mr. geoff carnegie canadian hydro developers, …...november 22, 2007 mr. geoff carnegie canadian...
TRANSCRIPT
November 22, 2007 Mr. Geoff Carnegie Canadian Hydro Developers, Inc. 34 Harvard Road Guelph, ON N1G 4V8 Re: Fall 2007 Acoustic Audit Amaranth Transformer Station, Melancthon I Wind Plant Certificate of Approval (Air) Number 2233-6X9NBQ
Dear Mr. Carnegie,
As requested, Howe Gastmeier Chapnik Limited (HGC Engineering) has undertaken an acoustic audit of the Amaranth Transformer Station (TS) associated with the Melancthon I Wind Plant. This audit represents the first of four seasonal audits that will be conducted of the TS noise, as a condition of Certificate of Approval (Air) Number 2233-6X9NBQ issued October 17, 2007 by the Ministry of Environment (MOE).
In summary, the results of the fall 2007 audit are:
1) The data indicate that the noise impact from the TS at the three closest residences was in compliance with the MOE guidelines during the measurement period.
2) It appears that the residents’ concerns may be more related to audibility than to numerical magnitude of the sound level. By itself, audibility does not indicate non-compliance with the MOE Guidelines
3) While no evidence of unusual acoustic phenomena was found on the transformer side of the barrier, and the transformer fans are not an issue, there were periods when the sound levels on the switch side of the acoustic barrier wall were higher than expected. This phenomenon has not
Canadian Hydro Developers, Inc. Page 2 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
been adequately explored at this time, and will be further addressed during the subsequent acoustic audits.
The acoustic audit is presented in the following sections.
We trust that this information is sufficient for your current needs, and we look forward to working with you in the future.
Howe Gastmeier Chapnik Limited
Nick McCabe, PEng Brian Howe, MEng, PEng
Canadian Hydro Developers, Inc. Page 3 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Introduction
The acoustic audit followed the requirements of MOE guideline NPC-233 “Information to be Submitted for Approval of Stationary Sources of Sound”, and also followed the methodology described in a letter prepared by HGC Engineering dated September 17, 2007, agreed to by Dr. Al Lightstone of Valcoustics Canada Ltd. (Valcoustics) and the John Kowalewski of the MOE. This letter, developed with input from the surrounding residents, is attached as Appendix A.
The acoustic audit was based upon a complex series of attended and unattended sound measurements and other data recorded between October 1 and October 9, 2007. These include:
• Attended and automated unattended sound level measurements conducted on the TS site, on both sides of the acoustic barrier;
• Attended and automated unattended sound level measurements conducted at the three principal receptors;
• Electrical power data provided by Canadian Hydro Developers, Inc. (Canadian Hydro) and verified against Independent Electrical System Operator (IESO) data for the same period;
• Meterological data monitored at one of the residences during the measurement period
• The residents’ own logs of observations made during the measurement period.
Throughout this report, the acronym ‘TS’ is used to refer to the transformer station as a whole. However, there are times when the transformer itself is meant, and at these times, the word ‘transformer’ is used.
Background
As part of the C of A application process, Aercoustics Engineering Ltd. (Aercoustics) prepared an Environmental Noise Impact Study for the TS, dated August 21, 2006 along with a supplement dated September 12, 2006. That work addressed the noise impact from the transformer at five neighbouring residential receptors, one of which belongs to the lessor of the land the TS is on. The other four receptors, which are located predominantly to the south, west and northwest of TS, at distances ranging between 360 and 560 m, were predicted by the report to experience sound levels exceeding the nighttime criteria of the MOE when accounting for the tonality of noise produced by the transformer.
A 6.5 metre high Durisol wall has been constructed on three sides of the transformer, although not around the station switchgear or control equipment. Following construction of the acoustic barrier wall, an acoustic evaluation of the transformer was undertaken by HGC Engineering in February of 2007. However, due to inclement weather occurring during the measurements, and restrictions in access to the adjacent private lands at that time, only a limited evaluation was possible. Nonetheless, that report concluded that the measurements made in February 2007 indicated that the TS was operating in compliance with the MOE guideline limits.
Canadian Hydro Developers, Inc. Page 4 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Following publication of that evaluation, the MOE and other parties requested additional information. Thus, in preparation for this audit, a protocol document was prepared with input from the local residents, Valcoustics on behalf of the Township of Amaranth, and the MOE. Several drafts of the protocol were prepared, and the final version, dated September 17, 2007 forms the basis of the measurement methodology underlining this audit report, and is attached as Appendix A. This audit represents the first of four seasonal audits that will be conducted at the transformer station.
Site Description
The TS is located on the east side of 10th Line, south of 15th Side Road, in Amaranth Township, County of Dufferin. There is one 100 MVA GE Prolec transformer on the TS site, along with supporting ancillary facilities. Figure 1A shows the TS in relation to the surrounding roads and residences, and Figure 1B illustrates the TS itself. Photo Plate 1 shows the acoustic barrier wall shielding the nearest residences from the transformer.
There are five residences near the TS. One of these is the participating landowner and is not considered in this assessment. The three closest residences are the key receptor locations, and these are described in Table 1, with the Receptor ID following the nomenclature used in the original Aercoustics report.
