Page 1: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication
Page 2: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Safety Precautions Observe the following notices to ensure personal safety or to prevent accidents. To ensure that you use this product correctly, read this User’s Manual thoroughly before use. Make sure that you fully understand the product and information on safety. This manual uses two safety flags to indicate different levels of danger.

WARNING If critical situations that could lead to user’s death or serious injury is assumed by mishandling of the product. -Always take precautions to ensure the overall safety of your system, so that the whole system remains safe in the event of failure of this product or other external factor. -Do not use this product in areas with inflammable gas. It could lead to an explosion. -Exposing this product to excessive heat or open flames could cause damage to the lithium battery or other electronic parts.

CAUTION If critical situations that could lead to user’s injury or only property damage is assumed by mishandling of the product. -To prevent excessive exothermic heat or smoke generation, use this product at the values less than the maximum of the characteristics and performance that are assured in these specifications. -Do not dismantle or remodel the product. It could cause excessive exothermic heat or smoke generation. -Do not touch the terminal while turning on electricity. It could lead to an electric shock. -Use the external devices to function the emergency stop and interlock circuit. -Connect the wires or connectors securely. The loose connection could cause excessive exothermic heat or smoke generation. -Do not allow foreign matters such as liquid, flammable materials, metals to go into the inside of the product. It could cause excessive exothermic heat or smoke generation. -Do not undertake construction (such as connection and disconnection) while the power supply is on. It could lead to an electric shock.

Copyright / Trademarks -This manual and its contents are copyrighted. -You may not copy this manual, in whole or part, without written consent of Panasonic

Industrial Devices SUNX Co., Ltd. -Windows is a registered trademark of Microsoft Corporation in the United States and other countries. -All other company names and product names are trademarks or registered trademarks of their respective owners.

PLC_ORG

Page 3: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

i

Table of Contents Before You Start

1. Functions and Restrictions of the Unit ................................................. 1-1

1.1 Features and Functions of the Unit ............................................................................... 1-2 1.1.1 Functions ..................................................................................................................... 1-2

1.2 Unit Types ........................................................................................................................ 1-4 1.2.1 Multi Communication Unit ........................................................................................... 1-4 1.2.2 Communication Blocks ............................................................................................... 1-4

1.3 Restrictions on Units Combination ............................................................................... 1-5 1.3.1 Restrictions on Installation position and Number of Units .......................................... 1-5

2. Specifications and Functions ................................................................ 2-1

2.1 FP2 Multi Communication Unit ...................................................................................... 2-2 2.1.1 Parts and Functions .................................................................................................... 2-2

2.2 FP2 Communication Blocks ........................................................................................... 2-4 2.2.1 Types of Communication Blocks................................................................................. 2-4 2.2.2 Names and Major Applications of Port ....................................................................... 2-6

2.3 Table of Specifications ................................................................................................... 2-7 2.3.1 General Specifications ................................................................................................ 2-7 2.3.2 Communication Specifications .................................................................................... 2-8

2.4 Confirming the I/O Contacts and Slot Number ........................................................... 2-11 2.4.1 The Role of Input/Output Contacts. .......................................................................... 2-11 2.4.2 Confirming the I/O Number Allocation ...................................................................... 2-12 2.4.3 Confirming Slot Number ............................................................................................ 2-13 2.4.4 Confirming Root No. ................................................................................................. 2-14

3. Installation and Wiring of Communication Blocks .............................. 3-1

3.1 Installation of Communication Blocks .......................................................................... 3-2

3.2 Wiring of Communication Blocks .................................................................................. 3-3 3.2.1 FP2-CB232(AFP2803), FP2-CB422(AFP2804) ......................................................... 3-3 3.2.2 FP2-CB485 (AFP2805) ............................................................................................... 3-4 3.2.3 Selection of Cables ..................................................................................................... 3-6

4. Communication Function ....................................................................... 4-1

4.1 Communication Mode ..................................................................................................... 4-2 4.1.1 PC(PLC) Link Mode .................................................................................................... 4-2

Page 4: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

ii

4.1.2 General-purpose Serial Communciation Mode ........................................................... 4-3 4.1.3 Computer Link Mode ................................................................................................... 4-3

4.2 Remote Control using Modem ........................................................................................ 4-4

4.3 Settings ............................................................................................................................. 4-5 4.3.1 Operation Mode Setting .............................................................................................. 4-5 4.3.2 Communication Condition Setting ............................................................................... 4-5 4.3.3 Unit No. Setting ........................................................................................................... 4-6

4.4 How to Set ........................................................................................................................ 4-7 4.4.1 Unit No. Setting Switch ............................................................................................... 4-7 4.4.2 Mode Speed Setting Switch ........................................................................................ 4-7 4.4.3 Memory Switch ............................................................................................................ 4-8 4.4.4 Flow Chart ................................................................................................................... 4-9

4.5 Timing for Transmission of Communication Setting Data ........................................ 4-10

5. Communication Function: PC(PLC) Link .............................................. 5-1

5.1 Overview of Funcation .................................................................................................... 5-2 5.1.1 What is PC(PLC) Link ................................................................................................. 5-2 5.1.2 Operation of PC(PLC) link ........................................................................................... 5-3

5.2 Setting the Operation Mode and Baud Rate ................................................................. 5-4 5.2.1 Setting using Mode Speed Setting Switch .................................................................. 5-4 5.2.2 Setting of Unti Numbers .............................................................................................. 5-4 5.2.3 Link Relay and Link Register Allocations .................................................................... 5-6

5.3 Monitoring ...................................................................................................................... 5-12

5.4 Connection Example of PLC Link ................................................................................ 5-13 5.4.1 When using three PLCs ............................................................................................ 5-13 5.4.2 Sample program ........................................................................................................ 5-15

5.5 PC(PLC) Link Response Time ...................................................................................... 5-16

5.6 Troubleshooting (PC(PLC) Link) .................................................................................. 5-18

6. Communication Function: General-purpose Serial communication .. 6-1

6.1 Overview of Funcation .................................................................................................... 6-2 6.1.1 What is General-purpose Serial Communication ........................................................ 6-2

6.2 Setting the Operation Mode and Baud Rate ................................................................. 6-4 6.2.1 Setting using Mode Speed Setting Switch .................................................................. 6-4 6.2.2 Setting using Memory Switch ...................................................................................... 6-5

6.3 I/O Allocation .................................................................................................................... 6-6

6.4 Communication with External Devices ......................................................................... 6-8

Page 5: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

iii

6.4.1 Programming Example of General-purpose Serial Communication ........................... 6-8

6.5 Data Transmission F159 (MTRN) Instruction ................................................................ 6-9

6.6 Data Reception F161 (MRCV) Instruction ................................................................... 6-12 6.6.1 Data to be Sent/Received with MCU ........................................................................ 6-14 6.6.2 Flag Operation in Serial Communication .................................................................. 6-15

6.7 Connection with 1:1 Communication (General-purpose Serial Communication) .. 6-18 6.7.1 Connection Example with External Device <1:1 Communication with Micro-Imagechecker> .................................................................................................................. 6-19 6.7.2 Connection Example with External Device <1:1 Communication with FP Series PLC > ........................................................................................................................................... 6-23

6.8 1:N Communication (General-purpose Serial Communication) ............................... 6-28

6.9 Troubleshooting (General-purpose Serial Communication) ..................................... 6-29

7. Communication Function: Computer link ............................................ 7-1

7.1 Overview of Function ...................................................................................................... 7-2 7.1.1 What is Computer Link ................................................................................................ 7-2 7.1.2 Unit Operation ............................................................................................................. 7-3

7.2 Setting the Operation Mode and Baud Rate ................................................................. 7-5 7.2.1 Setting using Mode Speed Setting Switch .................................................................. 7-5 7.2.2 Setting using Memory Switch ...................................................................................... 7-6 7.2.3 Setting of Unit Numbers (C-NET 1:N Communication) ............................................... 7-7

7.3 Connection with Serial Devices ..................................................................................... 7-9 7.3.1 Communication Conditions and Restrictions Relating to Functions ......................... 7-10

7.4 Table of MEWTOCOL Command .................................................................................. 7-12 7.4.1 MEWTOCOL-COM Commands ................................................................................ 7-12 7.4.2 Table of MEWTOCOL-COM Error code ................................................................... 7-12

7.5 Troubleshooting (Computer Link) ............................................................................... 7-13

8. Applications ............................................................................................ 8-1

8.1 Changing Application of COM. Port .............................................................................. 8-3

8.2 Setting Communication Conditions and Monitoring ................................................... 8-4 8.2.1 Example of Communication Condition Setting using F159 (MTRN) Instruction ......... 8-6 8.2.2 Example of Monitoring Communication Condition using F161 (MRCV) Instruction ... 8-7

8.3 MCU Status Monitor ........................................................................................................ 8-8

9. Specifications ......................................................................................... 9-1

Page 6: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

iv

9.1 Table of Specifications .................................................................................................... 9-2 9.1.1 General Specifications ................................................................................................ 9-2 9.1.2 Communication Specifications .................................................................................... 9-3 9.1.3 Setting Communication Conditions and Monitoring .................................................... 9-5 9.1.4 I/O Allocation (General-purpose Serial Communication) ............................................ 9-7

9.2 Appendix ........................................................................................................................... 9-9 9.2.1 Detailed Time Chart of Data Transmission and Reception ......................................... 9-9 9.2.2 Time Chart of Multiplex Reception ............................................................................ 9-10

10. Dimensions and Sample Programs ................................................... 10-1

10.1 Dimensions................................................................................................................... 10-2 10.1.1 FP2 Multi Communication Unit ............................................................................... 10-2 10.1.2 Communication Blocks ............................................................................................ 10-3

10.2 ASCII Codes ................................................................................................................. 10-4

Page 7: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

v

Before You Start

CPU units The CPUs as below are necessary to use this unit. FP2: Ver. 1.50 or later FP2SH: Ver. 1.50 or later Note) The unit does not work due to the CPU error when using the older version than Ver. 1.40. Programming tools The programming tools as below are necessary to use this unit. FPWIN GR: Ver. 2.40 or later FPWIN Pro: Ver. 5.02 or later FP2 communication block is necessary for FP2 Multi Communication Unit. FP2 Multi Communication Unit cannot be used alone. FP2 communication block must be installed for using FP2 Multi Communication Unit. Difference from the conventional models FP2-SDU

FP2-SDU and FP2 Multi Communication Unit is not interchangeable as all uses such as settings or commands are different.

FP2-CCU

FP2-CCU and FP2 Multi Communication Unit is interchangeable, however, there are following differences - Unit number is available. There is no unit number on CCU, but the unit number is available in the computer link mode of MCU. (The default setting for the unit number is 1.) - Command relay function (hierarchy function) for the network unit such as MEWNET-W. It is not available for MCU. - Data transmission by SEND (F145)/RECV (F146) commands. It is not available for MCU.

Page 8: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

vi

Page 9: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 1 Functions and Restrictions of the Unit

Page 10: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

1-2

1.1 Features and Functions of the Unit

1.1.1 Functions

Features and functions of Multi Communication Unit Multi Communication Unit is a communication interface to be used with the programmable controller FP2/FP2SH to connect with serial communication devices. Multi Communication Unit corresponds to multiple communication modes and standards, and has features as below. Adopted the removable serial communication block Three kinds of communication standard, RS232C, RS422 and RS485 are selectable due to the removable serial communication block.

Three kinds of communication mode. There are three modes, general serial, computer link and PC(PLC) link, are available. Depending on the combination with the communication block, it can be connected with many serial communication devices.

Page 11: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

1-3

High-speed and large-capacity communication MCU corresponds to 230 kbps-high-speed communication. Also 2048 characters data per frame can be transmitted.

Note) When setting to 230400 bps, use USB ports at computers. If connecting to RS232C ports, a device open error occurs and communication is not available. Stable communication by double insulation As the areas between the internal circuits and between channels are electrically insulated, it is irrefrangible, and has less effect on connecting devices. The communication is stable.

Program Ladder programs for the general serial communication can be easily created by the special instruction. (Programming is not necessary for the PC (PLC link and the computer link).

Page 12: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

1-4

1.2 Unit Types

1.2.1 Multi Communication Unit

Name Specifications Part No. Product No. FP2 Multi Communication Unit Serial port 2 channels FP2-MCU AFP2465

Key Point: Multi Communication Unit is occasionally abbreviated as “MCU” in this manual.

1.2.2 Communication Blocks

Name Specifications Part No. Product No. FP2 communication block (RS232C) RS232C FP2-CB232 AFP2803 FP2 communication block (RS422) RS422 FP2-CB422 AFP2804 FP2 communication block (RS485) RS485 FP2-CB485 AFP2805

Note: FP2 communication block is necessary for FP2 Multi Communication Unit. FP2 Multi Communication Unit cannot be used alone. Use it with FP2 communication block.

Page 13: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

1-5

1.3 Restrictions on Units Combination

1.3.1 Restrictions on Installation position and Number of Units When using PC(PLC) link function 1. Up to two units, including FP2-MW (Multi-wire link unit) used in W mode, can be used.

2. When CPU is FP2SH, install two units within five units in combination with FP2-MW, FP-CCU and FP2-MCU.

3. When CPU is FP2, install two units within three units in combination with FP2-MW, FP-CCU and FP2-MCU.

When using General-purpose serial communication Can be installed in any position. When using Computer link function Up to eight units of FP2-MCU can be installed.

Note) The restrictions are not related to the number of channels for each unit.

(Either COM.1 port and COM.2 port is counted as one unit in case of the CCU setting.)

Page 14: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

1-6

Page 15: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 2 Specifications and Functions

Page 16: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-2

2.1 FP2 Multi Communication Unit

2.1.1 Parts and Functions

Operation indicator LEDs

Status indicator LED Display Operation

SD Green Send Data monitor

Flashes while data is being sent. Goes out when no data is being sent.

RD Green Receive Data monitor

Flashes while data is being received. Goes out when no data is being received.

ERR Red Communication error

In PC(PLC) link mode: Lights if PC(PLC) link error occurs. In other modes: Lights if communication error occurs. In PC(PLC) link mode: Goes out if PC(PLC) link is liked up. In other modes: Goes out if no communication error occurs.

S. ERR Red Setting error Lights if setting error occurs. (The numbers at the top “1” and “2” mean COM. port No.) Goes out in normal status.

ALARM Red Alarm Lights if unit error occurs. (Lights if watch dog timer error occurs.) Goes out if no error occurs.

Key Point: The communication error LED lights when the receive error occurs. Receive error: Parity, framing, overrun, buffer capacity overflow, receive buffer FULL

Reference: <8.3 MCU Status Monitor> Operation mode LED

Display Operation W0 Green PC(PLC) link mode Lights in PC(PLC) link mode.

GP Green General-purpose serial communication mode

Lights in General-purpose serial communication mode.

MC Green Computer link mode Lights in computer link mode. Note) W0 (PC(PLC) link mode) is not available for COM. 2.

Page 17: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-3

Installation position for communication block

The communication blocks are installed in COM.1 and COM.2. Unit No. setting switch

Unit No. for the COM.1 is set when the PC(PLC) link and computer link is selected for the operation mode. Unit No. can be selected in a range of 1 to 15.

Factory default setting: 0 (memory switch selection)

Mode speed setting switch Used to set the operation mode and communication speed.

Port COM. 1 COM. 2

Switch No. 1 2 3 4 5 6 7 8

Operation mode

Spare OFF OFF OFF OFF PC(PLC) link ON OFF ON OFF

General-purpose serial communication

OFF ON OFF ON

Computer link ON ON ON ON

Baud rate

115200 bps OFF OFF OFF OFF 19200 bps ON OFF ON OFF 9600 bps OFF ON OFF ON

Memory switch ON ON ON ON Note) If selecting the setting marked with diagonal lines, the setting error occurs. Factory default setting Operation mode: Computer link Communication unit No.: 1 (Memory switch and computer link are selected.) Baud rate: 9600 (Memory switch selection) Character bit: 8 Parity: Odd Stop bit length: 1 RS/CS: Disable Note) The factory default settings for the mode speed setting switch (dip SW) are all ON.

Reference: For the detail on the communication settings (unit No., memory switch setting, etc.), refer to <4.3.3 Unit No. Settings> and <4.4.3 Memory Switch>

Page 18: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-4

2.2 FP2 Communication Blocks

2.2.1 Types of Communication Blocks

There are three types of communication cassettes, each having a particular field of application. FP2 communication block (RS232C) FP2-CB232 (AFP2803) This communication block is a 1-channel unit with a five-wire RS232C port. It supports 1:1 computer links, general-purpose serial communication and PC(PLC) link between two units. RS/CS control is possible in general-purpose serial communication mode.

Pin No. Name Abbr. Signal direction 1 (Not connected) (NC) 2 Send Data SD Unit to external devices 3 Receive Data RD External devices to Unit 4 Request to Send RS Unit to external devices 5 Clear to Send CS External devices to Unit

6 (Connection unavailable)

-

7 Signal Ground SG

8 (Connection unavailable)

-

9 Data terminal ready ER Unit to external devices Note1) RS (Request to Send) is controlled at Y contact. Note2) When setting the RS/CS control to “Able”, data cannot be sent without the pin CS (Clear to Send).

