1. THIS CONTRACTOR SHALL CAREFULLY EXAMINE THE ENTIRE SET OF CONTRACT DOCUMENTS AND VISIT THE SITE OF WORK, AND FULLY INFORM HIMSELF AS TO ALL CONDITIONS AND MATTERS THAT CAN, IN ANY WAY, AFFECT THE WORK OR THE COST THEREOF. SHOULD THIS CONTRACTOR FIND DISCREPANCIES IN, OR OMISSIONS FROM THE DRAWINGS, SPECIFICATIONS OR OTHER DOCUMENTS, OR BE IN DOUBT AS TO THEIR MEANING, NOTIFY THE ENGINEER AT ONCE, IN WRITING, OF ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND NEW WORK, AND OBTAIN CLARIFICATION PRIOR TO SUBMITTING ANY BID. LACK OF NOTIFICATION SHALL BE INTERPRETED TO INDICATE NO DISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL COMPENSATION WILL NOT BE GRANTED AFTER AWARD OF CONTRACT FOR ANY WORK REQUIRED TO COMPLY WITH THESE REQUIREMENTS AND INTENT. 2. THIS CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL ALL ELECTRICAL COMPONENTS, SYSTEMS, OR AS MAY BE REQUIRED OR DESCRIBED HEREIN. ALL EQUIPMENT AND DEVICES FURNISHED, OR REQUIRED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. IT WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PURCHASE ALL EQUIPMENT AND FURNISH LABOR AND EQUIPMENT FOR A COMPLETE CODE COMPLIANT OPERATING ELECTRICAL SYSTEM. 3. SPECIFIC VOLTAGE AND CURRENT REQUIREMENTS ON THE ELECTRICAL DRAWINGS SHALL NOT RELIEVE THIS CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TO PURCHASING OR ROUGH-IN WORK. THIS CONTRACTOR SHALL REVIEW ALL DEVICES FURNISHED BY HIS CONTRACT AND DEVICES FURNISHED BY OTHER CONTRACTORS ARE IN AGREEMENT WITH THE DATA SHOWN ON THE DRAWINGS. THE E.C. SHALL PROVIDE FEEDERS, CABLE AND DEVICES THAT ARE IN ACCORD WITH CODE. 4. THIS CONTRACTOR SHALL VERIFY ALL EQUIPMENT AND DEVICE MOUNTING ARRANGEMENTS, HEIGHTS AND LOCATIONS PRIOR TO ROUGH-IN. ANY MENTION OF A SPECIFIC MOUNTING ARRANGEMENT, HEIGHT OR LOCATION SHALL NOT RELIEVE THIS CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT WITH THE EQUIPMENT FURNISHED BY THE OTHER TRADES IN THE SAME AREA. NO ADDITION TO THE CONTRACT SUM WILL BE PERMITTED FOR WRONG LOCATIONS, IN CONFLICT WITH OTHER WORK, ETC. THE OWNER RESERVES THE RIGHT TO RELOCATE ANY DEVICE 10' - 0" PRIOR TO ROUGH-IN WITHOUT ANY ADDITIONAL CHARGE BY THIS CONTRACTOR. THIS CONTRACTOR SHALL FULLY COORDINATE ELECTRICAL WORK WITH THE INSTALLATION OF WORK BY ALL OTHER TRADES AND MAKE NECESSARY FIELD ADJUSTMENTS AS REQUIRED TO ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF THE ABOVE SHALL BE INCLUDED IN THE SCOPE OF WORK AT NO ADDITIONAL COST TO THE OWNER. 5. ALL INSTRUMENTS, APPARATUS AND EQUIPMENT SHALL BE TESTED AND PROVED TO BE ELECTRICALLY AND MECHANICALLY WITHOUT DEFECTS. THE ELECTRICAL SYSTEM SHALL BE TESTED FOR GROUNDS OR SHORTS. IF THE TROUBLE IS WITHIN THE CIRCUIT WIRING, ALL SHORTED OR GROUNDED WIRES SHALL BE REPLACED AND THEN RE-TESTED. ALL METERS, CABLES, EQUIPMENT OR APPARATUS NECESSARY FOR MAKING ALL TESTS SHALL BE FURNISHED AND PROVIDED BY THIS CONTRACTOR. ANY TESTING OR EQUIPMENT MUST CONFORM TO OSHA REQUIREMENTS. 6. THE ENGINEER WILL MAKE PERIODIC VISITS TO THE JOBSITE TO OBSERVE THE PROGRESS OF THE WORK AND TO OBSERVE WHETHER OR NOT IT IS BEING PERFORMED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THIS DOES NOT IN ANY WAY MEAN THAT THE ENGINEER IS A GUARANTOR OF THE CONTRACTOR'S WORK, OR RESPONSIBLE FOR SAFETY IN, ON, OR ABOUT THE JOBSITE, IN CONTROL OF THE SAFETY OR ADEQUACY OF ANY SHIPMENT, BUILDING, SCAFFOLDING, FORMS OR OTHER WORK AIDS, OR FOR SUPERINTENDING, DIRECTION OR HAVING CHARGE AT THE ERECTION AND/OR CONSTRUCTION OF THE WORK. 7. ANY AND ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT ACCORD WITH CITY ELECTRICAL, BUILDING, AND FIRE CODES. ANY AND ALL PERMITS, LICENSE, INSPECTION FEES, AND TAX THAT MAY RESULT FROM WORK UNDER THIS CONTRACT SHALL BE INCLUDED IN THE BASE BID. 8. THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING DELIVERY, RECEIVING, UNLOADING, UNCRATING, STORING, SETTING IN PLACE, AND PROTECTING FROM DAMAGE, VANDALISM, THEFT OR WEATHER DURING CONSTRUCTION ALL NEW EQUIPMENT FURNISHED BY THIS CONTRACTOR. THIS SHALL ALSO APPLY TO ITEMS FURNISHED BY THE OWNER TO THE ELECTRICAL CONTRACTOR. THIS CONTRACTOR SHALL COORDINATE THE DELIVERY TO MEET THE PROJECT COMPLETION DATES AS ESTABLISHED BY THE OWNER. 9. THIS CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES FOR THE PROTECTION OF THE WORKMEN IN ALL PHASES OF WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF ALL CITY, STATE AND FEDERAL SAFETY LAWS (OSHA). THIS SHALL INCLUDE "LOCK-OUT/TAG-OUT" AND REQUIRED GROUNDING. WORK UNDER THIS CONTRACT SHALL NOT BE DONE ON ENERGIZED CIRCUITS. 10. ALL WIRE AND CABLE SHALL BE COPPER, 600 VOLT INSULATION WITH "TYPES" AS FOLLOWS: a. "THHN"-FEEDER AND BRANCH CIRCUIT WIRING ABOVE FINISHED FLOORS AND AREAS NOT SUBJECT TO MOISTURE. b. "THWN"-FEEDER AND BRANCH CIRCUIT WIRING UNDER THE FINISHED SLAB OR "XHHW"-AREAS SUBJECT TO MOISTURE, AND VFD DRIVE "T" LEADS. c. "XHHW"-UNDERGROUND FEEDER AND BRANCH CIRCUIT WIRING. (ONLY). d. MINIMUM BRANCH WIRE SIZE SHALL BE SIZE #12 AWG STANDARD COPPER (WITH THE EXCEPTION OF CONTROL WIRING AND FIXTURE WHIPS MAY BE SIZE #14 AWG). 11. ALL CONDUIT UNLESS NOTED SHALL BE TYPE "EMT" WITH STEEL GLAND OR COMPRESSION COUPLINGS AND CONNECTORS ONLY. ALL CONDUIT UNLESS NOTED SHALL BE SUPPORTED ON UNISTRUT OR KINDORF CHANNEL WITH TWO PIECE CONDUIT STRAPS. CONDUIT MOUNTED ON EQUIPMENT FRAMES MAY BE MOUNTED WITH "MINNIE" TYPE CONDUIT STRAPS. ONE HOLE STRAPS ARE NOT ALLOWED. ALL CONDUIT IN OUTDOOR EXPOSED AREAS SHALL BE TYPE "IMC" WITH SEALTITE FINAL CONNECTIONS. SPRING TYPE (CADDY OR EQUAL) SHALL NOT BE ALLOWED. USE OF "ONE-HOLE" STRAPS SHALL NOT BE ALLOWED. 12. CONDUIT AND EMT FITTINGS SHALL BE MADE OF STEEL OR MALLEABLE IRON. DIE- CAST FITTINGS OF POT METAL WILL NOT BE ACCEPTABLE. SET-SCREW OR INDENTER TYPE FITTINGS SHALL NOT BE USED. 13. THIS CONTRACTOR SHALL INSTALL SIZE OF CONDUIT CALLED FOR ON DRAWINGS AND AS SCHEDULED ABOVE AND SHALL NOT REDUCE SIZE OF CONDUITS TO SUIT WIRE FILL CAPACITY. MINIMUM SIZE OF CONDUIT SHALL BE 1/2" UNLESS OTHERWISE NOTED. THIS CONTRACTOR SHALL LEAVE A WIRE PULLING LINE IN ALL CONDUITS WHICH ARE NOT FILLED TO CAPACITY. THE E.C. SHALL VERIFY ALL CONDUIT SIZE PRIOR TO INSTALLATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANY CONFLICT. 14. THIS CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE FULL YEAR AFTER FINAL ACCEPTANCE BY THE OWNER. 15. THIS CONTRACTOR SHALL FURNISH AS-BUILT DRAWINGS IN AUTOCAD TO THE ENGINEER BEFORE FINAL PAYMENT WILL BE ISSUED. THE AS-BUILD DRAWINGS SHALL DIAGRAMMATICALLY INDICATE THE INSTALLED CONDITION, CIRCUIT NUMBERS, AND LOCATION OF THE DEVICES FOR ALL WORK. THESE DRAWINGS SHALL BE CONSIDERED CONTRACT RECORD DOCUMENTS AND SHALL ACCURATELY REFLECT THE ACTUAL INSTALLATION OF THE ELECTRICAL COMPONENTS AND CONDUITS. 16. FINAL CONNECTION TO MOVABLE DEVICES, OR DEVICES THAT MAY TRANSMIT VIBRATION SHALL BE FINAL CONNECTED WITH FLEXIBLE METALLIC CONDUIT (GREENFIELD) OR LIQUID-TIGHT FLEXIBLE CONDUIT. (MOTORS, TRANSFORMERS, DUCT MOUNTED DEVICES, ETC.) 17. ALL CONDUITS SHALL BE RIGIDLY SUPPORTED BY MEANS OF APPROVED CONDUIT HANGERS OR CLAMPS FIRMLY ANCHORED IN PLACE AND SPACED AT INTERVALS NOT TO EXCEED 7'-0". ALL EXPOSED CONDUIT SHALL BE RACKED AND PARALLEL OR PERPENDICULAR TO WALLS AND 6758&785$/ 0(0%(56 :,7+ r %(1'6 :+(5( 5(48,5(' 38// $1' -81&7,21 %2;(6 6+$// %( HELD TO A MINIMUM. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL RODS, ANGLES, RAILS, STRUTS, BRACE PLATES, PLATFORMS, ETC.. REQUIRED FOR SUSPENSION OR SUPPORT OF CONDUIT AND EQUIPMENT AND ALL STRAPS, CLAMPS, THREADED RODS, TURNBUCKLES, ANCHORS, ETC., AND MISCELLANEOUS SPECIALTIES FOR THE ATTACHMENT OF HANGERS AND SUPPORTS TO THE STRUCTURE. ALL CONDUIT FASTENERS, STRAPS, SUPPORTS AND ETC., MUST BE "BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION. SINGLE CONDUIT SUPPORTS SHALL BE MINNERALIC OR EQUAL. SPRING TYPE CLAMPS ARE NOT ALLOWED. 18. ENDS OF ALL METALLIC CONDUITS SHALL BE EQUIPPED WITH INSULATED GROUNDING BUSHINGS. ENDS OF ALL CONDUITS SHALL BE TEMPORARILY CAPPED PRIOR TO INSTALLATION AND DURING CONSTRUCTION TO EXCLUDE FOREIGN MATERIAL. UPON THE COMPLETION OF CONSTRUCTION THE OPEN END OF CONDUITS OR SLEEVES SHALL BE SEALED WATERTIGHT. 19. THE DRAWINGS MAY NOT SHOW COMPLETE OR ACCURATE DETAILS OF THE EXISTING FACILITY IN EVERY RESPECT. EXACT LOCATIONS AND RELATIONS ARE TO BE DETERMINED IN THE FIELD AND SHALL BE TO THE SATISFACTION OF THE OWNER. THIS CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL FIELD MEASUREMENTS AND EXACT EQUIPMENT LOCATIONS. 20. ALL NON-ELECTRICAL WORK (IE. CORING, PAINTING, ETC.) SHALL BE PERFORMED BY A COMPETENT MECHANIC SKILLED IN HIS PARTICULAR FIELD OR TRADE IN A NEAT AND WORKMANSHIP-LIKE MANNER. THESE COSTS SHALL BE INCLUDED IN THE CONTRACTOR'S BASE BID THOUGH WORK SHALL BE PERFORMED BY OTHERS. 21. ACCESS TO WORK AREAS, INCLUDING WORK SCHEDULED THEREIN, MUST HAVE PRIOR APPROVAL OF THE OWNER. ALL WORK AREAS WILL BE KEPT CLEAN BY THIS CONTRACTOR WITH THOROUGH CLEAN UP AT END OF EACH DAY'S WORK. ALL EXISTING ELECTRIC SERVICE EQUIPMENT IS TO REMAIN OPERATIONAL DURING THE CONSTRUCTION PERIOD. ANY TEMPORARY WIRING OR REROUTING OF CIRCUITRY TO ACHIEVE THIS IS BY THE ELECTRICAL CONTRACTOR. ANY SHUTDOWN OF SYSTEMS, OR POWER DOWN SHALL BE SCHEDULED AND APPROVED IN WRITING BY THE BUILDING OWNER. 22. PROVIDE NECESSARY START-UP AND INSTRUCTION FOR ALL EQUIPMENT AND SYSTEMS TO OWNERSHIPS DESIGNATED EMPLOYEES. ALSO SUBMIT OPERATING INSTRUCTIONS, MAINTENANCE SCHEDULES AND PART LISTS FOR ALL EQUIPMENT AND SYSTEMS TO OWNERSHIP TO ENABLE MAINTENANCE/SUPERVISORY PERSONNEL TO INSTALL, REPAIR AND MAINTAIN THE EQUIPMENT PROPERLY. 