pfc harmonic filter
DESCRIPTION
Pfc Harmonic FilterTRANSCRIPT
-
EPCOSEPCOSEPCOSEPCOS
Power Factor Correction & Harmonic filter
EPCOSEPCOSEPCOSEPCOSEPCOSEPCOSEPCOSEPCOS
Power Factor Correction & Power Factor Correction & Harmonic filterHarmonic filter
-
Definition:Definition:
Power Factor, Harmonics, Transients, Power Factor, Harmonics, Transients,
Voltage and frequency variations and other Voltage and frequency variations and other
disturbances in electric power supply disturbances in electric power supply
networksnetworks
Power Quality
-
Adjustable Speed Drives
Notching on the input can interfere with other loads on the same branch circuit
Flat topping of Drive input voltage, heavily distorted current
Examples for poor power quality
-
Past Past -- load:load: most loads were linearmost loads were linear
InductionInduction--motors, heating, bulbsmotors, heating, bulbs
voltage was followed by current voltage was followed by current -- only a few problemsonly a few problems
Changing load structure
Features Customer benefits
Simple and rugged design
No commutator
High degree of protection
High reliability
Long lifetime
Favourably-priced
Unrestricted operation for partial- and overload conditions
Low maintenance (only the bearings)
Can be universally used
-
Todays Todays -- loads:loads: most loads act non linearmost loads act non linear
Computer, motorComputer, motor--control, drives, etc.control, drives, etc.
Current is pulse shapedCurrent is pulse shaped
Current is no longer following the sinusoidal wave shapeCurrent is no longer following the sinusoidal wave shape
Result: HarmonicsResult: Harmonics
-- Increasing number of sources causing disturbancesIncreasing number of sources causing disturbances
-- Equipment become more and more sensitive Equipment become more and more sensitive
-- DeDe--regulated energy marketregulated energy market
Changing load structure
-
Problems caused by harmonics
-
Non linear loads
Loads which have non linear voltage-current characteristics are called non linear
loads. When connected to a sinusoidal voltage, these loads produce non
sinusoidal currents. Modern power electronic systems result into non sinusoidal
currents when connected to the sinusoidal networks.
The non linear devices can be classified under the following three major categories:
1. Power Electronics: e.g. rectifiers, variable speed drives, UPS systems, inverters, ...
2. Ferromagnetic devices: e.g. transformers (non linear magnetizing characteristics)
3. Arcing devices: Arcing devices, e.g. arc furnace equipment, generate harmonics due to the
non linear characteristics of the arc itself.
Harmonic disturbances are created by non-linear loads!
Origin of harmonics
-
Voltage-source DC link converter
Current-sourceDC link converter
Cycloconverter
Design
Features
Driveconverter
Voltage is impressed in the DC link
SIMOVERT MASTERDRIVESSIMOVERT MVSIMOVERT ML
Current is impressed in the DC link
SIMOVERT ASIMOVERT ISIMOVERT S
Cycloconverter, no DC link
SIMOVERT D
~=
=~
M3~
~=
M3~
~=
~=
~=
=~
M3~
Modern drives a main source for harmonics
-
0%
20%
40%
60%
80%
100%
Order number
6-pulse
12-pulse
6-pulse 100,00% 29,00% 9,00% 6,00% 3,50% 2,50% 2,00% 1,20% 1,10%
12-pulse 100,00% 2,90% 0,90% 6,00% 3,50% 0,25% 0,20% 1,20% 1,10%
1 5 7 11 13 17 19 23 25
HARMONICS fed back by 6/12 pulse rectifier
Voltage characteristic at the drive converter output (PWM)
Voltage characteristic at the drive converter output (PWM)
Current characteristic at the drive converter output
Current characteristic at the drive converter output
-
Example of a non-linear load: Switched mode power supply
AC Current Voltage
Current
LOAD
Example for single phase Non-Linear load
-
Harmonic currents or voltages are integer (whole number) multiples of thefundamental frequency.
