results presentation, tests about air conditioning equipment made in metaplus … · 2019. 6....

103
RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS (BEPENSA- COCA-COLA) IN MERIDA, YUCATAN, MEXICO. MERIDA, YUCATAN AUGUST 2006

Upload: others

Post on 29-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING

EQUIPMENT MADE IN METAPLUS (BEPENSA- COCA-COLA) IN MERIDA,

YUCATAN, MEXICO.

MERIDA, YUCATAN

AUGUST 2006

Page 2: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Objective

The purpose of this document is to present the results of the test made by Grupo Energético Mexicano

in the unit YORK, serial number NFYMD37370 of 7.5 tons, treated with our MaxR 100 additive and

located in the Human Resources area in Metaplus, in the city of Merida, Yucatan.

The unit is 7.5 tons. The objectives of the test were:

Increase the equipment´s useful life by increasing it´s oiling (lubrication).

Reduce it´s Energy consumption.

Increase the skills and speed of cooling, using less energy.

After making the test, we conclude that the three objectives have been accomplished, demonstrated

by measurements taken before and after the use of our additives.

II. Test description

Two devices were installed to measure the temperature, they measured every 3 minutes during a time

line before and after the application of MAXR 100, using the ASHRAE 37-1988 procedure as a guide.

Output, Return, environmental and exterior temperatures were measured. The Energy used by the

equipment during the process in the same period of time was measured as well.

During a period of 7 days of measurement before and after the test, we looked for a segment of three

days, during which certain conditions such as the external temperature were kept as similar as

possible between the two periods. This was made to give more consistency to the test.

For analysis reasons, when PRE is mentioned, we will be referring to the measurements made before

the application of MAXR; and when using POST, we will be referring to the measurements made after

treating the equipment with MAXR.

III. Test development

The differences demonstrated in the results show that there are big differences in the unit’s operation,

comparing the PRE and POST periods. The cooling skills of the unit have increased, cooling faster and

in a more efficient way, using less energy.

The comparison period was from the 14th to the 17th of June for the PRE period and from the 12th

to the 15th

of July for the POST period. During this two periods the external temperature was similar.

Average the POST period was 2 degrees higher than the PRE period.

Page 3: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

GRAPHIC OF EXTERNAL TEMPERATURE

USEFULL LIFE OF THE EQUIPMENT

The first analysis is about the use of the equipment. In a summary of 610 analyzed

cycles, we count how many times were the equipment’s compressors on by measuring

the energy consumption. In the PRE period compressors were on 91.64% of the time. In

the POST period they were on only 53.94% of the time.

We can conclude that the equipment is extending its useful life by keeping its

temperature and turning on 40% less of the times, as a consequence it will as well

reduce reparation needs. This is an effect of the importance of lubrication (oiling), it

allows it to work easier.

EVENTS SUMMARY

EVENTS “ON” AVERAGE

PRE 610 559 91.64 %

POST 610 329 53.94 %

DIFFERENCE 0 230 37.70 %

ENERGY SAVING

The next results are about the energy consumption on the PRE and POST periods,

(Metaplus rates in July 2007 and a sales price of 75usd. per oz).

We could find a 35% save in its potential consume in KWH between PRE and POST

periods, improving conditions and reducing effort. With a price of 65 American dollars

per oz, the pay-back time is one year and 12 days. This application assures that the

Ext. Environment

POST

Ext. Environment

PRE

Page 4: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

equipments temperature will stay for 10 years, this way we are talking about a 9 years

saving period.

Page 5: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

SAVINGS $ 188.94

IVA $ 28.34

$ 217.28

DAP $ 10.86

TOTAL $ 855.68

SAVINGS WITHOUT IVA 199.81

INVESTMENT $2,475.00

TRS 12.39 MONTHS

ENERGY

DEMAND ENERGY DEMAND TOTAL

BASIC INTER.

PICO

BASIC

INTER

PICO

BASIC

INTER

PICO

PRE MAXR 187.36 552.96 63.93 8.74 8.74 8.74 $114.7 $410.9 $145.67 $1181.74 $1862.01

POST MAXR 109.50 394.64 54.16 8.74 8.74 8.74 $67.03 $293.25 $131.05 $1181.74 $1673.07

DIFFERENCE 77.86 158.32 9.77 ---------- --------- --------- $47.67 $117.65 $23.62 ----------- $188.94

COST

Page 6: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

TARIFA JULIO

KWH BASE $0.6122 pesos

KWH INTER $0.7431 pesos

KWH PICO $2.4194 pesos

DEMAND $135.2100 pesos

We have considered that Metaplus Works with a rate above 100KW. In the case of realizing the same tests in lower rates, the result

will be the following:

RATE LOWER THAN 100KW = 10.61 MONTHS GENERAL USE RATE = 4.08 MONTHS

Page 7: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

THERMAL CONDITIONS AND ENERGY

The internal temperature was kept between 21.20 °C and 23.97°C in both periods, with

an average of 22.68°C.

In the analysis of this tables we can conclude the following:

As we could see, The output, return and exterior temperatures were higher in the POST in

comparison to the PRE period, but the internal temperature remained in 22°C and the

equipment showed savings in its consumption.

This situation demonstrates that the unit has recovered its skills and speed of cooling,

the equipment has now a more efficient operation, which allows it to have better results

with less effort. This is the result of two conditions: A significant increase in the lubrication

(oiling) of the equipment, which allows it to work in a mechanically efficient way and the

thermal improvement in its coils.

Table of Measurements PRE

Temperature Minimum Maximum Average

Output 9.46° C 28.01° C 13.15° C

Return 21.63° C 26.77° C 22.83° C

Exterior 22.06° C 37.10° C 27.99° C

Table of Measurements POST

Temperature Minimum Maximum Average

Output 9.73° C 27.97° C 14.75° C

Return 21.22° C 33.75° C 23.95° C

Exterior 22.34° C 40.74° C 29.77° C

As we can see, the minimum and maximum temperatures do not show any significant difference, but

the graphic bellow allows us to observe the most important result of the application of R 100:

Page 8: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

TEMPERATURE AND ENERGY GRAPHIC

This graphic shows the unit´s behavior of turn “on” in PRE and POST related to the

temperature. The red line explains that the compressor in PRE turned on and off in less

occasions, keeping a constant temperature.

The blue line shows the unit´s current behavior, where the compressor turns on and off

in more occasions, for short periods of time, saving energy and keeping the temperature.

The internal temperature was kept between 21.20 °C and 23.97°C in both periods, with

an average of 22.68°C.

In the analysis of this tables we can conclude the following:

As we could see, The output, return and exterior temperatures were higher in the POST in

comparison to the PRE period, but the internal temperature remained in 22°C and the

equipment showed savings in its consumes.

This situation demonstrates that the unit has recovered its skills and speed of cooling,

the equipment has now a more efficient operation, which allows it to have better results

with less effort. This is the result of two conditions: A significant increase in the

lubrication(oiling) of the equipment, which allows it to work in a mechanically efficient way

and the thermal improvement in its coils

.

Output PRE, °C

Output POST, °C

Page 9: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

IV. Conclusions

1. The unit presented savings of 35% in KWH consume.

2. The unit increased its life by reducing 37.7% its own use, because of its lubrication.

3. The pay-back time of the investment in the equipment would be of 12 months in the

highest rate (100kw), of 10 months in a rate lower than 100 kw and of 4 months in the

general use rate.

Page 10: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

TEST REPORT (Prepared May 12, 2009)

FOR CCSD ENGINEERING SERVICES AT THE CLARK COUNTY SCHOOL DISTRICT OF NEVADA

MAXR 100 PERFORMANCE TEST

UNIT: ONE YORK 365 TON WATER COOLED SCREW CHILLER

AIR CONDITIONER UNIT AT SILVERADO HIGH SCHOOL IN LAS VEGAS, NEVADA

TEST REPORT AUTHORIZED AND FUNDED BY:

TRANS BIO ENERGY COMPANY, LLC Owner/Manufacturer of MAXR Products

201 N. Cleveland-Massillon Road, Akron, OH 44333

Prepared by Charles H. Fuller, BSEE President, FULLER INSTRUMENTS, INC. P.O. Box 9040, Chesapeake, VA 23321

757-484-4179

Page 11: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

2

MAXR 100 PERFORMANCE TEST 365 TON YORK SCREW CHILLER

What is MAXR 100? Manufacturer’s definition: MaxR 100 is an inter-metallic compound. The treatment process requires the removal of existing refrigerant oil in equal proportion to the amount of MaxR 100 to be installed. During the integration period, as MaxR 100 is bonding to the metal, existing oil fouling is removed and a permanent bond of the inter-metallic compound is created on the metal surfaces. As a result, MaxR 100 brings the HVAC or Refrigerant unit back to spec in efficiency producing a dramatic energy savings while improving overall operating efficiency.

Information Provided for Documentation of Test:

The existing air conditioning system for Silverado High School consisted of two 365 ton Chillers complete with adequate numbers of Temtrol Air Handlers to maintain comfort levels for the entire school complex. The original design and installation was intended for each Chiller to run alternately and independent of one another. Over time, the gradual degradation of efficiency for both units made it necessary to operate both units simultaneously, with one another, to meet the cooling needs of the building. Running both units at the same time not only increases the utility costs, but places a much higher demand on the operating system as the design had originally intended. One of the main contributing factors in efficiency loss is a phenomenon called oil fouling. As the oil fouling takes hold of the interior surfaces of the Chiller, the heat transfer properties are impaired to the extent that the capacity of the Chiller to produce cooler water is lowered. Air Handlers are devices that are equipped with a set of coils that accept cool water from the Chiller. Fans blow air across the coils of circulating cool water and pass directly to the area needing cooling. The fans usually blow all the time to keep the air in a re-circulating mode. The temperature of the water being supplied to the cooling coil is controlled by various thermostats, pumps, and valves. The Air Handlers were not monitored as part of the Test Procedure. Specifically for the Engineering Services Department of the Clark County School District, this section presents a summary of all the significant test conditions from the MaxR 100 treatment of one of the three-hundred-sixty-five ton YORK SCREW CHILLER (referred to in this test report as “Chiller #2”), located at the Silverado High School in Las Vegas, Nevada. The test procedure is presented in this section as follows:

Page 12: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

3

A. Test unit, dates, location and identification.

1. The original Specifications for Chiller #2 unit is:

York International Model YSDBCBS3-CLA Serial Number: SNBM9216653087B Capacity: 365 Tons Entering (Return) Water Temp 55.01 degF

Leaving (Supply) Water Temp 45.0 degF Design kW/Ton (238 motor kW / 365 ton is .652 kW/Ton)

The performance test on Chiller #2 at Silverado High School was monitored with temperature, humidity and kWh meters in multiple locations. Cold Water Supply and Return and Outside Air Temperatures each were monitored and data was logged in five-minute intervals. A certified state-of-the-art BTU Meter was purchased from Onicon and installed to accurately determine flow rates and various temperatures. During June 23 through June 30, ENV measuring and logging equipment from Climate Automation Systems, 1570 Vivian Lane, Incline Village, NV 89451, was installed in the Chiller unit. All equipment had been tested for accuracy by the manufacturer and certified for use. Installation of all equipment was done by certified technicians from All-Star Air Conditioning and/or AJS Technology, Inc. for Climate Automation Systems in close consultation with Clark County School District personnel. The Outside Air Temperature sensor was installed on the roof of the two-story Silverado High School building above the Chiller room. INSTRUMENTATION: Flow Meter: Onicon BTU/flow meter appropriate for the expected flow range and factory calibrated. This is meter of choice by most equipment manufacturers. Accuracy: 0.5% at calibrated rate, 1% at 10:1 turndown and 2% at 50:1 turndown. 4-20 Ma, 0-5V or 0-10V output over operating range. Temperature sensors were calibrated and be accurate to + or – 0.15 Deg F.

