chilled water system.ppt

Upload: larry-bea

Post on 02-Jun-2018

388 views

Category:

Documents


4 download

TRANSCRIPT

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    1/48

    Chilled Water Piping Systems (VPF Focus)

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    2/48

    AgendaChilled Water Distribution Systems

    Chilled Water Distribution Systems

    Primary (Constant) / Secondary (Variable2W Valves)

    Low Delta T

    Primary Only (Variable Flow - 2W Valves)

    VPF Design/Control Considerations

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    3/48

    Primary (Constant Flow) / Secondary (Variable Flow)

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    4/48

    Primary/Secondary System

    Primary Pumps

    Secondary Pumps

    Common Pipe

    Typical

    load

    with

    two

    way

    valve

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    5/48

    Primary (Constant Flow) / Secondary (Variable Flow)

    2 Way Valves

    Higher Capital Cost Installed (vs Constant Flow 3W Valve system)

    Lower CHW Pumping Energy (vs Constant Flow 3W Valve system)

    Well Understood & Easy to Control

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    6/48

    Primary/Secondary System at Design

    56.0 F

    56.0 F

    56.0 F

    44.0 F

    44.0 F

    44.0 F

    Primary Pumps

    1000 GPM Each

    3000 GPM @ 56.0 F

    Secondary Pumps

    3000 GPM @ 44.0 F

    Typical

    Coil

    No flow

    44.0 F

    56.0 F

    500 ton chillers

    1000 GPM Each

    56.0-44.0F

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    7/48

    Primary/Secondary System at Part Load

    53.0 F

    53.0 F

    53.0 F

    44.0 F

    44.0 F

    44.0 F

    Primary Pumps

    1000 GPM Each

    3000 GPM @ 53.0 F

    Secondary Pumps

    2250 GPM @ 44.0 F

    Typical

    Coil

    44.0 F

    56.0 F

    750 GPM @ 44.0 F

    2250 GPM @ 56.0 F

    75% System Load

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    8/48

    Primary/Secondary System

    53.0 F

    53.0 F

    44.0 F

    44.0 F

    Primary Pumps

    1000 GPM Each

    2000 GPM @ 53.0 F

    Secondary Pumps

    1500 GPM @ 44.0 F

    Typical

    Coil

    44.0 F

    56.0 F

    500 GPM @ 44.0 F

    1500 GPM @ 56.0 F

    OFF 50% System Load

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    9/48

    Low Delta T Syndrome

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    10/48

    10

    Dirty Coils

    Major Causes of Low Delta T

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    11/48

    Chilled Water Coil

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    12/48

    12

    Dirty Coils

    Controls Calibration

    Leaky 2 Way Valves

    3 Way Valves at end of Index circuit

    Major Causes of Low Delta T

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    13/48

    Primary/Secondary System

    Primary Pumps

    Secondary Pumps

    Common Pipe

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    14/48

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    15/48

    15

    Dirty Coils

    Controls Calibration

    Leaky 2 Way Valves

    3 Way Valves at end of Index circuit

    Coils piped up backwards

    Major Causes of Low Delta T

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    16/48

    Chilled Water Coil

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    17/48

    17

    P Load= Flow X Delta T S Load= FlowX Delta T

    Primary (Constant) / Secondary (Variable)

    SecondaryPumps

    PrimaryPumps

    Typical load with 2 way valve

    Decoupler/Bypass

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    18/48

    18

    100% Load = 100% Sec Flow

    Primary (Constant) / Secondary (Variable)

    Ideal Operation

    SecondaryPumps

    PrimaryPumpsDecoupler

    /Bypass

    100% Flow = 3000 gpm

    100% Flow = 3000 gpm

    0 gpm

    1

    2

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    19/48

    SecondaryPumps

    PrimaryPumpsDecoupler

    /Bypass

    67% Flow = 2000 gpm

    67% Flow = 2000 gpm

    0 gpm

    19

    67% Load = 67% Sec Flow

    Primary (Constant) / Secondary (Variable)

    Ideal Operation

    1

    2

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    20/48

    20

    Primary / Secondary Rule of Flow

    Primary flow must always be equal

    to or greater than Secondary flow.

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    21/48

    SecondaryPumps

    PrimaryPumpsDecoupler

    /Bypass

    100% Flow = 3000 gpm

    80% Flow = 2400 gpm (400 gpm over-pumped)

    600 gpm

    21

    67% Load = 80% Sec Flow

    Primary (Constant) / Secondary (Variable)

    Low Delta T Operation

    1

    0

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    22/48

    Higher Secondary Pump Energy

    Higher CHW Plant Chiller/Auxiliary Energy

    Major Effects of Low Delta T

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    23/48

    23

    Solution to (or reduce effects of) Low Delta T

    Address the causes

    Clean Coils

    Calibrate controls occasionally

    Select proper 2W valves (dynamic/close-off ratings) and maintain them

    no 3W valves in design

    find and correct piping installation errors

    Over pump chillers at ratio of Design Delta T / Actual Delta T

    Increase Delta T across chillers with CHW Re-set (down).

