pfc harmonic filter

55
EPCOS EPCOS EPCOS EPCOS Power Factor Correction & Harmonic filter EPCOS EPCOS EPCOS EPCOS EPCOS EPCOS EPCOS EPCOS Power Factor Correction & Power Factor Correction & Harmonic filter Harmonic filter

Upload: santhosh-os

Post on 06-Sep-2015

32 views

Category:

Documents


6 download

DESCRIPTION

Pfc Harmonic Filter

TRANSCRIPT

  • EPCOSEPCOSEPCOSEPCOS

    Power Factor Correction & Harmonic filter

    EPCOSEPCOSEPCOSEPCOSEPCOSEPCOSEPCOSEPCOS

    Power Factor Correction & Power Factor Correction & Harmonic filterHarmonic filter

  • Definition:Definition:

    Power Factor, Harmonics, Transients, Power Factor, Harmonics, Transients,

    Voltage and frequency variations and other Voltage and frequency variations and other

    disturbances in electric power supply disturbances in electric power supply

    networksnetworks

    Power Quality

  • Adjustable Speed Drives

    Notching on the input can interfere with other loads on the same branch circuit

    Flat topping of Drive input voltage, heavily distorted current

    Examples for poor power quality

  • Past Past -- load:load: most loads were linearmost loads were linear

    InductionInduction--motors, heating, bulbsmotors, heating, bulbs

    voltage was followed by current voltage was followed by current -- only a few problemsonly a few problems

    Changing load structure

    Features Customer benefits

    Simple and rugged design

    No commutator

    High degree of protection

    High reliability

    Long lifetime

    Favourably-priced

    Unrestricted operation for partial- and overload conditions

    Low maintenance (only the bearings)

    Can be universally used

  • Todays Todays -- loads:loads: most loads act non linearmost loads act non linear

    Computer, motorComputer, motor--control, drives, etc.control, drives, etc.

    Current is pulse shapedCurrent is pulse shaped

    Current is no longer following the sinusoidal wave shapeCurrent is no longer following the sinusoidal wave shape

    Result: HarmonicsResult: Harmonics

    -- Increasing number of sources causing disturbancesIncreasing number of sources causing disturbances

    -- Equipment become more and more sensitive Equipment become more and more sensitive

    -- DeDe--regulated energy marketregulated energy market

    Changing load structure

  • Problems caused by harmonics

  • Non linear loads

    Loads which have non linear voltage-current characteristics are called non linear

    loads. When connected to a sinusoidal voltage, these loads produce non

    sinusoidal currents. Modern power electronic systems result into non sinusoidal

    currents when connected to the sinusoidal networks.

    The non linear devices can be classified under the following three major categories:

    1. Power Electronics: e.g. rectifiers, variable speed drives, UPS systems, inverters, ...

    2. Ferromagnetic devices: e.g. transformers (non linear magnetizing characteristics)

    3. Arcing devices: Arcing devices, e.g. arc furnace equipment, generate harmonics due to the

    non linear characteristics of the arc itself.

    Harmonic disturbances are created by non-linear loads!

    Origin of harmonics

  • Voltage-source DC link converter

    Current-sourceDC link converter

    Cycloconverter

    Design

    Features

    Driveconverter

    Voltage is impressed in the DC link

    SIMOVERT MASTERDRIVESSIMOVERT MVSIMOVERT ML

    Current is impressed in the DC link

    SIMOVERT ASIMOVERT ISIMOVERT S

    Cycloconverter, no DC link

    SIMOVERT D

    ~=

    =~

    M3~

    ~=

    M3~

    ~=

    ~=

    ~=

    =~

    M3~

    Modern drives a main source for harmonics

  • 0%

    20%

    40%

    60%

    80%

    100%

    Order number

    6-pulse

    12-pulse

    6-pulse 100,00% 29,00% 9,00% 6,00% 3,50% 2,50% 2,00% 1,20% 1,10%

    12-pulse 100,00% 2,90% 0,90% 6,00% 3,50% 0,25% 0,20% 1,20% 1,10%

    1 5 7 11 13 17 19 23 25

    HARMONICS fed back by 6/12 pulse rectifier

    Voltage characteristic at the drive converter output (PWM)

    Voltage characteristic at the drive converter output (PWM)

    Current characteristic at the drive converter output

    Current characteristic at the drive converter output

  • Example of a non-linear load: Switched mode power supply

    AC Current Voltage

    Current

    LOAD

    Example for single phase Non-Linear load

  • Harmonic currents or voltages are integer (whole number) multiples of thefundamental frequency.

