Form No S3451-918Supersedes S3451-818Page 1 of 20
The Bard I-TEC Indoor Heat Pump system is designed for classrooms and other similar applications demanding high efficiency and the lowest possible sound levels that are practical and achievable, and also accommodates the over-the-window sill requirement for many replacement projects on older school buildings. The I-TEC Series meets that challenge with many innovative design features resulting in a highly refined appearance while at the same time improving on the very important maintenance and serviceability features needed by the facilities maintenance and service staffs.
I-TEC® I30H-I60H 2-Stage CompressorHigh Efficiency Air Source Heat Pumps
Four Ventilation Options:Both ERV and CRV have ECM motors, filter system, and positive shut-off.Energy Recovery Ventilator (ERV) is designed for both modulating or fixed supply and exhaust airflow operation depending upon environmental controls used, and has positive shutoff on intake and exhaust sides when unoccupied.• Modulating mode requires CO2 controller, has intake rate that is higher than exhaust, and has optional minimum CFM to address building IAQ requirements. The system modulates to maintain selected maximum CO2 level.• Fixed mode can be used with thermostat or DDC that has a dedicated Occupied output that is ON during Occupied and OFF during Unoccupied. Intake and exhaust rates can be independently adjusted.Commercial Room Ventilator (CRV Option M) is a fan powered ventilation package to manage intake & exhaust air at fixed rates but without energy recovery capability.• The rates are: 300-375-450-525 CFM, are independently selectable & has positive shutoff on intake and exhaust sides when unoccupied.• Requires control system that has a dedicated ventilation control output to be ON during Occupied and OFF during Unoccupied. CO2 controller with ON/OFF output relay can be used.• Factory setting is 375 CFM balanced to meet pressurization requirements of ASHRAE.Commercial Room Ventilator (CRV Option N) is same as CRV Option M and also has a free-cooling economizer mode that can provide up to 525 CFM when the outdoor ambient temperature is below the set point of the outdoor thermostat.
I-TEC Optional Features & Accessories
I-TEC Standard Features
Commercial Room Ventilator (CRV Option Q) is modulating design that requires 0-10Vdc control signal from CO2 controller.
Other Options: • Dehumidification (hot gas reheat) models • Low Ampacity Models available • Hot water coil packages, both Duct-Free and Ducted versions available.
Accessories: See Page 9 & 10.
• Units designed to be flush to a smooth interior wall and not require trim kits by use of adjustable wall sleeves; Trim Kits available where required • Low sound levels are achieved by numerous system design innovations including special acoustical insulation • Installation flexibility. Can be installed in corner applications with one side against a wall. • Condensate overflow detection system with diagnostics monitors equipment and shuts down compressor to prevent condensate overflow. • Freezestat on indoor coil safeguards against indoor coil freeze up by shutting down the compressor.
• Double wall construction, 20-ga. exterior skin, no visible fasteners • Non fiberglass insulation • Hinged, lockable, removable doors • Removable sides and modularized construction for transporting through standard doors or in elevators allows installation on second and third floor • Suitable for any floor installations • Can be installed in left or right corners with no modifications • Non-corrosive drainpans with no standing water • 2-Stage scroll compressors with discharge muffler, double floating isolation mounting system, and sound muffling cover • R-410A Green Refrigerant • Heating and cooling thermostatic expansion valves • Extra large full width control panel for easy access to all controls • Circuit Breakers on 230V models, and Toggle Disconnect on 460V • Evaporator coils constructed with hydrophilic fin stock with the following advantages: Acrylic coating Wettable surface with low contact angle – no bead-up condensate, lower wet-coil air-side pressure drop, improved draining & lower re-entrainment of moisture back into the air stream in continuous blower operating modes Antimicrobial properties provide microbial resistance to fungicidal growth Resistant to Mold and Mildew, ASTM D3273 – no growth Seals fin surface against aluminum oxide formation • 24VAC 75VA control transformer with circuit breaker • 24VAC low-voltage terminal strip for thermostat or DDC control • ECM indoor and outdoor motors • Modulating outdoor fan motor and low ambient control • Modulating indoor fan motor for constant CFM in different operating modes up to 0.50" ESP • High and Low Pressure switches with lockout circuit • Electronic heat pump control board with diagnostics • Liquid line filter/drier • Readily accessible service ports located behind locking hinged doors • Pleated 2" MERV 8 filter • Designed for over-the-window sill wall penetration and has 3" vertical adjustment for wall sleeve attachment
Cooling Capacities: 22,800 to 54,000 Btuh Heating Capacities: 19,800 to 54,000 Btuh
MIS-3741
MIS-3742
ERV
CRV
Form No S3451-918Supersedes S3451-818Page 2 of 20
Specifications - 4 and 5 Ton
Specifications - 2½ through 3½ Ton
MODELS I48H1-A I48H1-B I48H1-C I60H1-A I60H1-B I60H1-C
ELECTRICAL RATING--60 HZ 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 414-506 197-253 414-506
COMPRESSOR
Volts 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Rated Load Amps (230/208) 15.6/17.5 10.4/11.6 5.4 22/23.4 13.4/14.3 6.3
Branch Circuit Selection Current 19.9 11.6 6.4 27.2 16.6 7.2
Locked Rotor Amps 104.0 83.1 41 152.9 110.0 52.0
ENERGY RECOVERY VENTILATOR
Volts 230/208-60-1 230/208-60-1
Full Load Amps (3-motors) 2.2 2.2
FAN MOTOR – ECM
Horsepower 1/2 1/2
Volts 230/208-60-1 230/208-60-1
Full Load Amps 3.2 3.2
+ CFM 2600 2600
BLOWER MOTOR – ECM
Horsepower 1/2 3/4
Volts 230/208-60-1 230/208-60-1
Full Load Amps 3.2 4.4
+ CFM @ rating points, will modulate based upon O.D. ambient.
+ CFM @ rating points, will modulate based upon O.D. ambient.
• Complies with efficiency requirements of ANSI/ASHRAE/IESNA 90.1-2013.• Certified to ANSI/ARI Standard 390-2003 for SPVU (Single Package Vertical Units).• Intertek ETL Listed to Standard for Safety Heating and Cooling Equipment ANSI/UL 1995/CSA 22.2 No. 236-05, Fourth Edition.• Intertek ETL Listed to Standard for Gas-Fired Central Furnaces ANSI Z21.47-2006, CSA 2.3-2006 Fifth Edition, Addenda A dated 10-01-2007, Addenda B dated 06-01-2008.• Commercial Product - Not intended for Residential application.
Bard is anISO 9001:2015
Certified Manufacturer
MODELS I30H1-A I30H1-B I30H1-C I36H1-A I36H1-B I36H1-C I42H1-A I42H1-B I42H1-C
ELECTRICAL RATING--60 HZ 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Operating Voltage Range 197-253 414-506 197-253 414-506 197-253 414-506
COMPRESSOR
Volts 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3 230/208-1 230/208-3 460-3
Rated Load Amps (230/208) 10.0/11.5 7.4/8.4 4.2 11.1/13 8.5/9.9 4.9 13.8/15.6 11.0/12.4 5.5
Branch Circuit Selection Current 13.1 8.7 4.3 15.3 11.7 5.8 18.0 14.2 6.3
Locked Rotor Amps 73 58 28 83 73 38 96 88 44
ENERGY RECOVERY VENTILATOR
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps (3-motors) 2.2 2.2 2.2
FAN MOTOR – ECM
Horsepower 1/3 1/3 1/3
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps 1.7 2.6 2.6
+ CFM 1950 2300 2300
BLOWER MOTOR – ECM
Horsepower 1/3 1/2 1/2
Volts 230/208-60-1 230/208-60-1 230/208-60-1
Full Load Amps 1.9 2.5 2.5
Form No S3451-918Supersedes S3451-818Page 3 of 20
Capacity and Efficiency Ratings (Stage 1) Part Load Operation
EER = Energy Efficiency Ratio - BTU/WATT efficiency IPLV = Integrated Part Load Value - BTU/WATT efficiency (combines full and part load performance) COP = Coefficient of Performance - BTU/WATT efficiency
Motor will deliver consistent CFM through voltage supply range with no deterioration. Continous fan CFM is the total air being circulated during continuous fan mode. Will operate @ rated Full Load Airflow when operating with Heat Pump. Will occur automatically with a call for "W3" or "Emergency Heat" signal from thermostat (Heat Pump Operation is terminated @ this condition).
