part a, section 1emanuals.nordson.com/adhesives/3000v/manuals/parta/a3/a... · 2001-09-27 · 1....

38
E 2000 Nordson Corporation All rights reserved 41-3000V Issued 5/00 A3EN-04-[3V-1-MEAR]-7 Part A, Section 1 Installation This section covers the following unit configurations. Model 3100V Voltage 1, 2 Pump Piston (E) Manifold 4-Port (A) Control Vista Temperature (TC)

Upload: others

Post on 05-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Part A, Section 1

Installation

This section covers the following unit configurations.

Model 3100V

Voltage 1, 2

Pump Piston (E)

Manifold 4-Port (A)

Control Vista Temperature (TC)

Page 2: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-0

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Page 3: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-1

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Section A 1Installation

WARNING: Allow only qualified personnel to perform thefollowing tasks. Follow the safety instructions in this documentand all other related documentation.

This section of the manual describes how to

S install the unit, hoses, and gunsS program system settingsS prepare the unit for operation

If you have purchased optional features with your unit, such as alow-level indicator or an input/output (I/O) board, refer to the Optionssection of this manual for installation instructions.

Besides using normal care, you need no special instructions to unpackthe unit or the equipment you purchased with it. All hoses and guns areshipped in separate packages.

After unpacking the equipment, inspect it for any damage that may haveoccurred during shipping. Look for dents and scratches and make sureall fasteners are tight. Report any damage to your Nordsonrepresentative.

This part of the installation section gives you the installation requirementsand recommendations that you need to know before installing your unit.It includes

S Location RequirementsS Wiring RequirementsS Hose/Gun Power Requirements

Other requirements and recommendations are provided in the installationprocedures when they are needed.

1. Introduction

2. Unpacking

3. Inspection

4. InstallationRequirements

Page 4: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-2

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Carefully select the location for the unit and its associated guns andhoses. Make sure that the location meets the following requirements:

S There is enough room to open the tank lid, open the electricalenclosure, remove the filter assembly, remove the pump enclosure,and make electrical connections for the hoses. For unit dimensionsand recommended clearances, refer to Dimensions in the Descriptionsection of this manual.

S An operator can reach all controls.

S Maintenance personnel have room to service and repair the unit.

S Installers can route the hoses without bending them. The minimumbend radius for hoses is shown in Figure A 1-6.

S The mounting surface can support the weight of the unit when the unitis filled with adhesive. Refer to Specifications in the Descriptionsection of this manual.

S The mounting surface is level.

S The mounting surface is raised at least 152 mm (6 in.) for drainingadhesive. See Figure A 1-1.

S The drain valve projects over the edge of the mounting surface.

4130685A

152 mm(6.0 in.)

Fig. A 1-1 Required Clearance for Draining and Filter Flushing

Location Requirements

Page 5: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-3

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

See Figure A 1-2. To install a Series 3100V unit, you will need an areathat is at least

S 796 mm (32 in.) highS 875 mm (35 in.) longS 550 mm (22 in.) wide

4130395

1

2

3

Fig. A 1-2 Space Requirements for Operation and Maintenance

1. Removing the pump enclosure(796 mm [32 in.])

2. Opening the unit and connectinghoses (875 mm [35 in.])

3. Removing the manifold filter(550 mm [22 in.])

Page 6: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-4

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Follow these guidelines when installing wiring to the unit:

S Allow enough room to route your electrical service line to the unit.You can use either of the two access holes in the base of the unit forelectrical service. One hole is for rear access and the other is forbottom access.

S Route any wires away from AC power lines, solenoid output lines,and electrical equipment such as motors, contacts, and relays.

S Make connections with the minimum length of wire needed. A longwire can act as an antenna for electrical noise.

The power requirements of your hoses and guns must be determined tomake sure that you do not overload the unit. If your Nordsonrepresentative has not already checked to see that your unit can supportall of the hoses and guns you plan to install, you need to calculate yourhose/gun power requirements now. You also need to check yourcalculations if you change your system configuration or add new hosesand guns.

To determine your hose/gun power requirements, refer to CalculatingHose/Gun Capacity at the end of this manual. If you need help with thisprocedure, contact your Nordson representative.

Wiring Requirements

Hose/Gun Power Requirements

Page 7: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-5

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

This part of the installation section gives you the procedures for installingthe unit mechanically. It includes

S Mounting the UnitS Installing the Tank StrainerS Connecting the Air SupplyS Installing GunsS Installing Hoses

For electrical installation procedures, refer to Electrical Installation later inthis section.

