Fault Level Calculations

Page 2: Fault Level Calculations

Fault Level Calculations 2

What is ahead?

• Overview of transmission network.

• What is mean by fault level

• PU Concept

• Network Modeling

• Fault Level Calculation

• Example

Page 3: Fault Level Calculations

Fault Level Calculations 3

Step-1Overview of power system

grid and transmission network

Page 4: Fault Level Calculations

Fault Level Calculations 4

Typical State Level Power System & our area of interest

Page 5: Fault Level Calculations

Fault Level Calculations 5

Typical State Level Power System & our area of interest

Page 6: Fault Level Calculations

Fault Level Calculations 6

400kV

220kV

220kV

132kV

33kV

33kV220kV

132kV

11kV33kV

S/S - A

S/S - F S/S - E

S/S - B

S/S - C

S/S - D

Local Network – or – Sub-Transmission System

Page 7: Fault Level Calculations

Fault Level Calculations 7

Step-2What is mean by fault level

Page 8: Fault Level Calculations

Fault Level Calculations 8

What is fault level

ABC Transmission Co. Ltd.

3 Ph Fault Levels For 2010-2011

14530 MVA

18290 MVA

9700 MVA

8400 MVA

11300 MVA

4630 MVA

5800 MVA

6400 MVA

7200 MVA

2700 MVA

1185 MVA

3670 MVA

9730 MVA

S/S - B

S/S - A

S/S - C

14530 MVA

8400 MVA

9730 MVA

S/S - B

Page 9: Fault Level Calculations

Fault Level Calculations 9

What is fault level-Continued….

14530 MVA

9730 MVA

S/S - B

2200 MVA 2200 MVA 2300 MVA

2450 MVA 2450 MVA

1465 MVA1465 MVA

8700 MVA

1030 MVA

Page 10: Fault Level Calculations

Fault Level Calculations 10

Step-3Understanding Per-Unit

Measurements

Page 11: Fault Level Calculations

Fault Level Calculations 11

PU Concept

• PU impedance values are calculated by

– For Transformers

• %Impedance = Ohmic Value * ( Base MVA / Name Plate MVA )

– For Lines

• %Impedance = Ohmic Value * ( Base MVA / BasekV2 )

Page 12: Fault Level Calculations

Fault Level Calculations 12

PU Concept

• PU impedance values are calculated by

– For Transformers

• %Impedance = Ohmic Value * ( Base MVA / Name Plate MVA )

– For Lines

• %Impedance = Ohmic Value * ( Base MVA / BasekV2 )

Page 13: Fault Level Calculations

Fault Level Calculations 13

PU Concept

400/220 kV

15% 315 MVA

12 Ohm

Sec DSec CSec B

0.4 ohm/Km 200 Km

0.4 ohm/Km 50 Km220/132 kV

14% 200 MVA

132/33 kV

9.33% 25 MVA

0.4 ohm/Km 30 Km

Sec A

Base MVA = 200 MVA

400kV 33kV132kV220kV

T1 L1 T2 L2 T3 L3

Page 14: Fault Level Calculations

Fault Level Calculations 14

PU Concept

400/220 kV

15% 315 MVA

L3T3L2T2L1T1

0.4 ohm/Km 200 Km

0.4 ohm/Km 50 Km220/132 kV

14% 200 MVA

132/33 kV

9.33% 25 MVA

0.4 ohm/Km 30 Km

Page 15: Fault Level Calculations

Fault Level Calculations 15

Short Circuit Current

• 3 Phase Short Circuit MVA at fault point

Base MVA x 100 = ----------------------------------------------------

Percentage Impedance (from source to fault point)

Page 16: Fault Level Calculations

Fault Level Calculations 16

PU Concept-Continued

9.52% 33.05% 14% 22.96% 74.64% 220%

XT1 XL1 XL2 XL3XT2 XT3

Page 17: Fault Level Calculations

Fault Level Calculations 17

PU Concept

400/220 kV

15% 315 MVA

12 Ohm

65 Ohm20 Ohm34 Ohm80 Ohm75 Ohm

0.4 ohm/Km 200 Km

0.4 ohm/Km 50 Km220/132 kV

14% 200 MVA

132/33 kV

9.33% 25 MVA

0.4 ohm/Km 30 Km

Page 18: Fault Level Calculations

Fault Level Calculations 18

Step-4Finding Source Impedance

Page 19: Fault Level Calculations

Fault Level Calculations 19

Typical State Level Power System & our area of interest

4630

Base MVA=Xs(pu)