Table 1. Summary of Receptors.
ID Description Distance from Substation [m]
R01 214292 10th Line – northwest of TS 390 R02 214242 10th Line – southwest of TS 360 R04 214215 10th Line – south of TS 490
Receptor R01 is located to the northwest of the TS, and is partially illustrated by Photo Plate 2. A number of trees exist around the home and barn, but the area is otherwise quite open, with fields surrounding the structures.
Receptor R02 is the closest home to the TS, and is partially illustrated by Photo Plate 3. The area around the home and work shed is nearly entirely exposed, with no significant trees.
Receptor R04 is heavily treed, and considerable background sound results from these trees. Two barns exist on the property, which is partially illustrated by Photo Plate 4.
Canadian Hydro Developers, Inc. Page 5 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Criteria
Under the MOE’s guideline NPC-232 “Sound Level Limits for Stationary Sources in Class 3 Areas (Rural)”, the most stringent of the applicable criteria is 40 dBA during the nighttime hours (23:00 to 07:00). This sound level criterion has been selected as the governing sound level limit for the TS.
MOE guideline NPC-104, “Sound Level Adjustments”, specifies a 5 dB penalty for a tonal sound source such as a transformer. Applying the penalty to the sound levels produced by the operation of the TS to the criterion results in an effective criterion is 35 dBA (5 dB less than the 40 dBA criterion).
Canadian Hydro is proposing to install a second transformer on the site in order to service power for the proposed Melancthon II Wind Plant. The new transformer is proposed for installation beside the existing unit, but we understand that additional acoustic treatments are being considered. The 35 dBA effective sound level will apply to the TS as a whole. If the sound level impact of each of the two transformers and associated equipment is 32 dBA or less at the most impacted closest receptor, then the aggregate impact will meet the 35 dBA requirement (32 dBA plus 32 dBA results in a combined sound level of 35 dBA). Thus, 32 dBA is used as the effective target sound level for the existing equipment in this report.
It is important to realize that the guideline documents of the MOE do not require that noise from sound sources be inaudible at a residence. In fact, it should be understood that in a very quiet rural environment, a sound level of 35 dBA will be audible at times.
The sound level limits of the MOE guidelines are presented in terms of hourly energy equivalent average sound levels, designated LEQ. This means that if sound levels vary somewhat over an hour, it is the average sound level rather than the maximum or minimum sound levels which is relevant.
Background sound levels are also at times quantified by determining the ninetieth percentile (L90) sound level. An L90 sound level represents the level which was exceeded 90% of the time during a measurement. NPC-232 indicates that using the L90 to determine sound level criteria is appropriate in some cases, although under the guideline a criterion derived in this way can not be less than the 40 dBA upon which the 32 dBA target level is based; this audit uses the most stringent criterion of the MOE. L90 sound levels are also useful as they allow some separation of steady sound from an overall measured sound level. That is: when a continuous steady sound is masked at times by transient sounds such as those caused by wind gusts, birds, vehicles, and animals, the L90 sound level tends to more accurately reflect the sound level impact of the stationary sound by itself than does the LEQ sound level.
Canadian Hydro Developers, Inc. Page 6 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Measurement Methodology
The study is based on a complex collection of data series, obtained during the period from Monday, October 1 to Tuesday, October 9, 2007. A week-long period was chosen to collect data under a variety of weather conditions, and to include periods of different ambient sound conditions including day and night periods, and weekday and weekend periods.
Non-acoustic Data
Various measurements of non-acoustic quantities such as wind speed and power production were required to conduct this audit. To acquire this information, a number of actions were taken:
• On October 2, an automatic meteorological station was deployed at receptor R02 to record wind speed, wind direction, temperature and humidity. This data is attached to this report as Appendix B;
• Canadian Hydro deployed a current logging system to record any periods where the transformer fans were in operation before the acoustic measurements commenced on October 1;
• The residents agreed to record observations regarding the subjective impact of the sound of the TS throughout the measurement period. Summaries of the residents logs are attached to this report as Appendix C;
• Following the measurements, power production data was also acquired from Canadian Hydro and from the IESO. The data is attached as Appendices D and E, respectively. The data obtained directly from Canadian Hydro agreed with the IESO data.
Unattended Acoustic Measurements
Seven unattended sound level meters were deployed, and configured to record energy equivalent average (LEQ) sound levels in 10-minute intervals. L90 sound levels were also recorded. The locations of these instruments are shown on Figures 1A and 1B. Descriptions of the meters are provided in the Instrumentation section of this report, and records of the measurements are included in Appendixes F and G.
Three sound level meters were deployed inside the TS fenceline, about two metres west of the east fence and thus about 30 metres from the centre of the transformer. These three locations are identified as Locations 1, 2 and 3 on Figure 1B. These monitors were on the transformer side of the acoustic barrier wall, with a line of sight to the equipment. One of these three was positioned to the northeast of transformer, one to the east and one to the southeast, but all with a view of the transformer. Three instruments were used at this location, rather than a single instrument, in order to provide some spatial averaging of the sound levels near the transformer.
