Spray in Place Pipe (SIPP): Materials Composite and Implementation Methodology for Surviving Pressure Pipe Failure Kent Weisenberg 1 , Tom Iseley, Ph.D., P.E. 2 , and Lin Li, Ph.D. 3 1 Sipp Technologies, LLC, 5245 Old Kings Rd, Jacksonville, FL, 32254; e-mail: [email protected] 2 Trenchless Technology Center (TTC), Louisiana Tech University, P.O. Box 10348, Ruston, LA 71272; e-mail: [email protected] 3 Sipp Technologies, LLC, 5245 Old Kings Rd, Jacksonville, FL, 32254; e-mail: [email protected] ABSTRACT Major advancements have been made utilizing Spray in Place Pipe (SIPP) renewal technologies for both pressure and non-pressure pipe applications. For pressure pipe, current systems have been developed for non-structural and semi-structural applications. This paper will describe the development of a fully structural SIPP technology for pressure pipe applications including but not limited to potable water systems capable of meeting NSF 61 requirements. SIPP technology has several advantages, such as same-day return to service, effortless service reinstatement, reduced environmental footprint, economy, market versatility and minimized community impact. Conversely, ancestral SIPP lining technologies preclude current processes from yielding structurally independent linings in pressure pipe systems: Traditional SIPP lining materials have low creep resistance; Adhesion between host pipe and lining can cause fracture of the lining during pipe failure events; Both radial and longitudinal shrinkage of thermosetting materials will create an annular space between the lining and pipe. This annulus will result in hydraulic failures when fluid infiltrates behind the liner system at discontinuities. This study will explain in detail how the robotic and concurrent application of a closed cell porous elastomer, helically wound carbon fiber filament and high-tensile strength rigid polymer will result in a composite system to create structurally independent linings. This paper will explain how this lining system can meet the requirements to be able to 1

Upload: others

Post on 16-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

Spray in Place Pipe (SIPP): Materials Composite and Implementation Methodology for Surviving Pressure Pipe Failure

Kent Weisenberg1, Tom Iseley, Ph.D., P.E.2, and Lin Li, Ph.D.3

1Sipp Technologies, LLC, 5245 Old Kings Rd, Jacksonville, FL, 32254; e-mail: [email protected] Technology Center (TTC), Louisiana Tech University, P.O. Box 10348, Ruston, LA 71272; e-mail: [email protected] Technologies, LLC, 5245 Old Kings Rd, Jacksonville, FL, 32254; e-mail: [email protected]

ABSTRACT

Major advancements have been made utilizing Spray in Place Pipe (SIPP) renewal technologies for both pressure and non-pressure pipe applications. For pressure pipe, current systems have been developed for non-structural and semi-structural applications. This paper will describe the development of a fully structural SIPP technology for pressure pipe applications including but not limited to potable water systems capable of meeting NSF 61 requirements. SIPP technology has several advantages, such as same-day return to service, effortless service reinstatement, reduced environmental footprint, economy, market versatility and minimized community impact. Conversely, ancestral SIPP lining technologies preclude current processes from yielding structurally independent linings in pressure pipe systems: Traditional SIPP lining materials have low creep resistance; Adhesion between host pipe and lining can cause fracture of the lining during pipe failure events; Both radial and longitudinal shrinkage of thermosetting materials will create an annular space between the lining and pipe. This annulus will result in hydraulic failures when fluid infiltrates behind the liner system at discontinuities. This study will explain in detail how the robotic and concurrent application of a closed cell porous elastomer, helically wound carbon fiber filament and high-tensile strength rigid polymer will result in a composite system to create structurally independent linings. This paper will explain how this lining system can meet the requirements to be able to span perforations, cracks and other discontinuities in host pipe to provide hoop strength and resistance to buckling forces.