Harmonicorder
F 3rd 5th 7th
Frequency 50 150 250 350
Understanding harmonics
-
Overheating of transformers (K-Factor), and rotating equipment
Increased hysteresis losses
Neutral overloading / unacceptable neutral-to-ground voltages
Distorted voltage and current waveforms
Failed capacitor banks
Breakers and fuses tripping
Unreliable operation of electronic equipment, and generators
Erroneous register of electric meters
Wasted energy / higher electric bills - KWD & KWH
Wasted capacity - Inefficient distribution of power
Increased maintenance cost of equipment and machinery
Problems caused by HARMONICS
HARMONICS
Time
Am
plitu
de
Fundame
h3
h5
h7
SUM
-
Additional investment due to faster equipment deratingShorter life time of equipmentHigher energy consumptionHigher downtime of production equipmentHigher maintenance and repair costReduced product qualityReduced production outputInvestment for stronger equipments/components
alternatively
One time investment for harmonic filter
COST caused by HARMONICS
-
Tripping of circuit breakers and fuses Due to resonance effects, the current levels may rise to multifold levels which results into tripping ofcircuit breakers and melting fuses. This situation results into serious problems in industries which relyon the quality of power for the continuous operation of their sensitive processes (e.g. semiconductor)
Overloading / decrease of life time of transformersTransformers are designed to deliver power at network frequency (50/60Hz). The iron losses arecomposed of the eddy current loss (which increase with the square of the frequency) and hysteresis losses (which increase linearly with the frequency). With increasing frequencies the losses also increase, causing an additional heating of the transformer.
Overloading of the capacitors Capacitive reactance decreases with the frequencies. Even smaller amplitudesof the harmonic voltages result into higher currents which are detrimental tothe capacitors: I = U * 2 * 3.14 * f * C.
Losses in distribution equipmentHarmonics in addition to the fundamental current cause additional losses inthe cables, fuses and also the bus bars.
Effect of harmonics
-
Excessive currents in the neutral conductor Under balanced load conditions without harmonics, the phase currents cancel each other in neutral,and resultant neutral current is zero. However, in a 4 wire system with single phase non linear loads,odd numbered multiples of the third harmonics (3rd, 9th, 15th) do not cancel, rather add together in theneutral conductor. In systems with substantial amount of the non linear single phase loads, the neutral currents may riseto a dangerously high level. There is a possibility of excessive heating of the neutral conductor sincethere are no circuit breakers in the neutral conductors like in the phase conductors.
Malfunctioning of the electronic controls and computersElectronic controls and computers rely on power quality for their reliable operation. Harmonics resultinto distorted waveforms, neutral currents and over voltages which affect the performance of thethese gadgets.
Measurement errors in the metering systemsThe Accuracy of metering systems is affected by the presence of harmonics. Watt-hour metersaccurately register the direction of power flow at harmonic frequencies, but they have magnitudeerrors which increase with frequency.The accuracy of demand meters and VAr meters is even less in the presence of harmonics.Wrong multi meter readings. Use true RMS meter!
Effect of harmonics
-
3rd harmonic in the neutral conductor
-
3rd harmonic in the neutral conductor
-
Synthesis of a wave form
-
Limit for harmonics
-
Consumer structure has changed from linear to non linear loads
Harmonics in the net are increasing
Increasing unknown energy losses
Unknown overloads
Problems in the net become more complex
Beside convent. PFC, filters become more and more important
De-tuned filters for most applications
Active filters for a niche market
Summary
-
Unlike other solutions that: Waste energy Connect in series Generate higher harmonics (through injection) Have limited fixed sizes and are not expandable Are bulky and expensive
The Solution EPCOS AG offers:
Specific harmonic filtering of any magnitude
Enhanced power quality
Elimination of associated wasted energy
Modular and expandable circuitry, to include additional load
EPCOS Harmonics solution
-
1. Harmonics can overload PFC capacitors due to over voltage and over current created by the harmonic source and reduced reactance of PFC capacitors at higher frequencies.
2. But more critical are applications in which the application configuration (PFC capacitor and transformer) form a resonance circuit with anfrequency close to existing harmonic frequencies. In such a caseharmonic currents stimulate the resonance circuit and create resonance amplification with harmful over voltages and over currents.
Resonance is one of the main reasons for failed PFC capacitors or short life cycle of PFC capacitors!
