    Heat recovery units

    Save EnergyReduce Your ExpensesTake Care of the Environment

    HEATINGVENTILATIONAIR-CONDITIONINGTANGRA

  • 7/24/2019 Heat Recovery Units Range

    2/35

    Peoplewhostayindoorsmostofthetimeneedfreshair.Thisaffectstheirhealth,efficiencyandmuchmore.

    Exhaustingairoftechnologicalsystems(hot,humidorharmful)hastobecompensated.

    Theinstallationssupplyingfreshairarebigenergyconsumers forheatinginwinterandcooling insummer.Thecostofthis

    energyforventilationiscommensuratewiththatforheatingbutstillnotadequatelyassessed.

    Nowadays there systemswhich can reduce theseexpenseswith40%up to 80%. The correct choice is tobe subjected to

    accurateeconomicanalysesoftheinitialinvestmentaswellastheexpensesoftheirexploitation.

    Thebasicfactorstobeconsideredare:

    Dailyoperation(hourperday);

    Ambientconditions;

    Energy

    costs;

    Initialinvestments;

    Maintenanceexpenses.

    Lifetimeoftheinstallation;

    System withoutrecuperation

    E=0%

    System with plateheat exchanger

    E=45 55%

    System with highefficiency plateheat exchanger

    E=60 70%

    System with rotaryheat exchanger

    E=65 75%

    System with plateheat exchanger and

    heat pump

    E=75 85%

    0

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    10000

    -15 -10 -5 0 5 10

    Q ,kWh

    text ,

    ENERGY CONSUMPTION PER YEAR, kWh

    AHU - A

    0

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    10000

    -15 -10 -5 0 5 10

    Q ,kWh

    text ,

    ENERGY CONSUMPTION PER YEAR, kWh

    AHU - A

    AHU - B

    0

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    10000

    -15 -10 -5 0 5 10

    Q ,kWh

    text ,

    ENERGY CONSUMPTION PER YEAR, kWh

    AHU - A

    AHU - C

    0

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    10000

    -15 -10 -5 0 5 10

    Q ,kWh

    text ,

    ENERGY CONSUMPTION PER YEAR, kWh

    AHU - A

    AHU - D

    0

    1000

    2000

    3000

    4000

    5000

    6000

    7000

    8000

    9000

    10000

    -15 -10 -5 0 5 10

    Q ,kWh

    text ,

    ENERGY CONSUMPTION PER YEAR, kWh

    AHU - A

    AHU - E

    AHU - A

    RECAHU - B

    AHU - CREC REC

    AHU - D

    AHU - E REC

  • 7/24/2019 Heat Recovery Units Range

    3/35

    The initial investments for an energy saving system is higher, but the operation expenses are

    significantlylower

    Thedatashownarenotuniversal.These

    parametersarevalidforthefollowing

    conditions:

    Bulgaria,

    Sofia;

    Indoortemperature22oC;

    Airvolume3000m3/h;

    Dailyoperation10h.of24h.

    Installationlifetime10years;

    Energyprice0.1Euro/kWh;

    8%annualexpensesformaintenance;

    Growthoftheenergyprice12%peryear;

    TheinitialexpensesforHVACsystemare

    tentative;

    SystemtypeDallowsmoistexchange;

    System

    type

    E

    allows

    cooling

    during

    the

    summertime.

    theseareyourlostmoney

    Thereisapreliminarytrendforgrowingofenergypriceforthelast10years.

    Thereisnodoubtaboutthefollowing:

    Thepriceoftheenergywillnotgodown!

    The

    quality

    of

    the

    microclimate

    is

    something

    with

    which

    we

    cannot

    make

    a

    compromise!

    Theprotectionoftheenvironmentisourobligationtothefuturegeneration!

    -

    5 000

    10 000

    15 000

    20 000

    25 000

    30 000

    35 000

    40 000

    45 000

    50 000

    0 1 2 3 4 5 6 7 8 9 10

    Amount,

    Years

    Anual ex penc es w ith acc umulation,

    A B C D E

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010

    US $/BarrelPrice trend of oil

  • 7/24/2019 Heat Recovery Units Range

    4/35

    HeatrecoveryunitsapplicationVentilationandairconditioningsystemsupplyingfreshair:

    Officeandresidentialbuildings;

    Hotels,restaurants,coffeebars,nightclubs;

    Sporthall,gym,swimmingpool;

    Hospitals,schools,laboratories;

    Cinema,theatersconcerthalls;

    Food

    industry

    bakery;

    Technologicalventilation,workshops.