Use this procedure to mount your unit.

1. Remove the bolts that secure the unit to the shipping pallet. Save thebolts for later use.

2. For installation within the European Community, find the packet ofadhesive-backed, local-language warning tags that was shipped withthe unit. Overlay the non-English language part of the tags alreadyon this unit with the tags from the packet in your own language.Carefully follow the instructions in the packet for the correctplacement of the tags.

WARNING: Take care when lifting the unit. Using inadequatemeans to lift the unit can cause equipment damage, personalinjury, or both.

3. Using a suitable lifting device that is capable of lifting the unit, positionthe unit on the mounting surface. To determine the weight of yourunit, refer to Specifications in the Description section of this manual.

4. Check to see that the unit is level. Provide shims as needed.

5. Using the unit’s base as a guide, drill four holes in the mountingsurface for 8-mm (5/16-in.) mounting bolts.

5. Mechanical Installation

Mounting the Unit

Page 8: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-6

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

6. See Figure A 1-3. Secure the unit to the mounting surface with thebolts you removed in step 1.

4130009A

Fig. A 1-3 Securing the Unit to the Mounting Surface

Follow this procedure to install the tank strainer.

1. Locate the tank strainer that was shipped with your unit.

2. Remove all wrapping from the strainer. Small pieces of wrapping cancause blockage in the pump.

3. Open the tank lid.

4. Place the strainer on the fins in the bottom of the tank. Position thecutout in the strainer around the pump.

5. Close the tank lid.

Mounting the Unit (contd.)

Installing the Tank Strainer

Page 9: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-7

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Follow this procedure to connect the air supply to your unit

1. See Figure A 1-4. Install the air pressure regulator, gauge, and filterthat were shipped with your unit.

4130014A

Fig. A 1-4 Installing the Air Pressure Regulator, Gauge, and Filter

2. Turn the regulator fully counterclockwise (off).

NOTE: Nordson recommends installing a shutoff valve with alock-out in the air supply line to isolate the unit from the air supply formaintenance procedures.

3. Connect a supply of clean, dry air to the input air fitting or shutoffvalve.

NOTE: To achieve the rated adhesive output of the unit, you mustconnect a plant air supply that is capable of providing the maximumair pressure specified on the unit. The maximum air pressure is either483 kPa (70 psi) or 620 kPa (90 psi), depending upon the type ofpump your unit has. To find the maximum air pressure for your unit,check the air pressure tag, which is located next to the inlet air port,above the hose connectors.

Connecting the Air Supply

Page 10: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-8

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

This part of the installation section refers you to the correct installationprocedure for the type of gun you plan to install. Use Figure A 1-5 todetermine which type of gun you are installing, an air-operated gun, anelectric gun, or a hand-operated gun. Then refer to one of the followingprocedures:

S To Install an Air-Operated GunS To Install an Electric GunS To Install a Hand-Operated Gun

NOTE: Air-operated and electric guns are also referred to as automaticguns.

4130692

Fig. A 1-5 Air-Operated Gun (left), Electric Gun (center), and Hand-Operated Gun (right)

To Install an Air-Operated Gun

Follow the instructions in the manual shipped with the gun to completethese procedures:

S Mount the gun on the production line.S Install the gun solenoid valve.S Connect air to the solenoid valve.S Connect a triggering device to the solenoid valve.S Connect a hose to the gun.

Instructions for connecting the hose and gun cordsets are given later inthis section. Refer to Connecting Gun and Hose Cordsets.

Installing Guns

Page 11: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-9

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

To Install an Electric Gun

Follow the instructions in the manual shipped with the gun to completethe following procedures:

S Mount the gun on the production line.S Install the gun driver.S Connect power to the driver.S Connect a triggering device to the driver.S Connect a hose to the gun.

Instructions for connecting the hose and gun cordsets are given later inthis section. Refer to Connecting Gun and Hose Cordsets.

To Install a Hand-Operated Gun

Follow the instructions in the manual shipped with the gun to connect thehose to the hand-operated gun. One end of the hose is wired to the gun;the other end connects to the unit. Instructions for connecting the hoseand gun cordsets are given later in this section. Refer to Connecting Gunand Hose Cordsets.

Follow this procedure to route the hoses and connect them to the gunsand the unit.