Capacity and Efficiency Ratings (Stage 2) Full Load Operation
Indoor Blower Performance
Unit Weights
Model RatedESP.
Max.ESP
Continuous
CFM
Rated2nd Stage
CFM
Rated1st Stage
CFM
4-10 KW
CFM
15-20 KW
CFM
I30H1 0.15 0.50 500 900 650 700 1050
I36H1 0.15 0.50 600 1150 850 700 1050
I42H1 0.20 0.50 650 1300 950 700 1050
I48H1 0.20 0.50 725 1500 1050 700 1400
I60H1 0.20 0.50 850 1700 1200 700 1400
Deduct 49# from all values for installed weight.
MODELS I30H1 I36H1 I42H1 I48H1 I60H1
Cooling BTUH, Full Load Capacity, 95-80/67 EER Rated CFM
27,80011.7900
35,00012.01150
41,50012.01300
47,00012.01500
54,00011.21700
IPLV (Integrated Full & Part Load) 80-80/67 15.4 16.5 15.7 16.1 15.5
Heating BTUH, Full Load Capacity 47/43-70 COP Rated CFM
26,6003.6900
32,8003.7
1150
38,5003.7
1300
44,5003.7
1500
54,0003.6
1700
MODELS I30H1 I36H1 I42H1 I48H1 I60H1
Cooling BTUH, Part Load Capacity, 80-80/67 EER Rated CFM
22,80015.4650
27,60016.6850
32,00016.15950
36,00016.21050
41,00014.551200
Heating BTUH, Part Load Capacity 47/43-70 COP Rated CFM
19,8003.5650
22,8003.6850
27,0003.6950
30,5003.6
1050
36,5003.4
1200
MODELS NO VENT CRV ERV
I30H1-A 816 908 943
I30H1-B 816 908 943
I30H1-C 851 943 978
I36H1-A 846 938 973
I36H1-B 846 938 973
I36H1-C 881 973 1008
I42H1-A 896 988 1023
I42H1-B 896 988 1023
I42H1-C 931 1023 1058
I48H1-A 884 976 1011
I48H1-B 884 976 1011
I48H1-C 919 1011 1046
I60H1-A 931 1023 1058
I60H1-B 931 1023 1058
I60H1-C 966 1058 1093
MODELS NO VENT CRV ERV
I30H1DA 830 920 955
I30H1DB 830 920 955
I30H1DC 865 955 990
I36H1DA 858 950 985
I36H1DB 858 950 985
I36H1DC 893 985 1020
I42H1DA 908 1000 1035
I42H1DB 908 1000 1035
I42H1DC 943 1035 1070
I48H1DA 930 1022 1057
I48H1DB 930 1022 1057
I48H1DC 965 1057 1092
I60H1DA 943 1035 1070
I60H1DB 943 1035 1070
I60H1DC 978 1070 1105
Form No S3451-918Supersedes S3451-818Page 4 of 20
Hot Water Coil Correction FactorsEntering Air Temp
(F)
Entering Water Temperature (F)
100 110 120 130 140 150 160 170 180 190 200
50 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091 1.182 1.273 1.364
55 0.409 0.500 0.591 0.682 0.773 0.864 0.955 1.045 1.136 1.227 1.318
60 0.363 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091 1.182 1.273
65 0.318 0.409 0.500 0.591 0.682 0.773 0.864 0.955 1.045 1.136 1.227
70 0.272 0.363 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091 1.182
75 0.227 0.318 0.409 0.500 0.591 0.682 0.773 0.864 0.955 1.045 1.136
80 0.182 0.272 0.363 0.455 0.545 0.636 0.727 0.818 0.909 1.000 1.091
GPMCFM
800 900 1000 1100 1200 1300 1400 1500 1600 1700
1.5 32,000 32,667 33,333 34,000 34,500 35,000 35,500 36,000 36,400 36,750
2 42,000 43,200 44,400 45,600 46,400 47,200 48,000 48,500 49,000 49,500
3 49,000 51,667 53,750 57,000 59,400 61,750 64,000 65,200 66,000 67,000
4 56,000 59,000 62,000 65,000 69,000 73,000 77,000 79,500 82,000 84,000
5 59,000 62,583 66,167 69,750 72,833 75,917 79,000 81,000 83,000 85,000
6 62,000 66,167 70,333 74,500 77,000 79,500 82,000 83,500 85,000 86,500
7 63,500 67,708 71,917 76,125 78,917 81,708 84,500 86,500 88,000 89,200
8 65,000 69,250 73,500 77,750 80,833 83,917 87,000 88,900 90,500 91,750
9 66,000 70,525 75,050 79,575 82,883 86,192 89,500 91,500 93,000 94,500
10 67,000 71,800 76,600 81,400 84,933 88,467 92,000 94,500 96,000 97,500
Factory Built-in Electric Heat Table
Model Voltage PhaseKW Amps BTUH
240 208 240 208 240 208
-A04 240/208 1 4 3 16.7 14.4 13,652 10,239
-A05 240/208 1 5.00 3.75 20.8 18.0 17,065 12,799
-A10 240/208 1 10.00 7.50 41.7 36.1 34,130 25,598
-A15 240/208 1 15.00 11.25 62.5 54.1 51,195 38,396
-A20 240/208 1 20.00 15.00 83.3 72.1 68,260 51,195
-B06 240/208 3 6.00 4.50 14.4 12.5 20,478 15,359
-B09 240/208 3 9.00 6.75 21.7 18.7 30,717 23,038
-B15 240/208 3 15.00 11.25 36.1 31.2 51,195 38,396
-B18 240/208 3 18.00 13.50 43.3 37.5 61,434 46,076
NOTE: Not all KW's available in all models. See Minimum Circuit Ampacity and Maximum Overcurrent Protection table on following page.
Optional IHWC Hot Water Coil Performance
Model Voltage PhaseKW Amps BTUH
480V 460V 480V 460V 480V 460V
-C06 480 3 6.00 5.52 7.2 6.9 20,478 18,840
-C09 480 3 9.00 8.28 10.8 10.4 30,717 28,260
-C15 480 3 15.00 13.80 18.0 17.3 51,195 47,099
-C18 480 3 18.00 16.56 21.7 20.8 61,434 56,519
Form No S3451-918Supersedes S3451-818Page 5 of 20
These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing.Caution: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.Maximum size of the time delay fuse or HVAC type circuit breaker for protection of field wiring conductors.Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.Maximum KW that can operate with the heat pump is 10KW for 1-Phase and 9KW for 3-Phase. Represents Electric Heat only. Electric Control Circuit will lock-out Heat Pump Operation.
Minimum Circuit Ampacity & Maximum Overcurrent Protection – Std. & Dehum.
MODEL
Rated Volts,
Hertz & Phase
Single Circuit Dual Circuit
No. Field Power
Circuits
Minimum Circuit
Ampacity
Maximum External Fuse or
Ckt. Brkr.
