Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery Brief Introduction for Automated Testing of LFDC101/102 Relay Kamin Dave Manager – Marketing & Protection Applications South Asia & Middle East DOBLE ENGINEERING COMPANY, INDIA kdave@doble.com

Upload: sristhi-ganguli

Post on 28-Nov-2014

181 views

Category:

Documents


15 download

TRANSCRIPT

Page 1: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Brief Introduction for Automated Testing of LFDC101/102 Relay

Kamin DaveManager – Marketing & Protection Applications

South Asia & Middle EastDOBLE ENGINEERING COMPANY, INDIA

[email protected]

Page 2: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Protection Relay Testing:

Testing of LFDC101/102Relay by using F6150

Page 3: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

High speed directional comparison protection using signaling channel

Distance Zone Backup

Switch On to Fault Protection

Voltage Transformer supervision

Page 4: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Operating time of Directional comparison unit is 12 to 15ms

Operating time of Distance zone (Backup) is adjustable

Page 5: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Page 6: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 7: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 8: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 9: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 10: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 11: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 12: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Page 13: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

RA RBCommunication(Signaling betn two relays)

Page 14: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

Carrier scheme supervised by Mho elementIf there is fault in Line & fault impedance falls under preset value then Both relays will send carrier signals to each otherScheme is normally applied as a primary protection for short line length (<5km)

Page 15: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 External fault (F1) in Forward direction

IA = - IBIA + IB = 0

Page 16: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1

External fault (F1) in Forward direction

IA

IB

Page 17: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1

External fault (F1) in Forward direction

ZA

ZB

ZF

ZF

Forward Direction

Reverse Direction

Page 18: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 External fault (F1) in Reverse direction

Both currents are zero in Radial feeder IA = 0IB = 0

Page 19: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

External fault (F1) in Reverse direction

ZA ZB

ZFZF

Reverse Direction

S1 S2

RA RB

F1

IA IB

Page 20: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 Internal fault (F1) in Forward direction

IA

IB

Page 21: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

F1 Internal fault (F1) in Forward direction

ZA

ZBZF

ZF

Page 22: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

ZA

ZB ZF

ZF

RF

RF

Kn = 0.75

Internal Fault: Fault measurement for Phase to Ground faults

Kn = 0.75

R in Ohms

X in Ohms

R in Ohms

X in Ohms

RA

RB

Page 23: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

Internal fault (F1) in Forwarddirection& fault feeding is from End A

F1 F2

Internal fault (F2) in Forwarddirection& fault feeding is from End B

Page 24: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

Internal fault (F1) in Forward direction & Fault feeding is from source “S1”

ZA ZB

ZFZF

S1RA RBF1

RC RDZC ZD

ZF

ZF

Relay “RC” will operate on Back Zone

IA IB

Page 25: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

ZA

ZB ZF

ZF

Relay Operating time faster (12 to 15ms) when carrier signal receive & impedance falls under preset value during internal faults

R in Ohms

X in Ohms

R in Ohms

X in Ohms

RA

RB

Page 26: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: Measuring Principle

ZA

ZB ZF

ZF

Relay Operating time based on time delay set in relay when carrier signal NOT receive & impedance falls under preset value during internal faults

R in Ohms

X in Ohms

R in Ohms

X in Ohms

RA

RB

Page 27: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

LFDC Relay for Line1

LFDC Relay for Line2

220KV GETCO S/S

Page 28: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

220KV GACL S/S

LFDC Relay for Line1

LFDC Relay for Line2

PLCC Cabinet

Page 29: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCPLCC: Power Line Carrier Communication (PLCC) is used to communicate devices between substations.The Audio frequency is carried out by a carrier frequency and the range of carrier frequency is 24kHz to 500kHzWave trap: It is an inductor of rating in mili henry. It is connected in series with the power transmission line. It blocks the high frequency carrier waves (24kHz to 500kHz) and let Power waves (50Hz – 60Hz) to pass through.

Page 30: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCCoupling Capacitor: It provides low impedance path for carrier energy to H.V. line and blocks the power frequency circuit by being a high impedance path.HF Cable: It is used to carry to signal from PLCC cabinet to switchyard

Page 31: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCPLCC Cabinet: It indoor equipment. It is divided in two parts;

TransmitterReceiver

Page 32: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCCWave trap or Line trap

Page 33: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Carrier send Carrier receive

Carrier receive Carrier send

Communication through PLCC

Exchange SignalsBoth are thinking same

Scheme Stable on External Faults

220KV GETCO S/S 220KV GACL S/S

F1RA RB

Delta V = 0Delta I = 0IA - IB = Delta IIA = IB VA - VB = Delta VVA = VB

IA IB

Page 34: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Carrier send Carrier receive

