operators manual for mm1 series hood - evs...

38
MM1 Series Hoods Model: MM1 Form#: OM032_MM1_Series_Hoods Date: 04-13-2016 - Rev2 Operators Manual for MM1 Series Hood Manual provides Operation, Maintenance and Service Instructions

Upload: dangdiep

Post on 19-Apr-2018

223 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

MM1 Series Hoods Model: MM1

Form#: OM032_MM1_Series_Hoods Date: 04-13-2016 - Rev2

Operators Manual for MM1 Series Hood

Manual providesOperation, Maintenance and Service Instructions

Page 2: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

2MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

GENERAL DESCRIPTION Halton’s MM1 Series hood is designed to efficiently capture and remove the grease, smoke, and other effluents generated when cooking with pizza ovens. The hood is designed to mount close to the top of the pizza oven which provides an operational advantage of capturing the grease, smoke and other effluents directly above the pizza oven outlets. By localizing the capture area the hood can efficiently capture and effectively eliminate convective heat spillage to the store.

The MM1 has a control panel that is designed to set the exhaust airflow based on the number of oven decks in operation to maximize energy savings potential. Exhaust airflow is monitored at all times via a T.A.B. (Test And Balance) Port installed in the hood plenum. A wiring harness connects between the pizza oven’s blower motor control boxes and exhaust hood’s control panel to report when the oven is on and how many oven decks are operating. Additionally, makeup air operation (on/off) is dictated by the control panel to maintain kitchen space air balance. An oven wiring harnesses and current switches to monitor the pizza ovens are included and are shipped inside the control panel for field installation. The control panel contains a terminal strip for field connection to the exhaust fan, the fire suppression system (if required) and the make up air fan (if used). All wiring must conform to local electrical and building codes. Field wiring instructions begin on page 19.

The exhaust hood’s control panel is recessed into the rear fascia panel of the hood, with status lights on the control panel face for troubleshooting purposes. The indicator lights show status for each oven deck, status of the exhaust fan and the makeup air unit. A manual override switch to drive the hood to full design airflow is incorporated as well. This switch should only be used if a problem occurs with the hoods control panel sensing the pizza oven’s individual decks on/off status. Field wiring of the control panel interface with the pizza oven decks, using the oven wiring harness, should be performed before the oven/hood is placed in its final position, especially if the oven is to be positioned near a wall. Access to the pizza oven’s blower motor control box for each deck is required to complete the oven wiring harness installation process.

Make up air, if used, should operate any time the exhaust fan for the pizza hood is on to assure the proper air balance in the kitchen. The only exception to this is during a fire event in the pizza oven. In this case the exhaust fan will remain on and the make up air will shut off.

Part of the Control Panel wiring is a provision to detect a dry contact (micro switch) closure in the fire suppression system when the fire suppression system activates. Two wires from the terminal strip contacts numbered 9A and 10 must be connected between the fire suppression system and the control panel for correct exhaust fan operation in the event of a fire event. Local fire codes typically require the exhaust fan to turn on during a fire event. See detailed field wiring instructions starting on page 19.

Oven power (natural gas and electric) must be tied into the fire suppression dry contacts (micro switches) to ensure shutdown of cooking equipment in case of a fire. For electrical control, this is typically achieved by tying the oven power inlet to a shunt trip breaker connected to the fire suppression dry contacts. For natural gas supply, an electronically actuated solenoid valve is tied to the fire suppression dry contacts.

The control panel is only to be used with an EC (electronically commutated) equipped exhaust fan. Optional low voltage transformer must be factory installed when selecting the exhaust fan.

For Installation and Control Wiring questions: call EVS at 586-779-0996.

Page 3: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

3MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

SYSTEM CAPABILITIES The hood system is ETL listed in both the United States and Canada for use with the Middleby-Marshall PS360G, 536, 540, 555, 570, 636, 640 and 670 model ovens, both gas and electric. The hood can be used with single, double or triple-stack configurations at the design exhaust airflows shown on the submittal drawings in Appendix 1. Optional side skirts (Model MMSS) can also be utilized with all oven configurations (single, double and triple stack) to reduce the required exhaust airflow. An optional eyebrow over the front loading window is available when desired or required by local codes.