Field Power
Wire Size
Ground Wire
Minimum Circuit
Ampacity
MaximumExternal
Fuse or Ckt. Breaker
Field Power Wire Size
Ground Wire Size
Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B
I30H1-A0ZA05A10
230/208-111
1 or 2
224874
355080
884
10108 48 30 50 30 8 10 10 10
I30H1-B0ZB06B09
230/208-3111
173544
253545
1088
101010
I30H1-C0ZC06C09
460-3111
91822
102025
141210
141210
I36H1-A0ZA05A10
A15
230/208-1
11
1 or 21 or 2
26527884
40608090
8644
101088
2626
5252
4040
6060
88
66
1010
1010
I36H1-B0ZB06B09
B15
230/208-3
1111
22404951
30455060
10886
10101010
I36H1-C0ZC06C09
C15
460-3
1111
11202428
15202530
14121010
14121010
I42H1-A0ZA05A10
A15
230/208-1
11
1 or 21 or 2
30568282
45609090
8644
101088
5656
2652
6060
3060
66
86
1010
1010
I42H1-B0ZB06B09
B15
230/208-3
1111
25435252
35506060
10866
10101010
I42H1-C0ZC06C09
C15
460-3
1111
12212628
15253030
14101010
14101010
I48H1-A0ZA04A05A10
A15 A20
230/208-1
11
1 or 21 or 21 or 21 or 2
3454598585
110
5060709090
110
866332
10108886
35353559
26525252
45454560
30606060
8886
10666
10101010
10101010
I48H1-B0ZB06B09
B15 B18
230/208-3
11111
2644535353
3550606060
108666
1010101010
I48H1-C0ZC06C09
C15 C18
460-3
11111
1221262626
1530303030
1410101010
1410101010
I60H1-A0ZA05A10
A15 A20
230/208-1
11 or 21 or 21 or 21 or 2
44709696
112
6080
100100120
84332
108886
44444460
26525252
60606060
30606060
8886
10666
10101010
10101010
I60H1-B0ZB06B09
B15 B18
230/208-3
11112
31495858–
45606060–
8866–
10101010– 31 54 45 60 8 6 10 10
I60H1-C0ZC06C09
C15 C18
460-3
11111
1525292929
2030303030
1210101010
1210101010
Form No S3451-918Supersedes S3451-818Page 6 of 20
Model D.B. / W.B.
COOLING CAPACITY 60°F 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
I30H1
75/62Total CoolingSensible Cooling
30,76423,517
30,05623,129
29,34922,741
28,64122,352
27,93421,964
27,22621,575
26,51921,187
25,81220,799
24,97620,596
24,14020,393
23,30520,191
22,46919,988
21,63319,785
20,79819,583
80/67Total CoolingSensible Cooling
33,48823,981
32,67523,488
31,86322,994
31,05022,500
30,20022,000
29,38821,506
28,61321,019
27,80020,525
26,90020,325
26,00020,125
25,10019,925
24,20019,725
23,30019,525
22,40019,325
85/72Total CoolingSensible Cooling
35,99023,806
35,37223,272
34,75422,738
34,13622,204
33,51821,671
32,90021,137
32,28220,603
31,66420,069
30,63919,873
29,61419,678
28,58919,482
27,56419,287
26,53919,091
25,51418,896
I36H1
75/62Total CoolingSensible Cooling
39,01330,182
38,16129,782
37,31029,383
36,45928,983
35,60828,584
34,75628,184
33,90527,785
33,05427,385
31,80026,853
30,54726,321
29,29325,789
28,04025,257
26,78724,725
25,53324,193
80/67Total CoolingSensible Cooling
42,46930,788
41,48830,250
40,50629,713
39,52529,175
38,50028,600
37,51928,063
36,58127,563
35,00027,025
34,25026,500
32,90025,975
31,55025,450
30,20024,925
28,85024,400
27,50023,875
85/72Total CoolingSensible Cooling
45,63230,567
44,90629,975
44,18029,384
43,45428,792
42,72728,200
42,00127,608
41,27527,016
40,54826,424
39,01125,911
37,47325,398
35,93524,884
34,39824,371
32,86023,858
31,32323,344
I42H1
75/62Total CoolingSensible Cooling
46,86535,042
45,74034,686
44,61634,331
43,49233,975
42,36833,620
41,24433,264
40,12032,909
38,99632,553
38,00632,198
37,01531,843
36,02531,488
35,03531,133
34,04530,778
33,05430,423
80/67Total CoolingSensible Cooling
51,01335,756
49,72535,238
48,43834,719
47,15034,200
44,50032,675
43,21332,156
43,28832,644
41,50032,125
40,93331,775
39,86731,424
38,80031,074
37,73430,723
36,66730,373
35,60130,022
85/72Total CoolingSensible Cooling
54,83535,505
53,83634,921
52,83634,336
51,83633,751
50,83733,166
49,83732,581
48,83831,996
47,83831,411
46,62331,068
45,40830,726
44,19430,383
42,97930,040
41,76429,698
40,54929,355
I48H1
75/62Total CoolingSensible Cooling
51,84339,521
50,51238,811
49,18038,101
47,84937,391
46,51736,681
45,18535,971
43,85435,261
42,52234,551
40,91033,856
39,29933,161
37,68732,466
36,07631,771
34,46431,076
32,85230,381
80/67Total CoolingSensible Cooling
56,91338,814
55,49738,219
54,08137,624
52,66437,029
51,00035,950
49,58435,355
48,41635,245
47,00034,650
45,21933,953
43,43733,256
41,65632,559
39,87531,862
38,09331,165
36,31230,467
85/72Total CoolingSensible Cooling
54,00838,517
53,71237,839
53,41637,162
53,12036,484
52,82335,806
52,52735,129
52,23134,451
50,40833,795
48,58533,138
46,76132,482
44,93831,825
43,11531,169
41,29230,513
39,46929,856
I60H1
75/62Total CoolingSensible Cooling
61,06245,691
59,31844,741
57,57543,790
55,83142,840
54,08741,890
52,34340,939
50,59939,989
48,85539,039
47,36638,482
45,87737,926
44,38737,370
42,89836,813
41,40936,257
39,91935,701
80/67Total CoolingSensible Cooling
67,03844,881
65,17544,063
63,31343,244
61,45042,425
59,58841,606
57,72540,788
55,86339,969
54,00039,150
52,35438,592
50,70838,034
49,06237,476
47,41536,918
45,76936,360
44,12335,802
85/72Total CoolingSensible Cooling
72,83444,530
70,73943,620
68,64442,710
66,55041,800
64,45540,890
62,36039,980
60,26539,070
58,17038,160
56,39737,616
54,62437,072
52,85136,528
51,07735,985
49,30435,441
47,53134,897
Model D.B. / W.B. k
COOLING CAPACITY 60°F 65°F 70°F 75°F 80°F 85°F 90°F 95°F 100°F 105°F 110°F 115°F 120°F 125°F
I30H1
75/62Total CoolingSensible Cooling
24,11118,256
23,36317,908
22,61517,561
21,86817,214
21,12016,866
20,37216,519
19,62516,172
18,87715,825
18,21215,526
17,54815,227
16,88414,929
16,21914,630
15,55514,332
14,89114,033
80/67Total CoolingSensible Cooling
26,02518,000
25,25017,700
24,47517,400
23,70017,100
22,80016,675
22,02516,375
21,37516,200
22,80015,900
19,87515,600
19,15015,300
18,42515,000
17,70014,700
16,97514,400
16,25014,100
85/72Total CoolingSensible Cooling
27,26717,242
26,72917,056
26,19016,869
25,65216,683
25,11316,497
24,57516,310
24,03716,124
23,49815,938
22,67115,637
21,84415,336
21,01715,036
20,19014,735
19,36314,434
18,53614,133
I36H1
75/62Total CoolingSensible Cooling
29,64523,790
28,68323,242
27,72022,694
26,75822,146
25,79621,599
24,83321,051
23,87120,503
22,90919,955
22,23319,743
21,55719,532
20,88119,321
20,20619,109
19,53018,898
