project report (2) 3rd sem n.docx

Upload: raj-mike

Post on 04-Jun-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 Project report (2) 3rd sem n.docx

    1/117

    7. Poly phase synchronous machine:The synchronous machines are usually built

    with field winding on the rotor and armaturewinding on the stator. However in order to

    represent the two axis model of the synchronous

    machine, the armature is placed on rotor and

    field is mount on stator.

    7.1. Basic synchronous machineparameter:

    A three phase synchronous machine has four

    basic s winding; namely three identical and

    symmetrical armature windings and one fieldwinding.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    2/117

    Fig.7.1. Basic two pole

    synchronous machine

    Fig.(7.1) shows the elementary two pole

    synchronous machine. With salient pole

    construction. The field winding axis is taken asdirect axis and the inter polar axis as quadrature

    axis. The d- and q- axes remain fixed with the

    field winding on stator , but three magnetic axes

    of three phase armature phases rotate as the

    rotor revolves. In order to concentrate more onthe synchronous machine basic features and to

    further analysis, the following assumption are

    made.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    3/117

    1.Influences of damper are neglected.

    2.Hysteresis and magnetic saturation are

    neglected.3.Space distribution of armature m.m.f wave

    and field flux wave are assumed sinusoidal.

    4.The armature slots dont have any effect on

    synchronous machine inductances.

    7.1.1. Synchronous machine resistances:The armature circuit resistances for A,B,C

    phases are designated by ra,rb, rc respectively.

    Since the phase windings are identical, the

    magnitudes of all the three resistances are equal,

    i.e. . For convenience is used toidentify the winding resistance of phase A aswell as armature circuit resistance for any of the

    three phases. The symbol

    is used to represent

    the field-circuit resistance.

    7.1.2. Synchronous machine inductances:

  • 8/14/2019 Project report (2) 3rd sem n.docx

    4/117

    a) Field self-inductances. The air gaplength seen by the field m.m.f remains

    constant, whatever the rotor position w.r.tfield poles may be. As a result of it, the

    reluctance seen by the field m.m.f is always

    constant and consequently field self-

    inductances

    is constant.

    b) Armature to field mutual inductances.The mutual inductances between armatureand field windingsvary periodically with

    space angle. Here the mutual inductances

    between phase A and field winding

    is

    cosine in nature as shown in fig.(7.2) below.Therefore

  • 8/14/2019 Project report (2) 3rd sem n.docx

    5/117

    c) Armature self-inductances.

    is a constant term, whereas is the

    amplitude of second-harmonic component.

    There is some flux, produced by phase A, which

    does not cross the air gap to link the stator. This

    flux is called leakage flux and can be accounted

    for phase leakage inductance

    The variation

    of self inductance

    with space angle

    is

    depicted in figure.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    6/117

    Fig.7.2. Variation of self

    inductance of phase A with space angle

    d) Armature mutual inductance

    (7.3)For round rotor machine, Where are the mutual inductancesbetween phases A, B; are the mutual

  • 8/14/2019 Project report (2) 3rd sem n.docx

    7/117

    inductances between phases B, C and

    are the mutual inductances between phases

    C, A. can be found by determining the fluxlinkages with phase B when only phase A isexcited or vice versa. The variation of orwith space angle is shown in figure 7.3

    Fig.7.3. Variation of armature mutual

    inductances with space angle7.2 Three-phase Synchronous Machine (with

    no Amortisseurs)

    The synchronous machine voltage equations ind-q can be obtained by a simple graphical

    method developed in Art. () and same is done in

  • 8/14/2019 Project report (2) 3rd sem n.docx

    8/117

    this article. The primitive machine model or

    generalized model of a polyphase machine

    without amortisseurs is illustrated in figure (7.3).

    Fig. 7.3 generalized model of a polyphase

    synchronous machine

    The stator coil DS represents the field winding

    and the rotor coils DR, QR represent the

    polyphase armature winding. In the analysis to

    follow, the effect of ammortisseur circuits (or

    damper bars) is neglected, so that basicimportant results are obtained more clearly. The

  • 8/14/2019 Project report (2) 3rd sem n.docx

    9/117

    voltage equations in matrix form for the model

    of fig (7.3) are written as follows:

    =

    (7.4)

    Now the field winding is designated by F in

    place of more general DS. Similarly the

    armature winding DR and QR are designated by

    D and Q respectively.

    Since the armature winding is uniformly

    distributed and balanced,

    =

    =

    (say).

    With these constraints, the voltage Eq. ()

    becomes,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    10/117

    (7.5)The voltage-current relations given by Eq. (7.5)

    are applicable both for steady state and transient

    analysis of synchronous macine.

    7.2.1 Balanced Steady-State Analysis

    With d.c. field winding on the outer fixed

    member, the stator field does not revolve and is,

    therefore, stationary in space. Polyphase

    currents in the armature winding produce

    synchronously revolving field and for the

    relative speed between the two fields to be zero,

    the armature must revolve synchronous speed

    opposite to the direction of rotating field. Thus

    the speed of resultant air-gap flux is stationary

    in space and in view of this, the operator p must

  • 8/14/2019 Project report (2) 3rd sem n.docx

    11/117

    be replaced by zero. On the steady state the

    armature can run at synchronous speed only,

    therefore, rotor angular velocity electrical radians per second.Thus the steady-state voltage equations, from

    Eq. (7.5) are

    (7.6)

    The subscript zero indicates constant or d.c.

    values. In place of etc. should have beenwritten, but it is not done here merely to use

    them at a later stage.