SYSTEM OVERVIEW

Page 4: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

4MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

PARTS IDENTIFICATION

Page 5: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

5MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

ITEMS SHIPPED INSIDE CONTROL PANEL

Page 6: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

6MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

MODEL MM1 INSTALLATION INSTRUCTIONSSUGGESTED SEQUENCE OF ASSEMBLE

1. Uncrate hood and side skirts (if side skirts were ordered). Inspect the crating carefully. If there are signs of damage, call the freight carrier before uncrating the units. Uncrate the units carefully. ** Important note ** Do not leave units out in the weather for an extended time period. The protective PVC covering around the hood will become very difficult to remove if left exposed to the weather conditions for a long period of time. The hood will be hung from the ceiling support structure using ½” all thread rods and ½ - 13 nuts. Use the hanging brackets that are attached to the back of each hood pod section, 4 places, to anchor the all thread rods at the hood. For structural calculations assume the hood assembly weighs 500 lbs. The fascia panels between the pods are removable to facilitate assembly. Removing the front panel will allow easier access to the top of the hood and the ductwork assembly. Additional parts are shipped inside the control panel. Remove the shipping cover that protects the control panel face by removing the four screws that hold it in place. Save the four screws but the shipping cover may be discarded. Remove the four additional screws that hold the control panel face and inside you will find the oven wiring harness with an 8 pin connector on one end and three 2 pin connectors on the other end, three current switches in boxes and a wiring diagram in a packing list envelope. Do not lose these parts found inside the control panel; they are very important to the operation of the MM1 hood. The control panel will be replaced using all 8 screws after all field wiring is completed.

Page 7: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

7MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

2. Add the oven wiring harness and current switches to interface between the oven’s blower control boxes (one per oven deck) and the hood control panel. The harness interconnects each oven deck with the control panel on the MM1 hood. Adding this harness is easier to accomplish before the oven and hood are located near a wall or other obstruction that would complicate access to the blower control boxes.

Oven Wiring Harness Installation Instructions (8 pin Connector)

A. Ensure the power to the oven is disconnected prior to wiring the control panel and oven.

B. Locate the control panel at the exhaust hood and wiring diagram for the system. Review the wiring diagram and all instructions prior to beginning the process.

C. Install current switches on blower fan as shown in photos below. Locations vary among ovens; examples are shown for the 360G and 570/670. Remove necessary shrouding to access the blower fan wiring. The wire to the motor should be temporarily disconnected to allow the wire to pass through the provided current switch. After insertion of the wire through the switch, replace the wire to the terminal. Route the current switch wiring in such a manner that it is in a safe position away from any moving parts using zip ties as necessary and ensure that the Molex connector is easily accessible for connection. See examples below.

Installation of Current Switch on 360G

Page 8: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

8MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Installation of Current Switch on 570/670

Alternate Installation of Current Switch on 570/670, wires routed into electrical access panel

Page 9: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

9MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Alternate 570/670 Installation of current switch

D. Locate the wiring harness for connection between the oven and control panel. The harness consists of 3 pairs of cable to connect to each deck for operation status. For single and triple stack ovens, the remaining pairs will not be used and are to be stored in a neat, safe fashion in the lowest oven deck.

E. It will be necessary to drill holes as shown in the photos below to allow for harness routing. Install grommets to avoid chafing of wires. Holes should 7/8” diameter to allow grommet insertion. Locations shown are approximate - red circles indicate hole location, yellow dashed line indicates proposed harness routing. Installed harness examples are shown as well.

Note: On the 570/670 ovens if the wires are routed through the electrical access panel drilling the hole can be avoided. If wires are routed in this fashion ensure they are not pinched in any of the doors. See the alternate 570/670 examples below.

Page 10: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

10MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

360G Harness Routing, 2 Deck Example

360G Harness Installation Example

Page 11: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

11MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

670 Harness Routing, 3 Deck Example

670 Harness Installation Example

Page 12: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

12MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Alternate 570/670 Install Example with wires secured to thermostat line

Alternate 570/670 Install Example

Avoid attaching adhesive pads directly to areas that get hot during cooking.

F. The 8 pin connector should be positioned near the control panel location with sufficient slack to allow for connection to the panel. Secure with fastener mount cable holders as necessary, see photo below.

Page 13: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

13MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Cable Holder Installation with Self Tapping Screw Example

G. Route the 3 wire pairs from the harness along the paths shown and down into the first oven deck control cabinet. Each pair will be labeled to indicate appropriate oven deck. Locate Deck 1 2-pin connection and connect to the current switch. Ensure the all wires are safely installed using fastener mount cable holders and zip ties as necessary, see photo below.

H. Repeat the process for the remaining oven decks.

I. When an extra connection is present, safely store in the lowest cabinet, see photo below. The harness is designed to accommodate a triple stack oven.