23. UPON COMPLETION OF THE DENOTED WORK, THE ELECTRICAL ENGINEER WILL PERFORM A PUNCH LIST IN ORDER TO VERIFY COMPLIANCE TO ALL PLANS, DETAILS AND SPECIFICATIONS. A WRITTEN REPORT WILL BE PREPARED BY THE ENGINEER AND ISSUED TO THE OWNER DESCRIBING ALL DISCREPANCIES. THE OWNER WILL ISSUE THIS REPORT TO THE ELECTRICAL CONTRACTOR FOR HIS IMMEDIATE CORRECTION. UPON COMPLETION OF ALL PUNCH LIST ITEMS, THE ELECTRICAL CONTRACTOR WILL NOTIFY THE OWNER WHO WILL THEN CONTACT THE ENGINEER FOR A FINAL WALK-THROUGH. 24. MATERIALS AND EQUIPMENT SHALL BE NEW AND LISTED AND/OR LABELED BY U.L., OR CITY APPROVED TESTING LAB. 25. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND OWNER IN WRITING OF ANY EXISTING MATERIALS OR APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE IN VIOLATION OF LAWS, ORDINANCES RULES OR REGULATIONS OF AUTHORITIES HAVING JURISDICTION. 26. THE CONTRACTOR SHALL INCLUDE IN HIS BID ELECTRICAL UNIT PRICES (U.P.) TO PROVIDE ADDITIONAL DEVICES INCLUDING CONDUIT AND WIRE AS SCHEDULED. PROVIDE A UNIT PRICE FOR QUANTITY ADJUSTMENT OF EACH DEVICE. THE U.P. SHALL INCLUDE ALL GENERAL CONDITIONS ASSOCIATED COSTS TO INSTALL DEVICES WITHIN CEILING SYSTEMS INSTALLED. 27. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED, TOOLED, CONNECTED, CLEANED, ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS. 28. THE CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS, WHICH ARE REQUIRED FOR THEIR APPROVAL. 29. SHOP DRAWINGS SHALL INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBER, CUTS, DIAGRAMS AND OTHER SUCH DESCRIPTIVE DATA AS MAY BE REQUIRED TO IDENTIFY AND REVIEW THE EQUIPMENT. PARTIAL SUBMITTALS WILL NOT BE REVIEWED. 30. ALL CONDUIT RACEWAYS AND BOXES FOR ALL SYSTEMS SHALL BE INSTALLED WHERE REQUIRED, TIGHT-UP TO BOTTOM OF STRUCTURAL BEAMS AND SUPPORTED FROM CONCENTRATE FLOOR DECK ABOVE. 31. CONDUIT RUNS OR PULL BOXES SHALL NOT BLOCK OR PREVENT FULL COMPLETE ACCESS AND/OR OPERATION OF HVAC EQUIPMENT, ACCESS DOORS, PIPING VALVES, JUNCTION BOXES, MAIN RETURN AIR DUCTS, PULL BOXES, CLEAN OUTS, ETC. 32. ALL BUILDING STANDARD EQUIPMENT, DEVICES AND MATERIALS SHALL BE EQUAL TO OR GREATER IN QUALITY WITH APPROVED BUILDING STANDARD MATERIALS, AND BE SUBJECT TO APPROVAL BY ENGINEER. 33. VERIFY CODE CLEARANCES FOR ALL NEW ELECTRICAL WORK BEFORE PROCEEDING WITH CONSTRUCTION. COORDINATE USAGE OF AVAILABLE SPACE WITH ALL TRADES. IN THE EVENT OF CONFLICTS, NOTIFY THE ENGINEER BEFORE PROCEEDING WITH THE WORK. 34. PROVIDE PERMANENT IDENTIFICATION MARKINGS AND NAMEPLATES FOR WIRING AND EACH ITEM OF ELECTRICAL APPARATUS AND ASSOCIATED CONTROLLED EQUIPMENT, WITH THE SAME DESCRIPTIONS AS SHOWN ON THE DRAWINGS, OR AS DIRECTED, CLEARLY AND NEATLY APPLIED. 35. PROVIDE A TYPEWRITTEN DIRECTORY OF CIRCUITS IN PANEL AND PROVIDE PANEL IDENTIFICATION IN BLACK ALKYD PAINT STENCILED INSCRIPTIONS ON THE INSIDE OF THE DOOR, DIRECTLY ABOVE THE CENTERLINE OF DIRECTORY FRAME, OR ON VERTICAL AND HORIZONTAL CENTERLINE OF DOORS WITHOUT DIRECTORY FRAMES. 36. ALL COMMUNICATION CABLING INSTALLED IN PLENUM AIR SPACES SHALL BE IN CONDUIT, WITHOUT ANY EXCEPTIONS. 37. UPON COMPLETION OF THE WORK, THIS CONTRACTOR SHALL REVIEW AND CHECK THE ENTIRE PORTION OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS MATERIALS AND RUBBISH FROM THE OWNER'S PROPERTY, LEAVING THE WORK IN A NEAT AND CLEAN ORDER AND IN COMPLETE WORKING CONDITION. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL OF ANY SPOILS, DEBRIS, ETC., FOR EQUIPMENT INSTALLED BY THIS CONTRACTOR OR FURNISHED BY SUBCONTRACTOR'S. 38. THE OWNERS TENANTS DESERVE THE HIGHEST RESPECT AND THE EC EMPLOYEES AND AND SUBCONTRACTOR'S SHALL AT ALL TIME CONDUCT THEMSELVES IN A PROFESSIONAL MANNER. FOUL LANGUAGE AND HORSEPLAY WILL NOT BE TOLERATED. 39. ELECTRICAL CONTRACTOR SHALL MEASURE ALL OPERATING VOLTAGE AND AMPERAGE ON EACH MOTOR. VERIFY THAT THE CORRECT OVERCURRENT TRIP INFORMATION IS PROGRAMMED INTO THE VFD DRIVE UNITS. VERIFY PROPER ROTATION WITH THE MECHANICAL CONTRACTOR. 40. ELECTRICAL CONTRACT SHALL PROVIDE U.L. LISTED FIRE STOPPING IN WALL, FLOOR, OR CEILING WHEN PENETRATES. MAINTAIN EXISTING FIRE RESISTANCE RATING. 41. ELECTRICAL CONTRACTOR SHALL SUBMIT FOUR (4) SETS OF EQUIPMENT PRODUCT DATA FOR ENGINEERING REVIEW PRIOR TO ORDERING EQUIPMENT. 42. REMOVE ALL UNUSED AND ABANDONED WIRING, INCLUDING LOW VOLTAGE, COMPLETELY BACK TO SOURCE. 43. PROVIDE ALL GENERAL CONTRACTING WORK AS REQUIRED. GENERAL NOTES GENERAL NOTES (CONTINUED) 1. DEMOLITION: a. THE E.C. SHALL INCLUDE IN HIS CONTRACT ALL REQUIRED DISCONNECTION AND REMOVAL OF ELECTRICAL EQUIPMENT, CONDUIT, AND CABLE BACK TO THE SOURCE PANEL. CONDUIT THAT IS TO BE ABANDONED SHALL BE REMOVED OR SAW-CUT FLUSH WITH THE FLOOR AND FILLED WITH LOW SHRINK CONCRETE. b. DISCONNECT AND REMOVE EXISTING LOT 'B' GENERATOR AND ASSOCIATED GROUNDING, FUEL TANKS, LOCAL LOAD BANKS AND OTHER COMPONENTS NOT USED BY THE REST OF THE EMERGENCY DISTRIBUTION SYSTEM. c. REFER TO DRAWINGS FOR ADDITIONAL SCOPE. d. PROVIDE TEMPORARY LIGHTING AND POWER DURING CONSTRUCTION PERIOD AS REQUIRED. 2. NEW: a. THE WORK DESCRIBED HEREIN IS GENERAL IN NATURE AND THE FINAL INSTALLATION SHALL BE A SAFE, CODE COMPLIANT ELECTRICAL SYSTEM. THE WORK SHALL INCLUDE, BUT NOT BE LIMITED TO: 1) FURNISH AND INSTALL (2) NEW FEEDERS FROM EXISTING 'LEFT FIELD' GENERATOR DISTRIBUTION TO RECONNECT LOT 'B' GENERATOR PANELBOARD AND CHICAGO SPORTS DEPOT MAIN EMERGENCY PANELBOARD AS SHOWN ON THE FLOORPLANS AND RISER DIAGRAM. 2) REFER TO DRAWINGS FOR ADDITIONAL SCOPE. SCOPE OF WORK 1. ALL FUSES FEEDING DISTRIBUTION AND PANEL BOARDS SHALL BE BUSSMAN "LPN-RK" UNLESS NOTED OTHERWISE. 2. ALL BRANCH CIRCUIT BREAKERS OF A 2P. OR 3P. CONFIGURATION SHALL BE MANUFACTURED WITH A COMMON TRIP MECHANISM. FIELD-INSTALLED HANDLE TIES WILL NOT BE PERMITTED. 3. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ENGRAVED LAMINATED PLASTIC NAMEPLATES (BLACK FACE WITH WHITE LETTERS) A MINIMUM OF 1/2" HIGH SCREWED TO THE COVERS FOR ALL SWITCHBOARDS, DISTRIBUTION PANELS, VFD DRIVES, STARTER. AND CONTROL PANEL INDICATING THE PANEL TAG AND ON ALL SWITCH UNITS INDICATING THE EQUIPMENT SERVED. 4. ALL DEVICES MOUNTED EXPOSED TO WEATHER SHALL BE MOUNTED IN CAST ALUMINUM OR HIGH IMPACT ENCLOSURES THAT ARE NEMA RATED 3R OR 4. 5. ALL FUSED (FD) AND NON-FUSED (NF) DISCONNECTS SHALL BE SQUARE D COMPANY, 3-POLE HEAVY DUTY TYPE ONLY. ALL UNITS INSTALLED OUTDOORS SHALL BE RATED WEATHERPROOF NEMA 3R. EQUIPMENT NOTES AC ALTERNATING CURRENT ACL ACROSS THE LINE AFF ABOVE FINISHED FLOOR AIC AMPERES INTERRUPTING CAPACITY AL ALUMINUM ALM ALARM AMP AMPERE ANN ANNUNCIATOR ATS AUTOMATIC TRANSFER SWITCH BAL BALLAST BGB BUILDING GROUND BOX BASC BUILDING AUTOMATION SYSTEM CONTRACTOR C CONDUIT CAB CABINET CATV CABLE TELEVISION C.B. CIRCUIT BREAKER CCT CIRCUIT CCTV CLOSED CIRCUIT TELEVISION cd CANDELA CECO COMMONWEALTH EDISON COMPANY CLO CLOSET COAX COAXIAL CT CURRENT TRANSFORMER CU COPPER C.U. COEFFICIENT OF UTILIZATION CUH CABINET UNIT HEATER DC DIRECT CURRENT DO DRAW OUT DPDT DOUBLE POLE DOUBLE THROW DPST DOUBLE POLE SINGLE THROW DS DISCONNECT SWITCH DT DUST TIGHT ELEC ELECTRIC EM EMERGENCY EMT ELECTRIC METALLIC TUBING (THIN WALL CONDUIT) EP EXPLOSION PROOF EQ EQUIPMENT ER EXISTING TO BE REMOVED ERL EXISTING TO BE RELOCATED EUH ELECTRIC UNIT HEATER EWC ELECTRIC WATER COOLER EWH ELECTRIC WALL HEATER EX EXISTING F FUSE FA FIRE ALARM FB FLOOR BOX FDC FIRE DEPARTMENT CONNECTION FLUOR FLUORESCENT FPB FAN POWERED BOX F.S. FUSED SWITCH FVNR FULL VOLTAGE NON-REVERSING FVR FULL VOLTAGE REVERSING GEN GENERATOR GFCI GROUND FAULT CIRCUIT INTERRUPTER GHW GALVANIZED HEAVY WALL STEEL CONDUIT GRD GROUND HP HORSEPOWER HV HIGH VOLTAGE HZ HERTZ (CYCLES/SECOND) INC INCANDESCENT IC INTERRUPTING CAPACITY IG ISOLATED GROUND IMC INTERMEDIATE GRADE CONDUIT JB JUNCTION BOX KO KNOCKOUT KVA KILOVOLT-AMPERE KW KILOWATT KWH KILOWATT-HOUR LS LOUD SPEAKER LTG LIGHTING LV LOW VOLTAGE MAG MAGNETIC MAN MANUAL MCA MINIMUM CIRCUIT AMPS MCC MOTOR CONTROL CENTER MFR MANUFACTURER MH METAL HALIDE MOCP MAXIMUM OVER CURRENT PROTECTION MTD MOUNTED MTR MOTOR MV MERCURY VAPOR NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NEUT NEUTRAL NIC NOT IN CONTRACT NO NORMALLY OPENED NTS NOT TO SCALE OCP OVER CURRENT PROTECTION PA PUBLIC ADDRESS PB PULL BOX PCU PACKAGED CONTROL UNIT PH PHASE PNL PANEL PRI PRIMARY PROT. PROTECTION OR PROTECTIVE PT POTENTIAL TRANSFORMER PWR POWER R RESISTANCE RECP RECEPTACLE RC REMOTE CONTROL RT RAIN TIGHT RVNR REDUCED VOLTAGE NON-REVERSING RVR REDUCED VOLTAGE REVERSING S SWITCH SC SHORT CIRCUIT SEC SECONDARY SP SINGLE POLE SPC SINGLE POINT CONNECTION SPDT SINGLE POLE DOUBLE THROW SPEC SPECIFICATION SPKR SPEAKER SPST SINGLE POLE SINGLE THROW SS STAINLESS STEEL STA STATION SWBD SWITCHBOARD SWGR SWITCHGEAR SYM SYMMETRICAL SYS SYSTEM T TRIP TC TERMINAL CABINET TEL TELEPHONE TEL.CL. TELEPHONE CLOSET TERM. TERMINAL TL TWIST LOCK TTC TELEPHONE TERMINAL CABINET TV TELEVISION TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION UH UNIT HEATER UL UNDERWRITER'S LABORATORIES UNG UNGROUNDED UNO UNLESS NOTED OTHERWISE V VOLT VA VOLT-AMPERE VFD VARIABLE FREQUENCY DRIVE VP VAPOR PROOF VT VAPOR TIGHT W WATT WG WIRE GUARD WP WEATHERPROOF WT WATER TIGHT XFMR TRANSFORMER ABBREVIATIONS POWER SYMBOLS FUSE SWITCH FUSED DISCONNECT TRANSFORMER METER GENERATOR NON-FUSED DISCONNECT PANELBOARD PANELBOARD AUTOMATIC TRANSFER SWITCH G M N E L GUARANTEED RATE FIELD 333 W 35TH ST, CHICAGO, IL 60616 B LOT GENERATOR REPLACEMENT GENERAL NOTES (CONTINUED) E0.1 17141 DESCRIPTION DATE REV. ISSUE/REVISION: PROJECT NO: CHECKED BY: DRAWN BY: DESIGNED BY: SCALE: SHEET NO. PROJECT: DRAWING TITLE: 333 W 35th St, Chicago, IL 60616 GUARANTEED RATE FIELD B-LOT GENERATOR REPLACEMENT ISSUED FOR BID 7/28/17 SCALE: LOCATION MAP 1 NO SCALE SHEET LIST TABLE Sheet Number Sheet Title E0.1 ELECTRICAL COVER SHEET ED1.1 ELECTRICAL DEMOLITION PLAN - GROUND FLOOR ED2.1 SINGLE LINE DIAGRAM - ELECTRICAL DEMOLITION E1.1 GROUND LEVEL ELECTRICAL NEW WORK PLAN E2.1 SINGLE LINE DIAGRAM - ELECTRICAL NEW WORK KEY PLAN KEY PLAN N 10 9 8 6 7 11 1 3 5 4 2

