MEDIUM VOLTAGE CE-B METAL CLAD

SWITCHBOARDS

CE - B - C - en - REV.02 2011.8 32

MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS

AP

PLI

CAT

ION

STA

ND

AR

D

CE-B Metal Clad switchboards

are designed for use in public

and industrial distribution system

up to 24kV for the operation and

protection of lines, generators,

transformers, motors, capacitor

banks. The switchboards are

composed combining the various

typical standard cubicles.

CEI 17-6 Italian standard

IEC 62271-200 International standard

IEC 60-298 (replaced by IEC 62271-200)

DPR 547 Italian accident prevention Standard

IEC 60129 Earthing switches

IEC 60694 High voltage switchgear

IEC 62271 Circuit breakers

These switchboards have performed all relevant

tests carried out by qualifi ed laboratories.

Utilities and Power Plants• Power Stations

• Generator switchgear

• Transformer stations

• Main and auxiliary switchboards

Industry• Metallurgy

• Pulp and Paper

• Cement

• Chemical

• Rolling mills

• Automotive

• Petrochemical

• Oil and gas

Marine applications• Drilling platforms

• Off-shore oil rigs

• Ferries and ships

Services• Hospitals

• Infrastructures

• Data center

Transports• Airports

• Ports

• Railways

TY

PIC

AL

US

ES

The company is qualifi ed to supply standard ENEL type units.

MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS

CE - B - C - en - REV.02 2011.8

General CharacteristicsAccording to the international standard IEC 62271-200

the CE-B switchboards are classifi ed for “loss of service

continuity category” as LSC2B with partition class PM

(Metallic Partitions).

The optional version CE-BA is also foreseen fully withstanding

to internal arc fault:

• Internal arc classifi cation (IAC)

• Accessibility type:

A (restricted to authorized personnel only)

F (Front)

L (Lateral)

R ( Rear)

Mechanical characteristicsEnclosure: Under normal operation the degree of protection

is of IP 31 for metal enclosure and IP2X in the LV instrument

compartment.

The individual structures are made of die-bended galvanized

sheet steel elements of no less than 2 mm thickness.

The external coloured panels are realized with carbon steel

painted with electrostatic epoxy powder, the standard

colour is light grey RAL 7035 smooth (all RAL scale colours

or specifi c colours can be realized on request). Standard

painting minimum thickness of 60 +/- 10 microns is

guaranteed.

Structure: all structural parts are solidly fastened together by

special screws ensuring a good electrical contact between

the connected parts.

Nuts and bolts used to assemble structure and enclosure

are galvanized and passivated with minimum thickness of

12 microns.

Earthing Circuit-breaker: earthing of circuit-breaker is ensured on

the whole isolating stroke by means of a sliding jaw type

contact on the copper conductor which is directly connected

with the earthing bus-bar.

Components: all main components such as CTs, VTs, etc.,

are positively earthed.

Doors: are connected to the frame by a 25 mmq. cross

section fl exible braids.

Earthing bus-bar: the earthing bus-bar in copper with a

normal 350 mmq. cross section runs along the length of the

switchboard, thus ensuring maximum safety for personnel

and equipment.

Access and limited overall dimensions: the overall dimensions are particularly restricted if compared

with the high performances achieved for the insulation level,

rated busbars current and short-circuit current.

Optionally only front access could be required for installation

and maintenance.

Versatility and fl exibility: any single line

diagram can be realized to meet the most varied technical

requirements. Special and customized adaptation units allow

easy extension of existing switchboards even from supplied

by other suppliers or not jet in production.

Maximum service reliability: reinforced

insulation of all live parts minimizes the occurrence of faults

between phases or to earth. The various compartments of

each cubicle are fully segregated and can, besides, be simply

and rapidly inspected. As a matter of fact, equipment such as

circuit-breakers, instrument transformers and terminals are

readily accessible for inspection and maintenance purposes.

Easy inspection and maintenance: through easy access to the equipment in the various

compartments by hinged doors or removable bolted panels

and through the isolation and withdrawal on truck of circuit-

breakers, VT, fuses.

Easy installation and connection: the

cubicles are factory assembled and tested before being

shipped to site, therefore they only need to be secured to

the fl oor, coupled together and connected to the external

circuits.

Personnel safety ensured by:

• positive earthing on the entire switchboard structure

• earthing of circuit-breaker frame throughout racking-in or

withdrawing operations;

• metal shutters automatically operated during circuit

breaker truck movement;

• metal shutters automatically operated during VTs truck

movement;

• insulating protections and coatings are available for live

parts;

• easy access to low voltage apparatus and control wirings

without any risk of accidental contact with medium voltage

parts;

• set of mechanical and electromechanical interlocks;

• various signalling and control devices.

No fi re risk: metal partitions of compartments and use

of self-estinguishing insulating material prevent fi res from

spreading.

Standard routine factory tests:• Visual inspection and check.

• Mechanical sequence operations.

• Cabling check.

• Electrical sequence operations.

• Insulation test.

FEATURES

54

MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS

CE - B - C - en - REV.02 2011.8

Rated voltage kV 12 17,5 24

Rated power frequency withstand voltage (1min) kV 28 38 50

Rated lightning impulse withstand voltage kV 75 95 125

Rated frequency Hz 50/60 50/60 50/60

Rated short-time withstand current (3 sec) kA 50 50 40

Peak current kA 125 125 100

Internal arc withstand current IAC-FLR (1sec)* kA 50 50 40

Rated current max. A 3150 3150 2500

Rated current with forced ventilation ** max. A 4000 4000 4000

Rated current with two breakers in parallel ** max. A 5000 5000 4000

Rated voltage 12KV 17,5KV 24KV

Depth (mm) 1625 1860 2060

Height (mm) 2325 2325 2325

Height (mm) - IAC 2780 2780 2780

Width (mm) 600 800 1000 800 1000 800 1000

Rated current up to (A) 630 1600 4000 1600 4000 1600 2500

DIMENSIONS

Note * Internal arc withstanding in option ** Type tested

TECHNICAL DATA

Electrical Data

Maximum ambient temperature C° +40

Minimum ambient temperature C° -5

Height m a.s.l. ≤ 1000

Maximum relative humidity % 95

For different conditions contact our offi ces. Dimensions could be affected by specifi c equipment and confi guration.