Resonance
-
Parallel resonance
-
Meter: 0001 K-f ac tor: 1.041 V olts : 277 Frequenc y :60.01 Hz
H# % H# % T.H.D.: 2.8% max : 2 .9% min: 0.5% 1 100.0 0 2 0.0 69 3 0.4 116 4 0.1 68 5 2.1 272 6 0.0 69 7 1.6 41 8 0.0 70 9 0.2 133 10 0.0 6811 0.4 11 12 0.0 6813 0.7 36 14 0.1 6815 0.1 68 16 0.0 6817 0.2 37 18 0.0 15819 0.1 69 20 0.0 15821 0.1 327 22 0.0 6923 0.0 69 24 0.0 6925 0.1 301 26 0.0 827 0.0 158 28 0.0 24829 0.1 319 30 0.0 30931 0.2 20 32 0.0 68
Meter: 0001 K-f ac tor : 1.829 V olts : 290 Frequenc y :59.97 Hz
H# % H# % T.H.D.: 18.8% max : 21.6% min: 1.9% 1 100.0 0 2 0.1 26 3 0.5 352 4 0.3 31 5 18.8 203 6 0.0 259 7 1.2 126 8 0.0 259 9 0.0 80 10 0.0 20011 0.1 312 12 0.0 25913 0.0 80 14 0.0 8015 0.1 116 16 0.0 20017 0.0 320 18 0.0 16919 0.0 319 20 0.0 25921 0.1 192 22 0.0 25923 0.0 169 24 0.0 34925 0.1 259 26 0.0 25927 0.1 259 28 0.0 34929 0.0 259 30 0.0 25931 0.1 31 32 0.0 79
Harmonics MAGNIFICATION
No PFC capacitors With PFC capacitors
Meter: 0001 K-f ac tor: 1.533 A mps : 1716 Frequenc y :60.01 Hz
H# % H# % T.H.D.: 13.6% max : 18.1% min: 2.1% 1 100.0 0 2 0.5 100 3 0.4 29 4 0.1 119 5 12.3 53 6 0.4 66 7 5.5 356 8 0.1 91 9 0.7 299 10 0.2 2911 1.3 7 12 0.1 2913 0.1 210 14 0.0 2915 0.3 29 16 0.0 11917 0.3 285 18 0.0 2919 0.0 210 20 0.1 9021 0.1 90 22 0.0 2923 0.0 210 24 0.0 11925 0.1 29 26 0.1 2927 0.0 29 28 0.1 11929 0.1 29 30 0.1 11931 0.0 29 32 0.0 209
Meter: 0001 K-f ac tor: 32.38 A mps : 2033 Frequenc y : 59.97 Hz
H# % H# % T.H.D.: 89.5% max : 152.3% min: 3.6% 1 100.0 0 2 2.3 9 3 1.0 169 4 2.9 79 5 150.0 263 6 3.8 259 7 8.7 141 8 1.2 300 9 1.5 280 10 1.5 25911 1.6 259 12 0.8 31013 1.7 279 14 0.5 25915 1.2 79 16 1.1 29417 0.5 260 18 0.3 819 1.0 331 20 0.5 25921 1.5 259 22 0.5 31223 1.2 339 24 0.1 25925 0.5 180 26 0.6 34927 0.9 182 28 0.3 30729 0.7 349 30 0.2 1931 0.6 292 32 0.0 259
V o
l t a
g e
Cu
rre
nt
-
Real case of parallel resonance in KL/Malaysia
-
point of view
In
harm onicload
X Lmotor
X Ttransformer
X N, networkimpedance
X Ccapacitor
Parallel resonance
Harmonics present on LV side of the transformer
Transformer together with PFC capacitors on LV-side
acts as a parallel resonant circuit
At resonant frequency the inductive reactance is
equal the capacitive reactance
The resultant impedance of the circuit increases to
very high value at resonant frequency
Excitation of a parallel resonant circuit results into a
high voltage across the impedances and very high
circulating currents inside the loop
Transformers and capacitors are additionally loaded
which may cause overloading of them
-
1) I is constant and imprinted
DC
AC
I Ic IL
UZ
What happens in case of parallel resonance?
1) + 2) voltage U (ohmic law)
3) With U Ic = IL
2) Impedance Z
Parallel resonance
-
U = 20 KVSk = 500 MVA
P = 500 KW, 6-pulseI50 Hz = 720AI250 Hz = 144AI350 Hz = 103AI550 Hz = 65AI650 Hz = 55AI850 Hz = 42AI950 Hz = 38A
DCAC
P = 100 KW
M
I350 Hz = A720
7
S = 1000 kVA
uk = 6%Transformer
U = 400 V
Qc = 400kvar
Parallel resonance: example
-
Attention:close to the 7thharmonic!
DCAC M
SKLV = STr
uk 100
SKLV = 1000 kVA
6100 = 16.67MVA
frp = 50Hz SKLV
Qc
= 322 Hzfrp = 50 Hz 16.67 MVA
0.4 Mvar
Parallel resonance: exampleKC
TR uQ
Sf
=
10050
-
System bus bar: impedance vs. frequency
Resulting harmonic voltage for 350 Hz :322 Hz is close to the 7th harmonic
00,20,40,60,8
11,21,41,6
50 150 250 350 450 550
o
322Hz
Frequency Hz
350 Hz
0.5
DCAC M
I350 Hz = 103 Amp
U350 = 0.5 * 103A = 51.5V
Parallel resonance: example
12.7% 400V51.5V
-
Resonance?
