lessons learned from the texas synchrophasor … learned from the texas synchrophasor network by...

44
Lessons Learned from the Texas Synchrophasor Network by Presented at the SWEDE 2011 Annual Conference Bastrop, TX Wednesday, April 27, 2011 Prof. W. Mack Grady Dept. of Electrical & Computer Engineering U.T. Austin Page 1 of 44

Upload: ngocong

Post on 24-May-2018

219 views

Category:

Documents


2 download

TRANSCRIPT

Lessons Learned from the Texas Synchrophasor Network

by

Presented at the

SWEDE 2011 Annual Conference

Bastrop, TX

Wednesday, April 27, 2011

Prof. W. Mack GradyDept. of Electrical & Computer Engineering

U.T. Austin

Page 1 of 44

Why are SynchrophasorsImportant?

Here’s All You Need to Remember

Average Power Flow P Through a Mostly Inductive Transmission Line (138kV and above)

)sin( 2121 δδ −=XVVP

11 δ∠V 22 δ∠V

jX

+

+

ground

These are about 1pu

For small x, sin(x) = x

Charles Steinmetz, developed phasortheory to analyze

AC circuits

Page 2 of 44

UT Pan Am

Austin

McDonald Observatory

400 miles

300 miles

Implementation and Application of anIndependent Texas Synchrophasor Network

Monitoring 120V Wall Outlet Voltages and Communicating Through the Public Internet

Austin

Majority of load is in the green rectangles, i.e. “Central ERCOT”

120V wall outlet at U.T. Austin, and 69kV 3Φmonitor at nearby Austin Energy Harris Sub

Wind Country

• Funding provided by EPRI

• Equipment provided by Schweitzer Engineering Labs

Page 3 of 44

Bus 2DFW

Bus 4SA

Bus 5VAL

Bus 6COAL

Bus 7WIND

300 km

250 km

150 km300 km

400 km

500 km400 km

Bus 3UT

Bus 1HOU

Positive-sequence line constants for each 345kV circuit:

• R = 0.06 Ω/km per conductor

• L = 1 µH/m

• C = 12 pF/m

• Rating = 800 A per conductor

• From the L, XL (500 km) = 188.5 Ω

• For 345 kV, 100 MVA base, Zbase = 1190 Ω

• For each 500 km circuit, XL = 0.158 pu

• Thus, four parallel circuits have XL = 0.040pu, and six parallel circuits have XL = 0.026 pu

Relatively small phase angle variation in central ERCOT

McDonald Observatory

PMU

UT Austin PMU

Bus 2DFWBus 2DFW

Bus 4SA

Bus 4SA

Bus 5VAL

Bus 5VAL

Bus 6COALBus 6COAL

Bus 7WINDBus 7WIND

300 km

250 km

150 km300 km

400 km

500 km400 km

Bus 3UT

Bus 3UT

Bus 1HOUBus 1HOU

Positive-sequence line constants for each 345kV circuit:

• R = 0.06 Ω/km per conductor

• L = 1 µH/m

• C = 12 pF/m

• Rating = 800 A per conductor

• From the L, XL (500 km) = 188.5 Ω

• For 345 kV, 100 MVA base, Zbase = 1190 Ω

• For each 500 km circuit, XL = 0.158 pu

• Thus, four parallel circuits have XL = 0.040pu, and six parallel circuits have XL = 0.026 pu

Relatively small phase angle variation in central ERCOT

McDonald Observatory

PMU

UT Austin PMU

U.T. Pan AmPMU

Synchrophasor Homework Network for ERCOT

U.T. McDonald ObservatoryPMU

Oscilloscope View. If UT Austin = 0º ref, then McD leads by 60º, and Pan Am lags by 30º

360º

+60º −30º

Small oscillations in the relative phase angles give an indication grid stability. Essentially, these oscillations provide an “EKG” for large power grids.

Page 4 of 44

Our First Remote Phasor Measurement Unit, UT Austin’s McDonald Observatory, in the Attic of the Fire Station

Living is good at the Astronomers’ Lodge

Page 5 of 44

Grady, Brooks, NREL, 1/27/11 6

WECC Grid - The Cloudcroft, NM, (near White Sands National Monument, but 4000’higher in elevation). Long way from Pullman. Doorknob-sized GPS antenna mounted

on a PVC pipe and Christmas tree Stand. Two views of antenna.

