps ethernet fibre interface inc. IEC 61850 **PCP coating = Default

VAMP 50, VAMP 51 or VAMP 52: VAMP 55:

Note:

* Communication modules for withdrawable model

** Option available only with communication module 1: B and L

!! Supply voltage has to be 110 Vac/dc or more. Check out our website for "DualPortEthernetInterface_AppNote_006".

Default model

Slim fit model (S)

Withdrawable model (W)

VAMP 5 -

Page 17: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

Dimensional drawings

H

I

J

VAMP 50 Cut-out panel

Default model A B C D E F H I J

Millimetres 128 171 213 185 137 80 82 139 1-10

Inches 5.04 6.73 8.39 7.28 5.39 3.15 3.23 5.47 0.04-0.4

Default model VAMP 50

Panel mounting technique

E

AC

D F

B

Order code Description NoteVX052-3 USB programming cable (Vampset) Cable length 3 mVX054-3 Interface cable to VPA 3 CG (Profibus module) for RS 232 Cable length 3 mVSE001 Fiber optic Interface ModuleVIO 12 AA RTD Module, 12pcs RTD inputs, Optical Tx Communication (24-230 Vac/dc)VIO 12 AB RTD Module, 12pcs RTD inputs, RS 485 Communication (24-230 Vac/dc)VIO 12 AC RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (24 Vdc)VIO 12 AD RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (48-230 Vac/dc)VA1DA-6 Arc sensor Cable length 6 mVA1DA-20 Arc sensor Cable length 20 mV50WAF V50 wall assembly frame

Available option-cards possible to be ordered separately:5VCM 232+ET Ethernet interface (10Mbps RJ45)5VCM 232+I6 IEC 61850 interface (10Mbps RJ45)

5VCM 485+00 RS 485 interface (4-wire)5VCM 485+FI RS 485 -and RTD fibre optic interface (Glass fibre)5VCM 485+ET RS 485 -and ethernet interface (10Mbps)5VCM 485+I6 RS 485 -and IEC 61850 interface (10Mbps)5VCM 485+IR RS 485 interface with time synchronization input (IRIG-B)5VCM 485+LC RS 485 -and ethernet fibre interface (100Mbps)5VCM 485+L6 RS 485 -and IEC 61850 ethernet fibre interface (100Mbps)

5VCM 232+00 RS 232 interface5VCM 232+FI RS 232 -and RTD fibre optic interface (Glass fibre)5VCM 232+ET2 RS 232 -and ethernet interface (10Mbps RJ45)5VCM 232+I62 RS 232 -and IEC 61850 interface (10Mbps RJ45)5VCM 232+IR RS 232 interface with time synchronization input (IRIG-B)5VCM 232+LC RS 232 -and ethernet fibre interface (100Mbps LC)5VCM 232+L6 RS 232 -and IEC 61850 ethernet fibre interface (100Mbps LC)

5VCM PP Plastic/Plastic serial fibre interface5VCM GG Glass/Glass serial fibre interface5VCM PG Rx Plastic/Tx Glass serial fibre interface5VCM GP Rx Glass/Tx Plastic serial fibre interface5VOM Arc+BI ARC option card (2S+BI)5VOM4DI1DO Digital Input/Output option card

Accessories

17

Page 18: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

18

VAMP 50 series protection relays

Dimensional drawingsWithdrawable model VAMP 50W

Slim fit model VAMP 50S

Panel mounting technique

A

iF1

F2

VAMP 50S c

FD

C

B E

H

I

VAMP

50S

F1F2J

VAMP 50W Cut-out panel

Withdrawable A B C D E F H I J

Millimetres 139 176 233 194 158 106 108 159 1-10

Inches 5.46 6.94 9.17 7.62 6.21 4.19 4.25 6.26 0.04-0.4

VAMP 50S Cut-out panel

Slim fit size A B C D E F H I J

Millimetres 143 105 214 185 85 140 138 83 1-18

Inches 5.64 4.13 8.39 7.26 3.34 5.51 5.43 3.26 0.04-0.7

A

B E

C

D

F

1H

I

J

Page 19: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

Auxiliary voltageVoltage range 40…265 V ac / dc (option A)

18…36 V dc (option B)

Measuring circuity 1A/5A- Current measuring range 0.005…50 x INRated neutral current I0N 1 A or 5 A (optionally 0.2 A or 1 A)- Current measuring range 0.003…10 x IN

Thermal withstand 4 x IN (continuous) 100 x IN (for 1 s)

Rated frequency fN 50 / 60 Hz (45…65 Hz)

I/ODigital inputs (external voltage) 2 pcs (7 option)- Selectable nominal voltage (threshold) 24 / 110 / 220 V ac / dcTrip contacts 4 pcs (5 option)