    Harmonicorder

    F 3rd 5th 7th

    Frequency 50 150 250 350

    Understanding harmonics

  • Overheating of transformers (K-Factor), and rotating equipment

    Increased hysteresis losses

    Neutral overloading / unacceptable neutral-to-ground voltages

    Distorted voltage and current waveforms

    Failed capacitor banks

    Breakers and fuses tripping

    Unreliable operation of electronic equipment, and generators

    Erroneous register of electric meters

    Wasted energy / higher electric bills - KWD & KWH

    Wasted capacity - Inefficient distribution of power

    Increased maintenance cost of equipment and machinery

    Problems caused by HARMONICS

    HARMONICS

    Time

    Am

    plitu

    de

    Fundame

    h3

    h5

    h7

    SUM

  • Additional investment due to faster equipment deratingShorter life time of equipmentHigher energy consumptionHigher downtime of production equipmentHigher maintenance and repair costReduced product qualityReduced production outputInvestment for stronger equipments/components

    alternatively

    One time investment for harmonic filter

    COST caused by HARMONICS

  • Tripping of circuit breakers and fuses Due to resonance effects, the current levels may rise to multifold levels which results into tripping ofcircuit breakers and melting fuses. This situation results into serious problems in industries which relyon the quality of power for the continuous operation of their sensitive processes (e.g. semiconductor)

    Overloading / decrease of life time of transformersTransformers are designed to deliver power at network frequency (50/60Hz). The iron losses arecomposed of the eddy current loss (which increase with the square of the frequency) and hysteresis losses (which increase linearly with the frequency). With increasing frequencies the losses also increase, causing an additional heating of the transformer.

    Overloading of the capacitors Capacitive reactance decreases with the frequencies. Even smaller amplitudesof the harmonic voltages result into higher currents which are detrimental tothe capacitors: I = U * 2 * 3.14 * f * C.

    Losses in distribution equipmentHarmonics in addition to the fundamental current cause additional losses inthe cables, fuses and also the bus bars.

    Effect of harmonics

  • Excessive currents in the neutral conductor Under balanced load conditions without harmonics, the phase currents cancel each other in neutral,and resultant neutral current is zero. However, in a 4 wire system with single phase non linear loads,odd numbered multiples of the third harmonics (3rd, 9th, 15th) do not cancel, rather add together in theneutral conductor. In systems with substantial amount of the non linear single phase loads, the neutral currents may riseto a dangerously high level. There is a possibility of excessive heating of the neutral conductor sincethere are no circuit breakers in the neutral conductors like in the phase conductors.

    Malfunctioning of the electronic controls and computersElectronic controls and computers rely on power quality for their reliable operation. Harmonics resultinto distorted waveforms, neutral currents and over voltages which affect the performance of thethese gadgets.

    Measurement errors in the metering systemsThe Accuracy of metering systems is affected by the presence of harmonics. Watt-hour metersaccurately register the direction of power flow at harmonic frequencies, but they have magnitudeerrors which increase with frequency.The accuracy of demand meters and VAr meters is even less in the presence of harmonics.Wrong multi meter readings. Use true RMS meter!