    Use Variable Speed Chillers & sequence to operate from 30 to 70% Load

    Use VPF Systems (mitigates energy waste in plant)

    Header pumps & operate more pumps than chillers

    If dedicated pumping, over-size (design at 80% speed).

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    24/48

    Primary/Secondary System

    Primary Pumps

    Secondary Pumps

    Common Pipe

    P

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    25/48

    Primary Only (Variable Flow)

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    26/48

    Primary/Secondary System

    Variable Primary System

    SecondaryPumps

    PrimaryPumps

    Primary Pumps

    Flow Meter

    BypassValve

    Automatic Isolation Valve

    Typical load with 2 way valve

    Typical load with 2 way valve

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    27/48

    Primary Only (Variable Flow)

    2 Way Valves

    Lower Capital Cost Installed (vs Primary/Secondary)

    No secondary pumps/piping/valves/electrical to buy and install

    No large Common pipe, but smaller Bypass pipe/valve/flow meter/controls

    Lower CHW Pumping Energy

    Smaller Footprint (vs Primary/Secondary)

    Relatively New & More Complex Controls

    Reduces Negative Impacts from Low Delta T

    Chillers are not staged on by flow requirements

    Chillers can load up and are staged on load

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    28/48

    Primary Only (Variable Flow)

    Disadvantages

    Higher (potentially) PSID rated 2-Way valves in system

    Requires more robust (complex and calibrated) control system

    Requires coordinated control of chillers, isolation valves, and pumps in sequencing

    Longer (potentially) Commissioning time

    Requires greater operator sophistication

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    29/48

    Variable-Primary-Flow System

    Primary Pumps

    Flow Meter

    Typical

    load

    with

    twoway

    valve

    AutomaticIsolation Valve

    Bypass

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    30/48

    Variable Primary System at Design

    56.0 F

    56.0 F

    56.0 F

    44.0 F

    44.0 F

    44.0 F

    Primary Pumps

    1000 GPM Each

    3000 GPM @ 56.0 F

    3000 GPM @ 44.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    500 ton chillers

    1000 GPM Each56.0-44.0F

    Typical

    load

    with

    two

    wayvalve

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    31/48

    Variable Primary SystemPart Load

    56.0 F

    56.0 F

    56.0 F

    44.0 F

    44.0 F

    44.0 F

    Primary Pumps

    750 GPM Each

    2250 GPM @ 56.0 F

    2250 GPM @ 44.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    twoway

    valve

    75% System Load

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    32/48

    Variable Primary SystemPart Load

    56.0 F

    56.0 F

    44.0 F

    44.0 F

    Primary Pumps

    750 GPM Each

    1500 GPM @ 56.0 F

    1500 GPM @ 44.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    twoway

    valve

    50% System LoadChiller off

    Pump off

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    33/48

    Variable Primary SystemPart Load

    52.0 F

    52.0 F

    44.0 F

    44.0 F

    Primary Pumps

    750 GPM Each

    2250 GPM @ 52.0 F

    2250 GPM @ 44.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    twoway

    valve

    50% System Load

    Low T

    Chiller off

    Pump on

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    34/48

    Variable Primary SystemMin Flow (400 gpm each)

    50.0 F

    44.0 F

    Primary Pumps

    400 GPM (oneoperating)

    400 GPM @ 50.0 F

    200 GPM @ 44.0 F

    AutomaticIsolation Valve

    Bypass

    Open

    Typical

    load

    with

    twoway

    valve

    System flow below chiller

    minimum flow

    Chiller off

    Chiller off

    Closed

    Closed

    200 GPM @ 44.0

    200 GPM @ 56.0 FFlowmeter

    Pumps

    off

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    35/48

    Chiller Design Considerations

    Flow rate changesStaging on additional chillers

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    36/48

    Variable Primary System (1 chiller running)

    56.0 F

    44.0 F

    Primary Pumps

    333 GPM Each

    1000 GPM @ 56.0 F

    1000 GPM @ 44.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    two

    wayvalve1000 GPM

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    37/48

    Variable Primary System (Staging on second chiller)

    57.0 F

    45.0 F

    Primary Pumps

    333 GPM Each

    1100 GPM @ 57.0 F

    1100 GPM @ 45.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    two

    wayvalve1100 GPM

    Need to add chiller

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    38/48

    Variable Primary System (Open isolation valve)

    57.0 F

    45.0 F

    Primary Pumps

    333 GPM Each

    1100 GPM @ 57.0 F

    1100 GPM @ 45.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    two

    wayvalve550 GPM

    550 GPM

    Load = F X DT DT = 12 = 57- 45

    24Load = 1/2F X 2DT DT = 24

    24 LCHWT = 35!

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    39/48

    Variable Primary System (Open isolation valve)

    57.0 F

    45.0 F

    Primary Pumps

    333 GPM Each

    1100 GPM @ 57.0 F

    1100 GPM @ 45.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    two

    wayvalve550 GPM

    550 GPM

    LCHWT approaches 35

    LWT Cutout at 4 deg below

    44 set-point or 40

    Off goes chiller 1

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    40/48

    Variable Primary System (Open isolation valve slowly)