Current Switch Connection to Wiring Harness

Page 14: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

14MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Extra Plug Stored in Lowest Oven Cavity Example

J. Upon installation of the harness and current switches, connect the 8 pin connection of the oven harness to the mating connector on the control panel.

3. Carefully position oven/hood combination in its final location.

4. Hang hood from ceiling support structure with all thread support rods (page 3). Check fit of side skirts to hood before completing attachment.

5. Assemble side skirts to oven/hood (page 16, 17, 18). Side skirts, when desired, may be installed on both pods or are sometimes only required on the intake end of the oven. See the job specific submittal drawings or cut sheets for guidance on the locations and number of the side skirts. Side skirts are installed, if desired, by fastening the upper edges of the side skirt to the lower edges of the hood pod end walls where holes are provided for this purpose. Plastic knob fasteners are included to attach the top of the side skirt to the bottom edge of the hood. Tabs are provided along the side skirt flange which runs down the oven body which allows the side skirt to be attached to the oven at predetermined points. These points are places where the end plugs or other parts are to be fastened or already are fastened to the oven. Install the side skirts before the end plugs or motor housings for new installations. For existing installations remove the screws holding the end plug or other part in place and locate the side skirt tabs over the screw holes. The screw(s) are then reinstalled through the slotted tabs, and tightened to hold the side skirt in position. Different models of ovens have different accessories. The side skirts often fasten under the screws that hold on the end plugs. The rear side skirt may have holes to allow the photocell sensor to operate through the side skirt. Align these holes with the photocell feature when installing the rear side skirt. The rear skirts often fasten under one of the sets of screws that hold on the motor housing. If the side skirts were ordered as an option, but will not be used, a blue jumper wire in the control panel must be removed from between terminals 1 and 2. Please see details; item seven on page 26 and wiring diagram page 29.

Page 15: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

15MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Side Skirt Attachment Side Skirt Knobs

Side Skirt Attachment

Side Skirt Attachment

Page 16: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

16MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Page 17: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

17MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

6. Assemble ductwork. The MM1 hood is ducted to the exhaust fan with NFPA 96 compliant ductwork. The hood is fabricated with a 14” X 14” exhaust collar. When the hood is used with a triple stack oven the exhaust duct should be 14” X 14” to the exhaust fan. When the hood is used with a single or double stack oven the exhaust duct should be 11.5” X 11.5” to the exhaust fan. A transition from the 14” X 14” exhaust collar to 11.5” X 11.5” exhaust

Page 18: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

18MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

duct is included to make the connection to the exhaust ductwork. The exhaust collar and the transition have 1” flanges to facilitate connection to the exhaust ductwork. All duct connections must be 100% liquid tight welded per NFPA 96 requirements.

The MM1 hood may also be connected to Metal Fab pre-engineered exhaust ducting. The hood would then be ordered with a 14” diameter round exhaust collar attached to the hood and comes with a 14” diameter by 9” tall round extension for the duct (Metal Fab part no. 14PSW9) and duct connector (Metal Fab part no. 14RHC, called a flange band in the following instructions) and a tube of caulk (P080 sealant) which is used in the assembly of the duct sections. Appendix 2 is an instruction sheet from Metal Fab which describes the assembly of the duct sections. These instructions must be followed carefully and completely.

7. Replace fascia panels if they have been removed.

8. Complete Ansul installation (page 22, Fire Suppression System) if required.

A. Locate the hood control panel and remove and discard the shipping cover (keep the screws) and remove the control panel face plate. The control panel is located at the rear of the hood assembly, recessed into the rear fascia panel between the hood pods, see photo below.

B. Field wire terminals F9A and F10 to an open set (when Ansul fire suppression system is cocked) of dry contacts on one of the Ansul system micro switches. The Ansul micro switches are found in the Ansul Automan Regulated Release assembly. The contacts will close when the system discharges. This will send a signal to the control panel that the fire suppression system has actuated. Fire suppression systems may not be required in some jurisdictions. Skip this step if no fire suppression system for the ovens is in place.

Control Panel Locations Wiring harness and Current switches shippedInside Control Panel

Page 19: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

19MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

C. Terminals M98 and M99 are a normally open dry contact that must be field wired to complete a start circuit for a Make Up Air fan, if one is present. The dry contact (CR1) will close when a signal is sent to start the exhaust fan. Maximum voltage for this circuit is 24 volts. The control panel will close the normally open contacts of the 24 volt Control Relay 1 (located in the control panel) to which terminals M98 and M99 are connected, when the exhaust fan turns on. This circuit is optional dependent upon makeup air unit configuration. Please refer to site drawings to determine if required. The field wiring from Terminal Strip contacts M98 and M99 to the make up air start/stop contactor shall be 2 strands and 18 gauge minimum.