Upload: others

Post on 22-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: GUARANTEED RATE FIELD B LOT GENERATOR REPLACEMENT236c3m49r38mg7ixa39zqru1-wpengine.netdna-ssl.com/wp... · 2017. 8. 2. · 32.all building standard equipment, devices and materials

1. THIS CONTRACTOR SHALL CAREFULLY EXAMINE THE ENTIRE SET OF CONTRACT DOCUMENTS ANDVISIT THE SITE OF WORK, AND FULLY INFORM HIMSELF AS TO ALL CONDITIONS AND MATTERS THATCAN, IN ANY WAY, AFFECT THE WORK OR THE COST THEREOF. SHOULD THIS CONTRACTOR FINDDISCREPANCIES IN, OR OMISSIONS FROM THE DRAWINGS, SPECIFICATIONS OR OTHER DOCUMENTS,OR BE IN DOUBT AS TO THEIR MEANING, NOTIFY THE ENGINEER AT ONCE, IN WRITING, OF ANYDISCREPANCIES BETWEEN EXISTING CONDITIONS AND NEW WORK, AND OBTAIN CLARIFICATIONPRIOR TO SUBMITTING ANY BID. LACK OF NOTIFICATION SHALL BE INTERPRETED TO INDICATE NODISCREPANCIES OR CONFLICTS EXIST. ADDITIONAL COMPENSATION WILL NOT BE GRANTED AFTERAWARD OF CONTRACT FOR ANY WORK REQUIRED TO COMPLY WITH THESE REQUIREMENTS ANDINTENT.

