Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Brief Introduction for Automated Relay Testing Kamin Dave Application Engineer (Protective Relaying) DOBLE ENGINEERING COMPANY

Upload: terezkam

Post on 07-Mar-2015

406 views

Category:

Documents


15 download

DESCRIPTION

testing of alstom kbch differential relay

TRANSCRIPT

Page 1: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Relay Testing

Kamin DaveApplication Engineer (Protective Relaying)

DOBLE ENGINEERING COMPANY

Page 2: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Protection Relay Testing:

Testing of Differential Protection Relay type KBCH120

Page 3: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120

Two Differential Protection relaysAutomatic calculation for TAP values based on CTRSettings for Transformer & CT vector group compensations 2nd Harmonic Blocking during inrush period due to point on wave switching

Inrush Gap Detection Criterion

5th Harmonic Blocking for Over excitation phenomenaInverse Time Over Excitation Trip Characteristic

Page 4: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120MAKE : AREVAMODEL : KBCH120Relay Settings:Differential Element:

Rated MVA = 100HV = 220KVLV = 66KVTR VECTOR GROUP = YY0.CT CONNECTION = YYID> = 0.2PUTurn Point1 = 1.0PUID>> = 5.0PUSLP1 = 20% SLP2 = 80%In = 1A

Page 5: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120MAKE : AREVAMODEL : KBCH120Relay Settings:Differential Element:

HV CT Ratio = 300/1ALV CT Ratio = 1200/1ACF1 = 1.14CF2 = 1.37HV Vector Correction = YY0LV Vector Correction = YY0

Page 6: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: KBCH120

FLC on TR Primary side:IFLC = (100*1000) / (1.7325*220)

= 262.36 AmpereFLC on TR Secondary side:

IFLC = (100*1000) / (1.7325*66)= 874.54 Ampere

CF1 = (1*300) / (262.36*1) = 1.14

CF2 = (1*1200) / (874.54*1) = 1.37

Page 7: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Page 8: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Characteristic: Dual Slope

Idiff@SLP1 = (IBIAS)*(0.2) + (IS)

Idiff@SLP2 = (IS) + 0.2 + (Ibias - 1)*0.8

Page 9: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.18-1028

Page 10: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Page 11: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

IA

IB

IC

I1

I2

I3

KBCH

Test Circuit:

Source Configurations:Six current sources

Winding 1 currents

Winding 2 currents

Page 12: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Pickup test for Winding1

• Pickup test for winding2

• Slope Characteristic test

Tests conducted:

Page 13: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test

Use “RAMP” Module

Page 14: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:Pickup Test for Winding1 (WDG1):-Ipickup = (IS)*(1/CF1)

= (0.2)*0.8745= 0.1749A

Pickup Test for Winding2 (WDG2):-Ipickup = (IS)*(1/CF2)

= (0.2)*0.7287 = 0.1457A

Page 15: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Winding Pickup Test:

How to Create Test Plan???

Page 16: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Location Level

Add new Location or Double click on Existing Location

Page 17: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Level

Add new Relay or Double click on Existing Relay

Page 18: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on Mouse & Press “Append”& create New Testplan

Page 19: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on “New test Plan”

Page 20: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse” & Press on “Append”& Create new Test Module

Page 21: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “RAMP” Module from list

Page 22: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “OK” & Create New Test Definition

Page 23: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “6 Currents (Right bank)”

Page 24: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “Yes”

Page 25: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

WDG1 current sources

Enter Expected Value = 0.175A

Enter “Action”details

Select “Trigger”

Page 26: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG1

Actual Test value = 0.197A

Click on “RUN”

Page 27: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

WDG2 current sources

Enter Expected Value = 0.165A

Enter “Action”details

Select “Trigger”

Page 28: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test: WDG2

Actual Test value = 0.167A

WDG2 current sources

Page 29: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test

Use “DiffChar” Module

Page 30: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Slope Characteristic Test:

Star conn. Star conn.

IP Is

Page 31: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to Create Slope Characteristic???

Page 32: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Add” & select “Differential”

Page 33: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Bias current (Ibias) formula from list

Bias current Formula:Ibias = (IP+IS) / 2

Page 34: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

R

YY0 YY0

Star conn. Star conn.YY0

SoftwareConfiguration

Amplitude Compensation

Page 35: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Pickup” Column & then after Click on “Modify”

Page 36: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Pickup settingSay; 0.2

Select IBias Vs Idiff

Page 37: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Slope 20% & 80% based on relay setting

SLP1=20%

SLP2=80%

How to AdjustSlope?

Page 38: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Close”

Page 39: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse”& click on “Append”

How to create New Test Module?

Page 40: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

How to create New Test Module?

Select “DiffChar” Module from list

Page 41: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double Click on Test Module & create New Test Definition

Page 42: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Page 43: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select elements

Page 44: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Max. Test current (i.e. 12A)

Page 45: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Page 46: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select test points on curve

Page 47: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

click on Add Point to List

Page 48: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Points are added for Test

Page 49: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on check box

Right Click on check box

Page 50: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “RUN”

Page 51: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Red color shows Expected Curve & White color shows actual Curve

Test results

Page 52: KBCH120 Relay Testing With F6150

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

DOBLE ENGINEERING COMPANY305-SAKAR, O.P. ROADNR. ABS TOWERVADODARA-390 015INDIA. Tel:- +91 265 655 77 15EMAIL ID:- [email protected]:- www.doble.com