siemen - daytona beach, florida

11
SIEMEN FIRE ALARM Submittal Project Name: DR. PECK FHM DAYTONA 4TH FL 125 MEMORIAL MEDICAL PARKWAY DAYTONA BEACH, FL 32117 Project Number: DATE SUBMITTED: 11/10/14 WILE COPY SIEMENS Industry Inc. Building Technologies Division. 4122 METRIC DRIVE SUITE 100 WINTER PARK, FLORIDA OFFICE: (407) 571-1999 FAX: (407) 571-1998

Upload: others

Post on 01-Jan-2022

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SIEMEN - Daytona Beach, Florida

SIEMEN

FIRE ALARM Submittal

Project Name:

DR. PECK FHM DAYTONA 4TH FL

125 MEMORIAL MEDICAL PARKWAY

DAYTONA BEACH, FL 32117

Project Number:

DATE SUBMITTED: 11/10/14WILE COPY

SIEMENS Industry Inc. Building Technologies Division.

4122 METRIC DRIVE SUITE 100

WINTER PARK, FLORIDAOFFICE: (407) 571-1999 FAX: (407) 571-1998

Page 2: SIEMEN - Daytona Beach, Florida

SIEMENS

INSTALLATION INSTRUCTIONS

2-WIRE FIELD SELECTABLE HORN, STROBE

AND HORN/STROBE APPLIANCES

(WALL AND CEILING MOUNT)

IMPORTANT - All audible and visual signaling appliances must beinstalled in accordance with all applicable national and local fire alarmcodes and any other required regulatory agencies.

Series Z horn, strobe, and horn/strobe appliances are designed foreasy installation. The ZH horn/strobes, ZH Horn and ZR strobes arefor 24V operation. The appliance comes in two main parts. Theuniversal mounting back plate allows the appliance to be mounted toa single-gang, double-gang, four square backbox, 4" octagon

backbox, or a 3 J4" octagon backbox. Two wire appliance wiring isthen connected to the mounting back plate. This allows a continuitycheck of the entire NAC circuit before any appliances are attached. Italso allows the appliances to be installed after all finish work has beencompleted. The installer can snap or install the appliances when allother work is complete.

Refer to P/N 315-096363 for the maximum number of appliances on asingle notification appliance circuit.

SPECIFICATIONS:

->

Table 1: Models and Settings

Model"

Voltage Range(Special Application)

Per UL/ULC

(VDCA/RMS)

Strobe

(cd)Horn

Current Draw

See TableMounting

ZR-MC

ZR-HMC 16.0-33.0 135/185 - 3 Wall

ZR-MC-C 16.0-33.0 15/30/75/95 - 3 Ceiling

ZR-HMC-C | 16.0-33.0 115/177 3 Ceiling

ZH-MC

ZH-HMC 16.0-33.0 135/185 X 4 Wall

ZH-MC-C 16.0-33.0 15/30/75/95 X 4 Ceiling

ZH-HMC-C I 16.0-33.0 115/177 X 4 Ceiling

ZH 16.0-33.0 -

X 5 Wall or Ceiling

** All models available in red and white.

STROBE AND HORN STROBE APPLIANCES:

Siemens' Series Strobe Appliances are UL Listed under Standard 1971 (Signaling Devices for the Hearing Impaired) for indoor Fire Protection Serviceand ULC Listed under Standard CAN/ULC-S526-02 for indoor Fire Protective Service. They are listed for indoor use only. Siemens' Series HornAppliances provide a selectable Continuous or Code 3Horn tone when connected directly to an unsynchronized NAC (Notification Appliance Circuit).They can also provide a synchronized code 3 or march time horn tone when connected to a notification appliance circuit running the Siemens syncprotocol The Horn Appliances can be field set for High (HI) or Low (LO) dBA sound output. The Horn Appliances are UL Listed under Standard 464for Audible Siqnal Appliances and ULC Listed under Standard CAN/ULC-S525-99 for Audible Signaling Devices for Fire Alarm Systems. They arelisted for indoor use only. These models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (VRMS) input voltage.All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP. The ZR Strobe, ZH Horn/Strobe, andZH Horn are for 24V operation only.

NOTE- The Code 3temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specifiedby ANSI and NFPA 72 for standard emergency evacuation signaling. The Code 3Horn should be used only for fire evacuation signaling and notfor any other purpose.