    Tangra HeatrecoveryunitsStandardrangeEVBAL

    Middlerangelowpressure EVBCBM

    Middlerangehighpressure EVBCBP

    High

    efficiency

    range

    EVB

    TOP/

    PLUS

    Rotaryheatexchangersrange EVBROT

  • 7/24/2019 Heat Recovery Units Range

    5/35

  • 7/24/2019 Heat Recovery Units Range

    6/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    HEAT RECOVERY UNITS

    EVB-AL

    Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.Operation temperatures from -20

    oC up to 50

    oC.

    Designed to work with clean air in nonaggressive and non-sparkling environment.

    CONSTRUCTION

    Supporting construction, made by anodized aluminum profiles.

    Thermo and sound insulated panels, powder coated RAL7035;

    o Internal insulation Firex 10 mm, fire resistance class: 0-BS 476 Part 6; class 1 BS 476 Part7;

    o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;

    Cross flow aluminum plate heat exchanger with efficiency up to 55%;

    Double inlet direct drive centrifugal fans 230V, 50Hz, IP 20 (higher protection by request); Air filters class G4 EN 779:2002;

    Rectangular or round duct connector;

    Drain tray with connection;

    Configuration allows easily modifying position of the filters, fans and duct connectors;

    Service doors from the bottom and from the side;

    By-pass with multiple leaf damper by request;

    Heating/ cooling coil by request;

    Hanging support or basic steps by request;

    Roof panels for outdoor installation by request.

    The construction allows horizontal () or vertical (V) installation.

    05 01.01

  • 7/24/2019 Heat Recovery Units Range

    7/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    HEAT RECOVERY UNITS EVB AL

    INSTALLATIONHorizontal installation H

    Vertical installation - V

    Type sizeMax.

    capacitym

    3/h

    Dimensions, mm

    L H max C D G IVB PP-04-H 500 800 280 800 320 215 150 200 215 150

    VB AL-06-H 700 1000 350 1000 390 225 180 250 225 180

    VB AL-10-H 1000 1000 420 1300 460 235 210 280 300 250

    VB AL-20-H 2200 1060 480 1500 520 300 260 315 300 300

    VB AL-30-H 3000 1200 580 1600 620 265 290 355 400 300

    VB AL-35-H 3500 1200 680 1600 720 335 290 355 400 400

    Type sizeMax.

    capacitym

    3/h

    Dimensions, mm

    B H L Bmax C D G I KVB PP-04-V 500 280 800 800 320 150 150 200 215 150 45

    VB AL-06-V 700 350 1000 1000 390 180 225 250 225 180 50

    VB AL-10-V 1000 420 1000 1300 460 210 235 280 250 300 85

    VB AL-20-V 2200 510 1060 1500 550 260 300 315 300 300 105

    VB AL-30V 3000 580 1200 1600 620 290 265 355 300 400 90

    VB AL-35-V 3500 680 1200 1600 620 290 335 355 400 400 140

    Heat recovery units EVB-L

    05 01.02

  • 7/24/2019 Heat Recovery Units Range

    8/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units EVB-L

    05 01.03

    HEATRECOVERYUNITSEVBALH (BYPASSBS)

    By-pass with internal multiple leaf damper;

    Manual control - by request;

    Belimo ON-OFF actuator standard execution

    BY PASS BS

    Type size

    Dimensions, mm

    L H max C D G I VB AL-06-BS 1050 450 1200 520 225 180 225 180 250

    VB AL-10-BS 1050 520 1300 590 235 210 300 250 280

    VB AL-20-BS 1060 650 1500 720 300 260 300 300 315

    VB AL-30-BS 1200 750 1600 820 265 290 400 300 355

    VB AL-35-BS 1300 850 1600 920 335 290 400 400 355

  • 7/24/2019 Heat Recovery Units Range

    9/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units EVB-L

    05 01.04

    HEAT

    RECOVERY

    UNITS

    EVB

    AL

    H

    (HEAT+BY

    PASS

    HBS)

    By-pass with internal multiple leaf damper;

    Manual control - by request;

    Belimo ON-OFF actuator standard execution

    Two rows water coil Cu/Al;

    Four rows water coil (cooling) - by request.

