john palmer - bre l 2013 launch event... · john palmer working groups ... boiler, the hot water...

33
Part of the BRE Trust John Palmer AECOM

Upload: vankhuong

Post on 27-Aug-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

Part of the BRE Trust

John PalmerAECOM

Part L 2013 – Launch eventBuilding Services Compliance Guides

08th October 2013, BRE

John Palmer

Working Groups

CLG and other Government Departments

Individual Representation

Part L 2013 Launch event – Building Services Compliance Guides

Process

Minimal changes to recommended energy efficiency standards

Mainly to bring into line with BSEN Standards and EU Directives Ecodesign Directive 2009/125/EC Energy Labelling Directive 2010/30/EU

No other changes for work on existing dwellings

Note other requirements Renewable Energy Directive 2009/28/EC Energy Efficiency Directive 2012/27/EU Energy Performance of Buildings Directive 2010/31/EU Microgeneration Certification Scheme, RHI, Green Deal

SAP Product Characteristics Database

Also corrections, clarifications, improved layout

Part L 2013 Launch event – Building Services Compliance Guides

Aims

Domestic – Defining ‘new’ and ‘existing’New system means a fixed building services system installed:

a. in a new buildingb. for the first time in an existing buildingc. as a complete replacement for a system in an existing building.

1.7 Work on existing systems

A requirement of building regulations is that work on existing buildings should be carried out in such a way that when the work is complete:

a. the work itself complies with the applicable requirements of building regulationsb. the parts of the building not affected by the work are no more unsatisfactory in

relation to the requirements of the regulations than before the work was started.

This means that when a system component such as a boiler or a room thermostat is replaced, only the new component needs to comply with the standards in this guide (which in some cases may be lower than for new systems).

It is not a general requirement to upgrade the rest of the existing system, although this guide does include recommendations for minor upgrades where they would be cost-effective or may be needed to ensure efficient operation of the new component.

Part L 2013 Launch event – Building Services Compliance Guides

Domestic – Wet systems

New systems

New systems for gas-fired wet central heating in new and existing dwellings should meet the minimum standards for:

a. boiler efficiency, system circulation, hot water storage, system preparation and commissioning in Table 2

b. boiler interlock, zoning, and time and temperature control of the heating and hot water circuits in Table 3

c. pipework insulation in Table 5.

Existing systems

Components installed as replacements in existing systems should meet the same standards as for new systems, except where indicated otherwise in Table 4.

Table 4 in addition identifies good practice upgrades to the rest of the system (beyond the requirements of building regulations) when making planned and emergency replacements.

Part L 2013 Launch event – Building Services Compliance Guides

Part L 2013 Launch event – Building Services Compliance Guides

Domestic - Control of space heating

a. Space heating demand in each heating circuit should be determined by independent time control for that circuit, and either:i. a room thermostat or programmable room thermostat located in a

reference room served by that heating circuit; orii. individual networked radiator controls in each room on the circuit.

Part L 2013 Launch event – Building services compliance guides

Domestic – Zoning requirements

a. In dwellings with a total floor area4 up to 150 m2, zoning of space heating should be delivered by means of a single heating circuit with individual radiator controls such as thermostatic radiator valves (TRVs) on all radiators except those in the reference room.

b. In dwellings with a total floor area greater than 150 m2, zoning of space heating should be delivered by at least two heating circuits, each controlled as defined in row 2.0 above, together with individual radiator controls such as TRVs on all radiators except those in the reference rooms.

c. Unless the hot water is produced instantaneously, as by a combination boiler, the hot water circuit in all dwellings should be treated as a separate zone with independent time control

Part L 2013 Launch event – Building services compliance guides

Domestic - Community heating systems

All pipe-work should be insulated to prevent uncontrolled heat loss when passing through communal spaces that may otherwise suffer from overheating.

Part L 2013 Launch event – Building services compliance guides

Domestic - Mechanical ventilation systems

Part L 2013 Launch event – Building services compliance guides

c. comply with European Commission Regulation No 327/2011 implementing Directive 2009/125/EC with regard to ecodesignrequirements for fans driven by motors with an electrical input power between 125 W and 500 kW.

Supplementary information

GPG 268 ‘Energy efficient ventilation in dwellings – a guide for specifiers’, is a source of further information.