    Note that the term is associated with and with . These quantities andare known as

  • 8/14/2019 Project report (2) 3rd sem n.docx

    12/117

    , direct axis synchronous reactanceand

    = quadrature axis synchronousreactance.In order to include these terms, Eq. (7.6) is re-

    written as,

    (7.7)7.2.3 Phasor equation and Phasor diagrams

    In order to determine the performance character

    tics of the machine in actual machine in actual

    machine axes, i.e. a-b-c co-ordinates, the

    transformation from d, q, o to abc variables asgiven by Eq. (7.4) can be used.

    Considering phase a only,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    13/117

    (7.8)Now ] And ] =

    .

    (7.9)

    For phase a, let the voltage be given by Where

    is the angle that

    makes at

    .

    Also .

  • 8/14/2019 Project report (2) 3rd sem n.docx

    14/117

    ; Where

    (7.10)Where,

    and

    Similarly (7.11)Where,

    and

    7.2.4 Open-circuit conditions

    On no load, , i.e. the actualarmature currents are zero. These zero values

    when transformed to d-q axes currents are . In view of this, Eq. (7.7)becomes

  • 8/14/2019 Project report (2) 3rd sem n.docx

    15/117

    and

    .

    The no-load r.m.s. voltage of phase a, from Eq.

    (), is (7.12)

    Where is called the excitation e.m.f. or excitation

    voltage. This voltage can also be expressed in

    terms of maximum mutual inductances (between any armature phase and the fieldwinding).

    (7.13)

    7.2.5 Load conditions

  • 8/14/2019 Project report (2) 3rd sem n.docx

    16/117

    In this case, the voltage of phase a is obtained

    by the substitution of

    from Eq. (7.12)

    for . (7.14)

    [ ( )] (7.15)

    In Eq. (7.15); and are only magnitudeand not in complex notation. In order to expressthem as a phasors, refer to fig. 7.4 , where d-axis

    is taken as the reference or real-axis.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    17/117

    Fig. 7.4 (a) Phase-a axis at an angle

    from d-axis and

    (b) Phasor component of Ia

    The phasor notation for armature current , interms of phasors

    and

    can be written as

    From Eq. (7.14); (7.16) and or

    With these changes, Eq. (7.15) becomes

  • 8/14/2019 Project report (2) 3rd sem n.docx

    18/117

    (7.17)

    is the terminal voltage of any one phase for asalient-pole type synchronous motor.For a generator, the voltages are generated and

    the currents are output currents. In view of this,

    the generator voltage equation can be obtainedfrom motor voltage equations by writing in place of . Therefore, the generator voltageequation is

    (7.18)

    Eq. (7.18) gives phasor diagram for a salient-

    pole synchronous generator as shown in figure

    7.5.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    19/117

    Fig. 7.5 Phasor diagram for synchronous

    generator

    7.2.6 Internal Power Factor Angle

    For calculating and , the internal powerfactor angle

    for a generator must be

    known. For this purpose draw ab normal to asshown in figure 7.6 ; where for simplicitywith is dropped. Since ab is 90 away from , it

  • 8/14/2019 Project report (2) 3rd sem n.docx

    20/117

    must be a reactance drop, say . Draw acperpendicular to ob as shown in figure 7.6.

    Fig.7.6 Resolving of Iainto its d- and q-axes

    components Id and Iq for synchronousgenerator

    rom generator phasor diagram of figure 76

    it is seen that oa and oc are right angled

    triangles and, therefore,

    .

    Thus,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    21/117

    Or or (7.19)This shows that in fig. (7.6), . If ob isdesignated as

    and, therefore the angular

    position of excitation voltage with respect to, i.e. the power angle is is known. From this,angle , therefore, and can becomputed. Fig (7.6) also reveals that

    (7.20)Eq. (7.18) may now be written as

    (7.21)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    22/117

    Eq. (7.21) include a term which isdue to saliency, i.e. no-uniform air gap. This

    quantity reduces to zero for a cylindrical-rotorsynchronous machine in which . Thissaliency factor in salient-pole synchronous

    machine is quite appreciable, since isapproximately 60 to 70% larger then

    . Even

    in turbo alternators, small salient-pole effect is

    present due to the effect of field-winding slots

    on q-axis reluctance consequently differsslightly (about 10%) from

    in cylindrical-

    rotor synchronous machines.From the generator phasor diagram of Fig (7.6),

    it is seen that

    (7.22)

    7.2.7 Cylindrical-rotor synchronous

    machines

  • 8/14/2019 Project report (2) 3rd sem n.docx

    23/117

    These machines are characterized by uniform air

    gap so that reluctances along d and q axes are

    equal. In view of this, Whereis called the synchronous reactance.Thus the voltage equations for a cylindrical-

    rotor synchronous generator, from Eq. (), is (7.23)Here

    is called the synchronous

    impedance. With the help of Eq. (7.23), the

    voltage phasor diagram of a cylindrical-rotor

    alternator is as shown in fig.7.7 (a). This Eq.

    (7.23) also help in representing this type of

    machine by the equivalent circuit of fig. 7.7 (b)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    24/117

    Fig. 7.7 Cylindrical rotor alternator

    (a) Phasor diagram and (b) Its equivalent

    circuit

    7.2.8 Steady-state Power-angle

    Characteristics:

    The expressions for power are derived from the

    torque matrix of synchronous machine.

    The torque matrix G is given by

  • 8/14/2019 Project report (2) 3rd sem n.docx

    25/117

    Now,

    Total synchronous power,

    Under steady state, Since the power is invariant in the two systems

    of variables, power per phase is

    ( ) ( ) 724)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    26/117

    If d.c. excitation is reduced to zero, andEq. (7.24) becomes

    ( ) 725)

    This power given by Eq. 7.25 is called the

    reluctance power and is the basis of operation of

    a wide variety of reluctance motors.