Canadian Hydro Developers, Inc. Page 7 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
One sound level meter was placed on the switch side of the acoustic barrier wall (Location 4), approximately 30 metres from the centre of the transformer, monitoring noise from the switchgear. Observations indicated that at the time, the transformer audibility was very low at this location.
One instrument was then placed at each of the three residences described in Table 1, near to the dwellings. Locations were selected in conjunction with discussions with the residents, and were generally near the houses themselves, with no more acoustic screening from the TS than the homes themselves experienced.
Attended Acoustic Measurements
Attended measurements were made at the receptors during both daytime and nighttime hours during the period from October 4 to October 5, 2007. Observations as well as sound levels were made. The instrumentation used for the attended measurements is described in the Instrumentation section of this report.
A variety of attended measurements were also conducted at various locations around the TS on October 4, 2007. These latter measurements were generally intended to:
• Investigate the spectrum of the noise radiated by the TS;
• Verify typical sound levels emitted by the TS and radiated in different directions;
• Investigate propagation of sound with distance from the TS;
• Ensure that the acoustic barrier wall is providing attenuation to the noise from the transformer;
• Investigate the potential significance of noise from the transformer cooling fans;
• Investigate the potential significance of power production at the wind farm on the noise of the transformer.
Measurements were conducted simultaneously at three locations to the south, east, and northwest, of the transformer at a distance of about 30 to 40 metres. These locations are identified in Figure 1B as Location 8 through Location 10, respectively. At this distance, the sound of the TS was clearly the dominant source of noise. The three locations were then moved further from the TS to investigate propagation with distance. As requested by the MOE, the microphones were manually swept in a continuous fashion over as large an area as practical while standing in one spot in an attempt to minimize any local effects of acoustic radiation patterns, modal interference, small-scale shielding phenomena, etc. which might cause variations in measured sound level from location to location. Several cycles of microphone location changes occurred during each 5 minute measurement. Larger swept areas were not used as footsteps were found to generate excessive noise.
Canadian Hydro Developers, Inc. Page 8 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Specific TS operating conditions were investigated by forcing the cooling fans on and then off, and by shutting down all wind plant turbines for a period of about 15 minutes during the measurements.
Instrumentation
MOE publication NPC-102, “Instrumentation” provides specifications for sound level measurement instrumentation. All equipment used in the Audit meets these requirements.
Unattended Acoustic Measurements
Six Bruel & Kjaer Integrating Sound Level Metres were used for the unattended monitoring, together with a Larson Davis sound level analyzer. The instruments are described in Table 2, below.
Table 2: Instrumentation used For Unattended Sound Level Measurements
Measurement Location Instrument Make and Model Instrument Serial Number
Inside fenceline, NE location Bruel and Kjaer Type 2238 2448501 Inside fenceline, E location Bruel and Kjaer Type 2236 2039554 Inside fenceline, SE location Larson Davis LxT 0001724 Inside fenceline, SW location Bruel and Kjaer Type 2236 1735525 Receptor R01 Bruel and Kjaer Type 2238 2262611 Receptor R02 Bruel and Kjaer Type 2238 2562612 Receptor R04 Bruel and Kjaer Type 2238 2343948
Both of the 2236 and 2238 sound level meters meet the specifications contained in NPC-102, however the newer Type 2238 sound level has replaced Type 2236 in the Bruel and Kjaer catalogue. The clocks of all seven instruments were synchronized.
Correct calibration of the acoustic instrumentation was verified using Bruel and Kjaer and Rion acoustic calibrators. Wind screens were used on all microphones, consistent with the requirements of NPC-103, “Procedures”.
Meteorological data was collected using a Davis Instruments Corp. Vantage Pro2 weather station, equipped with an anemometer, wind vane, thermometer, hygrometer and barometer. The system was configured to record data in 10 minute intervals. The MOE guidelines indicate that sound level measurements should not be conducted during periods with high wind speeds. Specifically, NPC-102 indicates that measurements of low sound levels should not be undertaken when winds exceed 15 km/h. However, as the winds in Amaranth Township are frequently strong, making the
Canadian Hydro Developers, Inc. Page 9 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
area the subject of interest for wind farm projects, some consideration of the sound level during higher wind speeds is appropriate. The data from the weather station is presented in Appendix B.
Attended Acoustic Measurements
Three Hewlett Packard Type 3569A Real Time Frequency Analyzers (serial numbers 3222A00134, 3222A00199 and 3442A00141), in conjunction with Bruel & Kjaer Microphones, were used for the attended measurements. Correct calibration of the acoustic instrumentation was verified using Bruel and Kjaer and Rion acoustic calibrators. Wind screens were used on all microphones, consistent with the requirements of NPC-103.
Assessment and Discussion
Unattended Acoustic Measurements – Transformer Station
Figure 2 shows the sound levels measured at four points around the transformer, within the fenced area. The northeast, east and southeast locations (Locations 1 through 3) are near the transformer, and on the transformer side of the acoustic barrier wall; they show relatively steady levels of 45 to 55 dBA over the week. Site observations indicate that sound from the TS is clearly the dominant noise at these locations. In the absence of unusual phenomena, a sound level of 55 dBA at a distance of 30 metres from the transformer would be expected to result in a sound level of about 33 dBA at the closest residence (360 metres away), not accounting for the effect of the acoustic barrier wall or the absorption of sound by the air and ground. Thus, the unattended sound level measurements at the TS indicate that the impact of the transformer itself should be in compliance with the MOE guideline limits at the closest residences, even with no acoustic barrier wall.