LOCATION

Latitude Longitude AltitudeN 32.52.54 W 105.39.10 7583 feet

Satellite Signal Strengths (Min for Lock, 3 Sats > 3.0)12.0 ; 7.0 ; 5.2 ; 6.0 ; 3.6 ; 5.2 ; 1.8 ; 15.2 ; -.- ; -.- ; -.- ; -.-

Page 6 of 44

7

The Cloudcroft, NM, Station, Piggy-Backed onto Standard DSL Internet Service

“The Grid Monitor”(a power strip)

Cloudcroft

GPS ReceiverSpare Antenna

SEL 421 Relay/PMU

DSL Modem and Wireless Router

Page 7 of 44

The Good News and the Bad News

The good news – each remote PMU streams back via internet

• 30 readings per second, • times 60 seconds per minute, • times 60 minutes per hour, • times 24 hours per day,

which equals 2.5 million lines of Excel data per PMU per day.

Each line has voltage angle, freq, Vrms, modal information, …

Page 8 of 44

The Good News and the Bad News, cont.

The bad news – how do you deal with all the data, process it, and find the nuggets?

So we become Synchrophasor Detectives – EVERY day has surprises and clues.

We look for events, and when we find something interesting, we post it on the Texas SynchrophasorNetwork web page.

Let’s now take a look at some lessons learned thus far.

Page 9 of 44

Lesson 0. Either Wind Affects the US Congress, or the US Congress Affects Wind

Page 10 of 44

Thur Fri

West Texas voltage phase angle swings nearly 100º and back with respect to U.T. Austin in about 24 hours

Wind generation and West Texas phase angle can go through large daily swings

McDonald Observatory Voltage Phase Angle with respect to U.T. AustinMarch 25, 26, 2010

-60

-40

-20

0

20

40

60

24 36 48 60 7236 Hours Beginning 12am, March 24, 2010

Deg

rees

Wind Generation in ERCOT - MWMarch 25, 26, 2010

0

1000

2000

3000

4000

5000

6000

24 36 48 60 72

MW

48

Lesson 1. Every Day has Synchrophasor Surprises

Page 11 of 44

Generator Trips and Frequency Rises?24 Seconds, Beginning Mon, April 11, 2011, 01:31:36 CDT

59.85

59.90

59.95

60.00

60.05

60.10

0.6 0.7 0.8 0.9 1.0Minutes

Freq

uenc

y

UT 120VHarris 69kVUT Pan Am 120V

24 Seconds, Beginning Mon, April 11, 2011, 01:31:36 CDT

-2

0

2

4

6

8

10

0.6 0.7 0.8 0.9 1.0Minutes

Volta

ge P

hase

Ang

le

Harris 69kVUT Pan Am 120V

From Kent Saahoff, ERCOT: Thunderstorms with high winds and lightning in north Texas tripped a double circuit 345 KV line at 1:32 that also took out two large units carrying about 800 MW. Another 200 MW unit tripped about a minute later. Preceding high frequency probably caused by loss of load due to distribution outages caused by the severe weather.

Inertial Droop

Ringdown Starts

Freq. Jumps Up?

South Texas Angle Rises

Page 12 of 44

Voltage Phase Angles Relative to U.T. Austin (One-Minute Averages, 1800 Readings in Each Minute)

-60

-40

-20

0

20

40

60

0 24 48 72 96 120 144 168 192 216 240 264 288 312 336 360 384 408

Hour Beginning 00:00 CST, Sunday, March 27, 2011

McDUTPA

Voltage Phase Angles, 1-Minute Averages

-20

-10

0

10

20

30

40

50

24 Hours Beginning 18:00 CST, Saturday, April 2, 2011

McDUTPA

Zoom-In, 24 hours wide

1 2

2 2

1. Rapid wind gen ramp, approx 45º in 1.5 hours.

2. Unusual large, slow angle rings I had not noticed before. Period = 30 mins, 10º to 15º peak-to-peak.

Page 13 of 44

Frequency, 1-Minute Averages

59.90

59.95

60.00

60.05

60.10

8 Hours Beginning 10:00 CST, Sunday, April 3, 2011

McDUTPA

-20

-10

0

10

20

30

40

8 Hours Beginning 10:00 CST, Sunday, April 3, 2011

McDUTPA

Voltage Phase Angle, 1-Minute Averages

• Frequency measurements (bottom graph) are of course very valuable, but are basically the same across the grid

• Frequency variations are in the 3rd or 4th significant digit, near the limit of measurement resolution

• Phase angle measurements (top graph) are rich with regional response, providing “stereo vision” that is useful in localizing disturbances.

• Measured angle variations are much greater than the 0.1 degree accuracy.