    Many times, it is convenient to include load

    angle in the synchronous power expression of

    Eq. 7.24. This can be easily done with the helpof phasor diagram

  • 8/14/2019 Project report (2) 3rd sem n.docx

    27/117

    Fig. 7.8 Phasor diagram

    From the above phasor diagram,

    and i.e.

    726)

    and 727)Substitute the values ofId andIq in Eq. (7.24)

    728)For a round rotor machine, ,therefore, synchronous power from Eq. (7.24) is 729)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    28/117

    SubstituteIqfrom Eq. (7.27) in Eq. (7.29) gives

    ................................................ (7.30)

    With the help of Eq. 7.30 the variation of power

    P with is plotted in ig1a to give the power-

    load angle characteristics of a cylindrical rotor

    synchronous machine. Eq. 7.28 gives the power

    angle characteristics of a salient pole

    synchronous machine, which is illustrated in

    Fig. 7.9 (b)

    Fig. 7.9 Power-angle characteristics for

  • 8/14/2019 Project report (2) 3rd sem n.docx

    29/117

    (a) Cylindrical rotor synchronous machine.

    (b) Salient-pole machine.

    Fig. 7.9(a) reveals that maximum power in a

    cylindrical-rotor machine occurs when = 90

    For a salient pole machine, the maximum power

    as seen from Fig. 7.9(b) is at load angle less

    than 90 This value of load angle can be

    obtained from Eq. 7.28 as follows:

    731)Its solution gives the value of and sustitution

    of angle as calculated from Eq 731 in Eq

    (7.28) gives the maximum power which is

    sometimes called the pull-out power.

    7.2.9 Reactive Power:

  • 8/14/2019 Project report (2) 3rd sem n.docx

    30/117

    The reactive power Q is determined from phasor

    diagram of Fig. 1(a) by noting that reactive

    power is equal to the product of voltage andquadrature lagging component of armature

    current.

    Substitution of Id and Iq , from Eq. (3) and (4)respectively, gives

    ............................................ (7.32)For a cylindrical-rotor machine,

    , and reactive power for this machine, From

    Eq. (7.32) is given by

  • 8/14/2019 Project report (2) 3rd sem n.docx

    31/117

    7.33)

    Eq. (7.33) shows that

    When

    i.e. under normal

    excitation,

    and motor operates at

    unity p.f.

    When i.e. Motor is under-excited, Q is positive and, therefore, the

    motor draws reactive power from supply

    lines.When i.e. Motor is over-

    excited, Q is negative and, therefore, the

    motor delivers reactive power to the supply

    lines.

    For a salient-pole alternator, it can be shown

    that

  • 8/14/2019 Project report (2) 3rd sem n.docx

    32/117

    .

    /

    And for a cylindricalrotor alternator

    For both the generator and motor operations, it

    can be stated in general that an over-excited

    ( machine delivers or exportsreactive power to the supply system; an under-

    excited (

    machine absorbs,

    imports or draws reactive power from thesupply system.

    7.3 Short Circuit Ratio (SCR):

    SCR of a synchronous machine helps in

    obtaining an estimate of its operating

    characteristics.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    33/117

    Fig. 7.10 Short Circuit Ratio

    SCR is defined as the ratio of field current

    required to generate rated voltage on open

    circuit, to the field current required to circulate

    rated armature current on three phase shortcircuit.

    As triangles oab and ode are similar, therefore

  • 8/14/2019 Project report (2) 3rd sem n.docx

    34/117

    734)

    From Eq. 7.34 735)It is thus seen that SCR is equal to the reciprocalof per unit value of direct axis synchronous

    reactance Xd.SCR effects both the physical size

    and operating characteristics of the synchronous

    machine. A significance SCR can be gained

    from the following considerations.

    a) Low SCR: Low value of SCR meansgreater value of Xd. An examination of

    Fig.[] with

    , shows that low SCR

    results in large voltage variations with loadand thus a poor voltage regulation.

    Therefore, in order to maintain constant

  • 8/14/2019 Project report (2) 3rd sem n.docx

    35/117

    terminal voltage, the field current will have

    to be varied over a wide range.

    Eq. (7.28) shows that low value of SCRmeans less synchronous power P and

    consequently a lower stability limit.

    A low value of SCR means more Xd (or Xs)

    and therefore a low value of synchronizing

    power Ps( The synchronizing power is transient in

    nature and come into play only when there is

    a disturbance in the system. In other words,

    the function of Ps is to keep the machine in

    synchronism. Therefore, a machine with low

    value of SCR has low synchronizing power

    and therefore a low tendency for keeping the

    machine in parallel with the infinite bus.A low value of SCR results in low value of

    armature short-circuits current.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    36/117

    b) High SCR: The synchronous machinewith high SCR has better voltage regulation

    and improved steady-state stability limit.The disadvantage of high SCR is the high

    values of armature short-circuit current.

    A synchronous generator, feeding a long

    transmission, or cable, line, may be

    capacitive loaded in which ease of armaturecurrent leads the terminal voltage. The mmf

    set up by a leading armature current , aids

    the field mmf and consequently the

    generated voltage increases. In order to

    reduce the effect of armature mmf on thefield mmf and to retain the voltage under

    control, air gap length should be increased,

    which means a synchronous machine with

    high SCR should be used.

    Transient Analysis:

    Transient behavior analysis is important because

    Determine the shaft stress.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    37/117

    Winding and bus bar stress. Protective relay setting. Circuit breaker rupturing duties etc.

    For transient analysis two assumption, usually

    made during transient analysis, are as follows.

    The machine is running initially on noload and under steady-state condition.