Normal Service Conditions

76

MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS

CE - B - C - en - REV.02 2011.8

Typical composition:

A Instrument compartmentAll the low voltage equipment can be housed in the instrument

compartment, which is usually placed above the circuit-

breaker compartment

B Circuit-breaker compartmentThis compartment is designed to accommodate the circuit-

breaker, contactor or link complete of its withdrawable truck

and all mechanical parts required for the extraction.

The device is provided with auxiliary switches for signalling

the “connected position” and “disconnected/test position”.

C Feeder compartmentThe feeder compartment, accessible from the rear of the

cubicle by removing the panel or by opening the eventual

door.

CONSTRUCTION SAFETY INTERLOCKS

Earthing switch• Mechanical lock to prevent the earthing switch closing if the

circuit-breaker is in connected position

On the circuit-breaker• Mechanical lock to prevent the connection or disconnection

of the circuit breaker when closed

• Mechanical lock to prevent the circuit breaker connection

when the earthing switch is in closed position

• Mechanical lock to prevent the disconnection of auxiliary

connector with circuit breaker in connected position

• Mechanical lock to prevent the manual opening of the

shutters when the circuit breaker is removed from the

compartment. The shutters can only be operated by the

circuit breaker truck.

• Mechanical protection (IP20) form live parts even with door

open is always maintained with circuit breaker in connected

and disconnected position.

On the VT’s compartment (if present)• Mechanical lock to prevent opening of the door when VTs

are in connected position.

• Mechanical lock to prevent the manual opening of the

shutters when the VTs are removed from the compartment.

The shutters can only be operated by the VTs truck.

D Busbar compartmentThis compartment contains the main bus-bars which are

directly supported by the lower fi xed isolating contacts of the

circuit-breakers and isolator supports fi xed on the structure.

E Wiring duct for interconnectionsOn the cubicle roof front side, a wiring duct is provided to hold the

auxiliary connections between the various cubicles and towards

the external installation.

F Voltage transformer compartment (VT compartment)This compartment can contains the fi xed or draw-out version

voltage transformers and the related fuses

The draw-out version allows VTs and fuses replacement in

safe conditions even with switchbord on voltage.

This compartment can be located in incoming or outgoing

feeder cubicles as well as in bus tie cubicles.

The device could be provided with auxiliary switches for

signalling the “racking-in” and “racked-out position.

G Earthing switchThe unit can be equipped with Casagrande Elettrocostruzioni

“CE-SEZ” earthing switch. The switch is activated with an high

speed rotating snap, sized to conduct the rated short circuit

making current when close to under load. The speed of the

snap action closing operation is independent of controls.

A manual switch operating lever is provided on the front of the

switchbord.

The device is provided with auxiliary switches for signalling the

open and closed positions.

H Gas exhaust duct (Optional)The gas exhaust duct, positioned on the top of the cubicles,

collects and ejects outside the safety area the gas resulting by

the eventual internal arc fault.

98

MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS

CE - B - C - en - REV.02 2011.8

VERSIONS AND CONFIGURATIONS

TYPICAL UNITS

Special VersionsEnvironment

• For special environments and temperature

• For indoor use with protection degree up to IP54

• For outdoor use in metal box up to IP56 or NEMA 4X

Connection

• Incoming/outgoing by cables form the TOP

• Incoming/outgoing by bus duct form the TOP

Options and accessoriesAvailable Locks

• Key locks permitting the key to be released with Circuit

Breaker locked in open positions

• Key locks permitting the key to be released with Circuit

Breaker locked in disconnected position

• Key locks permitting the key to be released with circuit

breaker door closed

• Key lock permitting the key to be released with earthing

switch closed and locked in closed position

• Key lock permitting the key to be released with earthing

switch open and locked in open position

• Electromechanical lock to prevent closing of earthing switch

• Mechanical lock to allow door opening only if circuit breaker

is in disconnected position

• Padlock facility on circuit breaker shutters in closed position

• Padlock facility to prevent circuit breaker connecting or

disconnecting movement

• Padlock facility to prevent opening or closing of earthing

switch

• Padlock facility on circuit breaker door

Command

• Motorized command for draw-out / draw-in circuit breaker

trolley

• Motorized command for earthing switch

Accessories

• Light or pressure device to limit internal arc fault duration

• Circuit breaker trolley for handling when removed from the

compartment

• Contactor trolley for handling when removed from the

compartment

• Handle for circuit breaker / contactor connecting or

disconnecting movement

• Handle for earthng switch command

Eart

hing

Eart

hing

Eart

hing

Optional

Example of confi guration

1110

MEDIUM VOLTAGE CE-B METAL CLADSWITCHBOARDS

Headquarters and Factory:

via G. Rossini, 24

37060 Castel d’Azzano

(Verona) Italy

Tel. +39 045 8546511

Fax +39 045 8520214

E-mail: [email protected]

Production Branch:

Contrada Piana Z.I.

86019 Vinchiaturo

(Campobasso) Italy

Tel. +39 0874 340225

Faz +39 0874 340227

www.casagrande.vr.it