Table 2A: ZH and ZH-MC dBA Sound Output

Description Volume

Reverberant dBA per UL 464 Anechoic Per CANAJLC-S525-99

Zl I and ZH-MC at 24 V Zl land ZH-MC at 24V

16.0V 24.0V 33.0V 16.0V 24.0V 33.0V

Continuous I lornHigh 83 87 90 93 95 96

I ,ow 77 81 83 88 90 91

Code 3 Mom or

* March Time

High 79 82 86 93 95 96

Low 72 76 79 88 90 91

Siemens Building Technologies, Inc.8 Fernwood Road

1'lorhamPark. New Jersey 07932

"Available in sync mode only.

Siemens Building Technologies, Ltd.2185 Deny Road West

Mississauga Ontario L5N 7A6Canada

Page 3: SIEMEN - Daytona Beach, Florida

CURRENT DRAW:

Table 2B: ULC Directional Characteristics

-3dBA 35 degrees left, 40 degrees right-6dBA 55 degrees left, 65 degrees right

Table 3: ZR Strobe Current Draw (Amps) at 16.0-33.0 Volts I

VoltageStrobe Setting (cd)

MC HMC MC-C HMC-C

15 30 75 110 135 185 15 30 75 95 115 177

DC 0.064 0.098 0.175 0.233 0.318 0.445 0.069 0.111 0.200 0.264 0.318 0.445

FWR 0.108 0.164 0.268 0.368 0.482 0.684 0.117 0.180 0.297 0.398 0.482 0.684

Table 4: ZH Horn/Strobe Current Draw (Amps) at 16.0-33.0 Volts

Voltage

Strobe Setting (cd)

Horn

SettingMC HMC MC-C HMC-C

15 30 75 110 135 185 15 30 75 95 115 177

DCHigh* 0.078 0.113 0.195 0.259 0.371 0.506 0.087 0.131 0.222 0.292 0.371 0.506

Low* 0.070 0.107 0.188 0.246 0.324 0.455 0.075 0.121 0.213 0.277 0.324 0.455

FWRHigh* 0.141 0.200 0.302 0.406 0.521 0.722 0.149 0.216 0.331 0.436 0.521 0.722

Low* 0.123 0.179 0.290 0.391 0.497 0.699 0.131 0.195 0.319 0.421 0.497 0.699

Current Draw is the same for the Continuous Horn, Code 3 Horn and March Time Settings.

Table 5: ZH Horn Current Draw (Amps)Voltage Horn Setting 16.0-33.0 Volts

DCHigh* 0.044

Low* 0.018

FWRHigh* 0.075

Low* 0.045

* Cunent Draw is the same for the Continuous Horn, Code 3, and March Time Settings.

NOTE: Candela and Horn Setting will determine the current draw of the product.

When calculating the total cunents use Tables 3-5 to determine the highest value of RMS current for an individual appliance, then multiply thesevalues by the total number of appliances. Be sure to add the currents for any other appliances, including audible signaling appliances powered by thesame source, and to include any required safety factors.

NOTE: These notification appliances are UL Listed as "Special Application". They are intended to be used only with Siemens notification appliancecircuits.

NOTE- THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE RANGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USINGFILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.

NOTE- REFER TO THE INSTALLATION INSTRUCTIONS FOR THE APPROPRIATE NAC TO FIND THE MAXIMUM ALLOWED VOLTAGE DROP.USE THIS VALUE ALONG WITH THE CURRENT DRAW FOR THE APPLIANCE TO DETERMINE THE ALLOWABLE WIRE RESISTANCE. THEMAXIMUM WIRE RESISTANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.

NOTE: Strobes arenot designed tobeused on coded systems in which the applied voltage iscycled onand off.

NOTE- MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM'SPRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGSOF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSERATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULTIN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TOYOU AND/OR OTHERS.

WIRING AND MOUNTING BASE:

FROM PRECEDING

APPLIANCE OR FACP

+ + -

Figure 1:

Siemens Building Technologies, Inc.

TO NEXT APPLIANCEOR END OF LINE

RESISTOR (EOLR)

Figure 2:

All strobe appliances have in-outwiring terminals thataccept two#12 to #18 American Wire Gauge (AWG)wires at each screw terminal. Strip leads 3/8 inches andconnect to screw terminals.

Break ail in-out wire runs on supervised circuits to ensureintegrity of circuit supervision as shownin Figure 2. Thepolarity showninthe wiring diagramsis forthe operationof the appliances. The polarity is reversed by the FACPduring supervision.

P84860-001 E

Sheet 2 of 4

Page 4: SIEMEN - Daytona Beach, Florida

WIRING AND MOUNTING SETTINGS:

Note: The ZH is factory set for the most common application of High dB and Code 3.