    Speed before and after the short circuitremains unchanged from its synchronous

    speed Voltage equations for a synchronous generator

    are ( )

    ( )736)For transient analysis above equation havelengthy manipulations. In order to avoid this

  • 8/14/2019 Project report (2) 3rd sem n.docx

    38/117

    some term in equation may be omitted to obtain

    an easier solution of the transient problem.

    A. All resistances neglected.With the neglect the resistances of both the

    field ( ) and armature windings and with alternator speed

    737)Before short circuit i.e. at

    The armature currents 738)The field current before short circuit is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    39/117

    Now from Eq. (7.37) and Eq. (7.38)

    Before the short circuit After the short circuit

    Thus the effect of short circuit is to

    reduceto zero suddenly and this can betaken as equivalent to the sudden applicationof a unit step-function voltage tothe q-axis terminal.

    Both before and after the short circuit,the voltage applied to the field winding is therefore superimposed voltage for fieldwinding is zero.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    40/117

    Now from above discussion the voltage

    equation after balanced

    short circuit, in

    terms of superimposed quantities, are 739

    740

    741From eq. (7.39)

    742

    Now put in eq. (7.40) then 743Where,

    744 axis transient inductance.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    41/117

    Now put in eq. (7.41) and then

    745From eq. (7.43)

    7.46)

    Now put the value of from eq. (7.43) in eq.(7.45) and in complex frequency domain is

    747After taking partial fraction eq. (7.46) becomes

    Take Laplace inverse of above equation we get

    a result

  • 8/14/2019 Project report (2) 3rd sem n.docx

    42/117

    748

    Fig.7.11 Variation of Id (t) for a sudden 3-phase short circuit

    Note:- transient d-axis current consist of A D.C. component

    .

    Fundamental frequencycomponent .

    Put in Eq. (7.46)and we get 749

  • 8/14/2019 Project report (2) 3rd sem n.docx

    43/117

    Fig.7.12 Variation of Iq (t) for a sudden 3-

    phase short circuit

    Note:-transient q-axis current contain only

    fundamental component of current.

    The actual phase current when angle between d-

    axis and axis of phase a is

    after

    short circuit, at any time t second is

    Fig. 7.13 Phase-a axis displaced from d-axis

    by an angle

  • 8/14/2019 Project report (2) 3rd sem n.docx

    44/117

    (a) at the instant of short circuit and(b)

    at any time t

    [ ]750From equation (7.48),(7.49) and (7.50) we get

    751Where

    =An angle made by phase-a with d-axis when

    short circuit occurs.

    Before the short circuit, i.e. at , and with this equation Eq.(7.51) becomes

  • 8/14/2019 Project report (2) 3rd sem n.docx

    45/117

    . /

    752Similarly current forPhase-b, Phase-c,

    From Eq. 7.52 we seen that phase current( ) consist of First term as fundamental frequency

    component Second term as the D.C. component. Third term as the second harmonic

    component.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    46/117

    Note:-

    The neglect of field and armatureresistance imply that none of the term in Eq.(7.52) decay with time. Magnitude of, fundamental, D.C. and

    second harmonic component depends upon

    the Pre-fault excitation

    .

    Magnitude of fundamental componentdepends upon the d-axis transient reactance.

    Magnitude of D.C. component dependsupon

    .

    The magnitude of second harmoniccomponent depends on the term ,which is called the transient saliency. If short circuit occurs at then

    D.C. component of current

    is zero.

    D.C. component of becomesfundamental frequency component of phasecurrent

  • 8/14/2019 Project report (2) 3rd sem n.docx

    47/117

    Fundamental frequency component of

    and

    get transformed to D.C. and

    second harmonic component of Transient field current can be obtain bysubstituting from eq.(7.48) in eq.(7.42)

    Total field current is

    ..(7.53)Now put in Eq. (7.53) thenwe finally

    754

  • 8/14/2019 Project report (2) 3rd sem n.docx

    48/117

    Fig.7.14 Variation of If (t) for a sudden 3-

    phase short circuit

    B. In this, the term containing are the transformervoltages of armature voltage and neglect this

    term from armature voltage equation alsoneglect the resistances of both the field( )and armature windings .So in this case after balance 3-short circuit Eq.

    (7.39), (7.40) and (7.41) becomes

    755 756

  • 8/14/2019 Project report (2) 3rd sem n.docx

    49/117

    757

    From Eq. (7.55)

    From Eq. (7.56)

    From Eq. (7.57)

    Field current,

    Total field current

  • 8/14/2019 Project report (2) 3rd sem n.docx

    50/117

    758Current in phase-a is

    [ ]

    Put the value of and in above equation

    759Note:- If transformer voltages are neglected

    from the armature voltage equation, the

    phase currents consist only fundamental

    terms(D.C. and second harmonic terms are

    absent).

  • 8/14/2019 Project report (2) 3rd sem n.docx

    51/117

    Current and purely in D.C. innature i.e. it is constant.

    Dynamic analysis of synchronous machine is

    usually carried out by neglecting the armature

    transformer voltages.

    C. Armature transformer voltages andits resistances neglected ( )Under this condition,

    760

    761

    762From Eq. (7.60)

    763From Eq. (7.62)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    52/117

    0

    1

    Ratio field time constant.d-axis open circuit transient time constantThus

    * + 764

    is called the d-axis short circuit

    transient time constant

    From Eq. (7.64)

    Now convert above equation in s-domain and

    finally in time domain so

  • 8/14/2019 Project report (2) 3rd sem n.docx

    53/117

    765Now

    ( ) 766So total field current is

    767The phase current is given by

  • 8/14/2019 Project report (2) 3rd sem n.docx

    54/117

    768Note:- The effect of including the field

    resistance

    is to make the amplitude of

    short circuit current equal to after thetransient have decay and its R.M.S value is . The equation of envelope of the short

    circuit current, from eq.(32) is . / The R.M.S value of short circuit current

    as function of time is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    55/117

    769Now from above equation

    Just after the short circuit i.e. at thearmature phase current is

    , which is

    depends on transient reactance and itsfinal steady state current is , whichdepend on d-axis synchronous reactance.