11 kV level
132 kV level
Parallel resonance
I
I
Series resonance
I
Capacitorbank
Transformer1000 kVA, uk = 5 %
DC drive600 kWcos = 0.65
...
415 V level
Transformer630 kVA, uk = 5 %
Capacitorbank
300 kWcos = 0.65
...
415 V level
3
if fr = f Xc 0 Ic
-
Se rie s re so na nce
0
24
68
10
1214
16
50 100 150 200 250 300 350 400Frequency
Impe
danc
e
Induc tance
Reactance
Im pedance
fr
Series resonance
S
L
C
Series resonant circuit
S=signal source
KCNR eQ
Sv
=
1
100
The point of series resonance is given by the following formula:
Series resonant circuit formed by combination of inductive and capacitive reactance. The impedance behavior of this circuit is as illustrated in the diagram. It is seen that at resonant frequency the impedance reduces to a minimal value. Thus the circuit offers very low impedance at the input signal at this frequency which results into multiple fold increase in the current. The voltage drop on the individual component increases moving closer to resonant frequency.
-
Limiting total output of harmonic sources
Limiting the number of simultaneously operating harmonic sources
Balanced connection of single phase loads to the three phases
Pull in extra neutral wires
Isolated ground separated from the safety ground
Tuned filter circuits
De-tuned HARMONIC filters
Using equipment with higher pulse number
Active harmonic filter
Remedial measures
-
Various supplier of capacitors offer so called Harmonic proof capacitors.
Harmonic proof capacitors are special designed capacitors, e.g. mixed
dielectric, ALL PP or MPP with thicker dielectric
As explained before the main problem for capacitor failures is resonance
amplification due to series or parallel resonance
Both cases can not be solved with harmonic proof capacitors
From physical point of view only one passive solution is known:
Harmonic filter circuits (de-tuned or tuned)
Harmonic proof capacitors
-
Filter circuits, which are in series connected reactors and capacitors, form a series resonance circuit. Design and dimensioning of the components has to be done in such a way, that one of the following points will be fulfilled:
De-tuned filter circuitThe main purpose of de-tuned filter is to avoid resonance condition of the capacitor with the transformer inductance. Depending of the de-tuning frequency more or less harmonic currents will be sucked from the grid. Very common is a de-tuning to a frequency of 189 Hz (7 %) with a reduction of harmonics of app. 30-50 %.
Tuned filter circuitThe tuning has to be done for each harmonic frequency, means each harmonic frequency requires its own filter circuit. The harmonic current will be reduced by approximately 90 %.
For the fundamental frequency both types are reactive and are working with nearly its full kvar load as a PFC capacitor.
Harmonic filter circuits
-
De-tuned harmonic filters
-
Improvement of Power Factor
Reduction of harmonics
Reduction of ohmic losses, real kW energy savings
Elimination of reactive energy consumption
Elimination of power utilities penalties on low power factor
Power Quality improvement
Climatic protection, reduction of greenhouse gas emissions
Reduction of new investment for distribution equipment
(transformers, LV switchgear, )
Reduction of equipment maintenance cost and down time of
production equipment
Improvement of production process stability
Customer benefits of detuned filters
-
De-tuned harmonic filter
-
WHAT IS THE DEGREE OF DETUNING?
The most common degree of detuning is p = 7 %.