When using with a three-wire port, short-circuit the pin RS and CS, or disable them. Note3) The ER signal is shorted in the RS signal and the communication block. Note4) Do not connect to the pin “connection unavailable”. Note5) The shell part and the mounting screw part of the connector is connected to the ground terminals

of the power supply unit. FP2 communication block (RS422) FP2-CB422 (AFP2804) This communication block is a 1-channel unit with a four-wire RS422 port. It supports 1:1 computer link, general-purpose communication and PC(PLC) link (MEWNET-W0) between two units.

Pin No. Name Abbr. Signal direction 1 (Not connected) (NC) 2 Send Data SD+ Unit to external devices 3 Receive Data RD+ External devices to Unit 4 Send Data SD- Unit to external devices 5 Receive Data RD- External devices to Unit

6 (Connection unavailable)

-

7 (Connection unavailable)

-

8 (Connection unavailable)

-

9 (Connection unavailable)

- Unit to external devices

Note1) The shell part and the mounting screw part of the connector is connected to the ground terminals of the power supply unit.

Note2) The terminating resistor (120 Ω) is built in between the RD+ and RD-.

Page 19: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-5

FP2 communication block (RS485) FP2-CB485 (AFP2805) This communication block is a 1-channel unit with a two-wire RS485 port. It supports 1:N computer link, general-purpose serial communication and the PC(PLC) link.

Pin No. Name Abbr. Signal direction

1 Terminal station setting E 2 Transmission line (-) - 3 Transmission line (+) + 4 Transmission line (-) - 5 Transmission line (+) +

Note1) The mounting screws are connected to the ground terminals of the power supply unit. Note2) As for the setting of the terminal unit, short-circuit the terminals E and (-).

The terminating resistor (120 Ω) is built in.

Page 20: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-6

2.2.2 Names and Major Applications of Port

Two communication ports are equipped with FP2 Multi Communication Unit (MCU). By mounting either communication blocks, RS232C, RS422 or RS485, the communication becomes available with external devices.

The upper communication port is called COM. 1 port, and the lower port is called COM. 2 port. Select suitable communication block after determine the following applications.

Port Communication blocks RS232C (AFP2803) RS422 (AFP2804) RS485 (AFP2805)

COM. 1 - Computer link (1:1) - General-purpose serial communication (1:1) Note2)

- Computer link (1:1) - General-purpose serial communication (1:1) Note2)

- Computer link (1:N) - General-purpose serial communication (1:N) - PC(PLC) link (MEWNET-W0)

COM. 2 - Computer link (1:1) - General-purpose serial communication (1:1)

- Computer link (1:1) - General-purpose serial communication (1:1)

- Computer link (1:N) - General-purpose serial communication (1:N)

Note1) MEWTOCOL-COM can be used on all ports which support computer link. With MEWTOCOL-COM, the same commands are supported on both two channels, and frames of up to 2048 bytes (header <) are supported. Note2) The PC(PLC) link with two units is available.

Page 21: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-7

2.3 Table of Specifications

2.3.1 General Specifications

Item Description Ambient temperature 0 to +55 °C Storage temperature -20 to +70 °C Ambient humidity 30 to 85% RH (at 25 °C non-condensing) Storage temperature 30 to 85% RH (at 25 °C non-condensing) Vibration resistance 10 to 55 Hz, 1 cycle/min, double amplitude of 0.75 mm

10 min on X, Y, Z axes Shock resistance Shock of 98 m/s2, 4 times on X, Y, Z axes Noise immunity 1000 Vp-p with pulse widths 50 ns and 1µs (by noise simulator) Operation condition Free from corrosive gases and excessive dust Consumption current Approx. 480 mA Weight (main unit) Approx. 130 g Weight (communication block) Approx. 35 g

Page 22: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-8

2.3.2 Communication Specifications

Item

General-purpose Serial communication

Computer link

(PC) PLC link 1:1 communi-

cation Note1) 1:N communi-

cation Note1) 1:1 communi-

cation Note1)

1:N communi-cation Note1)

AFP 2803

AFP 2804

AFP2805 AFP 2803

AFP 2804

AFP2805 AFP2803 AFP2805

Interface RS232C RS422 RS485 RS232C RS422 RS485 RS232C RS485

Communication method

Full duplex transmission

Two-wire, half duplex

transmission

Half duplex transmission

Two-wire, half duplex

transmission

Token bus (Floating master)

Synchronous method

Start stop synchronous system

Transmission line

Multicore shield wire

Twisted pair shield cable

Multicore shield wire

Twisted pair shield cable

Twisted pair shield cable

Transmission distance

15m (3 m for 115200 bps or more)

Max. 400 m

Max. 1200 m Note2) Note3)

15m (3 m for 115200 bps or more)

Max. 400 m

Max. 1200m Note2) Note3)

1200m (RS485) 3m (RS232C)

Baud rate (to be set by memory switch)

300 to 230400 bps

300 to 230400 bps Note2) Note3)

(19200 bps when C-NET adapter is connected)

300 to 230400 bps

300 to 230400 bps Note2) Note3)

(19200 bps when C-NET adapter is connected)

115200 bps

Transmission code

ASCII, JIS7, JIS8, Binary ASCII, JIS7, JIS8

Communication format (to be set by memory switch)

Data length: 7-bit / 8-bit

Parity:0/None/Even/Odd

Stop bit: 1-bit / 2-bit

Start code: STX/No STX

End code:CR/CR+LF/Time setting/ETX

Number of units

Max. 99 units (32 units max. when C-NET adapter is connected.) Note2)

Max. 99 units (32 units max. when C-NET adapter is connected.) Note2)

Max. 16 units Note4)

PLC link capacity

Link relay: 1024 points Link register: 128 words

Note1)Although it has adequate noise resistance ,It is recommendable to make the user program to execute re-transmission (in order to improve reliability of the communication in case of communication errors occurred by excessive noises or when a receiver equipment cannot receive temporarily.) Nore2)When connecting a commercially available device that has an RS485 interface, please confirm

Page 23: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-9

operation using the actual device. In some cases, the number of units, transmission distance, and baud rate vary depending on the connected device. Note3)The values for the transmission distance, baud rate and number of units should be within the values noted in the graph below.

When using a baud rate of 2400 bps to 38400 bps, you can set up to a maximum of 99 units (stations) and maximum transmission distance of 1200 m. Note4)The number of units of the PLC link with RS232C/RS422 is two. Note5) When setting to 230400 bps, use USB ports at computers. If connecting to RS232C ports, a device open error occurs and communication is not available.

Page 24: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-10

Precaution when using RS485 port RS485 communication is a communication method to perform sending and receiving by two-wire system. Therefore, only one device enables to send data in the communication line at the same time.

Multi Communication Unit (MCU) can send back responses (send data) instantaneously for the transmitted data from other devices . However, depending on other devices connected, it may need a time to open the communication line. In this case, data cannot be sent correctly as the transmitted data from MCU and the transmitted line of the other devices clash. (The above figure shows an example that the transmission “a” and “b” clash.) In this case, it is necessary to adjust the time until starting sending at MCU side, to enable the normal transmission. The time taken until starting the transmission is called “send waiting time”, and specified with the memory switch. 1. MCU setting 2. F159 (MTRN) instruction Specify the necessary waiting time for the “send waiting time” area. Example: With the RS232C/RS485 converter SI35 manufactured by Lineeye Co., Ltd., adjust the response time by this instruction if necessary.

Reference: <9.2 Communication Condition settings and Monitors> <4.4.3 Memory Switch MCU settings>

Page 25: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-11

2.4 Confirming the I/O Contacts and Slot Number

2.4.1 The Role of Input/Output Contacts.

Multi Communication Unit (MCU) has input/output contacts which enable communication with the CPU unit. (They are mainly used in the general-purpose serial communication.) These contacts play various roles, such as alerting the CPU unit when sending and reception have been completed, alerting when an error has occurred, or resetting the port of MCU. The contacts are turned on and off from the CPU unit, which also controls the timing of serial communication being carried out by the MCU.

Page 26: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-12

2.4.2 Confirming the I/O Number Allocation

Like other units, the Multi Communication Unit (MCU) also allocates inputs (X) and outputs (Y). Each MCU has 16 inputs and 16 outputs, for a total of 32 contacts. The I/O numbers and slot numbers are always necessary when creating a program. These vary depending on the position at which the unit is installed in the backplane. Always check to see if the numbers match the design. Confirming the I/O Number Allocations The occupied I/O areas for all of the units mounted between the CPU unit and the MCU should be confirmed. The next number is allocated as I/O areas for the MCU. Example: The following is an example of MCU being mounted in succession following three 16-point I/O units.

Note: • Regardless of the mode settings for the COM. ports, the allocations of 16SX/16SY are necessary,

however, when using the PC link/computer link only, it can be changed to 0 point (0SE) using the tool software.

• If there are any empty slots between the CPU and the Multi Communication Unit (MCU), check to see whether an I/O area has been allocated to the empty slot.

• If I/O mount allocation and automatic allocation are being carried out, 16 points for each type of allocation will automatically be assigned to empty slots.

• If the CPU unit being used is a 2-module type, also check any I/O areas occupying the units incorporated in the CPU unit.

Reference: For information on how I/O allocations are made, refer to <FP2/FP2SH Hardware Manual>.

Page 27: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-13

2.4.3 Confirming Slot Number

When mounted on the CPU backplane Slots are numbered in sequential order, with the slot to the right of the CPU unit being No. 0.

Note: If the CPU unit being used is a 2-module type, the slot number of the units incorporated in the CPU unit should be counted as “0”.

If the CPU unit being used is a CPU unit with S-LINK, the slot number of the unit incorporated in the CPU unit should be counted as “0” and “1”.

When mounted on an expansion backplane The slot number of the slot to the right of the power supply unit on the expansion backplane should be counted as “16”.

Page 28: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

2-14

2.4.4 Confirming Root No.

If multiple Multi Communication Units (MCU) have been installed, they are labeled “Root No. 1”, “Root No. 2” and “Root No. 3” in sequential order, starting from the unit closest to the CPU unit. Root numbers are not used directly in the handling of the Multi Communication Unit, but if a Multi-wire Link Unit (when setting MEWNET-W mode or MEWNET-W2 mode), an ET-LAN unit or a computer communication unit is being used at the same time, these numbers are sometimes specified on the Multi-wire Link Unit or the ET-LAN unit side.

Key Point: When the Multi Communication Unit is being used in the MEWNET-F mode, it is not counted as a Root No. Also when the MCU is being used in the general-purpose serial communication mode, it is not counted as a Root No.

Page 29: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 3 Installation and Wiring of

Communication Blocks

Page 30: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

3-2

3.1 Installation of Communication Blocks 1. Insert a communication block to the COM. port of the main unit.

2. Push the communication block into the main unit until it stops and tighten mounting screws.

(Tightening torque: 0.4 N・m or less)

Page 31: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

3-3

3.2 Wiring of Communication Blocks

3.2.1 FP2-CB232(AFP2803), FP2-CB422(AFP2804)

D-sub connector and connector cover set comes with MCU. Use the attached set or equivalent.

Accessories Manufacturer Product No. D-sub connector J.S.T. Mfg Co.,Ltd Equivalent to JEZ-9P Cover set J.S.T. Mfg Co.,Ltd Equivalent to J-C9-2C

Note1) When using any cover set other than the attached one, the cover set should be the one of which width is 35 mm or less in order to avoid the interference with the connector cover of the COM. 1 and COM. 2. Note2) When using the attached cover set, the cable diameter should be 7 mm or less.

Reference: For the details of the connection examples with external devices, <Chapter 6, Chapter 7 Communication Functions> For the details of the pin names of connectors, <2.2.1 Type of Communication Blocks>

Page 32: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

3-4

3.2.2 FP2-CB485 (AFP2805)

Accessory communication connector/Suitable wire The communication block AFP2805 has a screw-type terminal block. Use the following items for wiring.

Accessory communication connector If additional connectors are needed, use the communication connector manufactured by Phoenix Contact.

Number of pins Phoenix Contact Co. product ID Model No. Product No.

5 pins MC1, 5/5-ST-3, 5 1840395

Reference: For the details of the connection examples with external devices, <Chapter 6, Chapter 7 Communication Functions> For the details of the pin names of connectors, <2.2.1 Type of Communication Blocks>

Suitable wire (twisted wire)

Number of wires Size Cross-sectional area 1 AWG#28 to 16 0.08mm2 to 1.25 mm2

Use the above wires shielded. It is recommended to ground the shielded part. Pole terminals If you wish to use pole terminals, Phoenix Contact offers the following models.

Manufacturer Cross-sectional area Size Product number

With insulating sleeve

Without insulating sleeve

Phoenix Contact Co.

0.25 mm2 AWG#24 AI 0, 25-6 BU A 0,25-7 0.34 mm2 AWG#22 AI 0,34-6 TQ A 0,34-7 0.50 mm2 AWG#20 AI 0, 5-6 WH A 0,5-6 0.75 mm2 AWG#18 AI 0, 75-6 GY A 0,75-6 1.00 mm2 AWG#18 AI 1-6 RD A 1-6

Pressure welding tool for pole terminals

Manufacturer Phoenix Contact product ID Model No. Product No.

Phoenix Contact Co. CRIMPFOX UD6 1204436

Page 33: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

3-5

Screwdriver for terminal block To tighten the terminals of the communication connector, use a screwdriver by Phoenix Contact Co.(product no. 1205037, blade size 0.4 x 2.5, model no. SZS 0,4 x 2,5) or Manufactured by us(part no. AFP0806). The tightening torque should be 0.22 to 0.25 Nm (2.3 kgfcm to 2.5 kgfcm). Wiring method 1. Remove 7 mm of the wire’s insulation.

2. Insert wire into terminal hole until it stops. Tighten screw clockwise to fix wire in place. (Tightening torque: 0.22 Nm to 0.25 Nm (2.3 kgfcm to 2.5 kgfcm)

Notes for wiring • When removing the wire’s insulation, be careful not to scratch the core wire. • Do not twist the wires to connect them. • Do not solder the wires to connect them. The solder may break due to vibration. • After wiring, make sure stress is not applied to the wire. • In the terminal block socket construction, if the wire is fastened upon counter-clockwise rotation of the

screw, the connection is faulty. Disconnect the wire, check the terminal hole, and then re-connect the wire.

Page 34: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

3-6

3.2.3 Selection of Cables

The communication blocks to be selected vary depending on communication blocks. System using AFP2803, AFP2804 Appropriate electrical cables (twisted cables)

Type Cross-sectional view

Conductor Insulator Cable diam.

Sample appropriate

cable Size Resist-ance

(at 20°C) Material Thick-

ness

Shielded multi-core cable

0.3 mm2 (AWG22) or greater

Max. 58.8 Ω/km

vinyl chloride

Max. 0.3 mm

Approx. 6.6 mm

Onamba Co., Ltd.

ONB-D6×0.3mm2

System using AFP2805 Appropriate electrical cables (twisted cables)

Type Cross-sectional view

Conductor Insulator Cable diam.

Sample appropriate

cable Size Resist-ance

(at 20°C) Material Thick-

ness

Shielded twisted

pair

1.25 mm2 (AWG16) or greater

Max. 16.8 Ω/km

Polye-thylene

Max. 0.5 mm

Approx. 8.5 mm

Belden 9860 Hitachi Cable,

Ltd. KPEV-S1.25 mm2 x

1P

0.5 mm2 (AWG20) or greater

Max. 33.4 Ω/km

Polye-thylene

Max. 0.5 mm

Approx. 7.8 mm

Belden 9207 Hitachi Cable,

Ltd. KPEV-S0.5 mm2 x

1P

Note: • Use shielded twisted pair cables. • Use only one type of transmission cable. Do not mix more than 1 type. • Twisted pair cables are recommended in noisy environments. • When using shielded cable with crossover wiring for the RS485 transmission line, grounded one end.

Page 35: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 4 Communication Function

Page 36: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-2

4.1 Communication Mode The following three types of communication function are available with FP2 Multi Communication Unit (MCU).

4.1.1 PC(PLC) Link Mode

• MCU supports the PC(PLC) link of MEWNET-W0 mode. • In a PLC link, data is shared with all PLCs connected via MEWNET using dedicated internal relays

called link relays (L) and data registers called link registers (LD). • If the link relay contact for one PLC goes on, the same link relay also goes on in each of the other

PLCs connected to the network. Likewise, if the contents of a link register are rewritten in one PLC, the change is made in the same link register of each of the other PLCs connected to the network.

• The status of the link relays and link registers in any one PLC is fed back to all of the other PLCs connected to the network, so control of data that needs to be consistent throughout the network, such as target production values and type codes, can easily be implemented to coordinate the data, and the data of all units are updated at the same time.

- Applicable communication block RS232C FP2-CB232 (Product No.: AFP2803) RS485 FP2-CB485 (Product No.: AFP2805) Note) The number of units for the PC(PLC) link with RS232C is up to 2 units.