Jumper Plug and Candela Selectors

HORN SELECTION

_zxT7-

ANDELA SELECTION

CANDELA POINTERpANDELA SELECTION

CANDELA POINTER

Siemens Building Technologies, Inc.

HMC-C CANDELA POINTER

MC-C CANDELA POINTER

MC CANDELA

POINTER

Note: Candela Factory Settings are shown in above illustration.

Jumper plug settings for High dB Jumper plug settings for Low dB andand Code 3 (or March Time). Code 3 (or March Time).

nn | |N . i 11 t

i M

UillLf Uii iLu u u u

NO PLUG HORN LOW NO PLUG HORN LOW

WITH PLUG C0DE3 HI ;V;TH PLUG C00E3 H

Jumper plug settings for High dB Jumper plug settings for Low dB andand Continuous Horn. Continuous Horn.

! ID •

NO PLUG HORN LOW NO PLUG HORN LOW

H PLUG|C0DE3i H. WITH PLUG C0DE3

HMC CANDELA

POINTER

P84860-00I E

Sheet 3 of 4

Page 5: SIEMEN - Daytona Beach, Florida

NOTE:Useneedlenoseplierstopullandproperlysetthejumperplugs.NojumperplugsareneededforContinuousHornandlowdBsettings.However,itisrecommendedthatthejumperplugberetainedintheunitforfutureuse(ifneeded)asshown.

•CAUTION:Checkthattheinstalledproductwillhavesufficientclearanceandwiringroompriortoinstallingbackboxesandconduit,especiallyifsheathedmulticonductorcableor3/4"conduitfittingsareused.

CAUTION:DONOTOVERTIGHTENMOUNTINGSCREWS.EXCESSIVETORQUECANDISTORTTHEBASEANDMAYAFFECTOPERATION.

MOUNTINGOPTIONS:

SIDEOPENINGFORFLATSCREWDRIVER

Figure3:Installation

OPTIONAL

SECURING

SCREWS

1.Installmountingplateasshowninfigure1toasingle-gang,double-gang,4"square,4"octagon,ora3!4"octagonbackboxwiththeprovidedpanheadscrews.Toremovedustcover,placethumbandindexfingerontopedoesofcoverandpulloffcover.

2.Connectfieldwiringperfigures2and3.3.Addresswiresbackintobackbox.

4.Placedustcoverovermountingplatetoprotecttheterminalswhileperformingwiringcontinuitycheck..

5.Removedustcoverbeforesnappingorinstallingtheapplianceontothemountingplateperfig3.

Figure4:Removal(Seestep8below)

Important:Deviceonlyhasonemountingorientation.Matchthetopofthebasetothetopofthedevice.Ifitisdesiredtofurthersecurethedevicetothebase,thentwooptionalscrewsareprovided.Toinstallthesescrewspunchoutthescrewholeslocatedatthetopandbottomofthedevice.Toremovetheappliance,pushasmallflat-bladedscrewdriverintothesideopening.ThescrewdrivermustclearthesnapreleaseopeningbyV*todisengagethesnap.Donotpryoffhousingwiththescrewdriver.Applypressurewithscrewdriver,insertedineithersideopening,asshowninFig4toreleasethehousing.

NOTE:NFPA72/ANS1117.1conformtoADAAGEquivalentFacilitationGuidelinesinusingfewer,higherintensitystrobeswithinthesameprotectedarea.

NOTE:ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimitsaredesignedtoprovidereasonableprotectionagainstharmfulinterferenceinresidentialinstallation.Thisequipmentgenerates,usesandcanradiateradiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructions,maycauseharmfulinterferencetoradiocommunications.However,thereisnoguaranteethatinterferencewillnotoccurinaparticularinstallation.Ifthisequipmentdoescauseharmfulinterferencetoradioortelevisionreception,whichcanbedeterminedbyturningtheequipmentoffandon,theuserisencouragedtotrytoconecttheinterferencebyoneormoreofthefollowingmeasures:1)Reorientorrelocatethereceivingantenna,2)Increasetheseparationbetweentheequipmentandreceiver,3)Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected,and4)Consultthedealeroranexperiencedradio/TVtechnicianforhelp.

SiemensBuildingTechnologies,Inc.P84860-001E

Sheet4of4

Page 6: SIEMEN - Daytona Beach, Florida

SIEMENSINSTALLATION INSTRUCTIONS

MULTI-CANDELA ELECTRONIC CHIME STROBE

IMPORTANT: All audible and visual signaling appliances must beinstalled in accordance with all applicable national and local fire alarmcodes and any other required regulatory agencies.