    The decay from

    to

    is an

    exponential and is determine by time

    constant.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    56/117

    Fig. 7.15 Variation of rms short-circuitarmature current during transient

    D. Armature transformer voltages andits resistances neglected ( ) butamortisseur circuits included.

    The synchronous machines fitted with damperbars, or amortisseurs, are studied with one coil

    KD in d-axis and another coil KQ in q-axis

    Due to damper winding effect

    770

  • 8/14/2019 Project report (2) 3rd sem n.docx

    57/117

    Where

    =Sub transientcomponent of current due to damper winding.This component of current decay with a time

    constant

    ,which is called the d-axis short

    circuit sub-transient time constant. In case the effect of armature

    transformer voltage consider

    Then examine the Eq. (7.48) reveals that

    ,with damper bar present must include a

    fundamental frequency component 771 In case armature resistance also

    consideredThen fundamental frequency component of would decay with the armature timeconstant .Thus complete expression of current

  • 8/14/2019 Project report (2) 3rd sem n.docx

    58/117

    772Similarly

    773Now

    0

    .

  • 8/14/2019 Project report (2) 3rd sem n.docx

    59/117

    /

    .

    / 1774In above equation second harmonic component

    is usually small. In modern synchronous

    generator

    therefore eq. (39) becomes

    775Note:-

    In case the fault occurs at

    and at time

  • 8/14/2019 Project report (2) 3rd sem n.docx

    60/117

    776From eq. (7.76) we note that first term is A.C.

    component of and second term is D.C.component of. . Maximum possible value of armature

    phase current is after one half ofcycle i.e. and i.e. if axis ofphase-a along d-axis at the instant of fault

    and attenuation does not take place. R.M.S. value of symmetrical armature

    short-circuit current is given by

  • 8/14/2019 Project report (2) 3rd sem n.docx

    61/117

    777

    Fig. 7.16 Variation of rms short-circuitarmature current during sub-transient

    In the above graph at Just after the short circuit, current is

    equal to .

  • 8/14/2019 Project report (2) 3rd sem n.docx

    62/117

    Current change exponentially to with a time constant

    and to with time constant. The asymmetrical or D.C. component of

    total short circuit armature current

    The R.M.S or effective value of the total

    short circuit armature current

    778)

    The effective value of greatest armaturecurrent including A.C. and D.C. component

    is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    63/117

    7.5 Transient Torque:

    The object of this article is to calculate the

    maximum value of torque at the instant of short

    circuit. In order to do this the following

    assumptions are made:

    Field current remains constant at Maximum value of ; reachedafter sudden 3-phase short circuit dont

    decay.

    The torque in a cylindrical-rotor synchronousmachine is given by 7.79)Therefore the short-circuit torque is

    ( ) where

  • 8/14/2019 Project report (2) 3rd sem n.docx

    64/117

    ( after shortcircuit)

    And Therefore,

    = .(7.79)

    If the synchronous machine has

    as its

    rated phase values of voltage and currentrespectively, then rated torque is given by .(7.80)From Eqs. (7.79) and (7.80)

    .(7.81)If With this,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    65/117

    (7.82)In Eq. (5), ratio of short-circuit torque to rated

    torque is maximum, when sint=1,

    i.et=90o

    Therefore

    If ,then

    It is seen from above that maximum value of

    torque, after sudden 3-phase short circuit, is

    several times greater than its rated torque.

    7.6 Sudden reactive loading and unloading:

    In this case, variation of currents and voltages is

    investigated when sudden reactive loading or

  • 8/14/2019 Project report (2) 3rd sem n.docx

    66/117

    unloading of synchronous generators carried

    out.

    7.6.1 Sudden reactive loading:

    It is assumed that the synchronous generator is

    initially unloaded and is developing a nominal

    terminal voltage at synchronous speed. The

    nature of balanced reactive loading may be

    inductive or capacitive.

    (a)Sudden inductive loading:

    For a sudden inductive loading, the load

    reactance XL is taken to be lumped with the

    alternator internal reactances and then sudden

    short circuit is assumed to occur at its

    terminals. Thus the r.m.s value of armature

    phase current at any time t is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    67/117

    =

    .(7.83)

    Where load time constant TL , is ..(7.84)The voltage across the load reactance XLat anytime t is given by Therefore, 0 1..(7.85)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    68/117

    The variation of field current after sudden

    inductive loading XL,is given by

    0

    1..(7.86)The variation of excitation voltage with time is

    given by

    =

    0

    1

  • 8/14/2019 Project report (2) 3rd sem n.docx

    69/117

    =

    0 1(7.87)Starting of large induction motors is a fairly

    good example of sudden inductive loading of

    synchronous generators.

    Examination of Eq. (8) shows that just after

    sudden inductive loading , the terminal voltage

    at once drops from Efoto OA=. This value

    decreases finally to

    with a load time

    constant of , as depicted in fig. (7.17)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    70/117

    Fig. 7.17 Variation of alternator terminal

    voltage with sudden inductive loading

    (b)Sudden capacitive loading:

    The behavior of an alternator for sudden

    capacitive loading can be obtained simply by

    replacing XLwith (-XC).

    From Eq. (7.83) the r.m.s value of armature

    current is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    71/117

    (7.88)Where

    (7.89)

    From Eq. (7.85) , the voltage across the load

    reactance Xcis given by

    .(7.90)From Eq.(7.86) the field current is given by

    0 1..(7.91)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    72/117

    From Eq. (7.87)

    0 1..(7.92)Sudden switching of a long transmission line is

    a common example of sudden capacitive

    loading of synchronous generators.

