advancements in physical layer with ff - fieldbus · 2013-02-08 · © 1994 – 2011 fieldbus...

43
Advancements in Physical layer with FF Unnikrishnan R Technical Support

Upload: others

Post on 07-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

Advancements in Physical layer with FF

Unnikrishnan R

Technical Support

Page 2: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 2

Agenda

Introduction to FF and FF Physical Layer

FF Physical Layer Components

FF Concepts

FF Wiring Topologies

FF technology and maintenance

Technology developments

Summary

Page 3: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 3

What is Fieldbus?

HOST

Field Device

Fieldbus is an all-digital, serial, two-way communication protocol that

interconnects devices in the field such as sensors, actuators, and controllers.

FOUNDATION fieldbus also has the capability to distribute control applications across its

network in the field. Furthermore, it enables advanced diagnostics for all fieldbus

components and asset management tools resulting in higher plant availability.

Page 4: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 4

Main components of physical layer

FF - Power Supply, Cables, Surge Protector, Terminators, Wiring Blocks,

Process interfaces etc

Wiring Block

HOST

Wiring Block FIELDBUS

TERMINATOR

SURGE PROTECTOR

PROCESS

INTERFACE

Ff POWER

SUPPLY

CONVENTIONAL

FIELD DEVICES

FIELDBUS

DEVICES

JUNCTION

BOX

Home Run Spurs

Page 5: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 5

How to optimize FF Physical Layer?

Optimization of field devices by using proper segment design methodology

as well as segment revalidation tools where we can optimize loop checking

and commissioning time.

Usage of digital communication to achieve predictive intelligence through

advanced diagnostics and asset management of the plant.

Usage of features of the device to effect control in field which will optimize

lower bandwidth of 31.25kb/sec.

Page 6: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 6

Fieldbus in Hazardous Area

The first step

Simplifying

validation

MAX power + FISCO

Re-inventing Intrinsic Safety

Redundant

FISCO

Page 7: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 7

Enhancements in Fieldbus Technology

Ex-i (Entity) Concept

10.6 V @ 70 mA (Ex ia IIC)

Very Less No. of instruments,

very short trunk cable length,

complex proof of intrinsic safety

Ex-i (FISCO) Model

● 12.8 V @ 100 mA (Ex ia IIC)

● Less No. of instruments, short

trunk cable length , simple

proof of intrinsic safety

High Power Trunk Concept

● 28 V @ 500 mA

● Changeover to IS in the field

in acc. with FISCO Model

(physical layer)

Page 8: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 8

Page 9: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 9

FF Wiring Topologies in Hazardous Area

Page 10: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 10

Spurs

Field Instruments

Basic Principles: Typical Topology

Power Supply

Advanced Diagnostic Module

Device Couplers with

Short-circuit protection

Trunk

Surge Protector

Terminator

Host

Page 11: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 11

Spurs

Field Instruments

Basic Principles: Typical Topology

Segment Protectors

Trunk

Surge Protector

Terminator

Plant Asset

Management

Diagnostic Gateway

Page 12: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 12

Spurs

Field Instruments

Basic Principles: Typical Topology

Segment Protectors

Trunk

Surge Protector

Terminator

Plant Asset

Management

Diagnostic Gateway

Page 13: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 13

Why do we need Predictive Intelligence?

Maintenance Cost Reduction Drives End Users

40% of Mfg. Cost is Maintenance

50% of Maintenance is Corrective

10 times More expensive than preventative

maintenance

Preventative Maintenance is Done 25% of Time

5 Times More costly Than Predictive

Maintenance

60% of Preventative Maintenance is

Unnecessary

Lack of Proactive Maintenance strategy

Page 14: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 14

What Does Foundation Fieldbus Enable?

FF is a digital plant architecture that uses the power of Predictive intelligence to

improve plant performance

FF Predictive intelligence helps to detect and correct potential problems before

they can affect Plant Performance

FF Predictive Diagnostics will help users develop a proactive maintenance

strategy

FF Predictive Diagnostics avoid unplanned shutdown and help end-user's reap the

real cost benefit of FOUNDATION technology during the operational phase of

the plant

Goal = Improved operational efficiency

Result = increase plant availability

Page 15: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 15

Strategies to Minimize unplanned shutdowns

Time

Equipment health

100%

Minimum Device Health

FAILURE

Warning Level

Time to respond

Page 16: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 16

Basic Principles: Diagnostic Functions Today

At the power supply

Measure signal level, noise, jitter, earth leakage…

At the operator station

Simple summary alarms

At the maintenance station

Expert system interprets measured data

Produce actionable information in clear text

Increase availability through pro-active handling of fieldbus as

manageable asset

Page 17: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 17

FF Physical Layer Monitoring and Diagnosis

Page 18: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 18

Recommendation for an ideal FF physical layer diagnostic tool

Measurements

Multi-meter Handheld

Tester

Handheld

Communicator

Oscilloscope Note-book

Bus Analyzer

Advanced

Diagnostic

Module

Segment voltage ● ● ● ●

Segment current ◙

Segment noise (low freq.) ● ● ●

Segment noise (high freq.) ●

Segment signal level ● ● ●

Segment signal jitter ●

Instrument signal level =

Instrument signal jitter

Instrument noise (individual)

Fieldbus termination = = ●

Segment earth fault (imbalance)

Device communication ● ●

Communication faults ●

Cable degradation (trending)

Device configuration ● ●

Remote access

Page 19: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 19

Are you protected from EMI?