1. Follow the instructions in the gun manual to connect a hose to eachgun, but do not connect the gun cordsets at this time.

2. Route the hose from the gun back to the unit. Make sure the hosedoes not contact sharp or abrasive surfaces. Follow the hose-routingguidelines shown in Figure A 1-6.

Installing Hoses

Page 12: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-10

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

5920010

P/N 111 940

X=13 mm (0.50 in.)

R=203 mm (8.00 in.)

P/N 271 486 -- 8 mm (5/16 in.)P/N 274 174 -- 16 mm (5/8 in.)

X

P/N 274 174 -- 29 mm (1 1/8 in.)

Fig. A 1-6 Hose Installation Guidelines

Installing Hoses (contd.)

Page 13: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-11

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

WARNING: Hose ports that are unused must be closed with aplug. Removing plugs can cause hot adhesive to spray or flowfrom the port and injure operators.

CAUTION: Failure to connect the first hose as instructedcreates a dead area where char builds up, causing downtime.

3. Remove the O-ring plug from the hose port where you plan to installthe first hose. See Figure A 1-7 for the correct sequence for installinghoses. Keep the O-ring plug for later use during maintenance andservicing procedures.

41301384 3 2 1 1 2 3 4

Fig. A 1-7 Correct Sequence for Installing Hoses

4. See Figure A 1-8. Take one of the hose-connector fittings that wasshipped with the unit and apply an anti-seize compound to thethreads. Thread the fitting into the hose port.

4103398A

Fig. A 1-8 Threading the Hose Connector Fitting into the Hose Port

Page 14: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-12

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

5. Tighten the fitting with a wrench.

6. Connect a hose to the fitting. Use two wrenches to tighten the hoseas shown in Figure A 1-6.

7. Install any additional hoses by repeating steps 2--6. Be sure toconnect a second hose next to the first, working from right to left. Youcan connect a maximum of four hoses this way.

This part of the installation section includes procedures that requireinstalling wiring or making electrical connections. Before making anyelectrical connections, first make the required mechanical connections.Refer to Mechanical Installation in this section.

WARNING: Allow only qualified personnel to perform electricalconnections. Observe the safety instructions.

CAUTION: If you are adding hoses and guns to an existingsystem, make sure that you do not exceed the maximum powercapabilities of your unit. Refer to the Calculating Hose/GunCapacity section of this manual.

Follow this procedure to connect gun and hose cordsets.

1. Determine whether you are installing an automatic gun or ahand-operated gun. An automatic gun is either air-operated orelectrically operated. A hand-operated gun is manually operated (seeFigure A 1-5).

Installing Hoses (contd.)

6. Electrical Installation

Connecting Gun and HoseCordsets

Page 15: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-13

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

2. Follow the instructions below that apply to the type of gun you areinstalling.

CAUTION: If you are connecting a hand-operated gun, takecare not to connect the heater wires to the resistancetemperature detector (RTD) wires. Otherwise, the controlsystem or RTD will be destroyed when the system is placed inoperation.

Type of Gun Connection

Automatic Connect the gun cordset to the electricalconnector at the end of the hose.

Hand-operated Follow the instructions in the gun manual toconnect the cordset and wires at the end of thehose to the gun. Be sure not to connect thewires for heater power to the RTD. Otherwise,the control system or RTD will be destroyedwhen the system is placed in operation.

3. Find the hose plug of the first hose you connected to the manifold.

4. See Figure A 1-9. Connect this hose plug to electrical receptaclenumber 1 on the unit.

5. If you have additional guns and hoses, continue connecting gun andhose cordsets. Connect the cordset of the next hose (the hoseclosest to the rear of the unit) to the hose electrical receptacle labelednumber 2 on the unit. Continue connecting gun and hose cordsets,working from the rear of the unit to the front of the unit, until you haveconnected all gun and hose cordsets.

4103958A

Fig. A 1-9 Connecting a Hose Cordset to the Unit

Page 16: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-14

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

To make the electrical connections inside the unit, follow this procedureto open the unit and access the electrical enclosure.

WARNING: Risk of equipment damage, personal injury, ordeath. Disconnect and lock out electrical power to the unit.

1. Place the unit’s POWER switch in the off position and disconnect andlock out electrical power to the unit at the branch circuit disconnectswitch.

2. See Figure A 1-10. Loosen the captive screws on the electricalenclosure lid, lift the lid from the unit, and prop it against the pumpcover. Take care not to disconnect the ground wire.