Note: • Different hardwares are used for MEWNET-W0 and MEWNET-W/MEWNET-W2. They cannot be

mixed in the same network. • Used link relays (L) and link registers (LD) are shared areas with MEWNET-W. Therefore, up to 2 units

of MEWNET-W0 and MEWNET-W specified in the PLC link mode can be used for one CPU system.

Page 37: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-3

4.1.2 General-purpose Serial Communciation Mode

• In general-purpose serial communication, data is sent and received over the COM ports to and from an external device such as an image processing device or a bar code reader.

• Data is read from and written to an external device connected to the COM port by means of an FP2/FP2SH ladder program.

- Applicable communication block For 1:1 communication RS232C FP2-CB232 (Product No.: AFP2803)

RS422 FP2-CB422 (Product No.: AFP2804) For 1:N communication RS485 FP2-CB485 (Product No.: AFP2805) (C-NET)

4.1.3 Computer Link Mode

• Computer link is used for communication with a computer connected to the PLC. Instructions (command messages) are transmitted to the PLC, and the PLC responds (sends response messages) based on the instructions received.

• A proprietary MEWNET protocol called MEWTOCOL-COM is used to exchange data between the computer and the PLC. There are two different communication methods, 1:1 and 1:N communication. A 1:N network is called a C-NET.

• The PLC answers automatically to the commands received from the computer, so no program is necessary on the PLC side in order to carry out communication.

- Applicable communication block For 1:1 communication RS232C FP2-CB232 (Product No.: AFP2803)

RS422 FP2-CB422 (Product No.: AFP2804) For 1:N communication RS485 FP2-CB485 (Product No.: AFP2805) (C-NET)

Page 38: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-4

4.2 Remote Control using Modem Modem initialization When the operation mode is set to the general-purpose serial communication/computer link mode, the modem can be initialized by specifying “able” for the modem initialization setting in the communication condition settings. There are 2 methods to set communication conditions as below. Type Timing for modem initialization command issue Method by MCU setting - When the power turns on.

- When the mode is changed from PROG. to RUN. Method by F159 (MTRN) instruction When F159 (MTRN) instruction is executed.

There are 2 commands for modem initialization as below. Firstly command 1 is sent to the modem and then command 2. Command Description Status of modem initialization 1. ATcR Initialization command H0: Not processed

H0100: Initializing now H0200: Initialization completed.

2. ATSO=1cR Respond at the sound of a beep H20FF: Initialization failed.

Reference: The status can be confirmed by using F161 (MRCV) instruction. <8.3 MCU Status Monitor> Operation flow of modem initialization

Note: The initialization can be executed again if the above modem initialization command is issued even if the initialization has been completed once. In case any commands other than the above 2 commands are issued, any AT command can be issued in the general-purpose serial communication mode.

Page 39: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-5

4.3 Settings Specify modes, communication conditions and unit numbers.

4.3.1 Operation Mode Setting

Specify the mode for each COM. port.

Mode setting Mode speed setting switch

Memory switch MCU setting F159 (MTRN)

PC(PLC) link A N/A N/A General-purpose serial communication A N/A A Computer link A N/A A

(A: Available N/A: Not available)

Reference: <4.4.3 Memory Switch>

4.3.2 Communication Condition Setting

Specify the communication condition for each COM. port. The memory switch setting is made by the MCU setting or F159 (MTRN) instruction.

Item Allowable setting value Initial value Setting

Unit No. 0 to 15 (can be set for COM.1 port only) 1 Note5)

Unit No. setting switch

1 to 99 Memory switch

Baud rate

9600, 19200, 115200 bps

9600

Mode speed setting switch

300 to 230400 bps Only available when selecting memory switch

Memory switch

Character bit 7 bits, 8 bits 8 Memory switch Parity Odd, Even, Parity0, None Parity Odd Memory switch Stop bit length 1 bit, 2 bits 1 Memory switch RS/CS(only with RS232C) Note1) Invalid/Valid Invalid Memory switch

Send Waiting time 0 to 100 ms (0.01 ms unit) 0 Memory switch Only for general-purpose serial communi-cation

Header STX Not exist/Exist Not exist Memory switch

Termi-nator Note2)

cR, cR+Lf, ETX Timeout (0.01 to 100 ms) In 0.01 unit

cR Memory switch

Others Initialize modem Note3)

No/Yes No Memory switch

Note1) When setting the RS/CS to be invalid, the RS signals from MCU can be always received, and the CS signals are always ignored. Note2) If the terminator is set to “Timeout=0”, the data reception will complete when the time for more than approx. 3 characters has passed from the time that last data was received.

Page 40: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-6

Note3) The setting for modem initialization becomes effective whenever the power supply turns on after it was specified by the MCU setting, and ATcr and ATS0=1cr is transmitted. If it failed, it is retried for 5 times. The communication format and baud rate is set to the allowable values for modem communication. Once the modem initialization succeed or failed, it is executed using the “Timing for modem initialization command issue”. Note4) Use a USB port at computer side when it is set to 230400 bps. If a RS232C port is used, communication is not possible due to a device open error. Note5) The default setting of the memory switch is 0 in the PC(PLC) link mode.

4.3.3 Unit No. Setting

Specify unit No.

Mode setting COM. port Unit No. setting switch

Memory switch MCU setting F159 (MTRN)

PC(PLC) link COM. 1 1 to 15 1 to 16 General-purpose serial communication - No need to specify No need to specify

Computer link COM. 1 1 to 15 1 to 99 COM. 2 Not available 1 to 99

Note) COM. 2 port cannot be used in PC(PLC) link mode.

Page 41: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-7

4.4 How to Set How to set is as follows. Unit No. setting switch : Rotary switch at the back of the unit Mode speed setting switch : Dip switch at the back of the unit Memory switch : Setting by the internal memory (MCU setting/F159 (MTRN) instruction)

4.4.1 Unit No. Setting Switch

No. of Unit No. setting switch Unit No.

No. of Unit No. setting switch Unit No.

0 Memory switch Note1) 8 8 1 1 9 9 2 2 A 10 3 3 B 11 4 4 C 12

Rotary SW at the back of the unit

5 5 D 13 6 6 E 14 7 7 F 15

Note1) Sets by the MCU setting and F159 (MTRN) instruction, and sets more than 15 unit numbers. The initial value of the memory switch is 1. (For PC(PLC) link, it is 0.)

Note2) Only COM. 1 port can be set. (COM. 2 port is set by the memory switch.)

4.4.2 Mode Speed Setting Switch

Dip SW at the back of the unit

Port COM. 1 COM. 2 Switch No. 1 2 3 4 5 6 7 8

Operation mode

Spare OFF OFF OFF OFF PC(PLC) link ON OFF ON OFF

General-purpose serial communication

OFF ON OFF ON

Computer link ON ON ON ON

Baud rate

115200 bps OFF OFF OFF OFF 19200 bps ON OFF ON OFF 9600 bps OFF ON OFF ON

Memory switch ON ON ON ON Note) If selecting the setting in any shaded column, the setting error occurs.

Note: When COM2 port is not used, use the factory default setting (initial condition).

Page 42: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-8

4.4.3 Memory Switch

Memory switch is a MCU internal memory for communication settings. There are two methods for setting, such as MCU setting and F159 (MTRN) instruction. What is MCU setting This is a setting display by the programming tool that is exclusive for FP2 Multi Communication Unit. The detailed settings for various communication conditions and unit No. etc, are available, however, the mode setting is not available. Setting procedure using FPWIN GR (Ver 2.4 or later version is necessary.) The MCU setting is not possible online. Go offline, and download after specifying the MCU setting.

Note: When using FP2 CPU unit, the system register “No. 2 Configuration capacity setting” should be set to 2k word in advance. When using FP2SH, this setting is not necessary. 1. Start up “MCU setting” on the “Option” menu. 2. “MCU select the Slot No.” dialog box is shown.

3. Specify the communication conditions correctly in the display below.

Setting using F159 (MTRN) instruction The communication conditions for each COM. port can be specified or changed by using F159 (MTRN) instruction during the ladder program.

Reference: <8.2 Setting Communication Conditions and Monitoring>

Page 43: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-9

4.4.4 Flow Chart

Page 44: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

4-10

4.5 Timing for Transmission of Communication Setting Data

1. The MCU communication setting data by the tool is stored in the CPU during the program download. 2. The MCU communication setting data which is stored in the CPU unit is automatically set in the MCU

when the power turns on, or when changing the mode PROG >RUN. 3. When a communication parameter is specified during the execution of F159 (MTRN) instruction, it is set in the MCU.

Key Point: When setting the communication parameter in the MCU, the communication channel will be reset. (It takes about 1 second to complete the COM. port setting.) However, this operation is not applied in case of the PC(PLC) link mode. In the PC(PLC) link communication, only unit No. can be changed, and if the parameter is changed by F159 (MTRN) instruction, the communication will not be reset. Reset means “Abort sending” and “Clear receiving and error”. (However, some errors cannot be cleared.) Therefore, when the MCU setting is carried out by the tool, the data which is received in the PROG. mode will be all cleared when the mode is switched to the RUN mode.

Page 45: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 5 Communication Function:

PC(PLC) Link

Page 46: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-2

5.1 Overview of Funcation

5.1.1 What is PC(PLC) Link

• The PLC link is an economic way of linking the maximum of 16 PLCs which are corresponding to MEWNET-W0, using a twisted-pair cable.

• Data is shared between FP2, FP2SH and FPΣ using link relays (L) and link registers (LD). • The statuses of the link relays and link registers of one PLC are automatically fed back to the other

PLCs on the same network. • PC(PLC) link is not the default setting. Therefore, the mode setting switch must be set to “PLC Link” in

order to use this function. PC(PLC) link is only available for the COM.1 port. • Unit numbers and l/ink areas are allocated using the unit No. setting switch or setting tool.

Note: • Different hardwares are used for MEWNET-W0 and MEWNET-W/MEWNET-W2. They cannot be

mixed in the same network.

Reference: For the details on the PC(PLC) link of FPΣ, refer to <Chapter 7 in FPΣ User’s Manual ARCT1F333>.

Page 47: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-3

5.1.2 Operation of PC(PLC) link

• Turning on a link relay contact in one PLC turns on the same link relay in all other PLCs on the same network.

• Likewise, if the contents of a link register in one PLC are changed, the values of the same link register are changed in all PLCs on the same network.

Page 48: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-4

5.2 Setting the Operation Mode and Baud Rate

5.2.1 Setting using Mode Speed Setting Switch

PC(PLC) link (MEWNET-W0) are set using the mode speed setting switch. Setting PC(PLC) link mode

COM. 1 Note) COM. 2 port cannot be used for PC (`PLC) link mode.

1 2 ON OFF

Setting communication format The setting for PC(PLC) link is fixed as below. (The setting made using the memory switch is ignored.)

Setting Setting value Baud rate 115200 bps Character bit 8 bits Parity Odd Stop bit 1 bit RS/CS (Only when using RS232C) Invalid Send waiting time 0.00 ms Header STX not exist Terminator CR Initialize modem No

Note: The mode speed setting switch is at the back of Multi Communication Unit.

5.2.2 Setting of Unti Numbers

For the PC(PLC) link which connects multiple PLCs to the transmission line, the unit number must be specified so that each PLC can be identified. The unit number is specified either by using the unit number setting switch or the memory switch (F159 (MTRN), MCU setting). Note1) Unit numbers should be set sequentially and consecutively, starting from 1, with no breaks between them. If there is a missing unit number in the link system, the transmission time will be longer. Note2) If fewer than 16 units are linked, the transmission time can be shortened by setting the largest unit number in system register no. 47.

Note: In case of PC(PLC) link, the default setting for the memory switch is 0. Change the setting to use it.

Key Point: The priority order for station number settings is as follows: 1. Unit number settings switch 2. SYS1 instruction 3. System registers

Page 49: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-5

Unit numbers are the numbers to identify the different PLCs on the same network. The same number must not be used for more than one PLC on the same network. If unit number setting switch is 0, the memory switch (F159 (MTRN), MCU setting) is valid. If unit number setting switch is a number other than 0, the unit number setting switch is valid, and the unit number setting with the memory switch is ignored.

Note: When using the PC(PLC) link with FP2-CB232 (AFP2803) the number of units is up to two. Setting unit numbers with the setting switch The unit number setting switch is located at the back of the unit. The rotary switch can be used to set a unit number between 1 and 15. (With FP2-CB232 (AFP2803) a maximum of 2 unit number can be set.) Table of switch settings and related unit numbers

Unit No. setting switch

Unit No. Unit No.

setting switch Unit No.

0 Memory switch Note)

8 8

1 1 9 9 2 2 A 10 3 3 B 11 4 4 C 12 5 5 D 13 6 6 E 14 7 7 F 15

Note) Sets by the MCU setting and F159 (MTRN) instruction, and sets more than 15 unit numbers. The default setting of PC(PLC) link is 1, therefore, the unit No. will be 0 without the setting with the memory switch, and PC(PLC) link will be unavailable.

Setting using F159 (MTRN) Setting the unit number setting switch to 0 makes F159 (MTRN) setting valid.

Reference: <8.2 Communication Conditions Settings and Monitor>. Setting using MCU setting Setting the unit number setting switch to 0 makes the MCU setting in the programming tool valid.

Reference: <4.4.3 Memory Switch MCU Settings.>.

Reference: For the details on the PC(PLC) link of FP, refer to <FP User’s Manual ARCT1F333>.

Page 50: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-6

5.2.3 Link Relay and Link Register Allocations Link relays and link registers used with the PC(PLC) link function are allocated to the link area of CPU. The link area is allocated by specifying the system register for the CPU. System registers

No. Name Default value Setting range

For PC (PLC) link 0

40 Specification of range of link relays used for communication 0 0 to 64 words

41 Specification of range of link registers used for communication 0 0 to 128 words

42 Starting number for link relay transmission (No. of first word) 0 0 to 63

43 Link relay transmission size 0 0 to 64 words

44 Starting number for link register transmission (first number ) 0 0 to 127

45 Link register transmission size 0 0 to 127 words

46 PC(PLC) link switching flag Stan-dard

Standard: 1st unit Reverse: 2nd unit

47 Setting of max. unit No. for MEWNET-W0 PC(PLC) link 0 0 to 16 Note)

For PC (PLC) link 1

46 PC(PLC) link switching flag Stan-dard

Standard: 2nd unit Reverse: 1st unit

50 Specification of range of link relays used for communication 0 0 to 64 words

51 Specification of range of link registers used for communication 0 0 to 128 words

52 Starting number for link relay transmission (No. of first word) 64 64 to 127

53 Link relay transmission size 0 0 to 64 words

54 Starting number for link register transmission (first number) 128 128 to 255

55 Link register transmission size 0 0 to 127 words 57 Setting of max. unit No. for MEWNET-W0 PC(PLC) link 0 0 to 16 Note)

Note) The same number must be specified as the maximum unit No. for all the PLCs with PC(PLC) link. The maximum link register transmission size is 127 words. It is not possible to set all the 128 words.

Link area configuration

• Link areas consist of link relays and link registers, and are divided into areas for PC(PLC) link 0 and

PC(PLC) link 1 and used with those units. • The link relay which can be used in an area for either PC(PLC) link 0 or PC(PLC) link 1 is maximum

1024 points (64 words), and the link register is maximum 128 words.

Note: Link areas are the shared areas for MEWNET-W0 (supported by MCU) and MEWNET-W (supported by Multi-wire Link Unit). Therefore, the PC(PLC) link modes with MEWNET-W0 and MEWNET-W are limited up to 2 systems in the combination of PC(PLC) link 0 and 1.

Reference: For the details on MEWNET-W, refer to <FP2 Multi-wire Link Unit Manual ARCT1F284>.

Page 51: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-7

Example of allocation The areas for PC(PLC) link are divided into send areas and receive areas. The link relays and link registers are sent from the send area to the receive area of a different FP2/FP2SH/FPΣ. Link relays and link registers with the same numbers as those on the transmission side must exist in the receive area on the receiving side. For PC(PLC) link 0 Link relay allocation

System registers

No. Name Setting for various units

No. 1 No. 2 No. 3 No. 4 40 Range of link relays used 64 64 64 64 42 Starting No. of word for link relay transmission 0 20 40 0 43 Link relay transmission size 20 20 24 0

Note) No. 40 (range of link relays used) must be set to the same range for all the units. Link register allocation

System registers

No. Name Setting for various units No. 1 No. 2 No. 3 No. 4

41 Range of link registers used 128 128 128 128 44 Starting No. for link register transmission 0 40 80 0 45 Link register transmission size 40 40 48 0

Note) No. 41 (range of link registers used) must be set to the same range for all the units. When link areas are allocated as shown above, the No. 1 send area can be sent to the No. 2, No. 3 and No. 4 receive areas. Also, the No. 1 receive area can receive data from the No. 2 and No. 3 send areas. No. 4 is allocated as a receive area only, and can receive data from No. 1, No. 2 and No. 3, but cannot transmit it to other stations.