Page 13: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

4

Climate Automation Systems instrumentation was installed to measure: Outside Air (dry bulb) temperature (deg F)

Entering Chilled Water Temperature (deg F)

Leaving Chilled Water Temperature (deg F)

Chilled Water BTU/flow (gpm)

Entering Condenser Water Temperature (deg F)

Leaving Condenser Water Temperature (deg F)

Chiller kW (true RMS power as measured by certified kW/kWh meter)

INSTALLATION OF TEST WELLS: Two “hot tap” test wells were installed by CCSD at the appropriate location identified for the test. This location was selected in full accord with the flow measurement device manufacturer’s recommendations for length of straight pipe and other location criteria. The BTU/flow meter was installed, fully consistent with the criteria expressed at: http://www.onicon.com/pdfs/Insertion%20Turbine%20Flow%20Meters%20Selection%20and%20Site%20Selection.pdf DATA AND DATA RECORDING: All instrumentation are self-contained (i.e. independent of the CCSD EMS). Data is recorded at five-minute intervals. Recorded data values represent the

average value of the parameter over the five-minute measurement interval. Data is logged and recorded over the entire logging period and it is

downloadable such that continuous files of five minute readings are created for the PRE and POST test periods. Only data taken during chiller operation for a full five minutes is used to calculate the performance.

Data is recorded continuously at the stated intervals during the PRE and

POST test period regardless of whether the chiller is in operation or not. Data is downloadable and archived or stored in files continuously so that a

continuous record of all five-minute interval data is available. The data is capable of being exported to Excel and other formats for analysis.

Data is downloadable and stored on hardware purchased from Climate

Automation Systems of Reno, Nevada and displayed on software supplied

Page 14: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

5

and programmed by them. Connection to the Internet allows observation of current data and accumulated data is monitored by authorized personnel. Remote change of program is limited to only specific personnel. Security restriction was rigidly set and monitored.

CALCULATIONS: Chilled water data calculations is available for: Chiller CHW BTU’s for each five minute period

Chiller CHW flow (gpm) for each five minute period

Chiller average kW over each five minute period

kWh per day PRE = The total kilowatt hours for the PRE installation period per day = the sum of the measured kWh for all of the five minute intervals that the chiller was in operation for that day. Ton-hours per day PRE = The total ton-hours for the PRE installation period per day = the sum of the tons for all of the five minute intervals that the chiller was in operation for that day. The PRE installation kWh/ton = kWh PRE/Ton-Hours PRE kWh per day POST = The total kilowatt hours for the POST installation period per day = the sum of the measured kWh for all of the five minute intervals that the chiller was in operation for that day. Ton-hours per day POST = The total ton-hours for the POST installation period per day = the sum of the tons for all of the five minute intervals that the chiller was in operation for that day. The POST installation kW/ton = kWh POST/Ton-Hours POST DURATION OF TESTING: PRE installation measurements were recorded from July 1, 2008 through July 21, 2008, representing the PRE test period for Chiller #2. MaxR 100 was installed on July 22, 2008, initiating the POST installation test period. CONDITIONS DURING TESTING PERIOD: In order to collect comparative data, the protocol for operation required that Chiller #2 operate solely from 4:00 a.m. through 12:30 p.m. While this protocol

Page 15: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

6

was adhered to during the PRE test period of July 1 through July 21, on July 23 (the first POST day following installation of MaxR 100), the protocol was interrupted due to a school function in the building. As was common practice to accommodate cooling comfort levels, Chiller #1 was set to run simultaneously with Chiller #2. This continued through August 3, 2008. On August 4, the test protocol resumed and Chiller #2 ran solo from 4:00 a.m. through 12:30 p.m. In the days following August 4, the building was open to faculty and students in preparation for the school year, as well as public functions. These occupancy levels interfered with the ability to provide “similar circumstance” evaluation for a PRE to POST period comparable analysis. August 4 therefore became the POST date for the purpose of this test report, representing similar PRE period circumstances and protocol of operation. The operating parameter set points; control strategies; settings and control algorithms were recorded at the beginning of the test and were not changed during the entire testing period. During the testing period, no changes were made including changing water or water treatment equipment or practices; cooling tower or tower water treatment modifications or repairs; evaporator or condenser tube cleaning; revisions to condenser or chilled water set-points or set-point adjustment (reset) strategies. CCSD did not perform any maintenance or repairs during the test period that might change factors that impact chiller performance with the exception of permitting All-Star Air Conditioning to change Chiller #2’s oil filter due to an increasing PSI. On June 2, 2008, All-Star Air Conditioning replaced the oil filter in Chiller #2 to prepare for the test. After MaxR 100 was installed, maintenance noticed that the PSI was increasing and called All-Star Air Conditioning to the site. On July 28, 2008, seven days after the MaxR 100 installation, All-Star Air Conditioning had to replace the oil filter which was found to be saturated with debris and was causing the increase in PSI.

Page 16: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

7

RESULTS: In order to make a proper and accurate analysis of the data, PRE to POST, a single day comparison was necessary. August 4 was the best possible POST day, as previously explained and July 17 was chosen as the PRE day, as it represented the best display of capacity for Chiller #2, reaching the lowest Supply Water Temperature during the PRE period between the hours of 4:00 a.m. and 12:30 p.m. The single day comparisons of July 17 and August 4 (demonstrated in the incorporated graph), reveal that MaxR 100 enabled Chiller #2 to reach a much lower Supply Water Temperature (the temperature it was originally designed to meet); maintain the lower water temperature and reach that set temperature in less time. The Chiller oil filter explains how these results were achieved and is incorporated as a part of the results. The raw, accumulated data is available upon request. CONCLUSION: Chiller #2 was markedly improved and restored to the original design capacity after being treated with MaxR 100. It is recommended that Chiller #1 be treated with MaxR 100 at the earliest opportunity. If this step is taken, the staff responsible for the operating parameters of the Chillers, can take advantage of the restored operating capacity and reset the units according to original design and spec to maximize their function. A large reduction in operating expenses for Silverado High School should be realized as the two chillers may be alternately cycled. Another benefit to the CCSD, is the tremendous reduction in maintenance and replacement expense. As verified by the necessity to change the oil filter after treatment, MaxR 100 was fully capable of restoring the test unit by cleaning out oil foulings that degrade the efficiency of the cooling unit and shorten the life of the system over time. Charles H Fuller

Page 17: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

8

Page 18: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

9

Page 19: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

10

Appendix

York International Factory Order Form…………………………….… Pages 11 -12 Temtrol, Inc. Air Handler Specs…………………………....………… Pages 13 - 32 Onicon Flow Meter………………………………………...………..…. Pages 33 - 36 WattNode Pulse Output kWh Transducer………………….……….. Pages 37 - 41

Page 20: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

~.

( 6/28/93 YORK INTERNATIONAL FACTORY ORDER FORMscrewpaks

'tc::st £66t-6C:-tJnr

PAGE 1 0f YVersion: 12/92

Revil;ionNOI

Revision Dates

York OrdQr Number: 9:2 - /6'1'530-~7Order Date I 02/22/93 JUL 13 1993

Fabrication Releasel Y York c9ntract No:-2-66~30

Partial Shi~ment: N

York SQ No:Ou-, .1'7, ('193Extactory 8 ip Date: 12/23/93 / sched Ship Date:

Job Name: SILVERADO HIGH SCHOOL

Cust Order Nos 03031-142Location: LAS VEGAS, NV Region: SW c(jCode: 66-729-0000-02-5321-10

District: Phoenix A .SJ-S. GOODHr--t

Sold To Address:

Ship To Address:

QUALITY MECHANICAL

QUALITY MECHANICAL3175 WESTWOOD DR.

C/O SLLVERADO HLGH SCHOOL1650 E. OLETA AVE.LAS VEGAS, NV

89109LAS VEGAS, NV99123

Shi1via: BEST WAY

Markst PO 193031-142Fre qht:"FOB YORK PPD FRGHT ALLOWD

special Shippinq Instructions:

TRUCKER TO ~QUALITY MECHANICAL @ 702/732-2545

48 HOURS PRIO 0 DELIVERY

S"/ () :rV() tJ /17

ItemlEquipment Details

A ~IT TAG: CH-l & CH-2

B BABE UNITs YSDBCBS3-CLA,,­ell Package DBCB

Comp/Motor 83-qL-------------------------------------------------~

Qty. IMLP Ea.

22\..

C.IOPTIONS

EVAPORATOR: " _Marine Water Box for Evaporatorv/-Water Flow SwitCh FS8V"r' .

CONDENSER:

Marine Water Box tor cpndenser~-WAter Flow Switch FS8V~

UNIT OPTIONS: , /Factory Insulation 3/4" ThickV

rorm 1 Shipment (Retriqerant-Charqed)\(-Current Limit & Temp control Reset Interfaces~--------------------------------------------------STARTER AND OPTIONS:

t I SSS-14LA-46~~Unit Mounted Disconnecev -

/CL c Co' 2/,.•'/1-

22

22

222

22

,

msimmons
11
Page 21: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

.'SOO"d

( 6/28/93

G6G6S~ ~09 G~:st £66T-6G-Nnf

YORK INTERNATIONAL FACTORY ORDER FORM PAGE 2 at' 4screwpak8 Versions 12/92

Revision NOI York Order Number: ~2-1",S:3(j-f7Revi8ion Date: Order Dates 02/22/93

Item Equipment Details Qty.MLP Ea. I-EXTENDED MLP FOR STARTER(S)

IEXTENDED HLP FOR UNIT(S) 0MLP FOR SPECIAL FEATURESMLP SUB-TOTAL

SCREWPAK PERFORMANCE SPECIFICATIONSREFRIGERANT:

R-22 -CAPACITYs

365QUANTITY:

2 ,..,FLOW ORIFICE SIZE:

RMOTOR KW I

238 -MOTOR HPs

.3tt:1 ,.., .MOTOR:

460-3-60 /'ISTARTER I York Solid state ~Jv9"-

0IIMOTOR FLA: 340 ,,-I

LRA.2130 .....•I

IN-RUSH I960 -!

AtJK~"eI W A~

-HI 0 :3 ~c:r-CODEPAK OPERATING WEIGHT:

~5eae-1"qIOSHIPMENT FORM:

1 ."..