    Equation (7.90) reveals that just after the

    sudden capacitive loading ,i.e at t=0+ the

    voltage at once varies from Efoto .Thisvalue changes from

    to its final value

    with a load time constant of

    .

    7.6.2 Sudden reactive unloading:

  • 8/14/2019 Project report (2) 3rd sem n.docx

    73/117

    The synchronous generator ,running at

    synchronous speed is initially connected to a

    reactive load.Here the behavior of alternator isinvestigated first with sudden removal of

    inductive load and then with the sudden

    removal of capacitive load.

    (a)Sudden inductive unloading:

    In this case since the armature current ,after

    the load has been disconnected, is zero,its

    expression is not of much importance.For the

    field current, the voltage expression is given by

    ( ) .(7.93)We know from generalized theory of dc

    machine

  • 8/14/2019 Project report (2) 3rd sem n.docx

    74/117

    And

    Here and , before the inductive load isremoved, are and . After the load isremoved and are and Zerorespectively. Due to this the superimposed field

    voltage .Therefore the total field current =

    ..(7.94)After the load is disconnected, excitation

    voltage and terminal voltage are equal.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    75/117

    Therefore

    0 1 .(7

    .95)

    If

    is the load terminal voltage before the

    load is disconnected,then Or

    * +(7.96)

    Substituting in Eq. (7.95) , the value of fromEq. (7.96), we get

  • 8/14/2019 Project report (2) 3rd sem n.docx

    76/117

    *

    + 0 1

    .(7.97)

    An examination of Eq. (7.97) shows that just

    after the inductive load is disconnected,

    terminal voltage at once rises to * +=OB. The increase from * + to its finalvalue

    * + with a time constant

    as shown in fig 7.18.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    77/117

    Fig. 7.18 Variation of alternator terminal

    voltage with sudden inductive unloading

    (b)Sudden capacitive unloading:

    The behavior of an alternator for sudden

    capacitive unloading can again be obtained

    simply by replacing XLwith (-XC) as before.

    In view of this ,field current from Eq. (7.94) is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    78/117

    (7.98)

    from Eq. (7.96) is,

    The terminal voltage from eq. (7.97), is * + 0

    1

    .(7.99)

    7.7 Transient Analysis: a qualitative

    approach

  • 8/14/2019 Project report (2) 3rd sem n.docx

    79/117

    In this article e, a simple qualitative treatment of

    the transient behavior of the alternator, after a

    sudden three-phase short circuit is presented.For simplicity, the synchronous machine

    resistances are neglected. With this assumption,

    the total flux linkages with any close circuit

    cant change suddenly at the time of any

    disturbance. In other words, the flux linkagesafter sudden disturbance in any close circuit

    remain constant at their predisturbance value-

    this fact has come to be known as constant flux

    linkage theorem.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    80/117

    Fig. 7.19 The Symmetrical waveforms for

    armature short-circuit current for a 3-phase

    synchronous generator

    With zero armature resistance, the steady-state

    armature short circuit current lags the excitation

    voltage

    by 90 as shown in fig(). This figure

    shows that short circuit armature m.m.f.

    is in

    the d-axis of the machine, consequently d-axis

    parameter are mainly involved during the short

    circuit analysis. This conclusion is revealed by

    Eq. (), which shows that the armature short-

    circuit is affected by d-axis parameter

    and.The Symmetrical waveforms for armature short-

    circuit current for a 3-phase synchronous

    generator is shown in fig. 7.19.

    7.7.1 Reactances and Time-constants from

    Equivalent circuits

  • 8/14/2019 Project report (2) 3rd sem n.docx

    81/117

    Expressions for the reactances

    and time constants

    can be derived fromthe transformer-type equivalent circuits of asynchronous machine.

    7.7.2 Reactances from equivalent-circuits

    d-axis synchronous reactance of a synchronousmachine is given by ; is the d-axismagnetizing reactance.

    d-axis transient reactance of a synchronousmachine is given by

  • 8/14/2019 Project report (2) 3rd sem n.docx

    82/117

    Fig.7.20 d-axis equivalent circuit for a

    synchronous machine without damper bars

    d-axis sub-transient reactance of a synchronous

    machine is given by

    Fig 7.21 (a)d-axis equivalent circuit with

    damper bars but field winding assumed

    absent

    (b) d-axis equivalent circuit for a

    synchronous machine

  • 8/14/2019 Project report (2) 3rd sem n.docx

    83/117

    7.7.3 Time constants from equivalent-circuits

    (a) Direct-axis open circuit transient time

    constant,

    (b) Direct-axis short circuit transient time

    constant,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    84/117

    Fig 7.22 Determination of time constant (c) Direct-axis open-circuit sub-transient time

    constant, 0 1(d) Direct-axis open-circuit sub-transient

    time constant,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    85/117

    7.7.4 Transient power angle characteristics:

    In this article, it is assumed that a sudden 3phase short circuit occur at terminals of

    alternator which is initially working under

    loaded conditions. After the disturbance,

    according to constant flux linkage theorem in a

    closed circuit, here the flux remain constant atits pre-disturbance value. Alternatively, it may

    be assumed that the voltage regulator action

    takes place so as to keep the field flux linkages

    constant at their pre-disturbance value.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    86/117

    Minus sign before is due to the fact thatshort-circuit armature m.m.f opposes the field

    flux. The -axis armature flux linkage

    From Eq.(7.101) Substitution of this value in Eq. (1) gives

    . /

  • 8/14/2019 Project report (2) 3rd sem n.docx

    87/117

    Here

    Is the -axis transient inductance.Multiplication of Eq. (7.102) by gives

    or

    [

    ]

    or The generalized form of voltage equation of

    alternator is ( )

  • 8/14/2019 Project report (2) 3rd sem n.docx

    88/117

    From the above equation of , if armatureresistance and transformer voltage are

    neglected, then ( ) After putting the value of Eq.(70.104) willbecome

    ( ) Dividing every term of the above equation bywe get its rms value.