Page 52: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-8

For PC(PLC) link 1 Link relay allocation

System registers

No. Name Setting for various units No. 1 No. 2 No. 3 No. 4

50 Range of link relays used 64 64 64 64 52 Starting No. of word for link relay 0 84 104 64 53 Link relay transmission size 20 20 24 0

Note) No. 50 (range of link relays used) must be set to the same range for all the units. Link register allocation

System registers

No. Name Setting for various units No. 1 No. 2 No. 3 No. 4

51 Range of link registers used 128 128 128 128 54 Starting No. for link register transmission 0 168 208 0 55 Link register transmission size 40 40 48 0

Note) No. 41 (range of link registers used) must be set to the same range for all the units. When link areas are allocated as shown above, the No. 1 send area can be sent to the No. 2, No. 3 and No. 4 receive areas. Also, the No. 1 receive area can receive data from the No. 2 and No. 3 send areas. No. 4 is allocated as a receive area only, and can receive data from No. 1, No. 2 and No. 3, but cannot transmit it to other stations.

Note: There is no area for PC(PLC) link 1 with FPΣ. Even when using the PC(PLC) link1 at MCU side, the link relays and link registers No. to be used at FPΣ side are WL0 to WL63 and LD0 to LD127. FP2: WL65 ⇔ WL1 : FPΣ LD200 ⇔ LD136

Page 53: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-9

Partial use of link areas In the link areas available for PC(PLC) link, link relays with a total of 1024 points (64 words) and link registers with a total of 128 words can be used. This does not mean, however, that it is necessary to reserve the entire area. Parts of the area which have not been reserved can be used as internal relays and internal registers. Link relay allocation

No. Name No. No. 40 Range of link relays used for PLC link 50 No. 42 Start address of link relay send area 20 No. 43 Size of link relay send area 20

With the above settings, the 14 words (224 points) consisting of WL50 to WL63 can be used as internal relays.

Link register allocation

No. Name No. No. 41 Range of link registers used for PLC link 100 No. 44 Start address of link register send area 40 No. 45 Size of link register send area 40

With the above settings, the 28 words consisting of LD100 to LD127 can be used as internal registers.

Note: The above example shows the case for PC(PLC) link 0.

Page 54: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-10

Note: Precautions When Allocating Link Areas If a mistake is made when allocating a link area, be aware that an error will result, and communication will be disabled. Avoid overlapping send areas When sending data from a send area to the receive area of another FP2/FP2SH/FPΣ, there must be a link relay and link register with the same number in the receive area on the receiving side. In the example shown below, there is an area between No. 2 and No. 3 which is overlapped, and this will cause an error, so that communication cannot be carried out. Example of link relay allocations

System registers

No. Name Set value of various control units No. 1 No. 2 No. 3

No. 40 Range of link relays used 64 64 64 No. 42 Starting word no. of link relay send area 0 20 30 No. 43 Size of link relay send area 20 20 34

Invalid allocations The allocations shown below are not possible, neither for link relays nor for link registers: - Send area is split

- Send and receive areas are split into multiple segments

Page 55: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-11

Setting the largest unit number for a PC(PLC) link The largest unit number can be set using system register no. 47 (using system register no. 57 for PC(PLC) link 1). [Sample setting]

No. of units linked Setting contents 2 1st unit: Unit no. 1 is set

2nd unit: Unit no. 2 is set A largest unit no. of 2 is set for each.

4 1st unit: Unit no. 1 is set 2nd unit: Unit no. 2 is set 3rd unit: Unit no. 3 is set 4th unit: Unit no. 4 is set A largest unit no. of 4 is set for each.

n Nth unit: Unit no. n is set A largest unit no. of n is set for each.

Note: • Unit numbers should be set sequentially and consecutively, starting from 1, with no breaks between

them. If there is a missing unit number, the transmission time will be longer. • If fewer than 16 units are linked, the transmission time can be shortened by setting the largest unit

number in system register no. 47 (in system register no. 57 for PC(PLC) link 1). • For all PLCs which are linked, the same value should be set for the largest unit number. • If there are fewer than 16 units linked and the largest unit number has not been set (default=16), or the

largest unit number has been set but the unit number settings are not consecutive, or the unit number settings are consecutive but there is a unit for which the power supply has not been turned on, the response time for the PLC link (the link transmission cycle) will be long

Reference: <5.5 PC(PLC) Link Response Time>. Setting PC(PLC) link switching flag PC(PLC) link switching flag can be set using system register no. 46. If it is set to 0 (default value), the first half of the link relay (WL0 to WL63) and register (LD0 to LD127) is used for the first PC(PLC) link unit (PC link W0 or PC link W), and the second half of the link relay (WL64 to WL127) and register (LD128 to LD255) is used for the second PC(PLC) link unit. However, if it is set to 1, the second half of the link relay and register is used for the first PC(PLC) link unit (PC link W0 or PC link W).

Page 56: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-12

5.3 Monitoring When using a PC(PLC) link, the operation status of the links can be monitored using the following relays. Transmission assurance relays For PC(PLC) link 0: R9060 to R906F (correspond to unit no. 1 to 16) For PC(PLC) link 1: R9080 to R908F (correspond to unit no. 1 to 16) If the transmission data from a different unit is being used with the various PLCs, check to make sure the transmission assurance relay for the target unit is on before using the data.

Operation mode relays For PC(PLC) link 0: R9070 to R907F (correspond to unit no. 1 to 16) For PC(PLC) link 1: R9090 to R909F (correspond to unit no. 1 to 16) The operation modes (RUN/PROG.) can be checked for any given PLC.

PLC link transmission error relay R9050 (link 1) to R9054 (link 5) This relay goes on if a problem is detected during transmission.

Key Point: Monitoring the PLC link status In FPWIN GR, the PLC link status items, such as the transmission cycle time and the number of times that errors have occurred, can be monitored by selecting the PLC link switch on the FPWIN GR Status Monitor screen.

Note: Remote programming of the linked PLCs is not possible.

Page 57: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-13

5.4 Connection Example of PLC Link

5.4.1 When using three PLCs

The following example demonstrates how the PLC can be connected to two other FPΣ PLCs using a PLC link connection. In the example shown here, link relays are use. When X1 of control unit no. 1 turns on, Y0 of unit no. 2 turns on. When X2 of unit no. 1 turns on, Y0 of unit no. 3 turns on.

System register settings When using a PC(PLC) link, the settings are fixed as below. (The settings using the memory switch are ignored.)

Setting Setting value Baud rate 115200 bps Character bit 8 bits Parity Odd Stop bit 1 bit RS/CS (Only when using RS232C) Invalid Send waiting time 0.00 ms Header STX not exist Terminator CR Initialize modem No

Unit no. and communication mode settings - Setting for FPΣ of unit no. 1

Name Set value COM port 1 unit no. 1 (setting using the unit no. setting switch) COM port 1 communication mode PC(PLC) link (system register No. 412)

- Setting for FP2 of unit no. 2 Name Set value

COM port 1 unit no. 2 (setting using the unit no. setting switch) COM port 1 communication mode PC(PLC) link (using the mode speed setting switch)

- Setting for FP2SH of unit no. 3 Name Set value

COM port 1 unit no. 3 (setting using the unit no. setting switch) COM port 1 communication mode PC(PLC) link (using the mode speed setting switch)

Key Point: Make sure the same unit number is not used for more than one of the PLCs connected through the PC(PLC) link function. The method of some settings for FP2/FP2SH is different from the method for FPΣ.

Reference: For the details on PC(PLC) link of FPΣ, refer to <FPΣ User’s Manual ARCT1F333>.

Page 58: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-14

Link area allocation - Link relay allocation

System registers

No. Name Set value of various control units No. 1 No. 2 No. 3

No. 40 Range of link relays used 64 64 64 No. 42 Starting no. of link relay send area 0 20 40 No. 43 Size of link relay send area 20 20 24

- Link register allocation

System registers

No. Name Set value of various control units No. 1 No. 2 No. 3

No. 41 Range of link registers used 128 128 128 No. 44 Starting no. of link register send area 0 40 80 No. 45 Size of link register send area 40 40 48

Setting the largest unit number

No. Name Set value No. 47 Largest unit number setting for PC(PLC) link 3

Connection diagram

Reference: For the details on PC(PLC) link of FPΣ, refer to <FPΣ User’s Manual ARCT1F333>.

Page 59: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-15

5.4.2 Sample program

- Control unit no. 1 When X1 is input, L0 of the link relay goes on, and when X2 is input, L1 of the link relay goes on.

- Control unit no. 2 When L0 of the link relay goes on, Y0 is output.

- Control unit no. 3 When L1 of the link relay goes on, Y1 is output.

Page 60: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-16

5.5 PC(PLC) Link Response Time The maximum value for the transmission time (T) of one cycle can be calculated using the following formula.

The various items in the formula are calculated as described below. Ts (transmission time per station) Ts = scan time + Tpc (PLC link sending time) Tpc = Ttx (sending time per byte) x Pcm (PC(PLC) link sending size) Ttx = 1/(baud rate x 1000) x 11 ms …. Approx. 0.096 ms at 115.2 kbps Pcm = 23 + (number of relay words + number of register words) x 4 Tlt (link table sending time) Tlt = Ttx (sending time per byte) x Ltm (link table sending size) Ttx = 1/(baud rate x 1000) x 11 ms …. Approx. 0.096 ms at 115.2 kbps Ltm = 13 + 2 x n (n = number of stations being added) Tso (master station scan time) This should be confirmed using the programming tool. Tlk (link addition processing time) …. If no stations are being added, Tlk = 0. Tlk = Tlc (link addition command sending time) + Twt (addition waiting time) + Tls (sending time for command to stop transmission if link error occurs) + Tso (master station scan time) Tlc = 10 x Ttx (sending time per byte) Ttx = 1/(baud rate x 1000) x 11 ms …. Approx. 0.096 ms at 115.2 kbps Twt = Initial value 400 ms (can be changed using SYS1 system register instruction) Tls = 7 x Ttx (sending time per byte) Ttx = 1/(baud rate x 1000) x 11 ms …. Approx. 0.096 ms at 115. 2 kbps Tso = Master station scan time Calculation example 1 When all stations have been added to a 16-unit link, the largest station number is 16, relays and registers have been evenly allocated, and the scan time for each PLCs is 1 ms. Ttx = 0.096 Each Pcm = 23 + (4 + 8) x 4 = 71 bytes Tpc = Ttx x Pcm = 0.096 x 71 ≒ 6.82 ms Each Ts = 1 + 6.82 = 7.82 ms Tlt = 0.096 x (13 + 2 x 16) = 4.32 ms Given the above conditions, the maximum value for the transmission time (T) of one cycle will be: T max. = 7.82 x 16 + 4.32 + 1 = 130.44 ms Calculation example 2 When all stations have been added to a 16-unit link, the largest station number is 16, relays and registers have been evenly allocated, and the scan time for each PLC is 5 ms Ttx = 0.096 Each Pcm = 23 + (4 + 8) x 4 = 71 bytes Tpc = Ttx x Pcm = 0.096 x 71 ≒ 6.82 ms Each Ts = 5 + 6.82 = 11.82 ms Tlt = 0.096 x (13 + 2 x 16) = 4.32 ms Given the above conditions, the maximum value for the transmission time (T) of one cycle will be: T max. = 11.82 x 16 + 4.32 + 5 = 198.44 ms

Page 61: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-17

Calculation example 3 When all but one station have been added to a 16-unit link, the largest station number is 16, relays and registers have been allocated evenly, and the scan time for each PLC is 5 ms. Ttx = 0.096 Each Ts = 5 + 6.82 = 11.82 ms Tlt = 0.096 x (13 + 2 x 15) ≒ 4.13 ms Tlk = 0.96 + 400 + 0.67 + 5 ≒407 ms Note: The default value for the addition waiting time is 400 ms. Given the above conditions, the maximum value for the transmission time (T) of one cycle will be: T max. = 11.82 x 15 + 4.13 + 5 + 407 = 593.43 ms Calculation example 4 When all stations have been added to an 8-unit link, the largest station number is 8, relays and register have been evenly allocated, and the scan time for each PLC is 5 ms. Ttx = 0.096 Each Pcm = 23 + (8 + 16) x 4 = 119 bytes Tpc = Ttx x Pcm = 0.096 x 119 ≒ 11.43 ms Each Ts = 5 + 11.43 = 16.43 ms Tlt = 0.096 x (13 + 2 x 8) ≒ 2.79 ms Given the above conditions, the maximum value for the transmission time (T) of one cycle will be: T max. = 16.43 x 8 + 2.79 + 5 = 139.23 ms Calculation example 5 When all stations have been added to a 2-unit link, the largest station number is 2, relays and registers have been evenly allocated, and the scan time for each PLC is 5 ms. Ttx = 0.096 Each Pcm = 23 + (32 + 64) x 4 = 407 bytes Tpc = Ttx x Pcm = 0.096 x 407 ≒ 39.072 ms Each Ts = 5 + 39.072 = 44.072 ms Tlt = 0.096 x (13 + 2 x 2) ≒ 1.632 ms Given the above conditions, the maximum value for the transmission time (T) of one cycle will be: T max. = 44.072 x 2 + 1.632 + 5 = 94.776 ms Calculation example 6 When all stations have been added to a 2-unit link, the largest station number is 2, 32 relays and 2 register words have been evenly allocated, and the scan time for each PLC is 1 ms. Ttx = 0.096 Each Pcm = 23 + (1 + 1) x 4 = 31 bytes Tpc = Ttx x Pcm = 0.096 x 31 ≒ 2.976 ms Each Ts = 1 + 2.976 = 3.976 ms Tlt = 0.096 x (13 + 2 x 2) ≒ 1.632 ms Given the above conditions, the maximum value for the transmission time (T) of one cycle will be: T max. = 3.976 x 2 + 1.632 + 1 = 10.584 ms

Note: • In the description, “stations that have been added” refers to stations which are connected between

station no. 1 and the largest station number and for which the power supply has been turned on. • Comparing examples 2 and 3, the transmission cycle time is longer if there is one station that has not

been added to the link. As a result the PC(PLC) link response time is longer.

Page 62: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

5-18

5.6 Troubleshooting (PC(PLC) Link)

Status indicator LEDs Indication Function

ERR Red Communication error Light (on): when PC(PLC) link error occurs Off: when PC(PLC) link is established

S. ERR Red Setting error Light (on): when setting error occurs Off: Normal

Note) When the ERR LED lights out and the SD/RD-LED is flashing, the PC link is operating properly. Troubleshooting

Trouble Contents to check How to confirm Transmission error Link stops (ERR LED lights)

- Is a communication block installed? - Is the wiring correct? - Isn’t there any problem in environments such as noise?

Check the special relays R9050 to R9054 (transmission error flag).

Unit no. overlaps (ERR LED lights)

- Check unit Nos. for each unit. - Is the unit no. setting correct? (Are the unit Nos. set sequentially and consecutively from 1? Isn’t there any overlapping unit no? Isn’t any number over 16 used for unit no?)

Check the special registers DT90161, DT90163 and DT90165 (error content).

PC link area overlaps (ERR LED lights)

- Check if there are overlapping send areas of each unit. - Is the setting of the send/receive areas of PC link correct? (Isn’t it set to send redundantly?)

Check the special registers DT90170, DT90200 and DT90230.

PC link error (ERR LED lights)

- Is a communication block installed? - Is the wiring correct? - Isn’t there any problem in environments such as noise?

Check the special registers DT90160 to DT90247.

Disagreement of max. unit no.(ERR LED lights)

- Check if the same value is set for system register no. 47 (or no. 57) for each unit. - Is the maximum unit no. correct?(Is the same unit no. specified for all connected MCUs? Isn’t any no. over the maximum unit no. used?)

Check the system register.

S.ERR-LED is on. - Is the operation mode setting correct? - Isn’t it used excessively ignoring the usage restrictions?

Read out setting contents using F161 (MRCV) instruction and check the contents.

ALARM lights Hardware error Please contact your dealer. Note) The status can be monitored using the PC(PLC) link monitor of the MCU setting in abnormal conditions.

Page 63: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 6 Communication Function:

General-purpose Serial communication

Page 64: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-2

6.1 Overview of Funcation

6.1.1 What is General-purpose Serial Communication

• In general-purpose serial communication, data is sent and received over the COM ports to and from an external device such as an image processing device or a bar code reader.

• Data is read from and written to an external device connected to the COM port by means of a ladder program of the CPU unit.

Outline of operation To send data to and receive it from an external device using the general-purpose serial communication function, the data transmission and data reception functions described below are used. The F159 (MTRN) instruction and the F161 (MRCV) instruction are used in these operations, to transfer data between the FPΣ and an external device. Sending data Data to be transmitted is stored in the register used as the send buffer. When F159 (MTRN) is executed, the data is output from the COM port.

• The start and end code specified for the memory switch in the communication setting is automatically added to the data that has been sent.

• The maximum volume of data that can be sent by MCU is 2048 bytes including the start and end code.