Ground faults

Fieldbus and power cables tied

together

Page 20: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 20

Did they get it right?

Cable gland not tight

Seal missing

Page 21: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 21

And corrosion as a consequence

Water ingress or worse:

Aggressive media

Page 22: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 22

Will it hold next time?

Wear of surge protectors unknown

Page 23: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 23

Fieldbus Cabinet Too hot? Unauthorized access?

Fan is not working

Door not closed

Water ingress

Page 24: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 24

Is your topology protected?

Page 25: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 25

Diagnostic Device Couplers

Page 26: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 26

Diagnostic Device Couplers

Improved and innovative spur fault protection:

Progressive spur short-circuit protection

Jabber protection – cuts off devices talking too much

Contact bounce protection – suppresses unintentional bounce

Reliable containment of gradual overload conditions

Protects operations from manual intervention and device failure

Page 27: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 27

Jabber protection

Page 28: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 28

Diagnostic Device Couplers

Measures in the field:

Measures fieldbus signal conditions at the spur level

Reports changes all the way to Plant Asset Management

Feeds the expert system

Better advice – better knowledge – focused plant upkeep – fewer trips to the

field

Page 29: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 29

Diagnostic Surge Protector

Page 30: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 30

Diagnostic Surge Protector

Condition-based replacement

Monitors strike severity and count

Reports end of functional reserve to AMS

Instead of repetitive scheduled maintenance

Surely protects you from the next strike

Page 31: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 31

Diagnostic Device Coupler + SPD

Page 32: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 32

Water Ingress Sensor ELS-1

Page 33: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 33

Water Ingress Sensor ELS-1

Monitoring the inside of the enclosure

Placed inside the enclosure of choice

Connects in parallel to the fieldbus segment

Sends alarm all the way to plant asset management

Know what the housing looks like on the inside

Page 34: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 34

Take Control of your Control Cabinet

Page 35: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 35

Take Control of your Control Cabínet

Diagnostic Gateway

With FF-H1 integration and Ethernet

Discrete, frequency, temperature and humidity inputs

Solid state high-power outputs

The cabinet becomes a supremely managed asset

Page 36: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 36

With Diagnostics of Physical Layer We Can….

SEE what's going on in your physical layer

KNOW when and how to act

ACT in your Asset Management tool

Commission Segments

Monitor Segments Online

Predictive Fault finding of Segments

SEE KNOW ACT

Page 37: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 37

Asset Management Integration

One Plant Asset Management

Includes fieldbus now as asset

Customary look and feel

Reduces required training

Reduces potential for errors

Open Architecture Integration:

AMS Suite

PRM

FieldCare

FieldMate

PACTware

OPC Interface

Automatic

Setup

Included

Experion PKS Station

Page 38: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 38

Fieldbus in Hazardous Area

The first step

Simplifying

validation

MAX power + FISCO

Re-inventing Intrinsic Safety

Redundant

FISCO

Page 39: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 39

General Purpose Area

Zone 2 To DCS

Zone 1

DART: Intrinsically safe High-Power Trunk

Redundant, three-port isolated

DART Power Supply

DART Segment Protectors

The intrinsically safe High-Power Trunk

protected by DART®

Intrinsically safe spurs

Ex ib IIC

Page 40: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 40

Zone 1

DART: Intrinsically safe High-Power Trunk

More cable distance (compared to FISCO)

Higher device count (compared to FISCO)

Same installation throughout

Hot work on supplies, couplers, devices

For any fieldbus device:

Ex ib IIC

Page 41: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 41

Comparison of Various Concepts

Page 42: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 42

Summary

Fieldbus technology reduces effort in every phase of a project

Fieldbus is established as reliable technology

Advanced Diagnostic Tools bring transparency and simplicity

HPT and DART concept depending on power requirement

Various devices to provide maintenance information

Fieldbus itself is now an Asset in plant management

Page 43: Advancements in Physical layer with FF - Fieldbus · 2013-02-08 · © 1994 – 2011 Fieldbus Foundation 4 Main components of physical layer FF - Power Supply, Cables, Surge Protector,

© 1994 – 2011 Fieldbus Foundation 43

Questions?

Thanks [email protected]