  • Chilled Water Distribution System Dynamic Balancing

    Ir. Victor LeungProject Director, J. Roger Preston Limited

  • Chilled Water Distribution System Dynamic Balancing 2

    ContentContent

    Overview of traditional balancingmechanics, drawbacks & limitations

    Chilled water balancing with constant flow valvemechanics and problem

    3 in 1 chilled water dynamic balancingtechnical analysis, benefits

  • Chilled Water Distribution System Dynamic Balancing 3

    Traditional Chilled Water Balancing Traditional Chilled Water Balancing & Control& Control

    Mechanics Initial balancing with commissioning valves

    under full flow condition Maintain index circuit supply/ return pressure

    differential at preset level Modulate cooling coil chilled water control valve

    opening to regulate chilled water flow rate maintain preset indoor space temperature

  • Chilled Water Distribution System Dynamic Balancing 4

    Traditional Chilled Water BalancingTraditional Chilled Water Balancing

    Mechanics Initial balancing with commissioning

    valve under full flow condition Require comprehensive chilled

    water distribution circuit hydraulics analysis to determine initial commissioning valve setting & refinement / adjustment with on site measurement

    Problems Laborious process to determine

    valve setting Prone to improper and incomplete

    commissioning Initial static balancing under full flow

    condition will distorted under dynamic condition

  • Chilled Water Distribution System Dynamic Balancing 5

    Traditional Chilled Water ControlTraditional Chilled Water Control

    Mechanics Modulate chilled water control valve opening to

    regulate chilled water flow rate & maintain preset indoor space temperature

    Problems Space temperature controller can only modulate the

    control valve opening, its effect on chilled water flow rate is unknown

    Relatively high initial resistance due to necessary 50% control valve authority (ie full open control valve resistance = cooling coil + commissioning valve resistance)

  • Chilled Water Distribution System Dynamic Balancing 6

    % of Design Flow

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    Coil

    DRV

    0% 100%

    HydronicHydronic FundamentalsFundamentalsTraditional control valve and Double Regulating ValveTraditional control valve and Double Regulating Valve(index circuit)(index circuit)

  • Chilled Water Distribution System Dynamic Balancing 7

    % of Design Flow

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    Coil

    DRV

    0% 100%

    Coil + DRV

    HydronicHydronic FundamentalsFundamentalsTraditional control valve and double regulating valveTraditional control valve and double regulating valve(index circuit)(index circuit)

  • Chilled Water Distribution System Dynamic Balancing 8

    % of Design Flow

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    Control Valve

    Coil

    DRV

    0% 100%

    Coil + DRV

    HydronicHydronic FundamentalsFundamentalsTraditional control valve and double regulating valveTraditional control valve and double regulating valve(index circuit)(index circuit)

  • Chilled Water Distribution System Dynamic Balancing 9

    % of Design Flow

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    Control Valve

    Coil

    DRV

    0% 100%

    Coil + DRV

    HydronicHydronic FundamentalsFundamentalsTraditional control valve and double regulating valve Traditional control valve and double regulating valve (index circuit)(index circuit)

    Index circuit Total pressure drop

    Index circuit Total pressure drop

  • Chilled Water Distribution System Dynamic Balancing 10

    Chilled Water Balancing with Chilled Water Balancing with Constant Flow ValveConstant Flow Valve

    Mechanics Constant Flow Valves limit chilled water flow rate to below presetProblems Only serves to limit flow rate and do not have system resistance

    balancing function as for commissioning valve since pressure drop across valve remains relatively constant at below preset flow rate

    Introduces noticeable resistance to distribution system as valve balancing action depends on pressure loss across valve

  • Chilled Water Distribution System Dynamic Balancing 11

    33--inin--1 Chilled Water Dynamic Balancing1 Chilled Water Dynamic BalancingMechanics Combine commissioning/ automatic

    balancing/ control valve functions into one

    Deliver exact chilled water flow rate as determined by space temperature controller