The southwest monitor location (Location 4) is near the switch gear, on the opposite side of the acoustic barrier wall from the transformer, and any noise generated here would not be appreciably shielded from the residences. On occasion, the sound levels on this side of the barrier are significantly higher than on the transformer side of the barrier; sound levels of up to 70 dBA were recorded. This is a major anomaly, possibly due to corona noise on the wires or switch gear, but insects or wind in the trees located on the nearby berm are also possible contributors. While HGC Engineering personnel were on site, sound levels at this location were significantly lower, but at those times, noise from the wires and switch gear on the switch side of the barrier was the dominant sound. This phenomenon of higher sound levels at this location will be investigated in greater detail during future work.
Figure 2 also shows the background (L90) sound levels recorded at the residences at times corresponding with the time of day noted in the residents’ observation logs. The L90 sound level is cited in this case as it is a better indicator of the steady sound at the measurement location, rather than the aggregate sound of all sound sources. The logs are summarized in Appendix C. The comments in the logs, together with the corresponding times and measured sound levels, indicate
Canadian Hydro Developers, Inc. Page 10 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
that the residents typically notice the TS noise when the background sound levels are low, not when the overall sound levels, including all sounds at the receptor, is high.
For example, the resident at R02 in particular observed notable audibility (6 out of 10) when the L90 sound level was in the range from 20 to 28 dBA, well below MOE guidelines. Also, a resident at R01 reported the noise to the MOE when the L90 was 22 dBA. While this indicates that the impact of the TS is most objectionable when background sound is low, and audibility of the TS is therefore relatively high, it also tends to suggest that the impact of the TS was in compliance with the MOE guideline limits during the measurement period.
Figure 3a is a spectrogram of the unattended spectral measurements conducted at the southeast unattended measurement location. The figure confirms that the sound levels vary with time, but that the dominant A-weighted frequency bands (i.e., 400 and 500 Hz) do not appreciably vary with time. Figure 3b represents the same measurement location, but the instrument was temporarily reconfigured for greater temporal resolution for this time period (14:15 to 18:30 on October 4). The influence of the small air conditioning unit on the on-site control building can be seen as regular fluctuations in the magnitude of the sound levels.
Figure 4 adds a record of the electrical power monitored at the wind farm to the TS sound level data shown in Figure 2. The figure shows that there is no meaningful correlation between the wind plant power output and the sound levels at the transformer.
Figure 5 overlays the weather data on the sound levels near the transformer. No obvious correlations with wind speed, temperature or humidity exist with the sound levels monitored on the transformer side of the acoustic barrier wall. However, there appears to be a correlation between the sound levels monitored on the switch side of the barrier wall with both higher wind speeds and temperature. This correlation suggests that wind-induced noise such as the wind in the trees may be causing the elevated noise in this area, or that corona noise, if such is the case, is high when the temperature and/or the wind are high.
Unattended Acoustic Measurements – Residences
Figure 6 illustrates overall unattended sound levels measured at the residences. The levels are obviously influenced by wind and local activities, and include the sound of aircraft, distant and local vehicles, animals and voices as well as any sound from the TS. In particular, the heavily treed nature of R04 results in significant wind-induced noise even in relatively light wind conditions. This, combined with the animal activities at R04, likely explained the many spikes in the measured sound level data at this location.
The data summarized in Figure 6 show that the nighttime sound levels (when local activity is relatively low) at the residences are below 30 dBA on several occasions when the TS is producing noise. This fact indicates compliance with the 32 dBA target sound level, during those times.
Canadian Hydro Developers, Inc. Page 11 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Figure 7 adds unattended measurement data from the TS to the unattended data at the residences. As shown, there is little correlation between the sound on the transformer side of the acoustic barrier wall and the sound levels at the residences, although there may be some correlation with the sound on the switch side of the barrier wall. This tends to suggest that while the sound levels at the residence are varying, the contribution of the transformer by itself was not a dominant contributor sound levels measured at the residences.
Figure 8 illustrates the sound levels at the residences against the weather data. The local wind seems to correlate closely with the measured sound levels, rather than with the TS sound levels, demonstrating that the wind causes noise at the residences.
The fact that the sound levels at the residences was not correlated with the sound levels at the TS, the fact that the sound levels at the residences were at times less than 30 dBA when the TS was operating and producing noise, and the fact that the sound levels at the residences seems to correlate closely with the wind speed, indicates that the impact of the transformer was in compliance with the MOE guidelines during the measurement period.