    HEAT + BY PASS - HBS

    Type size Dimensions, mm

    L H max C D G I dVB AL-06-HBS 1050 450 1600 520 225 180 225 180 250

    VB AL-10-HBS 1050 520 1600 590 235 210 300 250 280

    VB AL-20-HBS 1200 650 1900 720 300 260 300 300 315 1

    VB AL-30-HBS 1300 750 1900 820 265 290 400 300 355 1

    VB AL-35-HBS 1300 850 1900 920 335 290 400 400 355 1

    d

  • 7/24/2019 Heat Recovery Units Range

    10/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units EVB-L

    05 01.05

    Typesize FanNominalpower,

    W

    Ratedcurrent

    A

    EVB PP 04 CBM/2 133/190 2x185 0.8

    Type size FanNominal power

    WRated current

    A

    BV AL- 06

    BM/2-146/180 2

    220 1,01

    EVB AL - 06

  • 7/24/2019 Heat Recovery Units Range

    11/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units EVB-L

    05 01.06

    Type size FanNominal power

    WRated current

    A

    BV AL-10 BM/4-180/180 2147 1,5

    BV AL-10/3V BM/4-180/180 V 2147 1,33

    Type size FanNominal power

    WRated current

    A

    BV AL- 20 BM/4-240/240 2370 4,2

    BV AL- 20/3V BM/4-240/240 3V 2370 3,8

  • 7/24/2019 Heat Recovery Units Range

    12/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units EVB-L

    05 01.07

    0

    100

    200

    300

    400

    500

    600

    0 500 1000 1500 2000 2500 3000 3500

    H,

    Pa

    EVBAL35

    V,m3/h

    E=50%

    E=48%

    E=46%

    E=46%

    +600/6002R

    1

    1

    Type size FanNominal power

    WRated current

    A

    BV AL-30 BM/4-270/200 2370 4,0

    BV AL-30/3V BM/4-270/20 3V 2370 3,0

    Type size FanNominal power

    WRated current

    A

    BV AL- 35 BM/4-270/270 2550 6,2

  • 7/24/2019 Heat Recovery Units Range

    13/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units EVB-L

    05 01.08

    STANDARD CONFIGURATIONS

    Horizontal installation

    Vertical installation

    Units are produced in configuration A and C. Modification from A to B or from C to D has to be orderedto the factory and also is possible at the building site.

    ACCESSOARIES

    External high efficiency filter F7, Pmax =80Pa;

    Sound attenuators;

    External electric heater;

    Roof for outdoor installation;

    Flexible duct connectors;

    3-way valve for water coil;

    Freeze protection;

    Pressure switch;.

    3-speed switch;

    Hanging supports;

    Basic steps;

    Frame for outdoor installation.

    ORDER DESIGNATION

    EVB AL 30 3V HBS

    Heating coil and by-pass

    3-speed fan

    Typesize

    Heat recovery unit

    A B

    C D

  • 7/24/2019 Heat Recovery Units Range

    14/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    HEAT RECOVERY UNITS

    MIDDLE RANGE LOW PRESURE

    VB AL- M

    Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.Operation temperatures from -20

    oC up to 50

    oC.

    Designed to work with clean air in nonaggressive and non-sparkling environment.

    CONSTRUCTION

    Supporting construction, made by anodized aluminum profiles.

    Thermo and sound insulated panels, powder coated RAL7035;

    o

    Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0; Cross flow aluminum plate heat exchanger with efficiency up to 55%;

    Double inlet direct drive centrifugal fans 380V, 50Hz;

    Air filters class G4 EN 779:2002;

    Rectangular duct connector;

    Drain tray with connection;

    Service doors from the bottom and from the side;

    By-pass with multiple leaf damper by request;

    Heating/ cooling coil by request;

    Support frame or basic steps by request;

    Roof panels for outdoor installation by request.

    The construction allows horizontal () or vertical (V) installation.