    Benefits System initial balancing much

    simplified Improves indoor condition with

    more direct control of chilled water flow rate

    Minimizes system chilled water flow resistance

    Orifice controlled

    by actuator

    Orifice self-adjusted by

    system pressure

  • Chilled Water Distribution System Dynamic Balancing 12

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    CoilDynamic Balancing Control valve

    % of Design Flow0% 100%

    HydronicHydronic FundamentalsFundamentalsDynamic BalancingDynamic Balancing

    Coil

  • Chilled Water Distribution System Dynamic Balancing 13

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    CoilDynamic Balancing Control valve

    % of Design Flow0% 100%

    HydronicHydronic FundamentalsFundamentalsDynamic BalancingDynamic Balancing

    Coil

    Total Pressure drop

  • Chilled Water Distribution System Dynamic Balancing 14

    Advanced TechnicalAnalysis

    Advanced TechnicalAnalysis

  • Chilled Water Distribution System Dynamic Balancing 15

    33--inin--1 Chilled Water Dynamic 1 Chilled Water Dynamic Balancing Balancing Static ConditionStatic Condition

    Under conditions of all parameters including

    P1, P3 and k1, k2, & K being fixed

    From (4), P2 varies only with A1From (3), Q varies only with A1Note (*) The linearity of Q in equations (1) and (2) depends on manufacturer design and construction tolerance

    A2, k2A1, k1

    2111 PPAkQ 3222 PPAkQ

    3231

    2 PPPPKkQ

    ..(1*)

    ..(2*)

    ..(3)

    Where k1 & k2 are flow coefficients, and K is relation of A2 to(P1-P3 ), From (1) and (3), we have

    3231

    22111 PPPPK

    kPPAk = ..(4)

  • Chilled Water Distribution System Dynamic Balancing 16

    33--inin--1 Chilled Water Dynamic 1 Chilled Water Dynamic Balancing Balancing Dynamic ConditionDynamic Condition

    Flow rate remain constant with system pressure variation

    31 PP 21 PP 32 PP

    322 PPAQ 31

    2 PPKA

    A2, k2A1, k1 ( - ) no change

    therefore, no change

    ....

    ....

    ..

    ..

  • Chilled Water Distribution System Dynamic Balancing 17

    What are theTechnical Advantages?

    What are theTechnical Advantages?

    Commissioning

    System Performance

    Energy Efficiency

  • Chilled Water Distribution System Dynamic Balancing 18

    Commissioning Performance Energy

    Easy Commissioning

  • Chilled Water Distribution System Dynamic Balancing 19

    Preset of Maximum FlowPreset of Maximum Flow

    Valve can be conveniently preset for maximum flow by local adjustment or remote via BMS

    Max. flow setting in actuator

    Max. flow setting by BMS

  • Chilled Water Distribution System Dynamic Balancing 20

    Commissioning Performance Energy

    Pressure Independent Control

  • Chilled Water Distribution System Dynamic Balancing 21

    Pressure Independent CharacteristicPressure Independent Characteristic

    Flow can be conveniently preset and then maintained constant under dynamic condition with minimum required pressure differential

    Accurate control of flow rate over larger control range as compared with traditional control valve

    Valve max. flow

    Pre-setDesignFlow

    50% 6V

    max kPamin kPadiff pressure

    0 2V

    Control SignalDesign flow

    Preset

    10V100%

  • Chilled Water Distribution System Dynamic Balancing 22

    Commissioning Performance Energy

    Good Space Temperature Control

  • Chilled Water Distribution System Dynamic Balancing 23

    Steady Space Temperature being maintainedSteady Space Temperature being maintained

    18

    20

    22

    24

    26

    28

    30

    6:00 8:00 10:00 12:00 14:00 16:00 18:00 20:00

    R

    o

    o

    m

    T

    e

    m

    p

    (

    )