Attended Acoustic Measurements – Transformer Station
Figure 9 illustrates minute measurements conducted simultaneously over a 5 minute period at three locations (Locations 8 through 10) around the TS, 30 to 40 metres from the centre of the transformer. Location 9 is not shielded from the transformer by the acoustic barrier wall, but is partially screened by fixed site equipment, whereas Locations 8 and 10 locations are shielded by the barrier wall, as are the residences. The distances were somewhat forced by the site geometry; any closer and Location 9 would have been affected by an acoustic reflection off of a large retaining wall, and any further and Location 8 would have been behind an earthen berm. The latter half of the 5 minute measurement was significantly affected by aircraft, and is not considered here. Thus, Figure 9 represents the LEQ spectra of the first 2.5 minutes of the measurement. The figure indicates tonal noise, with principal frequencies in the 50, 125 and 400 Hz 1/3 octave bands, and with the tone in the 400 Hz band as the dominant audible frequency.
During these measurements, the microphone was continuously swept over as wide an area as practical while standing still, with several cycles of microphone location occurring during each measurement.
Figure 10 illustrates how the noise of the transformer, represented by the 400 Hz octave band, varied with time and microphone location at the measurement locations. There is variation at all three locations, as a result of variations in location screening, refractions and reflections from moment to moment as the microphones are moved.
The attended measurements at Locations 8 through 10 were repeated with the transformer cooling fans forced on. At none of the three locations were the fans audible at all. The record provided by
Canadian Hydro Developers, Inc. Page 12 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Canadian Hydro of electrical current running to the fan motors indicated that this was the only time during the automated measurement period that the fans operated.
We understand that the transformer must be de-energized for the tap to be changed, and that the tap must be changed manually. Consequently, changes in tap position do not occur regularly, and we understand that the tap was in ‘position 2’ throughout the measurements.
Figures 11 and 12 summarize a similar set of measurements made when all turbines at the wind plant had been shut off. A comparison of these figures with Figures 9 and 10 indicates that the transformer noise at locations most exposed to the transformer, such as Location 9, does not appear to change when the wind plant is not producing power. Subjectively, no audible difference in sound was noted when the wind plant was shutdown.
Figure 13 shows sound level spectra obtained by approximately doubling the distance between the instruments and the transformer. In the east and south directions, the sound levels fell off markedly. The fact that the northwest direction did not fall off significantly is explained by the fact that the location is nearer and more exposed to road traffic on 10th Line.
Several Fast Fourier Transform (FFT) measurements were conducted at Location 9, approximately 40 metres from the transformer. These measurements are summarized on Figure 14, which illustrates the frequency makeup of the sound of the transformer in some detail. As expected, the sound is clearly tonal, and set by peaks at 120, 240 and 360 Hz, with other harmonics present. These three peaks are contained within the 125, 250 and 400 Hz 1/3 octave bands shown in Figure 9.
Attended Acoustic Measurements – Residences
Attended measurements were also conducted at each of the residences a few times, and the results are summarized in Table 3. These are short-duration measurements, generally one minute long, taken at moments when the influence of extraneous noises (e.g., wind noise, dogs, birds, farm animals, speech, cars and aircraft) was low.
Canadian Hydro Developers, Inc. Page 13 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
Table 3: Summary of Attended Measurements at Receptors
Location Date and Time
LEQ [dBA]
L90 [dBA] Comments
34 33 Oct 4, 2007 17:36 38 31
TS inaudible. Dog, insects, distant traffic, distant tractor dominant.
33 31 37 32
R01 Oct 5, 2007
01:15 33 32
Transformer hum faintly audible. Minimal animal activity, fog.
35 30 Oct 4, 2007 18:02 32 30
TS inaudible. Distant traffic dominant.
32 30 Oct 4, 2007 19:20 35 31
TS inaudible. Distant traffic and insects dominant, distant voices, dog present.
35 32 34 32
R02
Oct 5, 2007 02:10
33 33
Transformer hum audible. Resident at R02 indicates a 6/10. Distant dogs audible.
Oct 4, 2007 19:43 35 30 TS inaudible.
Barn animals, aircraft dominant. 33 31
33 31 R04 Oct 5, 2007
01:50 34 31
Transformer hum faintly audible. Animals audible.
As shown in Table 3 indicates, the measured LEQ sound levels were in a fairly tight range: 32 to 38 dBA over all the measurements, with the L90 sound levels ranging from 30 to 33 dBA. While during all measurements, the LEQ sound level at the receptors exceeded the 32 dBA criterion, this does not by itself indicate that the impact of the TS exceeds the criterion. These measured sound levels represent the aggregate sound level due to all sound sources in the area including sound from distant vehicles, farm animals, distant and local dogs, insects, birds, talking and wind-induced noises. As the measurements include the effect of these intermittent and extraneous sound sources, the measured L90 represent a better estimate of the steady sounds, including the noise from the TS.
As Table 3 indicates, the TS noise was audible at some times, and inaudible at others. It can safely be stated that when the TS was not audible, it is not contributing to any meaningful degree to the measured sound levels, and the impact of the TS by itself was thus well below the measured 30 to 33 dBA L90 sound levels. The fact that the sound levels do not appear to have increased
Canadian Hydro Developers, Inc. Page 14 Fall 2007 Acoustic Audit, Amaranth Transformer Station November 22, 2007
when the TS became audible tends to suggest that the contribution of the TS to the measured sound levels was also lower than the measured L90 sound levels when the TS was audible.