    05 02.01

  • 7/24/2019 Heat Recovery Units Range

    15/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    05 02.02

    Heat recovery units EVB-L

    INSTALLATION

    OVERALL AND JOINED DIMENTIONS VB AL M

    Horizontal installation - H

    Vertical installation - V

    Type-size

    FanRecuperative

    exchanger

    Dimensions, mm

    H L b h c d

    VB-AL- 40 CBM CBM 320/320 RECAL-1200/9-070 700 2550 400 340 600 500

    VB-AL- 60 CBM CBM 380/380 RECAL-1200/9-080 800 2650 475 400 700 600

    VB-AL- 80 CBM CBM 380/380 RECAL-1200/9-110 1000 2650 475 400 700 700

  • 7/24/2019 Heat Recovery Units Range

    16/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    05 02.03

    Heat recovery units EVB-L

    OVERALL AND JOINED DIMENTIONS VB AL M HBS (HEAT+BY PASS HBS)

    Horizontal installation - H

    Vertical installation - V

    Type-size

    FanRecuperative

    exchanger

    Dimensions, mm

    H L b h c d

    VBAL- 40 CBM HBS CBM 320/320 RECAL-1200/9-070 1000 3000 400 340 600 500

    VBAL- 60 CBM HBS CBM 380/380 RECAL-1200/9-080 1100 3100 475 400 700 600

    VBAL- 80 CBM HBS CBM 380/380 RECAL-1200/9-110 1300 3100 475 400 700 700

  • 7/24/2019 Heat Recovery Units Range

    17/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    05 02.04

    Heat recovery units EVB-L

    AERODYNAMIC CHARACTERISTICS

    0

    50

    100

    150

    200

    250

    300

    350

    2500 3000 3500 4000 4500 5000 5500 6000

    Externalpressure

    Pa

    Airvolumem3/h

    EVBAL40

    E=55%

    E=54%

    E=53%

    E=52%

    E=55%

    E=54%

    E=53%

    E=52%

    E=56%

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000

    Externalpressure

    Pa

    Ai r vo lume m3/h

    EVB - Al - 60

    ----- external External pressure ; Pa- - - external External pressure (with water heating coil 800/800 2R 80/60

    0C)

    Type size FanNominal power

    WRated current

    A

    BV AL- 40 CBM BM-320/320 21100 7,2

    Type size FanNominal power

    WRated current

    A

    BV AL- 60 CBM BM-380/380 22200 13,8

  • 7/24/2019 Heat Recovery Units Range

    18/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    05 02.05

    Heat recovery units EVB-L

    E=54%E=55%

    E=53%

    E=52%

    E=51%

    0

    50

    100

    150

    200

    250

    300

    350

    400

    5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 10500 11000

    Externalpressure

    Pa

    Air vol ume m 3/h

    EVB -Al - 80

    ---- external External pressure ; Pa- - - external External pressure (with water heating coil 800/800 2R 80/60

    0C)

    ORDER DESIGNATION

    Heat recovery unit EVB AL - 40 - CBM ST/HBS H/V

    EVB AL - 40 - CBM HBS - H

    Horizontal installation

    HEAT+BY PASS HBS

    ypesize

    Heat recovery unit AL

    Type size FanNominal power

    W

    Rated currentA

    BV AL- 80 CBM BM-380/380 22200 13,8

  • 7/24/2019 Heat Recovery Units Range

    19/35

    05 03.01

    HEAT RECOVERY UNITS

    MIDDLE RANGE HIGH PRESSURE

    VB AL- P

    Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.Operation temperatures from -20

    oC up to 50

    oC.

    Designed to work with clean air in nonaggressive and non-sparkling environment.

    CONSTRUCTION

    Supporting construction, made by anodized aluminum profiles.

    Thermo and sound insulated panels, powder coated RAL7035;

    o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;

    Cross flow aluminum plate heat exchanger with efficiency up to 55%;

    Double inlet belt driven centrifugal fans 380V, 50Hz;

    Air filters class G4 EN 779:2002;

    Rectangular duct connector;

    Drain tray with connection;

    Service doors from the side;

    By-pass with multiple leaf damper;

    External box with heating/ cooling coil by request;

    Support frame or basic steps by request;

    Roof panels for outdoor installation by request.

