hvac system survey ii - the hardy...
TRANSCRIPT
733 Ponte Vedra Blvd HVAC Survey II -- Advantek Consulting Engineering -- 2-5-2014
Page 1 of 5
HVAC SYSTEM SURVEY II Advantek Consulting EngineeringAdvantek Consulting EngineeringAdvantek Consulting EngineeringAdvantek Consulting Engineering | February 5, 2014 | February 5, 2014 | February 5, 2014 | February 5, 2014
Subject: Hoffecker House, 733 Ponte Vedra Blvd
Location: Ponte Vedra, St. John’s County Florida 32082
I. BACKGROUND
An initial site survey was conducted on October 30, 2013 and an Initial Report was
provided on November 8, 2013. The initial survey report describes several
recommendations for improving the cooling and dehumidification performance of the
five air-conditioning systems serving the 9,601 square foot home. Four of the
recommendations are addressed in this report based on work done at the home
November 21-23, 2013: performing a detailed cooling & heating load analysis,
diagnosing the under-performance of systems 1 and 2, checking airflow and fan control
programming on all AHUs, and performing envelope air-tightness testing.
II. FINDINGS
1. Cooling Load Analysis
An accurate zone-by-zone cooling load calculation was performed to positively identify
units that are significantly over- or under-sized and develop corrective actions.
Computed cooling loads were compared against the cooling load calculations submitted
with the 2006 permit application, and against the actual cooling capacity versus the
nominal nameplate rated capacity. Actual capacity is about 10% less than the rated
capacity for all systems, see Table 1. Computed cooling load is greater than both the
permitted cooling calculation and the actual cooling capacity for all systems except #1.
TABLE 1: HVAC CAPACITIES AND LOADS
STAGE 1 STAGE 2 Cool Tons Heat kW Cool Tons Heat kW
#1 Kitchen, South 1flr 5 3.4 4.6 3.3 4.4 13.9 4.4 13.9
1 Great Room 1flr 4.5 16.6
2 Loft 2flr 2.0 3.7
1 North bedrooms 1flr 1.6 10.3
2 North bedroom 2flr 1.4 2.9
#4 Master Suite 2lr 3 1.9 2.7 2.4 3.9 11.4 3.9 11.4
#5 Study, bedrooms 2flr 3 1.9 2.7 2.4 3.3 8.6 3.3 8.6
17 11.1 15.3 12.3 21.0 67.4 18.6 67.4
1 - NOM TONS is nameplate cooling capacity tonnage
2 - ACT TONS is actual cooling capacity at 74F / 63wb / 55%rh and 95F ambient.
3 - PERMIT references cooling load calculation submitted with permit application 8/3/2006
2.1
TOTAL
PERMIT3 COMPUTED LOADS PEAK LOADS
4.93.6
1.8
ACT TONS2
2.6
1.4#3 2
NOM
TONS1
4
SYSTEM ZONE SERVES
#2
13.2none
4.2 20.3
733 Ponte Vedra Blvd HVAC Survey II -- Advantek Consulting Engineering -- 2-5-2014
Page 2 of 5
Under-sizing is preferable to over-sizing since dehumidification performance improves
with longer compressor run time. With modified dehumidification controls, all systems
will be capable of providing ample dehumidification once the house is air-tightened and
slightly pressurized. Direct comparison of computed peak cooling load with the actual
available cooling capacity is shown in Table 2, and differences of more than ¾ -Ton
(9,000 Btuh) are highlighted in red. None of the systems are over-sized.
System #2 serving the Great Room and system #4 serving the Master Suite are
significantly undersized. When ready for replacement, outdoor compressor unit #2
should be increased from 4 to 5 tons. System #4 capacity shortfall can be mitigated with
air duct modifications and by directing more air to the occupied spaces and less to the
walk-in closets. Also, system #5 serving the study and bedrooms is undersized,
however, the next available equipment model would be too large. System #5 can be
mitigated with air duct modifications and air-tightening. Detailed results of the zone-by-
zone load analysis are provided at the end of this report. In summary:
• The permitted cooling load calculations submitted by the mechanical contractor in
2006 under-estimated the required equipment capacity, and missed two zones
entirely, resulting in systems having inadequate capacity.