Texas Nodal Market Has Created a New West Texas Resonant Mode with Time Period = 30 minutes

Page 14 of 44

Voltage Phase Angles, 1-Minute Averages

-20

-10

0

10

20

30

40

50

6 Hours Beginning 12:00 CST, Saturday, April 9, 2011

McDUTPA

5pm CST4pm

Sat., April 9, 2011. McDonald Observatory PMU Drops Out.

Page 15 of 44

Last 10 Minutes of Vrms at McDonald Observatory

0.95

0.96

0.97

0.98

0.99

1.00

1.01

1.02

0 1 2 3 4 5 6 7 8 9 10

Minute

Nor

mal

ized

Vrm

s

Sat., April 9, 20114:35pm, CST 4:45pm, CST

Zoom-In of the Last 10 Minutes of Vrms

Page 16 of 44

Last 10 Minutes of Vrms at McDonald Observatory

0.95

0.96

0.97

0.98

0.99

1.00

1.01

1.02

0 1 2 3 4 5 6 7 8 9 10

Minute

Nor

mal

ized

Vrm

s

Sat., April 9, 20114:35pm, CST 4:45pm, CSTLast 10 Minutes of Vrms at McDonald Observatory

0.95

0.96

0.97

0.98

0.99

1.00

1.01

1.02

0 1 2 3 4 5 6 7 8 9 10

Minute

Nor

mal

ized

Vrm

s

Sat., April 9, 20114:35pm, CST 4:45pm, CST

12 Seconds Centered Around Minute 5.5

0.96

0.97

0.98

0.99

1.00

1.01

5.4 5.5 5.6

Minute

Nor

mal

ized

Vrm

s

Zoom-In of 12 Seconds of Vrms

Page 17 of 44

McDonald Vrms at Restart

0.98

0.99

1.00

1.01

0 1 2 3 4 5 6

Minute Into Restart

McDonald Restarted About 11pm Monday Night

Page 18 of 44

McDonald Observatory Voltage Phase Angle w.r.t U.T. Austin 120V and Harris 69kV

-14

-13

-12

-11

-10

1600 1700 1800 1900 2000 2100 2200

Sample (30 samples per second)

Deg

rees w.r.t U.T. Austin

w.r.t Harris 69kV

10 seconds

• The fixed net multiple of 30 degree phase shift between U.T. Austin 120V and Harris 69kV has been removed. The variable but steady 0.1 degree power flow phase shift through the substation transformer has also been removed.

• Can you see any significant difference between the waveform seen by the 120V wall outlet (in black) and the waveform seen by the 69kV, 3Φ grid monitor (in red)? (The correct answer is NO!)

Voltage Ringdown at McDonald Observatory Observed at the Following Two Locations in Austin: a 120V Wall Outlet on Campus, and the Harris 69kV Substation that Feeds the Campus

Lesson 2. 120V Wall Outlets Work for Synchrophasors

Page 19 of 44

Steady-State Voltage Angle Between ECE Building 120V Wall Outlet and 69kV Substation Monitor Varies with UT Generation and Load

Week of April 27, 2011

Voltage Phase Angle Relative to UT Austin1-Minute Averages, Beginning Sunday, April 17, 2011

-5

-4

-3

-2

-1

0

0 24 48 72 96 120 144 168

Hour of the Week

Deg

rees

Harris

Page 20 of 44

Bus 7WINDBus 7WIND

500 km

Local conventional Pload,conv − Pgen,conv

Pexport

Thevenin Impedance jXTH

Central ERCOT

Vangle = 0

Vangle = δ

Wind MW Backdown. July 15, 2010. Thevenin Impedance Calculation, cont.

Use the Excel Solver with the 90 minutes of readings tominimize least-squared error and determine Xth

Lesson 3. You Can Estimate Thevenin Equivalent Impedances Across the Grid with Synchrophasors

Page 21 of 44

West Texas Power Export Estimates Pexp1 and Pexp2, MW

-1000

0

1000

2000

3000

0 10 20 30 40 50 60 70 80 90

Minute Beginning 0400 CDT, July 15, 2010

90-Minute Window

Wind MW Backdown. July 15, 2010. Thevenin Impedance Calculation, cont.