Carrier receive Carrier send

Communication through PLCC

Scheme Operates on Internal Faults

220KV GETCO S/S 220KV GACL S/S

F1RA RB

Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB

Exchange SignalsBut both are thinking in different

IA IB

Page 35: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Carrier send Carrier receive

Carrier NOT receive Carrier send

Communication through PLCC

Scheme Operates on Internal Faults

220KV GETCO S/S 220KV GACL S/S

F1RA RB

Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB

No Exchange of SignalsBut both are thinking in different

IA IB

Page 36: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCC

Page 37: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCC

Page 38: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: LFDC101/102

Relay Settings:Location: GETCO and GACL Ends, DahejLine length: 1.5kmLine voltage: 220kV (Line1)• Z = 0.2 Ohms• tZ = 0.2s• Line Angle = 78 Deg.• Kn = 0.75

Page 39: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment

• Make : DOBLE

• Model : F6150

Software

• F6TesT Version 2.19-1065

Page 40: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

VA

VB

VC

I1

I2

I3

Relay

Test Circuit:

Source Configurations:3V X 3I

CT Inputs

Page 41: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

• Zone Time Test during carrier signal received from other end

• Zone Time Test (Distance Zone Backup)

• Zone Characteristic Test

• SOTF Test

• Stability Test of scheme

Test Conducted:

Page 42: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone Time Test during Carrier signal received

from other end

Use “ZTime” Module

Page 43: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Location Level

Right click on Mouse & click on “Append” and create new Location

Page 44: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Level

Right click on Mouse & click on “Append” and create new Relay

Page 45: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Parameters

Click on “Add” button & select “Impedance” function

Page 46: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click here & then click on “New Zone” button

Page 47: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “MHO” & enter relay settings

Page 48: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Yes”

Page 49: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for Ph-N fault

Page 50: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for Ph-Ph & 3-Ph faults

Page 51: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click on “Yes”

Page 52: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on “Mouse” & Click on “Append” to create new Test plan

Page 53: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse” & click on “Append” to create new test module for testing

Page 54: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “Z-Time” Module from list

Page 55: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “OK” & Create New Test Definition

Page 56: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Page 57: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Test current (i.e. 2.3A)

Select Test Method

Page 58: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Enter Prefault duration & Max. fault duration

Page 59: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Click Test points in R-X Plane for “Ph-Ph” fault

Page 60: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green/Red Points areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Relay operated in 12 to 13ms

Carrier signal received from other end on E19 & E20terminals of Relay

Page 61: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display shows relay tripped on DIR (A-N fault)

Time Test: Directional Comparison

Page 62: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Zone Time Test (Distance Zone Backup)

Use “ZTime” Module

Page 63: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green/Red Points areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Relay operated in 250 to 260ms

Carrier signal NOT received from other end on E19 & E20 terminals of Relay

Page 64: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green/Red Points areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Relay operated in 250 to 260ms

Carrier signal NOT received from other end on E19 & E20 terminals of Relay

Page 65: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Display shows relay tripped on Z (T) (BC fault)

Time Test: Distance Backup Zone

Page 66: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic Test

Use “ZChar” Module

Page 67: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right click on “Mouse” & Press on “Append”& Create new Test Module

Page 68: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select “Z-Char” Module from list

Page 69: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Double click on “Characteristic Test”

Page 70: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Press on “OK” & Create New Test Definition

Page 71: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select characteristic from list

Page 72: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Test Method

Page 73: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Test current (i.e. 2.3A)

Page 74: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select Trigger (i.e. Open to Close)

Page 75: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Angle Boundary for test (Say; start from 0 to 180 Degree)

Page 76: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Enter Angle Boundary for test (Say; start from 0 to 180 Degree)

Page 77: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Green Points (white lines) areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Right Click on check box

Page 78: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Right Click on check box

Green Points (white lines) areActual Points have been tested

Blue color shows;Expected characteristic

Line Angle

Page 79: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

SOTF Test

Use “SSIMUL” Module

Page 80: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Select SSIMUL Module from list

Page 81: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

State1 set for SOTF

Page 82: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Operating time recorded 47ms

Page 83: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Scheme Testing

Page 84: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Comm Channel

Protectionunder test

GPS Synch: End to End Testing

Test PUTT/POTT Schemes

1pps Signal 1pps SignalF6910+F6885+F6895 Option

Page 85: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Communication through PLCC

Counter for Carrier send signals

Counter for Carrier receive signals

Both end relays tripped on 13ms

Page 86: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Page 87: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

F6TEST2.21-1157 Advance Line Version

Page 88: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery

Page 89: 38.LFDC Relay Testing With F6150-1

Knowledge Is PowerSM

Apparatus Maintenance and Power Management for Energy Delivery