D. Field wire terminals E34, E35 and SH (shield) to the exhaust fan control box on the exhaust fan. The wire from terminal E34 connects to the “0-10V” termination on the exhaust fan control box, the wire from terminal E35 connects to the “Common” termination. At the exhaust fan, 0-10VDC and Common are noted as shown in the Exhaust Fan Control photo below. Terminate the wire shield to a chassis ground at the control panel. Suggested field installed connection for the exhaust fan is 2 strand, 18 gauge minimum, shielded, plenum rated cable.

Terminal Strip

Page 20: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

20MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Exhaust Fan Control

Page 21: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

21MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

9. Connect hood to 120V building power source. Connect a three wire 120V, 15A circuit to terminals L (Line), N (Neutral) and G (Ground) in the Power Supply Box.

10. Commission system (starting on page 25). Make sure grease filters and grease cups are installed in place before start-up.

11. Check airflow balance in store, and perform final inspection (page 26).

For Installation and Control Wiring questions: call EVS at 586-779-0996.

Downloadable manuals may be found at www.evsvent.com

FIRE SUPPRESSION SYSTEMThe MM1 hood may be ordered pre-piped with a fire suppression system. Local codes or a desire for enhanced fire safety may dictate the inclusion of fire protection in the hood. The hood, if ordered pre-piped, will come with the detector bracket and fire protection nozzles installed in the exhaust plenum of both hood pods to cover the requirements of the duct protection and exhaust plenum protection. The local Ansul fire system installer must supply the distribution piping, Ansul Automan and suppressant tanks, detector conduit and wire rope runs, fusible links, remote pull station, Ansulex liquid fire suppressant and all other supplies to complete the fire system installation. If appliance protection is required the local Ansul installer must also design and install the distribution piping and nozzles for this requirement. This work must be performed by the Ansul system installer. The side skirts on the rear of the hood require notches to be cut or holes to be punched to allow access for the appliance protection distribution piping. Notches would be used if the side skirts are to be removed for cleaning later. The illustrations below depict the typical layout for an MM1 hood fire system. The pre-pipe components supplied by Halton are shown in solid lines and the components supplied by others are shown in dashed lines. The complete fire system must satisfy the requirements of the National Fire Protection Association (NFPA), Underwriters Laboratories Standard 300 and all local codes and Authorities Having Jurisdiction.

Please note: Maintain all clearances necessary for access, maintenance and cleaning when the oven is positioned for final assembly and installation of the fire suppression system.

Page 22: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

22MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

MM1 Typical Fire Suppression System Isometric View

Page 23: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

23MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

MM1 Typical Fire Suppression System Schematic

Page 24: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

24MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

MM1 FIELD COMMISSIONING INSTRUCTIONS

Operation Notes1. The Hood Control Panel is configured in such a manner that exhaust fan and makeup air unit

will be on when any combination of ovens are powered.

2. In the event of a fire, the make up air fan start/stop signal will switch to off and exhaust fan will go to full speed.

3. When the manual override is activated, the exhaust fan will operate at full speed.

Commissioning1. Ensure that the oven wiring harness is installed, all field connections are made and power is

applied to the control panel, exhaust fan and oven.

2. Locate the status indicator lights on the control panel face, see photo below.

3. Turn on the top oven deck and verify that the Exhaust Fan, the Make Up Air and the Top Deck (Oven 1 Status) lights are illuminated. See the status designations in photo below.

Control Panel Face

Page 25: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

25MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

4. Verify that the exhaust fan and the makeup air fan functions as they are intended to.

5. Repeat the process for the other oven decks.

6. When fire protection is required, consult with the Authority Having Jurisdiction on the required performance test.

7. If side skirts were ordered as an option but will not be used a jumper wire in the control panel circuitry must be removed. Remove the front cover of the control panel. Remove the BLUE wire jumper between terminals 1 and 2. This will initiate an override setting that will change the default exhaust fan airflows to a higher airflow setting for each of the three oven deck airflows. The higher airflows are necessary if the side skirts are not used.

8. If ovens are a WOW series oven (Oven Models 770, 670, 640, 360G - ovens will say WOW! on the front as well as have sensors near the belts and a touch screen on the front) the RED jumper from terminals 3 to 4 should be removed. (page 31).

