EXTENDING PLANTS AND CONTROLLERS BY INTEGRATING FF ADVANTAGES The gateway and Linking Device FG-110 FF is designed for plant operators and system integrators. It allows including up to four FOUNDATION fieldbus H1 segments with as many as 64 field devices into Modbus RTU based legacy (not FF-ready) plants or into control systems supporting Modbus TCP. This provides access to process data, while making use of FF advantages like reduced cabling, central field device parameterization, comprehensive diagnosis functionality, or intrinsically safe, fieldbus-powered field devices. The implementation of “Control in the Field”, a specialty of FF, is also possible by configuring the available field devices as a control loop without a dedicated controller component. COST SAVINGS THROUGH INCLUDED CONFIGURATION TOOL The FG-110 FF is delivered together with a Windows-based FOUNDATION fieldbus configuration tool, which communicates via the FF High Speed Ethernet (HSE) protocol. It provides the complete FF configuration functionality like the definition of Function Block linking and scheduling as well as bus parameter settings, and field device parameterization. The configuration tool makes use of registered standard Device Description files, as available from the field device manufacturers and the Fieldbus Foundation. In addition, the FG-110 FF provides an integrated web server, which allows defining the mapping of FF functions to Modbus registers, or monitoring the process values. ACCESS POINT FOR USING ADDITIONAL FUNCTIONALITY IN FF SEGMENT The FG-110 FF can be used as a key component for implementing additional automation functionality in the FF section of the plant. For instance, asset management systems (e.g. Emerson’s AMS) and Field Device Tool (FDT) frame applications (e.g. SMART VISION, FieldMate, Field Device Manager, or PACTware) can be included using the FG- 110 FF as access point. The FG-110 FF allows integrating FOUNDATION fieldbus (FF) technology into legacy plants and Modbus control systems. It includes a Windows-based FF configuration tool and can be used for implementing state-of-the-art information services. Modbus Gateway and Linking Device for Integrating FOUNDATION™ fieldbus CUSTOMER BENEFITS > Integration of FF Advantages Into Plants and Controllers > Cost Savings Through Included Configuration Tool > Possibility to Implement Additional FF Functionality FG-110 FF FOUNDATION FIELDBUS

Upload: others

Post on 20-Oct-2019

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: FOUNDATION FIELDBUS FG-110 FF - industrial.softing.com · the mapping of FF functions to Modbus registers, or monitoring the process values. ACCESS POINT FOR USING ADDITIONAL FUNCTIONALITY

Tech

nica

l cha

nges

rese

rved

© S

ofti

ng In

dust

rial

Aut

omat

ion

Gm

bH, F

F00

6E,

July

20

12

EXTENDING PLANTS AND CONTROLLERS BY INTEGRATING FF ADVANTAGES

The gateway and Linking Device FG-110 FF is designed for plant operators and system integrators. It allows including up to four FOUNDATION fieldbus H1 segments with as many as 64 field devices into Modbus RTU based legacy (not FF-ready) plants or into control systems supporting Modbus TCP. This provides access to process data, while making use of FF advantages like reduced cabling, central field device parameterization, comprehensive diagnosis functionality, or intrinsically safe, fieldbus-powered field devices. The implementation of “Control in the Field”, a specialty of FF, is also possible by configuring the available field devices as a control loop without a dedicated controller component.

COST SAVINGS THROUGH INCLUDED CONFIGURATION TOOL

The FG-110 FF is delivered together with a Windows-based FOUNDATION fieldbus configuration tool, which communicates via the FF High Speed Ethernet (HSE) protocol. It provides the complete FF configuration functionality like the definition of Function Block linking and scheduling as well as bus parameter settings, and field device parameterization. The configuration tool makes use of registered standard Device Description files, as available from the field device manufacturers and the Fieldbus Foundation.In addition, the FG-110 FF provides an integrated web server, which allows defining the mapping of FF functions to Modbus registers, or monitoring the process values.

ACCESS POINT FOR USING ADDITIONAL FUNCTIONALITY IN FF SEGMENT

The FG-110 FF can be used as a key component for implementing additional automation functionality in the FF section of the plant. For instance, asset management systems (e.g. Emerson’s AMS) and Field Device Tool (FDT) frame applications (e.g. SMART VISION, FieldMate, Field Device Manager, or PACTware) can be included using the FG-110 FF as access point.