In fact, because the TS was not audible at all during some of these times, the actual impact of the TS by itself may be less than the measured L90 sound levels.
In an attempt to further quantify the impact of the TS at the residences, a series of FFT measurements were made at each location during the nighttime, when the transformer hum was audible. These are summarized in Figure 15. As the figure indicates, the tones from the transformer could not be measured by the instrument at that time, implying that they were below the noise floor of the equipment, less than the 10 to 20 dB shown in the data.
Summary and Conclusions
1) The measurements show no particular correlation between the sound levels at the residences and the sound levels near the transformer. The sound at the residences is at times less than 30 dBA during periods when the TS is operating and producing noise. The sound at the residences correlated more closely with wind speed. These facts suggest that the impact of the TS was in compliance with the target 32 dBA sound level during the measurement period.
2) The logs of the residents’ observations, together with the sound levels measured during the times of the observations indicate that the impact of the TS was often considered objectionable when background sound was low, indicating that the concerns may be more related to audibility in a very quiet environment rather than to the numerical sound level impact.
3) While no evidence of unusual acoustic phenomena was found on the transformer side of the barrier, and the transformer fans are not an issue, there were periods when the sound levels on the switch side of the acoustic barrier wall were high. This may be due to wind, insects or birds in the nearby trees, which would have been shielded from the other three on-site unattended measurement locations. Alternately, these elevated sound levels may have been due to corona noise from the switch gear. Further investigation of this phenomenon will be made during subsequent studies.
Figu
re 2
: O
vera
ll L E
Q S
ound
Lev
el D
ata
Col
lect
ed A
utom
atic
ally
with
in th
e A
mar
anth
Tr
ansf
orm
er S
tatio
n, O
ctob
er 2
007,
Plo
tted
Aga
inst
the
Bac
kgro
und
(L90
) Sou
nd L
evel
s at
the
Res
iden
tial R
ecep
tors
Cor
resp
ondi
ng to
Com
men
ts fr
om th
e R
esid
ents
.
20304050607080
Mon, Oct 01, 00:00
Tue, Oct 02, 00:00
Wed, Oct 03, 00:00
Thu, Oct 04, 00:00
Fri, Oct 05, 00:00
Sat, Oct 06, 00:00
Sun, Oct 07, 00:00
Mon, Oct 08, 00:00
Tue, Oct 09, 00:00
Wed, Oct 10, 00:00
Overall A-Weighted Sound Pressure Level [dBA]
Loca
tion
3Lo
catio
n 4
Loca
tion
2Lo
catio
n 1
Loca
tion
7 (R
04)
Loca
tion
5 (R
01)
Loca
tion
6 (R
02)
Oct 01, 17:38Oct 02, 0:18Oct 02, 6:58
Oct 02, 13:38Oct 02, 20:18Oct 03, 2:58Oct 03, 9:38
Oct 03, 16:18Oct 03, 22:58Oct 04, 5:38
Oct 04, 12:18Oct 04, 18:58Oct 05, 1:36Oct 05, 8:16
Oct 05, 14:56Oct 05, 21:36Oct 06, 4:16
Oct 06, 10:56Oct 06, 17:36Oct 07, 0:16Oct 07, 6:56
Oct 07, 13:36Oct 07, 20:16Oct 08, 2:56Oct 08, 9:36
Oct 08, 16:16Oct 08, 22:56
204080160
315
630
1250
2500
5000
1000
0
2000
0
1/3 Octave Frequency Band
Figu
re 3
A:
A-W
eigh
ted
Spec
trog
ram
Mea
sure
d at
Loc
atio
n 3.
10-m
inut
e A
vera
ging
Inte
rval
s
50-5
545
-50
40-4
535
-40
30-3
525
-30
20-2
515
-20
10-1
55-
100-
5
Oct 04, 14:14Oct 04, 14:24Oct 04, 14:34Oct 04, 14:44Oct 04, 14:54Oct 04, 15:04Oct 04, 15:14Oct 04, 15:24Oct 04, 15:34Oct 04, 15:44Oct 04, 15:54Oct 04, 16:04Oct 04, 16:14Oct 04, 16:24Oct 04, 16:34Oct 04, 16:44Oct 04, 16:54Oct 04, 17:04Oct 04, 17:14Oct 04, 17:24Oct 04, 17:34Oct 04, 17:44Oct 04, 17:54Oct 04, 18:04Oct 04, 18:14Oct 04, 18:24
204080160
315
630
1250
2500
5000
1000
0
2000
0
1/3 Octave Frequency Band
Figu
re 3
B:
A-W
eigh
ted
Spec
trog
ram
Mea
sure
d at
Loc
atio
n 3.
1-m
inut
e A
vera
ging
Inte
rval
s
50.0
-55.
045
.0-5
0.0
40.0
-45.
035
.0-4
0.0
30.0
-35.
025
.0-3
0.0
20.0
-25.
015
.0-2
0.0
10.0
-15.
05.
0-10
.00.
0-5.