Part L 2013 Launch event – Building services compliance guides

Domestic – Heat pumps

Part L 2013 Launch event – Building services compliance guides

Domestic – Heat pumps

Part L 2013 Launch event – Building services compliance guides

Domestic – Heat pumps

Heat pumps – electrically driven

Coefficient of Performance (COP)New build Existing build

Air-to-air

Space heating ≤12 kW

SCOP 'D' rating for the median temperature range in EN 14825

All others

Space heating 2.5 at rating conditions in EN 14511

2.2 at rating conditions in EN 14511

Domestic hot water

2.0 at rating conditions in EN 14511

Domestic – Heat pumps

Part L 2013 Launch event – Building services compliance guides

Seasonal primary energy efficiency ratio (SPEER) is an emerging rating figure reflecting the use of primary energy for all types of heat pump, fossil fuel boiler and gas-driven cogeneration technologies, as well as hybrid systems where solar heating or a heat pump is backed up with electric heating or a fossil fuel boiler.

Energy labelling with the SPEER will be mandatory from 2015 under the Energy Labelling Directive. Testing and rating will be in accordance with EN 14825, as for SCOP.

c. comply with European Commission Regulation No 327/2011 implementing Directive 2009/125/EC with regard to ecodesign requirements for systems with a cooling capacity of less than 12 kW, and fans driven by motors with an electrical input power between 125 W and 500 kW.

Part L 2013 Launch event – Building services compliance guides

Domestic – Comfort cooling systems

Domestic - Circulators

In accordance with European Commission Regulation No 641/2009 implementing Directive 2005/32/EC with regard to ecodesign requirements for glandless circulators up to 2.5 kW:

From 1 January 2013, standalone glandless circulators, other than those specifically designed for primary circuits of thermal solar systems and of heat pumps, should have an Energy Efficiency Index (EEI) no greater than 0.27.

From 1 August 2015, standalone glandless circulators and glandless circulators integrated in products should have an Energy Efficiency Index (EEI) no greater than 0.23.

Part L 2013 Launch event – Building services compliance guides

Domestic - Lighting supplementary guidance

A single switch should normally operate no more than six light fittings with a maximum total load of 100 circuit-watts.

Part L 2013 Launch event – Building services compliance guides

Non-Domestic - Controls

Unless specified otherwise in this guide, it is recommended that, where appropriate, building services are provided with controls that as a minimum correspond to Band C in BS EN 15232:2007, ‘Energy performance of buildings – impact of building automation, controls and building management’

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Heating system efficiency boilers

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Heat pumps

Part L 2013 Launch event – Building services compliance guides

Heat pump units COP (Heat generator efficiency)

Air-to-air Space heating≤ 12 kW

SCOP 'D' rating for the median temperature range in EN 14825

All others except absorption and gas-engine

Space heating 2.5 (250%) at rating conditions in EN 14511

Domestic hot water

2.0 (200%) at rating conditions in EN 14511

Absorption 0.5 (50%) when operating at the rating conditions

Gas-engine 1.0 (100%) when operating at the rating conditions

Non-Domestic – Domestic hot water heaters

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Domestic hot water heaters

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Solar thermal systems

For solar systems with a cylinder capacity of less than 440 litres or collector surface area less than 20 sq metres, see the ‘Domestic building services compliance guide’

For larger systems, consult the CIBSE solar thermal design guide

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Comfort cooling

Small increases to full-load Energy Efficiency Ratios (EER)

ESEER is used for offices, ESEER being SEER with specified load profile weighting factors:

a = 0.03 (100%)b = 0.33 (75%)c = 0.41 (50%)d = 0.23 (25%)

Plant seasonal energy efficiency ratio (PSEER) value for multiple chillers may be calculated for use in SBEM

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Specific fan powers

Small decreases in specific fan power

An additional category for kitchen extract fans has been included

The specific fan power of air distribution systems at the design air flow rate should be no worse than in Table 35 for new and existing buildings. Specific fan power is a function of the system resistance that the fan has to overcome to provide the required flow rate. BS EN 13779 Table A8 provides guidance on system pressure drop. To minimise specific fan power it is recommended that the ‘low range’ is used as a design target.