MVA

100 Xs(pu)4630

Xs (pu) = 0.0216

Or

Xs% = 2.16%

Page 20: Fault Level Calculations

Fault Level Calculations 20

Solved Example

2850 MVA

8 Km

0.4 Ohms / Km

5 Km

0.4 Ohms / Km

50 MVA 10.21%

50 MVA 10.88 %

25 MVA 9.73 %

25 MVA 10.04 %

50 MVA 10.21%

50 MVA 10.88 %

25 MVA 9.73 %

25 MVA 10.04 %

50 MVA 10.03%

25 MVA 10.52 %

25 MVA 10.21 %

25 MVA 9.84 %

220/132kV Padegaon

132/33-11 kV Harsool

132/33-11 kV Chikalthana

132kV 33kV

11kV

132kV 33kV

11kV

Page 21: Fault Level Calculations

Fault Level Calculations 21

Solved Example

2850 MVA

668 MVA

2257 MVA

220/132kV Padegaon

132/33-11 kV Harsool

132/33-11 kV Chikalthana

132kV 33kV

11kV

132kV 33kV

11kV

1998 MVA

538 MVA

Page 22: Fault Level Calculations

Fault Level Calculations 22

Unsymmetrical Faults-Sequence Network

• Up till now we have discussed 3 Phase faults which are rear. Most of the fault in power system are single line to ground faults.

• To find out the short circuit MVA due to single phase to ground fault it is necessary to use Sequence Network

• Let us have a closer look of sequence network

Page 23: Fault Level Calculations

Fault Level Calculations 23

Unsymmetrical Faults-Sequence Network

M1

M2

T2 L GT1

Xg1XT11XL1XT21

XM21XM11

Xg2XT12XL2XT22

XM22XM12

Xg0XT10XL0XT20

XM20XM10

F

FF

SLD

+Ve Sequence Network

-Ve Sequence NetworkZero Sequence Network

Page 24: Fault Level Calculations

Fault Level Calculations 24

Single Line to Ground Fault-Sequence Network Connections

Xg1XT11XL1XT21

XM21XM11

F

Xg2XT12XL2XT22

XM22XM12

F

Xg0XT10XL0XT20

XM20

F

X1

X2

X0

Ia = 3 / (X1 + X2 + X0)

Page 25: Fault Level Calculations

Fault Level Calculations 25

Single Line to Ground Fault-Solved Example

3Ph 2850 MVA

8 Km

0.4 Ohms / Km

5 Km

0.4 Ohms / Km

50 MVA 10.21%

50 MVA 10.88 %

25 MVA 9.73 %

25 MVA 10.04 %

50 MVA 10.21%

50 MVA 10.88 %

25 MVA 9.73 %

25 MVA 10.04 %

50 MVA 10.03%

25 MVA 10.52 %

25 MVA 10.21 %

25 MVA 9.84 %

220/132kV Padegaon

132/33-11 kV Harsool

132/33-11 kV Chikalthana

132kV 33kV

11kV

132kV 33kV

11kV

1Ph 2230 MVA

Page 26: Fault Level Calculations

Fault Level Calculations 26

Single Line to Ground Fault-Solved Example

3Ph 2850 MVA

3Ph 2850 MVA

1Ph 2230 MVA

3*BaseMVA*100

( XS0 + (XL10 || XL20) )2*( XS1 + (XL11 || XL21) )( )+

1 Ph Short Circuit MVA

at 132kV Harsool Bus

Page 27: Fault Level Calculations

Fault Level Calculations 27

Solved Example220/132kV Padegaon

132/33-11 kV Harsool

132/33-11 kV Chikalthana

132kV 33kV

11kV

132kV 33kV

11kV

1998 MVA

538 MVA

3Ph 2850 MVA

1Ph 2230 MVA

3Ph 2257 MVA

1Ph 1662 MVA

3Ph 668 MVA

1Ph 604 MVA

Page 28: Fault Level Calculations