Page 65: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-3

Receiving data Data received in the COM port is stored in the receive buffer of MCU, and the “reception done” flag goes on. When the “reception done” flag goes on, the data is copied in the operation memory in the CPU using F161 (MRCV) instruction.

• Data can be always received in MCU. • When detecting the completion of data

reception, the “reception done” flag X0 (X2) of MCU turns on.

• When the data reception completes, the data can be copied in the operation memory of the CPU using the F161 (MRCV) instruction.

• No end code is included in the stored data. • The maximum volume of data that can be

received in MCU is 2048 bytes.

Page 66: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-4

6.2 Setting the Operation Mode and Baud Rate

6.2.1 Setting using Mode Speed Setting Switch

The operation mode is set using the mode speed setting switch. Setting general-purpose serial communication mode When COM. 1 and COM. 2 are both set to the general-purpose serial communication mode:

COM. 1 COM. 2 1 2 5 6

OFF ON OFF ON

• The general-purpose serial communication mode can be changed to the computer communication

mode using the F159 (MTRN) instruction.

Reference: <8.2 Setting Communication Conditions and Monitoring> Setting baud rate Baud rates for COM. 1 and COM. 2 ports are specified using the mode speed setting switch. The allowable baud rates specified with the switch are 9600 bps, 19200 bps and 115200 bps. The settings for each baud rate are as below.

Baud rate COM. 1 COM. 2 3 4 7 8

115200 bps OFF OFF OFF OFF 19200 bps ON OFF ON OFF 9600 bps OFF ON OFF ON Memory switch ON ON ON ON

Note) The values specified with this switch will be effective when the power turns on. Setting communication format The other formats are as below. (Default settings)

Setting Setting value Unit No. 1 Baud rate 9600 bps Character bit 8 bits Parity Odd Stop bit 1 bit RS/CS (Only when using RS232C) Invalid Send waiting time 0.00 ms Header STX not exist Terminator CR Initialize modem No

Note) The above setting values can be changed using the memory switch.

Note: The mode speed setting switch is at the back of Multi Communication Unit.

Page 67: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-5

6.2.2 Setting using Memory Switch

There are 2 kinds of settings available for the memory switch, which are the MCU setting using the programming tool and the setting using the F159 (MTRN) instruction. The mode speed setting switch should be set as below to enable the memory switch setting.

Baud rate COM. 1 COM. 2 3 4 7 8

Memory switch ON ON ON ON

Setting using F159 (MTRN) instruction Baud rate and communication format can be specified with this instruction.

Reference: <8.2 Setting Communication Conditions and Monitoring> Setting using MCU setting The detailed settings are specified on the exclusive screen for FP2 Multi Communication Unit using the programming tool.

Reference: <4.3 Settings and 4.4 How to set>

Note: The unit No. setting is not available for the general-purpose serial communication mode.

Page 68: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-6

6.3 I/O Allocation The flag information between MCU and the CPU unit is transmitted using X and Y. For this unit, 16 I/O each for X and Y, totally 32 I/O are allocated. I/O numbers are determined depending on the installation location and the I/O allocations of the other units. I/O numbers (when the unit is installed in the slot 0) (0: OFF, 1: ON)

Input signal Name Description Effective operation mode COM. 1 COM. 2

X0 X2 Reception done flag

When MCU completes the data reception, it turns on. When waiting for data reception: 0 When completing data reception: 1

General-purpose serial communication

X1 X3 PLC data reception done flag

When MRCV is completed, it is set/reset. Reading completes: 1 No reading data: 0 Note1)

X4 X5 Transmission done flag

When transmission is available: 1 During transmission: 0 Note2) When transmission is completed: 1

X6 X7 Reception error

When MRCV is completed, it is set/reset. Errors exist in the data read=1 No error exists in the data read=0 Note1)

X8 X9 CTS signal monitor

Status of the CTS signal sent from the device communicating with. Transmission is possible from MCU=0 Transmission is not possible from MCU=1 The RTS signal from MCU is controllable by Y18 and Y19.

Effective only when setting the RS/CS to be valid and using the communication block AFP2803 (RS232C type).

XA XC Latest reception error

Set when an error occurs during the reception of data by MCU No reception error: 0 Reception error: 1 The details of the reception error can be confirmed by reading out them to the PLC using MRCV instruction. Check X6/X7 to see whether there are errors in each receive buffer or not during multiple reception.

General-purpose serial communication (Reception)

XB XD Setting error Operation mode switch setting error Usage restrictions for the unit (For the details on the errors which the settings exceed the limited values of PC link mode/computer link mode, refer to the exhibit.)

All operation modes

XE XF CH reset done

Communication channels can be reset by turning on Y1E or Y1F. This flag is the signal of its completion. At completion: 1 When Y1E/Y1F is off: 0

General-purpose serial communication

Note1) This flag is effective after the execution of the F161 (MRCV) instruction until one of the following instructions is executed.

1: END instruction (Beginning of scan) 2: F161 (MRCV) instruction 3: Partial input instruction F143 (IORF)

Note2) When the transmission is completed within one scan, it may not be 0.

Page 69: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-7

(0: OFF, 1: ON) Output signal Name Description Effective

communication COM. 1 COM. 2 Y10 to Y17

Y10 to Y17

Undefined Do not turn on “undefined”. (Default setting is 0.)

None

Y18 Y19 RTS signal output

The transmission from the devices communicating with can be controlled by turning this output on. Permit the transmission from the devices communicating=0 Prohibit the transmission from the devices communicating=1 The CTS signal sent from the devices communicating can be monitored by X8 and X9.

Effective only when setting the RS/CS to be valid and using the RS232C communication cassette.

Y1A to Y1D

Y1A to Y1D

Undefined Do not turn on “undefined”. (Default setting is 0.)

None

Y1E Y1F Request to reset CH

Communication channels can be reset by turning on Y1E or Y1F. No request to reset=0 Request to reset=1 After 1 is output and the completion of the reset is confirmed by XE/XF, return to 0. The reset is performed only once when this signal rises. Details on the channel reset operation The following operations are performed. 1: Discontinues transmission 2: Discontinues reception 3: Clears receive buffer 4: Resets communication parameters 5: Clears error information (However, only errors which can be cleared) This function can be used to delete unnecessary received data or to clear errors before starting normal reception.

General-purpose serial communication

Note) The operation to reset channels can be automatically performed by executing the following processes as well as Y1E/Y1F. 1: When setting/changing communication parameters using MTRN instruction. 2: When changing operation modes (switching between the general-purpose communication and the computer link) using MTRN instruction. 3: When turning the PLC power supply on, or when changing the mode from PROG. to RUN in case that the MCU setting has been done using the tool. However, the reset done signal of XE/YF does not turn on in the above case.

Page 70: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-8

6.4 Communication with External Devices

6.4.1 Programming Example of General-purpose Serial Communication

The F159 (MTRN) and F161 (MRCV) instructions are used to send and receive data via the specified COM port. F150 (READ) nor F151 (WRT) instruction which is effective with the serial data unit (AFP2460) is not available with MCU. Transmission of data The amount of data specified by “n” is sent to the external device from among the data stored in the data table, starting with the area specified by “S”, through the COM port specified by “D”. Data can be sent with the start code and end code automatically attached. A maximum of 2048 bytes can be sent. When the program below is run, the eight bytes of data contained in DT101 to DT104 and stored in the send buffer starting from DT100 are sent from COM port 1. MCU starts the transmission within 10 µs normally (within a maximum of 500 µs approx. in the PC(PLC) link mode) right after the execution of the instruction.

Reception of data The data received in the communication port of MCU in the slot No. specified by “S” is read and stored in the data table saved by the specifications from “D1” to “D2”. A maximum of 2048 bytes can be received. In the program below, when X30 (reception done flag) (including the terminator data) turns on, the received data in the COM. 1 port of the MCU located in the slot 3 is stored from DT1 specified for the receive buffer. The number of received bytes is stored in DT0.

Page 71: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-9

6.5 Data Transmission F159 (MTRN) Instruction Communication with external devices is handled through the data registers located in the CPU unit.

Data to be output is stored in the register used as the send buffer (DT), and when the F159 (MTRN) instruction is executed, the data is output from the COM port specified by the MCU installed in the specified slot. The MCU starts the data transmission within 10 μs right after the F159 (MTRN) instruction is executed (when PC(PLC) link is performed, within approx. 500 μs at maximum).

Sample program for sending data The following program transmits the characters “ABCDEFGH (Hex)” to an external device using COM port 1 in the slot 2.

Data table for transmission (send buffer) The data table is specified using F159 (MTRN) instruction.

The program described above is executed in the following sequence. 1) “ABCDEFGH” is converted to an ASCII code and stored in a data register. 2) The data is sent from COM port 1 using the F159 (MTRN) instruction. Explanatory diagram

Page 72: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-10

Key Point: F95 (ASC) instruction The specified character string (12 characters) is converted to an ASCII code, and stored in the area of 6 words starting from the specified address. Terminator When the terminator is not necessary, the setting should be set to “None” on the MCU setting screen. Explanation of data table The data table for transmission starts at the data register specified in S.

Transmission process When the execution condition of the F159 (MTRN) instruction turns on and the “transmission done” flag X4 (X5) is on, operation is as follows: 1. The set data is transmitted in order from the lower-order byte in S+1 of the table. • During transmission, the “transmission done” flag X4 (X5) turns off. (The flag does not turn off right

after the execution of the instruction. It turns on when starting 2 scans. • If the header is set to “STX Exist”, the header is automatically added to the beginning of the data. • The terminator is automatically added to the end of the data.

2. When all of the specified quantity of data has been transmitted, the “transmission done” flag X4 (X5)

turns on. Note) If The transmission time is shorter than the scan time, X4 (X5) may not turn on. When you do not wish to add the terminator (end code) during transmissions: • Specify the number of bytes to be transmitted using a negative number. • If you also do not wish to add a terminator to received data, set the memory switch to “Terminator -

None”. Programming example: The following program transmits 8 bytes of data without adding the terminator.

Page 73: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-11

Key Point: • Do not include the terminator in the transmission data. The terminator is added automatically. • When “STX exist” is specified for the header, do not add the header to the transmission data. The

header is added automatically. • When using the communication block (AFP2803 RS232C type) and setting the RS/CS to be valid,

transmission does not take place until CS (Clear to Send) turns on. If you are not going to connect to the other device, set the RS/CS to be invalid.

• The maximum number of transmission bytes “n” is 2048. (However, the header and terminator are included.) When using the header and terminator subtract the byte numbers for them.

• The contact numbers in parentheses refer to COM port 2.

Reference: <9.2 Appendix (Time Chart)>

Note: Followings can be set using F159 (MTRN) as well as the data transmission. 1. Switching the applications of COM port. 2. Communication conditions.

Reference: <Chapter 8 Applications) > <9.6 F159 (MTRN)/F161 (MRCV) instructions>

Page 74: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-12

6.6 Data Reception F161 (MRCV) Instruction

The “reception done” flag X0 (X2) turns on when MCU receives data. The received data is read from MCU to the PLC using F161 (MRCV) instruction. MCU supports full duplex communication. Even if the data reception is completed, the data for 8 buffer can be received consecutively. It is not necessary to execute F159 (MTRN) instruction again to start the reception. The number of data which MCU can receive is 2048 bytes for 1 buffer (including the terminator).

Data table for reception (receive buffer) The data table is specified using F161 (MRCV) instruction.

Sample program for receiving data 10-byte data received in MCU through COM. 1 port of the MCU in the slot 1 are copied to DT200.

The program described above is executed in the following sequence. 1) Data is received through COM. 1 port and the completion of the data reception is detected. 2) The “reception done” contact turns on. The input of X10 turns on. 3) The received data is sent from the receive buffer to the area starting with data register DT200. Explanation of data table Data sent from an external device connected to the COM port is received in MCU, and the data reception is completed, the “reception done” signal X0 (X2) turns on. When F161 (MRCV) instruction is executed using the “reception done” signal, the data is stored in the receive buffer specified by MRCV instruction.

• Registers are used as the receive buffer. They are specified using the second and third operand of F161 (MRCV) instruction.

• Specify the data registers in system register 416 to 419. • The number of bytes of data received is stored in the starting

address of the receive buffer. The initial value is not necessary.

• Received data is stored in the received data storage area in order from the lower -order byte.

• The receive buffer should be specified to be larger than the supposed data to be received. • If the number of received data cannot be stored in the specified area, the data is copied within that

range only and an operation error occurs. (When the received byte numbers are odd number, the higher byte of the last word is always cleared.)

Page 75: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-13

Reception process When data is sent from an external device, the data is stored in the buffer in MCU as below. (1) Header and terminator is not stored.

(2) When the terminator is received, the “reception done” flag X0 (X2) turns on, and subsequently the next data received are stored in the MCU internal buffer. 8 data of 2048 bytes can be received consecutively. (3) Data is copied in the area specified using the operand when F161 (MRCV) instruction is executed, and the “reception done” flag X0 (X2) turns off. However, note that the “reception done” flag X0 (X2) actually turns off at the beginning of the next scan or later when the I/O is refreshed. When multiplex reception is carried out, the reception done status (status which X0 (X1) is on) remains after the received data are copied using MRCV instruction, therefore, the received data cannot be copied by rising the “reception done” signal. For repeated reception of data, perform the following steps 1 to 3: 1. Receive data 2. Reception done X0 (X2): on 3. Execute F161 (MRCV) instruction to read the received data from MCU Prepare for reception Any special preparation is not necessary to receive data, however, if you want to clear the receive buffer when the first data is received, Y1E (Y1F) must be turned on and the communication channel must be reset. After the completion of the resetting, XE (XF) turns on. Then turn off the request to reset Y1E (Y1F). In this case, the area specified using F161 (MRCV) instruction is not cleared.

Key Point: The contact numbers in parentheses refer to COM port 2.

Reference: <9.2 Appendix (Time Chart)>

Note: Followings can be set using F159 (MTRN) as well as the data reception. 1. Monitoring of communication conditions 2. Monitoring of MCU status

Reference: <Chapter 8 Applications> <9.6 F159 (MTRN)/F161 (MRCV) instructions>

Page 76: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-14

6.6.1 Data to be Sent/Received with MCU

Remember the followings when accessing data in the MCU send and receive buffers: • If a header has been chosen in the communication format settings, the code STX (H02) will

automatically be added at the beginning of the data begin sent. • The data without the Code STX at the reception is stored in the receive buffer, and the “reception

done” flag turns on when the terminator is received. However, if the code STX is added in the middle of the data, the data is stored from the beginning of the receive buffer.

• A terminator is automatically added to the end of the data being sent. • There is no terminator on the data stored in the receive buffer. Sending data: Data written to the send buffer will be sent just as it is. Example: The data “12345” is transmitted as an ASCII code to a device with RS232C port. 1. Data sent using the F95 (ASC) instruction should be converted to ASCII code data.

2. If DT100 is being used as the send buffer, data will be stored in sequential order in the data registers starting from the next register (DT101), in two-byte units consisting of the upper and the lower byte.

Receiving data: Data received using F161 (MRCV) instruction will be copied as it is and stored in specified data registers. Example: The data “12345CR” is transmitted from a device with RS232C port. • If DT200 is being used as the beginning of the receive buffer, received data will be stored in the

registers starting from DT201, in sequential order of first the lower byte and then the upper byte.

Page 77: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-15

6.6.2 Flag Operation in Serial Communication

Header: No-STX, Terminator: CR Receiving data: The “reception done” flag, the “transmission done” flag, the MTRN instruction and MRCV instruction are related as follows:

• For general-purpose serial communication, full duplex transmission must be used. • Receiving data still continues after the “reception done” flag turned on. There are 8 receive buffers of

2048 bytes each internally, therefore, data for the amount of these 8 sets can be received. • Data for the specified byte numbers is transmitted to MCU and the request to send is given when

executing F159 (MTRN) instruction. Transmission starts right after the execution of MTRN instruction. (within 10 µs normally, within 500 µs when using PC(PLC) link)

• Duplex transmission is disabled for the same COM. port after F159 (MTRN) is being executed until transmission is completed. The “transmission done” flag X4 (X5) must be observed. The “transmission done” flag does not turn off right after the execution of MTRN instruction. It will be turned off at the beginning of the next scan or later.

• When an error is detected in the received data, the error flag XA (XC) turns on.

Note: Be aware that although the “reception done” flag X0 (X2) normally changes at the beginning of a scan, it changes even while a scan is in progress if an instruction to refresh partially for MCU is executed.

Key Point: The contact numbers in parentheses refer to COM port 2. The input contact numbers of MCU such as the “transmission done” flag X4 (X5) or the “transmission done” flag X0 (X2) indicate 0 when the MCU is installed in the slot 0. If the MCU is installed any other slots, specify the slot number where it is installed.