    (

    ) Now this equation is suitable to draw the phasor

    diagram of synchronous machine which is

    shown in below.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    89/117

    Fig.7.23 Synchronous generator phasor

    diagram under transient condition

  • 8/14/2019 Project report (2) 3rd sem n.docx

    90/117

    Eq.(7.106) shows that when field flux linkage

    are considered constant ,the voltage

    remains constant during the transient state.

    In order to analyse sudden disturbance or

    sudden load application a power angle

    expression is useful.

    The power for synchronous machine is given by But And

    ( )

  • 8/14/2019 Project report (2) 3rd sem n.docx

    91/117

    .

    / The power angle expression of Eq.(7.107) isapplicable for a period of time short as

    compared with the transient time constant .This period of time less than , is sufficientto cover the critical period in many transient and

    dynamic analysis. If the field flux linkagesare maintained constant, then Eq.(7.107) isapplicable till the period of time ismaintained substantially constant by the voltage

    regulator action.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    92/117

    Fig. 7.24 The steady-state and transient

    power angle characteristics of synchronous

    machine

    In Fig.(7.24) the steady-state and transient

    power angle characteristics of a typical

    synchronous machine, from which it is seen that

    the general shape of the two curves is almost

    similar. Since is greater than , thefundamental term of power has larger

    magnitude during transient state. The physical

    reason of the transient amplitude being greaterthan the steady state amplitude is that, just after

    the short-circuit, there is a suddenly induced

    component of field current which results in

  • 8/14/2019 Project report (2) 3rd sem n.docx

    93/117

    greater excitation of the machine. Transient

    power angle curve of figure.(7.24) shows that a

    synchronous machine in a practical system canwithstand a large suddenly applied power

    overload, provided its duration is relatively

    short as compared with . The transient powerangle expression of Eq.(7.107) is usually

    simplified by neglecting the second harmonic

    term. The Fig.(7.23) shows isalmost equal to in magnitude. Though

    is less than

    , yet it is almost

    equal to the power given by Eq.(7.107). This is

    due to the fact that numerical value of second

    harmonic term in Eq.(7.107) is negative and the

    total transient power is equal to the difference of

    first term and the second harmonic term. Inview of this the transient the transient power is

    given by

  • 8/14/2019 Project report (2) 3rd sem n.docx

    94/117

    is more accurate than the use of Eq.(7.107)withtransient saliency ignored ( ) .Thevoltage equation

    leads to the

    equivalent circuit of Fig. (7.25),

    Fig.7.25. Approximate transient equivalentcircuit of a synchronous machine.

    which is commonly employed when transients

    and dynamics of a complex multi machine

    system are to be investigated even with the help

    of computers. The voltage is called thevoltage behind transient reactance.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    95/117

    Note that the use of the equivalent circuit is

    based on two assumptions as under:

    (i) The voltage behind transient reactanceduring the transient state is assumed constant.

    This means that the field flux constants are

    maintained constant during the transient time

    much less as compared to

    .

    (ii) The reactance and under transientconditions equal. This assumption onlypermits the neglect of transient saliency and

    enable to model the synchronous machine

    under transient condition by a single transient

    reactance of Fig.(7.25)

    7.7.5 Phasor diagram under transient and

    sub transient condition:

    Under transient conditions, the direct axis

    transient reactance is and q-axis transient

  • 8/14/2019 Project report (2) 3rd sem n.docx

    96/117

    reactance is . Fig.(7.23) reveals thatunder transient conditions,

    Here is the q-axis component of terminalvoltage .If is the d-axis component of,sothat

    ,then under transient

    conditions, In magnitude, , therefore .It is seen from Fig.(7.23) that is almost equalto

    , where

    Here voltage is called the voltage behindtransient reactance.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    97/117

    Fig 7.26 Synchronous generator (a) Phasor

    diagram (b) Equivalent circuit diagram

    under sub-transient condition

    Under sub transient conditions, the d-axis and

    q-axis sub transient reactances are andrespectively. The phasor sum of

  • 8/14/2019 Project report (2) 3rd sem n.docx

    98/117

    And

    is shown in the Fig.(7.26.a). The resultant of and is equal to .It is seen from thefigure that is almost equal to ,where

    The voltage

    is called the voltage behind

    subtransient reactance

    .Eq.(7.109) results in

    subtransient equivalent circuit of a synchronous

    machine. With the help of Figs.(7.23) and

    (7.26.a), one phasor diagram showing

    is illustrated in Fig.(7.27).The voltage

    , is

    called vopltage behind d-axis synchronous

    reactance,is given by .

  • 8/14/2019 Project report (2) 3rd sem n.docx

    99/117

    Note that and are almost are equal inmagnitude. This simplified phasor diagram of

    Fig.(7.27) is often for doing the analysis of asynchronous machine connected to a power

    system network.

    Note that in fig.(7.27)

    Fig. 7.27 Phasor diagram for the initial

    current and voltages under overloaded

    alternator

  • 8/14/2019 Project report (2) 3rd sem n.docx

    100/117

    for , , i.e. Sub-transientsaliency is ignored,

    for , , i.e. transientsaliency is ignored,and for , , i.e. Steady-statesaliency is ignored.

    If the effect of damper bar is included then the

    rms value of symmetrical, or a.c. component of

    short-circuit armature current is

    .

    / .