Squared area between the two curves is minimized whenA = -0.0471

B = 356

Xth = 0.0211 pu on 345kV, 100MVA base

Page 22 of 44

2 Hz Cluster

March 18, 02:00 – 03:00 Wind Generation > 20%

March 12, 02:00 – 03:00 Wind Generation ≈ 2%

Big Wind (20%) with 2 Hz Cluster Small Wind (2%) without 2 Hz Cluster

Lesson 4. A 2 Hz Mode in Ambient Oscillation Sometimes Forms with High Wind Generation

Page 23 of 44

Start Sec Stop Sec A t1 B Tau1 t2 C Tau2 Wdamp 2010/10/04 18:18:00.015 30 -41.60 21.38 -45.65 0.19 21.37 4.28 1.95 3.82 PMUs = McDonald 1P

Fdamp Zeta Angle reference = Aus0.608 0.134

UT Pan Am Voltage Angle with respect to U.T. Austin, 2010/10/04 18:18:00.000

-49

-48

-47

-46

-45

-44

-43

-42

-41

-40

15 20 25 30 35

MeasuredCurve Fit

Healthy response to a unit trip

Lesson 5. Wind Generation Does Not Appear to Impact System Damping or Damped Resonant Frequency

Page 24 of 44

Ringing Frequency vs Wind Generation (% of Total), Sep 2009 ‐ Feb 2010

0

0.5

1

1.5

2

2.5

3

0 2 4 6 8 10 12 14 16 18 20

Wind Generation (% of Total)

Freq

uency (Hz)

Ringdown Analysis of More Than 100 Unit Trips Yields No Clear Relationship Between Wind MW and Damped Resonant Frequency

Does Wind Generation Impact Grid Stability?

Page 25 of 44

Damping Ratio vs Wind Generation (% of Total), Sep 2009 ‐ Feb 2010

0

0.2

0.4

0.6

0.8

1

1.2

0 2 4 6 8 10 12 14 16 18 20

Wind Generation (% of Total)

Normalized

Dam

ping

Ratio

Ringdown Analysis of More Than 100 Unit Trips Yields No Clear Relationship Between Wind MW and Normalized Damping Ratio

Does Wind Generation Impact Grid Stability?

Page 26 of 44

( )rated

s

s

m

rated

ss

rated

s

PdtdP

PJ

P

JH ω

ωωωω

⎥⎦

⎤⎢⎣

⎡ Δ−=

•=≡

/21

212

1 2

( ) ( ) ( )dtdfPfP

dtdff

PP

dtdPPH

srated

sm

s

s

rated

m

s

s

rated

m/2/2

22/2

1 Δ−=

Δ−=⎥

⎤⎢⎣

⎡ Δ−=

ππ

ωω

H has the units of seconds. The correct interpretation is that the kinetic energy in the equivalent system machine corresponds to H seconds of rated power. Thus, the machine could provide rated power for H seconds, at which time it would have spun down to zero RPM.

EPRI Study. Purpose – to compute ERCOT System Inertia Constant H From Frequency Response During 42 Unit Trips Having 0.1 Hz or Greater Freq. Drop.

Lesson 6. Wind Generation Does Not Appear to Reduce System Inertia(but no generator operating at max power can contribute to governor

response)

Page 27 of 44

August 2010, Event 7, cont.

Event 7Voltage Phase Angle Event 7, 8/24/2010 07:31:00 PM GMT Minute

59.82

59.84

59.86

59.88

59.90

59.92

59.94

59.96

59.98

60.00

56 57 58 59 60 61 62 63 64 65 66

Second of the Minute

Freq

uenc

y UT AustinHarris 69McDUT PanAm

Inertia slope

Nadir slope

Zoom

Page 28 of 44

Estimated System H versus % Wind Generation(42 Unit Trip Events, June through November 2010)

0

2

4

6

8

10

12

0 5 10 15 20

Wind Generation - % of Total Generation

Estim

ated

H42 Major Unit Trips, 0.1 Hz or Greater. Any Correlation Between System

Inertia and Wind Generation (% of Total Gen)?

Page 29 of 44

Estimated System H versus Wind Generation (MW)(42 Unit Trip Events, June through November 2010)

0

2

4

6

8

10

12

0 1000 2000 3000 4000 5000 6000 7000

Wind Generation - MW

Estim

ated

H42 Major Unit Trips, 0.1 Hz or Greater. Any Correlation Between System

Inertia and Wind Generation (MW)?

Page 30 of 44

Event 7, 8/24/2010 07:31:00 PM GMT Minute

59.82

59.84

59.86

59.88

59.90

59.92

59.94

59.96

59.98

60.00

56 57 58 59 60 61 62 63 64 65 66

Second of the Minute

Freq

uenc

y UT AustinHarris 69McDUT PanAm

Inertia slope

Nadir slope

ΔTnadir

ΔFnadir

ΔFinertia

August 2010, Event 6, 8/24/2010, 07:31:00 PM GMT

Figure 48. Introduction and Graphical Illustration of the Proposed New Metric, Frequency Recovery Ratio (FFR).