INTRODUCTION

As the water system infrastructure in the United States (Ellison, et. al. 2010) and other countries (Ma et al. 2008, Kuliczkowski, et al. 2010, Tregoing 1996 and Zaneldin 2007) grows older, many authorities are particularly concerned about a growing investment deficit in the renewal of defective water mains. Nowadays, when municipal engineers, reliability engineers, and other end users search for rehabilitation or preventative maintenance solutions for water or industrial pipes, they highly prefer a “no dig”/trenchless solution (Vldeanu 2018). The broad impacts of using trenchless technologies for pipe rehabilitation include reduced environmental and carbon impacts during construction and fewer social disruptions, primarily due to vehicle traffic, as compared to traditional dig and replace methods (Gerasimova 2016). Trenchless repairs greatly reduce excavations and road restorations, which are the leading social costs and environmental; impacts related to pipeline projects.

1

Page 2: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

Since structurally independent linings can be used replacements for the host pipes, and the costs are much lower than dig and replace, the need for structurally independent lining becomes unprecedented prevalent. In most cases if the end user is going to expend the fiscal resources to rehabilitate a pipeline he or she will choose a structurally independent product for cheaper cost in a long-term application purpose. Spray in Place Pipe (SIPP) is a trenchless rehabilitation method (Najafi 2005) that utilizes both remote and robotic devices to apply thermosetting polymeric linings inside of pipe systems. The application of this method typically involves a single pass or multiple passes of equipment applying one or more polymeric material layers to form a structurally interactive lining. Spray-on linings have been applied to stop and prevent internal corrosion, restore hydraulic capacity, and eliminate water quality deterioration arising from iron or steel corrosion and associated scaling (Ellison, et. al. 2010). SIPP technology has several advantages compared to the other trenchless methods, such as same-day return to service, effortless service reinstatement, reduced environmental footprint, economy, market versatility and minimized community impact (Folgherait 2013 and Ellison, et. al. 2010). However, ancestral SIPP lining materials and methods have precluded these current processes from yielding structurally independent linings in pipe systems for several reasons:

1. Current SIPP technologies utilize polymeric or more specifically thermosetting plastics as the structural materials, such materials yield to radial and longitudinal shrinkage during the curing process which will create an annular space/annulus between the liner and pipe. This annulus will result in hydraulic failures when pressurized fluid infiltrates behind the liner system at discontinuities.

2. Typical SIPP lining materials, such as polyurea/polyurethane hybrids, polyurethanes, and epoxy systems, all possess high modulus and strength, as well as, the required rigidity. However, these materials are relatively brittle and unless applied at considerable thickness they cannot survive internal working fluid pressure, transverse shear and overburden. The resulting requirement is then for significantly increased lining thickness which leads to a considerable increase of both labor and material costs, as well as, reducing hydraulic capacities of the pipe systems.

3. When thermosetting materials are applied too thick in one pass they often have a tendency to crack, as the increased heat from the exotherm can result in embrittlement of the lining material, increased localized stress at the lining profiles and discontinuities as well as a significant reduction in the mechanical properties of the polymer as it gets close to its glass transition temperature.

4. If the rigid polymeric material is adhered directly to the pipe substrate the material shrinkage during curing can cause cracking or delamination of the lining material, especially in situations of high exotherm or mismatch in the coefficient of thermal expansions of different interfacing materials.

5. If the rigid lining material is adhered to the host pipe per ASTM F3182-16 standard, the liner will not survive pipe failure events. Once fractures or remarkable deformations happen in the host pipe where the liner is adhered, the displacements on the pipe will be transferred onto the liner, causing the lining material to crack, fracture or tear due to transferred strains as shown in Figure 1.

2

Page 3: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

Figure 1. Liner cracking caused by host pipe failure

6. Current SIPP technologies are constrained to the creep failure behavior of polymeric materials under long-term continuous stress as is present in pressure pipe systems. The strength and rigidity of thermoplastic materials will initially decrease rapidly and then gradually further decrease with the time during service life which is a part of the materials nature. This defect significantly affects the application of SIPP as a structurally independent lining.

