Apparatus Maintenance and Power Management for Energy Delivery
Brief Introduction for Automated Testing of LFDC101/102 Relay
Kamin DaveManager – Marketing & Protection Applications
South Asia & Middle EastDOBLE ENGINEERING COMPANY, INDIA
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Protection Relay Testing:
Testing of LFDC101/102Relay by using F6150
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
High speed directional comparison protection using signaling channel
Distance Zone Backup
Switch On to Fault Protection
Voltage Transformer supervision
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Operating time of Directional comparison unit is 12 to 15ms
Operating time of Distance zone (Backup) is adjustable
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
RA RBCommunication(Signaling betn two relays)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
Carrier scheme supervised by Mho elementIf there is fault in Line & fault impedance falls under preset value then Both relays will send carrier signals to each otherScheme is normally applied as a primary protection for short line length (<5km)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 External fault (F1) in Forward direction
IA = - IBIA + IB = 0
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1
External fault (F1) in Forward direction
IA
IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1
External fault (F1) in Forward direction
ZA
ZB
ZF
ZF
Forward Direction
Reverse Direction
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 External fault (F1) in Reverse direction
Both currents are zero in Radial feeder IA = 0IB = 0
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
External fault (F1) in Reverse direction
ZA ZB
ZFZF
Reverse Direction
S1 S2
RA RB
F1
IA IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 Internal fault (F1) in Forward direction
IA
IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
F1 Internal fault (F1) in Forward direction
ZA
ZBZF
ZF
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
ZA
ZB ZF
ZF
RF
RF
Kn = 0.75
Internal Fault: Fault measurement for Phase to Ground faults
Kn = 0.75
R in Ohms
X in Ohms
R in Ohms
X in Ohms
RA
RB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
Internal fault (F1) in Forwarddirection& fault feeding is from End A
F1 F2
Internal fault (F2) in Forwarddirection& fault feeding is from End B
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
Internal fault (F1) in Forward direction & Fault feeding is from source “S1”
ZA ZB
ZFZF
S1RA RBF1
RC RDZC ZD
ZF
ZF
Relay “RC” will operate on Back Zone
IA IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
ZA
ZB ZF
ZF
Relay Operating time faster (12 to 15ms) when carrier signal receive & impedance falls under preset value during internal faults
R in Ohms
X in Ohms
R in Ohms
X in Ohms
RA
RB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: Measuring Principle
ZA
ZB ZF
ZF
Relay Operating time based on time delay set in relay when carrier signal NOT receive & impedance falls under preset value during internal faults
R in Ohms
X in Ohms
R in Ohms
X in Ohms
RA
RB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
LFDC Relay for Line1
LFDC Relay for Line2
220KV GETCO S/S
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
220KV GACL S/S
LFDC Relay for Line1
LFDC Relay for Line2
PLCC Cabinet
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCPLCC: Power Line Carrier Communication (PLCC) is used to communicate devices between substations.The Audio frequency is carried out by a carrier frequency and the range of carrier frequency is 24kHz to 500kHzWave trap: It is an inductor of rating in mili henry. It is connected in series with the power transmission line. It blocks the high frequency carrier waves (24kHz to 500kHz) and let Power waves (50Hz – 60Hz) to pass through.