18,85418,686
80/67Total CoolingSensible Cooling
32,00023,463
31,00022,975
30,00022,488
29,00022,000
27,60021,175
26,60020,688
26,00020,538
27,60020,050
24,26319,838
23,52519,625
22,78819,413
22,05019,200
21,31318,988
20,57518,775
85/72Total CoolingSensible Cooling
33,54222,488
32,82422,146
32,10621,805
31,38821,463
30,67021,122
29,95320,780
29,23520,439
28,51720,098
27,67619,885
26,83519,672
25,99319,459
25,15219,246
24,31119,033
23,47018,819
I42H1
75/62Total CoolingSensible Cooling
30,06425,169
29,63124,766
29,19824,362
28,76523,958
28,33223,555
27,89923,151
27,46522,747
27,03222,344
26,09122,055
25,15021,767
24,20921,479
23,26821,191
22,32720,903
21,38620,615
80/67Total CoolingSensible Cooling
32,43124,813
32,01324,475
31,59424,138
31,17523,800
32,00023,600
31,58123,263
29,91922,788
32,00022,450
28,47322,160
27,44621,871
26,41921,581
25,39221,292
24,36521,002
23,33820,713
85/72Total CoolingSensible Cooling
33,81123,757
33,78823,578
33,76523,399
33,74223,220
33,71923,040
33,69622,861
33,67322,682
33,65022,503
32,47922,213
31,30721,923
30,13621,633
28,96421,342
27,79321,052
26,62220,762
I48H1
75/62Total CoolingSensible Cooling
36,48927,440
35,47726,922
34,46526,404
33,45325,886
32,44125,369
31,42924,851
30,41724,333
29,40523,815
28,40423,512
27,40323,210
26,40222,907
25,40122,604
24,40022,302
23,39921,999
80/67Total CoolingSensible Cooling
40,38027,189
39,25526,712
38,12926,234
37,00325,756
36,00025,241
34,87424,763
33,62624,323
32,50023,845
31,39423,542
30,28823,239
29,18122,936
28,07522,633
26,96922,330
25,86322,027
85/72Total CoolingSensible Cooling
37,19426,876
36,98726,403
36,78025,930
36,57325,457
36,36624,984
36,15924,511
35,95224,038
35,74523,565
34,52923,265
33,31222,966
32,09522,666
30,87922,367
29,66222,067
28,44521,768
I60H1
75/62Total CoolingSensible Cooling
42,80531,549
41,47230,890
40,13930,232
38,80729,574
37,47428,916
36,14228,258
34,80927,599
33,47626,941
32,48726,585
31,49726,230
30,50825,874
29,51825,518
28,52825,162
27,53924,806
80/67Total CoolingSensible Cooling
47,36931,263
45,88830,650
44,40630,038
42,92529,425
41,00028,500
39,51927,888
38,48127,588
41,00026,975
35,90626,619
34,81326,263
33,71925,906
32,62525,550
31,53125,194
30,43824,838
85/72Total CoolingSensible Cooling
51,94130,902
50,33430,296
48,72829,690
47,12129,083
45,51528,477
43,90827,870
42,30127,264
40,69526,658
39,49226,306
38,28925,954
37,08625,602
35,88325,250
34,68024,897
33,47724,545
Below 50°F, unit requires a factory or field installed low ambient control. Return air temp. °F Rated CFM.
Cooling Part Load Application Data
Cooling Full Load Application Data
Form No S3451-918Supersedes S3451-818Page 7 of 20
Heating Full Load Application Data
Heating Part Load Application Data
70°F DB indoor return air at rated CFM includes defrost operation below 45°.
70°F DB indoor return air at rated CFM includes defrost operation below 45°.
Unit Charge Rates
UNIT Std. Unit - Lbs.
Dehum. Units - Lbs.
I30H1 - High Efficiency Step Capacity Indoor HP
7.75 8.6250
I36H1 - High Efficiency Step Capacity Indoor HP
10.5625 10.9375
I42H1 - High Efficiency Step Capacity Indoor HP
10.75 11.1875
I48H1 - High Efficiency Step Capacity Indoor HP
12.9375 13.8125
I60H1 - High Efficiency Step Capacity Indoor HP
12.875 13.3125
Model Indoor 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F
I30H1
70°F
BTUHWATTS
COP
10,66318791.66
12,52519061.93
14,38819272.19
16,25019432.45
18,11319562.71
19,97519672.98
21,83819763.24
23,7001984
3.5
25,00020463.58
26,30021053.66
28,06021823.77
29,82022543.88
31,58023233.98
I36H1BTUH
WATTSCOP
12,81918042.08
14,78819392.24
16,75620562.39
18,72521602.54
20,69422522.69
22,66323342.85
24,63124083.00
26,60024743.15
29,40024613.50
32,20024513.85
34,20025113.99
36,20025684.13
38,20026214.27
I42H1BTUH
WATTSCOP
21,13826642.33
22,27526642.45
23,41326642.58
24,55026642.70
25,68826642.83
26,82526642.95
27,96326643.08
29,1002664
3.2
33,65027773.55
38,20028703.90
40,20029234.03
42,20029724.16
44,20030194.29
I48H1BTUH
WATTSCOP
19,80624332.39
22,51326602.48
25,21928702.58
27,92530642.67
30,63132462.77
33,33834152.86
36,04435742.96
38,75037233.05
41,26335353.42
43,77533843.79
46,82034893.93
49,86535864.07
52,91036774.22
I60H1BTUH
WATTSCOP
30,46940122.23
31,68839512.35
32,90638962.48
34,1253846
2.6
35,344 38002.73
36,563 37592.85
37,781 37212.98
39,000 3686
3.1
46,050 40583.33
53,10043833.55
56,60045063.68
60,10046223.81
63,60047303.94
Model Indoor 0° 5° 10° 15° 20° 25° 30° 35° 40° 45° 50° 55° 60°F
I30H1
70°F
BTUHWATTS
COP
6,55015201.26
8,10015561.53
9,65015821.79
11,20016012.05
12,75016152.31
14,30016272.58
15,85016372.84
17,40016453.10
18,50016603.27
19,60016743.43
21,12017173.60
22,64017563.78
24,16017913.95
I36H1BTUH
WATTSCOP
8,98116001.65
10,31316691.81
11,64417271.98
12,97517762.14
14,30618192.31
15,63818552.47
16,96918872.64
18,30019152.80
20,30018913.15
22,30018723.49
24,06018693.77
25,82018664.05
27,58018644.34
I42H1BTUH
WATTSCOP
10,16919851.50
11,88820221.72
13,60620511.94
15,32520742.17
17,04420932.39
18,76321082.61
20,48121212.83
22,20021333.05
24,27521723.28
26,3502206
3.5
28,11021903.76
29,87021774.02
31,63021654.28
I48H1BTUH
WATTSCOP
12,58823231.59
14,47523891.78
16,36324431.96
18,25024872.15
20,13825242.34
22,02525562.53
23,91325832.71
25,8002607
2.9
27,70025243.22
29,600 2,457
3.53
32,05025183.73
34,50025723.93
36,95026214.13
I60H1BTUH
WATTSCOP
12,61321331.73
15,22523671.89
17,83825652.04
20,45027362.19
23,06328852.34
25,67530152.50
28,28831312.65
30,90032332.80
33,13831473.09
35,37530763.37
38,17032013.49
40,96533173.62
43,76034263.74
Form No S3451-918Supersedes S3451-818Page 8 of 20
Performance and Application Data – Energy Recovery Vent Option "R"
LEGEND:
VLT = Ventilation Load - TotalVLS = Ventilation Load - SensibleVLL = Ventilation Load - LatentHRT = Heat Recovery - TotalHRS = Heat Recovery - SensibleHRL = Heat Recovery - LatentWVL = Winter Ventilation LoadWHR = Winter Heat Recovery
SUMMER COOLING PERFORMANCE(INDOOR DESIGN CONDITIONS 75°DB/62°WB)
AmbientO.D.