    Time

    With air conditioningWith air conditioning

  • Chilled Water Distribution System Dynamic Balancing 24

    Commissioning Performance Energy

    Linear Control on Flow Rate

  • Chilled Water Distribution System Dynamic Balancing 25

    Linear Control of Flow RateLinear Control of Flow Rate

    0.00

    3.60

    7.20

    10.80

    14.40

    2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10

    Control signal (V)

    F

    l

    o

    w

    r

    a

    t

    e

    (

    m

    3

    /

    h

    r

    )

    Testresult

    DirectDirect and linearlinear relationship of control signal with and flow rate over noticeable large control range as compared with traditional control valve

  • Chilled Water Distribution System Dynamic Balancing 26

    Commissioning Performance Energy

    Energy Saving

  • Chilled Water Distribution System Dynamic Balancing 27

    % of Design Flow

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    Control Valve

    Coil

    DRV

    0% 100%

    Coil + DRV

    HydronicHydronic FundamentalsFundamentalsTraditional control valve and double regulating valveTraditional control valve and double regulating valve(index circuit)(index circuit)

    Index circuitTotal pressure drop

    Index circuitTotal pressure drop

  • Chilled Water Distribution System Dynamic Balancing 28

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    CoilDynamic Balancing Control valve

    % of Design Flow0% 100%

    HydronicHydronic FundamentalsFundamentalsDynamic BalancingDynamic Balancing

    Coil

    Total Pressure drop

  • Chilled Water Distribution System Dynamic Balancing 29

    P

    r

    e

    s

    s

    u

    r

    e

    l

    o

    s

    s

    p

    [

    k

    P

    a

    ]

    % of Design Flow0% 100%

    Energy Saving Energy Saving in Dynamic Balancing systemin Dynamic Balancing system

    System with Traditional Control valve & Double

    Regulating Valve

    System with Dynamic Balancing

    Control Valve

    Energy saved

    160

    95 kPa

    50

    160 kPa

  • Chilled Water Distribution System Dynamic Balancing 30

    Commissioning Performance Energy

    Flowrate monitoring

  • Chilled Water Distribution System Dynamic Balancing 31

    Flow MonitoringFlow MonitoringComparison with Electromagnetic Type Flowmeter

    No specific requirementMin 5D upstream & 3D downstream to ensure accurate measurement

    Installation requirement

    Up to 35kPa for valve max. flow rate @ 2m/s

    No requirementDiff pressure

    Independent of installation.

    2% of valve maximum flow rate at 2m/s

    Highly depend on compliance of installation requirement.Typical catalogue quoted accuracy: 0.5% of operating range (flowmeter design at 9 to 10m/s).Accuracy @ pipe actual flow rate of 2m/s:1.8 -2.25%

    Accuracy

    Determine the flow rate by calibrated opening (orifices)

    Determine the fluid velocity by induced voltage

    Mechanics

    3-in-1 Dynamic Balancing Control Valve

    Flowmeter(electromagnetic type)

  • Chilled Water Distribution System Dynamic Balancing 32

    Case Study : Case Study :

    Flowrate feedback by the Dynamic Balancing Control valve and monitored by the BMS system