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCCoupling Capacitor: It provides low impedance path for carrier energy to H.V. line and blocks the power frequency circuit by being a high impedance path.HF Cable: It is used to carry to signal from PLCC cabinet to switchyard
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCPLCC Cabinet: It indoor equipment. It is divided in two parts;
TransmitterReceiver
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCCWave trap or Line trap
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Carrier send Carrier receive
Carrier receive Carrier send
Communication through PLCC
Exchange SignalsBoth are thinking same
Scheme Stable on External Faults
220KV GETCO S/S 220KV GACL S/S
F1RA RB
Delta V = 0Delta I = 0IA - IB = Delta IIA = IB VA - VB = Delta VVA = VB
IA IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Carrier send Carrier receive
Carrier receive Carrier send
Communication through PLCC
Scheme Operates on Internal Faults
220KV GETCO S/S 220KV GACL S/S
F1RA RB
Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB
Exchange SignalsBut both are thinking in different
IA IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Carrier send Carrier receive
Carrier NOT receive Carrier send
Communication through PLCC
Scheme Operates on Internal Faults
220KV GETCO S/S 220KV GACL S/S
F1RA RB
Delta V = ?Delta I = ?IA - IB = Delta IIA not equal to IBVA - VB = Delta VVA not equal to VB
No Exchange of SignalsBut both are thinking in different
IA IB
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCC
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCC
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Details: LFDC101/102
Relay Settings:Location: GETCO and GACL Ends, DahejLine length: 1.5kmLine voltage: 220kV (Line1)• Z = 0.2 Ohms• tZ = 0.2s• Line Angle = 78 Deg.• Kn = 0.75
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Test Equipment
• Make : DOBLE
• Model : F6150
Software
• F6TesT Version 2.19-1065
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
VA
VB
VC
I1
I2
I3
Relay
Test Circuit:
Source Configurations:3V X 3I
CT Inputs
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
• Zone Time Test during carrier signal received from other end
• Zone Time Test (Distance Zone Backup)
• Zone Characteristic Test
• SOTF Test
• Stability Test of scheme
Test Conducted:
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Zone Time Test during Carrier signal received
from other end
Use “ZTime” Module
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Location Level
Right click on Mouse & click on “Append” and create new Location
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Level
Right click on Mouse & click on “Append” and create new Relay
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Relay Parameters
Click on “Add” button & select “Impedance” function
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click here & then click on “New Zone” button
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select “MHO” & enter relay settings
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click on “Yes”
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic created for Ph-N fault
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic created for Ph-Ph & 3-Ph faults
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click on “Yes”
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on “Mouse” & Click on “Append” to create new Test plan
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right click on “Mouse” & click on “Append” to create new test module for testing
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select “Z-Time” Module from list
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Press on “OK” & Create New Test Definition
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select characteristic from list
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Test current (i.e. 2.3A)
Select Test Method
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select Trigger (i.e. Open to Close)
Enter Prefault duration & Max. fault duration
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Click Test points in R-X Plane for “Ph-Ph” fault
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green/Red Points areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Relay operated in 12 to 13ms
Carrier signal received from other end on E19 & E20terminals of Relay
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Display shows relay tripped on DIR (A-N fault)
Time Test: Directional Comparison
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Zone Time Test (Distance Zone Backup)
Use “ZTime” Module
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green/Red Points areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Relay operated in 250 to 260ms
Carrier signal NOT received from other end on E19 & E20 terminals of Relay
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green/Red Points areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Relay operated in 250 to 260ms
Carrier signal NOT received from other end on E19 & E20 terminals of Relay
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Display shows relay tripped on Z (T) (BC fault)
Time Test: Distance Backup Zone
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Characteristic Test
Use “ZChar” Module
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right click on “Mouse” & Press on “Append”& Create new Test Module
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select “Z-Char” Module from list
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Double click on “Characteristic Test”
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Press on “OK” & Create New Test Definition
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select characteristic from list
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select Test Method
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Test current (i.e. 2.3A)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select Trigger (i.e. Open to Close)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Angle Boundary for test (Say; start from 0 to 180 Degree)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Enter Angle Boundary for test (Say; start from 0 to 180 Degree)
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Green Points (white lines) areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Right Click on check box
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Right Click on check box
Green Points (white lines) areActual Points have been tested
Blue color shows;Expected characteristic
Line Angle
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
SOTF Test
Use “SSIMUL” Module
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Select SSIMUL Module from list
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
State1 set for SOTF
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Operating time recorded 47ms
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Scheme Testing
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Comm Channel
Protectionunder test
GPS Synch: End to End Testing
Test PUTT/POTT Schemes
1pps Signal 1pps SignalF6910+F6885+F6895 Option
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Communication through PLCC
Counter for Carrier send signals
Counter for Carrier receive signals
Both end relays tripped on 13ms
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
F6TEST2.21-1157 Advance Line Version
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
DOBLE ENGINEERING COMPANY2nd Floor Suvidhi Pride,Opp. Shell Petrol Pump,Gorwa-Refinery RoadVADODARA-390 015INDIA. Cell:- +91 98980 55956EMAIL ID:- [email protected]:- www.doble.com