3. Make sure the support strap is not wrapped around any boardcomponents. Untangle the strap if necessary.

4. Loosen the two captive screws on either side of the control-end frameand lower the frame. You may need to pull the front and rear panelsapart to release the frame.

5. Avoid direct contact with internal electrical connections, components,or wiring.

6. Make sure all ground wires are securely connected.

4130849A

Fig. A 1-10 Opening the Electrical Enclosure

Opening the ElectricalEnclosure

Page 17: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-15

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Follow this procedure to connect the standard output contacts that areprovided on all units. If you do not wish to connect any outputs, skip tothe next procedure, Connecting Electrical Service.

Output contacts allow you to automatically activate other equipment or toactivate devices for remote monitoring of the unit’s operations.Table A 1-1 describes the standard output contacts. If your unit has anoptional input/output (I/O) board, there are additional outputs and severalinputs you can connect. Refer to Series 3000V TC Input/Output Board inthe Options section.

Table A 1-1 Standard Output Contacts

Output Contact Function

System Warning Used to signal a device that will alert remotelylocated operators of a warning condition

System Fault Used to signal a device that will alert remotelylocated operators of a system fault condition. Thisoutput is typically used to turn on a light or to soundan alarm.

System Ready Used to signal a device that will alert remotelylocated operators that the system is ready foroperation (up to temperature) or that the unit’spump is on. This output is typically used to send aready signal to a production line so that the lineturns on only when the unit is ready to pumpadhesive.

7. If you have not already done so, open the electrical enclosure. Referto Opening the Electrical Enclosure in this section.

8. If you have not already done so, carefully remove a knockout holeplug from one of the larger holes on either the back side or the bottomof the unit (whichever is most convenient for your operation). Avoidcontact with any printed circuit boards.

9. To protect the wiring, install a strain relief in the hole. Refer to thefollowing table for the appropriate size strain relief.

Table A 1-2 Strain Relief Sizes for Knockouts

Size of Knockout Hole Size of Strain Relief to Install

23 mm (15/16 in.) PG-16 or 1/2-in. trade size

29.5 mm (15/32 in.) PG-21

35 mm (13/8 in.) 1-in. trade size

Connecting Output Contacts(Optional)

Page 18: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-16

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

WARNING: Risk of equipment damage, personal injury, ordeath. For a proper and safe installation, make sure you meetthe requirements in the following step.

10. See Figure A 1-11. Route the output contact wires (3) through thestrain relief (1) and the three ferrites (2) from the ship-with kit toterminal block TB2 (4). Make sure your installation meets theserequirements:

S Use 0.34--0.25 mm2 (22--24 AWG) stranded wire that is suitablefor National Electrical Code (NEC) Class 1 remote control andsignaling circuits. Output contacts are rated for 250 VAC, 2 Amaximum.

S Use the proper length of wire and route the wires so they do nottouch any of the printed circuit boards. Make sure the wires reachterminal block TB2 when the electrical enclosure is opened.

S Position the ferrites as close to the rear panel as possible.

4130385A

1

2

3

4

1

2

Fig. A 1-11 Connecting Output Contacts

1. Strain relief2. Ferrites

3. Output contact wires 4. TB2 terminal block

Connecting Output Contacts(Optional) (contd.)

Page 19: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-17

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

11. Connect the output wires to the plug for terminal block TB2 from theship-with kit. Refer to Table A 1-3.

Table A 1-3 Output Contact Connections

Output Contact asLabeled on Power

Behavior of Contact TB2 PositionsLabeled on PowerBoard Unit Power Off Unit Power On

TB2 Positions(see Note A)

Warning Contact(System Warning)

Open Closed(no warning)

Open(warning exists)

1, 2

Fault Contact(System Fault)

Open Closed(no fault)

Open(fault exists)

3, 4

Ready Contact(System Ready)

Open Open(unit not ready)

Closed(unit ready)

5, 6

NOTE A: The output contacts are not polarity sensitive. It does not matter which wire is inserted into a position.

12. Connect the plug to TB2. See Figure A 1-11 for the location of TB2.

13. Go to the next procedure, Connecting Electrical Service.

Page 20: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-18

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Follow this procedure to connect electrical service to your unit.

1. Open the electrical enclosure. Refer to Opening the ElectricalEnclosure in this section.

2. See Figure A 1-12. Locate the identification plate on your unit.

4130690A

123456

Fig. A 1-12 Location of Identification Plate

3. See Figure A 1-13. Determine the voltage specification of your unitby looking at the VOLTS (ac) portion (1) of the identification plate.