COOLER

CONDENSER

FLUID

WaterWater -GPM

87!51095EW'l'·F

55.0185.0LWT·F

45.094.40FF

.00025.00025DWP

150.....•150 -PASS

2 .,-2-PD(F'l')

12.220.2NOZZLE IN

7 ,.16 -NOZZLE OUT

8/17 _

TOTAL ORDER MLP FOR STARTERS

TOTAL ORDER MLP FOR UNITSTOTAL ORDER MLP FOR SPECIAL FEATURESTOTAL ORDER MLP

msimmons
msimmons
12
Page 22: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
13
Page 23: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
14
Page 24: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
15
Page 25: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
16
Page 26: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
17
Page 27: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
18
Page 28: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
19
Page 29: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
20
Page 30: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
21
Page 31: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
22
Page 32: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
23
Page 33: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
24
Page 34: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
25
Page 35: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
26
Page 36: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
27
Page 37: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
28
Page 38: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
29
Page 39: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
30
Page 40: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
31
Page 41: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
msimmons
32
Page 42: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

0439 5-061500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699www.onicon.com E-mail: [email protected]

The purpose of this guide is to provide customers and specifying engineers with information about how to choose between ONICON's F-1100 Series Single Turbine Meters vs. F-1200 Series Dual Turbine Meters.

How to choose between F-1100 and F-1200 Series Meters: Choosing between the F-1100 or F-1200 Series is primarily related to the amount of straight pipe run available. The straight pipe run requirement for any flow meter refers to the number of "pipe diameters" required before and after the meter. Pipe size, types of upstream obstructions and application type can also be factors in the choice*.

In a location with enough straight run to provide fully conditioned flow, the F-1100 and F-1200 Series Meters will provide the same level of accuracy. The F-1200 Series Meters maintain accuracy in shorter pipe runs by using two contra-rotating turbines to cancel out the effects of swirl in the flow profile, as well as doubling the velocity sampling area.

Selection Criteria: Consider the selection criteria below when choosing between the single and dual turbine configuration. Please note that ONICON's recommendations on straight pipe requirements are conservative to provide accurate results with "real world" piping conditions. Contact ONICON to discuss applications with less than the recommeded straight pipe run.

ONICON Insertion Turbine Flow MetersSingle Turbine vs. Dual Turbine Selection Criteria

FLOW

Downstream Upstream DiametersDiameters

Flow Meter Location Distance to

previousobstruction

INCORPORATED

F-1100 SeriesSingle Turbine

F-1200 SeriesDual Turbine &FB-1200 Series Bi-directional

• Pipe sizes: Carbon steel - 1.25 inch and larger Copper - 1 inch and larger

• Straight pipe runs of 25 or more pipe diameters • May be suitable with 15 to 25 pipe diameters*

F-1100 SeriesSingle Turbine

Flow Meter

• Pipe sizes: 2½" and larger

• Straight pipe less than 25 pipe diameters*

F-1200 SeriesDual TurbineFlow Meter

• Bi-directional flow application such as a CHW decoupler

• Pipe sizes: 2½" and larger

FB-1200 SeriesBi-directional

Flow Meter

How to determine the availablestraight pipe diameters: For each application, locate the longest straight, unobstructed section of pipe (no bends, tees, valves, other insertion probes, size transitions).

The longest straight pipe run in inches divided by nominal pipe size in inches equals "diameters of straight pipe."

For closed loop applications, consider both the supply and return lines as possible locations.

* Refer to the following pages for additional information about straight pipe recommendations and site selection guidelines: Discussion on Straight Pipe Run Recommendations and/or Flow Meter Site Selection Guidelines

Total Straight Run Required

(most important)

msimmons
33
Page 43: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

What happens inshorter pipe runs?

With ONICON's patented contra-rotating dual turbines, errorcaused by swirl is virtually canceled out, allowing significantlyimproved accuracy when compared to other meter types. For mostinstallations with less than 10 pipe diameters upstream, ourexperience has shown that the dual turbine meter provides accurate, repeatable results. Contact ONICON for installation recommendations on specific applications.

10 pipe diameters upstream, 5 diameters downstream, for themajority of pipe materials and upstream conditions.

Recommendation tomaintain specifiedaccuracies:

What happens inshorter pipe runs?

Recommendation tomaintain specifiedaccuracies:

The error caused by short pipe runs depends on the pipe size, thethe specific type/quantity of obstructions, and their proximity to eachother. Contact ONICON for installation recommendations onspecific applications.

20 pipe diameters upstream, 5 diameters downstream, for themajority of pipe materials and upstream conditions.Will ONICON's single turbine meter perform well using theindustry's standard "10 up/ 5 down" rule? YES, as long as it reallyis the defined "typical" installation with only a single bend upstream and 9 diameters of straight pipe upstream of the bend.

ONICONSingle

TurbineMeter

ONICONDual

TurbineMeter

0299A-1 5-061500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699www.onicon.com E-mail: [email protected]

All flow meter types have a requirement for straight pipe runs upstream and downstream of the meter location to maintain the specified accuracy. This is typically expressed as a number of pipe diameters. There is a standard "10 up / 5 down" rule in the industry that many manufacturers refer to as the "typical" installation. This is a little misleading, due to the fact that this "typical" installation allows for only a single 90 degree bend upstream of the meter location, with 9 or more pipe diameters upstream of the elbow! In reality, these conditions rarely exist in a mechanical room. With multiple obstructions upstream, the "10 up / 5 down" rule simply doesn't work for most insertion meter types.

ONICON Recommendations

ONICON has chosen to make conservative recommendations for straight pipe runs that addressthe majority of piping conditions encountered in typical HVAC applications. Following are ONICON's recommendations, along with a discussion on applications where insufficient straight pipe runs exist:

Discussion on Straight Pipe Run Recommendations

FLOW

Downstream Upstream DiametersDiameters

Flow Meter Location Distance to

previousobstruction

INCORPORATED

msimmons
34
Page 44: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Series F-1100 Single Turbine Flow Meters

GENERAL PRACTICES

1) For best results, install the flow meter in a straight run of pipe,free of bends, tees, valves, transitions, and obstructions, for a dis-tance of 20 pipe diameters upstream and 5 diameters downstream.

2) Longer straight runs may be required in applications where themeter is placed downstream from devices which cause unusualflow profile disruption or swirl, for example, modulating valves ortwo elbows in close proximity and out of plane, etc.

3) If there is insufficient straight run, allow 80% of the run upstreamand 20% of the run downstream. If the total length of straight runis less than 20 diameters, performance may seriously degrade,and consideration should be given to changing to the series F-1200Dual Turbine flow meter.

Minimum upstreamstraight run distance

20 pipe diameters from anyvalve, elbow, fitting, etc.

Minimum downstreamstraight run distance

5 pipe diameters to anyvalve, elbow, fitting, etc.

FLOW DIRECTION

FLOW DIRECTION

Horizontal Run Pipe

Installation in vertical run pipes isalso acceptable

(Meter must always beperpendicular to the pipe)

THIS AREA ACCEPTABLE

Insert meter at any angle to therun pipe in upper 1⁄2 of pipe.

(Meter must always be perpendicular to the pipe)

Series F-1200 Dual Turbine Flow Meters

GENERAL PRACTICES

1) For best results, install the flow meter in a straight run of pipe,free of bends, tees, valves, transitions, and obstructions, for a dis-tance of 10 pipe diameters upstream and 5 diametersdownstream.

2) Longer straight runs may be required in applications where themeter is placed downstream from devices which cause unusualflow profile disruption or swirl, for example, modulating valves ortwo elbows in close proximity and out of plane, etc.

3) If there is insufficient straight run, allow 70% of the run upstreamand 30% of the run downstream. If the total length of straight runis less than 12 diameters, performance may degrade.

Minimum upstreamstraight run distance

10 pipe diameters from anyvalve, elbow, fitting, etc.

Minimum downstreamstraight run distance

5 pipe diameters to anyvalve, elbow, fitting, etc.

FLOW DIRECTION

FLOW DIRECTION

Horizontal Run Pipe

Installation in vertical run pipes isalso acceptable

(Meter must always beperpendicular to the pipe)

THIS AREA ACCEPTABLE

Insert meter at any angle to therun pipe in upper 1⁄2 of pipe.

(Meter must always be perpendicular to the pipe)

MECHANICAL INSTALLATION LAYOUTFOR INSERTION TURBINE FLOW METERS

0299B 5-061500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699www.onicon.com E-mail: [email protected]

INCORPORATED

msimmons
35
Page 45: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

20% 80%

5-06

msimmons
36
Page 46: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

WattNode® Pulse Output kWh Transducer Connection Instructions

for use with HOBO® Energy Logger Pro™

Applies to these WattNode Pulse Output kWh Transducers:

Onset Part No. Configuration / VAC Output WattNode Part No.

T-WNB-3Y-208 Single-phase 120 or

Wye 208-240

Pulses representing kWh WNB-3Y-208-P

T-WNB-3Y-480 Wye 480 Pulses representing kWh WNB-3Y-480-P

T-WNB-3D-240 Delta 208-240 Pulses representing kWh WNB-3D-240-P

T-WNB-3D-480 Delta 480 Pulses representing kWh WNB-3D-480-P

DANGER!—HIGH VOLTAGE HAZARD

© 2005 – 2008 Onset Computer Corporation Manual Part No: MAN-WATTNODE Doc No: 10332-D

Installing transducers in an energized electrical enclosure or on any energized conductor can result in severe injury or death. These transducers are for installation by qualified personnel only. To avoid electrical shock, do not perform any installation or servicing of these transducers unless you are qualified to do so. Disconnect and lock-out all power sources during installation and servicing. Please read transducer user manuals for instructions and use.

This document provides instructions on connecting the WattNode Pulse Output kWh Transducers listed above to the Onset

Part No: S-UCC-M006 Pulse Input Adapter. The Pulse Input Adapter allows a listed WattNode transducer to be used with

the HOBO Energy Logger Pro. Note: For information on connecting the kWh transducer to the power source, and other

transducer details, refer to the WattNode documentation provided by Continental Control Systems.

Required:

WattNode Pulse Output kWh Transducer (Onset Part No. T-WNB-3Y-208 shown)

Selected WattNode Pulse Output kWh Transducer

Appropriately rated Current Transducer(s)

Pulse Input Adapter, Onset Part No: S-UCC-M006*

HOBO Energy Logger Pro, Onset Part No: H22-001

(or HOBO U30 and H21 Series data loggers)

HOBOware®

Pro Software, version 2.2.1 or higher

Configuring the System: See pages 2 and 3 for applicable connection diagram that corresponds to

your electrical power configuration.

Using HOBOware Pro Software: Once the system is configured, the next step will be to launch the H22-001 HOBO Energy Logger Pro using HOBOware Pro

software. See page 4 for an example of utilizing the software’s kWh Data Assistant for plotting logged data.

New WattNode Pulse Output kWh Transducer Features:

The WattNode transducer includes three LEDs—one per phase—for diagnostics and indication of power direction,

low power factor, and correctly installed CTs.