    Effect of harmonics

  • 3rd harmonic in the neutral conductor

  • 3rd harmonic in the neutral conductor

  • Synthesis of a wave form

  • Limit for harmonics

  • Consumer structure has changed from linear to non linear loads

    Harmonics in the net are increasing

    Increasing unknown energy losses

    Unknown overloads

    Problems in the net become more complex

    Beside convent. PFC, filters become more and more important

    De-tuned filters for most applications

    Active filters for a niche market

    Summary

  • Unlike other solutions that: Waste energy Connect in series Generate higher harmonics (through injection) Have limited fixed sizes and are not expandable Are bulky and expensive

    The Solution EPCOS AG offers:

    Specific harmonic filtering of any magnitude

    Enhanced power quality

    Elimination of associated wasted energy

    Modular and expandable circuitry, to include additional load

    EPCOS Harmonics solution

  • 1. Harmonics can overload PFC capacitors due to over voltage and over current created by the harmonic source and reduced reactance of PFC capacitors at higher frequencies.

    2. But more critical are applications in which the application configuration (PFC capacitor and transformer) form a resonance circuit with anfrequency close to existing harmonic frequencies. In such a caseharmonic currents stimulate the resonance circuit and create resonance amplification with harmful over voltages and over currents.

    Resonance is one of the main reasons for failed PFC capacitors or short life cycle of PFC capacitors!

    Resonance

  • Parallel resonance

  • Meter: 0001 K-f ac tor: 1.041 V olts : 277 Frequenc y :60.01 Hz

    H# % H# % T.H.D.: 2.8% max : 2 .9% min: 0.5% 1 100.0 0 2 0.0 69 3 0.4 116 4 0.1 68 5 2.1 272 6 0.0 69 7 1.6 41 8 0.0 70 9 0.2 133 10 0.0 6811 0.4 11 12 0.0 6813 0.7 36 14 0.1 6815 0.1 68 16 0.0 6817 0.2 37 18 0.0 15819 0.1 69 20 0.0 15821 0.1 327 22 0.0 6923 0.0 69 24 0.0 6925 0.1 301 26 0.0 827 0.0 158 28 0.0 24829 0.1 319 30 0.0 30931 0.2 20 32 0.0 68

    Meter: 0001 K-f ac tor : 1.829 V olts : 290 Frequenc y :59.97 Hz

    H# % H# % T.H.D.: 18.8% max : 21.6% min: 1.9% 1 100.0 0 2 0.1 26 3 0.5 352 4 0.3 31 5 18.8 203 6 0.0 259 7 1.2 126 8 0.0 259 9 0.0 80 10 0.0 20011 0.1 312 12 0.0 25913 0.0 80 14 0.0 8015 0.1 116 16 0.0 20017 0.0 320 18 0.0 16919 0.0 319 20 0.0 25921 0.1 192 22 0.0 25923 0.0 169 24 0.0 34925 0.1 259 26 0.0 25927 0.1 259 28 0.0 34929 0.0 259 30 0.0 25931 0.1 31 32 0.0 79

    Harmonics MAGNIFICATION

    No PFC capacitors With PFC capacitors

    Meter: 0001 K-f ac tor: 1.533 A mps : 1716 Frequenc y :60.01 Hz

    H# % H# % T.H.D.: 13.6% max : 18.1% min: 2.1% 1 100.0 0 2 0.5 100 3 0.4 29 4 0.1 119 5 12.3 53 6 0.4 66 7 5.5 356 8 0.1 91 9 0.7 299 10 0.2 2911 1.3 7 12 0.1 2913 0.1 210 14 0.0 2915 0.3 29 16 0.0 11917 0.3 285 18 0.0 2919 0.0 210 20 0.1 9021 0.1 90 22 0.0 2923 0.0 210 24 0.0 11925 0.1 29 26 0.1 2927 0.0 29 28 0.1 11929 0.1 29 30 0.1 11931 0.0 29 32 0.0 209

    Meter: 0001 K-f ac tor: 32.38 A mps : 2033 Frequenc y : 59.97 Hz

    H# % H# % T.H.D.: 89.5% max : 152.3% min: 3.6% 1 100.0 0 2 2.3 9 3 1.0 169 4 2.9 79 5 150.0 263 6 3.8 259 7 8.7 141 8 1.2 300 9 1.5 280 10 1.5 25911 1.6 259 12 0.8 31013 1.7 279 14 0.5 25915 1.2 79 16 1.1 29417 0.5 260 18 0.3 819 1.0 331 20 0.5 25921 1.5 259 22 0.5 31223 1.2 339 24 0.1 25925 0.5 180 26 0.6 34927 0.9 182 28 0.3 30729 0.7 349 30 0.2 1931 0.6 292 32 0.0 259