4130689A

1

2

Fig. A 1-13 Unit Identification Plate

1. VOLTS (ac) portion 2. AMPS (max.) portion

Connecting Electrical Service

Page 21: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-19

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

CAUTION: Operate the unit only when it is connected to thecorrect line voltage, as shown in Table A 1-4. Operating the unitat a different voltage can damage the unit or impair itsperformance.

4. Ensure that your unit has the correct voltage specification to acceptthe type of electrical service that you will be connecting to it.Table A 1-4 shows all the Series 3000V voltage specifications and thetypes of electrical service that you can connect to each.

Table A 1-4 Types of Electrical Service for Each Voltage Specification

Unit VoltageSpecification(See Note A)

VoltageCode

(See Note B)

Types of Service You Can Connect to the Unit See Note

200--240 VACor3 AC 230Vor3/PE AC 200--240V

1 200--240 VAC 1 (two wire service without a neutral) 200--240 VAC 3 (three wire service without a neutral)

3/N/PE AC 400/230V 2 230 VAC 1 (two wire service, including a neutral) 400/230 VAC 3 (four wire service, including a neutral)

CD

NOTE A: The voltage specification is shown in the VOLTS (ac) portion of the unit’s identification plate.B: The voltage code is part of your unit configuration code. It is included here for information only and is

not something you need to know to install your electrical service line. For more information about yourunit configuration code, refer to Explanation of Configuration Code at the end of the Description section.

C: This type of service also includes voltage used primarily in the British Commonwealth: 240 VAC 1(two wire service, including a neutral)

D: This type of service also includes voltage used primarily in the British Commonwealth: 415/240 VAC 3(four wire service, including a neutral).

Page 22: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-20

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

5. See Figure A 1-13. Size your electrical service line based on themaximum amperage shown in the AMPS (max.) portion (2) of theidentification plate. The line must also meet local electrical coderequirements.

WARNING: Risk of equipment damage, personal injury ordeath. Install a strain relief to protect wires from beingdamaged by the edges of the knockout hole.

CAUTION: Circuit boards can be easily damaged. Avoid anycontact with circuit boards when removing a knockout hole plug.

6. If you have not already done so, remove and discard the plug from aknockout hole on either the back side or the bottom of the unit(whichever is most convenient for your operation) and install a strainrelief in the hole. Refer to the following table for the appropriate sizestrain relief.

NOTE: Your unit may have several knockout holes. You should routeyour electrical service wiring through a smaller hole.

Table A 1-5 Strain Relief Sizes for Knockouts

Size of Knockout Hole Size of Strain Relief to Install

23 mm (15/16 in.) PG-16 or 1/2-in. trade size

29.5 mm (15/32 in.) PG-21

35 mm (13/8 in.) 1-in. trade size

Connecting Electrical Service(contd.)

Page 23: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-21

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

7. Route the electrical service line to the unit.

WARNING: Use the proper length of cable. Inadequate wirelength could result in disconnection at TB1 when you open theoperator panel. Excess wiring can be pinched when you closethe panel, causing equipment damage, personal injury, ordeath.

8. See Figure A 1-14. Route the electrical service line through the strainrelief, determine the length of cable required to reach terminalblock TB1 and the ground terminal, and cut the cable.

4130764

1

2

Fig. A 1-14 Routing the Electrical Service Line Through the Strain Relief

1. Strain relief 2. Electrical service line

Page 24: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-22

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

9. Remove the required amount of cable insulation and wire insulationand then secure the cable with a cable strap of the correct size, asshown in Figure A 1-15. Three different sizes of cable strap areprovided: one is attached to the unit just below the power board andthe other two are included in the ship-with kit.

4130763

1

2

Fig. A 1-15 Installing the Cable Strap on the Electrical Service Line

1. Electrical service line 2. Cable strap

10. Connect the ground wire of your electrical service line to the groundterminal below TB1 as shown in Figure A 1-16.

4130765

Fig. A 1-16 Connecting the Ground Wire

Connecting Electrical Service(contd.)

Page 25: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-23

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

11. Connect the remaining wires of the electrical service line to TB1 asshown in Figure A 1-17. Refer to Table A 1-6 to determine whichillustration in Figure A 1-17 shows the type of service line you areconnecting.