The WattNode transducer provides bidirectional power measurements (positive and negative power). It can be used

for conventional power and energy measurement as well as for net metering and PV applications. *For monitoring

power demand as well as generated power, a second pulse input adapter is required (at output terminal P2).

Note: Refer to the WattNode WNB Series Installation and Operation Manual for details of these features.

msimmons
37
Page 47: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

WattNode Pulse Output kWh Transducer Connection Instructions

Page 2 of 5

LO

AD

Phase A

Phase B

Neutral

LIN

E

Current Transformers

Source Faces

Split-Phase/Single-Phase Three-Wire Connection

WhiteBlack

WhiteBlack

Connect to any open RJ12

jack on the H22-001

White

Black

H22-001

HOBO Energy Logger Pro

S-UCC-M006

Pulse Input Adapter

T-WNB-3Y-xxx

Pulse Output kWh Transducer

Outp

utP3

P2P1COM

A CT

B CT

C CT

Status

Status

Status

N

A

B

C

LO

AD

Phase A

Neutral

LIN

E

Current Transformer

Source Face

H22-001

HOBO Energy Logger Pro

S-UCC-M006

Pulse Input Adapter

T-WNB-3Y-xxx

Pulse Output kWh Transducer

Single-Phase Two-Wire Connection

White

BlackWhite

Black

Connect to any open RJ12

jack on the H22-001

Ou

tpu

tP3P2P1COM

A CT

B CT

C CT

Status

Status

Status

N

A

B

C

msimmons
38
Page 48: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

WattNode Pulse Output kWh Transducer Connection Instructions

Page 3 of 5

LO

AD

Phase A

Phase B

Phase C

Neutral

LIN

E

Current Transformers

Source Faces

Three-Phase Four-Wire Wye Connection

WhiteBlack

WhiteBlack

WhiteBlack

Connect to any open RJ12

jack on the H22-001

White

Black

H22-001

HOBO Energy Logger Pro

S-UCC-M006

Pulse Input Adapter

T-WNB-3Y-xxx

Pulse Output kWh Transducer

Ou

tpu

tP3P2P1COM

A CT

B CT

C CT

Status

Status

Status

N

A

B

C

LO

AD

Phase A

Phase B

Phase C

LIN

E

Current Transformers

Source Faces

Three-Phase Three-Wire Delta Connection

WhiteBlack

WhiteBlack

Connect to any open RJ12

jack on the H22-001

White

Black

H22-001

HOBO Energy Logger Pro

S-UCC-M006

Pulse Input Adapter

T-WNB-3D-xxx

Pulse Output kWh Transducer

Outp

utP3

P2P1COM

A CT

B CT

C CT

N

A

B

C

WhiteBlack Status

Status

Status

msimmons
39
Page 49: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

WattNode Pulse Output kWh Transducer Connection Instructions

Page 4 of 5

Using HOBOware Pro Software: If not already done, insert the HOBOware Pro CD into your computer’s CD-ROM drive and follow the prompts to install the

software. Download any updates if so indicated. HOBOware Pro includes a kWh Data Assistant that allows you to view the logged

data plotted in appropriate kWh engineering units. Below is an example configuration showing how easy it is to select and

configure the kWh Data Assistant. Note: For detailed information on all of HOBOware’s Pro’s features, such as launching loggers

and reading out logged data, use the online help or refer to the “HOBOware Pro User’s Guide.” You can find the “HOBOware Pro User’s Guide” on your installation CD, or visit www.onsetcomp.com and navigate to the software manual area.

1. After reading out and saving the logged data, the “Plot Setup”

window appears. All available data assistants that are used with the

S-UCC-M006 Pulse Input Adapter are listed in the “DataAssistants” area near the bottom of the window. Click “kWH

Assistant” to select it and then click “Process…” to bring up the

assistant.

2. In the “kWh Assistant” window, select the model number* of

the WattNode energy transducer being used, the current transformer

(CT) size used (in Amps), and the output series to be plotted. Series

choices include: Energy Used per interval (in kWh), Average Power

per interval (in kW), and Usage Cost.

* Depending on the version of HOBOware Pro being used, WattNode

model number choices may only include those beginning with T-

WNA. If this is the case, and you are using a T-WNB model, then just

select the equivalent ‘A’ model. For example, select T-WNA-3Y-208

for a T-WNB-3Y-208 model.

Type in location name here

Tip: To identify the data series once the logger is read out

and the data plotted, remember to add a unique location

name of your choice when you are in the logger’s

Launch window. To do this, first click on “Pulse

Adapter (S-UCC-MXXX)” in the “Channels to Log”

area, then on “1. Counts.” Next, click “SetLocation…” to bring up the “Set Channel Location”

window. Type in location name and click “OK.”

msimmons
40
Page 50: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

WattNode Pulse Output kWh Transducer Connection Instructions

Page 5 of 5

Service and Support

HOBO products are easy to use and reliable. In the unlikely event that you

have a problem with this instrument, contact the company where you bought

the logger: Onset or an Onset Authorized Dealer. Before calling, you can

evaluate and often solve the problem if you write down the events that led to

the problem (are you doing anything differently?) and if you visit the

Technical Support section of the Onset web site at

www.onsetcomp.com/support.html. When contacting Onset, ask for technical

support and be prepared to provide the product number and serial number for

the logger and software version in question. Also completely describe the

problem or question. The more information you provide, the faster and more

accurately we will be able to respond.

Onset Computer Corporation

470 MacArthur Blvd., Bourne, MA 02532

Mailing: PO Box 3450, Pocasset, MA 02559-3450

Phone: 1-800-LOGGERS (1-800-564-4377) or 508-759-9500

Fax: 508-759-9100

E-mail: [email protected]

Internet: www.onsetcomp.com

Warranty

Onset Computer Corporation (Onset) is acting as a distributor of the sensor(s)

or transducer(s) described in this document. Onset hereby transfers to the

original end-user purchaser the warranty provided by the product manufacturer

(one year from the date of original purchase). During the warranty period

Onset will, at its option, either repair or replace products that prove to be

defective in material or workmanship. This warranty shall terminate and be of

no further effect at the time the product is (1) damaged by extraneous cause

such as fire, water, lightning, etc. or not maintained in accordance with the

accompanying documentation; (2) modified; (3) improperly installed; (4)

repaired by someone other than Onset; or (5) used in a manner or purpose for

which the product was not intended.

THERE ARE NO WARRANTIES BEYOND THE EXPRESSED

WARRANTY ABOVE. IN NO EVENT SHALL ONSET BE LIABLE

FOR LOSS OF PROFITS OR INDIRECT, CONSEQUENTIAL,

INCIDENTAL, SPECIAL OR OTHER SIMILAR DAMAGES ARISING

OUT OF ANY BREACH OF THIS CONTRACT OR OBLIGATIONS

UNDER THIS CONTRACT, INCLUDING BREACH OF WARRANTY,

NEGLIGENCE, STRICT LIABILITY, OR ANY OTHER LEGAL

THEORY.

Limitation of Liability. The Purchaser's sole remedy and the limit of Onset's

liability for any loss whatsoever shall not exceed the Purchaser's price of the

product(s). The determination of suitability of products to the specific needs of

the Purchaser is solely the Purchaser's responsibility. THERE ARE NO

WARRANTIES BEYOND THE EXPRESSED WARRANTY OFFERED

WITH THIS PRODUCT. EXCEPT AS SPECIFICALLY PROVIDED IN

THIS DOCUMENT, THERE ARE NO OTHER WARRANTIES

EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO, ANY

IMPLIED WARRANTIES OF MERCHANTIBILITY OR FITNESS

FOR A PARTICULAR PURPOSE. NO INFORMATION OR ADVICE

GIVEN BY ONSET, ITS AGENTS OR EMPLOYEES SHALL CREATE

A WARRANTY OR IN ANY WAY INCREASE THE SCOPE OF THE

EXPRESSED WARRANTY OFFERED WITH THIS PRODUCT.

Indemnification. Products supplied by Onset are not designed, intended, or

authorized for use as components intended for surgical implant or ingestion

into the body or other applications involving life-support, or for any

application in which the failure of the Onset-supplied product could create or

contribute to a situation where personal injury or death may occur. Products

supplied by Onset are not designed, intended, or authorized for use in or with

any nuclear installation or activity. Products supplied by Onset are not

designed, intended, or authorized for use in any aeronautical or related

application. Should any Onset-supplied product or equipment be used in any

application involving surgical implant or ingestion, life-support, or where

failure of the product could lead to personal injury or death, or should any

Onset-supplied product or equipment be used in or with any nuclear

installation or activity, or in or with any aeronautical or related application or

activity, Purchaser will indemnify Onset and hold Onset harmless from any

liability or damage whatsoever arising out of the use of the product and/or

equipment in such manner.

Returns

Please direct all warranty claims and repair requests to place of purchase.

Before returning a failed unit directly to Onset, you must obtain a Return

Merchandise Authorization (RMA) number from Onset. You must provide

proof that you purchased the Onset product(s) directly from Onset (purchase

order number or Onset invoice number). Onset will issue an RMA number that

is valid for 30 days. You must ship the product(s), properly packaged against

further damage, to Onset (at your expense) with the RMA number marked

clearly on the outside of the package. Onset is not responsible for any package

that is returned without a valid RMA number or for the loss of the package by

any shipping company. Loggers must be clean before they are sent back to

Onset or they may be returned to you.

Repair Policy

Products that are returned after the warranty period or are damaged by the

customer as specified in the warranty provisions can be returned to Onset with

a valid RMA number for evaluation.

© 2005 – 2008 Onset Computer Corporation. All rights reserved.

Manual Part No: MAN-WATTNODE

Doc No: 10332-D

Onset, HOBO, and HOBOware are registered trademarks and Energy Logger Pro is a trademark of Onset Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners.

msimmons
41
Page 51: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Resumen de resultados cámaras de conservación y refrigeración Hotel Hyatt Regency Mérida

Septiembre 2006

Atención: Ing. Federico Salgado, Gerencia de Mantenimiento Hotel Hyatt Regency Mérida

TABLA DE AHORRO CAMARA 5

HYATT REGENCY MERIDA MONTLY CONSUPTION RATE COST ENERGY DEMAND ENERGY DEMAND TOTAL BASE INTERL PEAK BASE INTERL PEAK BASE INTERL PEAK Costo/dia ANTES MAXR 480 718 121 5 5 5 296.93 539.38 295.51 683.60 1815.42 60.51 POST MAXR 347 520 87 4 4 4 214.96 390.47 213.92 546.88 1366.22 45.54 AHORRO 449.20

RATES: SEPTIEMBRE KWH BASE 0.62 pesos KWH INTERL 0.75 pesos KWH PEAK 2.45 pesos DEMAND 137 pesos

AHORRO 449.20 IVA 67.38 516.58 DAP 25.83

GRAN TOTAL 542.41

AHORRO SIN IVA 475.03 INVERSION 605.00

TRS 1.27 meses

En base a las mediciones realizadas, se proyecto el comportamiento de la cámara en su operación diaria para calcular su costo de operación mensual antes y después de la aplicación de MaxR 100, con un costo de 55 usd por onza y un tipo de cambio de 11 pesos mexicanos por dólar estadounidense. Encontramos que el equipo ahorro un 25% de su costo de consumo energético, lo que , además de ser un gran ahorro en cuanto a su costo de operación, también permite suponer la extensión de la vida útil del equipo. La metodología de la prueba se realizó como explicamos a continuación: Se instalaron equipos de medición en la unidad y en la cámara de conservación. Estos equipos midieron durante varios días el consumo de energía de la unidad.A estos resultados les hemos llamado resultados “PRE”. Al término de esta fase, se le aplicaron 1 onza de MAXR a la unidad. Se dejaron transcurrir más de 15 días y se realizaron mediciones nuevamente, instalando nuevamente los equipos durante el mismo tiempo y los mismos días de la semana para representar las mismas circunstancias de operación. A estas mediciones se les denominó “POST”.