2. THIS CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL ALL ELECTRICAL COMPONENTS,SYSTEMS, OR AS MAY BE REQUIRED OR DESCRIBED HEREIN. ALL EQUIPMENT AND DEVICESFURNISHED, OR REQUIRED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. IT WILLBE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PURCHASE ALL EQUIPMENT ANDFURNISH LABOR AND EQUIPMENT FOR A COMPLETE CODE COMPLIANT OPERATING ELECTRICALSYSTEM.

3. SPECIFIC VOLTAGE AND CURRENT REQUIREMENTS ON THE ELECTRICAL DRAWINGS SHALL NOTRELIEVE THIS CONTRACTOR OF THE RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR TOPURCHASING OR ROUGH-IN WORK. THIS CONTRACTOR SHALL REVIEW ALL DEVICES FURNISHED BYHIS CONTRACT AND DEVICES FURNISHED BY OTHER CONTRACTORS ARE IN AGREEMENT WITH THEDATA SHOWN ON THE DRAWINGS. THE E.C. SHALL PROVIDE FEEDERS, CABLE AND DEVICES THATARE IN ACCORD WITH CODE.

4. THIS CONTRACTOR SHALL VERIFY ALL EQUIPMENT AND DEVICE MOUNTING ARRANGEMENTS,HEIGHTS AND LOCATIONS PRIOR TO ROUGH-IN. ANY MENTION OF A SPECIFIC MOUNTINGARRANGEMENT, HEIGHT OR LOCATION SHALL NOT RELIEVE THIS CONTRACTOR OF THERESPONSIBILITY TO VERIFY THE SPECIFIC REQUIREMENT WITH THE EQUIPMENT FURNISHED BY THEOTHER TRADES IN THE SAME AREA. NO ADDITION TO THE CONTRACT SUM WILL BE PERMITTED FORWRONG LOCATIONS, IN CONFLICT WITH OTHER WORK, ETC. THE OWNER RESERVES THE RIGHT TORELOCATE ANY DEVICE 10' - 0" PRIOR TO ROUGH-IN WITHOUT ANY ADDITIONAL CHARGE BY THISCONTRACTOR. THIS CONTRACTOR SHALL FULLY COORDINATE ELECTRICAL WORK WITH THEINSTALLATION OF WORK BY ALL OTHER TRADES AND MAKE NECESSARY FIELD ADJUSTMENTS ASREQUIRED TO ACCOMMODATE THE ELECTRICAL INSTALLATION. ALL OF THE ABOVE SHALL BEINCLUDED IN THE SCOPE OF WORK AT NO ADDITIONAL COST TO THE OWNER.

5. ALL INSTRUMENTS, APPARATUS AND EQUIPMENT SHALL BE TESTED AND PROVED TO BEELECTRICALLY AND MECHANICALLY WITHOUT DEFECTS. THE ELECTRICAL SYSTEM SHALL BETESTED FOR GROUNDS OR SHORTS. IF THE TROUBLE IS WITHIN THE CIRCUIT WIRING, ALL SHORTEDOR GROUNDED WIRES SHALL BE REPLACED AND THEN RE-TESTED. ALL METERS, CABLES,EQUIPMENT OR APPARATUS NECESSARY FOR MAKING ALL TESTS SHALL BE FURNISHED ANDPROVIDED BY THIS CONTRACTOR. ANY TESTING OR EQUIPMENT MUST CONFORM TO OSHAREQUIREMENTS.

6. THE ENGINEER WILL MAKE PERIODIC VISITS TO THE JOBSITE TO OBSERVE THE PROGRESS OF THEWORK AND TO OBSERVE WHETHER OR NOT IT IS BEING PERFORMED IN ACCORDANCE WITH THECONTRACT DOCUMENTS. THIS DOES NOT IN ANY WAY MEAN THAT THE ENGINEER IS A GUARANTOROF THE CONTRACTOR'S WORK, OR RESPONSIBLE FOR SAFETY IN, ON, OR ABOUT THE JOBSITE, INCONTROL OF THE SAFETY OR ADEQUACY OF ANY SHIPMENT, BUILDING, SCAFFOLDING, FORMS OROTHER WORK AIDS, OR FOR SUPERINTENDING, DIRECTION OR HAVING CHARGE AT THE ERECTIONAND/OR CONSTRUCTION OF THE WORK.

7. ANY AND ALL WORK UNDER THIS CONTRACT SHALL BE DONE IN STRICT ACCORD WITH CITYELECTRICAL, BUILDING, AND FIRE CODES. ANY AND ALL PERMITS, LICENSE, INSPECTION FEES, ANDTAX THAT MAY RESULT FROM WORK UNDER THIS CONTRACT SHALL BE INCLUDED IN THE BASE BID.

8. THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING DELIVERY, RECEIVING, UNLOADING,UNCRATING, STORING, SETTING IN PLACE, AND PROTECTING FROM DAMAGE, VANDALISM, THEFT ORWEATHER DURING CONSTRUCTION ALL NEW EQUIPMENT FURNISHED BY THIS CONTRACTOR. THISSHALL ALSO APPLY TO ITEMS FURNISHED BY THE OWNER TO THE ELECTRICAL CONTRACTOR. THISCONTRACTOR SHALL COORDINATE THE DELIVERY TO MEET THE PROJECT COMPLETION DATES ASESTABLISHED BY THE OWNER.

9. THIS CONTRACTOR SHALL ESTABLISH SAFE WORKING PROCEDURES FOR THE PROTECTION OF THEWORKMEN IN ALL PHASES OF WORK, COMPLYING WITH THE APPLICABLE PROVISIONS OF ALL CITY,STATE AND FEDERAL SAFETY LAWS (OSHA). THIS SHALL INCLUDE "LOCK-OUT/TAG-OUT" ANDREQUIRED GROUNDING. WORK UNDER THIS CONTRACT SHALL NOT BE DONE ON ENERGIZEDCIRCUITS.

10. ALL WIRE AND CABLE SHALL BE COPPER, 600 VOLT INSULATION WITH "TYPES" AS FOLLOWS:

a. "THHN"-FEEDER AND BRANCH CIRCUIT WIRING ABOVE FINISHED FLOORS AND AREAS NOTSUBJECT TO MOISTURE.

b. "THWN"-FEEDER AND BRANCH CIRCUIT WIRING UNDER THE FINISHED SLAB OR "XHHW"-AREASSUBJECT TO MOISTURE, AND VFD DRIVE "T" LEADS.

c. "XHHW"-UNDERGROUND FEEDER AND BRANCH CIRCUIT WIRING. (ONLY).

d. MINIMUM BRANCH WIRE SIZE SHALL BE SIZE #12 AWG STANDARD COPPER (WITH THEEXCEPTION OF CONTROL WIRING AND FIXTURE WHIPS MAY BE SIZE #14 AWG).

11. ALL CONDUIT UNLESS NOTED SHALL BE TYPE "EMT" WITH STEEL GLAND OR COMPRESSIONCOUPLINGS AND CONNECTORS ONLY. ALL CONDUIT UNLESS NOTED SHALL BE SUPPORTED ONUNISTRUT OR KINDORF CHANNEL WITH TWO PIECE CONDUIT STRAPS. CONDUIT MOUNTED ONEQUIPMENT FRAMES MAY BE MOUNTED WITH "MINNIE" TYPE CONDUIT STRAPS. ONE HOLE STRAPSARE NOT ALLOWED. ALL CONDUIT IN OUTDOOR EXPOSED AREAS SHALL BE TYPE "IMC" WITHSEALTITE FINAL CONNECTIONS. SPRING TYPE (CADDY OR EQUAL) SHALL NOT BE ALLOWED. USE OF"ONE-HOLE" STRAPS SHALL NOT BE ALLOWED.

12. CONDUIT AND EMT FITTINGS SHALL BE MADE OF STEEL OR MALLEABLE IRON. DIE- CAST FITTINGS OFPOT METAL WILL NOT BE ACCEPTABLE. SET-SCREW OR INDENTER TYPE FITTINGS SHALL NOT BEUSED.

13. THIS CONTRACTOR SHALL INSTALL SIZE OF CONDUIT CALLED FOR ON DRAWINGS AND ASSCHEDULED ABOVE AND SHALL NOT REDUCE SIZE OF CONDUITS TO SUIT WIRE FILL CAPACITY.MINIMUM SIZE OF CONDUIT SHALL BE 1/2" UNLESS OTHERWISE NOTED. THIS CONTRACTOR SHALLLEAVE A WIRE PULLING LINE IN ALL CONDUITS WHICH ARE NOT FILLED TO CAPACITY. THE E.C. SHALLVERIFY ALL CONDUIT SIZE PRIOR TO INSTALLATION. NOTIFY THE ENGINEER IMMEDIATELY OF ANYCONFLICT.

14. THIS CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS FOR A PERIOD OF ONE FULLYEAR AFTER FINAL ACCEPTANCE BY THE OWNER.