    `

  • 7/24/2019 Heat Recovery Units Range

    20/35

    05 03.02

    Heat recovery units EVB-L

    INSTALLATION

    OVERALL AND JOINED DIMENSIONS VB AL P

    Standard Version for vertical mounting

    Type-size

    FanRecuperative

    exchangerDimensions, mm

    B H L b h c d

    VB AL- 41 CBP CBP 10/10 RECAL-600/5-040 1150 1350 1900 335 290 600 400

    VB AL- 61 CBP CBP 12/12 RECAL-1200/9-060 850 2000 2500 400 340 500 600

    VB AL- 81 CBP CBP 15/15 RECAL-1200/9-080 1050 2000 3000 470 400 600 600

    Type-size

    FanHeating/ cooling

    coil

    Dimensions, mm

    B H H1 L L1,m L1 b h c d

    VB AL- 41 CBP CBP 10/10 800/500 2R 1150 1350 1600 1900 1300 1500 335 290 600 400

    VB AL- 61 CBP CBP 12/12 800/800 2R/ 4R 1050 2000 2400 2500 1400 1600 400 340 500 600

    VB AL- 81 CBP CBP 15/15 1000/800 2R/ 4R 1250 2000 2700 3000 1600 1800 470 400 600 600

  • 7/24/2019 Heat Recovery Units Range

    21/35

    05 03.03

    Heat recovery units EVB-L

    AERODYNAMIC CHARACTERISTICS free pressure

    1. EVB AL- 41 CBP

    Note: the curve is valid for EVB-CBP with incor porated water heating coi l COT 800/500 2R

    2. EVB AL- 61 CBP

    Note: the curve is valid for EVB-CBP with incor porated water heating coi l COT 800/800 2R

  • 7/24/2019 Heat Recovery Units Range

    22/35

    05 03.04

    Heat recovery units EVB-L

    2. EVB AL- 81 CBP

    Note: the curve is valid for EVB-CBP with incor porated water heating coi l COT 1000/800 2R

    ORDER DESIGNATION

    Heat recovery unit EVB AL - 41 - CBP

    EVB AL - 41/1600 - CBP

    ype size/ Rpm

    Heat recovery unit AL

  • 7/24/2019 Heat Recovery Units Range

    23/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    05 04.01

    HEAT RECOVERY UNITS

    HIGH EFFICIENCY RANGE

    VB TOP/ PLUS

    Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.Operation temperatures from -20

    oC up to 50

    oC.

    Designed to work with clean in nonaggressive and non-sparkling environment.

    CONSTRUCTION

    Supporting construction, made by anodized aluminum profiles.

    Thermo and sound insulated panels, powder coated RAL7035;

    o Internal insulation Firex 10 mm, fire resistance class: 0-BS 476 Part 6; class 1 BS 476 Part7;

    o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0;

    Counter flow aluminum plate heat exchanger with efficiency up to 70%;

    Double inlet direct drive centrifugal fans 230V, 50Hz, IP 20 (higher protection by request);

    Air filters class G4 EN 779:2002;

    Rectangular or round duct connector;

    Drain tray with connection;

    Fixed configuration:

    o type TOP for vertical installation with connections on the top side only;

    o type PLUS for horizontal installation. Panels with fans and inlet panels could be replaced on the

    front or on the side

    Service doors :

    o type TOP on the front side;

    o type PLUS on the bottom or on the side;

    By-pass with multiple leaf damper by request;

    Heating/ cooling coil by request;

    Hanging support or basic steps by request;

  • 7/24/2019 Heat Recovery Units Range

    24/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units ROT

    05 05.02

    OVERALL AND JOINED DIMENSIONS EVB P - (STANDARD VERSION)

    OVERALL AND JOINED DIMENSIONS EVB P - HBC (BY-PASS AND WATER COIL)

    TypesizeMax.