Page 52: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Las siguientes gráficas muestran el comportamiento de la unidad según los resultados obtenidos en las mediciones.

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

Resumen consumo de KWH

PRE MAX RPOST MAXR

Resumen consumo de KWH PRE MAX R 14.65 Kwh POST MAXR 10.61 Kwh

Responsables del Reporte Lic. Epifanio Sánchez Cabral Ing. Jorge García Valladares Grupo Energético Mexicano

Page 53: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Ove Summary of results: Storage and Cooling chambers(cameras)

Lattia!, Rancho Kankabchen November 2006

Attention: Ing. Alberto Barbosa, Service chief, Bepensa Industrial, Mérida, Yucatán, México.

1) OBJECTIVE.- Determine the Energy savings reached by the refrigeration units after being

treated by Grupo Energético Mexicano using the measurement methodology according to the ASHRAE Standard 37-1988 norms.

2) SETTING.- 2 FRIGUS devices in good conditions, feeding a storage Camera, which presented the following values before being treated:

Results Table “PRE”

Maximum Temperature 9.806 °C, Registered at 7:54 AM on 12/09/2006 Minimum Temperature -2.595°C Registered at 1:22AM on 13/09/2006 Average Temperature 2.961 °C (Results measured from the 11th to the 13th of Sept. of 2006). Daily Energy Consumption: 126.46 KWH (Results measured from the 11th to the 13th of Sept. of 2006).

3) DEVELOPMENT OF THE TEST.- Devices to measure Energy were installed in the unit and in the maintenance camera from the 11th to the 13th of Sept. of 2006. We have called this results “PRE” By the end of this phase, 2 oz. of MAXR were installed to each unit. After 50 days, measures were repeated, installing the devices during the same time and days, to have equal operation circumstances. These measures were called “POST”.

4) RESULTS / CONCLUSIONS.-

A Decrease in the consumption of kwh of 49.82% (126.46 pre V.S. 63.46 post).

The real annual savings of the Camera from NOV 06 will be of $21,102.84 without

considering the monthly increase (4%) in electricity tariffs.

The Camera’s temperature had positive variations:

Its new average temperature is -1.877°C, 4.83°C less than in the “Pre” period.

The minimum temperature reached in the “Post” period was -8.940 °C, 6.34°C lower than

the minimum temperature registered in the “Pre” period.

Page 54: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Results Table “POST”

Maximum Temperature 9.060 °C, Registered at 7:54 AM on 12/09/2006 Minimum Temperature -8.940°C Registered at 1:22AM on 13/09/2006 Average Temperature -1.877 °C (Results measured from the 11th to the 13th of Sept. of 2006). Daily Energy Consumption: 63.46 KWH (Results measured from the 11th to the 13th of Sept. of 2006).

After the explanation of our products and the obtainment of results, we can say that

the savings on Lattia’s devices will help the company to:

1) Save $21,102.84 pesos in one year, due to the energy savings in the devices of the

storage Camera.

2) The unit generates better temperatures, with less effort and lower cost.

3) An important increase in the useful life of the units.

4) In case of investing in this application (proposed by Grupo Energético Mexicano) the pay-back will be in 1.26 months. ($1,758.03 savings against $2,200.00 investment).

We can conclude that the project’s objective of saving energy has been accomplished.

5) GRAPHICS AND ANNEXES Consumption and Cost Table, based on November’s tariff (CFE) CONSUMPTION COST

ENERGY DEMAND ENERGY DEMAND TOTAL Cost/ day

BEFORE MAXR 3,763.86 11.00 $3,346.07 $1,421.75 $4,767.82 $158.93

POST MAXR 1,903.90 11.00 $1,692.57 $1,421.75 $3,114.32 $103.81

SAVINGS $ 1,653.50

SAVINGS $ 1,653.50

IVA $ 248.02

SUBTOTAL $ 1,901.52

DAP $ 95.08

TOTAL $ 1,996.60

SAVINGS WITHOUT IVA $1,758.57

Page 55: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

INVESTMENT $2,200.00

TRS 1.26 MONTHS

Daily Consumption of KWH

PRE MAX R 126.46 Kwh

POST MAXR 63.46 Kwh

KWH CONSUMPTION DURING THE MEASSUREMENT PERIOD

PERIODS

CONSUMPTION

Page 56: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

TEMPERATURE BEHAVIOR IN THE CAMERA

Page 57: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS
Page 58: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

*Technical Report*

Casino/Hotel Refrigerated Food Service Cooler

Background: Computerized monitoring was conducted on a food service cooler at the Luxor, a Las Vegas casino/hotel in March of 2001. This cooler provides refrigeration for a portion of the restaurant and food services department. The unit was a double door walk-in unit, three ton refrigeration capacity, using freon refrigerant gas.

Test Procedure:Baseline data was recorded for over two days in order to establish current operating data of the unit. The operating schedule has a built-in 30 minute de-frost cycle every 12 hours.

The additive was introduced into the refrigerant gas flow, carried throughout the system, blending with the refrigerant oil and treating all exposed metal surfaces.Computer monitoring was continued for an additional three days after introduction of additive. Computer data was analyzed to determine the effect of the treatment.

Results:Baseline data shows that the system compressor operates essentially at all times other than the two scheduled half hour periods daily for defrost. Over a 24 hour day, the compressor was off for only 30 minutes (circa), having reached its thermostat set point. (See Figure 1. following page)

Subsequent recorded data shows that over a 10 hour period, the refrigeration system, before the MAXR 100 treatment, was running nearly 97% (circa) of the time, because the thermostat set point was rarely ever attained. However, after the MAXR 100 treatment, the refrigeration system was running only 65% (circa) of the time, because the thermostat set point was attained regularly. (See Figure 2. following page)

Additional 1 hour periods have been a monitored during heavy use times, where therefrigeration system, after the MAXR 100 treatment, was able to shut down for over 40% of the time. (See Figure 3. following page)

Assessment:Significant savings were recorded after introduction of MAXR 100 due to the increased efficiency of the refrigeration system's heat exchangers. Prior to thetreatment, the unit was rarely able to attain set point which would allow the compressor to shut off. After treatment, the set point of the system was attained 30-40 percent of the time, resulting in significant savings in energy and mechanical wear.

STRATHMORE HOLDINGS L.L.C. energy efficient technologies!

Page 59: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

0 24hours hours

126 18

Compressor Baseline Data (24 hour period)

Key: = compressor running

(Fig. 1)

= scheduled defrost downtime

0 10hours hours

42 6

Compressor Run Time Comparison (10 hour period)

Key: - compressor running time before MAXR 100 treatment= 97% of time.

(Fig. 2)

- compressor running time after MAXR 100 treatment= 65% of time.

= compressor off

8

0 10hours hours

42 6 8

0 60minutes minutes

Compressor Run Time (1 hour period)

Key: - compressor running time after MAXR 100 treatment= 60% (40% savings)

30 40 5010 20

(Fig. 3)

STRATHMORE HOLDINGS L.L .C. energy efficent technologies!

Page 60: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

RESTORES, RECONDTIONS AND MAINTAINS THEEFFICIENCY OF A 23 YEAR OLD

AIR CONDITIONING UNIT

METROPOLITAN WASHINGTON COUNCIL of GOVERNMENTS ENERGY ADVISORY GROUP

WASHINGTON, D.C.

EFFICIENCY TEST

1

Page 61: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Onset Energy Monitor

Data collectionOne minute intervals anddown loaded to Onset Computer server everytwo hours

Space thermostat set at 74 Degree F

2

HOBO U30 Remote Monitoring Systems analyzed the efficiency of rooftop HVAC unit

performance. These state-of-the-art systems provide industrial-grade reliability with real-time

access to your data via the Internet.

Page 62: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Hierarchy of Efficiency

•Equipment benchmarked

• Increased kW /ton

•Poor heat transfer

•Longer run hours

•Lower thermostat settings

•Higher Decibel Levels

Phase 1

• Installation of MaxR 100

• Integration period

•Removal of oil fouling factor

• Inter-metallic Bonding

• Increase in kW/ton

•Lower Decibel Levels

Phase 2 •Lower kW /ton

• Improved Efficiency

•Latent heat BTUH increased

•Total BTUH increased

•Higher thermostat settings

•Plaque and varnish continues to be removed

Phase 3

3

Page 63: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Mechanical Reconditioning

•35,489 BTUH

•EER 6.0

•COP 1.7

•Average kW/ton 3.2

•Decibels “C” scale 93.009 average

Phase 1

•37,355 BTUH

•EER 6.2

•COP 1.9

•Average kW/ton 3.3

•Decibels “C” scale 87.306 average

Phase 2 •41,443 BTUH

•EER 6.8

•COP 2.0

•Average kW/ton 2.5

•Decibels “C” scale 86.715 average

Phase 3

4

Page 64: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

MaxR increased Efficiency

Average BTU/Hr increased efficiency

16.8%

Average increase in the EER

13.54%

Average increase in COP

13.54%

Average Reduction in kW/ton

19.88%

Return on Investment

One cooling season

5

Page 65: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

Life Cycle EfficiencyOriginal Air Conditioning

Equipment’s design specification

First year operation loss of 7% efficiency*. Due to the oil

fouling factor and lower heat transfer

Second year operation loss of 5% efficiency*. 1% loss* per

year continues due to oil fouling.

Installation of MaxR 100 inter-metallic compound removes oil

fouling , lacquer and plaque. Reconditioning

Improvements to thermal heat transfer and operating

efficiency.