Page 78: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-16

Header: STX, Terminator: ETX Receiving data: The “reception done” flag, the “transmission done” flag, and the MTRN instruction are related as follows:

• The data is stored in the receive buffer within MCU in sequential order. When the header is received,

the receive pointer is initialized. • Receiving data still continues after the “reception done” flag turned on. There are 8 receive buffers of

2048 bytes each internally, therefore, data for the amount of these 8 sets can be received. • If there are two headers, data following the second header overwrites the data in the receive buffer. • The “reception done” flag X4 (X5) is turned off when no data is received after executing F159 (MTRN)

instruction. (It does not turn off right after the execution of MTRN instruction. It will be turned off at the beginning of the next scan or later.)

Key Point: There is no relevance between the operation of transmission by F159 (MTRN) instruction and the operation of reception by F161 (MRCV) instruction. MCU can always receive data. • In case of transmission, a request to send is given to MCU using F159 (MTRN) instruction. • In case of reception, received data are copied from MCU using F161 (MRCV) instruction.

Page 79: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-17

Sending data: The “reception done” flag, the “transmission done” flag, and MTRN instruction are related as follows:

• Header (STX) and terminator (ETX) are automatically added to the data being transmitted. The data is

transmitted to an external device. • When the F159 (MTRN) instruction is executed, the “transmission done” flag X4 (X5) goes off. • F159 (MTRN) instruction is used to copy the transmitted data to MCU and request transmission.

Duplex transmission is disabled for the same COM. port while MCU is sending data. The “transmission done” flag X4 (X5) must be observed.

Key Point: • The contact numbers in parentheses refer to COM port 2.

Page 80: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-18

6.7 Connection with 1:1 Communication (General-purpose Serial Communication) Usable communication blocks It is used with all the communication blocks below. • FP2-CB232 AFP2803 (RS232C) • FP2-CB422 AFP2804 (RS422) • FP2-CB485 AFP2805 (RS485) Setting communication format Settings for COM. port

Item Allowable setting value Communication mode General-purpose serial communication Baud rate 300 to 230400 bps Character bit 7 bits, 8 bits Parity Odd, Even, Parity0, None Stop bit length 1 bit, 2 bits RS/CS(only with RS232C) Invalid/Valid Send waiting time 0 to 100 ms (0.01 ms unit) Only for general-purpose serial communi-cation

Header STX STX not exist/STX exist

Terminator cR, cR+Lf, ETX Timeout (0.01 to 100 ms) In 0.01 ms unit

Others Initialize modem No/Yes

Note) The setting must be done according to the devices connected.

Reference: For the details on the method to set, <4.4 How to Set>

Page 81: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-19

6.7.1 Connection Example with External Device <1:1 Communication with Micro-Imagechecker>

Overview The MCU and Micro-Image checker A200/A100 are connected using an RS232C cable. The results of the scan are stored in the registers of the FP2/FP2SH2/FP2SH.

• After the scan start code “%SC

R” has been sent from the FP2 side, the scan result is returned from the Micro-Imagechecker as the response.

Communication format settings for Micro-Image checker To set the communication mode and communication format settings for the Micro-Image checker, select “5: communication” under “5: ENVIRONMENT” on the main menu, and the set the following items.

No. Name Set Value No. 51 Communication mode Normal mode No. 52 Serial settings Baud rate: ………….

Bit length: ………….. Stop bit: …………….. Parity : ………….…... Flow control: ………..

9600 bps 8 bits 1 bit Odd None

No. 53 Serial output settings Output digit: ………… Invalid Digit: ………. Read End: …..……… Process End: ………. Numerical calculation: Judgment: ………….

5 column Repl. 0 None None Output Output

Key Point: • If “Del” is specified for the invalid processing parameter, zero suppression processing will be carried

out on the output data, and the output format will be changed. Always make sure “Repl. 0” is specified. • When outputting data to an external device, numerical calculation is required, so “Out” should be

specified for the “Numerical calculation” parameter. • With the above settings, the following data will be output from the Micro-Image checker.

Page 82: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-20

Connection example with Micro-Image checker A200/A100 <Using AFP2803> RS232C is connected.

Connection example with other RS422 device <Using AFP2804>

Reference: For the details on the connection with RS485 devices, refer to <6.8 Connection with 1:N Communication (General-purpose Serial Communication)>

Page 83: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-21

Procedure of communication In the following example, the Micro-Image checker is connected to COM. 1 port of the MCU in slot 0.

Page 84: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-22

Sample program In the following example, the Micro-Image checker is connected to COM port 1.

Buffer statuses The following shows the statuses of the send and receive buffers when the sample program is run.

Page 85: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-23

6.7.2 Connection Example with External Device <1:1 Communication with FP Series PLC >

Overview Connect the FP2/FP2SH and another FP series PLC using the RS232C interface and the MEWTOCOL-COM communication protocol.

• When the data area read command “%01#RDD00000 00001**C

R” is sent from the FPΣ side, the values of the data register of the PLC connected to the system are sent as a response. For example, if the value K100 is stored in DT0 and the value K200 is stored in DT1 of the PLC, “%01$RD6400C8006F C

R” is sent as a response to the command. If there is an error, “%01!** C

R” is returned ( is the error code).

• In addition to data area read and write commands, MEWTOCOL-COM also provides contact area read and write as well as many other commands.

System register settings of FP series PLCs (FP1, FP1 side) In the default settings, the COM port is set not to be used. For 1:1 general-purpose serial communication, the system registers should be set as shown below. Communication format settings for FP series PLC (FP0, FP1)

No. Name Set Value No. 412 COM port 1 selection of communication mode Computer link No. 413 * Communication format for COM port Character bit: ……

Parity check: ….. Stop bit: ………… Terminator: …….. Header: …………

8 bits Odd 1 bit CR STX not exist

No. 414 * Baud rate for COM port 19200 bps * These settings should be the same as the settings of the connected MCU. Connection to FP series PLCs (FP0, FP1) <Using AFP2803> RS232C • - Connection with FP0 COM port

Page 86: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-24

- Connection with FP1 COM port

Procedure of communication In this example, an FP series PLC is connected to the COM. 1 port of MCU in the slot 3. K100 and K200 are respectively being stored in DT0 and DT1 of the PLC on the other end.

Page 87: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-25

Sample program In the following example, the FP series PLC is connected to COM port 1 in the slot 3. (The contact of MCU is WX3/XY4.)

Buffer statuses The tables below show the statuses of the send and receive buffers when the sample program is run.

Page 88: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-26

Key Point: Contents of the response: If K100 is stored in DT0 and K200 is stored in DT1 of the FP series PLC on the other end, “%01$RD6400C8006FC

R” is returned from the FP series PLC on the other end as the response when the program is executed. The received data is stored in the data registers as shown below.

Extracting the data register values from the PLC on the other end In the program, the data segment of the response from the PLC on the other end is converted to hexadecimal data using the F72 (AHEX) (hexadecimal ASCII → hexadecimal data conversion) instruction and stored in DT50 and DT51, only if the character string “$1” stored in DT1 is detected as a comparison instruction

If an error occurs, “%01!C

R” is returned as the response ( is the error code and is the BCC).

Page 89: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-27

The values of DT50 and DT51 are written in DT0 and DT1 of the PLC connected to the COM. 2 port in the slot 0.

Page 90: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-28

6.8 1:N Communication (General-purpose Serial Communication) Overview Multi Communication Unit (MCU) and the external units having unit numbers are connected using an RS485 cable. Using the protocol that matches the external units, the F159 (MTRN) and F161(MRCV) instructions are used to send and receive data.

Usable communication blocks • FP2-CB485 AFP2805 (RS485) Setting communication format Settings for COM. port

Item Allowable setting value Communication mode General-purpose serial communication Baud rate 2400 to 230400 bps Character bit 7 bits, 8 bits Parity Odd, Even, 0 parity, None Stop bit length 1 bit, 2 bits RS/CS(only with RS232C) Invalid/Valid Send waiting time 0 to 100 ms (0.01 ms unit) Only for general-purpose serial communi-cation

Header STX STX not exist/STX exist

Terminator cR, cR+Lf, ETX Timeout (0.01 to 100 ms) In 0.01 ms unit

Others Initialize modem No/Yes

Note1) The setting must be done according to the devices connected. Note2) Connect the “-“ terminal and the “E” terminal with a lead wire to make the termination resistance of the AFP2805 effective.

Reference: For the details on the method to set, <4.4 How to Set>

Page 91: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-29

6.9 Troubleshooting (General-purpose Serial Communication) Status indicator LEDs

Indication Function

ERR Red Communication error Light (on): when reception error occurs Off: when received data was retrieved

S. ERR Red Setting error Light (on): when setting error occurs Off: Normal

Note) The details can be checked by monitoring the MCU status using F161 (MRCV) instruction. Troubleshooting

Trouble Contents to check How to confirm Communication is not possible. (ERR LED lights)

Is a communication block installed? Check if the communication block is installed firmly.

Is the wiring correct? Check the wiring again. Isn’t there any problem in environments such as noise?

Check the shielding.

S. ERR lights - Is the operation mode setting correct? - Isn’t it used excessively ignoring the usage restrictions?

Read out and check the status using F161 (MRCV) instruction.

Transmission is not possible.

Isn’t the request to send given redundantly during transmission?

Review the program.

In case of RS232C communication block, isn’t transmission forbidden by CTS signal? Isn’t operation error occurring when executing MTRN instruction? Is the setting for the communication conditions the same as the one for the device communicated?

Check the setting reading the status using F161 (MRCV) instruction.

Is the setting of the method for detecting “reception done” the same as the one for the device communicated?

Reception is not possible. Isn’t reception error occurring? Check the setting reading the status using F161 (MRCV) instruction.

Isn’t the reception buffer FULL error occurring? If the error occurs, the operation cannot be restarted without performing CH reset. Is the operation mode general-purpose communication? (Has the operation mode been changed using MTRN instruction?) When data is not received properly: (Isn’t it multiplex reception? Isn’t there garbage in the buffer caused by noise or something?)

Review the program. Check the setting reading the status using F161 (MRCV) instruction.

ALARM lights Hardware error Please contact your dealer.

Page 92: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

6-30

Page 93: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 7 Communication Function:

Computer link

Page 94: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-2

7.1 Overview of Function

7.1.1 What is Computer Link

The computer link mode is used as a communication interface that allows data to be read and written between an device such as a personal computer or display panel and a CPU unit.

Can be connected to a display panel and computer. Enables a 1:1 connection to a display panel and computer. No software program is needed for communication. Economic peer-to-peer communication with a personal computer is possible. This unit can be directly connected with a personal computer through RS232C to collect and write data from it without building up a large-scale network. No communication program is needed on the PLC. The PLC automatically returns responses using the FP series’ MEWTOCOL-COM communication protocol so that there is no need to prepare a communication program at the side of the PLC. Connection with Modem It is possible to receive data over telephone lines from another PLC, by connection modem with your PLC. (Receiving only)

Key Point: “C-NET link” is a communication function with 1:N communication (maximum of 99 units can be connected). When setting to 230400 bps, a USB port should be used at a computer side. When connecting with a RS232C port, the communication is not carried out due the occurrence of a device open error.

Page 95: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-3

7.1.2 Unit Operation

Operation overview of computer link mode (1:1 communication) The computer link mode is a function to read and write data and contact of the CPU unit by the host computer. When an command is sent from a host side, a response is returned from the PLC side. The formats of commands and responses are determined by the MEWTOCOL-COM, which is the communication protocol for the FP series of PLCs. Programs for host side devices such as computers and display panels are created in accordance with the protocol “MEWTOCOL-COM”. More than 20 types of commands are available, including commands for reading and writing the data area and contacts, etc. No program is necessary on the PLC side in order to carry out communication. Example: When the contents of the data registers are read to a host computer

Operation Overview of computer link mode (C-NET 1:N communication) For a 1:N computer link, the computer is connected through a commercially available RS232C-RS485 conversion adapter, and the respective PLCs are wired using an RS485 cable. The computer and the PLC communicate via commands and responses: The computer sends a command specifying the unit number, and the PLC with that unit number sends a response back to the computer.

Note) Lineeye SI-35 is recommended to be used as a conversion adapter.

Page 96: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-4

Key Point: The display panel for the FP series was designed ahead of time in conformance with the MEWTOCOL-COM communication protocol, so there is no need to take the contents of commands into consideration. MEWTOCOL-COM communication protocol for FP series are generally configured as shown below.

Page 97: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-5

7.2 Setting the Operation Mode and Baud Rate

7.2.1 Setting using Mode Speed Setting Switch

The operation mode is set using the mode speed setting switch. Setting general-purpose serial communication mode When COM. 1 and COM. 2 are both set to the general-purpose serial communication mode:

COM. 1 COM. 2 1 2 5 6

ON ON ON ON

• The computer link mode can be changed to the general-purpose serial communication mode using the

F159 (MTRN) instruction.

Reference: <8.2 Setting Communication Conditions and Monitoring> Setting baud rate Baud rates for COM. 1 and COM. 2 ports are specified using the mode speed setting switch. The allowable baud rates specified with the switch are 9600 bps, 19200 bps and 115200 bps. The settings for each baud rate are as below.

Baud rate COM. 1 COM. 2 3 4 7 8

115200 bps OFF OFF OFF OFF 19200 bps ON OFF ON OFF 9600 bps OFF ON OFF ON Memory switch ON ON ON ON

Note) The values specified with this switch will be effective when the power turns on. Setting communication format The other formats are as below. (Default settings)

Setting Setting value Unit No. 1 Baud rate 9600 bps Character bit 8 bits Parity Odd Stop bit 1 bit RS/CS (Only when using RS232C) Invalid Send waiting time 0.00 ms Header STX not exist Terminator CR Initialize modem No

Note) The above setting values can be changed using the memory switch.

Note: The mode speed setting switch is at the back of Multi Communication Unit.

Page 98: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-6

7.2.2 Setting using Memory Switch

There are 2 kinds of settings available for the memory switch, which are the MCU setting using the programming tool and the setting using the F159 (MTRN) instruction. The mode speed setting switch should be set as below to enable the memory switch setting.

Baud rate COM. 1 COM. 2 3 4 7 8

Memory switch ON ON ON ON

Setting using F159 (MTRN) instruction Baud rate and communication format can be specified with this instruction.

Reference: <8.2 Setting Communication Conditions and Monitoring> Setting using MCU setting The detailed settings are specified on the exclusive screen for FP2 Multi Communication Unit using the programming tool.

Reference: <4.3 Settings> and <4.4 How to set>

Page 99: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-7

7.2.3 Setting of Unit Numbers (C-NET 1:N Communication)

In the C-NET link that connects multiple PLCs on the same transmission line, the unit number must be set in order to identify the different PLCs. The unit number is specified either by using the unit number setting switch or the memory switch (F159 (MTRN), MCU setting).

Key Point: The priority order for unit number settings is as follows: 1. Unit number settings switch 2. F159 (MTRN) 3. MCU setting

Unit numbers are the numbers to identify the different PLCs on the same network. The same number must not be used for more than one PLC on the same network. If unit number setting switch is 0, the memory switch (F159 (MTRN), MCU setting) is valid. (Default setting: 1) If unit number setting switch is a number other than 0, the unit number setting switch is valid, and the unit number setting of the MCU setting is ignored.

Note: The unit number should be set to 1 in the 1:1 communication mode.

Reference: For the details on the PC (PLC) link of FPΣ, refer to <FPΣ User’s Manual ARCT1F333>.

Page 100: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-8

Setting unit numbers with the setting switch The unit number setting switch is located at the back of the unit. The rotary switch can be used to set a unit number between 1 and 15. Table of switch settings and related unit numbers

Unit No. setting switch Unit No.

Unit No. setting switch Unit No.

0 Memory switch Note1)

8 8

1 1 9 9 2 2 A 10 3 3 B 11 4 4 C 12 5 5 D 13 6 6 E 14 7 7 F 15

Note1) Sets by the MCU setting and F159 (MTRN) instruction, and sets more than 15 unit numbers. The default setting of the memory switch is 1. Note2) Only COM. 1 port can be specified. (COM. 2 port is specified using the memory switch.)

Setting using F159 (MTRN) instruction Baud rate and communication format can be specified with this instruction.

Reference: <8.2 Setting Communication Conditions and Monitoring> Setting using MCU setting The detailed settings are specified on the exclusive screen for FP2 Multi Communication Unit using the programming tool.

Reference: <4.4.3 Memory Switch MCU Setting>

Page 101: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-9

7.3 Connection with Serial Devices Example of the connection with our operation display panel <Using RS232C (communication block: FP2-CB232) (AIGT0030**)

<Using RS422 (communication block: FP2-CB422) (AIGT0032**)

<Using RS485 (communication block: FP2-CB485) (1:1 connection) (AIGT0032**)

Note: • A shielded cable must be used as the communication cable. In a noisy environment, measures against

noise should be taken, such as using a ferrite core. Take care for the shielded part not to be bare to avoid noises such as static electricity.

• Unit numbers, transmission distance and baud rate vary depending on connected devices. Check them in an actual operation.

Reference: For the details on transmission distance, refer to <2.3.2 Communication Specifications>

Page 102: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-10

7.3.1 Communication Conditions and Restrictions Relating to Functions

Precautions when Using the FP2 CPU Unit <1> If the processing of commands and responses sent from a host computer or display panel extends over multiple frames, a busy error (error code 53) will be returned to other ports if communication is currently being carried out on one port, and communication will be inhibited on those other ports. Combinations to which this restriction applies are shown in the diagram below.