    volumem

    3/h

    Dimensions, mm

    L D K N

    VB - 20-TOP 2500 600 1500 2100 315 50 72

    VB - 30-TOP 3000 700 1500 2100 355 50 172

    VB - 35-TOP 3500 800 1500 2100 355 50 222

    Typesize

    Max.volume,

    m3/h

    Dimensions, mm Water coilHeatingcapacity

    L D K N B/H kW

    VB -20-TOP-HBC 2500 680 1500 2100 315 50 162 500/300-2R 15

    VB -30-TOP-HBC 3000 880 1500 2100 355 50 262 700/400-2R 22,5

    VB -35-TOP-HBC 3500 980 1500 2100 355 50 312 700/400-2R 24,5

  • 7/24/2019 Heat Recovery Units Range

    25/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units TOP/ PLUS

    05 04.03

    AERODYNAMIC CHARACTERISTICS external stat ic pressure

    Curves, marked with 13 are corresponding to the three speeds of the fans (3V);

    For single speed fans use curve 1;

    Dotted line is valid for unit with by-pass and water coil.

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0 250 500 750 1000 1250 1500 1750 2000 2250 2500

    H,

    Pa

    V,m3/h

    EVB20 TOP

    1

    23

    E=69%

    E=67%

    E=65%

    +500/3002R1

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 500 1000 1500 2000 2500 3000

    H,

    Pa

    V,m3/h

    EVBAl30TOP

    12

    3

    E=69%

    E=67%

    E=65%

    1 +700/4002R

    Typesize FanMotor power

    WRated current

    A

    BV 20 - P BM/4-240/240 2370 4,2

    BV 20 - TOP/3V BM/4-240/240 3V 2370 3,8

    Typesize FanMotor power

    WRated current

    A

    BV-30-TOP BM/4-270/200 2370 4,0BV-30-TOP/3V BM/4-270/200 3V 2370 3,0

  • 7/24/2019 Heat Recovery Units Range

    26/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units TOP/ PLUS

    05 04.04

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 500 1000 1500 2000 2500 3000 3500

    H,

    Pa

    V,m3/h

    EVB35TOP

    E=65%

    E=67%

    E=72%

    Note:The Efficiency is calculated with the following parameters: amb. = -10/ 90%

    room. = 22/ 40%

    NOISE LEVEL INPUT/ OUTPUT OF VB [ dB(A)]

    Typesize Hz 63 125 250 500 1000 2000 4000 8000

    EVB 20-Pinput 40 52 58 53 56 57 56 50

    output 43 54 57 56 70 64 63 55

    EVB - 30-Pinput 43 57 60 55 57 69 65 56

    output 50 61 67 69 75 73 70 62

    EVB- 35-Pinput 44 58 61 56 58 59 60 54

    output 50 61 67 68 74 72 73 65

    ORDER DESIGNATION

    Heat recovery unit EVB 20 TOP- S/CB / 3V

    EVB - 20 -TOP- HBC 3V

    3-speed fan

    By-pass and water coil

    Model

    Typesize

    Heat recovery unit

    Typesize FanMotor power

    WRated current

    A

    BV- 35-TOP BM/4-270/270 2550 6,2

  • 7/24/2019 Heat Recovery Units Range

    27/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units TOP/ PLUS

    05 04.05

    OVERALL AND JOINED DIMENSIONS EVB PLUS - (STANDARD VERSION)

    OVERALL AND JOINED DIMENSIONS EVB PLUS - HBC (BY-PASS AND WATER COIL)

    TypesizeMax.

    volume,m

    3/h

    Dimensions, mm

    max L M E F

    VB - 20-PLUS 2500 1200 600 640 2400 315 90 140,5 70

    VB - 30-PLUS 3000 1300 700 740 2500 355 115 182,5 80

    VB 35-PLUS 3500 1300 800 840 2500 355 115 147,5 80

    Typesize

    Max.volume,

    m3/h

    Dimensions, mm COTHeating

    capacity.

    max L M E F B/H kW

    VB - 20-PLUS-HBC 2500 1200 780 640 2700 315 90 140,5 70 500/500-2R 16,7VB - 30-PLUS-HBC 3000 1300 880 740 2800 355 115 182,5 80 600/600-2R 24,1

    VB 35-PLUS-HBC 3500 1300 980 840 2800 355 115 147,5 80 600/600-2R 26,8

  • 7/24/2019 Heat Recovery Units Range

    28/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units TOP/ PLUS

    05 04.06

    AERODYNAMIC CHARACTERISTICS external stat ic pressure

    Curves, marked with 13 are corresponding to the three speeds of the fans (3V);

    For single speed fans use curve 1;

    Dotted line is valid for unit with by-pass and water coil.