• Actual cooling capacity is significantly less than the equipment nameplate rating for
all systems. This is good for dehumidification, but bad for temperature control.
• Even with modified fan programming and air duct mitigation measures, one of the
three under-sized systems should be increased in size when ready for replacement.
2. System #1 and #2 Under-Performance
Air handler AHU-1 condensate overflow switch was found to be bad (not making
contact) and incorrectly wired. The switch was found wired in series between
thermostat Y1 to the AHU only, so when the thermostat called for first-stage cooling the
TABLE 2: CAPACITY VS LOAD
PEAK
Cool Tons
#1 4.5 1750 4.4 0.1 3%
#4 2.7 1350 3.9 -1.2 -30%
#5 2.7 1350 3.3 -0.6 -17%
TOTAL 15.4 7150 18.6 -3.2 -17%
4.9
2.1
-1.3 -26%
-0.3 -14%
SHORT / OVER
3.6
1.8
ACT
TONS@CFM
1800
900
SYSTEM
#2
#3
733 Ponte Vedra Blvd HVAC Survey II -- Advantek Consulting Engineering -- 2-5-2014
Page 3 of 5
compressor energized but the fan speed stayed at the “circulate” speed setting. This is
likely the cause of poor cooling performance and ‘sweating’ diffusers noted by the
homeowners. The condensate switch should be replaced and wired in series with the R
terminal so the system (both the indoor air handler and the outdoor compressor) shuts
down if there is a condensate overflow event. The switch was temporarily
disconnected to restore operation, and the homeowner was advised. In any case,
condensate overflow on AHU-1 is unlikely because it is equipped with a condensate
pump.
System #2 was found low on refrigerant charge. Addition of 7/3-lbs/oz was needed; the
nominal system charge is 11/3-lbs/oz. The homeowner was advised that system #2 has
a considerable leak(s) that must be found and repaired before further refrigerant
additions can be made. This explains the poor performance found during testing.
3. Control Programming
The airflow and fan control programming was checked on all AHUs. Thermostat
program values were set to maximize dehumidification capability; however, thermostats
2-1, 2-2, and 3-1 are model versions that do not have a dehumidification feature, as
listed in Table 3. These three thermostats should be replaced with models to match the
other four TH8321U1006, see source below for ordering information1.
The dehumidification model of the Honeywell thermostat also does not have a “DH”
terminal for a true dehumidify signal. Instead, the thermostat simply energizes cooling
when there is a call for dehumidification, so the AHU controls should be modified to
create a dehumidification sequence. The existing controls will over-cool the space up to
3 degrees-F below setpoint in an attempt to satisfy the dehumidification call.
Alternatively, all thermostats could be replaced with a model having a true
dehumidification sequence, and the air handler connections modified accordingly, if the
homeowner prefers.
1 http://www.pexsupply.com/Honeywell-TH8321U1006-VisionPro-Thermostat-3H-2C-w-
Dehumidification-Control-3910000-p?gclid=CNGAxa6107wCFaxxOgodLiIAdw
TABLE 3: THERMOSTAT DEHUMIDIFICATION
#1 TH8321U1006 Yes
1 TH8320U1008 No
2 TH8320U1008 No
1 TH8320U1008 No
2 TH8321U1006 Yes
#4 TH8321U1006 Yes
#5 TH8321U1006 Yes
SYSTEM ZONETHERMOSTAT
Honeywell Model
#2
#3
DeH
733 Ponte Vedra Blvd HVAC Survey II -- Advantek Consulting Engineering -- 2-5-2014
Page 4 of 5
Existing AHU airflow and settings are listed in Table 4. These settings are not optimal
for the needed dehumidification and to satisfy the cooling demand. New settings
should be determined onsite after duct modifications are made, because external static
pressure (ESP) will need to be tested and airflow adjustments made iteratively to find
the best settings. Optimal settings along with modification of AHU controls will
significantly improve dehumidification performance and comfort.
4. Envelope Air-Tightness
Envelope infiltration testing using two instrumented blower doors and three static
pressure gauges was performed to (a) measure the home’s infiltration rate, (b) identify
locations needing sealing or other envelope remediation, and (c) determine the
required ventilation rate for pressurization. Observed leak locations are fireplace flues
(without dampers); the East wall notably around windows in the dining area, and
electrical boxes and baseboards in the bedroom; the North wall notably around
windows; and the recessed light fixtures and audio speakers in the outdoor ceilings
above the second floor Master Suite balcony, Study balcony, and the first floor terrace.