Disturbance tests Standard & Test class / level Test valueEmission EN 61000-6-4 / IEC 60255-26- Conducted EN 55011 class A / IEC 60255-25 0.01 - 30 MHz- Emitted EN 55011 class A / IEC 60255-25 / CISPR 11 30 - 1 000 MHzImmunity EN 61000-6-2 / IEC 60255-26- 1Mhz damped oscillatory wave IEC 60255-22-1 ±2.5kVp CM, ±1kVp DM- Static discharge (ESD) EN 61000-4-2 class IV / IEC 60255-22-2 8 kV contact, 15 kV air - Fast transients (EFT) EN 61000-4-4 class IV / IEC 60255-22-4 class A ±4 kV / (±2 kV signal ports), 5/50 ns, 5 kHz- Surge EN 61000-4-5 class III / IEC 60255-22-5 2 kV, 1.2/50 ms, CM

1 kV, 1.2/50 ms, DM- Conducted HF field EN 61000-4-6 class III / IEC 60255-22-6 0.15 - 80 MHz, 10 Vemf- Emitted HF field EN 61000-4-3 class III / IEC 60255-22-3 80 - 2700 MHz, 10 V/m- Voltage interruptions EN 61000-4-29 / IEC 60255-11 30%/1s, 60%/0.1s, 100%/0.05s- Voltage alternative component EN 61000-4-17 / IEC 60255-11 12% of operating voltage (DC) / 10min

- Voltage dips and short interruptions EN 61000-4-11 30%/10ms, 100%/10ms, 60%/100ms>95%/5000ms

- Power-frequency magnetic field EN 61000-4-8 300A/m (continuous), 1000A/m / 1-3s- Pulse magnetic field EN 61000-4-9 1000A/m, 1.2/50 ms

Electrical safety tests Standard & Test class / level Test value- Impulse voltage withstand EN 60255-5, class III 5 kV, 1.2/50 ms, 0.5 J- Dielectric test EN 60255-5, class III 2 kV, 50 Hz- Insulation resistance EN 60255-5- Protective bonding resistance EN 60255-27- Power supply burden IEC60255-1

Mechanical tests Standard & Test class / level Test valueDevice in operation- Vibrations IEC 60255-21-1, class II / IEC 60068-2-6, Fc 1Gn, 10Hz – 150 HZ- Shocks IEC 60255-21-2, class II / IEC 60068-2-27, Ea 10Gn/11msDevice de-energized - Vibrations IEC 60255-21-1, class II / IEC 60068-2-6, Fc 2Gn, 10Hz – 150 HZ- Shocks IEC 60255-21-2, class II / IEC 60068-2-27, Ea 30Gn/11ms- Bump IEC 60255-21-2, class II / IEC 60068-2-27, Ea 20Gn/16ms

Environmental conditions Standard & Test class / level Test valueDevice in operation- Dry heat EN / IEC 60068-2-2, Bd +65°C- Cold EN / IEC 60068-2-1, Ad -40°C- Damp heat, cyclic EN / IEC 60068-2-30, Db From +25°C to +40°C, From 93% RH to 98% RH, 6 days- Damp heat, static EN / IEC 60068-2-78, Cab +40°C, 93% RH, 10 days- Flowing mixed gas corrosion test, method 2 IEC 60068-2-60, Ke +25°C, 75% RH,10 ppb H2S, 200 ppb NO2, 10 ppb CL2

- Flowing mixed gas corrosion test, method 4 IEC 60068-2-60, Ke +25°C, 75% RH,10 ppb H2S, 200 ppb NO2, 10 ppb CL2, 200 ppb SO2

Device in storage- Dry heat- Cold

EN / IEC 60068-2-2, BbEN / IEC 60068-2-1, Ad

+75°C-40°C

CasingDegree of protection (IEC 60529) IP54Dimensions (W x H x D) 130 x 170 x 210 mmMaterial 1 mm steel plateWeight 2.0 kgColour code RAL 7032 (Casing) / RAL 7035 (Back plate)

PackageDimensions (W x H x D) 320 x 215 x 175 mmWeight (Terminal, Package and Manual) 3.0 kg

Main technical data

19

Page 20: VAMP 50, VAMP 51, VAMP 52, VAMP 55 - acdc-bg.com · The rapid device configuration and download via the dedicated VAMPSET setting tool raises usability to a new ... VAMP 50 series

VB5

0.EN

008

Vamp LtdP.O.Box 810FI-65101 VAASAFinland

Visiting address:Vaasa Airport ParkYrittäjänkatu 15Vaasa, Finland

Tel: +358 20 753 3200Fax: +358 20 753 3205Email: [email protected]:// www.vamp.fi

We reserve the rights to product alterations without prior notice. Copyright © Vamp Ltd. All trademarks are the property of their respective holders.

With its headquarters in Finland, Vamp Ltd specialises in protection relays,

arc flash protection and measuring and monitoring units for power systems.

Vamp’s medium-voltage and sub-transmission protection relays are used

in a number of applications, from overhead line feeders and substations to

power plants and industrial power system. Their unique integrated arc flash fault

protection functionality enhances the safety of both people and property and has

made Vamp a leading brand in arc flash protection worldwide. Vamp is a member

of Schneider Electric, a global specialist in energy management.

Our success is based on competitive standard products, constant develop-

ment by our designers possessing experience from three protection relay

generations, our long-term partnerships, flexibility and 24 hour care of the

customers.

Our organization has been audited and found to be in accordance with the

requirements of the ISO 9001 management system.

We keep electricity running