At fn=50Hz as the fundamental network frequency,
this degree of detuning corresponds to a resonance
frequency fres of 189 Hz, which can be calculated
as follows:
p = (f / fres) 100 (in %)
fres =fn
p / %100
De-tuned harmonic filter
EXAMPLES FOR DETUNING-FACTORS (f=50Hz)
5 % 224 Hz5.5 % 213 Hz
5.67 % 210 Hz6 % 204 Hz7 % 189 Hz8 % 177 Hz
12.5 % 141 Hz14 % 134 Hz
-
Supply Voltage Un + Overvoltage:
fn: 50 Hz
Calculation of a 7%-detuned filter:
400 V
p: 7 % fres: 189 Hz
Un = 400 V
1.534
430 V
0.767
Nc / kvar: 25
Uc: 430 V Design: Ucr: 440 V
Qcr / kvar: 28.13 56.27
50
Ln / mH:
154.26 308.52C / F:
462.78 925.56Cy / F:
De-tuned harmonic filter
-
MDC
AC
Previous Example, now for 7%-detuned filter
Resulting harmonic voltage e.g. :
5th (250Hz): 0.025 Ohm 144A = 3.6V 0.9%7th (350Hz):0.045 Ohm 103A = 4.6V 1.1%
System busbar: impedance vs. frequency
Kvar: 400
189H
oo
00,020,040,060,08
0,10,120,14
50 150 250 350 450 550
De-tuned harmonic filter
-
Im p e d a n c e b e h a v io u r o f a s e r ie s in d u c t a n c e c ir c u it
- 3
- 2
- 1
0
1
2
3
0 1 0 0 2 0 0 3 0 0 4 0 0 5 0 0 6 0 0 7 0 0 8 0 0
F r e q u e n c y
In d u c t iv e r e a c t a n c e
C a p a c it iv e r e a c t a n c e
R e s u lt a n t im p e d a n c e
r e s o n a n t f r e q . f r
c a p a c it iv e b e h a v io u r
in d u c t iv eb e h a v io u r
De-tuned harmonic filter
-
De-tuned harmonic filter
-
ImpedanceImpedance
o
00,020,040,060,08
0,10,120,14
50 150 250 350 450 550
189Hz5th 7th 11th
Summary: detuned filter
-
Resonance frequency not close to any harmonic
Filter frequency ffilter < fharmonic
A certain reduction of harmonic distortion
Export of some harmonics content to the HV-system
Capacitors are blocked against resonance, therefore de-tuned
filters are also known as anti-resonance- filter
Summary: detuned filter
-
Tuned harmonic filter
Power factor correction & Filtering harmonics (cleaning the grid)
-
Tuned harmonic filter
-
A typical tuned filter bank at 50Hz fundamental frequency
consists of :
1 filter for the 5th harmonic ( 250Hz),
tuned to 245 Hz
1 filter for the 7th harmonic ( 350Hz),
tuned to 345 Hz
1 filter for the 11th harmonic (550Hz),
tuned to 545 Hz
Tuned harmonic filter
-
Previous Example, now for a TUNED FILTER
Resulting harmonic voltage e.g.:
MDCAC
5 th 7 th 11 thkvar: 200 400 100
System bus bar: impedance vs. frequency
Frequency Hz
5th (250Hz): 0.01 Ohm 144 A = 1.4V 0.4%
7th (350Hz): 0.01 Ohm 103 A = 1.0V 0.2%
0
0,05
0,1
0,15
0,2
0,25
0,3
0,35
0,4
50 150 250 350 450 550
oo o
Tuned harmonic filter
-
Switching sequence of tuned filter: LIFO
Switching in:
Switching out:
3rd 5th 7th 11th
11th7th5th3rd
Tuned harmonic filter
-
Resonance frequencies of the series filter circuits are very close to
existing harmonics
Excellent reduction of harmonics on the bus bars
Capacitors are charged with high harmonic currents
cleaning of the network
No export of additional harmonic load to the HV-system
torture for the capacitors, if they are not rated for this high
effective current
Risk of sucking-off harmonic currents from HV side!!
Summary: tuned filter
-
7th 11th
0
0,050,1
0,15
0,2
0,250,3
0,35
0,4
50 150 250 350 450 550
oo o
5th
Summary: tuned filter
ImpedanceImpedance
-
FINAL COMPARISON:
Remaining harmonic voltage level,for instance for the 7th harmonic:
Capacitor bank without reactors: 12.7%
7% - detuned filter: 1.1%
tuned filter: 0.2%
Harmonic filters
-
EPCOS PFC
1 - Reduces KW Demand2 - Reduces KWH Consumption3 - Eliminates Power Factor Penalty4 - Reduces Monthly Electricity Bill5 - Reduces Maintenance & Downtime
1 - Reduces KW Demand2 - Reduces KWH Consumption3 - Eliminates Power Factor Penalty4 - Reduces Monthly Electricity Bill5 - Reduces Maintenance & Downtime
1 - Improves Voltage2 - Balances Three Phases3 - Filters Surges, Transients4 - Filters Harmonics5 - Improves Power Factor
1 - Improves Voltage2 - Balances Three Phases3 - Filters Surges, Transients4 - Filters Harmonics5 - Improves Power Factor
Savings
Power Quality
+
Up to 34% Savings
Less than 2 Year Payback SatisfiedCustomer
Enhanc
ed Pow
er Quali
ty
Reduce
d Down
time &
Mainte
nance
Return on Investment
-
All components for harmonic filters