15. THIS CONTRACTOR SHALL FURNISH AS-BUILT DRAWINGS IN AUTOCAD TO THE ENGINEER BEFOREFINAL PAYMENT WILL BE ISSUED. THE AS-BUILD DRAWINGS SHALL DIAGRAMMATICALLY INDICATETHE INSTALLED CONDITION, CIRCUIT NUMBERS, AND LOCATION OF THE DEVICES FOR ALL WORK.THESE DRAWINGS SHALL BE CONSIDERED CONTRACT RECORD DOCUMENTS AND SHALLACCURATELY REFLECT THE ACTUAL INSTALLATION OF THE ELECTRICAL COMPONENTS ANDCONDUITS.

16. FINAL CONNECTION TO MOVABLE DEVICES, OR DEVICES THAT MAY TRANSMIT VIBRATION SHALL BEFINAL CONNECTED WITH FLEXIBLE METALLIC CONDUIT (GREENFIELD) OR LIQUID-TIGHT FLEXIBLECONDUIT. (MOTORS, TRANSFORMERS, DUCT MOUNTED DEVICES, ETC.)

17. ALL CONDUITS SHALL BE RIGIDLY SUPPORTED BY MEANS OF APPROVED CONDUIT HANGERS ORCLAMPS FIRMLY ANCHORED IN PLACE AND SPACED AT INTERVALS NOT TO EXCEED 7'-0". ALLEXPOSED CONDUIT SHALL BE RACKED AND PARALLEL OR PERPENDICULAR TO WALLS ANDSTRUCTURAL MEMBERS WITH 90° BENDS WHERE REQUIRED. PULL AND JUNCTION BOXES SHALL BEHELD TO A MINIMUM. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL RODS,ANGLES, RAILS, STRUTS, BRACE PLATES, PLATFORMS, ETC.. REQUIRED FOR SUSPENSION ORSUPPORT OF CONDUIT AND EQUIPMENT AND ALL STRAPS, CLAMPS, THREADED RODS,TURNBUCKLES, ANCHORS, ETC., AND MISCELLANEOUS SPECIALTIES FOR THE ATTACHMENT OFHANGERS AND SUPPORTS TO THE STRUCTURE. ALL CONDUIT FASTENERS, STRAPS, SUPPORTS ANDETC., MUST BE "BOLT-ON" GALVANIZED STEEL ON EXPOSED CONSTRUCTION. SINGLE CONDUITSUPPORTS SHALL BE MINNERALIC OR EQUAL. SPRING TYPE CLAMPS ARE NOT ALLOWED.

18. ENDS OF ALL METALLIC CONDUITS SHALL BE EQUIPPED WITH INSULATED GROUNDING BUSHINGS.ENDS OF ALL CONDUITS SHALL BE TEMPORARILY CAPPED PRIOR TO INSTALLATION AND DURINGCONSTRUCTION TO EXCLUDE FOREIGN MATERIAL. UPON THE COMPLETION OF CONSTRUCTION THEOPEN END OF CONDUITS OR SLEEVES SHALL BE SEALED WATERTIGHT.

19. THE DRAWINGS MAY NOT SHOW COMPLETE OR ACCURATE DETAILS OF THE EXISTING FACILITY INEVERY RESPECT. EXACT LOCATIONS AND RELATIONS ARE TO BE DETERMINED IN THE FIELD ANDSHALL BE TO THE SATISFACTION OF THE OWNER. THIS CONTRACTOR SHALL VERIFY AND BERESPONSIBLE FOR ALL FIELD MEASUREMENTS AND EXACT EQUIPMENT LOCATIONS.

20. ALL NON-ELECTRICAL WORK (IE. CORING, PAINTING, ETC.) SHALL BE PERFORMED BY A COMPETENTMECHANIC SKILLED IN HIS PARTICULAR FIELD OR TRADE IN A NEAT AND WORKMANSHIP-LIKEMANNER. THESE COSTS SHALL BE INCLUDED IN THE CONTRACTOR'S BASE BID THOUGH WORKSHALL BE PERFORMED BY OTHERS.

21. ACCESS TO WORK AREAS, INCLUDING WORK SCHEDULED THEREIN, MUST HAVE PRIOR APPROVALOF THE OWNER. ALL WORK AREAS WILL BE KEPT CLEAN BY THIS CONTRACTOR WITH THOROUGHCLEAN UP AT END OF EACH DAY'S WORK. ALL EXISTING ELECTRIC SERVICE EQUIPMENT IS TOREMAIN OPERATIONAL DURING THE CONSTRUCTION PERIOD. ANY TEMPORARY WIRING ORREROUTING OF CIRCUITRY TO ACHIEVE THIS IS BY THE ELECTRICAL CONTRACTOR. ANY SHUTDOWNOF SYSTEMS, OR POWER DOWN SHALL BE SCHEDULED AND APPROVED IN WRITING BY THEBUILDING OWNER.

22. PROVIDE NECESSARY START-UP AND INSTRUCTION FOR ALL EQUIPMENT AND SYSTEMS TOOWNERSHIPS DESIGNATED EMPLOYEES. ALSO SUBMIT OPERATING INSTRUCTIONS, MAINTENANCESCHEDULES AND PART LISTS FOR ALL EQUIPMENT AND SYSTEMS TO OWNERSHIP TO ENABLEMAINTENANCE/SUPERVISORY PERSONNEL TO INSTALL, REPAIR AND MAINTAIN THE EQUIPMENTPROPERLY.

23. UPON COMPLETION OF THE DENOTED WORK, THE ELECTRICAL ENGINEER WILL PERFORM A PUNCHLIST IN ORDER TO VERIFY COMPLIANCE TO ALL PLANS, DETAILS AND SPECIFICATIONS. A WRITTENREPORT WILL BE PREPARED BY THE ENGINEER AND ISSUED TO THE OWNER DESCRIBING ALLDISCREPANCIES. THE OWNER WILL ISSUE THIS REPORT TO THE ELECTRICAL CONTRACTOR FOR HIS

IMMEDIATE CORRECTION. UPON COMPLETION OF ALL PUNCH LIST ITEMS, THE ELECTRICALCONTRACTOR WILL NOTIFY THE OWNER WHO WILL THEN CONTACT THE ENGINEER FOR A FINALWALK-THROUGH.

24. MATERIALS AND EQUIPMENT SHALL BE NEW AND LISTED AND/OR LABELED BY U.L., OR CITYAPPROVED TESTING LAB.

25. THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND OWNER IN WRITING OF ANY EXISTINGMATERIALS OR APPARATUS BELIEVED TO BE INADEQUATE, UNSUITABLE IN VIOLATION OF LAWS,ORDINANCES RULES OR REGULATIONS OF AUTHORITIES HAVING JURISDICTION.

26. THE CONTRACTOR SHALL INCLUDE IN HIS BID ELECTRICAL UNIT PRICES (U.P.) TO PROVIDEADDITIONAL DEVICES INCLUDING CONDUIT AND WIRE AS SCHEDULED. PROVIDE A UNIT PRICE FORQUANTITY ADJUSTMENT OF EACH DEVICE. THE U.P. SHALL INCLUDE ALL GENERAL CONDITIONSASSOCIATED COSTS TO INSTALL DEVICES WITHIN CEILING SYSTEMS INSTALLED.

27. ALL MATERIALS AND EQUIPMENT SHALL BE ERECTED, INSTALLED, TOOLED, CONNECTED, CLEANED,ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THEMANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS.

28. THE CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS, WHICH ARE REQUIRED FORTHEIR APPROVAL.

29. SHOP DRAWINGS SHALL INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBER, CUTS, DIAGRAMSAND OTHER SUCH DESCRIPTIVE DATA AS MAY BE REQUIRED TO IDENTIFY AND REVIEW THEEQUIPMENT. PARTIAL SUBMITTALS WILL NOT BE REVIEWED.

30. ALL CONDUIT RACEWAYS AND BOXES FOR ALL SYSTEMS SHALL BE INSTALLED WHERE REQUIRED,TIGHT-UP TO BOTTOM OF STRUCTURAL BEAMS AND SUPPORTED FROM CONCENTRATE FLOOR DECKABOVE.

31. CONDUIT RUNS OR PULL BOXES SHALL NOT BLOCK OR PREVENT FULL COMPLETE ACCESS AND/OROPERATION OF HVAC EQUIPMENT, ACCESS DOORS, PIPING VALVES, JUNCTION BOXES, MAINRETURN AIR DUCTS, PULL BOXES, CLEAN OUTS, ETC.

32. ALL BUILDING STANDARD EQUIPMENT, DEVICES AND MATERIALS SHALL BE EQUAL TO OR GREATERIN QUALITY WITH APPROVED BUILDING STANDARD MATERIALS, AND BE SUBJECT TO APPROVAL BYENGINEER.

33. VERIFY CODE CLEARANCES FOR ALL NEW ELECTRICAL WORK BEFORE PROCEEDING WITHCONSTRUCTION. COORDINATE USAGE OF AVAILABLE SPACE WITH ALL TRADES. IN THE EVENT OFCONFLICTS, NOTIFY THE ENGINEER BEFORE PROCEEDING WITH THE WORK.

34. PROVIDE PERMANENT IDENTIFICATION MARKINGS AND NAMEPLATES FOR WIRING AND EACH ITEMOF ELECTRICAL APPARATUS AND ASSOCIATED CONTROLLED EQUIPMENT, WITH THE SAMEDESCRIPTIONS AS SHOWN ON THE DRAWINGS, OR AS DIRECTED, CLEARLY AND NEATLY APPLIED.

35. PROVIDE A TYPEWRITTEN DIRECTORY OF CIRCUITS IN PANEL AND PROVIDE PANEL IDENTIFICATIONIN BLACK ALKYD PAINT STENCILED INSCRIPTIONS ON THE INSIDE OF THE DOOR, DIRECTLY ABOVETHE CENTERLINE OF DIRECTORY FRAME, OR ON VERTICAL AND HORIZONTAL CENTERLINE OFDOORS WITHOUT DIRECTORY FRAMES.