Part L 2013 Launch event – Building services compliance guides

Non-Domestic - Lighting

Lighting in new and existing buildings should meet the recommended minimum standards for:

i. efficacy (averaged over the whole area of the applicable type of space in the building) and controls in Table 42; or

ii. the Lighting Energy Numerical Indicator (LENI) in Table 44 as calculated by the procedure described in Section 12.5

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Lighting option 1 minimum efficacy

Average initial efficacy increased from 55 to 60 luminaire lumens per circuit-watt

Additional control factors to reflect the greater range of available control systems

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – Lighting control factors

Part L 2013 Launch event – Building services compliance guides

Table 42: Recommended minimum lighting efficacy with controls in new and existing buildings

General lighting in office, industrial and storage spaces Initial luminaire lumens/circuit-watt

60

Controls Control factor

Reduced luminaire lumens/circuit-watt

a daylit space with photo-switching with or without override 0.90 54

b daylit space with photo-switching and dimming with or without override 0.85 51

c unoccupied space with auto on and off 0.90 54

d unoccupied space with manual on and auto off 0.85 51

e space not daylit, dimmed for constant illuminance 0.90 54

a + c 0.80 48

a + d 0.75 45

b + c 0.75 45

b + d 0.70 42

e + c 0.80 48

e + d 0.75 45

General lighting in other types of space The average initial efficacy should be not less than 60 lamp lumens per circuit-watt

Display lighting The average initial efficacy should be not less than 22 lamp lumens per circuit-watt

Non-Domestic – Lighting option 2 LENI not to exceed specific limit

Lighting Energy Numerical Indicator (LENI) is a measure of the performance of lighting in kWh/m2/year

Based on BS EN 15193 : 2007, ‘Energy performance of buildings’: LENI calculation takes account of lighting power; use of daylight, occupancy and illuminance controls; energy consumption of controls

LENI should not exceed lighting energy consumption limit specified in Table 44

Table 44 takes account of recommended illuminance values in BS EN 12464-1: 2011, ‘Light and lighting - Lighting of work places - Indoor work places’

Part L 2013 Launch event – Building services compliance guides

Non-Domestic – LENI limits

Part L 2013 Launch event – Building services compliance guides

Table 44: Recommended maximum lighting energy consumption (kWh) per sqm per year in new and existing buildings (lighting energy limit)

Hours Illuminance (lux) Display Lighting

Total Day Night 50 100 150 200 300 500 750 1000 Normal Shopwindow

1000 821 179 1.11 1.92 2.73 3.54 5.17 8.41 12.47 16.52 10.00

1500 1277 223 1.66 2.87 4.07 5.28 7.70 12.53 18.57 24.62 15.00

2000 1726 274 2.21 3.81 5.42 7.03 10.24 16.67 24.70 32.73 20.00

2500 2164 336 2.76 4.76 6.77 8.78 12.79 20.82 30.86 40.89 25.00

3000 2585 415 3.31 5.72 8.13 10.54 15.37 25.01 37.06 49.12 30.00

3700 3133 567 4.09 7.08 10.06 13.04 19.01 30.95 45.87 60.78 37.00

4400 3621 779 4.89 8.46 12.02 15.59 22.73 37.00 54.84 72.68 44.00 96.80

5400 4184 1216 6.05 10.47 14.90 19.33 28.18 45.89 68.03 90.17 54.00

6400 4547 1853 7.24 12.57 17.89 23.22 33.87 55.16 81.79 108.41 64.00

8760 4380 4380 10.26 17.89 25.53 33.16 48.43 78.96 117.12 155.29 87.60 192.72

Non-Domestic – Pumps and circulators

a. In accordance with European Commission Regulation No 641/2009 implementing Directive 2005/32/EC with regard to ecodesign requirements for glandless circulators up to 2.5kW:i. From 1 January 2013, standalone glandless circulators, other than

those specifically designed for primary circuits of thermal solar systems and of heat pumps, should have an Energy Efficiency Index (EEI) no greater than 0.27

ii. From 1 August 2015, standalone glandless circulators and glandless circulators integrated in products should have an Energy Efficiency Index (EEI) no greater than 0.23

b. Variable speed glandless circulators should be used on variable volume systems.

c. If a water pump is used on a closed loop circuit and the motor is rated at more than 750 W, then it should be fitted with or controlled by an appropriate variable speed controller on any variable volume system. On water pump booster sets with an open loop circuit, the static head should be checked before an appropriate variable speed controller is used.

Part L 2013 Launch event – Building services compliance guides

Thank you for your attendance.

The final versions of the Guides will be available from the DCLG website.

Part L 2013 Launch event – Building services compliance guides