7. It should also be noted that the management of lining thickness alone cannot effectively improve the lining creep resistance because of the nature of thermoplastic materials.

SOLUTIONS FOR STRUCTURALLY INDEPENDENT SIPP LINING

To make SIPP lining certifiable as a structurally independent lining, the liner shall closely fit the host pipe and no annulus shall be present between the lining and host pipe. Also, the liner shall possess the hoop and longitudinal strengths to resist all internal and external loading for both short-term and long-term durations. Furthermore, the lining shall not reduce the hydraulic capacity of pipe systems. This paper presents a filament reinforced composite lining solution to seamlessly addresses all the issues of current SIPP technologies and provides an approach to generate structurally independent linings for a wide range of pipe systems. The composite lining is composed of two dissimilar lining material layers and a filament reinforcement all applied robotically in a single pass through the pipe system: 1) a closed cell internally porous flexible layer is applied and bonded directly to the inside of a cleaned host pipe, 2) a high tensile filament is helically wound and fused to the flexible layer and, 3) a rigid layer is applied bonding to the flexible layer and encapsulating the fiber filament to form a composite lining structure.

3

Page 4: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

The elastomeric layer of the composite lining is made of a low modulus, low Poisson’s ratio high elongation material, with very low permeability. It is applied and bonded between the host pipe and rigid lining layer. Thus, the rigid polymeric layer is not adhered directly to the pipe substrate as with current SIPP technologies, but rather is adhered directly to the elastomeric or ‘flexible’ layer. This described elastomeric has the capability to stretch and yield to absorb strains and reduce the reaction forces between the rigid liner and host pipe when pipe movement or failure events occur as shown in Figure 2. In other words, the elastomeric lining in this laminate structure allows the rigid liner to be ‘suspended’ in the host pipe so that external forces or strains are not fully transferred onto the rigid liner but are instead dissipated throughout the elastomeric layer.

Figure 2: Elastomeric liner protect rigid liner through host pipe failure

Fluid infiltration in any annulus remaining between the liner and host pipe is an often misunderstood and sometimes trivialized as a problem in today’s pipeline rehabilitation industry however can be a common liner failure causation. To solve the problem, the flexible layer bonded to both the host pipe and the rigid lining layer expands due to its low Poisson’s ratio to fill and seal the annulus caused by rigid material shrinkage during the curing process. Since the elastomeric material is impermeable to pressurized liquids it can prevent the fluid/gas infiltration into an annulus and avoid the potential of hydraulic failures that often occur with other trenchless technologies.

4

Page 5: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

High strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and creep resistance as compared to today’s unreinforced rigid SIPP lining materials. Thus, the application of these filaments in a precise helix as part of a composite lining considerably increases the lining strength and stiffness. Additionally, the described filaments share and reduce the stress on the rigid liner material caused by internal pressure or exterior buckling forces. Lower stress on the lining material significantly extends the working life of the liner against fatigue and creep failure.

5

(a)

Page 6: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

Figure 3: Stress analysis on the liners under the same 150 psi internal pressure, (a) the hoop stress on the unreinforced rigid liner with 0.56” lining thickness, (b) the hoop stress on the reinforced rigid liner with 0.28” lining

thickness and 0.5” filament pitch.

Due to the extreme reinforcement effect of using filament in the composite lining, the requirement for the rigid lining thickness will be approximately 40~50% lower compared to thermosetting linings without filament as shown in Figure 3. One result of this innovation is that contractors can use less materials and spend shorter application time to install a new lining of greater strength. This method greatly reduces the total cost of the lining, and at the same time, does not increase the reduction of hydraulic capacity caused by applying thicker linings to reach the same goal.