    0

    50

    100

    150

    200

    250

    300

    350

    400

    0 250 500 750 1000 1250 1500 1750 2000 2250 2500

    H,

    Pa

    V,m3/h

    EVB20 PLUS

    1

    23

    E=69%

    E=67%

    E=65%

    +500/5002R1

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 500 1000 1500 2000 2500 3000

    H

    ,Pa

    V,m3/h

    EVBAl30PLUS

    12

    3

    E=69%

    E=67%

    E=65%

    1 +600/6002R

    Typesize FanMotor power

    WRated current

    A

    BV 20 - PLUS BM/4-240/2402370 4,2

    BV 20 - PLUS/3V BM/4-240/240 3V 2370 3,8

    Typesize FanMotor power

    WRated current

    A

    BV-30-PLUS BM/4-270/200 2370 4,0

    BV-30-PLUS/3V BM/4-270/200 3V 2370 3,0

  • 7/24/2019 Heat Recovery Units Range

    29/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development.

    Heat recovery units TOP/ PLUS

    05 04.07

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    500

    0 500 1000 1500 2000 2500 3000 3500

    H,

    Pa

    V,m3/h

    EVB35PLUS

    E=65%

    E=67%

    E=72%

    1

    1 +600/6002R

    Note:The Efficiency is calculated with the following parameters: amb. = -10/ 90%

    room. = 22

    / 40%

    NOISE LEVEL INPUT/ OUTPUT OF VB [ dB(A)]

    Typesize Hz 63 125 250 500 1000 2000 4000 8000

    EVB 20-Pinput 40 52 58 53 56 57 56 50

    output 43 54 57 56 70 64 63 55

    EVB - 30-Pinput 43 57 60 55 57 69 65 56

    output 50 61 67 69 75 73 70 62

    EVB- 35-Pinput 44 58 61 56 58 59 60 54

    output 50 61 67 68 74 72 73 65

    ORDER DESIGNATION

    Heat recovery unit EVB 20 TOP- S/CB / 3V

    EVB - 20 - PLUS - HBC / 3V

    3-speed fan

    Water coil and by-pass

    Model

    Typesize

    Heat recovery unit

    Typesize FanMotor power

    WRated cu rrent

    A

    BV- 35-PLUS BM/4-270/270 2550 6,2

  • 7/24/2019 Heat Recovery Units Range

    30/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product development .

    05 05.01

    HEAT RECOVERY UNITS

    WITH ROTARY REGENERATIVE HEAT EXCHANGER

    EVB ROT

    Units for secondary use of energy of the exhaust air in ventilation and air-conditioning systems.Operation temperatures from -20

    oC up to 50

    oC.

    Designed to work with clean air in nonaggressive and non-sparkling environment.

    CONSTRUCTION

    Supporting construction, made by anodized aluminum profiles.

    Thermo and sound insulated panels, powder coated RAL7035;

    o Sandwich panels 25 mm with XPS insulation class M1 or fiberglass class M0; Rotary regenerative heat exchanger with efficiency up to 75%;

    Double inlet belt driven centrifugal fans 380V, 50Hz;

    Air filters class G4 EN 779:2002;

    Rectangular duct connector;

    Drain tray with connection;

    Service doors from the side;

    By-pass with multiple leaf damper by request;

    Heating/ cooling coil by request;

    Supporting frame by request;

    Roof panels for outdoor installation by request.

  • 7/24/2019 Heat Recovery Units Range

    31/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product

    development.

    Heat recovery unit s ROT

    05 05.02

    OVERALL AND JOINED DIMENSIONS

    TypesizeV,

    m3/h

    B,mm

    L,

    mm

    L,

    mm

    L,

    mm

    L,

    mm

    L,

    mm

    H,

    mm

    H,

    mm

    H,

    mm

    H,

    mm

    h,mm

    b,mm

    42

    3000120

    0650

    1700

    - -170

    0700 700

    1400

    1500

    300 500

    4000 400 500

    5000 400 600

    62

    5000130

    0 800

    180

    0 - -

    180

    0 800 800

    160

    0

    170

    0

    400 700

    6000 400 8007000 500 800

    82

    7000155

    0800

    1650

    550 850135

    01000

    1000

    2000

    2100

    500 800

    8000 500 900

    9000 500 1000

  • 7/24/2019 Heat Recovery Units Range

    32/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product

    development.