Series CH-MC Multi-Candela Electronic Chime Strobe is UL Listedunder Standard 1971 for Signaling Devices for the Hearing Impairedand UL Standard for Private Mode Audible Signal Appliances. TheCH-MC Chime Strobe is designed for low current draw and versatileperformance. This model offers a choice of single stroke or vibratingoperation, has adjustable sound level, and has a chime tone adjustablefrom 800 to 1200Hz. The CH-MC Multi-Candela strobe provides fourselectable light output intensities in one unit. This appliance alsoincorporates a chime mounting plate attached to the chime for ease ofinstallation. The Chime Strobe model can provide a non-synchronizedstrobe appliance when connected directly to a fire alarm control panel(FACP), or provide a synchronized strobe appliance when connectedto a notification appliance circuit running the Siemens sync protocol.

The strobe uses a xenon flashtube with solid state circuitry enclosed ina polycarbonate lens to provide maximum visibility and reliability foreffective visible signaling. The CH-MC is Listed for indoor use, wallmount only with the backboxes specified in these instructions (seewiring and mounting information).

The CH-MC model is UL Listed for indoor use with a temperaturerange of +32°F to +120=F (0°C to +49°C) and maximum humidity of85% RH. The effect of shipping and storage temperatures shall notadversely affect the performance of the appliance when it is stored inthe original cartons and is not subjected to misuse or abuse.

NFPA 72/ANSI 117.1 conform to ADAAG Equivalent FacilitationGuidelines in using fewer, higher intensity strobes within the sameprotected area.

Refer to P/N 315-096363 for the maximum number of appliances on asingle notification appliance circuit.

SPECIFICATIONS:

->

Table 1: UL Listed Models and Ratings

Models*

Operating Voltage(Special Application)

Per UL 1971

(VDCA/RMS)

Maximum RMS

Current (Chime Only)dBA at 10 Feet

Candela

Mounting

OptionsReverberant

Max Min Max

CH-MC 16.0-33.0 0.024 52 58 15/30/75/110 A,B

'Available in red and white.

NOTES:

1. The strobe will produce 1 flash per second over the Input Voltage range.2. The strobes meet the required light distribution patterns defined in UL 1971.3. The chime must be set at maximum volume for Private Mode Fire Protective Service per UL 464 listing requirements (see page 3).4. The chime produces a brief inrush current of 0.100 Amps with filtered DC input (0.140 Amps with full-wave-rectified (VRMS) input) with a time

duration of 100 milliseconds.

! WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.

Table 2: UL Current Ratings (Strobe Only)Maximum RMS Current (Amps)

UL Voltage 15cd 30cd 75cd 110cd

DC 16-33VDC 0.064 0.098 0.175 0.233

FWR 16-33VRMS 0.108 0.164 0.268 0.368

When calculating the total currents use Table 2 to determine the highest value of RMS current for an individual strobe, then multiply these values by thetotal number of strobes. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, andto include any required safety factors.

Note: These notification appliances are UL Listed as "Special Application". They are intended to be used only with Siemens notification appliancecircuits.

These appliances were tested to the voltage limits of 16.0-33.0 volts for 24V models using filtered DC or unfiltered Full-Wave-Rectified Voltage. Do notapply voltage outside of this range.

Note: Refer to the installation instructions for the appropriate NAC to find the maximum allowed voltage drop. Use this value along with the current drawfor the appliance to determine the allowable wire resistance. The maximum wire resistance between strobes shall not exceed 35 ohms.

! CAUTION: Strobes are not designed to be usedoncoded systems in which the applied voltage is cycled onandoff.

! WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BYALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM'SPRIMARY AND SECONDARY POWER SOURCES DO NOT EXCEED THE POWER SOURCES' RATED CAPACITY OR THE CURRENT RATINGS

OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSERATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN

PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

Siemens Building Technologies, Inc.8 Fernwood Road

Florham Park, New Jersey 07932

P83932-005 B

Sheet l of 3

Page 7: SIEMEN - Daytona Beach, Florida

WIRING AND MOUNTING INFORMATION:

The following figures (A,B) show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If theselimits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damaqe theproduct.

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathedmulticondudor cable or 3/4" conduit fittingsare used.

FLUSH MOUNTING

(STROBE SPEAKER)

, r

SURFACE MOUNTING

(STROBE SPEAKER)SURFACE ;/"DACKBOX -^(SBBS) Vs •""

SPEAKER

MOUNTING

PLATE

SQUARE OR

ROUND GRILLE

SPEAKERMOUNTING

PLATE

MAXIMUM NUMBER QF CQNPUCIORS

AWG81B AWG0I6 AWOffM AWOQ1?