    V o

    l t a

    g e

    Cu

    rre

    nt

  • Real case of parallel resonance in KL/Malaysia

  • point of view

    In

    harm onicload

    X Lmotor

    X Ttransformer

    X N, networkimpedance

    X Ccapacitor

    Parallel resonance

    Harmonics present on LV side of the transformer

    Transformer together with PFC capacitors on LV-side

    acts as a parallel resonant circuit

    At resonant frequency the inductive reactance is

    equal the capacitive reactance

    The resultant impedance of the circuit increases to

    very high value at resonant frequency

    Excitation of a parallel resonant circuit results into a

    high voltage across the impedances and very high

    circulating currents inside the loop

    Transformers and capacitors are additionally loaded

    which may cause overloading of them

  • 1) I is constant and imprinted

    DC

    AC

    I Ic IL

    UZ

    What happens in case of parallel resonance?

    1) + 2) voltage U (ohmic law)

    3) With U Ic = IL

    2) Impedance Z

    Parallel resonance

  • U = 20 KVSk = 500 MVA

    P = 500 KW, 6-pulseI50 Hz = 720AI250 Hz = 144AI350 Hz = 103AI550 Hz = 65AI650 Hz = 55AI850 Hz = 42AI950 Hz = 38A

    DCAC

    P = 100 KW

    M

    I350 Hz = A720

    7

    S = 1000 kVA

    uk = 6%Transformer

    U = 400 V

    Qc = 400kvar

    Parallel resonance: example

  • Attention:close to the 7thharmonic!

    DCAC M

    SKLV = STr

    uk 100

    SKLV = 1000 kVA

    6100 = 16.67MVA

    frp = 50Hz SKLV

    Qc

    = 322 Hzfrp = 50 Hz 16.67 MVA

    0.4 Mvar

    Parallel resonance: exampleKC

    TR uQ

    Sf

    =

    10050

  • System bus bar: impedance vs. frequency

    Resulting harmonic voltage for 350 Hz :322 Hz is close to the 7th harmonic

    00,20,40,60,8

    11,21,41,6

    50 150 250 350 450 550

    o

    322Hz

    Frequency Hz

    350 Hz

    0.5

    DCAC M

    I350 Hz = 103 Amp

    U350 = 0.5 * 103A = 51.5V

    Parallel resonance: example

    12.7% 400V51.5V

  • Resonance?

    11 kV level

    132 kV level

    Parallel resonance

    I

    I

    Series resonance

    I

    Capacitorbank

    Transformer1000 kVA, uk = 5 %

    DC drive600 kWcos = 0.65

    ...

    415 V level

    Transformer630 kVA, uk = 5 %

    Capacitorbank

    300 kWcos = 0.65

    ...

    415 V level

    3

    if fr = f Xc 0 Ic

  • Se rie s re so na nce

    0

    24

    68

    10

    1214

    16

    50 100 150 200 250 300 350 400Frequency

    Impe

    danc

    e

    Induc tance

    Reactance

    Im pedance

    fr

    Series resonance

    S

    L

    C

    Series resonant circuit

    S=signal source

    KCNR eQ

    Sv

    =

    1

    100

    The point of series resonance is given by the following formula:

    Series resonant circuit formed by combination of inductive and capacitive reactance. The impedance behavior of this circuit is as illustrated in the diagram. It is seen that at resonant frequency the impedance reduces to a minimal value. Thus the circuit offers very low impedance at the input signal at this frequency which results into multiple fold increase in the current. The voltage drop on the individual component increases moving closer to resonant frequency.