The FG-110 FF allows integrating FOUNDATION fieldbus (FF) technology into legacy plants and Modbus control systems. It includes a Windows-based FF configuration tool and can be used for implementing state-of-the-art information services.

Modbus Gateway and Linking Device for Integrating FOUNDATION™ fieldbus

CUSTOMER BENEFITS

> Integration of FF Advantages Into Plants and Controllers

> Cost Savings Through Included Configuration Tool

> Possibility to Implement Additional FF Functionality

FG-110 FF

FOUNDATION FIELDBUS

Page 2: FOUNDATION FIELDBUS FG-110 FF - industrial.softing.com · the mapping of FF functions to Modbus registers, or monitoring the process values. ACCESS POINT FOR USING ADDITIONAL FUNCTIONALITY

Tech

nica

l cha

nges

rese

rved

© S

ofti

ng In

dust

rial

Aut

omat

ion

Gm

bH, F

F00

6E,

July

20

12

FOUNDATION fieldbus / FG-110 FF

ORDER NUMBER

GLA-YK-020110 FG-110 FF

TECHNICAL DATA

Communication

FOUNDATION fieldbus H1 Transfer Rate: 31.25Kbit/s

LED Indicators: Power On, Activity LED Per Segment

Connectors: 3-Position Screw Connection, Galvanically Isolated

FOUNDATION fieldbus HSE 100BASE-TX/10BASE-T, Automatic Recognition

Connector: RJ45

Modbus TCP, Modbus RTU Assign Registers to Process Values Using TAG Parameter of Analog Input Function Block

Serial Interface RS232 9-Pin D-Sub Female Connector

Transfer Rate: 1.2Kbit/s…115.2Kbit/s

Galvanically Isolated

Physical Properties

Dimensions (W x H x D) 47mm x 131mm x 111mm (1.9” x 5.2” x 4.4”)

Mounting Rail 35mm

Operating Temperature / Storage Temperature 0°C…+70°C / -20°C…+70°C

Relative Humidity 0%...95%, Non-Condensing

Degree of Protection IP20

Power Supply 24VDC (±20%), Typically 200mA

No Power Supply to FF H1 Segments Through FG-110 FF

Product Certifications

CE EN61000-6-2, EN61000-6-4, EN55022 Limit Class A

Electro Magnetic Compatibility (EMC) FCC Part 15 Subpart B Class C, VCCI Class 2 Information Technology Equipment 2002

Shock/Vibration DIN IEC68 Part 2

Hazardous Location Certifications UL508, CSA C22.2 No. 14-M95 Industrial Control Equipment

SCOPE OF DELIVERY

Softing Industrial Automation GmbHRichard-Reitzner-Allee 685540 Haar / Germany

Tel.: +49 89 4 56 56-340Fax: +49 89 4 56 [email protected]

Softing Industrial Automation is a world-leading provider of industrial communication products and technologies used with devices, controls, and systems in manufacturing and process automation applications. Our products are tailored to the requirements of system integrators, device vendors, machine and equipment manufacturers as well as end users and are known for its ease of use and functional advantages.

FG-110 FF

Hardware Gateway and Linking Device FG-110 FF

Software Windows-Based FF Configuration Tool, Web Server for Modbus Mapping Configuration

Documentation User’s Manual

ADDITIONAL PRODUCTS AND SERVICES

OPC-MODB-TCP Modbus TCP OPC Server

OPTIONS FOR BUILDING CUSTOMER-SPECIFIC FIELDBUS INTERFACE MODULE BASED ON FG-110 FF

AHA-YK-020111 FG-110 FF Option: IP65 Housing Plus Assembling Services

APA-YK-020111 FG-110 FF Option: Power Conditioner

GPA-YK-020111 FG-110 FF Option: RS232/RS485 Converter

AAA-YK-020101 FG-110 FF Option: CM 20 Conduit Adapter (Only one adapter can be selected)

AAA-YK-020102 FG-110 FF Option: PG 13.5 Conduit Adapter (Only one adapter can be selected)

AAA-YK-020103 FG-110 FF Option: 3/4“ NPT Conduit Adapter (Only one adapter can be selected)

AAA-YK-020104 FG-110 FF Option: 1/2“ NPT Conduit Adapter (Only one adapter can be selected)