Figure 1:Chime Appliance and Strobe Appliance operate independently.Recommended for coded systems where the chime is set on single stroke(SS) mode and is cycled on and offwhile the strobe flashes continuously.

FROM PRECEDING

CHIME OR FIRE ALARM +CONTROL PANEL (FACP)-

FROM PRECEDING +STROBE OR FACP I I

[HfcaJI

iSTROBE CHIME

Figure 3:

TO NEXT

CHIME OR

END-OF-LINE RESISTOR

(EOLR)

TO NEXT

STROBE OR EOLR

NOTE BACKK3XISCCMMT1BLEVUIHVVIREMCILDANOCONOU1TMOUNTING HOLES ARE TOR SINGLE-GANG. OOUOCE-OANO«' SQ 3- 1W & r OCTAGON OR ROUND BACKBOXES

MAXIMUM NUMBER OF CONDUCTORS

ftWGffIB AWOW1B AWttOM AWGW1?

Figure 2:Chime Appliance and Strobe Appliance operate in unison. Red and blackwires are supplied. The chime must be set for vibrating mode (VIB). (Useof Sync Protocol is not recommended in this wiring option)

FROM

PRECEDING

APPLIANCE OR

FIRE ALARM

CONTROL PANEL

(FACP)

STROBE CHIME

TO NEXT

APPLIANCE OR

END OF LINE

RESISTOR

(EOLR)

El I

The Chime Strobe model has in-out wiring terminals that accept two #12 to #18 American WireGauge (AWG) wires at each screw terminal. Strip leads 3/8 inches and connect to screwterminals.

Break all in-out wire runs on supervised circuits to assure integrityof circuit supervision as shownin Figure 3. The polarity shown in the wiring diagrams is for operation of the appliances. Thepolarity is reversed by the FACP during supervision.

GROUNDING: Install the appliance to a grounded backbox (Per NFPA 70, the National Electrical Code) using the lockwashers provided in hardwarebag under the head of each mounting screw for the appliance.

Figure 4: PC Board Layout

i i

Siemens Building Technologies, Inc.

1. The chime is factory set in single stroke (SS) mode. It can bechanged to vibrating (VIB) mode before wiring the appliancewith the provided jumper. Refer to PC Board layout shown inFigure 4. (SS = single stroke, VIB = vibrating)SINGLE STROKE OPERATION: The minimum input pulseduration must be at least 160 milliseconds "on" time and 160

milliseconds "off' time. The chime will only operate once eachtime it is pulsed. This mode is recommended for codedsystems.VIBRATING OPERATION: Continuous input voltage must beapplied to the chime to activate the chime at one secondintervals.

2. The volume and tone controls have been adjusted at the factoryto insure maximum dBA output. However, once the mode isselected, the installer may want to fine tune the appliance tobetter suit the application.

P83932-005 B

Sheet 2 of 3

Page 8: SIEMEN - Daytona Beach, Florida

Figure 5:

/^ r^"N\

• k,,jX,1 rl TsA^lol M

INSERT \DRIVER \

H1

1 U 11

NOTE: The CH-MCcomes pre-set at 15cd.

X WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATIONWHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT "CLICKS" IN PLACE. AFTER CHANGING THECANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.

MOUNTING PROCEDURES:

1. This model can be flush mounted to a 4" square by 2-1/8" deep backbox with a 4" square 1-1/2" extension ring (Figure A), surface mounted toaSurface Backbox (Figure B). Mounting hardware foreach mounting option is supplied.

2. Conduit entrances to the backbox should beselected to provide sufficient wiring clearance for the installed product. Do not pass additional wires(used for other than the signaling appliance) through the backbox. Such additional wires could result in insufficient wiring space for the signalingappliance.

3. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for thesignaling appliance.

4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on theproduct. This isespecially important for stiff, heavy gaugewires andwires with thick insulation orsheathing.

5. This model hasan integrated mounting plate which must beoriented correctly when it is mounted tothe backbox. Turn the mounting plate so thatthe arrow above the words"Horizontal Strobe" or "Top" pointsto the top side ofthe mounting plate

6. Tomove selectorswitch, insertscrewdriver into slotshown on the bottom side ofthe strobe. See Figure 5.7. Mount the chime mounting plateto the backbox with the cone protector on. After the chime mounting plateis attached to the backbox, remove the

cone protector before installing the grille. Next, attachthe grille to the chime mounting plateand attachwith (2)screws.

The110 Candela Strobe setting is Listed for use insleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards andthe Authority Having Jurisdiction.