    57.0 F

    45.0 F

    Primary Pumps

    333 GPM Each

    1100 GPM @ 57.0 F

    1100 GPM @ 45.0 F

    AutomaticIsolation Valve

    Bypass

    Closed

    Typical

    load

    with

    two

    wayvalve1100 GPM

    Open over 1.5 to 2 min

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    41/48

    42

    VPF Systems Design/Control Considerations Summary

    Chillers

    Equal Sized Chillers preferred, but not required

    Maintain Min flow rates with Bypass control (1.5 fps)

    Maintain Max flow rates (11.0 to 12.0 fps)

    Isolation Valves (Modulating or Stroke-able to 1.5 to 2 min)

    Dont vary flow too quickly through chillers (VSD Ramp function typical setting of 10%/min)

    Chiller Type

    System Water Volume

    Chiller Load

    Active Loads

    Sequence

    If Constant Speedrun chiller to max load (Supply Temp rise). Do not run more chillers than

    needed (water-cooled) If Variable Speedrun chillers between 30% and 70% load (depending on ECWT). Run more

    chillers than load requires.

    Add Chiller - CHW Supply Temp or Load (Adjusted* Flow X Delta T) or amps (if CSD)

    Subtract Chiller - Load (Adjusted* Flow X Delta T) or Amps (if CSD)

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    42/48

    43

    VPF Systems Design/Control Considerations Summary

    Pumps

    Variable Speed Driven

    Headered arrangement preferred

    Sequence

    with chillers (run more pumps than chillers for over-pumping capability)

    on flow (add pump when existing inadequate, subtract when can)

    optimized algorithm (total kW of more pumps, lower than less pumps)

    Stay within pump/motor limits (25% to 100% speed)

    Subtract a Pump at 25 to 30% speed

    Add a pump back when speed of operating pumps high enough

    Speed controlled by pressure sensors at endof index circuit

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    43/48

    44

    VPF Systems Design/Control Considerations Summary

    Bypass Valve

    Maintain a minimum chilled water flow rate through the chillers

    Differential pressure measurement across each chiller evaporator

    Flow meter preferred

    Modulates open to maintain the minimum flow through operating chiller(s).

    Bypass valve is normally open, but closed unless Min flow breeched

    Pipe and valve sized for Min flow of operating chillers

    High Rangeability (100:1 preferred)

    PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of Pumps

    Linear Proportion (Flow to Valve Position) Characteristic preferred

    Fast Acting Actuator

    Locate in Plant around chillers/pumps (preferrred)

    Energy

    Avoid Network traffic

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    44/48

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    45/48

    46

    Summary on VPF Design

    Chillers

    Size equally with same WPDs (best)

    Respect Min/Max Flows through chillers

    Set Pump VSD Ramp function to about 10%/min (600 sec 0 to Max Speed)

    Use Modulating or Strokeable Valves (preferred) on chiller evaps, headered pumping

    Use 2 Position Valves (1 min stroke) on chiller evaps, dedicated pumping

    Pumps

    VSD Controllers

    Headered Pumping Arrangement (preferred)

    Dedicated Pumping OK (over-size pumps)

    2 Way Valves

    Select for Static, Dynamic, Close-off ratings (PSID) equal to pump SOH (plus fill pressure)

    Range-ability 100 to 200:1

    If Bypassfast acting, linear proportion

    If Coilsslow acting, equal percentage, On-Off stagger air units (10-15 min intervals)

    Controls

    Set-point far out in index circuit (lower the value, the better the pump energy)

    Set Ramp function in VSD Controller (10%/min average)

    Run 1 more pump than chillers (when headered)

    Chillers On by common Supply Temp, Load, Amps, Adj Flow (Adj for Low Delta T)

    Chillers Off by Amps, Load, Adj Flow (Adj for Low Delta T)

    Over-pump Chillers to combat Low Delta T and get Max Cap out of chillers

    Bypass controlled by Min flow (preferred) or Min WPD of largest chiller (locate in plant for best energy, but can go anywhere in system)

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    46/48

    Chilled Water Piping Systems (VPF Focus)

    Questions?

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    47/48

    Supply

    Terminal

    Balance

    and

    Service

    Valve

    2-Way

    Control

    Valve

    Return

    Service Valve

    Air

    2 Way Valve/Coil Detail

  • 8/10/2019 CHILLED WATER SYSTEM.ppt

    48/48

    Electric Energy Cost Equations

    Chiller

    Energy Cost

    Lbs Refrig/hr X Head

    33,015 X Comp Eff

    X Hours X Cost/Unit Energy=

    Pump

    Energy Cost

    GPM X Head

    3960 X Pump Eff

    X Hours X Cost/Unit Energy=

    Fan

    Energy Cost

    CFM X TSP

    6356 X Fan Eff

    X Hours X Cost/Unit Energy=

    0.7459

    Mot Eff

    0.7459

    Mot Eff

    0.7459

    Mot Eff

    X

    X

    X

    Energy Cost

    Mass Flow/t X Lift

    33,015 X EfficiencyX Hours X Cost/Unit Energy=

    0.7459

    Mot EffX