Restoration and maintaining of equipment

6* ASHRAE

Page 66: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

1

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

Date: 18th September 2017

ENERGY SAVINGS REPORT WITH MAXR100 AT DIAMOND TOWER 5, DUBAI

SKM MAKE 190 TR, MODEL – APCS 5190Y.

a) Data Logger Installed on : 5th July 2017, @ 12.49 PM b) Pre installation Data recording starting date & Time : 5th July 2017 at 12.49 PM c) Pre Data Recording ending date & Time : 19th July 2017 at 11.34 AM d) MAXR100 installed on : 24th July 2017. e) Post MAXR100 data Recording Starting and Ending Dates : 4th September 17 to 10th September,17

Page 67: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

2

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

A) PRE MAXR100 Installation Data – Summary

SR.NO DATE TRH

Average Values Temperatures in Deg C

VLL VLN AMPS KW KWH PF AMB Chiller Condenser

Set Point IN OUT IN OUT

1 05-07-2017 11.00 401.11 231.5 375.3 228.7 2511.47 0.876 44.20 10.91 8.57 42.4 43.9 7.78

2 06-07-2017 23.75 402.90 232.6 362.8 220.4 5225.00 0.870 43.53 10.49 8.14 45.4 46.5 7.78

3 07-07-2017 23.75 400.40 231.2 366.6 225.5 5220.00 0.876 47.10 11.96 10.17 46.88 49.07 7.78

4 08-07-2017 12.50 403.90 233.2 415.4 254.2 3248.00 0.876 47.91 11.44 8.02 48.67 50.67 7.78

5 18-07-2017 23.75 399.94 230.9 383.8 231.3 5490.00 0.869 48.66 11.05 9.18 48.16 49.75 7.78

6 18-07-2017 11.50 400.40 231.1 328.6 196.7 2250.00 0.863 45.60 11.28 9.86 50.05 51.25 7.78

Total 106.25 23944.47 Average For

Bench marking 401.4 231.8 372 226.13 225.36 0.87 46.17 11.2 9 47 49 7.78

Page 68: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

3

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

MAXR100 INSTALLED ON 24th July 2017

Page 69: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

4

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

Important Note: On 28th July we were informed that the motors of the chiller burnt out and by the time our personnel

arrived at site the maintenance team dismantled the motors and oil has been drained out. The oil quality of ONE

compressor has turned black as shown in the pictures A & B.

PIC – A PIC - B

Page 70: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

5

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

CHILLER MOTOR REMOVED ON 28th July 2017

Page 71: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

6

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

Note: The rewound motors re installed on 20th August, 2017 and we installed data logger again on 21st August, 2017. As the lube oil of

two compressors removed during the dismantling of burnt out motors, and they have mixed the oil of the both compressors. With

MAXR100 the compressors have run only for 4 days till these motors failed hence, we let the run the compressors for 14 days and the

POST MAXR100 installation data recorded from 4th September, 2017 to 10th September, 2017.

II) POST MAXR100 Installation – Summary

SR.NO DATE TRH

Average Values Temperatures in Deg C

VLL VLN AMPS KW KWH PF AMB IN Deg C

Chiller Condenser SET POINT INLET OUTLET INLET OUTLET

1 04-09-17 23.75 402.2 232.2 338.8 203.1 4809.00 0.983

2 05-09-17 23.75 402.2 232.4 358.3 215.8 4582.00 0.983 46.00 11.43 9.30 47.35 48.52 7.8

3 06-09-17 23.75 404.3 233.4 392.0 238.1 4520.00 0.984 46.00 11.43 9.37 47.70 51.62 7.8

4 07-09-17 23.75 401.3 231.7 375.0 227.3 4622.00 0.984 45.70 11.37 9.37 48.20 51.05 7.8

5 08-09-17 23.75 400.7 231.3 384.2 232.3 4653.00 0.984 46.26 11.43 9.63 47.35 49.50 7.8

6 09-09-17 23.75 402.6 232.4 392.6 237.7 4784.00 0.984 45.70 11.42 9.30 47.70 51.62 7.8

7 10-09-17 23.75 402.3 232.2 397.3 241.0 4732.68 0.984 46.04 11.43 9.32 47.35 49.50 7.8

Total 166.3 32703

Average 402 232.2 376.9 227.9 196.71 0.983 46.00 11.4 9.4 47.61 50.3 7.8

Page 72: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

7

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

III) Summary of pre & post data:

DATES TRH VLL VLN AMPS KW KWH/HOUR PF AMB Chiller Condenser

SET POINT IN OUT IN OUT

PRE 5/7/17 to 18/7/17 106.25 401.4 231.8 372.0 226.13 225.36 0.870 46.17 11.2 9.00 47.00 49.0 7.8

POST 4/9/17 to 10/9/17 166.30 402.2 232.2 376.88 22.9 196.70 0..983 46.00 11.4 9.38 47.61 50.3 7.8

Page 73: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

8

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

D) Comparison of PRE & POST data:

SR.NO Parameters Pre Post

1 Total Running Hours 106.25 166.3

2 Total Energy Consumption in KWH 23944.47 32702.7

3 Average Energy Consumption in kwh/Hour 225.36 196.7

4 Average Voltages ( VLL) 401.4 402.2

5 Average Voltages ( VLN) 231.8 232.2

6 Average Current in Amps 372 376.88

7 Average Load in KW/ Hour 226.13 227.9

8 Average PF 0.87 0.983

9 Average Ambient Temperature in Deg C 46.17 46

10 Average Chiller Temperatures in Deg C (INLET) 11.2 11.4

11 Average Chiller Temperatures in Deg C ( OUTLET) 9 9.38

12 Average Condenser temperature in Deg C ( INLET) 47 47.61

13 Average Condenser temperature in Deg C ( OUTLET) 49 50.3

14 Average Set Point in Deg C 7.8 7.9

Page 74: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

9

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

E) CONCLUSION:

A) Energy Savings IN kWh/ Hour with MAXR100

a. Average Energy Consumption in KWH/ Hour without MAXR100 : 225.36 KWH

b. Average Energy Consumption in KWH/Hour with MAXR100 : 196.70 KWH

c. Improvement in kWh/ Hour : 28.66 Kwh

d. Energy Savings with MAXR100 IN % : (28.66/225.36) x 100 = 12.125 %

A) Energy Saving in kwh/KW with MAXR100

a) Pre installation Average energy consumption / KW in KWH : 225.36/226.13 = 0.99659 KWH b) Post installation Average Energy Consumption/ KW in KWH : 196.71/ 227.9 = 0.86314 KWH c) % of Improvement with MAXR100 : 0.99659 – 0.86314 = 0.13345

(0.12245/0.99659) X 100 = 13.339 %

Page 75: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

1

Date: 18th October 2017

ENERGY SAVINGS REPORT OF CARRIER MAKE 15 TR ROOF TOP PACKAGED SYSTEM-

NABORS DRILLING INTERNATIONAL GULF FZE

a. Data Logger Installed on : 17th September 2017 b. Data Recording ending date : 25th September 2017 c. MaxR100 installed on : 27th September 2017 d. Post MaxR100 installation data : 11th October to 16th October, 2017

Page 76: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

2

I) Pre – Installation Data day wise Summary

Sr.No DATE TRH Average Figures Average Temp In Deg C

VLL VLN AMPS KW KWH PF AMB SET POINT

1 17-09-2017 3.75 409 236.1 30.7 16.67 45.60 0.766 38.1

23.889

2 18-09-2017

5.75 406.3 234.6 24.56 13.15 75.60 0.761

49.85 2.50 406.8 234.9 24.12 12.8 32.00 0.759

13.25 404.1 232.1 27.2 14.96 199.30 0.79

3 19-09-2016

6.25 411.1 237.4 24.81 13.23 92.70 0.75

44.66 1.00 409.1 236.2 24.12 12.67 12.60 0.742

13.75 401.9 232 27.86 15.33 214.30 0.746

4 20-09-2017 8.50 405.7 234.2 24.5 13.11 115.50 0.763

45.11 14.25 403.4 232.9 25.49 13.81 213.30 0.764

5 21-09-2017

8.00 408.3 235.7 24.7 13.22 105.90 0.758

42.36 1.25 409.9 236.6 24.11 12.6 15.80 0.74

10.25 405.5 237.6 26.97 14.92 152.70 0.788

6 22-09-2017 1.25 411.5 237.6 24.18 12.59 15.80 0.731

42.13 11 405.3 234 25.88 14.28 157.60 0.788

7 23-09-2017

1.00 407.8 235.4 25.18 13.6 13.70 0.767

45.88

1.00 408.3 235.8 24.77 13.22 13.40 0.757

0.75 410.8 237.2 24.17 12.94 9.70 0.744

0.50 412.4 238 24.22 12.64 6.40 0.734

1.25 410.7 237.1 24.33 12.82 16.10 0.743

11.25 405.5 234.1 25.97 14.35 161.80 0.788

Page 77: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

3

8 24-09-2017

1.5 408.5 236 25.16 13.67 20.50 0.761

43.66

1.00 406.6 234.2 24.62 13.2 13.20 0.762

0.75 409.3 236.3 24.45 12.99 9.80 0.751

1.00 409.1 236.2 24.17 12.71 12.70 0.745

14.00 406.5 234.7 27.99 15.17 211.60 0.781

3.00 409.7 236.5 26.8 13.56 40.10 0.763

Total 137.75 1977.70

Average 407.8 235.5 25.42 13.62 14.3572 0.759 43.96 23.889

II) Post MAXR100 Installation day wise data Summary

SR.NO DATE TRH Average Values Total

KWH PF

Ave.Temp. In D.C

VLL VLN AMPS KW AMB SET POINT

1 11-10-2017 23.75 407.3 235.1 24.09 12.81 303.2 0.739 43.50 23.889

2 12-10-2017 23.75 407.7 235.4 24.12 12.84 302.4 0.744 42.00 23.889

3 13-10-2017 23.75 412.7 238.3 22.77 12.00 283.9 0.711 42.00 23.889

4 14-10-2017 23.75 414.2 239.1 21.97 11.45 270.7 0.672 42.00 23.889

5 15-10-2017 23.75 410.7 237.1 18.86 9.861 235.2 0.669 41.20 23.889

6 16-10-2017 21.25 412.5 238.1 20.55 10.74 219.5 0.692 40.00 23.889

Total 140 1615 23.889

Average 410.9 237.2 22.06 11.61 11.54 0.704 41.78 23.889

Page 78: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

4

III) Summary – PRE & POST data:

Sr.No Parameters Pre Post

1 Total Running Hours 135.5 140

2 Total Energy Consumption in KWH 1977.7 1615

3 Average Energy Consumption/ Hour in KWH 14.596 11.536

4 Average current in Amps 25.42 22.06

5 Average Load in KW 13.62 11.61

6 Average Voltage - VLL 407.8 410.9

7 Average Voltage - VLN 235.5 237.2

8 Average Ambient temperature IN Deg C 43.96 41.78

9 Average inside temperature in Deg C 23.999 23.889

Page 79: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

5

IV) Energy Savings & Reduction of Current with MAXR100

a) Reduction in KWH/Hour

Average Energy Consumption in KWH/ Hour without MAXR100 : 14.596 KWH Average Energy Consumption in KWH/Hour with MAXR100 : 11.536 KWH Improvement in kWh/ Hour : 3.06 Kwh Energy Savings with MAXR100 IN % : (3.06/11.536)x 100 = 20.96 %

b) Reduction in Current

Average Current in Amps Pre : 25.42 Amps Average Current in Amps (Post) : 22.06 Amps Improvement in Amps : 3.36 Amps Improvement % in Current (Amps) : (3.36/25.42) x 100 = 13.21 %

Page 80: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

6

V) Actual Energy Savings Considering the change in average Ambient Temperatures post MAXR100 installation period.