_L WARNING: INSTALLATION OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS SHOULD BE WALL MOUNTED AT LEAST 24"BELOW THE CEILING AS FOLLOWS: (1) THE ON-AXIS (DIRECTLY IN FRONT OF LENS) LIGHT OUTPUT SHOULD BE DIRECTED AT THEEYELIDS OF THE SLEEPING PERSON, E.G. PILLOW END OF BED, BED HEAD; (2) NO PART OF THE BED SHALL BE MORE THAN SIXTEEN(16) FEET FROM THE STROBE NOTIFICATION APPLIANCE. INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF BUILDINGS WITHSLEEPING OCCUPANTS, E.G. HOTELS AND MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE THE BEDLOCATION TO A POSITION VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR DURING AFIRE EMERGENCY.

X WARNING: ASMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDERCERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN AGLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, SIEMENS BUILDINGTECHNOLOGIES STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THEFIELD OF VIEW WHICH EXCEEDS FIVE (S) Hz AT THE OPERATING VOLTAGE OF THE STROBES. SIEMENS BUILDING TECHNOLOGIES ALSOSTRONGLY RECOMMENDS THAT THE INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELSESTABLISHED BY APPLICABLE LAWS, STANDARDS, REGULATIONS, CODES AND GUIDELINES.

NOTE: This equipment has been tested and found to comply with the limitsfor a Class B digital device, pursuant to Part 15 of the FCC Rules. Theselimits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and canradiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radiocommunications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmfulinterference to radio or television reception, which can be determined by turning the equipmentoffand on, the user is encouraged to try to correct theinterference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between theequipment and receiver, 3) Connect the equipment into an outlet on a circuit differentfrom that to which the receiver is connected, and 4) Consult thedealer or an experienced radio/TV technician for help.

Siemens Building Technologies, Inc. P83932-005 B

Sheet 3 of 3

Page 9: SIEMEN - Daytona Beach, Florida

SIEMENS Data SheetFire Safety &Security Products

FACP AccessoriesPAD-4 Distributed Power Supply UnitNotification Appliance Circuit ExtenderModels PAD-4-ENCL, PAD-4-MB (with FP2011-U1, FP2012-U1 power supplies)

ARCHITECT AND ENGINEER SPECIFICATIONSFour (4) 'Class B'# power-limited notification appliance circuits (NACs)'Class A', field-selectable wiring• Each unit can support an optional module (Model PAD-4-CLSA) that

converts two (2) built-in 'Class A' NACs into four (4) 'Class A' NACs

Up to 3 Amps of auxiliary-power output

Optional built-in strobe synchronization• Supports coded audible signals, includingTemporal 3, Temporal 4 patternsBattery supervision and control

'Form C general Trouble I AC Failmonitoring contactPower supplies support NAC power• Up to 6A used with Model FP2011-U1- Up to 9A used with Model FP2012-U1

24VDC output voltageGround-fault detection

Advanced microprocessor controlUses Flash memory-based system firmware• Optional system-diagnostic and firmware-upgrade tool

r* !v {Vl

••HI j.;

'Class A'

Adapter Card[Model PAD-4-CLSA]

Product Overview

Used with Siemens - Fire Safety fire alarm controlpanels (FACPs), the Distributed Power Supply PAD-4Unit is a NAC expander with a built-in, auxiliary-power output. Each PAD-4 unit distributesadditional power in buildings for audible and visualindicators that conform to the Americans with

Disabilities Act (ADA). PAD-4 also has the followingfeatures:

• NACs

• Signal-input circuits• Battery-charging circuit• Trouble relays for remote monitoring• Diagnostic light-emitting diodes (LEDs)• Alternating Current (AC) power connection

The Siemens NACs, which connect with alarmsignaling devices, have been designed to providethe highest level of reliability and performance.Signal coding on the circuits is accomplishedthrough integrated circuits (rather than relays),which eliminates mechanical wear on the outputcircuits.

Main Board(Model PAD-4-MB]

Unit Enclosure[Model PAD-4-ENCL]

Multi-module mounting in System 3™ enclosures• Multiple modules share battery set

ADA Compliant

®UL864 9th Edition Listed;®UL 1481 Listed (for power supplies)

The PAD-4 unit provides consistent 24VDC outputvoltage to each NAC - independent of voltagefluctuations on the primary or secondary powersource. As a result, a larger voltage drop and agreater wire length for each NAC are supported byeach PAD-4.