This filament reinforced composite lining can be used in wide range of applications, such as pressure pipes, gravity pipes, pipes working under elevated temperatures and/or fluctuating loads. The composite lining structure design is based on the pipe diameter, working condition, and optimal combination of lining thickness and dimensional filament pitch applied inside the lining. The filament pitch (distance between filament helix loops) can be adjusted based on the load. Typically, the filament pitch will be reduced to apply more filament and increase the hoop strength for the lining. In applications for exceedingly high internal pressure and/or overburden the rigid lining material can be robotically applied in multiple passes. Furthermore, in applications where the pipe will be subjected to high potential of bending and or shear forces axial fiber reinforcement is also incorporated during the robotic process. This novel method allows the filament to be repetitively applied within the rigid material matrix to create multiple reinforcement layers. This novel approach to utilizing filament reinforcement in SIPP linings tremendously increases the strength, rigidity, and buckling resistance of the lining composite.

6

(b)

Page 7: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

The composite lining is applied via a specifically designed robotic lining system. The robotic apparatus has three interactive major segments. The back segment applies the closed cell flexible material. This material is typically applied at a thickness of 20% of the total composite cross section. The second or middle segment stores a UV resin impregnated filament which is then helically extruded on and instantaneously fused to, the flexible layer via specific wavelength UV light. The front or third major segment then applies the rigid lining material, both encapsulating the filament and bonding to the flexible layer to finalize the composition. These functionalities work together efficiently in a specific sequence to apply the composite lining in one pass through the host pipe resulting in intermolecular adhesion of the layers therein creating the highest quality composite lining.

CONCLUSION

A filament reinforced composite lining was introduced and highlighted by demonstrating the materials, mechanics and methods for the installation of structurally independent linings via SIPP technology. This underlined technology elevates SIPP practices to a new level of pipe rehabilitation with a smarter, stronger, thinner, lower-cost and safer lining product. The composite lining structure absolutely solves the inherent problems of annulus, creep failure, as well as lining failures caused by adhesion. The revolutionary idea of integrating a reinforcing filament helix significantly increases the lining strength and resistance against creep failure while reducing the required lining thickness thus significantly lessening the costs of materials, labor and time while increasing flow capacity. Finally, the composite lining is robotically applied additionally reducing costs, application times, as well as appreciably more safe and precise applications.

7

Page 8: sipptech.comsipptech.com/Structural Linings SIPP White Paper Final.docx · Web viewHigh strength filaments such as carbon fiber, have extremely high modulus, tensile strength, and

REFERENCES

Ellison, D., Sever, F., Oram, P., Lovins, W., and Romer, A., Global Review of Spray-On Structural Lining Technologies, Subject Area: Infrastructure, Water Research Foundation, 2010.

Folgherait, B., Kirsch, S., Rogers, R., “Water Main Rehabilitation Using Polyurea Linings – Same Day Return to Service”, North American Society for Trenchless Technology (NASTT) NASTT’s 2013 No-Dig Show, Sacramento, California, March 3-7, 2013

Gerasimova, V., “Underground Engineering and Trenchless Technologies at the Defense of Environment”, Procedia Engineering, 165 (2016), 1395-1401

Kuliczkowski, A., Kubicka, U., Parka, A., “The comparative analysis of standards used in Poland for trenchless rehabilitation of sewage pipes and the problems in design of resin liners”, Tunnelling and Underground Space Technology, Vol. 25, Dec. 2010, 795-801

Ma, B., Najafi, M., “Development and applications of trenchless technology in China”, Tunnelling and Underground Space Technology, Vol. 23, Issue 4, July 2008, 476-480

Najafi, M., Trenchless Technology: Pipeline and Utility Design, Construction, and Renewal, McGraw-Hill Education 2005

Tregoing, C., “Trenchless technology research in the UK water industry”, Tunnelling and Underground Space Technology, Vol. 11, 1996, 61-66

Vladeanu, G., Matthews, J.C., “Analysis of risk management methods used in trenchless renewal decision making”, Tunnelling and Underground Space Technology, Vol. 72, Feb. 2018, 272-280

Zaneldin, E.K., “Trenchless construction: An emerging technology in United Arab Emirates”, Tunnelling and Underground Space Technology, Vol. 22, Issue 1, Jan. 2007, 96-105

8