  • Limiting total output of harmonic sources

    Limiting the number of simultaneously operating harmonic sources

    Balanced connection of single phase loads to the three phases

    Pull in extra neutral wires

    Isolated ground separated from the safety ground

    Tuned filter circuits

    De-tuned HARMONIC filters

    Using equipment with higher pulse number

    Active harmonic filter

    Remedial measures

  • Various supplier of capacitors offer so called Harmonic proof capacitors.

    Harmonic proof capacitors are special designed capacitors, e.g. mixed

    dielectric, ALL PP or MPP with thicker dielectric

    As explained before the main problem for capacitor failures is resonance

    amplification due to series or parallel resonance

    Both cases can not be solved with harmonic proof capacitors

    From physical point of view only one passive solution is known:

    Harmonic filter circuits (de-tuned or tuned)

    Harmonic proof capacitors

  • Filter circuits, which are in series connected reactors and capacitors, form a series resonance circuit. Design and dimensioning of the components has to be done in such a way, that one of the following points will be fulfilled:

    De-tuned filter circuitThe main purpose of de-tuned filter is to avoid resonance condition of the capacitor with the transformer inductance. Depending of the de-tuning frequency more or less harmonic currents will be sucked from the grid. Very common is a de-tuning to a frequency of 189 Hz (7 %) with a reduction of harmonics of app. 30-50 %.

    Tuned filter circuitThe tuning has to be done for each harmonic frequency, means each harmonic frequency requires its own filter circuit. The harmonic current will be reduced by approximately 90 %.

    For the fundamental frequency both types are reactive and are working with nearly its full kvar load as a PFC capacitor.

    Harmonic filter circuits

  • De-tuned harmonic filters

  • Improvement of Power Factor

    Reduction of harmonics

    Reduction of ohmic losses, real kW energy savings

    Elimination of reactive energy consumption

    Elimination of power utilities penalties on low power factor

    Power Quality improvement

    Climatic protection, reduction of greenhouse gas emissions

    Reduction of new investment for distribution equipment

    (transformers, LV switchgear, )

    Reduction of equipment maintenance cost and down time of

    production equipment

    Improvement of production process stability

    Customer benefits of detuned filters

  • De-tuned harmonic filter

  • WHAT IS THE DEGREE OF DETUNING?

    The most common degree of detuning is p = 7 %.

    At fn=50Hz as the fundamental network frequency,

    this degree of detuning corresponds to a resonance

    frequency fres of 189 Hz, which can be calculated

    as follows:

    p = (f / fres) 100 (in %)

    fres =fn

    p / %100

    De-tuned harmonic filter

    EXAMPLES FOR DETUNING-FACTORS (f=50Hz)

    5 % 224 Hz5.5 % 213 Hz

    5.67 % 210 Hz6 % 204 Hz7 % 189 Hz8 % 177 Hz

    12.5 % 141 Hz14 % 134 Hz

  • Supply Voltage Un + Overvoltage:

    fn: 50 Hz

    Calculation of a 7%-detuned filter:

    400 V

    p: 7 % fres: 189 Hz

    Un = 400 V

    1.534

    430 V

    0.767

    Nc / kvar: 25

    Uc: 430 V Design: Ucr: 440 V

    Qcr / kvar: 28.13 56.27

    50

    Ln / mH:

    154.26 308.52C / F:

    462.78 925.56Cy / F:

    De-tuned harmonic filter

  • MDC

    AC

    Previous Example, now for 7%-detuned filter

    Resulting harmonic voltage e.g. :

    5th (250Hz): 0.025 Ohm 144A = 3.6V 0.9%7th (350Hz):0.045 Ohm 103A = 4.6V 1.1%

    System busbar: impedance vs. frequency

    Kvar: 400

    189H

    oo

    00,020,040,060,08

    0,10,120,14

    50 150 250 350 450 550

    De-tuned harmonic filter

  • Im p e d a n c e b e h a v io u r o f a s e r ie s in d u c t a n c e c ir c u it