0
Figu
re 4
: O
vera
ll L E
Q S
ound
Lev
el D
ata
Col
lect
ed A
utom
atic
ally
w
ithin
the
Am
aran
th T
rans
form
er S
tatio
n, P
lotte
d A
gain
st E
lect
rical
Pow
er D
ata,
Oct
ober
20
07.
20304050607080
Mon, Oct 01, 00:00
Tue, Oct 02, 00:00
Wed, Oct 03, 00:00
Thu, Oct 04, 00:00
Fri, Oct 05, 00:00
Sat, Oct 06, 00:00
Sun, Oct 07, 00:00
Mon, Oct 08, 00:00
Tue, Oct 09, 00:00
Wed, Oct 10, 00:00
Overall A-Weighted Sound Pressure Level [dBA]
010203040506070
Wind Farm Power Production [MW]
Loca
tion
3Lo
catio
n 4
Loca
tion
2Lo
catio
n 1
Pow
er D
ata
from
IES
OP
ower
Dat
a fro
m C
andi
an H
ydro
Figu
re 5
: Su
mm
ary
of O
vera
ll L E
QSo
und
Leve
l Dat
a C
olle
cted
Aut
omat
ical
ly
With
in th
e A
mar
anth
Tra
nsfo
rmer
Sta
tion,
Plot
ted
Aga
inst
Met
erol
ogic
al D
ata,
Oct
ober
200
7
2030405060708090100
Mon, Oct 01, 00:00
Tue, Oct 02, 00:00
Wed, Oct 03, 00:00
Thu, Oct 04, 00:00
Fri, Oct 05, 00:00
Sat, Oct 06, 00:00
Sun, Oct 07, 00:00
Mon, Oct 08, 00:00
Tue, Oct 09, 00:00
Wed, Oct 10, 00:00
Overall A-Weighted Sound Pressure Level [dBA], Humidity [%]
048121620242832
Temperature [C], Ground Level Wind Speed [m/s]
Loca
tion
3Lo
catio
n 4
Loca
tion
2Lo
catio
n 1
Hum
idity
Rai
nTe
mpe
ratu
reW
ind
Win
d S
peed
Figu
re 6
: Su
mm
ary
of O
vera
ll L E
Q S
ound
Lev
el D
ata
Col
lect
ed A
utom
atic
ally
at t
he
Res
iden
ces,
Oct
ober
200
7O
vera
ll so
und
leve
ls in
clud
es th
e ef
fect
of a
ll so
und
souu
rces
incl
udin
g w
ind,
veh
icle
s, a
nim
als,
etc
.
20304050607080
Mon, Oct 01, 00:00
Tue, Oct 02, 00:00
Wed, Oct 03, 00:00
Thu, Oct 04, 00:00
Fri, Oct 05, 00:00
Sat, Oct 06, 00:00
Sun, Oct 07, 00:00
Mon, Oct 08, 00:00
Tue, Oct 09, 00:00
Wed, Oct 10, 00:00
Overall A-Weighted Sound Pressure Level [dBA]
Loca
tion
7 (R
04)
Loca
tion
5 (R
01)
Loca
tion
6 (R
02)
Figu
re 7
: Su
mm
ary
of O
vera
ll So
und
Leve
l Dat
a C
olle
cted
Aut
omat
ical
ly a
t the
R
esid
ence
s, W
ith O
vera
ll So
und
Leve
l Dat
a at
the
Tran
sfor
mer
Sta
tion,
Oct
ober
200
7O
vera
ll so
und
leve
ls in
clud
e th
e ef
fect
of a
ll so
und
sour
ces
incl
udin
g w
ind,
veh
icle
s, e
tc.
20304050607080
Mon, Oct 01, 00:00
Tue, Oct 02, 00:00
Wed, Oct 03, 00:00
Thu, Oct 04, 00:00
Fri, Oct 05, 00:00
Sat, Oct 06, 00:00
Sun, Oct 07, 00:00
Mon, Oct 08, 00:00
Tue, Oct 09, 00:00
Wed, Oct 10, 00:00
Overall A-Weighted Sound Pressure Level [dBA]
Loca
tion
7 (R
04)
Loca
tion
5 (R
01)
Loca
tion
6 (R
02)
Loca
tion
4Lo
catio
n 1
Figu
re 8
: Su
mm
ary
of O
vera
ll So
und
Leve
l Dat
a C
olle
cted
Aut
omat
ical
ly
at th
e A
mar
anth
Tra
nsfo
rmer
Sta
tion,
With
Met
erol
ogic
al D
ata,
Oct
ober
200
7O
vera
ll so
und
leve
ls in
clud
es th
e ef
fect
of a
ll so
und
souu
rces
incl
udin
g w
ind,
veh
icle
s, a
nim
als,
etc
.