    Heat recovery unit s ROT

    05 05.03

    TECHNICAL CHARACTERISTICS

    The data given in tables are valid for the following parameters of the air:

    Winter mode: inlet= -12, relative air humidity 80% (fresh air)

    outlet= 20, relative air humidity 30% (exhaust air)

    Water temperature 80/60C

    Summer mode: inlet= 33, relative air humidity - 35% (fresh air)

    outlet= 25, relative air humidity - 40% (exhaust air)

    Water temperature 7/12C

    TypesizeV

    [m/h]

    E

    [%]

    Working

    mode

    outletafter

    ROT[C]

    Heating/

    cooling watercoil

    Q ,

    [kW]

    outlet,

    []

    Pext,

    [Pa]Fan Rpm

    Motor

    power[kW]

    42-30 3000 72,3winter 11.1 1000/500-2R 32 40

    300 CBP 10/10 1420 1,1summer 27.1 1000/500-4R 15 15

    42-40 4000 67,1winter 9.5 1000/500-2R 38 36

    300 CBP 10/10 1480 1,5summer 27.6 1000/500-4R 17,5 16,1

    42-50 5000 62,8winter 8.1 1000/500-2R 43 33

    300 CBP 10/10 1620 2,2

    summer 27.9 1000/500-4R 20 17

    62-50 5000 75,6winter 11 1000/600-2R 41 38

    330 CBP 15/11 1030 2.2summer 27.2 1000/600-4R 18 15,5

    62-60 6000 68,6winter 9.9 1000/600-2R 52 33

    380 CBP15/11 1130 3,0summer 27.4 1000/600-4R 24 17

    62-70 7000 63,1winter 9 1000/600-2R 61 30

    420 CBP 15/11 1200 4,0summer 27.7 1000/600-4R 28 18

    82-70 7000 75,3winter 11.3 1200/600-2R 57 36

    400 BDB 400 1630 3summer 27.1 1200/600-4R 27 16,0

    82-80 800070,4

    winter 10.5 1200/600-2R 67 33430 BDB 400 1780 4

    summer 27.3 1200/600-4R 32 17

    82-90 9000 66,3winter 9.8 1200/600-2R 76 31

    540 BDB 400 1980 5.5summer 27.5 1200/600-4R 37 18

    Note: In case of parameters, different from the mentioned above, please, contact the producer.

  • 7/24/2019 Heat Recovery Units Range

    33/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product

    development.

    Heat recovery uni ts ROT

    05 05.04

    AERODYNAMIC CHARACTERISTICS PRESSURE DROP

  • 7/24/2019 Heat Recovery Units Range

    34/35

    www.tangra.bgWe reserve the right to introduce alternations both in design and technical data without prior notice, due to continued product

    development.

    Heat recovery uni ts ROT

    05 05.05

    SUPPORTING FRAME

    This is the base over which are assembled the separate sections. Supporting frame is made ofgalvanized profiles with openings for lift up and transportation, drainage and etc.

    FRAME FOR OUTDOOR INSTALLATION

    Designed for installation of the units over flat and low-pitched roofs without breach of the hydroinsulation.The frame consists of profiles over which are assembled the separate sections of the heatrecovery unit. Profiles are clamped together with special clutches. This makes the frame easy

    joinable and convenient for leveling and transportation.

    OPTIONS FOR CONTROL AND AUTOMATION

    Freeze protection;

    Torn belt differential presostat;

    Dirty filter differential presostat;

    Electric motor (actuator) for multiple leaf dampers;

    3-way valves for heating/ cooling water coils;

    Air temperature remote tracking;

    Power board for control and automation;

    Rotary heat exchanger automatic control system.

    ORDER DESIGNATION

    EVB ROT 42 40Air volume- (4000 /h)

    Typesize / series /

    Rotary regenerative heat exchanger

    Heat recovery unit