For calculating the actual savings we need to consider the change in ambient temperatures of pre data period with

the post data period, which is 2.5 Deg C. Any decrease in the ambient temperature will affect the energy consumption of the AC unit. Hence for calculating the actual savings we need to consider COP- Coefficient of Performance principle which is most commonly used method.

COP- is the ratio of heat removed from a system to the energy required to remove the heat. The theoretical maximum is equal to the coldest temperatures of the refrigerant divided by the difference between its coldest and hottest temperatures are expressed in Kelvins. Even the perfect system decreases efficiency with increased outside temperatures, dropping about 2% per Deg C.

Considering 2.18 Deg C decrease in the ambient Temperatures for the post MAXR 100 installation period the

energy consumption has to be INCREASED by 4.36 % during the period.

Page 81: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

7

Considering the above we have calculated the actual energy consumption during the post MAXR100 installation period. Total Energy consumption in KWH : 1615 KWH Increase in Energy consumption due to decrease in ambient temperature : 4.36 % Actual Energy Consumption in KWH : (1814 x 4.36)/100 = 70.4 KWH

1615.00 + 70.4 = 1685.4 kWh

Actual average Energy Consumption / Hour on kWh : 1685.4/140 = 12.03 kWh/Hour Actual % of Energy Savings with MAXR100 : (14.596 – 12.03 ) = 2.566 kwh

(2.566/14.596) x 100 = 17.58 %

Page 82: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

UNITED GLOBAL L.L.C

Authorized Exclusive Distributors for

UNITED GLOBAL L.L.C, P.O. Box No. 2861, Postal Code- 112, MUSCAT, Sultanate Of Oman. Tel: (968) 2481 6080

Date: 17th August, 2017

ENERGY SAVINGS REPORT OF ARMSTRONG MAKE 5.0 TR AC PACKAGED BINSALIM PLANT, MUSCAT

MODEL – SB601SC-F

a) Data Logger Installed on for pre installation data : 30th July 2017 to 2nd August 2017 b) MaxR 100 Installed on : 2nd August 2017 @ 12.30 PM c) Post maxr100 installation data recorded from : 14th August 2017 to 17th August 2017 d) Type of Refrigerant : R-22 e) Type of Maxr100 used : MAXR100 MO f) Quantity of MAXR100 used for One compressor : 05 Oz

Page 83: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

UNITED GLOBAL L.L.C

Authorized Exclusive Distributors for

UNITED GLOBAL L.L.C, P.O. Box No. 2861, Postal Code- 112, MUSCAT, Sultanate Of Oman. Tel: (968) 2481 6080

I) Pre Installation data

SR.NO DATS TRH VLL VLN AMPS KW KWH PF AMB in Deg.C Inside Temp Deg C

1 30-07-2017 3.5 344.7 276.7 7.75 6.278 21.97 0.974 37.3 24

2 31-07-2017 9.0 344.2 276.3 7.9 6.372 57.43 0.974 37.3 24

3 01-08-2017 9.5 346.8 275.9 8.11 6.508 61.78 0.972 38.4 24

4 02-08-2017 1.0 343.5 275.7 8.21 6.557 6.579 0.972 38.0 24

Total 23.0

147.8 Average

344.8 276.2 7.99 6.428 6.424 0.973 37.75 24

II) Post MAXR100 installation and post 14 days clean up data

SR.NO DATS TRH VLL VLN AMPS KW KWH PF AMB in Deg C Inside Temp Deg C

1 14-08-2017 6.25 435 251 7.7 4.88 30.56 0.988 36.11 24.00

2 15-08-2017 8.5 432 249 7.69 4.835 41.17 0.988 36.11 24.00

3 16-08-2018 8.75 433 250 7.67 4.825 42.18 0.988 36.11 24.00

4 17-08-2017 1.75 431 249 8.01 5.088 8.93 0.989 36.11 24.00

Total 25.25

122.8 Average

432.8 249.8 7.767 4.907 4.865 0.988 36.11 24.00

Page 84: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

UNITED GLOBAL L.L.C

Authorized Exclusive Distributors for

UNITED GLOBAL L.L.C, P.O. Box No. 2861, Postal Code- 112, MUSCAT, Sultanate Of Oman. Tel: (968) 2481 6080

III) Summary of Pre & Post Data

SR.NO Date TRH VLL VLN AMPS KW KWH/Hr AMB Temp in Deg C INSIDE Temp in Deg C

1 PRE 30/717 to 2/8/17 23.00 344.8 276.2 7.99 6.428 6.424 37.75 24.00

2 POST 14/8/17 to17/8/17 25.25 432.8 249.8 7.767 4.907 4.865 36.11 24.00

IV) Summary- Comparison of pre & Post data:

Sr.No Parameters Pre Post

1 Total Running Hours 23.00 25.25

2 Total Energy Consumption in KWH 147.8 122.8

3 Average Energy Consumption/ Hour in KWH 6.424 4.865

4 Average current in Amps 7.99 7.767

5 Average Load in KW 6.428 4.907

6 Average Voltage - VLL 344.8 432.8

7 Average Voltage - VLN 276.2 249.8

8 Average Ambient temperature IN Deg C 37.75 36.11

9 Average inside temperature in Deg C 24.00 24.00

Page 85: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

UNITED GLOBAL L.L.C

Authorized Exclusive Distributors for

UNITED GLOBAL L.L.C, P.O. Box No. 2861, Postal Code- 112, MUSCAT, Sultanate Of Oman. Tel: (968) 2481 6080

V) Energy Savings with MAXR100

Average Energy Consumption in KWH/ Hour without MAXR100 : 6.424 KWH Average Energy Consumption in KWH/Hour with MAXR100 : 4.865 KWH Improvement in kWh/ Hour : 1.559 Kwh Energy Savings with MAXR100 IN % : (1.559/6.424) x 100 = 24.268 %

Page 86: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

1

Report No.AI/GENPACT/18- 19/001- FINAL Date: 30th August, 2018

ENERGY SAVINGS REPORT (Total 11 Pages)

1. Client : GENPACT INDIA PVT LIMITED

Survey No.1, Uppal Kancha Village Opp. NGRI, Adj. Jeevan Foods, IDA – Uppal Habsiguda, Uppal, Hyderabad 500039

2. Location of Equipment : Uppal, Hyderabad

3. Equipment Details : TRANE MAKE, 400 TR CHILLER Model CVGF400. 4. Serial Number of Chillers : L02012375

5. Refrigerant : R134A

6. Pre Installation Data Recording Duration : 29/3/18 to 07/04/2018 7. Post Data Recording duration : 24/08/2018 to 29/08/2018

Page 87: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

2

A) TRANE MAKE 400 TR WATER COOLLED CHILLERS. Sr. No. L0201237

Page 88: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

3

B) Data Logger Installation recording the data

Page 89: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

4

C) Pre installation Data of TRANE make 400 TR water Cooled Chillers Sr.No. L02012375

Sr.No Date TRH VLL AMPS KW KWH PF Temp. In Deg C Chiller Condenser

RH

AMB Set Point IN LET OUTLET INLET

OUT LET

1 29-03-2018 9.00 399.8 375.00 234.50 2108.50 0.902 28.60 6.0 16.32 10.82 27.7 32.55 36.25

2 30-03-2018 11.00 406.2 357.33 225.20 2479.90 0.875

28.67 6.0 18.17 11.42 27.87 34.65 37.00 7.00 403.0 365.30 228.60 1620.50 0.894

3 31-03-2018 23.68 412.7 339.92 214.42 5026.00 0.879 27.30 6.0 10.90 5.73 27.81 31.79 38.30

4 01-04-2018 23.86 411.8 301.80 185.40 4365.00 0.860 27.25 6.0 10.35 6.54 26.55 30.64 41.00

5 02-04-2018 23.81 403.9 336.63 207.86 4932.00 0.878 27.21 6.0 14.78 8.57 28.25 32.95 44.90

6 03-04-2018 23.75 400.0 370.60 230.60 5482.70 0.897 27.23 6.0 14.61 8.33 28.02 32.95 47.72

7 04-04-2018 23.95 399.7 364.80 225.60 5381.90 0.896 27.59 6.0 14.37 8.51 27.60 32.95 48.96

8 05-04-2018 23.50 401.5 363.23 226.32 5321.90 0.894 27.40 6.0 15.10 8.874 27.85 32.01 50.00

9 06-04-2018 23.58 400.9 361.60 224.80 5078.00 0.894 27.67 6.0 14.20 8.45 27.53 32.12 50.55

10 07-04-2018 22.15 406.0 326.34 204.60 4772.20 0.867 28.08 6.0 12.78 9.17 33.02 38.2 31.96

Total 215.28 46568.60

Average 404.1 351.14 218.9 216.32 0.885 27.7 6.0 14.16 8.64 28.2 33.1 42.66

Page 90: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

5

D) POST DATA SUMMARY

Sr. No DATE

Total AVERAGE FIGURES Temperatures in Deg C

TRH KWH VLL VLN AMPS KW PF RH AMB CHILLER CONDENSER

INLET OUTLET INLET OUTLET

1 24-08-2018 11.75 2712 401.7 230 355.5 230.0 0.929 64.0 27.61 18.89 13.08 30.41 35.50

2 25-08-2018 23.11 4132 401.5 230 316.2 202.0 0.918 66.9 26.81 14.77 10.18 29.19 33.14

3 26-08-2018 22.88 3174 401.0 230 301.0 190.9 0.910 71.7 25.91 14.46 10.69 29.50 32.65

4 27-08-2018 23.66 3515 402.0 230 333.0 213.6 0.918 79.9 24.78 15.55 10.88 28.95 32.91

5 28-08-2018 23.96 4779 402.0 230 346.5 223.3 0.925 72.3 26.11 17.03 12.35 29.47 34.10

6 29-06-2019 23.55 4907 400.0 228 349.0 224.2 0.920 67.5 26.55 17.12 12.63 29.38 33.99

Total 128.9 23219

Average 180.1 401.4 229.7 333.5 214.0 0.920 70.4 26.29 16.30 11.63 29.48 33.72

Page 91: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

6

E) Comparison of PRE & POST summary of Data 400 TR Chiller Sr. No. L02012375

Sr. No Parameters Pre Data Post Data August

1 Total Running Hours 215.28 128.9

2 Total Energy Consumption in KWH 46568.6 23219

3 Average Energy Consumption per hour in KWH 216.32 180.13

4 Average Load in KW per Hour 218.9 214

5 Average KWH/ KW 0.988214 0.841738

6 Average Voltage Line to Line (VLL) in Volts 404.1 401.4

7 Average Current in Amps 351.14 333.5

8 Average PF 0.885 0.920

9 Average Ambient Temperature in Deg C 27.7 26.29

10 Average Set Point in Deg. C 6.0 6.0

11 Average chiller Inlet temperature in Deg C 14.16 16.30

12 Average chiller Out let temperature in Deg C 8.64 11.63

13 Average Condenser Inlet Temperature in Deg C 28.2 29.48

14 Average Condenser Inlet Temperature in Deg C 33.1 33.72

15 RH % 42.66 70.4

Page 92: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

7

F) Observations & Conclusions

a) Average Energy Consumption in KWH/ Hour (Pre) : 216.32 Kwh b) Average Energy Consumption in KWH/Hour (Post) : 180.13 kwh c) Difference : 216. 32- 180.13 = 36.19 Kwh /Hour

d) Improvement with MAXR100 in % : (36.19 /216.32) x 100 = 16.73 %

However, the Post MAXR100 the ambient temperature decreased from 27.7 Deg C to 26.29 Deg C (i.e. by 1.41 Deg C)

Actual Energy Savings Considering the change in average Ambient Temperatures post MAXR100 installation period.