Overall, the envelope can be characterized as “moderately leaky”.
The chart below shows tested air leakage CFM (cubic feet per minute) versus the
pressure difference between indoors and outdoors. The various standard leakage
metrics shown on the chart were calculated from the power curve using generally
accepted formulae. ACH50 is air changes per hour at a 50 Pa (0.2 in-wc or about 40 mph
wind force) pressure differential. CFMnat is the estimated natural infiltration airflow rate
at 10 Pa (0.04 in-wc or about 9 mph wind force) pressure differential; 263 cfm is
somewhat high and indicates this space would benefit from positive ventilation and
pressurization. Minimum code-required ventilation for this house is 149 cfm. ELA is
the effective leakage area at 97 square inches.
TABLE 4: EXISTING AIRFLOW SETTINGS AND CFM
AHU 1 2 3 4 5 6 7 8 ESP in-wc Cool CFM Heat CFM
AIRFLOW
1280
0.59 1130
1500
1400
1125
600
600
4
5
0.58 1950
0.16 1595
0.17 840
0.51
SETTINGS AS FOUND
1
3
2
733 Ponte Vedra Blvd HVAC Survey II -- Advantek Consulting Engineering -- 2-5-2014
Page 5 of 5
The tested value of ACH50=4.9 is 26% leakier than the median of U.S. homes (3.9), and
nearly twice as leaky as a new energy efficient home. The applicable building code is
the 2012 IEEC Standard, which limits air leakage to a value of ACH50 less than 5 for most
of Florida and less than 3 for the northern areas. House pressurization to 5 Pa (0.02 in-
wc) would require 2100 cfm without air-tightening, which is an impractically large
airflow for a house of this size. Achieving ACH50 = 3 will require a 40% increase in air-
tightness to provide minimal 2.5 Pa (0.01 in-wc) pressurization with 850 cfm of
dehumidified fresh air. A blower door follow-up test will be needed after air-tightening.
END OF REPORT
Final review by:
2/14/2014 _________________________________________ Michael West, PhD, PE Date ADVANTEK CONSULTING ENGINEERING, INC. This is an initial report based on limited observations. The recommendations in this report are presented in good faith and believed to be correct, however, items needing further investigation and engineering are noted in the report.
Envelope Air Leakage Test Results[733 Ponte Vedra Blvd 32082]
CFM = 825.6 [Pa] 0.5767
R2 = 0.99
ACH50 = 4.9 Q50 = 7881
ACHnat = 0.16 Qnat = 263
ELA = 97 in2
0
2000
4000
6000
8000
10000
0 10 20 30 40 50 60 70
Negative Space Pressure [Pa]
Airflow
[C
FM
]
HOFFECKER HOUSE PHOTOS 11-21-2013
IR-1. Air leakage from outdoors around electrical box, moisture at window corners and
baseboard.
IR-2. Supply air leakage between register box and register, behind drywall.
IR-3. Supply air leakage at flex-duct collar joint at distribution box.
IR-4. Possible supply air leakage between register box and register.