    - 3

    - 2

    - 1

    0

    1

    2

    3

    0 1 0 0 2 0 0 3 0 0 4 0 0 5 0 0 6 0 0 7 0 0 8 0 0

    F r e q u e n c y

    In d u c t iv e r e a c t a n c e

    C a p a c it iv e r e a c t a n c e

    R e s u lt a n t im p e d a n c e

    r e s o n a n t f r e q . f r

    c a p a c it iv e b e h a v io u r

    in d u c t iv eb e h a v io u r

    De-tuned harmonic filter

  • De-tuned harmonic filter

  • ImpedanceImpedance

    o

    00,020,040,060,08

    0,10,120,14

    50 150 250 350 450 550

    189Hz5th 7th 11th

    Summary: detuned filter

  • Resonance frequency not close to any harmonic

    Filter frequency ffilter < fharmonic

    A certain reduction of harmonic distortion

    Export of some harmonics content to the HV-system

    Capacitors are blocked against resonance, therefore de-tuned

    filters are also known as anti-resonance- filter

    Summary: detuned filter

  • Tuned harmonic filter

    Power factor correction & Filtering harmonics (cleaning the grid)

  • Tuned harmonic filter

  • A typical tuned filter bank at 50Hz fundamental frequency

    consists of :

    1 filter for the 5th harmonic ( 250Hz),

    tuned to 245 Hz

    1 filter for the 7th harmonic ( 350Hz),

    tuned to 345 Hz

    1 filter for the 11th harmonic (550Hz),

    tuned to 545 Hz

    Tuned harmonic filter

  • Previous Example, now for a TUNED FILTER

    Resulting harmonic voltage e.g.:

    MDCAC

    5 th 7 th 11 thkvar: 200 400 100

    System bus bar: impedance vs. frequency

    Frequency Hz

    5th (250Hz): 0.01 Ohm 144 A = 1.4V 0.4%

    7th (350Hz): 0.01 Ohm 103 A = 1.0V 0.2%

    0

    0,05

    0,1

    0,15

    0,2

    0,25

    0,3

    0,35

    0,4

    50 150 250 350 450 550

    oo o

    Tuned harmonic filter

  • Switching sequence of tuned filter: LIFO

    Switching in:

    Switching out:

    3rd 5th 7th 11th

    11th7th5th3rd

    Tuned harmonic filter

  • Resonance frequencies of the series filter circuits are very close to

    existing harmonics

    Excellent reduction of harmonics on the bus bars

    Capacitors are charged with high harmonic currents

    cleaning of the network

    No export of additional harmonic load to the HV-system

    torture for the capacitors, if they are not rated for this high

    effective current

    Risk of sucking-off harmonic currents from HV side!!

    Summary: tuned filter

  • 7th 11th

    0

    0,050,1

    0,15

    0,2

    0,250,3

    0,35

    0,4

    50 150 250 350 450 550

    oo o

    5th

    Summary: tuned filter

    ImpedanceImpedance

  • FINAL COMPARISON:

    Remaining harmonic voltage level,for instance for the 7th harmonic:

    Capacitor bank without reactors: 12.7%

    7% - detuned filter: 1.1%

    tuned filter: 0.2%

    Harmonic filters

  • EPCOS PFC

    1 - Reduces KW Demand2 - Reduces KWH Consumption3 - Eliminates Power Factor Penalty4 - Reduces Monthly Electricity Bill5 - Reduces Maintenance & Downtime

    1 - Reduces KW Demand2 - Reduces KWH Consumption3 - Eliminates Power Factor Penalty4 - Reduces Monthly Electricity Bill5 - Reduces Maintenance & Downtime

    1 - Improves Voltage2 - Balances Three Phases3 - Filters Surges, Transients4 - Filters Harmonics5 - Improves Power Factor

    1 - Improves Voltage2 - Balances Three Phases3 - Filters Surges, Transients4 - Filters Harmonics5 - Improves Power Factor

    Savings

    Power Quality

    +

    Up to 34% Savings

    Less than 2 Year Payback SatisfiedCustomer

    Enhanc

    ed Pow

    er Quali

    ty

    Reduce

    d Down

    time &

    Mainte

    nance

    Return on Investment

  • All components for harmonic filters