SpecificationsThis version of the Siemens Distributed Power SupplyUnit can be configured in the following manner thatmakes the outputs easily programmable:

• 'STEADY'outputs• Synchronized strobe outputs• American National Standards Institute (ANSI) Temporal 3• ANSI Temporal4 [for carbon monoxide (CO) alarm signal]

There are also two (2) inputs used to control theactivation of the four (4) outputs. Programming canbe set so one (1) input will silence the audible signalon Siemens Models 'AS'-series, 'NS'-series, or'ZH'-series horn and horn-strobes while the strobes

remain active.

Distributed Power Supply - NAC Extender (Model PAD-4 series) 3363SIEMENS Industry, Inc.Building Technologies Division

Page 10: SIEMEN - Daytona Beach, Florida

Specifications —(continued)Operation of each PAD-4 unit is controlled byfirmware stored in Flash memory on the main board,as well as the storage of a 10-event log, which canbe viewed via Model PAD-4-FDT. In the event that

an upgrade to the system firmware is required, thefirmware can be transferred to the system withoutthe replacement of firmware chips.

An optional firmware-download software tool,Model PAD-4-FDT, can be used for system diagnostictesting of the following:• Primary-power voltage readouts• Current draw for power charger• Configuration switch settings• Firmware version

• Battery voltage

When the tool is in communication with Model PAD-

4-MB, the Test Mode' LED is illuminated. ModelPAD-4-LUA is a USB serial port adapter that isrequired for tool-kit operation.

Each NAC extender supervises a variety of functionsincluding:• Low AC power• Battery-voltage level• Earth ground-fault conditions

All power can be directed to two (2) 'Class A' or four(4) 'Class B' power-limited NACs. Each NAC supportsup to 3 Amps per circuit. Either one (1) or two (2)inputs can control four (4) outputs, which arecompatible with all Siemens - Fire Safety 24VDCalarm signaling devices.

In cases where 'Class A' circuits are used, an optionalModel PAD-4-CLSA module can be added, providingtwo (2) additional 'Class A' outputs to each PAD-4unit.

Each NAC extender is also capable of operating otherparts of a Siemens fire alarm system, such as doorholders, via 3 Amps @ 24VDC max of power-limitedauxiliary output. When the output activated, thetotal power available cannot exceed 6 Amps whenused with Models FP2011-U1 or 9 Amps when usedwithFP2012-U1.

Trouble conditions are monitored through eachunit's two (2) inputs. In addition, one (1) 'Form CTrouble contact is provided for monitoring each unitthat is connected through the input of a SiemensFACP. Therefore, the user has the option ofconnecting a PAD-4 NAC extender unit into a NAC ofa Siemens FACP, or the unit may be monitored witha Model TRI-series monitoring module on a Siemensintelligent fire system.

Aseparate 'Form C Trouble contact is usedexclusively with each NAC extender to indicate ACFail Trouble events on the NAC extender.

SIEMENS Industry, Inc.Building Technologies Division

Each unit is packaged in its own sheet-metalenclosure with sufficient space to house up to 7AHbattery sets. The enclosure (Model PAD-4-ENCL) isavailable in red.

The battery charger used in each unit can energizebatteries of up to 18AH. Though, when battery setsgreater than 7AH are required, the battery set mustbe housed in a System 3 enclosure or a separate®UL Listed battery enclosure.

System 3 enclosures may also be used to housemultiple Model PAD-4 units in a single enclosure, viathe Model S3AP Adapter Plate. Two (2) units arecapable of sharing the same battery set whenmounted in the same enclosure. Model S3AP can

also be used to mount the PAD-4 main board and

170-Watt power supply (Model FP2011-U1) into aPAD-3 enclosure.

Each Model PAD-4-series unit complies with seismiccertification, pursuant to ASC / SEi 7-05, Section13.2.2, when used with the PAD-4 battery bracket(Model PAD4-BATT-BRKT).

Configuration OptionsOption Input[s] Output Controls | Circuit Types

1 Input 1 All outputs | 'Class B'circuits

2Input 1Input 2*

All outputs

Silences horns on Output 1

'Class B' circuits

3Input 1

Input 2

Outputs 1 and 2

Outputs 3 and 4

'Class B'circuits

'Class B'circuits

4Input 1

Input 2

Output 1

Outputs 2, 3 and 4

'Class B'circuits

'Class B'circuits

5 Input 1 Outputs 1 through 4'Class A'

circuit pairs

6Input 1

Input 2*

Outputs 1 through 4

Silences horns on Output 1

'Class A'

circuit pairs

7

Input 1

Input 2

Outputs 1 and 2

Outputs 3 and 4

'Class A'

circuit pairs

'Class A'

circuit pairs

8Input 1

Input 2

Outputs 1 and 2

Outputs 3 and 4

'Class A'

circuit pairs

'Class B'circuits

denotes when used with Siemens Model 'AS','NS'or "ZH'—serieshorn I strobe devices