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 1 - Kitchen
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 1 - Kitchen
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 1 - KitchenProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : July Peak Hour : 11:00 AM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.68 0.68Roof conduction 0.03 0.03Floor, ceiling, partitions 0.00 0.00Glass solar trans. 1.46 1.46Glass conduction 0.33 0.33Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.16 0.16Power equipment 0.18 0.18People 0.14 0.19 0.33Appliances 0.20 0.15 0.35Infiltration 0.20 0.47 0.67
Total Heat Gains 3.38 0.80 4.19
Sensible Heat Ratio : 0.81Ventilation Air : 40.00 CFM
Ventilation Load 0.06 0.13 0.18
Total Cooling Load on Coils and Refrig. Apparatus 4.37
Heating Load Report
Project Name : Hoffecker Zone 1 - KitchenProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 7750.70Walls below grade 0.00Roof 240.63Glass 11884.79Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 12124.85Ceiling 0.00Partitions 0.00Infiltration 13792.31Ventilation 1641.60
Total Heat Losses 47434.88
Ventilation Air : 40.00 CFM
-3.00
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 2-1 Great Room
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-3.00
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
5.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 2-1 Great Room
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 2-1 Great RoomProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15,2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : June Peak Hour : 11:00 AM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.41 0.41Roof conduction 0.16 0.16Floor, ceiling, partitions 0.00 0.00Glass solar trans. 1.64 1.64Glass conduction 0.36 0.36Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.07 0.07Power equipment 0.18 0.18People 0.14 0.19 0.33Appliances 0.00 0.00 0.00Infiltration 0.35 0.80 1.15
Total Heat Gains 3.30 0.99 4.29
Sensible Heat Ratio : 0.77Ventilation Air : 40.00 CFM
Ventilation Load 0.06 0.13 0.18
Total Cooling Load on Coils and Refrig. Apparatus 4.47
Heating Load Report
Project Name : Hoffecker Zone 2-1 Great RoomProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15,2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 5275.33Walls below grade 0.00Roof 1546.22Glass 12910.24Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 11542.50Ceiling 0.00Partitions 0.00Infiltration 23686.99Ventilation 1641.60
Total Heat Losses 56602.87
Ventilation Air : 40.00 CFM
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 2-2 Loft
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 2-2 Loft
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 2-2 LoftProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : July Peak Hour : 5:00 PM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.26 0.26Roof conduction 0.23 0.23Floor, ceiling, partitions 0.00 0.00Glass solar trans. 0.70 0.70Glass conduction 0.16 0.16Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.06 0.06Power equipment 0.18 0.18People 0.04 0.04 0.08Appliances 0.00 0.00 0.00Infiltration 0.10 0.17 0.27
Total Heat Gains 1.72 0.21 1.93
Sensible Heat Ratio : 0.89Ventilation Air : 10.00 CFM
Ventilation Load 0.02 0.03 0.05
Total Cooling Load on Coils and Refrig. Apparatus 1.98
Heating Load Report
Project Name : Hoffecker Zone 2-2 LoftProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 1817.66Walls below grade 0.00Roof 1341.42Glass 3887.65Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 0.00Ceiling 0.00Partitions 0.00Infiltration 5142.68Ventilation 410.40
Total Heat Losses 12599.81
Ventilation Air : 10.00 CFM
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 3-1 Bedrooms Flr1
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 3-1 Bedrooms Flr1
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 3-1 Bedrooms Flr1Project Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : June Peak Hour : 5:00 PM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.19 0.19Roof conduction 0.07 0.07Floor, ceiling, partitions 0.00 0.00Glass solar trans. 0.46 0.46Glass conduction 0.24 0.24Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.07 0.07Power equipment 0.18 0.18People 0.04 0.03 0.06Appliances 0.00 0.00 0.00Infiltration 0.10 0.18 0.28
Total Heat Gains 1.34 0.20 1.55
Sensible Heat Ratio : 0.87Ventilation Air : 15.00 CFM
Ventilation Load 0.03 0.05 0.07
Total Cooling Load on Coils and Refrig. Apparatus 1.62
Heating Load Report
Project Name : Hoffecker Zone 3-1 Bedrooms Flr1Project Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 2059.91Walls below grade 0.00Roof 383.13Glass 5906.40Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 20858.54Ceiling 0.00Partitions 0.00Infiltration 5257.49Ventilation 615.60