36. ALL COMMUNICATION CABLING INSTALLED IN PLENUM AIR SPACES SHALL BE IN CONDUIT, WITHOUTANY EXCEPTIONS.

37. UPON COMPLETION OF THE WORK, THIS CONTRACTOR SHALL REVIEW AND CHECK THE ENTIREPORTION OF WORK, CLEAN EQUIPMENT AND DEVICES, REMOVE SURPLUS MATERIALS AND RUBBISHFROM THE OWNER'S PROPERTY, LEAVING THE WORK IN A NEAT AND CLEAN ORDER AND INCOMPLETE WORKING CONDITION. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL OFANY SPOILS, DEBRIS, ETC., FOR EQUIPMENT INSTALLED BY THIS CONTRACTOR OR FURNISHED BYSUBCONTRACTOR'S.

38. THE OWNERS TENANTS DESERVE THE HIGHEST RESPECT AND THE EC EMPLOYEES AND ANDSUBCONTRACTOR'S SHALL AT ALL TIME CONDUCT THEMSELVES IN A PROFESSIONAL MANNER. FOULLANGUAGE AND HORSEPLAY WILL NOT BE TOLERATED.

39. ELECTRICAL CONTRACTOR SHALL MEASURE ALL OPERATING VOLTAGE AND AMPERAGE ON EACHMOTOR. VERIFY THAT THE CORRECT OVERCURRENT TRIP INFORMATION IS PROGRAMMED INTO THEVFD DRIVE UNITS. VERIFY PROPER ROTATION WITH THE MECHANICAL CONTRACTOR.

40. ELECTRICAL CONTRACT SHALL PROVIDE U.L. LISTED FIRE STOPPING IN WALL, FLOOR, OR CEILINGWHEN PENETRATES. MAINTAIN EXISTING FIRE RESISTANCE RATING.

41. ELECTRICAL CONTRACTOR SHALL SUBMIT FOUR (4) SETS OF EQUIPMENT PRODUCT DATA FORENGINEERING REVIEW PRIOR TO ORDERING EQUIPMENT.

42. REMOVE ALL UNUSED AND ABANDONED WIRING, INCLUDING LOW VOLTAGE, COMPLETELY BACK TOSOURCE.

43. PROVIDE ALL GENERAL CONTRACTING WORK AS REQUIRED.

GENERAL NOTES GENERAL NOTES (CONTINUED)

1. DEMOLITION:

a. THE E.C. SHALL INCLUDE IN HIS CONTRACT ALL REQUIRED DISCONNECTION AND REMOVALOF ELECTRICAL EQUIPMENT, CONDUIT, AND CABLE BACK TO THE SOURCE PANEL. CONDUITTHAT IS TO BE ABANDONED SHALL BE REMOVED OR SAW-CUT FLUSH WITH THE FLOOR ANDFILLED WITH LOW SHRINK CONCRETE.

b. DISCONNECT AND REMOVE EXISTING LOT 'B' GENERATOR AND ASSOCIATED GROUNDING,FUEL TANKS, LOCAL LOAD BANKS AND OTHER COMPONENTS NOT USED BY THE REST OF THEEMERGENCY DISTRIBUTION SYSTEM.

c. REFER TO DRAWINGS FOR ADDITIONAL SCOPE.

d. PROVIDE TEMPORARY LIGHTING AND POWER DURING CONSTRUCTION PERIOD AS REQUIRED.

2. NEW:

a. THE WORK DESCRIBED HEREIN IS GENERAL IN NATURE AND THE FINAL INSTALLATION SHALLBE A SAFE, CODE COMPLIANT ELECTRICAL SYSTEM. THE WORK SHALL INCLUDE, BUT NOT BELIMITED TO:

1) FURNISH AND INSTALL (2) NEW FEEDERS FROM EXISTING 'LEFT FIELD' GENERATORDISTRIBUTION TO RECONNECT LOT 'B' GENERATOR PANELBOARD AND CHICAGO SPORTSDEPOT MAIN EMERGENCY PANELBOARD AS SHOWN ON THE FLOORPLANS AND RISERDIAGRAM.

2) REFER TO DRAWINGS FOR ADDITIONAL SCOPE.

SCOPE OF WORK

1. ALL FUSES FEEDING DISTRIBUTION AND PANEL BOARDS SHALL BE BUSSMAN "LPN-RK" UNLESSNOTED OTHERWISE.

2. ALL BRANCH CIRCUIT BREAKERS OF A 2P. OR 3P. CONFIGURATION SHALL BE MANUFACTUREDWITH A COMMON TRIP MECHANISM. FIELD-INSTALLED HANDLE TIES WILL NOT BE PERMITTED.

3. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ENGRAVED LAMINATED PLASTICNAMEPLATES (BLACK FACE WITH WHITE LETTERS) A MINIMUM OF 1/2" HIGH SCREWED TO THECOVERS FOR ALL SWITCHBOARDS, DISTRIBUTION PANELS, VFD DRIVES, STARTER. AND CONTROLPANEL INDICATING THE PANEL TAG AND ON ALL SWITCH UNITS INDICATING THE EQUIPMENTSERVED.

4. ALL DEVICES MOUNTED EXPOSED TO WEATHER SHALL BE MOUNTED IN CAST ALUMINUM OR HIGHIMPACT ENCLOSURES THAT ARE NEMA RATED 3R OR 4.

5. ALL FUSED (FD) AND NON-FUSED (NF) DISCONNECTS SHALL BE SQUARE D COMPANY, 3-POLEHEAVY DUTY TYPE ONLY. ALL UNITS INSTALLED OUTDOORS SHALL BE RATED WEATHERPROOFNEMA 3R.

EQUIPMENT NOTES

AC ALTERNATING CURRENTACL ACROSS THE LINEAFF ABOVE FINISHED FLOORAIC AMPERES INTERRUPTING CAPACITYAL ALUMINUMALM ALARMAMP AMPEREANN ANNUNCIATORATS AUTOMATIC TRANSFER SWITCHBAL BALLASTBGB BUILDING GROUND BOXBASC BUILDING AUTOMATION SYSTEM CONTRACTORC CONDUITCAB CABINETCATV CABLE TELEVISIONC.B. CIRCUIT BREAKERCCT CIRCUITCCTV CLOSED CIRCUIT TELEVISIONcd CANDELACECO COMMONWEALTH EDISON COMPANYCLO CLOSETCOAX COAXIALCT CURRENT TRANSFORMERCU COPPERC.U. COEFFICIENT OF UTILIZATIONCUH CABINET UNIT HEATERDC DIRECT CURRENTDO DRAW OUTDPDT DOUBLE POLE DOUBLE THROWDPST DOUBLE POLE SINGLE THROWDS DISCONNECT SWITCHDT DUST TIGHTELEC ELECTRICEM EMERGENCYEMT ELECTRIC METALLIC TUBING (THIN WALL CONDUIT)EP EXPLOSION PROOFEQ EQUIPMENTER EXISTING TO BE REMOVEDERL EXISTING TO BE RELOCATEDEUH ELECTRIC UNIT HEATEREWC ELECTRIC WATER COOLEREWH ELECTRIC WALL HEATEREX EXISTINGF FUSEFA FIRE ALARMFB FLOOR BOXFDC FIRE DEPARTMENT CONNECTIONFLUOR FLUORESCENTFPB FAN POWERED BOXF.S. FUSED SWITCHFVNR FULL VOLTAGE NON-REVERSINGFVR FULL VOLTAGE REVERSINGGEN GENERATORGFCI GROUND FAULT CIRCUIT INTERRUPTERGHW GALVANIZED HEAVY WALL STEEL CONDUITGRD GROUNDHP HORSEPOWERHV HIGH VOLTAGEHZ HERTZ (CYCLES/SECOND)INC INCANDESCENTIC INTERRUPTING CAPACITYIG ISOLATED GROUNDIMC INTERMEDIATE GRADE CONDUITJB JUNCTION BOXKO KNOCKOUTKVA KILOVOLT-AMPEREKW KILOWATTKWH KILOWATT-HOURLS LOUD SPEAKERLTG LIGHTINGLV LOW VOLTAGE

MAG MAGNETICMAN MANUALMCA MINIMUM CIRCUIT AMPSMCC MOTOR CONTROL CENTERMFR MANUFACTURERMH METAL HALIDEMOCP MAXIMUM OVER CURRENT PROTECTIONMTD MOUNTEDMTR MOTORMV MERCURY VAPORNC NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEUT NEUTRALNIC NOT IN CONTRACTNO NORMALLY OPENEDNTS NOT TO SCALEOCP OVER CURRENT PROTECTIONPA PUBLIC ADDRESSPB PULL BOXPCU PACKAGED CONTROL UNITPH PHASEPNL PANELPRI PRIMARYPROT. PROTECTION OR PROTECTIVEPT POTENTIAL TRANSFORMERPWR POWERR RESISTANCERECP RECEPTACLERC REMOTE CONTROLRT RAIN TIGHTRVNR REDUCED VOLTAGE NON-REVERSINGRVR REDUCED VOLTAGE REVERSINGS SWITCHSC SHORT CIRCUITSEC SECONDARYSP SINGLE POLESPC SINGLE POINT CONNECTIONSPDT SINGLE POLE DOUBLE THROWSPEC SPECIFICATIONSPKR SPEAKERSPST SINGLE POLE SINGLE THROWSS STAINLESS STEELSTA STATIONSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICALSYS SYSTEMT TRIPTC TERMINAL CABINETTEL TELEPHONETEL.CL. TELEPHONE CLOSETTERM. TERMINALTL TWIST LOCKTTC TELEPHONE TERMINAL CABINETTV TELEVISIONTVSS TRANSIENT VOLTAGE SURGE SUPPRESSIONUH UNIT HEATERUL UNDERWRITER'S LABORATORIESUNG UNGROUNDEDUNO UNLESS NOTED OTHERWISEV VOLTVA VOLT-AMPEREVFD VARIABLE FREQUENCY DRIVEVP VAPOR PROOFVT VAPOR TIGHTW WATTWG WIRE GUARDWP WEATHERPROOFWT WATER TIGHTXFMR TRANSFORMER

ABBREVIATIONS

POWER SYMBOLSFUSE SWITCH

FUSED DISCONNECT

TRANSFORMER

METER

GENERATOR

NON-FUSED DISCONNECT

PANELBOARD

PANELBOARD

AUTOMATIC TRANSFER SWITCH

G

M

N E

L

GUARANTEED RATE FIELD333 W 35TH ST, CHICAGO, IL 60616

B LOT GENERATOR REPLACEMENT

GENERAL NOTES (CONTINUED)

E0.1

17141

DESCRIPTIONDATEREV.