VENTILATION RATE 450 CFM65% EFFICIENCY
VENTILATION RATE 375 CFM66% EFFICIENCY
VENTILATION RATE 300 CFM67% EFFICIENCY
DB/WB F VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL VLT VLS VLL HRT HRS HRL
105
75 21465 14580 6884 13952 9477 4475 17887 12150 5737 11805 8018 3786 14310 9720 4590 9587 6512 3075
70 14580 14580 0 9477 9477 0 12150 12150 0 8018 8018 0 9720 9720 0 6512 6512 0
65 14580 14580 0 9477 9477 0 12150 12150 0 8018 8018 0 9720 9720 0 6512 6512 0
100
80 31590 12150 19440 20533 7897 12635 26325 10125 16200 17374 6682 10692 21060 8100 12960 14110 5427 8683
75 21465 12150 9314 13952 7897 6054 17887 10125 7762 11805 6682 5123 14310 8100 6210 9587 5427 4160
70 12352 12150 202 8029 7897 131 10293 10125 168 6793 6682 111 8235 8100 135 5517 5427 90
65 12150 12150 0 7897 7897 0 10125 10125 0 6682 6682 0 8100 8100 0 5427 5427 0
60 12150 12150 0 7897 7897 0 10125 10125 0 6682 6682 0 8100 8100 0 5427 5427 0
95
80 31590 9720 21870 20533 6318 14215 26325 8100 18225 17374 5345 12028 21060 6480 14580 14110 4341 9768
75 21465 9720 11744 13952 6318 7634 17887 8100 9787 11805 5345 6459 14310 6480 7830 9587 4341 5246
70 12352 9720 2632 8029 6318 1711 10293 8100 2193 6793 5345 1447 8235 6480 1755 5517 4341 1175
65 9720 9720 0 6318 6318 0 8100 8100 0 5345 5345 0 6480 6480 0 4341 4341 0
60 9720 9720 0 6318 6318 0 8100 8100 0 5345 5345 0 6480 6480 0 4341 4341 0
90
80 31590 7290 24300 20533 4738 15794 26325 6075 20250 17374 4009 13365 21060 4860 16200 14110 3256 10854
75 21465 7290 14175 13952 4738 9213 17887 6075 11812 11805 4009 7796 14310 4860 9450 9587 3256 6331
70 12352 7290 5062 8029 4738 3290 10293 6075 4218 6793 4009 2784 8235 4860 3375 5517 3256 2261
65 7290 7290 0 4738 4738 0 6075 6075 0 4009 4009 0 4860 4860 0 3256 3256 0
60 7290 7290 0 4738 4738 0 6075 6075 0 4009 4009 0 4860 4860 0 3256 3256 0
85
80 31590 4860 26730 20533 3159 17374 26325 4050 22275 17374 2672 14701 21060 3240 17820 14110 2170 11939
75 21465 4860 16605 13952 3159 10793 17887 4050 13837 11805 2672 9132 14310 3240 11070 9587 2170 7416
70 12352 4860 7492 8029 3159 4870 10293 4050 6243 6793 2672 4120 8235 3240 4995 5517 2170 3346
65 4860 4860 0 3159 3159 0 4050 4050 0 2672 2672 0 3240 3240 0 2170 2170 0
60 4860 4860 0 3159 3159 0 4050 4050 0 2672 2672 0 3240 3240 0 2170 2170 0
80
75 21465 2430 19035 13952 1579 12372 17887 2025 15862 11805 1336 10469 14310 1620 12690 9587 1085 8502
70 12352 2430 9922 8029 1579 6449 10293 2025 8268 6793 1336 5457 8235 1620 6615 5517 1085 4432
65 4252 2430 1822 2764 1579 1184 3543 2025 1518 2338 1336 1002 2835 1620 1215 1899 1085 814
60 2430 2430 0 1579 1579 0 2025 2025 0 1336 1336 0 1620 1620 0 1085 1085 0
75
70 12352 0 12352 8029 0 8029 10293 0 10293 6793 0 6793 8235 0 8235 5517 0 5517
65 4252 0 4252 2764 0 2764 3543 0 3543 2338 0 2338 2835 0 2835 1899 0 1899
60 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
WINTER HEATING PERFORMANCE(INDOOR DESIGN CONDITIONS 70°F DB)
AmbientO.D.
VENTILATION RATE
450 CFM80% EFFICIENCY
375 CFM81% EFFICIENCY
300 CFM82% EFFICIENCY
DB/°F WVL WHR WVL WHR WVL WHR
65 2430 1944 2025 1640 1620 1328
60 4860 3888 4050 3280 3240 2656
55 7290 5832 6075 4920 4860 3985
50 9720 7776 8100 6561 6480 5313
45 12150 9720 10125 8201 8100 6642
40 14580 11664 12150 9841 9720 7970
35 17010 13608 14175 11481 11340 9298
30 19440 15552 16200 13122 12960 10627
25 21870 17496 18225 14762 14580 11955
20 24300 19440 20250 16402 16200 13284
15 26730 21384 22275 18042 17820 14612
NOTE: Sensible performance only is shown for winter application.
Form No S3451-918Supersedes S3451-818Page 9 of 20
I-TEC Accessory Model Numbers
Above table based on I-TEC unit being installed flush to inside of wall. 8" Depth Storm Louvers are field supplied
Available Special Order and requires additional lead-time. Reference Form S3508 for additional details.• Custom Finishes are quoted on a project-by-project basis and pricing is determined by quantity, finish option and size.• Custom Finishes are ordered/shipped directly from the louver supplier.• Purchaser of Custom Finishes assumes liability for quantity, finish match and size.• Contact your Bard Sales Representative for custom louver contact information.