    /

  • 8/14/2019 Project report (2) 3rd sem n.docx

    101/117

    In in a power system network, asynchronous

    machine is represented by Fig.(7.26.b) under

    transient conditions.

    7.8 Synchronous machine dynamics (electro-

    mechanical transients):

    Under normal running condition, the relative

    velocity between stator and rotor fields is zero.Whenever this relative position is disturbed,

    synchronizing restoring torques tending to

    maintain this equality come into play. This

    tendency of rotor to attain synchronous speed

    after a slight disturbance, is the basic reason forthe analysis of synchronous- machine dynamics.

    The phenomena involving rotor oscillations

    about its final equilibrium position is called

    hunting. The nature of synchronous machine

    oscillations or hunting can be known only if its

    electro-mechanical transients are investigated.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    102/117

    The cause of disturbances in synchronous

    machines may be any one of the following:

    (i) A sudden change of load.(ii) A fault in the supply system.(iii) A sudden change in the field current,(iv) Load torque containing harmonic

    torques in case of motors, or prime-mover

    torque containing harmonic torques in caseof synchronous generators.

    The effect of rotor oscillations on the

    performance of the synchronous machines is

    given below:(i) It increases the mechanical stresses and

    fatigue of the shaft.

    (ii) When working as a generator, the outputvoltage fluctuates which is an undesirable

    phenomenon(iii) It increase the machine losses and,

    therefore, increases its operating

    temperature.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    103/117

    (iv) The rotor oscillations may cause themachine to fall out of step.

    7.8.1Electro-mechanical equation:

    In a synchronous machine the general torque

    balance equation is

    Where = electromagnetic torque=mechanical torque= torque due to inertia of rotor

    =damping torque

    Neglect of the mechanical damping torquegives 7.8.2 Generator operation:

  • 8/14/2019 Project report (2) 3rd sem n.docx

    104/117

    In generator, electric power flows out of it.

    Likewise electric torque

    , corresponding to

    electric power, flows out of the generator, should, therefore, be treated as negative. In viewof this, Eq.(7.111) becomes;

    Here , is the mechanical torque input tothe generator. Also Where

    power due to inertia of rotor =

    In above equation it is given that

    has two

    component.

  • 8/14/2019 Project report (2) 3rd sem n.docx

    105/117

    One component is synchronous power, is due to

    the presence of load angle

    between

    and

    .

    That is given by Where And Where damping constant inwatts per radian per second.

    and= Power input to the shaft of alternatorTherefore the required electromechanical

    equation is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    106/117

  • 8/14/2019 Project report (2) 3rd sem n.docx

    107/117

    Subtraction of Eq.(7.113) from Eq.(7.114) gives

    After some mathematical manipulation the

    Eq.(7.115) can be reduced to

    Though

  • 8/14/2019 Project report (2) 3rd sem n.docx

    108/117

    Where synchronizing power per electricalradian.

    Therefore Eq.(7.116), can be re-written as,

    Eq.(7.117) is a second order linear differentialequation and may be written as,

    .

    / where .It is usually convenient to write Eq.(7.118) as

  • 8/14/2019 Project report (2) 3rd sem n.docx

    109/117

    A comparison of Eqs.(7.118) and (7.119)gives,

    and

    The solution of Eq.(7.119) consists of two parts,

    complementary function(C.F) and the particular

    integral(P.I).

    Complementary function:C.F. Particular integral:

  • 8/14/2019 Project report (2) 3rd sem n.docx

    110/117

    P.I The complete solution of Eq.(7.118) is C.F+ P.I

    The solution of Eq.(7.119) depends upon thevalue of damping factor or damping ratio which may be less than, equal to, or greater thanunity. For different value of , the solution ofEq.(7.119) is as under:

    0

    1

  • 8/14/2019 Project report (2) 3rd sem n.docx

    111/117

    For

    ,

    For ,With initial conditions,

    and For ,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    112/117

    With initial conditions,

    and

    Therefore , - , -Where

    natural frequency of oscillation

    natural damped angularfrequency and damping ratio

  • 8/14/2019 Project report (2) 3rd sem n.docx

    113/117

    The plot of Eqs.(7.122),(7.123),(7.124) and

    (7.125) are given for different values of

    damping ratio and it is seen that the magnitudeof oscillations can be controlled by varying .

    The value of (or ); as stated before, can beincreased by using large cross-sectional damperbars. This will decrease the magnitude of rotor

    oscillations.

    7.9 Cyclic variation of shaft torque (orForced Oscillations)

  • 8/14/2019 Project report (2) 3rd sem n.docx

    114/117

    An alternator driven by an internal combustion

    engine or a synchronous motor driving a

    reciprocating compressor is subjected tovariable shaft torques. The variable torque is

    equivalent to an average torque plus a large

    variety of harmonic torques. If any one of the

    harmonic torque component has a frequency

    approaching , the amplitude of oscillationsincreases and the machine may fall out of step.Such a state of affairs must be carefully

    investigated. If the frequencydiffers by morethan 25% from the frequency of forced

    oscillations, it is then assumed that stable

    operation remains unaffected.

    Let the harmonic-torque component variable

    shaft torque be represented by

    ;

    where is the maximum amplitude ofharmonic torque and its angular frequency is

  • 8/14/2019 Project report (2) 3rd sem n.docx

    115/117

    . Also, (synchronous speed of themachine)

    ( )

    The differential equation of motion governing

    the performance of synchronous machine under

    forced oscillation is

    d

    or

    d

    or

    d

    where, as before,

  • 8/14/2019 Project report (2) 3rd sem n.docx

    116/117

  • 8/14/2019 Project report (2) 3rd sem n.docx

    117/117

    ||

    For a given value of , the correspondingchange in synchronous power is ||watts