    Office Tower in Office Tower in SingaporeSingapore

  • Chilled Water Distribution System Dynamic Balancing 33

    AHU3

    AHU2

    AHU1

    Chiller1

    Chiller2

    Chiller3

    DCV

    CFV3

    CFV2

    CFV1

    FMb

    DCV

    DCV

    qS1

    qS2

    qS3

    qD1

    qD2

    qD3

    QbQS

    QD

    BPV

    AHUn DCVqDn

    FMQ

    DCV Dynamic balancing control valve CFV Constant flow valve BPV By-pass Valve

    bFM Flowmeter to measure bypass flow QFM Flowmeter to verify flow in riser

    iqD Air Handling Unit demand flow

    determined from Dynamic balancingcontrol valve feedback signal

    DQ Total system demand flow

    = nqDqDqDqD ++++ 321

    jqS Supply flow of each chiller

    SQ Total plant supply flow = 321 qSqSqS ++

    bQ Bypass flow, DS QQ Pumps and isolation valves not shown

    Schematic of the Schematic of the HydronicHydronic SystemSystem

  • Chilled Water Distribution System Dynamic Balancing 34

    Flow Rate VerificationFlow Rate VerificationResults

    QD, Required demand calculated via feedback signal of DCV (3-in-1 dynamic balancing control valves) = qD1 + qD2 + qD3 +. qDn= 27.44 Lps

    FMQ, flow rate measured in supply mains by flowmeter= 27.38 Lps

    Only minor variance between summation of DCV valve and flowmeter measurement

    AHU3

    AHU2

    AHU1

    Chiller1

    Chiller2

    Chiller3

    DCV

    CFV3

    CFV2

    CFV1

    FMb

    DCV

    DCV

    qS1

    qS2

    qS3

    qD1

    qD2

    qD3

    QbQS

    QD

    BPV

    AHUn DCVqDn

    FMQ

  • Chilled Water Distribution System Dynamic Balancing 35

    SummarySummary

  • Chilled Water Distribution System Dynamic Balancing 36

    Chilled Water Distribution System Dynamic BalancingChilled Water Distribution System Dynamic BalancingSummarySummary

    Deliver exact flow rate under dynamic condition as required by space temperature controller

    Only limit flow rate and do not have balancing function

    Only achieve balancing under full load static condition which becomes distorted under dynamic condition which resistance of system components changes

    Mechanics

    Dynamic system: 3-in-1 Dynamic Balancing Control valve

    Constant Flow valve in series with Control valve

    Traditional system: Balancing valve in series with Control valve

  • Chilled Water Distribution System Dynamic Balancing 37

    Convenient preset of maximum flow either locally at the valve or remotely at BMS

    No commissioning required

    Require laborious hydraulic analysis to determine appropriate valve setting, adjustment of valve setting has to be performed and verified locally at the valve which is prone to error

    Commissioning

    Dynamic system: 3-in-1 Dynamic Balancing Control valve

    Constant Flow valve in series with Control valve

    Traditional system: Balancing valve in series with Control valve

    Chilled Water Distribution System Dynamic BalancingChilled Water Distribution System Dynamic BalancingSummary (conSummary (cont)t)

  • Chilled Water Distribution System Dynamic Balancing 38

    Yes. NilNilFlow rate monitoring

    Energy saving due to low initial full load control valve pressure loss and ability to capture reduced system resistance at partial load

    Same as the case of Traditional system of balancing valve in series with control valve but with additional energy consumption due to balancing valve resistance

    Waste energy due to high initial full load control valve pressure loss and inability to capture reduced system resistance at partial load

    Energy efficiency

    Dynamic system: 3-in-1 dynamic balancing control valve

    Constant flow valve in series with control valve

    Traditional system: balancing valve in series with control valve

    Chilled Water Distribution System Dynamic BalancingChilled Water Distribution System Dynamic BalancingSummary (conSummary (cont)t)

  • Chilled Water Distribution System Dynamic Balancing 39

    Superior control performance due to direct relationship of space temperature control signal to chilled water flow rate and satisfactory modulating capability under partial load condition

    Do not have system resistance balancing function and hence performance is inferior to traditional commissioning valve

    Indirect relationship of space temperature control signal to chilled water flow rate and inferior modulating capability under partial load condition

    System Performance

    Dynamic system: 3-in-1 Dynamic Balancing Control valve

    Constant Flow valve in series with Control valve

    Traditional system: Balancing valve in series with Control valve

    Chilled Water Distribution System Dynamic BalancingChilled Water Distribution System Dynamic BalancingSummary (conSummary (cont)t)

  • Chilled Water Distribution System Dynamic Balancing 40

    Thank You!Question and Answer