Wall Sleeves (Required Option - Select One)
Model # Description Total Depth of Wall System When Used with 1" Louver
Total Depth of Wall System When Used with 2" Louver
IWS-A Wall Sleeve Adjustable 5.5 to 8.5" 6.5 to 8.5"
IWS-B Wall Sleeve Adjustable 8.0 to 13.5" 9.0 to 13.5"
IWS-C Wall Sleeve Adjustable 13.0 to 23.5" 14.0 to 23.5"
Model # Description Total Depth of Wall System When Used with 4" Louver
Total Depth of Wall System When Used with 8" Louver
IWS-A8H Wall Sleeve Adjustable 8.0 to 12.0" —
IWS-B8H Wall Sleeve Adjustable 12.0 to 20.0" 12.0 to 15.0"
IWS-C8H Wall Sleeve Adjustable — 15.0 to 20.5"
Outdoor Louver Grilles (Required Option - Select One)
Model # Description Color Sleeve (Required)
ILS1-10 1" Standard Anodized Aluminum IWS-A, -B, -C
ILS1-20 1" Standard Aluminum with Medium Bronze Finish IWS-A, -B, -C
ILS1-30 1" Standard Aluminum with Dark Bronze Finish IWS-A, -B, -C
ILS1-** 1" Standard Aluminum with Custom Finish IWS-A, -B, -C
ILA2-10 2" Architectural Anodized Aluminum IWS-A, -B, -C
ILA2-20 2" Architectural Aluminum with Medium Bronze Finish IWS-A, -B, -C
ILA2-30 2" Architectural Aluminum with Dark Bronze Finish IWS-A, -B, -C
ILA2-** 2" Architectural Aluminum with Custom Finish IWS-A, -B, -C
ILST4-10 4" Storm Anodized Aluminum IWS-AH, -BH, -CH
ILST4-20 4" Storm Aluminum with Medium Bronze Finish IWS-AH, -BH, -CH
ILST4-30 4" Storm Aluminum with Dark Bronze Finish IWS-AH, -BH, -CH
ILST4-** 4" Storm Aluminum with Custom Finish IWS-AH, -BH, -CH
Additional Louver Colors Available — Applies to ILS, ILA and ILST Louvers
-12 Arctic White
-14 Storm White
-18 Milano Beige
-32 Jet Black
-36 Graphite Gray
-40 School Bus Yellow
-42 Florida Orange
-44 School House Red
-46 Chili Red
-50 Deep Sea Blue
-52 Bahama Blue
-54 Ivy Green
-56 Sage Green
Form No S3451-918Supersedes S3451-818Page 10 of 20
Duct-Free Plenum BoxesModel #: Description:IPBDFH18-X 18" Duct Free Plenum – Beige. Black linear slot grilles, side w/shutoff damperIPBDFH18-1 18" Duct Free Plenum – White. Black linear slot grilles, side w/shutoff damperIPBDFH18-4 18" Duct Free Plenum – Gray. Black linear slot grilles, side w/shutoff damperIPBDFH12-X 12" Duct Free Plenum – Beige. Black linear slot grilles, side w/shutoff damperIPBDFH12-1 12" Duct Free Plenum – White. Black linear slot grilles, side w/shutoff damperIPBDFH12-4 12" Duct Free Plenum – Gray. Black linear slot grilles, side w/shutoff damperIPBDF18-X 18" Duct Free Plenum – Beige. (2) Anodized dual deflection front & side grillesIPBDF18-1 18" Duct Free Plenum – White. (2) Anodized dual deflection front & side grillesIPBDF18-4 18" Duct Free Plenum – Gray. (2) Anodized dual deflection front & side grillesIPBDF12-X 12" Duct Free Plenum – Beige. (2) Anodized dual deflection front & side grillesIPBDF12-1 12" Duct Free Plenum – White. (2) Anodized dual deflection front & side grillesIPBDF12-4 12" Duct Free Plenum – Gray. (2) Anodized dual deflection front & side grillesIPBDF8-X 8" Duct Free Plenum – Beige. Anodized dual deflection front & side grillesIPBDF8-1 8" Duct Free Plenum – White. Anodized dual deflection front & side grillesIPBDF8-4 8" Duct Free Plenum – Gray. Anodized dual deflection front & side grilles
Duct-Free Plenum Boxes with Hot Water CoilModel #: Description:IPBDF12HW-X 12" Duct Free Plenum–Beige. Anodized dual deflection front & side grilles, w/hot water coilIPBDF12HW-1 12" Duct Free Plenum–White. Anodized dual deflection front & side grilles, w/hot water coilIPBDF12HW-4 12" Duct Free Plenum–Gray. Anodized dual deflection front & side grilles, w/hot water coilNOTE: No water control valves included. Field-Installed.
Hot Water Coil with Duct ConnectionModel #: Description:IHWC Hot water coil assembly, mounts on top of I-TEC unit, 10" x 30" duct flangeNOTE: No water control valves included. Field-Installed.
NOTE: Order appropriate Cabinet Extension (Model ICX28-*) to enclose hot water coil assembly, valves, piping and ductwork.
Hot Water Coil Valves Model #: Description:5650-035 On/Off Water Valve, 3 way 3/4" 24V5650-047 Modulating Water Valve, 3 way 3/4" 24V
Cabinet ExtensionsModel #: Description:ICX28-X 28" extension for ceilings up to 10'2", beige paintICX28-1 28" extension for ceilings up to 10'2", white paint
ICX28-4 28" extension for ceilings up tp 10'2", gray paint
I-TEC Accessories — Optional per Job Requirement
Riser PlatformsModel #: Description: Model #: Description:IRP-3-X Riser platform 3" with trim kit, beige paint IRP-11-X Riser platform 11" with trim kit, beige paintIRP-3-1 Riser platform 3" with trim kit, white paint IRP-11-1 Riser platform 11" with trim kit, white paintIRP-3-4 Riser platform 3" with trim kit, gray paint IRP-11-4 Riser platfrom 11" with trim kit, gray paintIRP-6-X Riser platform 6" with trim kit, beige paint IRP-14-X Riser platform 14" with trim kit, beige paintIRP-6-1 Riser platform 6" with trim kit, white paint IRP-14-1 Riser platform 14" with trim kit, white paintIRP-6-4 Riser platform 6" with trim kit, gray paint IRP-14-4 Riser platform 14" with trim kit, gray paintIRP-9-X Riser platform 9" with trim kit, beige paintIRP-9-1 Riser platform 9" with trim kit, white paintIRP-9-4 Riser platform 9" with trim kit, gray paint
NOTE: Use of Riser Platforms will increase maximum ceiling height by riser height.
Form No S3451-918Supersedes S3451-818Page 11 of 20
Wall CurbsModel #: Description:ICURB740 7" Deep Curb to allow sleeve installation with a 40" window sill height
Side Trim KitsModel #: Description:IST4-X 4" Side Trim Kit, beige paint, adaptable for ceilings up to 12'IST4-1 4" Side Trim Kit, white paint, adaptable for ceilings up to 12'IST4-4 4" Side Trim Kit, gray paint, adaptable for ceilings up to 12'IST4L-X 4" Side Trim Kit, beige paint, adaptable for ceilings up to 12' 10"IST4L-1 4" Side Trim Kit, beige paint, adaptable for ceilings up to 12' 10"IST4L-4 4" Side Trim Kit, beige paint, adaptable for ceilings up to 12' 10"IST6-X 6" Side Trim Kit, beige paint, adaptable for ceilings up to 12'IST6-1 6" Side Trim Kit, white paint, adaptable for ceilings up to 12'IST6-4 6" Side Trim Kit, gray paint, adaptable for ceilings up to 12'IST10-X 10" Side Trim Kit, beige paint, adaptable for ceilings up to 12'IST10-1 10" Side Trim Kit, beige paint, adaptable for ceilings up to 12'IST10-4 10" Side Trim Kit, beige paint, adaptable for ceilings up to 12'
Other Optional AccessoriesModel #: Description:AHCK-2A Anti-Huffing Refrigerant Caps (Quantity 2) with KeySK111 Hard Start Kit for 1-Phase Models (I30H1-A, I36H1-A & I42H1-A) OnlySK118 Hard Start Kit for 1-Phase Models (I48H1-A & I60H1-A) Only
I-TEC Accessories — Optional per Job Requirement
Form No S3451-918Supersedes S3451-818Page 12 of 20
This page intentionally left blank.