2030405060708090100
Mon, Oct 01, 00:00
Tue, Oct 02, 00:00
Wed, Oct 03, 00:00
Thu, Oct 04, 00:00
Fri, Oct 05, 00:00
Sat, Oct 06, 00:00
Sun, Oct 07, 00:00
Mon, Oct 08, 00:00
Tue, Oct 09, 00:00
Wed, Oct 10, 00:00
Overall A-Weighted Sound Pressure Level [dBA], Humidity [%]
048121620242832
Temperature [C], Ground Level Wind Speed [m/s]
Loca
tion
7 (R
04)
Loca
tion
5 (R
01)
Loca
tion
6 (R
02)
Hum
idity
Rai
nTe
mpe
ratu
reW
ind
Spe
ed
Figu
re 9
. A
ttend
ed A
-Wei
ghte
d L E
QSo
und
Leve
l Spe
ctra
Mea
sure
d 30
to 4
0 m
etre
s fr
om T
rans
form
erM
easu
rem
ents
Con
duct
ed O
ctob
er 4
, 200
7
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
2531.5
40506380
100125160200250315400500630800
1000125016002000250031504000500063008000
10000125001600020000
dBA
1/3
Oct
ave
Ban
d C
entr
e Fr
eque
ncy
[Hz]
Sound Pressure Level [dBA]
Loca
tion
9Lo
catio
n 8
Loca
tion
10
Figu
re 1
0: A
-Wei
ghte
d Ti
me
Sign
als
- 400
Hz
1/3
Oct
ave
Ban
d,M
easu
rem
ents
Con
duct
ed 3
0 to
40
met
res
from
Tra
nsfo
rmer
, Oct
ober
4, 2
007
Fluc
tuat
ions
in S
ound
Lev
el d
ue to
Mic
roph
one
Mov
emen
t
1020304050607080
17
1319
2531
3743
4955
6167
7379
8591
9710
310
911
512
112
713
313
914
5
Tim
e [s
]
Sound Pressure Level [dB]
Loca
tion
9Lo
caito
n 8
Loca
tion
10
Figu
re 1
1. A
ttend
ed A
-Wei
ghte
d LE
Q S
ound
Lev
el S
pect
ra M
easu
red
30 to
40
met
res
from
Tra
nsfo
rmer
Mea
sure
men
ts C
ondu
cted
Oct
ober
4, 2
007
Fluc
tuat
ions
in S
ound
Lev
el d
ue to
Mic
roph
one
Mov
emen
t
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
2531.5
40506380
100125160200250315400500630800
1000125016002000250031504000500063008000
10000125001600020000
dBA
1/3
Oct
ave
Ban
d C
entr
e Fr
eque
ncy
[Hz]
Sound Pressure Level [dBA]
Loca
tion
9Lo
catio
n 8
Loca
tion
10
Figu
re 1
2: A
-Wei
ghte
d Ti
me
Sign
als
- 400
Hz
1/3
Oct
ave
Ban
d,M
easu
rem
ents
Con
duct
ed 3
0 to
40
met
res
from
Tra
nsfo
rmer
, Oct
ober
4, 2
007
Win
d Fa
rm N
ot P
rodu
cing
Ele
ctric
ityFl
uctu
atio
ns in
Sou
nd L
evel
due
to M
icro
phon
e M
ovem
ent
1020304050607080
17
1319
2531
3743
4955
6167
7379
8591
9710
310
911
512
112
713
313
914
5
Tim
e [s
]
Sound Pressure Level [dB]
Loca
tion
9Lo
catio
n 8
Loca
tion
10
Figu
re 1
3. A
ttend
ed A
-Wei
ghte
d LE
Q S
ound
Lev
el S
pect
ra M
easu
red
70 to
80
met
res
from
Tra
nsfo
rmer
Mea
sure
men
ts C
ondu
cted
Oct
ober
4, 2
007
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
2531.5
40506380
100125160200250315400500630800
1000125016002000250031504000500063008000
10000125001600020000
dBA
1/3
Oct
ave
Ban
d C
entr
e Fr
eque
ncy
[Hz]
Sound Pressure Level [dBA]
80 m
etre
s ea
st o
f tra
nsfo
rmer
70 m
etre
s S
outh
of t
rans
form
er70
met
res
Nor
thea
st o
f tra
nsfo
rmer
Figu
re 1
4: D
iscr
ete
Freq
uenc
y (F
FT) S
ound
Spe
ctra
Mea
sure
d at
Loc
atio
n 9,
Mea
sure
men
ts C
ondu
ted
Oct
ober
4, 2
007
55 d
B, 3
60 H
z
102030405060708090100
050
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
Freq
uenc
y [H
z]
Sound Pressure Level [dB]
Figu
re 1
5: D
iscr
ete
Freq
uenc
y (F
FT) S
ound
Spe
ctra
M
easu
red
at L
ocat
ion
9 an
d A
t Res
iden
ces
Mea
sure
men
ts C
ondu
ted
Oct
ober
4, 2
007
-1001020304050607080
050
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
1000
Freq
uenc
y [H
z]
Sound Pressure Level [dB]
Loca
tion
9 (T
S)
Loca
tion
5 (R
01)
Loca
tion
7 (R
04)
Loca
tion
6 (R
02)
Photo Plate 1: Part of the TS, Looking East
Photo Plate 2: Sound Level Meter Installed at Receptor R01, Looking Southwest
Photo Plate 3: Sound Level Meter Installed at Receptor R02, Looking South
Photo Plate 4: Sound Level Meter Installed at Receptor R04, Looking South. This monitor was later moved to a location near the front door.