ISSUE/REVISION:

PROJECT NO:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

SCALE:

SHEET NO.

PROJECT:

DRAWING TITLE:

333 W 35th St, Chicago, IL 60616

GUARANTEED RATE FIELDB-LOT GENERATORREPLACEMENT

ISSUED FOR BID7/28/17

SCALE:

LOCATION MAP1 NO SCALE

SHEET LIST TABLESheet Number Sheet Title

E0.1 ELECTRICAL COVER SHEET

ED1.1 ELECTRICAL DEMOLITION PLAN - GROUND FLOOR

ED2.1 SINGLE LINE DIAGRAM - ELECTRICAL DEMOLITION

E1.1 GROUND LEVEL ELECTRICAL NEW WORK PLAN

E2.1 SINGLE LINE DIAGRAM - ELECTRICAL NEW WORKKEY PLANKEY PLAN

N

10

9

8

67

111

3

5

4

2

Page 2: GUARANTEED RATE FIELD B LOT GENERATOR REPLACEMENT236c3m49r38mg7ixa39zqru1-wpengine.netdna-ssl.com/wp... · 2017. 8. 2. · 32.all building standard equipment, devices and materials

MATCH LINECORRIDOR

ELECTRICALROOM

2

EXISTING PANEL 'GDP-B-1A'

1. DISCONNECT AND REMOVE ALL DEVICES AS SHOWN IN THIS PLAN UNLESS OTHERWISE NOTED. REMOVE CONDUITAND WIRES BACK TO SOURCE.

2. REFER TO SHEET ED2.1 FOR DEMOLITION RISER DIAGRAM.

GENERAL DEMOLITION NOTES

1. DISCONNECT AND REMOVE EXISTING GENERATOR COMPLETELY AFTER NEW CONSTRUCTION WORK IS COMPLETEDAS SHOWN ON SHEETS E1.1 AND E1.2. REMOVE CONDUIT, WIRES, AND OTHER ASSOCIATED COMPONENTS UP TOMAIN DISTRIBUTION PANEL 'GPD-B1'.

2. DISCONNECT MAIN POWER CONNECTION FOR PANEL AS SHOWN ON SHEET ED2.1.

3. DISCONNECT AND REMOVE LOAD TEST BANK, CONDUIT, AND WIRES COMPLETELY FROM THE SOURCE.

4. DISCONNECT AND REMOVE FUEL TANK AND ALL ASSOCIATED PIPING.

KEYED DEMOLITION NOTES #

1. REMOVE PORTION OF THE FENCE AS SHOWN.

2. REMOVE EXISTING CONCRETE PAD AND GRAVEL.

KEYED OPTIONAL PRICE #1 DEMOLITION NOTES A1.X

S. SHIELDS AVE.

PARKING LOT 'B'

GENERATOR

FUEL TANK LOAD BANK

1

FENCED AREA SHALL REMAIN A1

A2

34

ED1.1SCALE:

GROUND LEVEL DEMOLITION PLAN1 1/16"=1'-0"

SCALE:

LOT 'B' GENERATOR DEMOLITION PLAN2 1/16"=1'-0"

KEY PLANKEY PLAN

N

10

9

8

67

111

3

5

4

2

17141

DESCRIPTIONDATEREV.

ISSUE/REVISION:

PROJECT NO:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

SCALE:

SHEET NO.

PROJECT:

DRAWING TITLE:

333 W 35th St, Chicago, IL 60616

GUARANTEED RATE FIELDB-LOT GENERATORREPLACEMENT

ISSUED FOR BID7/28/17

Page 3: GUARANTEED RATE FIELD B LOT GENERATOR REPLACEMENT236c3m49r38mg7ixa39zqru1-wpengine.netdna-ssl.com/wp... · 2017. 8. 2. · 32.all building standard equipment, devices and materials

PARKING LOT 'A'

PARKING LOT 'B'

G 200KW

PARKING LOT 'B'GENERATOR

400A/3P

200AS

200AF3P

3P100AS

100AF2P

3P (A,B)100AS

100AF2P

3P (A,C)100AS

100AF2P

3P (B,C)100AS

100AF3P

2P (A,C)200AS

125AF3P

3P400AS

300AF3P

3P

TAPBOXLOAD

BANK

75KW

N E

L

37.5 KVA,480-120/240V,

1PH, 3W

M

GPD-B1277/480, 3PH, 4W, 450A, MLO

200A120/240V

100AS3P

100AS3P

1PH, 3W

#271149370

100AS3P

100AS3P

60AS3P

60AS3P

GDP-B-1A277/480, 3PH, 4W, 400A

NE

L

N E

L

OFF

30FIRE PUMP

M#141528749

SERVICE

GEN.

B1

LOT B

100A

M#141505907

SERVICE

N E

L

SERVICE

ATS-1-6AATS-1-6B

60AS3P

EDP-1-6A277/480V, 400A, MLO, 3PH

60AS3P

60AS3P

100AS3P

100AS3P

EDP-1-6B120/208V, 3PH, 4W, 100A

OFF

EM-1-6STORE

EM EM-1-6A

100A, 3PMAIN

200A#271153988

NE

L100A

37.5 KVA,480-120/240V,

1PH, 3W

37.5 KVA,480-120/240V,

1PH, 3W

100A200A#271149469

N E

L

37.5 KVA,480-120/240V,

1PH, 3W

100AM 200A

#271153989

N E

L

PARKING LOT 'C1'

PARKING LOT 'C2'

60AS3P

100A/3PATS

100A/3PATS

150A/3PATS

SQUARE-D

100A, 3P,120/240V ATS

200A

LOCATED ATTHE GEN.

120/240, 1PH,3W, 125A, MLO

ELEV. RM

#3/0

ATS-1-6C

#3/0

AUX

LOT-C2

LOT-C1

EM-1-6B

LOT-A

OVERHEADCOMEDSERVICE

OVERHEADCOMEDSERVICE

NORTH PARKING LOT 'B'

INSIDE FENCE

N E

LFIRE PUMPATS

INSIDE NORTH BUILDING

OVERHEADCOMEDSERVICE

480/277V, 200KW/250KVA CATDIESEL WITH INTERNAL DAYTANK AND SEPARATE275-GALLON ABOVE GROUNDFUEL TANK

OVERHEADCOMEDSERVICE

NORMALFEED

G

LEFT FIELD GENERATOR750KW/938KVA, 277/480V, 3PH, 4W, 1200A DISCONNECTSWITCH WITH BASE FUEL TANK

400A 1200A

300KW LOAD BANK

GENERATORANNUNCIATOR

5 SETS (4)#350 + (1)#350G - 3 1/2"C EA.UL FIRE RATED RHW IN RIGIDGALVANIZED STEEL (RGS) CONDUIT

2 SETS (4)#350- 3"C EA.

600A3P

600A3P

400A3P

400A3P

200A3P

200A3P

400A3P

400A3P

GPD-1-5A277/480V, 3PH, 4W+G, 1200AMLO, 100000AIC

GPD-1-5B

200A3P

200A3P

100A3P

100A3P

600A3P

600A3P

GRD

250MCM GRD - 1 1/4"CBOND TO BLDG. GRD.ELECTRODE SYSTEM

OUTSIDEREMOTE

ANNUNCIATOR AT FIRECOMMAND PANEL (AT

OPERATION DESK)

GENERATORENCLOSURE

ATS ANNUNCIATORBY SIMPLEX

TO ATS UNITS WITH ANNUNCIATOR WIRING

FULLY-BUSSED SPACES

277/480V, 3PH, 4W+G, 1200AMLO, 100000AIC

LEFT FIELD GENERATOR SYSTEM

UNDERGROUNDCONDUIT AND WIRE TOLOT 'B' SHALL REMAIN

DISCONNECT WIRES ANDREMOVE FROM PANELBOARD

ED2.1

SCALE:

GENERATOR RISER DIAGRAM - DEMOLITION1 NTS

17141

DESCRIPTIONDATEREV.

ISSUE/REVISION:

PROJECT NO:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

SCALE:

SHEET NO.

PROJECT:

DRAWING TITLE:

333 W 35th St, Chicago, IL 60616

GUARANTEED RATE FIELDB-LOT GENERATORREPLACEMENT

ISSUED FOR BID7/28/17

KEY PLANKEY PLAN

N

10

9

8

67

111

3

5

4

2

Page 4: GUARANTEED RATE FIELD B LOT GENERATOR REPLACEMENT236c3m49r38mg7ixa39zqru1-wpengine.netdna-ssl.com/wp... · 2017. 8. 2. · 32.all building standard equipment, devices and materials

MATCH LINE

EXISTING PANEL GDP-1-5B

1

EXISTING PANEL GDP-1-5A

2

CONDUIT LOWERS TO ELECTRICAL ROOMCEILING LEVEL (GROUND LEVEL)

CONDUIT RISES TO 100LEVEL ELECTRICAL ROOM

3

CONDUIT ATCEILING HEIGHT

IMC CONDUITUNDER ROOF

OF BRIDGE

EXISTING PANEL 'GDP-B-1A'

4

CORRIDOR

1

NEW SPLICE BOX

ELECTRICALROOM

EM ELECTRICAL ROOM

TO 'GDP-B1' (LOT-B)

PULL BOX(DO NOT SPLICE)

PULL BOX - 100LEVEL ELEC. ROOM

(DO NOT SPLICE)

CONDUIT ON GROUNDLEVEL

6

FIRE-RATE ALL PENETRATIONS

WORK PERFORMEDWITHIN THE WHITE SOXOFFICE SPACE IS TO BE

DONE DURING NON-GAMEDAYS AND AFTER-HOURS.

FIRE-RATE ALL PENETRATIONS

FIRE-RATE ALL PENETRATIONS

FIRE-RATE ALL PENETRATIONS

1. REFER TO SHEET E2.1 FOR NEW WORK RISER DIAGRAM.

2. ALL NEW CONDUIT OUTSIDE THE BUILDING (EXPOSED TO THE WEATHER) SHALL BE IMC TYPE WITH COMPRESSIONFITTINGS ONLY.

3. ALL ELECTRICAL DEVICES EXPOSED TO THE WEATHER SHALL BE NEMA-3R.

GENERAL NEW WORK NOTES

1. FURNISH AND INSTALL NEW FUSED SWITCHES IN EXISTING DISTRIBUTION PANEL 'GDP-1-5A' AND 'GDP-1-5B' ASSHOWN ON SHEET E2.1. MODIFY EXISTING SWITCHBOARD BUS AS REQUIRED. NEW FUSE SWITCH AIC RATINGSSHALL MATCH THE EXISTING. EXISTING PANELBOARD MAKE IS GE 'SPECTRA' SERIES.