Form No S3451-918Supersedes S3451-818Page 13 of 20
33 4"
241 2"
221 4"
Lowe
rSe
ction
713 4"
Uppe
rSe
ction
Slee
veInn
er
Retur
n
Slee
veOu
ter
Slee
veInn
er
Air
Retur
n
Slee
veOu
ter
Air
Supp
lyAi
r
(2) O
pt.Un
itDra
inEn
tranc
es
" 8 3
1
8"
31 8"
High
Volt
age
Entra
nce
Entra
nce
Low
Volta
ge
20"x
24" S
upply
Fram
e
24"
1 "
8
4
2"
26"
8
1 28
4""
3
"
3
Total
Depth
8
"1 2
4
4
11
20"
7
1 "11
4
"Tota
lWidt
h
31
547
346
1 8"W
ith S
idesR
emov
ed
Vent
Intak
e
Disc
onne
ctEl
ectric
al
AirF
ilters
Vent
Exha
ust
Door
Latch
Lock
ing
Filter
sRe
turn A
ir
(2)1
2"x2
0"
Door
Latch
Lock
ing
AirF
ilters
(2)W
asha
ble
Hing
es(4
)Lift-
Off
Contr
ol Pa
nel
Elec
tricHe
at Wire
Chan
nel
(2)2
"x24
"x30
"
Fron
tFor
kliftH
oles
(Rem
oveF
ront
Trim
)
"5
58"
" 15
84
131
94"
Total
Heigh
t
(2)R
eturn
Open
ings
Side
Forkl
iftHo
les(R
emov
e Side
s)
2" 71
1
30"W
ithDo
orsa
ndSi
desR
emov
ed
Uni
t Spe
cific
atio
n S
heet
Top
Vie
w
Rig
htS
ide
Vie
w
Fron
tVie
w
MIS-
2917
A
(2)U
nitDr
ains
(2) S
ideHa
ndles
Bac
kV
iew
Form No S3451-918Supersedes S3451-818Page 14 of 20
2
2 2
2
12" MIN.FOR RIGHT
SIDEACCESS
12" MIN.FOR LEFT
SIDEACCESS
12" MIN.12" MIN.
12" MIN. 12" MIN.
0" REQUIRED12" RECOMMENDED
0" REQUIRED12" RECOMMENDED
4"
4"
4"
4"
4"
48" MIN.
31 3/8"
12" MIN.12" MIN.
48"MIN. FOR
FILTER ACCESS
24" MIN. 24" MIN.
DRAIN ACCESS
VIEW FROM BACK OF UNIT
AREA
DRAIN ACCESS DETAIL
REMOVABLESIDES
ACCESSDRAIN
2
ACCESSDRAIN
MIS-3273 A
DRAINACCESS
DRAINACCESS
DRAINACCESS
12" MINIMUM DIMENSIONS AREREQUIRED FOR UNIT OPERATION.IT IS STRONGLY RECOMMENDEDTO USE 20" MINIMUM DISTANCESIF POSSIBLE FOR EASE OF UNITSERVICEABILITY
RECOMMENDED SERVICE
WING WALL CONSTRUCTION TOP VIEW
CLOSET CONSTRUCTION TOP VIEW
1
LEFT CORNER CONSTRUCTION TOP VIEW
FILTERSSIDESREMOVABLE
RIGHT CORNER CONSTRUCTION TOP VIEW
ACCESS DIMENSIONS
1 ALL FILTER AND COMPONENTACCESS IS FROM THE FRONT.COILS CAN BE CLEANED FROMTHE FRONT, BUT SIDES AREEASILY REMOVED FOR ENHANCEDACCESS.
DRAIN OUTLET
WALL/ROOM DRAIN
LONGER HOSEON SIDE WITH
WALL/ROOM DRAIN
DRAIN HEADER ASSEMBLY
TO DRAIN OUTLETSATTACH HEADER
CLAMPS AND
USE PROVIDEDCLAMPS TO SECURE
HEADER TO DRAIN OUTLETS
REMOVE NYLON
INSTALL DRAIN OUTLETON SAME SIDE AS
WALL DRAIN
MIS-3832MIS-3832
DRAIN ACCESS LOCATIONS
OPTIONAL UNIT DRAIN ENTRANCES
3/4" PVCDRAIN OUTLET
Form No S3451-918Supersedes S3451-818Page 15 of 20
"3 8 7
183 4"
17.5"
35"
ORSU
PPLY
DUCT
BOX
OPTI
ONAL
DUCT
GRILL
E
WAL
LSLE
EVE
IRP
RISE
RKI
T
UNIT
CEILI
NG
TELE
SCOP
ING
OPTI
ONAL
TRIM
FLOO
R
Open
ingCe
ntere
don
Optio
nalT
op
Wall
Moun
tingh
oles
(4)o
ption
alUn
it
Moun
tingh
oles
(4)o
ption
alUn
it
Brac
ket
Room
Floor
Leve
l
Outsi
de
Slee
veMo
untin
gHo
leLo
catio
ns
FLOO
RMO
UNTI
NGHO
LE&
CENT
ERLIN
ES
207
"
"
8"DI
M "B
""
6"
8720
8
2156
8"
207 8"
42-3
/4" M
in. 20"
15
"
"43
16
"
48" M
in.8
49
1
Cente
red
8
Cente
red
3"
48-1
/2" M
ax.
3
43-1
/4" M
ax.
20"
20"
DIM
"C"
11
20"
DIM
"A"
16
7
" 4
433 8"
1Hi
gher
SillH
eights
Achie
vable
With
IRP
Rise
rKit.
2Se
para
te tel
esco
pings
leeve
sava
ilable
ford
iffere
ntwa
ll thic
knes
ses.
Rig
htS
ide
Vie
wFr
ont (
Wal
lOnl
y)V
iew
Wal
l Sec
tion
Vie
w
MIS-
3306
A
C L
C L
IRP
RISE
RKI
TDI
M A
DIM
BDI
M C
NONE
31"-3
4"29
17/32
"94
1/8"
IRP-
3(3"
)34
"-37"
MAX
3217
/32"
971/8
"IR
P-6(
6")
37"-4
0" M
AX35
17/32
"10
01/8"
IRP-
9(9"
)40
"-43"
MAX
3817
32"
1031
/8"IR
P-11
(11"
)42
"-44"
MAX
4017
/32"
1051
/8"
1
2
Form No S3451-918Supersedes S3451-818Page 16 of 20
B
94"
A
7' - 10"
UNIT POWER THROUGHBOX IN CONDUIT
ROUTE LOW VOLTAGE
ROUTE HIGH VOLTAGEUNIT POWER THROUGHBOX IN CONDUIT
DIMENSIONS
MIS-3057 C
IPBDF8, IPBDF12 AND IPBDF18DUCT-FREE PLENUM BOX
MODEL NO. DIM. A DIM. BIPBDF8 8" 102" (8'-6")
IPBDF12 12" 106" (8'-10")IPBDF18 18" 112" (9'-4")
DIMENSIONAL CHART
B
MIS-3057 A
DIMENSIONS
IPBDFH8 AND IPBDFH12DUCT-FREE PLENUM BOX
7' - 10"
A
ROUTE LOW VOLTAGEUNIT POWER THROUGH
BOX IN CONDUIT
94"
ROUTE HIGH VOLTAGEUNIT POWER THROUGHBOX IN CONDUIT
MODEL NO. DIM. A DIM. BIPBDFH8 8" 102" (8'-6")IPBDFH12 12" 106" (8'-10")
DIMENSIONAL CHARTMIS-3057
IPBDF8, IPBDFH12 AND IPBDFH18DUCT-FREE PLENUM BOX
DIMENSIONS
DIMENSIONAL CHARTMODEL NO. DIM. A DIM. B
IPBDF8 8" 102" (8'-6")IPBDF12 12" 106" (8'-10")IPBDF18 18" 112" (9'-4")
IPBDFH12 12" 106" (8'-10")IPBDFH18 18" 112" (9'-4")
IPBDF12 AND IPBDF18DUCT-FREE PLENUM BOX
DIMENSIONS
Form No S3451-918Supersedes S3451-818Page 17 of 20
106"8' - 10"
BOX IN CONDUITUNIT POWER THROUGHROUTE HIGH VOLTAGE
HIGH VOLTAGE
ENTRANCEPOWER
MIS-3059
12"
ROUTE LOW VOLTAGEUNIT POWER THROUGH
BOX IN CONDUIT2"
TOP VIEW
7' - 10"94"
IPBDF12HWDUCT-FREE
HOT WATER COILDIMENSIONS
ENTRANCEVALVE WIRING
Ø7/8" O.D. WATER CONNECTIONS. NOTDESIGNATED AS "IN" OR "OUT". CAN BE PIPEDAS NEEDED FOR EASE OF VALVE INSTALLATIONAND SUPPLY/RETURN CONNECTIONS.