Group A ….. Group comprising the tool port of the CPU unit and the COM. 1 port of Multi Communication Unit (MCU) Group B ….. Group comprising the COM port of the CPU unit and the COM. 2 port of Multi Communication Unit (MCU) A similar restriction also applies if access is being made from another station connected with the link unit.

Key Point: “Multiple frames” means that, if a command or response exceeds 118 bytes, the command or response is divided into multiple segments and transmitted or received. For example, this applies in cases such as when a program is read from a tool port, when commands, which continuously read multiple data, are transmitted from a host side. If using the FP2SH CPU unit, the above restriction does not apply.

Page 103: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-11

Precautions when Using the FP2 CPU Unit <2> Of the commands sent from a host computer or display panel, if the monitor commands (the MC, MD, and MG codes) are used, they cannot be read accurately if two or more devices within the same group are connected.

Group A ….. CPU unit tool port Group B ….. CPU unit COM. port Group C ….. COM. 1 port group of Multi Communication Unit (MCU) Group D ….. COM. 2 port group of Multi Communication Unit (MCU) A similar restriction also applies if access is being made from another station connected with the link unit.

Note: If a monitor command is used for a port in the same group, registered data will be rewritten in sequential order starting from the most recent data, and different data will end up being monitored.

Key Point: Monitoring commands are commands used to implement monitoring after the contact or data to be monitored has been registered on the PLC side. The above restriction does not apply if the FP2SH CPU unit is being used.

Page 104: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-12

7.4 Table of MEWTOCOL Command The following is a table of MEWTOCOL commands that can be used with the FP2 Multi Communication Unit (MCU).

7.4.1 MEWTOCOL-COM Commands RCS Read single point of contact information WCS Write single point of contact information RCP Read plural points of contact information WCP Write plural points of contact information RCC Read word unit of contact information WCC Write word unit of contact information SC Preset word unit in contact area RD Read data area WD Write data area SD Preset of data area RS Read timer and counter set value area WS Write timer and counter set value area RK Read timer and counter elapsed value area WK Write timer and counter elapsed value area MC Registration and reset of monitor contact MD Registration and rest of monitor data MG Monitor execution RR Read system register WR Write system register RT Read PLC status RM Remote control (RUN/PROGRAM mode switching) AB Transmission abort command

7.4.2 Table of MEWTOCOL-COM Error code 40 BCC error Transmission error occurred in received data. 41 Format error Command that does not match the format was received. 42 NOT support error An unsupported command was received. 43 Multi frame process error Another command was received during the processing of multi-

frame. 53 Busy error Command process cannot be received due to the processing of

multi-frame, or as the command during processing is busy. 60 Parameter error Specified parameter does not exist, or cannot be used. 61 Data error There is an error in the contact, data area, data number, size,

range or format specification. 62 Registration over error Number of registration exceeded the restriction, or operation is

performed without registration. 63 PC mode error Invalid command was executed in RUN mode. 65 Protect error Write operation was performed to the program area or system

register in the protect (such as password setting or dip SW) mode or ROM operation mode.

66 Address error There is an error in the specified address data. 67 Missing program

error/Missing data error Program cannot be read as there is no program in program area or an error in memory contents. Or unregistered program was read.

Page 105: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-13

7.5 Troubleshooting (Computer Link) Status indicator LEDs

Indication Function

ERR Red Communication error Light (on): when reception error occurs Off: when received data was retrieved.

S. ERR Red Setting error Light (on): when setting error occurs Off: Normal

Note) The details can be checked by monitoring the MCU status using F161 (MRCV) instruction. Troubleshooting

Trouble Contents to check How to confirm Communication is not possible. (ERR LED lights)

- Is a communication block installed? Check if the communication block is installed firmly.

- Is the wiring correct? Check the wiring again. - Isn’t there any problem in environments such as noise?

Check the shielding.

S. ERR lights - Is the operation mode setting correct? - Isn’t it used excessively ignoring the usage restrictions?

Read out and check the status using F161 (MRCV) instruction.

Transmission is not possible when RD of MCU is flashing.

Is the setting for the transmission conditions correct?

Read out and check the status using F161 (MRCV) instruction.

Is the setting for unit numbers correct? (Does the destination of MEWTOCOL-COM match with the unit no of MCU setting?) Is the mode set to the computer link mode?

Check the setting reading the status using F161 (MRCV) instruction.

In case of % header, isn’t the command length over 118 bytes?

Check the programs of connected devices.

In case of < header, isn’t the command length over 2048 bytes? Isn’t FF specified for the unit No. of the destination?

ALARM lights Hardware error Please contact your dealer.

Page 106: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

7-14

Page 107: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 8

Applications

Page 108: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-2

Page 109: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-3

8.1 Changing Application of COM. Port

An F159 (MTRN) instruction can be executed to change between general-purpose serial communication mode and computer link mode. To do so, specify H8000 for n (the number of transmission bytes) and execute the instruction. Changing from “general-purpose” to “computer link”

Changing from “computer link” to “general-purpose”

Whenever the above instruction is carried out, the mode changes to the other. Note) Current mode can be confirmed by “MCU status monitor”.

Reference: <8.3 MCU Status Monitor>

Note: When the power is turned on, the operating mode specified using the mode speed setting switch takes

effect. This is not available for the COM. port set to PC(PLC) link mode.

Page 110: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-4

8.2 Setting Communication Conditions and Monitoring

Setting communication conditions and motoring using instructions The communication conditions for Multi Communication Unit (MCU) can be changed in ladder programs using F159 (MTRN) instruction. The current communication conditions specified with F159 (MTRN) instruction or the MCU Setting using the programming tool can be monitored using F161 (MRCV) instruction. Settable items, contents and values (monitoring values) are as below.

Address Communi-

cation condition

Setting content and value

Settable operation mode

Remarks

1st word - Received No. of bytes

- Byte no. “24” is stored when monitoring (receiving). It has no meaning when setting.

2nd word Unit No. Note2)

K1 to K99 PC(PLC) link General-purpose

serial communication Computer link

COM. 1: Unit no. setting switch should be set to 0. COM. 2: Can be always set using F159 (MTRN) instruction.

3rd word Baud rate K0: 300 bps K1: 600 bps K2: 1200 bps K3: 2400 bps K4: 4800 bps K5: 9600 bps K6: 19200 bps K7: 38400 bps K8: 57600 bps K9: 115200 bps K10: 230400 bps

General-purpose serial communication

Computer link

There are following conditions to specify using F15 (MTRN) instruction. 1. The speed setting of the mode speed setting switch (at the back of the unit) must be set to the memory switch setting. 2. The setting for the COM. port which was set to PC(PLC) link mode is not available.

4th word Character bit

K0: 7-bit length K1: 8-bit length

General-purpose serial communication

Computer link

5th word Parity K0: No parity K1: Parity 0 K2: Parity odd K3: Parity even

General-purpose serial communication

Computer link

6th word Stop bit length

K0: 1 bit K1: 2 bits

General-purpose serial communication

Computer link

7th word RS/CS Valid/Invalid

K0: Invalid K1: Valid

General-purpose serial communication

Computer link PC(PLC) link

8th word Send waiting time

K0 to K10000 (K0: Immediate)

General-purpose serial communication

Computer link

Effective time=knx0.01 ms(0 to 100 ms)

9th word Header STX

K0: STX invalid K1: STX valid

General-purpose serial communication

10th word Terminator K0: cR K1: cR+LF K2: Time K3: ETX

General-purpose serial communication

For the time (K2), refer to “terminator judgement time”.

11th word Terminator judgement time Note3)

K0 to K10000 General-purpose serial communication

Effective time=knx0.01 ms (However, it is effective only when the terminator setting is “Time (K2)”.)

12th word Initialize modem

K0: Initialize K1: Not initialize

General-purpose serial communication

Computer link

Timing for execution of modem initialization Note4)

Page 111: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-5

Note1) The underlined values are default settings. Note2) When the unit No. setting switch was set to 0, the default setting of the memory switch is 1 for the computer link mode, and 0 for the PC(PLC) link mode. Note3) Supplementary explanation of terminator judgement time

1. When 0 is set, the time taken from the reception of one byte until the reception of the next one byte is the time for 32 bits of the specified baud rate.

Received data

Received data

1 byte 1 byte

If next data is not received within the time for 32 bits, the reception will be deemed to have been completed.

. <Example> In case of 9600 bps, 1/9600x32=3.33 ms 2. When n(n0) is set:

Received data

Received data

1 byte 1 byte

If next data is not received within the time for nx10 μs, the reception will be deemed to have been completed.

Note4) The timing for executing modem initialization is:

1. In case of MCU setting 1) when the power turns on 2) when switching the mode from PROG to RUN.

2. When executing F159 (MTRN) instruction

Reference: For the details on the modem initialization, refer to <4.2 Remote Control using Modem>. Regarding address There is a memory space for the communication condition setting and monitoring within Multi Communication Unit (MCU). n-th byte (n-th word) of the address term indicates the setting read and written using F159 (MTRN) or F161 (MRCV) instruction or the stored address of the register for monitor data.

Page 112: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-6

8.2.1 Example of Communication Condition Setting using F159 (MTRN) Instruction

When the following conditions are specified for the COM. 1 port in the slot 0. Unit No. : K3 : 3 Baud rate : K9 : 115200 bps Character bit : K1 : 8 bits Parity : K3 : Even Stop bit length : K0 : 1 bit RS/CS : K0 : Invalid Send waiting : K100 : 1 ms Header STX : K0 : not exist Terminator : K3 : ETX Terminator setting time : K0 : Unnecessary Initialize modem : K0 : No

Explanation of program operation If R0 is turned on when MCU is in the waiting status for transmission, the above communication conditions are specified for the COM. 1 port in the slot 0.

Key Point: Specify “22 bytes” for the number of bytes of setting data when specifying the communication

conditions. All communication conditions for registers should be specified all at once in advance in order to set the

communication conditions. The head of register (DT10 in the example) specified using F159 (MTRN) instruction is used by the

system. Valid data should be specified from the next address (DT11 in the example). Use the default settings for the conditions which is not needed to be set. Specify the settings for COM. 1 port and COM. 2 port separately. Some conditions cannot be changed depending on operating modes.

Reference: <Column of “Settable operation mode” in 8.2 Setting Communication Conditions and Monitoring>

Page 113: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-7

8.2.2 Example of Monitoring Communication Condition using F161 (MRCV) Instruction

When R0 turns on, the communication condition of COM. 2 port will be stored in the next address (DT101) of the receive buffer starting with DT100 to DT111. An example of data read after the above program was executed is shown below.

DT100 K22 ←Number of bytes K22 (11 words) of the received communication condition data is stored.

DT101 K3 ←Unit No.: 3

DT102 K7 ←Baud rate: 38400 bps

DT103 K1 ←Character bit: 8 bits

DT104 K2 ←Parity: Odd

DT105 K0 ←Stop bit length: 1 bit

DT106 K1 ←RS/CS control: Valid

DT107 K0 ←Send waiting time: Immediate

DT108 K0 ←Header STX: STX not exist

DT109 K0 ←Terminator: cR

DT110 K0 ←Terminator judgement time: Invalid(Valid only when the end code is set to K2: Time.)

DT111 K0 ←Initialize modem: No

Key Point: 12 words should be assured for the receive buffer. COM. 1 port and COM. 2 port should be read separately.

Page 114: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-8

8.3 MCU Status Monitor

The operation mode, the error of the installed communication blocks, or operation status of Multi Communication Unit (MCU) can be checked using F161 (MRCV) instruction. The statuses that can be checked are shown below. The status for each port (COM. 1 port, COM. 2 port) can be read.

Address Confirmed

status Setting content and value Description

1st word - - The system assures. 2nd word Operation

mode K0: Computer link mode K1: General-purpose serial communication mode K2: PC(PLC) link mode K7: In initializing modem

The operation modes specified for the COM. ports can be confirmed.

3rd word Discrimination of communication blocks

K0: Communication block is not installed. K232: AFP2803 (RS232C) K422: AFP2804 (RS422) K485: AFP2805 (RS485)

The installed communication blocks can be confirmed.

4th word Reception error code Note1)

Lower byte Bit 0: Receive buffer overrun Occurs only when an error occurs in the hardware. Bit 1: Framing error Note1-1) Becomes “1” when the character bit and the stop

bit differ from the setting. Bit 2: Parity error Note1-1) Becomes “1” when the parity of the received data

differs from the setting. Higher byte Bit 8: Receive buffer overflow Becomes “1” when the received message length

exceeds 2048 bytes. Bit 9: Receive buffer full error Note1-2)

Becomes “1” when the messages that CPU has not completed to receive exceeds 8 messages.

5th word No. of occurrences of reception error Note2)

H0 to HFFFF Counts the No. of occurrences of reception errors (overrun, framing error, parity error).

6th word Setting error code Note3)

Lower byte Bit 0: Setting error of mode speed setting switch

Becomes “1” when the mode setting of the mode speed setting switch is not acceptable. 1. When setting to OFF٠OFF 2. When setting COM. 2 port to PC link mode

Bit 1: this is the operation mode setting exceeding the usage restrictions for the unit Note5)

Becomes “1” when the setting exceeds the restrictions on the installation of the unit.

Higher byte Bit 8: Error in communication condition setting values

Becomes “1” when the setting value of the communication condition specified by F159 (MTRN) instruction is out of the specification.

Bit 9: Error in transmission data length)

Becomes “1” when the data length of the message transmitted by F159 (MTRN) instruction exceeds 2048 bytes.

Page 115: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-9

Address Confirmed

status Setting content and value Description

7th word Error parameter No. Note4)

K1: Unit No. setting error K2: Baud rate setting error K3: Character bit setting errorK4: Parity setting error K5: Stop bit length setting error K6: RS/CS valid/invalid setting error K7: Send waiting time setting error K8: Header STX setting errorK9: Terminator setting error K10: Terminator judgement time setting error K11: Initialize modem setting error

The bit 8 of the setting error code (communication condition setting value error) becomes “1” when the values that are out of range were specified. This area is the area to discriminate which setting value is abnormal. Note6)

8th word Modem initialization status

Shows the status of the modem initialization process.

H0: Not processed - H100: During initialization Mode LED flashes. H200: Initialization succeeded Modem initialization succeeded. The operation

mode automatically returns to the previous mode. H2FF: Initialization failed Modem initialization failed.

The operation mode automatically returns to the previous mode.

Each action of each operation mode when detecting reception

Error code ER-LED XA (C) X6 (7) Computer link Setting Lights Invalid Invalid General-purpose serial communication

Setting Lights Valid (Off to On) Valid (takes affect right after execution of F161 (MRCV))

PC(PLC) link Setting Note) Invalid Invalid Invalid Note) The error LED in the PC(PLC) link mode goes off when the link was established, and lights when an error occurs in the PC(PLC) link. Operation when detecting setting error Sets the setting error code. XB (D) turns on.

Page 116: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

8-10

Note1)

-: Fixed with 0. Note1-1) Errors may not be detected depending on received data organization. (Example: only when stop bit differs) Note1-2) When a buffer error occurs, MCU stops receiving data. Turn on YE (F) and reset the channel to clear the error. Note2) No. of counts is a ring counter (without code). Note3)

-: Fixed with 0. Note4) It is K0 when no parameter error occurs.

Note5) Reference: <1.3 Restriction on Units Combination>

Note6) Reference: <8.2 Setting Communication Conditions and Monitoring> Example of monitor program When monitoring the status of the COM. 2 port in the slot 3

When R0 turns on, the status of the COM.2 port in the slot 3 is stored in DT1 to DT7 of the receive buffer starting from DT0.

Note: The No. of bytes “K14” for valid received data is stored in the first address of receive buffer. Receive buffer should be assured for 8 words.