Table A 1-6 Key to Illustrations in Figure A 1-17

Number of Wires in Your Service Line(excluding the ground wire) Type of Service Illustration in Figure A 1-17 to

Use for Connecting ServiceSeeNote

Four wires (including a neutral) 400/230 VAC 3 Illustration A

Three wires (without a neutral) 200--240 VAC 3 400 VAC 3

Illustration B

Two wires (including a neutral) 230 VAC 1 Illustration C A

Two wires (without a neutral) 200--240 VAC 1 Illustration D B

NOTE A: If the VOLTS (ac) label on your unit is 3/N/PE AC 400/230V (voltage code 2), your unit is designed toaccept two wires with a neutral. Check the identification plate on your unit for the VOLTS (ac) label.

B: If the VOLTS (ac) label on your unit is 3 AC 230 V (voltage code 1), your unit is designed to accept twowires without a neutral. Check the identification plate on your unit for the VOLTS (ac) label.

L1 L2 L3 NL1 L2 L3 NL1 L2 L3 N

4130766A B C D

L1 L2 L3 N

Fig. A 1-17 Electrical Service Connections at TB1 (with ground wire shown)

12. If you connected three-phase power to the unit, go to Closing theElectrical Enclosure in this section. If you connected single-phasepower to the unit, go to the next procedure, Preparing the Unit forSingle-Phase Operation.

Page 26: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-24

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

All units are shipped to accept three-phase power. If you are supplyingsingle-phase power to your unit, use this procedure to modify your unit toaccept single phase power.

1. See Figure A 1-18. Locate the voltage plug on the power board. It isplugged into connector X3.

4130551

X3

Fig. A 1-18 Location of Voltage Plug on Power Board

Preparing the Unit forSingle-Phase Operation

Page 27: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

4130427

Installation A 1-25

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

2. Remove this three-phase voltage plug from connector X3 and replaceit with the appropriate voltage plug supplied in the installation kit. Avoltage plug is shown in Figure A 1-19. The part number of the plugyou must install is listed in Table A 1-7 and on the label of theelectrical enclosure lid.

Table A 1-7 Voltage Plug Part Numbers

Type of Service Part Number ofSingle-Phase Plug to Install

200--240 VAC single phase 227 567

230 VAC (with neutral) single phase 232 617

NOTE: If you are supplying 230 VAC (with neutral) single-phaseservice, the voltage plug consists of two connectors jumperedtogether. The large plug connects to connector X3 on the powerboard and the small plug connects to connector X4, which is locatednext to connector X3.

3. Go to the next procedure, Closing the Electrical Enclosure.

Fig. A 1-19 Typical Voltage Plug

Page 28: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-26

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

After you have completed electrical installation, follow this procedure toclose the electrical enclosure.

1. Reconnect any ground wires that may have become disconnectedduring electrical installation.

2. Raise the control-end frame into place and tighten the captive screwson each side of the frame. You may need to pull the front and rearpanels apart to position the frame.

3. Position the electrical enclosure lid on top of the unit and secure itwith the captive screws.

4. Remove the lock-out and turn on the power at the branch circuitdisconnect switch.

Before running your unit, program the unit for your operations. For thesystem to operate, you must, at a minimum, program the temperaturesetpoints for the tank, the hoses, and the guns. All programming is donefrom the Display area of the operator panel. From the Display area, youcan

S specify the operating (setpoint) temperature for each heated zone(the tank, all hoses, or all guns)

S choose Celsius or Fahrenheit temperature display

S specify the overtemperature setpoint (the temperature at which azone is determined to be too hot) for all heated zones

S set a system-ready time delay that begins when all zones reachoperating temperature and ends when the READY light turns on (thisdelay allows additional time for the adhesive to melt)

Figure A 1-20 shows the display area of the operator panel.

Closing the ElectricalEnclosure

7. System ProgrammingProcedures

Page 29: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-27

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

4130386

1

2

3

4

Fig. A 1-20 Operator Panel

1. System status area2. Display area

3. Feature list4. Power switch

You will probably find it helpful to read Control System in the Descriptionsection of this manual before programming any system controls. ControlSystem briefly describes the function of each control you will program.

Page 30: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-28

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

For programming purposes, each heated system component (tank, hose,and gun) belongs to a temperature setpoint group, referred to as a zone.You set the desired operating temperature for each zone. The defaultsetting for all zones is OFF (less than 38 �C or 100 �F). To turn a zoneon, you must set the setpoint temperature to 38 �C (100 �F) or higher.