Page 11: SIEMEN - Daytona Beach, Florida

Indicator LightsAC Power ON: | Green )

AUX/PS: Yellow

Ground Fault: Yellow

Output 1 Trouble: Yellow

Output 2 Trouble: Yellow

Output 3 Trouble: Yellow

Output 4 Trouble: Yellow

Test Mode: Yellow

Technical Data

AC Fail Trouble Contact Rating:{'Form A' - Normally Closed (N.C) }

2.0A @ 30VDC, max.[resistive]

Basic Trouble Contact Rating:{ 'Form C }

2.0A @ 30VDC, max.[resistive]

Alarm Current:{ for NACs and auxiliary power }

3.0A per circuit, max.6A, max. (via Model FP2011-U1)

9A, max. (via Model FP2012-U1}

Ambient

Temperature:32°-120° F

(0° - 49° C)

Relative Humidity: Up to 93% @ 86° F (30° C);non-condensinq

Auxiliary Power Circuit: One (1) circuit @ 3A max.

Battery Charging Capacity: 18AH

Input Circuits/Configurations:

Two (2) 'Class B'supervisedor

Two (2) 'Class A' supervised

Input Current: 7.0mA, max.

Input Voltage Range: 16-33VDC/VI-W

Installation Environment: Indoor, dry

NACs:

c Supervised, power-limited

c 1.0mA standbycurrent, max.

o Four (4) circuits

z 2K ohms (-r). 8K ohms (-)

Total Output Power:

24VDC@6Amps

(with Model FP2011-U1);

24VDC @ 9 Amps(with Model FP2012-U1)

Output Circuits /Configurations:

o Two (2) 'Class A';- Up to four (4)'Class A'

(via Model PAD-4-CLSA}.

o Four (4) 'Class B';

o One (1) Class A,Two (2) Class B;

Single-Unit Dimensions:{ W -x- H -x- D } 13.5"-x-18.75"-x-3.25"

(34.3 cm. -x- 47.6 cm. -x- 8.3 cm.)Model PAD-4-ENCL

Color:Red

Model PAD-4-ENCL

SIEMENS Industry, Inc.Building Technologies Division

Temperature and Humidity RangeEach PAD-4 Distributed Power Supply Unit is ®UL 8649th Edition Listed for indoor dry locations within atemperature range of 120+/-3°F (49+/-2°C) to32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2%at a temperature of 90+/-3°F (32-i-/-2nC).

Details for Ordering

Model

Number

Part

NumberDescription

PAD-4-ENCL 500-050081 PAD-unit enclosure

PAD-4-MB 500-650217 PAD-unit main board

FP2011-U1 500-450222 170-Watt power supplyFP2012-U1 S54400-Z60-A1 300-Watt power supply

— System Kits —

Model

Number

Part

NumberDescription

PAD4-6A S54339-A1-A1

Complete 6A PAD-4 kit with:- One (1) Unit Enclosure. PAD-4-ENCL- One (1) Main Board, PAD-4-M8

- One (1) 170W power supply. FP2011-U1

PAD4-6A-CtSA S54339-A2-A1

Complete 6A PAD-4 kit with:- One (1) Unit Enclosure, PAD-4-ENCL- One (1) Main Board. PAD-4-MB- One(1) 170W power supply, FP2011-U1- One (1) 'Class A' Adapter Card, PAD-4-CLSA

PAD4-9A S54339-A3-A1

Complete 9A PAD-4 kit with:- One (1) Unit Enclosure, PAD-4-ENCL

- One (1) Main Board. PAD-4-MB- One (1) 300W power supply, FP2012-U1

PAD4-9A-CtSA S54339-A4-A1

Complete 9A PAD-4 kit with:- One (1) Unit Enclosure. PAD-4-ENCL

- One (1) Main Board, PAD-4-MB

- One(1) 300W power supply, FP2012-U1- One (1) 'Class A' Adapter Card, PAD-4-CLSA

— Optional Accessories —

Model

Number

Part

NumberDescription

PAD4-BATT-BRKT S54430-B4-A1 Battery bracket for NACexpander

PAD-4-LU A S54389-C1-A1 PAD-4 Laptop-Upload Adapter

PAD-4-CLSA 500-850254 'Class A'Adapter Card

S3AP 500-650257PAD-4 NACexpander adapter plate(for use with PAD-3 and System 3 enclosures)