Status Designation on Control Panel

Page 26: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

26MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

AIR BALANCE

1. After installation is complete, it will be necessary to check and balance the airflows for the building.

a. Note: Adjustments to the exhaust fan should not be made without consulting EVS. The control system varies the exhaust flow based on the number of decks in operation as determined by inputs from the oven wiring harness and T.A.B. Port.

2. To ensure proper hood performance, locate all makeup and supply air diffusers a minimum of 2 feet away from the exhaust hood perimeter.

3. To ensure that proper air balance is maintained, the makeup air unit shall be interlocked with the exhaust fan operation.

a. Note: When a fire suppression system is installed, the makeup air unit is configured to be OFF in the event of a fire while the exhaust fan is to run at full design airflow.

4. After the system has been placed into service and the balancing of airflows has been accomplished, a final inspection should be made. Check for unusual noises, excess exhaust or supply rates and general operation of the system.

HOOD MAINTENANCE

1. Clean the hood pods inside and out as needed with mild soap and water. Never use harsh or abrasive cleaners on Stainless Steel or Painted surfaces.

2. Clean the hoods’ grease filters and grease cups daily, first washing by hand, and then placing them into a dishwasher for cleaning or by steam cleaning them.

Please Note: Handle the Grease filters carefully

Standard Equipment• 4 Aluminum Filters• Exhaust Hood is Listed per UL710• Exposed Surfaces are 430 Stainless Steel

Optional Equipment• Side Skirts (Painted is Optional)• Front Eyebrow Section • Cool Front Modified End Panels

Page 27: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

27MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

PARTS LIST

Description Halton Part NumberFilter –12” x 16” Aluminum Baffle 10163Filter - 12” x 20” Aluminum Baffle 1016414” x 14” to 11.5” x 11.5” transition 574439” Duct Collar Extension 14PSW9 (3AO) (Round Duct) 11461Collar Connector 14PICRHC (3AO) (Round Duct) 11462

WIRING DIAGRAMS

Page 28: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

28MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Wiring Diagram Detail – Oven Wiring Harness, 8 Pin Connector

Page 29: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

29MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Wiring Diagram Detail – Field wiring close up

Airflow Jumper Detail –Wiring close up

Page 30: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

30MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Wiring Diagram Detail – Jumper wiring close up

Page 31: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

31MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Appendix 1

Cut Sheets for the MM1 Series Hoods

Page 32: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

32MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Page 33: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

33MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Page 34: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

34MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Page 35: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

35MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Page 36: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

36MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Page 37: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

37MM1 Series Hood Installation, Operation & Maintenance Manual OM

032/

0420

16/r

ev2/

EN

Appendix 2

Pre-Fab Duct Installation

Page 38: Operators Manual for MM1 Series Hood - EVS Inc.evsvent.com/wp-content/uploads/2016/08/OM032_Halton_MM1Series... · Operators Manual for MM1 Series Hood ... The exhaust hood’s control

WARRANTY

Halton Company warrants all MM1 hoods for a period of 12 months from date of shipment to be without defects in workmanship and material. Omissions or defects will be re- placed or repaired at Halton’s option. Halton will not accept labor charges without prior approval.

GENERAL INSTALLATION

Upon receipt of the Halton hood, inspect it immediately for any shipping damage and notify carrier immediately if damage is found. Halton will not accept responsibility for any shipping damage, but will assist with getting a claim filed if needed.

There are no instructions contained within this manual for installation or maintenance of fan pack-ages. See appropriate manufacturer’s manual for detailed instructions.

It is the responsibility of the installing contractor to see that the system installation is completed in accordance with the project plans and specifications and that it meets all specific requirements of lo-cal code officials. The local authority having jurisdiction could overrule some of the installation details written in this manual. The installation shall be in accordance with NFPA-96. All electrical systems shall be installed following local and national codes.

It is very important that the system be turned over to the owner in the best condition pos- sible. The owner and/or operator should be instructed in the proper operation, care and maintenance of the system.

If questions or complications should arise during the installation of the Halton hood that cannot be solved using the instructions, please contact EVS at 586-779-0996. For Warranty questions or issues please contact the Halton office at 1-800-442- 5866.

Continuous product improvement is a Halton policy, therefore specifications and design are subject to change without notice.

For Warranty issues:101 Industrial Drive

Scottsville, KY 42164800-442-5866 (800-4-HALTON)

www.halton.com

For Installation and Control Wiring questions: call EVS at 586-779-0996.