Follow these guidelines when you are programming your temperaturesettings. Use the next procedure, Programming System Controls, toprogram your temperature settings.

S Check the Manufacturer’s Safety Data Sheet (MSDS) for therecommended operating temperature of the adhesive you will use.

S To turn a zone on, set the operating temperature at 38 �C (100 �F) orhigher, up to a maximum of 232 �C (450 �F).

S Before programming any temperature settings, make sure theovertemperature setpoint is at least 14 �C (25 �F) higher than thehighest setpoint temperature.

Use this procedure to program your unit, including setting thetemperature setpoints.

1. If you have not already done so, turn the unit on by pressing thePOWER switch.

2. See Figure A 1-21. Press the Up key (5) below the Selectordisplay (1) until the feature number you want shows in the display. Asthe feature number changes, the Multipurpose display changes toshow the setting for that feature.

NOTE: Nordson recommends that you program features 4 and 5 firstso you can display temperatures the way you want and so you canset your setpoint temperatures later without being blocked by theovertemperature setpoint.

NOTE: To access features 4, 5, or 6, press both Up keyssimultaneously.

Guidelines for ProgrammingTemperature Settings

Programming System Controls

Page 31: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-29

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

3. Press the Up or Down keys (4) below the Multipurpose display (2)until the display flashes.

4. Use the Up and Down keys below the Multipurpose display to adjustthe setting for the feature. Refer to Table A 1-8 for a list of featuresand the default setting and optional settings for each feature.

5. Press the Enter key (3) to save the setting. The display stopsflashing and reverts to showing the actual temperature of feature 1.

4130364

1 2

4 35

Fig. A 1-21 Display Area

1. Selector display2. Multipurpose display3. Enter key

4. Up and Down keys5. Up key

6. Record your setting on the form provided at the end of this section.Refer to Records of System Settings.

7. Repeats steps 2--6 for each feature you want to program.

Page 32: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-30

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Table A 1-8 Control System Features and Settings

FeatureNo.

Feature Description DefaultSetting

Optional Settings

1 TankTemperatureSetpoint

Allows you to specify the setpoint temperaturefor the tank.

(-- -- --)(Off)

38--232 �C(100--450 �F)

2 HosesTemperatureSetpoint

Allows you to specify the setpoint temperaturefor all hoses. (See Note A.)

(-- -- --)(Off)

38--232 �C(100--450 �F)

3 GunsTemperatureSetpoint

Allows you to specify the setpoint temperaturefor all guns. (See Note A.)

(-- -- --)(Off)

38--232 �C(100--450 �F)

4 Celsius/Fahrenheit

Allows you to specify whether the displayshould show Celsius or Fahrenheitmeasurements. (See Note B.)

C(Celsius)

F(Fahrenheit)

5 OvertemperatureSetpoint

Allows you to specify the maximumtemperature any zone can reach before thesystem initiates a fault condition. This settingmust be at least 14 _C (25 _F) higher than thehighest application setpoint temperature (SeeNote B.)

200 (�C) 52--246 (�C)[(125--475 (�F)]

6 System-ReadyTime Delay

Allows you to set the amount of additional timethe adhesive needs to melt after all zones havereached their setpoint temperatures. At the endof the system ready time delay, the READYlight turns on. (See Note B.)

18(minutes)

0--60 (minutes)

NOTE A: If, after your unit has been placed into operation, you decide to add, remove, or replace a hose or gun,refer to Procedure for Adding, Removing, or Replacing a Hose or Gun in the Operation section of thismanual to ensure that your unit properly recounts and stores the number of hoses or guns connected toit. Otherwise, an RTD fault will occur.

B: To access features 4, 5, or 6, press both Up keys simultaneously.

Programming System Controls(contd.)

Page 33: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

4103270

Installation A 1-31

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Follow these procedures to flush the system and prepare it for firstoperation.

WARNING: Allow only qualified personnel to operate the unit.

Use this procedure to fill the tank with unmelted adhesive. Beforecontinuing, refer to General Hot Melt Material Processing Instructions atthe beginning of this manual.

1. If you have not already done so, program your unit. Refer to SystemProgramming Procedures in this section.

2. Open the tank lid.

WARNING: Use a metal or plastic scoop to fill the tank withadhesive. Never use your bare hands.

3. See Figure A 1-22. Use a metal or plastic scoop and fill the tank withadhesive to within 25 mm (1 in.) of the top of the tank.