12" 12" 17 3/4"
8 3/16"
4 1/2"
Form No S3451-918Supersedes S3451-818Page 18 of 20
105"8' - 9"
ENTRANCELOW VOLTAGE
Ø7/8" O.D. WATER CONNECTIONS. NOTDESIGNATED AS "IN" OR "OUT". CAN BE PIPEDAS NEEDED FOR EASE OF VALVE INSTALLATIONAND SUPPLY/RETURN CONNECTIONS.
24 3/4"
9 7/8"
19 3/4"
40 7/8"
23 7/8"
29 7/8"
9 7/8"
8 1/4"
12"
DIMENSIONS
SUPPLY OPENING
TOP VIEW
7' - 10"
HOT WATER COILIHWC DUCTED
94"
ROUTE HIGH VOLTAGE
BOX IN CONDUITUNIT POWER THROUGH
11"
HIGH VOLTAGEPOWERENTRANCE
2.5"
MIS-3058
Form No S3451-918Supersedes S3451-818Page 19 of 20
1. dBA @ 10 feet, Values recorded in Bard Manufacturing Company, Inc. Sound Lab Facility.2. Actual field results may vary with classroom design and construction.3. Integrated values calculated per ANSI/ASA S12.60-2009 / Part 2, Section 5.2.2.1, Table 2 Triple Mode Type 3
HVAC System Duty Cycles: Ventilation 58%, Part Load 25%, Full Load 17%4. Integrated Sound Values are also applicable for use in learning spaces for CHPS and LEED Schools:
EQ Prerequisite 3 - Minimum Acoustical Performance, OPTION 1. Using methods prescribed in ANSI S12.60, classrooms must achieve a maximum background noise level of 45 dBA.
I30H-I60H Indoor Sound Data at 10 Feet
ModelI30H I36H I42H I48H I60H
63.7 66.6 67.3 67.9 67.8
Outdoor Sound Data at 10 Feet
Vent: ERV IPBDFH-12 Duct Free 12" Plenum Box Ducted
Model Operation ERV Off ERV @ 150 ERV @ 375 ERV @ 450 ERV Off ERV @ 150 ERV @ 375 ERV @ 450
I30H Integrated 33.7 34.0 39.3 40.0 33.6 34.0 39.0 40.1
I36H Integrated 37.7 38.0 40.7 41.7 36.5 37.1 41.7 42.7
I42H Integrated 38.6 40.7 41.3 41.9 39.4 39.3 41.8 42.4
I48H Integrated 39.0 39.0 39.7 39.8 39.8 39.8 40.3 40.6
I60H Integrated 41.4 41.3 41.6 41.6 41.3 41.3 41.8 41.9
Vent: CRV IPBDFH-12 Duct Free 12" Plenum Box Ducted
Model Operation CRV Off CRV@ 300
CRV@ 375
CRV@ 450
CRV@ 525 CRV Off CRV
@ 300CRV
@ 375CRV
@ 450CRV
@ 525
I30H Integrated 34.4 36.0 38.2 40.6 42.1 34.6 36.6 38.1 40.6 42.0
I36H Integrated 37.0 38.5 40.3 42.4 43.9 37.2 40.2 39.2 42.2 44.0
I42H Integrated 39.2 39.8 41.0 42.5 43.5 39.9 40.4 41.1 42.8 43.5
I48H Integrated 40.2 40.7 41.5 43.0 44.2 41.0 40.7 42.2 43.4 44.1
I60H Integrated 44.0 44.3 44.6 45.4 45.9 43.5 43.7 44.1 44.8 45.5
Factory Setting(s) shaded in Gray
Form No S3451-918Supersedes S3451-818Page 20 of 20
Form No. S3451
September 2018
Supersedes: S3451-818
CompleteStat™ Selection Guide
Vent Type Type ofVent Control
BACnet Communication
Ethernet Connection
ControlCode Description CompleteStat
Part Number
NoneN/A Yes No 1 CompleteStat THO (Temp, Humidity & Occupancy) CS9B-THOA
N/A Yes Yes 3 CompleteStat THO w/Ethernet CS9BE-THOA
CRV
On/Off Yes No 1 CompleteStat THO (Temp, Humidity & Occupancy) CS9B-THOA
Demand Yes No 2 CompleteStat THO w/CO2 CS9B-THOCA
On/Off Yes Yes 3 CompleteStat THO w/Ethernet CS9BE-THOA
Demand Yes Yes 4 CompleteStat THO w/CO2 & Ethernet CS9BE-THOCA
ERV
On/Off Yes No 1 CompleteStat THO (Temp, Humidity & Occupancy) CS9B-THOA
Demand Yes No 2 CompleteStat THO w/CO2 CS9B-THOCA
On/Off Yes Yes 3 CompleteStat THO w/Ethernet CS9BE-THOA
Demand Yes Yes 4 CompleteStat THO w/CO2 & Ethernet CS9BE-THOCA
I-TEC 2-Stage Air Source Heat Pumps Model Number Nomenclature
I 36 H 1 D A 0Z R P 4 X X 2
Controls:X = 24v terminal block Only w/o Stat1 = CompleteStat THO (Temp, Humidity & Occupancy)2 = CompleteStat THO w/CO23 = CompleteStat THO w/ Ethernet4 = CompleteStat THO w/CO2 & EthernetNote: CompleteStat must be field installed & wired. All units have 24V terminal block. See Selection Guide.
Coil Treatment:X = Std. Hydrophilic Fin Evap. & Uncoated Alum. Cond. Coil1 = Phenolic Coated ID coil2 = Phenolic Coated OD coil3 = Phenolic Coated ID & OD coil
Color:X = Beige, Painted Steel1 = White, Painted Steel4 = Gray, Painted Steel
Filter:P = 2 inch pleated MERV 8M = 2 inch pleated MERV 11N = 2 inch pleated MERV 13
Vent Option:B = Blank Off PlateM = Multi-Speed CRVN = Multi-Speed CRV with Economizer ModeQ = Modulating CRV (0-10Vdc)R = ERV
Electric Heat:0Z = No heat w/Breaker04 = 4KW 1-Phase05 = 5KW 1-Phase06 = 6KW 3-Phase09 = 9KW 3-Phase10 = 10KW 1-Phase15 = 15KW 1 & 3-Phase18 = 18KW 3-Phase20 = 20KW 1-Phase
Electrical Rating:A = 230/208, 60-1B = 230/208, 60-3C = 460-60-3
Revision Level
System Type:H = Heat Pump
Nominal Capacity: 30 = 30,000 BTUH36 = 36,00042 = 42,00048 = 48,00060 = 60,000
Model Series
(-) = Standard (Non-Dehum)D = Dehumidification
Door Vinyl Graphics OptionsX = No GraphicsA = Stacked Books (Color Code 1 - White Only)B = Paint Brush (Color Code 1 - White Only)
Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com
Due to our continuous product improvement policy, all specifications subject to change without notice. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
BACnet is standard - all versions, shielded twisted pair.
These models also have CAT 5 port for ease of networking in addition to twisted pair terminals.
Demand control for ventilation is ON/OFF based on CO2 set-point.
If modulating mode for ERV is required, use – THO controller plus 8403-067 CO2 controller with modulating output.