For calculating the actual savings we need to consider the change in ambient temperatures of pre data period with the post data period, which is 1.41 Deg C. Any increase in the ambient temperature will affect the energy consumption of the AC unit. Hence for calculating the actual savings we need to consider COP- Coefficient of Performance principle which is most commonly used method.

COP- is the ratio of heat removed from a system to the energy required to remove the heat. The theoretical maximum is equal to the coldest temperatures of the refrigerant divided by the difference between its coldest and hottest temperatures are expressed in Kelvins. Even the perfect system decreases efficiency with increased outside temperatures, dropping about 2% per Deg C.

Page 93: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

8

Considering 1.41 Deg C decrease in the ambient Temperatures for the post MAXR 100 installation period the energy consumption has decreased 2.82 % during the period.

Considering the above we have to calculate the actual energy consumption during the post MAXR100 installation period and add the difference to the recorded total energy consumption.

a) Total Energy consumption in KWH : 23219 Kwh b) Increase in Energy consumption due to rise in ambient temperature in % : 2.82 % c) Actual Energy Consumption in KWH : (23219 x 2.82)/100 = 654.7758 KWH

23219 + 654.7758 = 23873.75 Kwh

Page 94: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

9

G) SUMMARY OF PRE & POST DATA( After adding the kwh consumption due to decrease in post Ambient Temperatures

Sr. No Parameters Pre Data Post Data

(After adding the difference in KWH consumption due to decrease in post Amb temp)

1 Total Running Hours 215.28 128.9

2 Total Energy Consumption in KWH 46568.6 23873.78

3 Average Energy Consumption per hour in KWH 216.32 185.2116

4 Average Load in KW per Hour 218.9 214.0

5 Average KWH/ KW 0.988214 0.865475

6 Average Voltage Line to Line (VLL) in Volts 404.1 401.4

7 Average Current in Amps 351.14 333.5

8 Average PF 0.885 0.92

9 Average Ambient Temperature in Deg C 27.7 26.29

10 Average Set Point in Deg. C 6.0 6.0

11 Average chiller Inlet temperature in Deg C 14.16 16.30

12 Average chiller Out let temperature in Deg C 8.64 11.63

13 Average Condenser Inlet Temperature in Deg C 28.2 29.48

14 Average Condenser Inlet Temperature in Deg C 33.1 33.72

15 RH % 42.66 70.4

Page 95: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

10

H) FINAL ENERGY SAVINGS WITH MAXR100 :

a) Actual average Energy Consumption / Hour on kWh : 23873.75 /128.9 = 185. 2116 KWH/Hour b) Average Energy Consumption /Hour Pre : 216.32 KWH/ Hour c) Average Energy Consumption / Hour Post : 185.2116 KWH/ Hour d) Difference : 216.32- 185.2116 = 31.10 Kwh/Hour

e) Improvement with MAXR100 : ( 31.10/216.32) x 100 = 14.37 %

Page 96: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

11

I) PRE & POST DATA - GRAPH

215.28 216.32

218.9

0.988214

404.1

351.14

0.88527.7

6.0

128.9

185.2116

214.0

0.865475

401.4

333.5

0.92

26.296.0

0

50

100

150

200

250

300

350

400

450

Total Running Hours

Average Energy

Consumption per hour in

KWH

Average Load in KW per

Hour

Average KWH/ KW

Average Voltage Line to

Line (VLL) in Volts

Average Current in

Amps

Average PF Average Ambient

Temperature in Deg C

Average Set Point in Deg. C

Pre Data

Post Data

Page 97: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

1

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

Date: 12th October, 2017

ENERGY SAVINGS REPORT OF 25 TR CARRIER CHILLERS – KOLSON FOODS, DUBAI

a) Data Logger Installed on for pre installation data : 23rd July 2017 b) MaxR 100 Installed on : 8th August 2017 c) Post maxr100 installation data recorded on : 21st to 22ndAugust 2017 d) Type of Refrigerant : R-22 e) Type of Maxr100 used : MAXR100 MO f) Quantity of MAXR100 used : 25 Oz g) Post Installation data recorded for 2nd time : 30th September to 5th October 2017

Page 98: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

2

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

I) Pre Installation data

Sr.No Date TRH VLL VLN AMPS KW KWH PF AMB

1 23-07-2017 10.50 394.0 227.4 39.77 21.60 227.63 0.765 42.8

2 24-07-2017 23.75 392.7 226.7 37.28 20.18 461.80 0.747 44.0

3 25-07-2017 23.75 390.9 225.7 37.05 19.93 472.60 0.775 45.0

4 26-07-2017 14.50 392.6 226.6 31.92 16.92 238.55 0.773 46.2

Total 72.50 1400.58

Average 392.6 226.6 36.5 19.66 19.318 0.765 44.5

II) Post MAXR100 installation and post 14 days clean up data

Sr.No Date TRH VLL VLN AMPS KW KWH PF AMB

1 21-08-2017 17.25 397.0 229.2 31.04 16.02 271.10 0.703 43.0

2 22-08-2017 16.85 393.2 227 32.26 17.27 299.10 0.727 46.0

Total 34.10 570.20

Average 395.1 228.1 31.65 16.65 16.721 0.715 44.5

Page 99: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

3

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

III) Summary of Pre & Post Data

SR.NO TRH VLL VLN AMPS KW KWH AMB INSIDE

1 PRE 72.50 392.6 226.6 36.5 19.66 19.318 44.5 23

2 POST 34.10 395.1 229.1 31.65 16.65 16.721 44.5 23

IV) Summary- Comparison of pre & Post data:

Sr.No Parameters Pre Post

1 Total Running Hours 72.50 34.10

2 Total Energy Consumption in KWH 1400.58 570.20

3 Average Energy Consumption/ Hur in KWH 19.318 16.721

4 Average current in Amps 36.5 31.65

5 Average Load in KW 19.66 16.65

6 Average Voltage - VLL 392.6 395.1

7 Average Voltage - VLN 226.6 229.1

8 Average Ambient temperature IN Deg C 44.5 44.5

9 Average inside temperature in Deg C 23 23

Page 100: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

4

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

V) Energy Savings& Reduction of Current with MAXR100

Average Energy Consumption in KWH/ Hour without MAXR100 : 19.318 KWH Average Energy Consumption in KWH/Hour with MAXR100 : 16.721 KWH Improvement in kWh/ Hour : 2.597 Kwh Energy Savings with MAXR100 IN % : (2.597/19.318)x 100 = 13.44 %

Average Current in Amps Pre : 36.5 Amps Average Current in Amps (Post) : 31.65 Amps Improvement in Amps : 4.85 Amps Improvement % in Current (Amps) : (4.85/36.5) x 100 = 13.28%

Page 101: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

5

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

Post MAXR100 installation Data recorded for 2nd time:

SR.NO DATE TRH VLL VLN AMPS KW KWH PF amb Inside

1 30-09-2017 14.25 395.20 228.30 38.26 20.5 206.6 0.745 42.0 23.0

2 01-10-2017 23.50 394.80 228.00 44.83 23.8 288.9 0.746 42.5 23.0

3 02-10-2017 23.75 394.00 227.50 47.22 25.0 291.5 0.754 42.5 23.0

4 03-10-2017 23.75 393.20 227.00 49.10 25.8 350.9 0.760 42.0 23.0

5 04-10-2017 23.75 395.30 228.20 49.65 26.2 372.3 0.755 42.0 23.0

6 05-10-2017 18.50 396.30 228.80 45.43 23.8 303.6 0.741 41.0 23.0

Total 127.5 1814

Average 394.8 228 45.75 24.17 14.23 0.75 42.0 23.0

Summary of comparison with pre and 2nd time post MAXR100 installation data

Sr.No Parameters Pre Post

1 Total Running Hours 72.5 127.5

2 Total Energy Consumption in KWH 1400.58 1814

3 Average Energy Consumption/ Hur in KWH 19.318 14.227 4 Average current in Amps 36.5 45.78

5 Average Load in KW 19.66 24.17

6 Average Voltage - VLL 392.6 394.8

7 Average Voltage - VLN 226.6 228

8 Average Ambient temperature IN Deg C 44.5 42

9 Average inside temperature in Deg C 23 23

Page 102: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

6

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

VI) Energy Savings& Reduction of Current with MAXR100

Average Energy Consumption in KWH/ Hour without MAXR100 : 19.318 KWH Average Energy Consumption in KWH/Hour with MAXR100 : 14.227 KWH Improvement in kWh/ Hour : 5.091 Kwh Energy Savings with MAXR100 IN % : (5.091/19.318)x 100 = 26.35 %

Actual Energy Savings Considering the change in average Ambient Temperatures post MAXR100 installation period.

For calculating the actual savings we need to consider the change in ambient temperatures of pre data period with the post data period, which is 2.5 Deg C. Any decrease in the ambient temperature will affect the energy consumption of the AC unit. Hence for calculating the actual savings we need to consider COP- Coefficient of Performance principle which is most commonly used method.

COP- is the ratio of heat removed from a system to the energy required to remove the heat. The theoretical maximum is equal to the coldest temperatures of the refrigerant divided by the difference between its coldest and hottest temperatures are expressed in Kelvins. Even the perfect system decreases efficiency with increased outside temperatures, dropping about 2% per Deg C.

Page 103: RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS … · 2019. 6. 12. · RESULTS PRESENTATION, TESTS ABOUT AIR CONDITIONING EQUIPMENT MADE IN METAPLUS

7

CITC USA HEADQUARTERS 541 E. Cimarron St Colorado Springs, CO 80903 TEL 719-955-3110 FAX 719-578-1121 EMAIL [email protected]

Considering 2.5 Deg C decrease in the ambient Temperatures for the post MAXR 100 installation period the energy consumption has to be INCREASED by 5 % during the period.

Considering the above we have calculated the actual energy consumption during the post MAXR100 installation period. Total Energy consumption in KWH : 1814.00 Kwh Increase in Energy consumption due to rise in ambient temperature in % : 5 % Actual Energy Consumption in KWH : (1814 x 5)/100 = 90.7 KWH

1814.00 + 90.7 = 1904.7 kWh Actual average Energy Consumption / Hour on kWh : 1904.7/127.5 = 14.938 kWh/Hour Actual % of Energy Savings with MAXR100 in % : (19.318 – 14.938 ) = 4.38 Kwh/ Hour

(4.38/19.318) x 100 = 22.67 %