FrequencyRecoveryRatio

nadir

inertiaFF

FRRΔΔ

Page 31 of 44

• 42 Major Unit Trips, 0.1 Hz or Greater. FRR is affected by wind generation because wind generators typically operate at max power and thus have no spinning reserve.

• But wind generators do not appear to reduce system inertia.

Frequency Recovery Ratio (FRR) versus % Wind Generation(42 Unit Trip Events, June through November 2010)

0

1

2

3

4

0 5 10 15 20Wind Generation - % of Total Generation

FRR

Page 32 of 44

Let’s Do Some Detective Work for This Week

Voltage Phase Angle Relative to UT Austin1-Minute Averages, Beginning Sunday, April 24, 2011

-50-40-30-20-10

01020304050

0 24 48 72 96 120 144 168

Hour of the Week, CDT

Deg

rees McD

PanAm

Sun Mon Tue

Page 33 of 44

Voltage Phase Angle Relative to UT Austin1-Minute Averages, Monday, April 25, 2011, Beginning 09:00 CDT

-20

-10

0

10

20

30

40

33 36 39 42 45

Hour of the Week, CDT

Deg

rees McD

PanAm

Looks Like the New Texas Nodal Market Oscillation ProblemIs Still Here

Page 34 of 44

Angle Ringdownat McD

1 Minute Window Angle Ringdown at PanAm

1 Minute Window

Page 35 of 44

59.98

59.99

60.00

60.01

60.02

60.03

60.04

60.05

0 1 2 3

Minutes

Hz Harris 69

PanAm

Frequency, 3 Minutes Beginning April 24, 2011,19:54 CDT

59.98

59.99

60.00

60.01

60.02

60.03

60.04

60.05

0 1 2 3

Hz Harris 69

McD

Page 36 of 44

Voltage Phase Angle, 3 Minutes Beginning April 24, 2011,19:54 CDT

-1

0

1

2

3

0 1 2 3

Deg

rees

McD

18

19

20

21

22

0 1 2 3

Minutes

Deg

rees

PanAm

Page 37 of 44

Unit Trip,

April 24, 2011,

21:15 CDT

Page 38 of 44

Unit Trip,

April 24, 2011,

21:15 CDT

Page 39 of 44

PanAm

McD

Unit Trip, April 24, 2011, 21:15 CDT

Page 40 of 44

Start Sec Stop Sec A t1 B Tau1 t2 C Tau2 Wdamp24.5 28.9 13.31 24.88 13.98 0.14 25.14 0.88 2.97 3.68

Fdamp Zeta0.585 0.092

Unit Trip April 24, 2011, 21:15:25 CDT. McDonald Angle Relative to U.T. Austin

13

14

15

23 24 25 26 27 28 29 30 31 32 33Seconds

Deg

rees

MeasuredCurve Fit

Damped Resonant Frequency, Hz Normalized

Damping Coefficient

Ring Magnitude, degrees

Steady-State Change = 13.98 – 13.31 = 0.7 degrees

McDonald

Page 41 of 44

Start Sec Stop Sec A t1 B Tau1 t2 C Tau2 Wdamp24.5 28.9 17.68 24.62 14.40 0.23 24.93 -2.23 1.58 3.71

Fdamp Zeta0.591 0.170

Unit Trip April 24, 2011, 21:15:25 CDT. Pan Am Angle Relative to U.T. Austin

12

13

14

15

16

17

18

23 24 25 26 27 28 29 30 31 32 33Seconds

Deg

rees

MeasuredCurve Fit

Damped Resonant Frequency, Hz Normalized

Damping Coefficient

Ring Magnitude, degrees

Steady-State Change = 14.40 – 17.68 = -3.3 degrees

Pan Am

Page 42 of 44

Damped Oscillation Frequencies, Magnitudes, and Normalized Damping Ratiosfor the Hour 21:00 – 22:00 CDT, April 24, 2011

McD Voltage Angle Relative to UT Austin UT Pan Am Voltage Angle Relative to UT Austin

Page 43 of 44

Texas Synchrophasor Network

Thanks to

• Schweitzer Engineering Laboratories, especially Mr. David Costello, for providing all the equipment and technical support that we need

• EPRI, especially Ms. Karen Forsten and Mr. Daniel Brooks, for past, present, and future funding of graduate students and faculty summer support

• Startup money in 2008 from the Texas Governor Rick Perry’s Emerging Technology Fund through CCET, Dr. Milton Holloway

• Austin Energy, especially Mr. Scott Bayer, for installing the 69kV phasor measurement unit, and providing advice on system operating and protection

• PhD student Moses Kai at U.T. Austin for his dedication and research in synchrophasors and their applications to power grids

Page 44 of 44