4. Close the tank lid.

5. As the system scans through the system settings, check that alltemperatures are set as recommended by your adhesive supplier.

6. Go to the next procedure, Flushing the System.

Fig. A 1-22 Filling the Tank withAdhesive

8. System Preparation

Filling the Tank with Adhesive

Page 34: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-32

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Before operating your unit for the first time, flush the system by pumpingadhesive through it to remove trapped air and residue left during factorytesting.

1. Use one of the following methods to prevent accidental guntriggering:

S Air-operated guns: turn off the operating air.S Electric guns: turn off the gun driver.S Hand-operated guns: lock the trigger.

WARNING: Hot! Risk of burns. Wear heat-protective clothing,safety goggles, and heat-protective gloves.

2. Place a drain pan under each gun and remove all gun nozzles.

3. If the unit is not already on, press the power switch to turn the unit on.Allow the unit to reach operating temperature.

4. Clean the manifold filter. Refer to Cleaning a Standard Manifold Filterin the Maintenance section of this manual.

5. Prepare each gun in your system for operation as follows:

S Air-operated guns: increase the operating air pressure to240 kPa (35 psi).

S Electric guns: turn on the gun driver.

S Hand-operated guns: unlock the trigger.

WARNING: Trapped air may still be in the hoses and guns.Shield the area and operator from splashing adhesive.

6. Trigger the guns, keeping them open so that no pressure builds up.

NOTE: You may need to adjust the gun air pressure depending onthe viscosity of the adhesive and the gun response.

Flushing the System

Page 35: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-33

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

7. Gradually increase air pressure to the pump by turning the airpressure regulator clockwise.

8. Allow adhesive to flow out of the guns until all trapped air, cleaningsolution, and impurities are flushed out of the system. If the pumpslows noticeably or stops, increase pump air pressure slightly.

9. Stop triggering the guns.

10. Reduce pump air pressure to 0 by turning the air pressure regulatorfully counterclockwise.

11. Trigger the guns momentarily to relieve trapped hydraulic pressure.

WARNING: Hot! Risk of burns. Wear heat-protective clothing,safety goggles, and heat-protective gloves.

12. Attach the nozzles to the guns.

13. Adjust the pump air pressure regulator until the air pressure is at thedesired operating setting. Test adhesive patterns as necessary.

14. Air-operated guns only: adjust the gun air pressure regulator until theair pressure is at the desired operating setting. Test adhesivepatterns as necessary.

15. If your system has an air-operated pump or gun, record the initial airpressure settings in the Records of System Settings at the end of thissection.

16. Refer to the gun product manual for additional setup information forthe specific gun.

Page 36: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-34

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Use these forms to record your system settings and system faults. Therecords of your system settings will be useful if you ever need toreprogram the system. You may want to give a copy of these forms toothers in your workplace who need the information.

Table A 1-9 Record of Programmed Settings

FeatureNo.

Feature Default Setting Optional Settings Your Setting

1 Tank TemperatureSetpoint

(-- -- --) (Off) 38--232 (_C)[100--450 (_F)]

2 Hoses TemperatureSetpoint

(-- -- --) (Off) 38--232 (_C)[100--450 (_F)]

3 Guns TemperatureSetpoint

(-- -- --) (Off) 38--232 (_C)[100--450 (_F)]

4 Celsius/Fahrenheit _C (Celsius) _F (Fahrenheit)

5 OvertemperatureSetpoint

200 (_C) 52--246 (_C)[125--475 (_F)]

6 System-Ready TimeDelay

18 (minutes) 0--60 (minutes)

Table A 1-10 Record of Air Pressure Settings

System Component Air Pressure Setting

Pump

Gun 1

Gun 2

Gun 3

Gun 4

9. Records of SystemSettings

Record of ProgrammedSettings

Record of Air Pressure Settings

Page 37: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

Installation A 1-35

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7

Table A 1-11 Record of System Faults

Day Occurred Fault Action Taken

Record of System Faults

Page 38: Part A, Section 1emanuals.nordson.com/adhesives/3000V/manuals/parta/a3/a... · 2001-09-27 · 1. Introduction 2. Unpacking 3. Inspection 4. Installation ... Mounting the Unit (contd.)

InstallationA 1-36

E 2000 Nordson CorporationAll rights reserved

41-3000VIssued 5/00

A3EN-04-[3V-1-MEAR]-7