Total Heat Losses 35081.08
Ventilation Air : 15.00 CFM
-0.60
-0.40
-0.20
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 3-2 Bed North Flr2
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-0.60
-0.40
-0.20
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 3-2 Bed North Flr2
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 3-2 Bed North Flr2Project Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15,2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : June Peak Hour : 5:00 PM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.12 0.12Roof conduction 0.18 0.18Floor, ceiling, partitions 0.00 0.00Glass solar trans. 0.29 0.29Glass conduction 0.18 0.18Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.19 0.19Power equipment 0.18 0.18People 0.04 0.03 0.06Appliances 0.00 0.00 0.00Infiltration 0.05 0.09 0.14
Total Heat Gains 1.24 0.12 1.35
Sensible Heat Ratio : 0.92Ventilation Air : 15.00 CFM
Ventilation Load 0.03 0.05 0.07
Total Cooling Load on Coils and Refrig. Apparatus 1.43
Heating Load Report
Project Name : Hoffecker Zone 3-2 Bed North Flr2Project Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15,2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 1276.68Walls below grade 0.00Roof 1039.22Glass 4447.83Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 0.00Ceiling 0.00Partitions 0.00Infiltration 2616.30Ventilation 615.60
Total Heat Losses 9995.64
Ventilation Air : 15.00 CFM
-3.00
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 4 Master Suite
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-3.00
-2.00
-1.00
0.00
1.00
2.00
3.00
4.00
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 4 Master Suite
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 4 Master SuiteProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : June Peak Hour : 4:00 PM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.89 0.89Roof conduction 0.64 0.64Floor, ceiling, partitions 0.00 0.00Glass solar trans. 0.83 0.83Glass conduction 0.46 0.46Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.07 0.07Power equipment 0.18 0.18People 0.04 0.05 0.09Appliances 0.00 0.00 0.00Infiltration 0.26 0.44 0.70
Total Heat Gains 3.36 0.48 3.85
Sensible Heat Ratio : 0.87Ventilation Air : 15.00 CFM
Ventilation Load 0.03 0.05 0.08
Total Cooling Load on Coils and Refrig. Apparatus 3.92
Heating Load Report
Project Name : Hoffecker Zone 4 Master SuiteProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 11201.09Walls below grade 0.00Roof 3475.86Glass 10838.59Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 0.00Ceiling 0.00Partitions 0.00Infiltration 12848.50Ventilation 615.60
Total Heat Losses 38979.64
Ventilation Air : 15.00 CFM
-2.00
-1.50
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
January To June - Hoffecker Zone 5 - Study & Bedrms
Total Cooling Load - Tons
Jan Feb Mar Apr May Jun
-2.00
-1.50
-1.00
-0.50
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
Cooling Load (T
ons)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Hour of Day (Solar Time)
July To December - Hoffecker Zone 5 - Study & Bedrms
Total Cooling Load - Tons
Jul Aug Sep Oct Nov Dec
Peak Cooling Load Summary Report
Project Name : Hoffecker Zone 5 - Study & BedrmsProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 95.00 Deg FOutside Design WB Temp : 78.00 Deg FDaily Range : 15.30 Deg F
Inside Design DB Temp : 74.00 Deg FInside Design Rel Hum : 50.00 %RH
Peak Month : June Peak Hour : 5:00 PM, Solar Time
Summary of Heat Gains :Sensible Heat Latent Heat Total Heat
Item ( Ton ) ( Ton ) ( Ton )
Walls conduction 0.13 0.13Roof conduction 0.54 0.54Floor, ceiling, partitions 0.00 0.00Glass solar trans. 0.98 0.98Glass conduction 0.40 0.40Skylights 0.00 0.00Glass blocks 0.00 0.00Lights 0.00 0.00Electronic equipment 0.14 0.14Power equipment 0.04 0.04People 0.12 0.09 0.21Appliances 0.00 0.00 0.00Infiltration 0.24 0.43 0.68
Total Heat Gains 2.59 0.52 3.11
Sensible Heat Ratio : 0.83Ventilation Air : 40.00 CFM
Ventilation Load 0.07 0.13 0.20
Total Cooling Load on Coils and Refrig. Apparatus 3.31
Heating Load Report
Project Name : Hoffecker Zone 5 - Study & BedrmsProject Address : 733 Ponte Vedra Blvd, Ponte Vedra Beach, FLProject Designer : Devin PeckDate : Dec 15, 2013
Weather Station : Jacksonville, Mayport Naval, FloridaLatitude : 30.40 Deg NorthLongitude : 81.42 Deg WestElevation : 16.00 Feet
Outside Design DB Temp : 34.00 Deg FInside Design DB Temp : 72.00 Deg F
Summary of Heat Losses :Sensible Heat
Item ( Btu/h )
Walls above grade 1847.10Walls below grade 0.00Roof 3052.39Glass 9938.14Skylights 0.00Glass blocks 0.00Floor above unheated space 0.00Floors on or below grade 0.00Ceiling 0.00Partitions 0.00Infiltration 12737.54Ventilation 1641.60
Total Heat Losses 29216.77
Ventilation Air : 40.00 CFM