2. FURNISH AND INSTALL NEW CONDUIT AND WIRES FOR NEW FEEDERS AS SHOWN ON THE FLOORPLAN AND NEWWORK RISER DIAGRAM. FURNISH AND INSTALL PULL BOXES AND MOUNTING ACCESSORIES AS REQUIRED TOFACILITATE THE FEEDER INSTALLATION. CONDUIT SHALL BE INSTALLED TIGHT TO THE STRUCTURE.

3. FURNISH AND INSTALL NEW SPLICE BOX ABOVE EXISTING PANEL 'GDP-B-1A' TO CONNECT NEW 100A FEEDER TOUNDERGROUND CONDUIT AND WIRES ROUTED TO LOT-B PANELBOARD 'GPD-B1'.

4. INSTALL NEW 200A FEEDER TO MAIN LUGS OF EXISTING PANELBOARD 'GDP-B-1A'. FURNISH AND INSTALL LUGS KITAS REQUIRED TO INSTALL FEEDER AS SIZED ON THE RISER DIAGRAM.

5. FURNISH AND INSTALL NEW 100A NON-FUSED DISCONNECT SWITCH IN LOT-B LOCATION NOTED ON DETAIL #2 ONTHIS SHEET. INSTALL NEW SWITCH ON THE SIDE OF THE PANEL. EXTEND EXISTING WIRES AS REQUIRED.

6. INSTALLING CONTRACTOR SHALL BE REQUIRED, AS PART OF THEIR SCOPE OF WORK, TO DISCONNECT, REMOVE,AND RE-INSTALL THE EXISTING ACOUSTICAL TILE CEILING SYSTEMS LOCATED THROUGHOUT THE FACILITY ASNECESSARY TO INSTALL NEW CONDUIT INDICATED ON THE FLOORPLAN. THIS WORK SHALL INCLUDES, BUT IS NOTLIMITED TO, ALL REQUIRED CEILING TILES AND GRID, LIGHT FIXTURES, FIRE ALARM, OR EMERGENCY FIXTURESCURRENTLY INSTALLED AS PART OF THE EXISTING CEILING SYSTEM WITHIN THE AREA OF WORK.

7. FURNISH AND INSTALL NEW CONDUIT AND WIRES FROM NEW NON-FUSED DISCONNECT SWITCH TO EXISTINGPANELBOARD 'GPD-B1' AS INCOMING POWER TO THE PANELBOARD.

KEYED NEW WORK NOTES #

1. MODIFY EXISTING FENCE WITH NEW GATE AS SHOWN IN FRONT OF THE ELECTRICAL EQUIPMENT. THE REQUIREDSPACE BETWEEN ELECTRICAL EQUIPMENT AND THE NEW FENCE AND GATE SHALL BE 4'-0". PROVIDE 3'-0" FENCEGATE WITH ALL LOCKING HARDWARE. HEIGHT OF THE NEW FENCE AND GATE SHALL MATCH THE EXISTING.

2. LEVEL EXISTING GROUND AND PROVIDE NEW LANDSCAPING TO MATCH THE EXISTING.

OPTIONAL BID NEW WORK NOTES A1.X

S. SHIELDS AVE.

PARKING LOT 'B'

5

100A/3PNEMA 3R

EXIST. PANEL GDP-B1

7

A1.1

A1.2

E1.1SCALE:

GROUND LEVEL NEW WORK PLAN1 1/16"=1'-0"

SCALE:

NEW WORK PLAN - LOT-B DISTRIBUTION AREA2 1/16"=1'-0"

KEY PLANKEY PLAN

N

10

9

8

67

111

3

5

4

2

17141

DESCRIPTIONDATEREV.

ISSUE/REVISION:

PROJECT NO:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

SCALE:

SHEET NO.

PROJECT:

DRAWING TITLE:

333 W 35th St, Chicago, IL 60616

GUARANTEED RATE FIELDB-LOT GENERATORREPLACEMENT

ISSUED FOR BID7/28/17

Page 5: GUARANTEED RATE FIELD B LOT GENERATOR REPLACEMENT236c3m49r38mg7ixa39zqru1-wpengine.netdna-ssl.com/wp... · 2017. 8. 2. · 32.all building standard equipment, devices and materials

PARKING LOT 'A'

PARKING LOT 'B'

200AS

200AF3P

3P100AS

100AF2P

3P (A,B)100AS

100AF2P

3P (A,C)100AS

100AF2P

3P (B,C)100AS

100AF3P

2P (A,C)200AS

125AF3P

3P400AS

300AF3P

3P

TAPBOX

N E

L

37.5 KVA,480-120/240V,

1PH, 3W

M

GPD-B1277/480, 3PH, 4W, 450A, MLO

200A120/240V

100AS3P

100AS3P

1PH, 3W

#271149370

100AS3P

100AS3P

60AS3P

60AS3P

GDP-B-1A277/480, 3PH, 4W, 400A

NE

L

N E

L

OFF

30FIRE PUMP

M#141528749

SERVICE

LOT B

100A

M#141505907

SERVICE

N E

L

SERVICE

ATS-1-6AATS-1-6B

60AS3P

EDP-1-6A277/480V, 400A, MLO, 3PH

60AS3P

60AS3P

100AS3P

100AS3P

EDP-1-6B120/208V, 3PH, 4W, 100A

OFF

EM-1-6STORE

EM EM-1-6A

100A, 3PMAIN

200A#271153988

NE

L100A

37.5 KVA,480-120/240V,

1PH, 3W

37.5 KVA,480-120/240V,

1PH, 3W

100A200A#271149469

N E

L

37.5 KVA,480-120/240V,

1PH, 3W

100AM 200A

#271153989

N E

L

PARKING LOT 'C1'

PARKING LOT 'C2'

60AS3P

100A/3PATS

100A/3PATS

150A/3PATS

SQUARE-D

100A, 3P,120/240V ATS

200A

LOCATED ATTHE GEN.

120/240, 1PH,3W, 125A, MLO

ELEV. RM

#3/0

ATS-1-6C

#3/0

LOT-C2

LOT-C1

EM-1-6B

LOT-A

OVERHEADCOMEDSERVICE

OVERHEADCOMEDSERVICE

NORTH PARKING LOT 'B'

INSIDE FENCE

N E

LFIRE PUMPATS

INSIDE NORTH BUILDING

OVERHEADCOMEDSERVICE

OVERHEADCOMEDSERVICE

NORMALFEED

G

LEFT FIELD GENERATOR750KW/938KVA, 277/480V, 3PH, 4W, 1200A DISCONNECTSWITCH WITH BASE FUEL TANK

400A 1200A

300KWLOADBANK

GENERATORANNUNCIATOR

5 SETS (4)#350 + (1)#350G - 3 1/2"C EA.UL FIRE RATED RHW IN RIGIDGALVANIZED STEEL (RGS) CONDUIT

2 SETS (4)#350- 3"C EA.

600A3P

600A3P

400A3P

400A3P

200A3P

200A3P

400A3P

400A3P

GPD-1-5A277/480V, 3PH, 4W+G, 1200AMLO, 100000AIC

GPD-1-5B

200A3P

200A3P

100A3P

100A3P

600A3P

600A3P

GRD

250MCM GRD - 1 1/4"CBOND TO BLDG. GRD.ELECTRODE SYSTEM

OUTSIDEREMOTE

ANNUNCIATOR AT FIRECOMMAND PANEL (AT

OPERATION DESK)

GENERATORENCLOSURE

ATS ANNUNCIATORBY SIMPLEX

TO ATS UNITS WITH ANNUNCIATOR WIRING

FULLY-BUSSED SPACES100AF3P

100AS3P

277/480V, 3PH, 4W+G, 1200AMLO, 100000AIC

LEFT FIELD GENERATOR SYSTEM

200AF3P

200AS3P

SPLICE BOX(EM ELEC.ROOM)

NEW (4)#4/0, (1)#4G IN 2-1/2"C

NEW (4)#1, (1)#6GIN 1-1/2"C

100A/3PNEMA 3R

EXISTING FEEDER

NEW (4)#3, (1)#8GIN 1-1/4"C

J J JJTO LEFT FIELD

GENERATOR

(2)#14 GENERATOR START WIRESIN 3/4" CONDUIT - PARALLED TO

THE NEW FEEDER CONDUIT

NEW

NEW

NEW

NEW

SPARE SPARE

NEW (4)#3, (1)#8GIN 1-1/4"C

CONNECT EXISTINGGENERATOR STARTWIRES TO EXISTING ATS

CONNECT EXISTINGGENERATOR STARTWIRES TO EXISTING ATS

CONNECT EXISTINGGENERATOR STARTWIRES TO EXISTING ATS

CONNECT EXISTINGGENERATOR STARTWIRES TO EXISTING ATS

SPLICE ALL EXISTING PARKING LOT ATS GENERATORSTART WIRES TO EXISTING UNDERGROUND

GENERATOR START WIRES TO SEND SIGNAL TO LEFTFIELD GENERATOR TO START IN CASE OF LOSS OF

POWER. PROVIDE CONDUIT AND WIRES AS REQUIRED.

J

JEXISTING

EXISTING

TO PARKING LOT ATS UNITS

SPLICEEXISTINGWITH NEW

E2.1

SCALE:

GENERATOR RISER DIAGRAM - NEW WORK1 NTS

17141

DESCRIPTIONDATEREV.

ISSUE/REVISION:

PROJECT NO:

CHECKED BY:

DRAWN BY:

DESIGNED BY:

SCALE:

SHEET NO.

PROJECT:

DRAWING TITLE:

333 W 35th St, Chicago, IL 60616

GUARANTEED RATE FIELDB-LOT GENERATORREPLACEMENT

ISSUED FOR BID7/28/17

KEY PLANKEY PLAN

N

10

9

8

67

111

3

5

4

2