Page 117: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 9 Specifications

Page 118: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-2

9.1 Table of Specifications

9.1.1 General Specifications

Item Description Ambient temperature 0 to +55 °C Storage temperature -20 to +70 °C Ambient humidity 30 to 85% RH (at 25 °C non-condensing) Storage temperature 30 to 85% RH (at 25 °C non-condensing) Vibration resistance 10 Hz to 55 Hz, 1 cycle/min, double amplitude of 0.75 mm

10 min on X, Y, Z axes Shock resistance Shock of 98 m/s2, 4 times on X, Y, Z axes Noise immunity 1000 Vp-p with pulse widths 50 ns and 1чs (by noise simulator) Operation condition Free from corrosive gases and excessive dust Consumption current Approx. 480 mA Weight (main unit) Approx. 130 g Weight (communication block) Approx. 35 g

Page 119: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-3

9.1.2 Communication Specifications

Item

General-purpose Serial communication Computer link

(PC) PLC link 1:1 communi-

cation Note1) 1:N communi-

cation Note1) 1:1 communi-

cation Note1)

1:N communi-cation Note1)

AFP 2803

AFP 2804 AFP2805 AFP

2803 AFP 2804 AFP2805 AFP2803

AFP2805

Interface RS232C RS422 RS485 RS232C RS422 RS485 RS232C RS485

Communication method

Half duplex transmission

Two-wire, half duplex

transmission

Half duplex transmission

Two-wire, half duplex

transmission

Token bus (Floating master)

Synchronous method Start stop synchronous system

Transmission line

Multicore shield wire

Twisted pair shield cable

Multicore shield wire

Twisted pair shield cable

Twisted pair shield cable

Transmission distance

15m (3 m for 115200 bps or more)

Max. 400 m

Max. 1200 m Note2) Note3)

15m (3 m for 115200 bps or more)

Max. 400 m

Max. 1200m Note2) Note3)

1200m (RS485) 3m (RS232C)

Baud rate (to be set by memory switch)

300 to 230400 bps

300 to 230400 bps Note2) Note3)

(19200 bps when C-NET adapter is connected)

300 to 230400 bps

300 to 230400 bps Note2) Note3)

(19200 bps when C-NET adapter is connected)

115200 bps

Transmission code ASCII, JIS7, JIS8, Binary ASCII, JIS7, JIS8 −

Communication format (to be set by memory switch)

Character bit: 7-bit / 8-bit

Parity:0/None/Even/Odd Stop bit: 1-bit / 2-bit Header: STX/No STX − Terminator:CR/CR+LF/Time setting/ETX

Number of units −

Max. 99 units (32 units max. when C-NET adapter is connected.) Note2)

Max. 99 units (32 units max. when C-NET adapter is connected.) Note2)

Max. 16 units Note4)

PLC link capacity − − − −

Link relay: 1024 points Link register: 128 words

Page 120: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-4

Note1)Although it has adequate noise resistance ,It is recommendable to make the user program to execute re-transmission (in order to improve reliability of the communication in case of communication errors occurred by excessive noises or when a receiver equipment cannot receive temporarily.) Nore2)When connecting a commercially available device that has an RS485 interface, please confirm operation using the actual device. In some cases, the number of units, transmission distance, and baud rate vary depending on the connected device. Note3)The values for the transmission distance, baud rate and number of units should be within the values noted in the graph below.

When using a baud rate of 2400 bps to 38400 bps, you can set up to a maximum of 99 units (stations) and maximum transmission distance of 1200 m. Note4)The number of units of the PLC link with RS232C/RS422 is two. Note5)When setting to 230400 bps, use USB ports at computers. If connecting to RS232C ports, a device open error occurs and communication is not available.

Page 121: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-5

9.1.3 Setting Communication Conditions and Monitoring

Setting communication conditions and motoring using instructions The communication conditions for Multi Communication Unit (MCU) can be changed in ladder programs using F159 (MTRN) instruction. The current communication conditions specified with F159 (MTRN) instruction or the MCU Setting using the programming tool can be monitored using F161 (MRCV) instruction. Settable items, contents and values (monitoring values) are as below.

Address Communi-

cation condition

Setting content and value

Settable operation mode Remarks

1st, 2nd byte (1st word)

- Received No. of bytes

- Byte no. “24” is stored when monitoring (receiving). It has no meaning when setting.

3rd, 4th byte (2nd word)

Unit No. Note2)

K1 to K99 • PC(PLC) link • General-purpose

serial communication • Computer link

COM. 1: Unit no. setting switch should be set to 0. COM. 2: Can be always set using F159 (MTRN) instruction.

5th, 6th byte (3rd word)

Baud rate K0: 300 bps K1: 600 bps K2: 1200 bps K3: 2400 bps K4: 4800 bps K5: 9600 bps K6: 19200 bps K7: 38400 bps K8: 57600 bps K9: 115200 bps K10: 230400 bps

• General-purpose serial communication

• Computer link

There are following conditions to specify using F15 (MTRN) instruction. 1. The speed setting of the mode speed setting switch (at the back of the unit) must be set to the memory switch setting. 2. The setting for the COM. port which was set to PC(PLC) link mode is not available.

7th, 8th byte (4th word)

Character bit

K0: 7-bit length K1: 8-bit length

• General-purpose serial communication

• Computer link

9th, 10th byte (5th word)

Parity K0: No parity K1: Parity 0 K2: Parity odd K3: Parity even

• General-purpose serial communication

• Computer link

11th, 12th byte (6th word)

Stop bit length

K0: 1 bit K1: 2 bits

• General-purpose serial communication

• Computer link

13th, 14th byte (7th word)

RS/CS Valid/Invalid

K0: Invalid K1: Valid

• General-purpose serial communication

• Computer link

15th, 16th byte (8th word)

Send waiting time

K0 to K10000 (K0: Immediate)

• General-purpose serial communication

• Computer link

Effective time=knx0.01 ms(0 to 100 ms)

17th, 18th byte (9th word)

Header STX K0: STX not exist K1: STX exist

• General-purpose serial communication

19th, 20th byte (10th word)

Terminator K0: cR K1: cR+LF K2: Time (24 bits) K3: ETX

• General-purpose serial communication

For the time (K2), refer to “terminator judgement time”.

21st, 22nd byte (11th word)

Terminator judgement time Note3)

K0 to K10000 (K0: 32 bits)

• General-purpose serial communication

Effective time=knx0.01 ms (However, it is effective only when the terminator setting is “Time (K2)”.)

23rd, 24th byte (12th word)

Initialize modem

K0: Initialize K1: Not initialize

• General-purpose serial communication

• Computer link

Timing for execution of modem initialization Note4)

Page 122: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-6

Note1) The underlined values are default settings. Note2) When the unit No. setting switch was set to 0, the default setting of the memory switch is 1 for the computer link mode, and 0 for the PC(PLC) link mode. Note3) Supplementary explanation of terminator judgement time

1. When 0 is set, the time taken from the reception of one byte until the reception of the next one byte is the time for 32 bits of the specified baud rate.

Received data

Received data

1 byte 1 byte

If next data is not received within the time for 32 bits, the reception will be deemed to have been completed.

<Example> In case of 9600 bps, 1/9600x32=3.33 ms 2. When n(n0) is set:

Received data

Received data

1 byte 1 byte

If next data is not received within the time for nx10 μs, the reception will be deemed to have been completed.

Note4) The timing for executing modem initialization is: 1. In case of MCU setting

1) when the power turns on 2) when switching the mode from PROG to RUN.

2. When executing F159 (MTRN) instruction

Reference: For the details on the modem initialization, refer to <4.2 Remote Control using Modem>. Regarding address There is a memory space for the communication condition setting and monitoring within Multi Communication Unit (MCU). n-th byte (n-th word) of the address term indicates the setting read and written using F159 (MTRN) or F161 (MRCV) instruction or the stored address of the register for monitor data.

Page 123: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-7

9.1.4 I/O Allocation (General-purpose Serial Communication)

The flag information between MCU and the CPU unit is transmitted using X and Y. For this unit, 16 I/O each for X and Y, totally 32 I/O are allocated. I/O numbers are determined depending on the installation location and the I/O allocations of the other units. I/O numbers (when the unit is installed in the slot 0) (0: OFF, 1: ON)

Input signal Name Description Effective operation mode COM. 1 COM. 2

X0 X2 Reception done flag

When MCU completes the data reception, it turns on. When waiting for data reception: 0 When completing data reception: 1

General-purpose serial communication

X1 X3 PLC data reception done flag

When MRCV is completed, it is set/reset. Reading completes: 1 No reading data: 0 Note1)

X4 X5 Transmission done flag

When transmission is available: 1 During transmission: 0 Note2) When transmission is completed: 1

X6 X7 Reception error

When MRCV is completed, it is set/reset. Errors exist in the data read=1 No error exists in the data read=0 Note1)

X8 X9 CTS signal monitor

Status of the CTS signal sent from the device communicating with. Transmission is possible from MCU=0 Transmission is not possible from MCU=1 The RTS signal from MCU is controllable by Y18 and Y19.

Effective only when setting the RS/CS to be valid and using the communication block AFP2803 (RS232C type).

XA XC Latest reception error

Set when an error occurs during the reception of data by MCU No reception error: 0 Reception error: 1 The details of the reception error can be confirmed by reading out them to the PLC using MRCV instruction. Check X6/X7 to see whether there are errors in each receive buffer or not during multiple reception.

General-purpose serial communication (Reception)

XB XD Setting error Operation mode switch setting error Usage restrictions for the unit (For the details on the errors which the settings exceed the limited values of PC link mode/computer link mode, refer to the exhibit.)

All operation modes

XE XF CH reset done

Communication channels can be reset by turning on Y1E or Y1F. This flag is the signal of its completion. At completion: 1 When Y1E/Y1F is off: 0

General-purpose serial communication

Note1) This flag is effective after the execution of the F161 (MRCV) instruction until one of the following instructions is executed.

1: END instruction (Beginning of scan) 2: F161 (MRCV) instruction 3: Partial input instruction F143 (IORF)

Note2) When the transmission is completed within one scan, it may not be 0.

Page 124: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-8

(0: OFF, 1: ON) Output signal Name Description Effective

communication COM. 1 COM. 2 Y10 to Y17

Y10 to Y17

Undefined Do not turn on “undefined”. (Default setting is 0.)

None

Y18 Y19 RTS signal output

The transmission from the devices communicating with can be controlled by turning this output on. Permit the transmission from the devices communicating=0 Prohibit the transmission from the devices communicating=1 The CTS signal sent from the devices communicating can be monitored by X8 and X9.

Effective only when setting the RS/CS to be valid and using the RS232C communication cassette.

Y1A to Y1D

Y1A to Y1D

Undefined Do not turn on “undefined”. (Default setting is 0.)

None

Y1E Y1F Request to reset CH

Communication channels can be reset by turning on Y1E or Y1F. No request to reset=0 Request to reset=1 After 1 is output and the completion of the reset is confirmed by XE/XF, return to 0. The reset is performed only once when this signal rises. Details on the channel reset operation The following operations are performed. 1: Discontinues transmission 2: Discontinues reception 3: Clears receive buffer 4: Resets communication parameters 5: Clears error information (However, only errors which can be cleared) This function can be used to delete unnecessary received data or to clear errors before starting normal reception.

General-purpose serial communication

Note) The operation to reset channels can be automatically performed by executing the following processes as well as Y1E/Y1F. 1: When setting/changing communication parameters using MTRN instruction. 2: When changing operation modes (switching between the general-purpose communication and the computer link) using MTRN instruction. 3: When turning the PLC power supply on, or when changing the mode from PROG. to RUN in case that the MCU setting has been done using the tool. However, the reset done signal of XE/YF does not turn on in the above case.

Page 125: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-9

9.2 Appendix

9.2.1 Detailed Time Chart of Data Transmission and Reception

Explanation of operation

MCU detects the completion of data reception. The reception done flag X0(X2) is taken in the CPU by the I/O refresh operation. Makes the reception done flag X0(X2) be the execution condition, and the received data is copied in

the operation memory using F161 (MRCV). Once copying data completes, the PLC data reception done flag X1(X3) turns on. After completing the execution of the MRCV instruction, the MCU reception done flag turns off. As the MCU reception done flag is taken in by the I/O refresh operation of the CPU, X0(X2) turns off. Also the PLC data reception done flag X1(X3) turns off by the I/O refresh operation.

Precautions The MCU reception done flag (above-mentioned ) turns off within a maximum of 100 µs after the MRCV instruction is executed, so that it may not turn off in the next scan after the execution of the MRCV instruction depending on PLC scan time and the timing to execute the MRCV instruction. In that case, the received data has been copied from the MCU to the CPU, however, note that the reception done flag X0(X2) has been left to be on even in the next scan. It is recommended to execute the MRCV instruction as soon as the reception done flag X0(X2) turned on as mentioned below. If the moment that the reception done flag X0(X2) turns on is not used as the execution condition, the PLC data reception done flag X1(X3) after the execution of the MRCV instruction can be used to tell whether there are any received data or not.

Page 126: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-10

9.2.2 Time Chart of Multiplex Reception

Explanation of operation: The operation if multiplexed data are received when executing the MRCV instruction.

MCU detects the completion of data reception. The reception done flag X0(X2) is taken in the CPU by the I/O refresh operation, however, new data

is received with MCU by then. Makes the reception done flag X0(X2) be the execution condition, and the received data is copied in

the operation memory using F161 (MRCV). Once copying data completes, the PLC data reception done flag X1(X3) turns on. After completing the execution of the MRCV instruction, the reception done flag remains to be on as

the data that has been completed to be received is left in MCU. As the MCU reception done flag is taken in by the I/O refresh operation of the CPU, X0(X2) remains

to be on. Also the PLC data reception done flag X1(X3) turns off by the I/O refresh operation. Makes the reception done flag X0(X2) be the execution condition, and the received data is copied in

the operation memory using F161 (MRCV). Once copying data completes, the PLC data reception done flag X1(X3) turns on. After completing the execution of the MRCV instruction, the MCU reception done flag turns off as the

reception done data disappears. As the MCU reception done flag is taken in by the I/O refresh operation of the CPU, X0(X2) turns off. Also the PLC data reception done flag X1(X3) turns off by the I/O refresh operation.

Page 127: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-11

Precautions The MCU reception done flag (above-mentioned ) turns off within a maximum of 100 µs after MRCV instruction is executed, so that it may not turn off in the next scan after the execution of the MRCV instruction depending on PLC scan time and the timing to execute the MRCV instruction. In that case, the received data has been copied from the MCU to the CPU, however, note that the reception done flag X0(X2) has been left to be on even in the next scan. For only one received data, it is recommended to execute the MRCV instruction as soon as the reception done flag X0(X2) turned on. However, for multiplex reception, as the rise of the reception done flag cannot be detected, use F-type instruction to execute the MRCV instruction for every scan. In that case, the PLC data reception done flag X1(X3) after the execution of the MRCV instruction can be used to tell if there are any received data. The following is the time chart if the F161 (MRCV) instruction is executed twice in one scan.

Page 128: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-12

MCU completes to receive the data 1, and turns the reception done flag on. An error occurs while MCU is receiving the data 2, MCU detects the reception error and turns the reception error flag on. CPU loads the MCU reception done flag and MCU reception error flag which were turned on at

and by the I/O refresh, CPU turns X0(X2) and XA(XC) on. MCU receives the data 3. An error occurs while MCU is receiving the data 4. MCU receives the data 5. An error occurs while MCU is receiving the data 6. MCU receives the data 7. An error occurs while MCU is receiving the data 8. CPU receives the first buffer. As no error is detected during the reception of the first buffer, the reception error flag remains OFF. CPU receives the second buffer. As an error was detected during the reception of the second buffer, the reception error flag turns on.

On state is effective until the next scan. CPU receives the third buffer. As no error is detected during the reception of the third buffer, the reception error flag remains OFF. CPU receives the forth buffer. As an error was detected during the reception of the forth buffer, the reception error flag turns on.

On state is effective until the next scan.

Page 129: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-13

CPU receives the fifth buffer. As no error is detected during the reception of the fifth buffer, the reception error flag remains OFF. CPU receives the sixth buffer. As an error was detected during the reception of the sixth buffer, the reception error flag turns on.

On state is effective until the next scan. CPU receives the seventh buffer. As no error is detected during the reception of the seventh buffer, the reception error flag remains

OFF. CPU receives the eighth buffer. As an error was detected during the reception of the eighth buffer, the reception error flag turns on.

On state is effective until the next scan. As there is no received data in MCU, the reception done flag of MCU turns off. As no error exists in the received data in MCU, the reception error flag turns off. CPU reads the reception done flag of MCU, and turns the reception done flag X0(X2) off. CPU reads the reception error flag of MCU, and turns the reception error flag XA(XC) off. The reception error flag X7(X8) which was set using the MRCV instruction when the data was

received turns off.

Page 130: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

9-14

Page 131: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Chapter 10 Dimensions and Sample

Programs

Page 132: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

10-2

10.1 Dimensions

10.1.1 FP2 Multi Communication Unit

When one AFP2803 or AFP2804 is installed.

When one AFP2805 is installed. Installation space in the panel

Page 133: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

10-3

10.1.2 Communication Blocks

FP2-CB232 (AFP2803) FP2-CB422 (AFP2804)

FP2-CB485 (AFP2805)

Page 134: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

10-4

10.2 ASCII Codes

Page 135: PROGRAMMABLE CONTROLLER FP2 Multi Communication ......1-2 1.1 Features and Functions of the Unit 1.1.1 Functions Features and functions of Multi Communication Unit Multi Communication

Record of changes Manual No. Date Description of changes

ARCT1F396E

ARCT1F396E-1

ARCT1F396E-2

ARCT1F396E-3

ARCT1F396E-4

ARCT1F396E-5

ARCT1F396E-6

SEP.2004

SEP.2004

NOV.2006

JAN.2007

NOV.2008

AUG.2011

JUL.2013

First edition

2nd edition

3rd edition

4th edition

5th edition - Change in Corporate name

6th edition - Change in Corporate name - Fixed Errors

7th edition - Change in Corporate name